ELITE ® SERIES GAS FURNACE
UPFL0W / HORIZONTAL AIR DISCHARGE
507333-01
11/2017
Supersedes 05/2016
THIS MANUAL MUST BE LEFT WITH THE
HOMEOWNER FOR FUTURE REFERENCE
This is a safety alert symbol and should never be
ignored. When you see this symbol on labels or in manuals, be alert to the potential for personal injury or death
CAUTION
As with any mechanical equipment, contact with sharp
sheet metal edges can result in personal injury. Take
care while handling this equipment and wear gloves and
protective clothing.
Contents
Unit Dimensions .............................................................2
EL280UH Gas Furnace ..................................................3
Shipping and Packing List ..............................................3
Safety Information ..........................................................3
Use of Furnace as Construction Heater .........................4
General ........................................................................... 4
Combustion, Dilution & Ventilation Air ............................5
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, personal
injury or loss of life. Installation and service must be
performed by a licensed professional HVAC installer or
equivalent, service agency, or the gas supplier.
Gas Piping .................................................................... 21
Repair Parts List ........................................................... 36
Start-Up & Performance Checl List ..............................37
Page 1
Page 2
Unit Dimensions - inches (mm)
AIR FLOW
23
(584)
(19)
3/4
(19)
1
Bottom Return
Air Opening
GAS PIPING INLET
(Either Side)
Side Return
Air Opening
(Either Side)
1
Bottom Return
Air Opening
FLUE OUTLET
(Top)
ELECTRICAL INLET
(Either Side)
SUPPLY AIR
OPENING
FRONT VIEWSIDE VIEW
TOP VIEW
A
B
9/16 (14)
C
D
3/4
27-3/4
(705)
19-7/16
(494)
23-1/2
(597)
1-1/2
(38)
9-1/8 (232) Right
8-5/8 (219) Left
5-3/8 (137) Right
2-3/16 (56) Left
33
(838)
3-1/8 (79)
1-15/16 (49)
14
(356)
9/16
(14)
3 (76) Right
7 (178) Left
2
FLUE OUTLET
(Either Side)
3
OPTIONAL
EXTERNAL
SIDE RETURN
AIR FILTER KIT
(Either Side)
16
(406)
14-3/4
(375)
3
OPTIONAL
EXTERNAL
SIDE RETURN
AIR FILTER KIT
(Either Side)
2
Flue outlet may be horizontal but furnace must be
vented vertically
3
Optional External Side Return Air Filter Kit is not for use
with the optional Return Air Base.
1
NOTE - 60C and 60D size units that require second stage
air volumes over 1800 cfm (850 L/s) must have one
of the following:
1. Single side return air with transition, to accommodate
20 x 25 x 1 in. (508 x 635 x 25 mm) cleanable air
filter. Required to maintain proper air velocity.
2. Single side return air with optional Return Air Base
3. Bottom return air.
4. Return air from both sides.
5. Bottom and
one side return air.
See Blower Performance Ta bles for additional information.
3-1/4 (83)
5/8
(16)
1
3-1/4
(83)
23-3/4
(603)
25
(635)
1-1/2 (38)
Front Panel
EL280UH Model
070P24A
070(X)P36A
090P36A
090(X)P48B
110P48C
110(X)P60C
14-1/236813-3/8340133304-3/4121
17-1/244616-3/8416164066-1/4159
ABCD
inmminmminmminmm
2153319-7/850419-1/24958203
135P60D24-1/262223-3/8546235849-3/4248
Page 2
Page 3
EL280UH Gas Furnace
The EL280UH unit is shipped ready for installation in the
upow or horizontal right position (for horizontal left position the combustion air pressure switch must be moved).
The furnace is shipped with the bottom panel in place.
The bottom panel must be removed if the unit is to be in-
stalled in a horizontal application. The panel may also be
removed in upow applications.
Shipping and Packing List
Package 1 of 1 contains
1 - Assembled EL280UH unit
1 - Bag assembly containing the following:
1 - Owner’s manual and warranty card
The following items may be ordered separately:
1 - Thermostat
1 - Suspension kit (for horizontal installations)
1 - Propane/LP changeover kit
1 - Return air base
1 - High altitude kit
1 - Side lter kit
Check equipment for shipping damage. If you nd any
damage, immediately contact the last carrier.
Safety Information
DANGER
Danger of explosion.
There are circumstances in which odorant used with LP/
propane gas can lose its scent. In case of a leak, LP/
propane gas will settle close to the oor and may be
difcult to smell. An LP/propane leak detector should be
installed in all LP applications.
WARNING
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, personal
injury or loss of life. Installation and service must be
performed by a licensed professional installer (or
equivalent), service agency or the gas supplier.
CAUTION
As with any mechanical equipment, contact with sharp
sheet metal edges can result in personal injury. Take
care while handling this equipment and wear gloves and
protective clothing.
Certications
EL280UH units are CSA International certied to ANSI
Z21.47.
In the USA, installation of gas furnaces must conform with
local building codes. In the absence of local codes, units
must be installed according to the current National Fuel
Gas Code (ANSI-Z223.1). The National Fuel Gas Code is
available from the following address:
American National Standards Institute, Inc.
11 West 42nd Street
New York, NY 10036
Clearances
Adequate clearance must be made around the air openings into the vestibule area. In order to ensure proper unit
operation, combustion and ventilation air supply must
be provided according to the current National Fuel Gas
Code. Vent installations must be consistent with the venting tables (in this instruction) and applicable provisions of
local building codes.
This furnace is CSA International certied for installation
clearances to combustible material as listed on the unit
nameplate and in the tables in gures 7 and 11. Accessibility and service clearances must take precedence over
re protection clearances.
NOTE - For installation on combustible oors, the furnace
shall not be installed directly on carpeting, tile, or other
combustible material other than wood ooring.
Installed Locations
For installation in a residential garage, the furnace must
be installed so that the burner(s) and the ignition source
are located no less than 18 inches (457 mm) above the
oor. The furnace must be located or protected to avoid
physical damage by vehicles. When a furnace is installed
in a public garage, hangar, or other building that has a
hazardous atmosphere, the furnace must be installed according to recommended good practice requirements and
current National Fuel Gas Code.
Temperature Rise
NOTE - Furnace must be adjusted to obtain a temperature rise within the range specied on the unit nameplate.
Failure to do so may cause erratic limit operation and may
result in premature heat exchanger failure.
This EL280UH furnace must be installed so that its electrical components are protected from water.
Page 3
Page 4
Installed in Combination with a Cooling Coil
When this furnace is used with cooling units, it shall be installed in parallel with, or on the upstream side of, cooling
units to avoid condensation in the heating compartment.
See gure 1. With a parallel ow arrangement, a damper
(or other means to control the ow of air) must adequately
prevent chilled air from entering the furnace. If the damper
is manually operated, it must be equipped to prevent operation of either the heating or the cooling unit, unless it is
in the full HEAT or COOL setting. See gure 1.
Heating Unit Installed Parallell to Air Handler Unit
Dampers
(open during heating operation only)
Gas Unit
Air Handler Unit
Dampers
(open during cooling operation only)
Use of Furnace as Construction Heater
Lennox does not recommend the use of EL280UH units
as a construction heater during any phase of construction. Very low return air temperatures, harmful vapors and
operation of the unit with clogged or misplaced lters will
damage the unit.
EL280UH units may be used for heating of buildings or
structures under construction, if the following conditions
are met:
• The vent system must be permanently installed per
these installation instructions.
• A room thermostat must control the furnace. The
use of xed jumpers that will provide continuous
heating is not allowed.
• The return air duct must be provided and sealed
to the furnace.
• Return air temperature range between 60°F (16°C)
and 80°F (27°C) must be maintained.
• Air lters must be installed in the system and must
be maintained during construction.
Heating Unit Installed Upstream of Cooling Unit
Gas Unit
Evaporator
FIGURE 1
When installed, this furnace must be electrically grounded
according to local codes. In addition, in the United States,
installation must conform with the current National Electric Code, ANSI/NFPA No. 70. The National Electric Code
(ANSI/NFPA No. 70) is available from the following address:
National Fire Protection Association
1 Battery March Park
Quincy, MA 02269
NOTE - This furnace is designed for a minimum continuous return air temperature of 60°F (16°C) or an intermittent
operation down to 55°F (13°C) dry bulb for cases where a
night setback thermostat is used. Return air temperature
must not exceed 85°F (29°C) dry bulb.
The EL280UH furnace may be installed in alcoves, closets, attics, basements, garages, crawl spaces and utility
rooms in the upow or horizontal position.
This furnace design has not been CSA International
certied for installation in mobile homes, recreational
vehicles, or outdoors.
• Air lters must be replaced upon construction com-
pletion.
• The input rate and temperature rise must be set
per the furnace rating plate.
• One hundred percent (100%) outdoor air must be
provided for combustion air requirements during
construction. Temporary ducting may supply outdoor air to the furnace. Do not connect duct direct-
ly to the furnace. Size the temporary duct following
these instructions in section for Combustion, Dilu-
tion and Ventilation Air in a conned space with air
from outside.
• The furnace heat exchanger, components, duct
system, air lters and evaporator coils must be
thoroughly cleaned following nal construction
clean-up.
• All furnace operating conditions (including ignition,
input rate, temperature rise and venting) must be
veried according to these installation instructions.
General
These instructions are intended as a general guide and
do not supersede local codes in any way. Consult authorities having jurisdiction before installation.
In addition to the requirements outlined previously, the
following general recommendations must be considered
when installing a EL280UH furnace
• Place the furnace as close to the center of the air
distribution system as possible. The furnace should
also be located close to the chimney or vent termination point.
Page 4
Page 5
• Do not install the furnace where drafts might blow
directly into it. This could cause improper combustion and unsafe operation.
• Do not block the furnace combustion air openings
with clothing, boxes, doors, etc. Air is needed for
proper combustion and safe unit operation.
• When the furnace is installed in an attic or other
insulated space, keep insulation away from the furnace.
• Please consult the manufacturer of your evaporator
coil for their recommendations on distance required
between the heat exchanger and their drain pan.
Adequate space must be provided between the
drain pan and the furnace heat exchanger.
NOTE - The Commonwealth of Massachusetts stipulates these additional requirements:
• Gas furnaces shall be installed by a licensed
plumber or tter only.
• The gas cock must be “T handle” type.
• When a furnace is installed in an attic, the pas-
sageway to and service area surrounding the
equipment shall be oored.
WARNING
This product contains a chemical known to the State
of California to cause cancer, birth defects, or other
reproductive harm.
Combustion, Dilution & Ventilation Air
In the past, there was no problem in bringing in sufcient
outdoor air for combustion. Inltration provided all the air
that was needed. In today’s homes, tight construction
practices make it necessary to bring in air from outside for
combustion. Take into account that exhaust fans, appli-
ance vents, chimneys, and replaces force additional air
that could be used for combustion out of the house. Unless outside air is brought into the house for combustion,
negative pressure (outside pressure is greater than inside
pressure) will build to the point that a downdraft can occur in the furnace vent pipe or chimney. As a result, combustion gases enter the living space creating a potentially
dangerous situation.
In the absence of local codes concerning air for combustion and ventilation, use the guidelines and procedures in
this section to install EL280UH furnaces to ensure efcient and safe operation. You must consider combustion
air needs and requirements for exhaust vents and gas
piping. A portion of this information has been reprinted
with permission from the National Fuel Gas Code (ANSI-Z223.1). This reprinted material is not the complete
and ofcial position of the ANSI on the referenced subject,
which is represented only by the standard in its entirety.
CAUTION
Insufcient combustion air can cause headaches,
nausea, dizziness or asphyxiation. It will also cause
excess water in the heat exchanger resulting in rusting
and premature heat exchanger failure. Excessive
exposure to contaminated combustion air will result
in safety and performance related problems. Avoid
exposure to the following substances in the combustion
air supply:
Permanent wave solutions
Chlorinated waxes and cleaners
Chlorine base swimming pool chemicals
Water softening chemicals
De-icing salts or chemicals
Carbon tetrachloride
Halogen type refrigerants
Cleaning solvents (such as perchloroethylene)
Printing inks, paint removers, varnishes, etc.
Hydrochloric acid
Cements and glues
Antistatic fabric softeners for clothes dryers
Masonry acid washing materials
All gas-red appliances require air for the combustion
process. If sufcient combustion air is not available, the
furnace or other appliances will operate inefciently and
unsafely. Enough air must be provided to meet the needs
of all fuel-burning appliances and appliances such as exhaust fans which force air out of the house. When replaces, exhaust fans, or clothes dryers are used at the
same time as the furnace, much more air is necessary
to ensure proper combustion and to prevent a downdraft.
Insufcient air causes incomplete combustion which can
result in carbon monoxide.
In addition to providing combustion air, fresh outdoor air
dilutes contaminants in the indoor air. These contaminants
may include bleaches, adhesives, detergents, solvents
and other contaminants which can corrode furnace components.
The requirements for providing air for combustion and
ventilation depend largely on whether the furnace is in-
stalled in an unconned or a conned space.
Unconned Space
An unconned space is an area such as a basement or
large equipment room with a volume greater than 50 cubic
feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of the combined input rating of all appliances installed in that space.
This space also includes adjacent rooms which are not
separated by a door. Though an area may appear to be
un conned, it might be necessary to bring in outdoor air
for combustion if the structure does not provide enough air
by inltration. If the furnace is located in a building of tight
construction with weather stripping and caulking around
the windows and doors, follow the procedures in the air
from outside section.
Page 5
Page 6
Conned Space
Air from Inside
A conned space is an area with a volume less than 50
cubic feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of
the combined input rating of all appliances installed in that
space. This denition includes furnace closets or small
equipment rooms.
When the furnace is installed so that supply ducts carry
air circulated by the furnace to areas outside the space
containing the furnace, the return air must be handled by
ducts which are sealed to the furnace casing and which
terminate outside the space containing the furnace. This
is especially important when the furnace is mounted on
a platform in a conned space such as a closet or small
equipment room.
Even a small leak around the base of the unit at the plat-
form or at the return air duct connection can cause a potentially dangerous negative pressure condition. Air for
combustion and ventilation can be brought into the con-
ned space either from inside the building or from outside
.
EQUIPMENT IN CONFINED
CHIMNEY
OR GAS
VENT
FURNACE
AIR FLOW
NOTE - Each opening shall have a free area of at least one square
inch (645 mm
ing of all equipment in the enclosure, but not less than 100 square
inches (64516 mm
2
2
).
SPACE ALL AIR FROM INSIDE
WATER
HEATER
OPENINGS
(To Adjacent
Room)
If the conned space that houses the furnace adjoins a
space categorized as unconned, air can be brought in by
providing two permanent openings between the two spaces. Each opening must have a minimum free area of 1
square inch (645 mm2) per 1,000 Btu (.29 kW) per hour of
total input rating of all gas-red equipment in the conned
space. Each opening must be at least 100 square inches
(64516 mm2). One opening shall be within 12 inches (305
mm) of the top of the enclosure and one opening within 12
inches (305 mm) of the bottom. See gure 2.
Air from Outside
If air from outside is brought in for combustion and ventilation, the conned space must have two permanent openings. One opening shall be within 12 inches (305 mm) of
the top of the enclosure and one opening within 12 inches
(305 mm) of the bottom. These openings must communicate directly or by ducts with the outdoors or spaces (crawl
or attic) that freely communicate with the outdoors or indirectly through vertical ducts. Each opening shall have a
minimum free area of 1 square inch (645 mm2) per 4,000
Btu (1.17 kW) per hour of total input rating of all equipment
in the enclosure. See gures 3 and 4. When communicating with the outdoors through horizontal ducts, each
opening shall have a minimum free area of 1 square inch
(645 mm2) per 2,000 Btu (.56 kW) per total input rating of
all equipment in the enclosure. See gure 5.
When ducts are used, they shall be of the same cross-sectional area as the free area of the openings to which they
connect. The minimum dimension of rectangular air ducts
shall be no less than 3 inches (75 mm). In calculating free
area, the blocking effect of louvers, grilles, or screens
must be considered. If the design and free area of protec-
tive covering is not known for calculating the size opening
required, it may be assumed that wood louvers will have
20 to 25 percent free area and metal louvers and grilles
will have 60 to 75 percent free area. Louvers and grilles
must be xed in the open position or interlocked with the
equipment so that they are opened automatically during
equipment operation.
FIGURE 2
Page 6
Page 7
CHIMNEY OR
EQUIPMENT IN
CONFINED SPACE
ALL AIR FROM
OUTSIDE
OUTLET AIR
INLET AIR
WATER
HEATER
CHIMNEY
OR GAS
VENT
NOTE - Each air duct opening shall have a free area of at least
one square inch (645 mm
2
) per 2,000 Btu (.59 kW) per hour of
the total input rating of all equipment in the enclosure. If the
equipment room is located against an outside wall and the air
openings
ing shall have a free area of at least one square inch (645 mm
2
)
per 4,000 Btu (1.17 kW) per hour of the total input rating of all
other equipment in the enclosure.
FURNACE
AIR FLOW
GAS VENT
FURNACE
(Inlet Air from Crawlspace and Outlet Air to Ventilated Attic)
VENTILATION LOUVERS
(Each end of attic)
EQUIPMENT IN CONFINED SPACE
ALL AIR FROM OUTSIDE
OUTLET
AIR
WATER
HEATER
CHIMNEY
OR GAS
VENT
FURNACE
VENTILATION
LOUVERS
(For unheated crawl space)
AIR FLOW
NOTE-The inlet and outlet air openings shall each have a free area of at least one square inch (645
2
mm
) per 4,000 Btu (1.17 kW) per hour of the total input rating of all equipment in the enclosure.
INLET
AIR
FIGURE 3
EQUIPMENT IN CONFINED SPACE
ALL AIR FROM OUTSIDE
(All Air Through Ventilated Attic)
VENTILATION LOUVERS
(Each end of attic)
OUTLET
AIR
INLET AIR
(Ends 12 in.
above bottom)
WATER
HEATER
AIR FLOW
NOTE-The inlet and outlet air openings shall each have a
free area of at least one square inch (645 mm
ment in the enclosure.
FIGURE 4
2
) per 4,000
FIGURE 5
Page 7
Page 8
Setting Equipment
WARNING
Do not install the furnace on its front or its back. Do not
connect the return air ducts to the back of the furnace.
Doing so will adversely affect the operation of the safety
control devices, which could result in personal injury or
death.
The EL280UH gas furnace can be installed as shipped in
either the upow position or the horizontal position. Select a location that allows for the required clearances that
are listed on the unit nameplate. Also consider gas supply
connections, electrical supply, vent connection, and installation and service clearances [24 inches (610 mm) at unit
front]. The unit must be level.
NOTE - Units with 1/3HP and 1/2HP blower motors are
equipped with three exible legs and one shipping leg. See
gure 6. In some units with 1/3HP blower motor, the shipping leg is exible with rubber mounting grommets similar
to the other three mounting legs and require no modication. The rest of the units with 1/3HP and 1/2HP blower
motors (these blower motor housings will be tagged) have
a rigid shipping leg equipped with a shipping bolt and at
white plastic washer. The bolt and washer must be re-moved before the furnace is placed into operation. After the bolt and washer have been removed, the rigid leg
will not touch the blower housing.
Blower motor with three exible legs and one
rigid shipping leg. Blower motor housings
will be tagged for shipping bolt removal
RIGID LEG
(Remove shipping bolt
and washer)
Upow Applications
Allow for clearances to combustible materials as indicated
on the unit nameplate. Minimum clearances for closet or
alcove installations are shown in gure 7.
Upflow Application Installation Clearances
Top
Left Side
AIR FLOW
Bottom
Type of Vent
Connector
Top1 in. (25 mm)1 in. (25 mm)
*Front2-1/4 in. (57 mm)**2-1/4 in. (57 mm)
Back00
Sides0†0
Vent6 in. (152 mm)1 in. (25 mm)
Floor0‡0‡
*Front clearance in alcove installation must be 24 in. (610 mm).
Maintain a minimum of 24 in. (610 mm) for front service access.
** 3-1/4 in. if single wall vent pipe is used.
‡For installation on a combustible floor, do not install the furnace
directly on carpeting, tile or other combustible materials other
than wood flooring.
†Left side requires 3 inches if a single wall vent is used on 14-1/2
inch
nets.
Type CType B1
Right Side
FIGURE 6
FIGURE 7
Page 8
Page 9
Return Air -- Upow Applications
Return air can be brought in through the bottom or either
side of the furnace installed in an upow application. If the
furnace is installed on a platform with bottom return, make
an airtight seal between the bottom of the furnace and the
platform to ensure that the furnace operates properly and
safely. The furnace is equipped with a removable bottom
panel to facilitate installation.
Markings are provided on both sides of the furnace cabinet for installations that require side return air. Cut the
furnace cabinet at the maximum dimensions shown on
page 2.
NOTE - 60C and 60D units that require air volumes
over 1800 cfm (850 L/s) must have one of the following:
1 - Single side return air with transition to accommodate
20 x 25 x 1 in. (508 x 635 x 25 mm) cleanable air
lter. (Required to maintain proper air velocity.) See
gure 8.
2 - 2 - Single side return air with optional return
airbase. See gure 9.
3 - 3 - Bottom return air.
4 - 4 - Return air from both sides.
5 - 5 - Bottom and one side return air.
Refer to Engineering Handbook for additional information.
Single Side Return Air
(with transition and filter)
20” X 25” X 1”
(508mm X635mm X 25mm)
Cleanable Filter
Return Air
Plenum
AIR FLOW
Transition
FIGURE 8
Optional Return Air Base
(Upflow Applications Only -- For use with A, B, C and D cabinets)
FURNACE
FRONT
IF BASE
IS USED
WITHOUT
INDOOR AIR
AIR FLOW
14−1/2” (368) A Width (65W75)
17−1/2” (446) B Width (50W98)
21”− (533) C Width (50W99)
24−1/2”− (622) D Width (51W00)
NOTE- Optional Side Return Air Filter Kits are not for use with Optional Return Air Base.
1
Both the unit return air opening and the base return air opening must be covered by a single plenum or IAQ cabinet.
Minimum unit side return air opening dimensions for units requiring 1800 cfm or more of air (W x H): 23 x 11 in. (584 x 279 mm).
The opening can be cut as needed to accommodate plenum or IAQ cabinet while maintaining dimensions shown.
Side return air openings must be cut in the field. There are cutting guides stenciled on the cabinet for the side return air
opening. The size of the opening must not extend beyond the markings on the furnace cabinet.
2
To minimize pressure drop, the largest opening height possible (up to 14 inches) is preferred.
OPTIONAL
RETURN AIR BASE
IAQ CABINET,
A SINGLE
RETURN AIR
PLENUM
MUST
COVER BOTH
UNIT AND
RETURN
AIR BASE
OPENINGS
3−1/4
(83)
7−1/4
(184)
1
23 (584)
Overall
(Maximum)
1
Unit side return air
Opening
5−5/8
(143)
SIDE RETURN
AIR OPENINGS
(Either Side)
26−7/8
(683)
SIDE VIEW
23
(584)
1
Minimum
11 (279)
2
Maximum
14 (356)
1
22−7/16
(570)
Overall
(Maximum)
3/4
(19)
FIGURE 9
Page 9
Page 10
Removing the Bottom Panel
Removing the Bottom Panel
Hori
zontal Application
Horizontal Applications
Remove the two screws that secure the bottom cap to the
furnace. Pivot the bottom cap down to release the bottom
panel. Once the bottom panel has been removed, reinstall
the bottom cap. See gure 10.
Screw
Bottom Cap
The EL280UH furnace can be installed in horizontal applications. Order horizontal suspension kit (51W10) from
Lennox, or use equivalent suspension method. Allow for
clearances to combustible materials as indicated on the
unit nameplate. Minimum clearances for closet or alcove
installations are shown in gure 11.
This furnace may be installed in either an attic or a crawlspace. Either suspend the furnace from roof rafters or
oor joists, as shown in gure 12, or install the furnace on
a platform, as shown in gure 13.
Typical Horizontal Application
Unit Suspended in Attic or Crawlspace
Bracket
Metal Strap
Bottom Cap
3/16 inch
Air Flow
Bottom Panel
FIGURE 10
Installation Clearances
Left
End
Vent Connector
Type
Top00
*Front2-1/4 in. (57 mm)**2-14 in. (57 mm)
Back00
Ends2 in. (51 mm)2 in. (51 mm)
Vent6 in. (152 mm)1 in. (25 mm)
Floor0‡0‡
*Front clearance in alcove installation must be 24 in. (610 mm).
Maintain a minimum of 24 in. (610 mm) for front service access.
** 3-1/4 in. if single wall vent pipe is used.
‡For installations on a combustible floor, do not install the furnace
directly on carpeting, tile or other combustible materials other
than wood flooring.
Top
Right
AIR FLOW
End
Bottom
Type CType B1
FIGURE 12
NOTE - Heavy-gauge perforated sheet metal straps may
be used to suspend the unit from roof rafters or ceiling
oists. When straps are used to suspend the unit in this
way, support must be provided for both the ends. The
straps must not interfere with the plenum or exhaust piping installation. Cooling coils and supply and return air
plenums must be supported separately.
NOTE - When the furnace is installed on a platform in a
crawlspace, it must be elevated enough to avoid water
damage and to allow the evaporator coil to drain
. Return Air -- Horizontal Applications
Return air must be brought in through the end of a fur-
nace installed in a horizontal application. The furnace is
equipped with a removable bottom panel to facilitate in-
stallation. See gure 10.
CAUTION
If this unit is being installed in a space serviced by an
exhaust fan, power exhaust fan, or other device which
may create a negative pressure in the space, take care
when sizing the inlet air opening. The inlet air opening
must be sized to accommodate the maximum volume
of exhausted air as well as the maximum volume of
combustion air required for all gas appliances serviced
by this space.
FIGURE 11
Page 10
Page 11
Horizontal Application
Unit Installed on Platform
Line contact is permissible
See the unit nameplate for
clearances.
GAS
ENTRY
SERVICE PLATFORM
VENT
PIPE
FIGURE 13
WARNING
Improper installation of the furnace can result in personal
injury or death. Combustion and ue products must
never be allowed to enter the return air system or the
living space. Use screws and joint tape to seal the return
air system to the furnace.
In platform installations with bottom return air, the furnace
should be sealed airtight to the return air plenum. A
door must never be used as a portion of the return air
duct system. The base must provide a stable support
and an airtight seal to the furnace. Allow absolutely no
sagging, cracks, gaps, etc. The return and supply air
duct systems must never be connected to or from other
heating devices such as a replace or stove, etc. Fire,
explosion, carbon monoxide poisoning, personal injury
and/or property damage could result.
WARNING
The blower access panel must be securely in place when
the blower and burners are operating. Gas fumes, which
could contain carbon monoxide, can be drawn into living
space resulting in personal injury or death.
Filters
This unit is not equipped with a lter or rack. A eld-provided high-velocity lter is required for the unit to operate
properly. Table 1 lists recommended lter sizes.
A lter must be in place any time the unit is operating.
IMPORTANT
If a highefciency lter is being installed as part of this
system to ensure better indoor air quality, the lter must
be properly sized. Highefciency lters have a higher
static pressure drop than standardefciency glass/foam
lters. If the pressure drop is too great, system capacity
and performance may be reduced. The pressure drop
may also cause the limit to trip more frequently during
the winter and the indoor coil to freeze in the summer,
resulting in an increase in the number of service calls.
Before using any lter with this system, check the
specications provided by the lter manufacturer against
the data given in the appropriate Lennox Product
Specications bulletin. Additional information is provided
in Service and Application Note ACC002 (August 2000).
TABLE 1
Furnace Cabinet
Width
14-1/2”16 X 25 X 1 (1)14 X 25 X 1 (1)
17-1/2”16 X 25 X 1 (1)16 X 25 X 1 (1)
21”16 X 25 X 1 (1)20 X 25 X 1 (1)
24-1/2”16 X 25 X 1 (2)24 X 25 X 1 (1)
Side ReturnBottom Return
Filter Size
Page 11
Page 12
Duct
Use industry-approved standards (such as those published by Air Conditioning Contractors of America or American Society of Heating, Refrigerating and Air Condition-
ing Engineers) to size and install the supply and return
air duct system. This will result in a quiet and low-static
system that has uniform air distribution.
NOTE - Do not operate the furnace in the heating mode
with an external static pressure that exceeds 0.5 inches
w.c. Higher external static pressures may cause erratic
limit operation.
Supply Air Plenum
If the furnace is installed without a cooling coil, a removable access panel must be installed in the supply air duct.
The access panel should be large enough to permit in-
spection (either by smoke or reected light) of the heat
exchanger for leaks after the furnace is installed. The
furnace access panel must always be in place when the
furnace is operating and it must not allow leaks into the
supply air duct system.
Return Air Plenum
NOTE - Return air must not be drawn from a roomwhere
this furnace, or any other gas-fueled appliance (i.e., water
heater), or carbon monoxide producing device (i.e., wood
replace) is installed.
When return air is drawn from a room, a negative pressure
is created in the room. If a gas appliance is operating in
a room with negative pressure, the ue products can be
pulled back down the vent pipe and into the room. This
reverse ow of the ue gas may result in incomplete combustion and the formation of carbon monoxide gas. This
toxic gas might then be distributed throughout the house
by the furnace duct system.
In upow applications, the return air can be brought in
through the bottom or either side of the furnace. If a furnace with bottom return air is installed on a platform, make
an airtight seal between the bottom of the furnace and
the platform to ensure that the unit operates properly and
safely. Use berglass sealing strips, caulking, or equivalent sealing method between the plenum and the furnace
cabinet to ensure a tight seal. If a lter is installed, size the
return air duct to t the lter frame.
Page 12
Page 13
Venting
UPFLOW POSITION
A 4-inch diameter ue transition is factory-installed on
the combustion air inducer outlet of all models. Figure 15
shows the combustion air inducer as shipped from the factory.
Mounting Screws Location
Mounting Screws
FIGURE 14
UPFLOW POSITION
Top Vent Discharge
Vent Pipe
Flue
Transition
Pressure
Switch
Make -Up
Box
Collector Box
If necessary reposition the combustion air inducer, pressure switch and or make up box as needed per the follow-
ing steps and see gures 16 through 21.
1 - Remove the four mounting screws which secure the
combustion air inducer / pressure switch assembly
to the orice plate. See gure 14. Lift and rotate
the assembly 90 degrees clockwise or counter
clockwise to either the 3 o’clock position or to 9
o’clock position and re-secure with four screws.
Gasket should be left in place.
2 - 2 - Use tin snips to cut preferred opening
on the cabinet for repositioning the ue
outlet. Use the cut out piece
Left Side Vent Discharge
xoB rotcelloCetalP revoC
Pressure
Switch
Vent Pipe
Flue
Transition
Gas supply piping must be brought into the unit from the right
side in order to accommodate the flue pipe.
Remove make-up box assembly (2 screws) and cut wire tie to
free make-up box wires. Re-install make-up box on other side
of cabinet.
Re-secure make-up box wires, either pulling excess wires
through the blower compartment and securing with supplied
wire tie, or coil excess wire and secure to the gas manifold.
Make-Up
Box
AIR
FLOW
FLOW
AIR
FIGURE 15
IMPORTANT
The unit will not vent properly with the ue transition
pointed down in the 6 o’clock position. The combustion
air inducer may be rotated clockwise or counterclockwise
by 90° to allow for top or side vent discharge in all
applications. When the unit is installed, the ue transition
must be in the 9 o’clock, 12 o’clock or 3 o’clock position.
FIGURE 16
UPFLOW POSITION
Right Side Vent Discharge
Cover Plate
Pressure
Switch
Collector
Box
Make-Up
Box
FLOW
AIR
Pressure switch tubing may be too long. Cut to
fit , then re-attach to barbed fitting on pressure
switch. Tubing must not be allowed to sag.
Flue Transition
FIGURE 17
Vent Pipe
Page 13
Page 14
HORIZONTAL LEFT POSITION
tie or coil excess wire and secure to the gas manifold.
HORIZONTAL LEFT POSITION
wire tie, or coil excess wire and secure to the gas manifold.
HORIZONTAL RIGHT POSITION
wire tie, or coil excess wire and secure to the gas manifold.
Top Vent Discharge
Vent Pipe
Pressure Switch
Vent Pipe
Flue Transition
Top Vent Discharge
Pressure Switch
Flue
Transition
FLOW
Cover Plate
Make-Up Box
Disconnect
sure switch assembly. Remove pressure switch assembly (1
screw) and cut wire tie to free pressure switch wires. Re-install
pressure switch on the other side of orifice plate and re-connect
pressure switch hose.
Re-secure pressure switch wires by either pulling excess wires
through the blower compartment and securing with supplied wire
Collector Box
FIGURE 18
Side Vent Discharge
Pressure Switch
AIR
Cover Plate
AIR
FLOW
Collector Box
Make-Up Box
Gas supply piping must be brought into the unit from the bottom
in order to accommodate the flue pipe.
Remove make-up box assembly (2 screws) and cut wire tie to
free make-up box wires. Re-install make-up box on other side
of cabinet.
Re-secure make-up box wires by either pulling excess wires
through the blower compartment and securing with supplied
FIGURE 20
HORIZONTAL RIGHT POSITION
Side Vent Discharge
Pressure Switch
AIR
Flue Transition
Make-Up Box
Disconnect pressure switch hose from barbed fitting on the
pressure switch assembly. Remove pressure switch assembly
(1 screw) and cut wire tie to free pressure switch wires. Reinstall pressure switch on the other side of orifice plate and reconnect pressure switch hose.
Re-secure pressure switch wires by either pulling excess wires
through the blower compartment and securing with supplied
Collector Box
FLOW
AIR
FLOW
Flue
Transition
Collector Box
make up box
FIGURE 21
FIGURE 19
Page 14
Page 15
The EL280UH series units are classied as fan-assisted
Category I furnaces when vertically vented according to
the latest edition of National Fuel Gas Code (NFPA 54 /
ANSI Z223.1) in the USA. A fan-assisted Category I furnace is an appliance equipped with an integral mechanical means to either draw or force combustion products
through the combustion chamber and/or heat exchang-
er. The EL280UH is not approved for use with horizontal
venting.
NOTE - Use these instructions as a guide. They do not
supersede local codes. This furnace must be vented according to all local codes these installation instructions,
and the provided venting tables in these instructions
The venting tables in this manual were extracted from the
National Fuel Gas Code (NFPA 54 / ANSI Z223.1) and are
provided as a guide for proper vent installation. Proper
application, termination, construction and location of vents
must conform to local codes having jurisdiction. In the ab-
sence of local codes, the NFGC serves as the dening
document.
Refer to the tables and the venting information contained
in these instructions to properly size and install the venting
system.
Use self-drilling sheet metal screws or a mechanical fas-
tener to rmly secure the vent pipe to the round collar of
the ue transition. If self-drilling screws are used to attach
the vent pipe, it is recommended that three be used. Drive
one self-drilling screw through the front and one through
each side of the vent pipe and collar. See gure 22.
Install the rst vent connector elbow at a minimum of six
inches (152 mm) from the furnace vent outlet. See gure
22.
Venting Using a Masonry Chimney
The following additional requirements apply when a lined
masonry chimney is used to vent this furnace.Masonry
chimneys used to vent Category I central furnaces must
be either tile-lined or lined with a listed metal lining system or dedicated gas vent. Unlined masonry chimneys are
prohibited. See gures 23 and 24 for common venting.
A chimney with one or more sides exposed to the outside
of the structure is considered to be an exterior chimney.
An exterior masonry chimney that is not tile-lined must be
lined with B1 vent or a listed insulated exible metal vent.
An exterior tile-lined chimney that is sealed and capped
may be lined with a listed uninsulated exible metal vent.
If the existing chimney will not accommodate a listed metal liner, either the chimney must be rebuilt to accommodate one of these liners or an alternate approved venting
method must be found.
Insulation for the exible vent pipe must be an encapsulated berglass sleeve recommende
IMPORTANT
Once the venting system is installed, attach the
“Disconnected Vent” warning sticker to a visible area
of the plenum near the vent pipe. See gure 22. The
warning sticker is provided in the bag assembly. Order
kit 66W04 for additional stickers..
WARNING
Asphyxiation hazard. The exhaust vent for this furnace
must be securely connected to the furnace uetransition
at all times.
VENT CONNECTION UPFLOW AND HORIZONTAL POSITION
“DISCONNECTED VENT”
WARNING
VENT PIPE
(min. 6” length)
FLUE TRANSITION
COLLAR
STICKER
“DISCONNECTED VENT”
FIGURE 22
Page 15
WARNING
STICKER
VENT PIPE
(min. 6” length)
FLUE
TRANSITION
COLLAR
Page 16
Common Venting Using Metal-Lined Masonry Chimney
4 in. (102 mm)
minimum
MIN. LENGTH -- AS
SHORT AS PRACTICAL
MAX. LENGTH
-- SEE NOTE 1
BELOW.
SEALED
PERMANENTLY
SEALED FIREPLACE
OPENING
EXTERIOR
CHIMNEY WITH
METAL
LINER
VENT CONNECTOR
NOTE 1 - Refer to the provided venting tables for installations. Refer
to the capacity requirements shown in the provided venting tables.
OTHER
APPLIANCE
FURNACE
5 ft. (1.5 m)
minimum
AIR FLOW
FIGURE 23
DO NOT insulate the space between the liner and
the chimney wall with puffed mica or any other loose
granular insulating material.
IMPORTANT
SINGLE appliance venting of a fan-assisted furnace into
a tile-lined masonry chimney (interior or outside wall)
is PROHIBITED. The chimney must rst be lined with
either type B1 vent or an insulated single wall exible
vent lining system which has been sized according to the
provided venting tables and the vent pipe manufacturer’s
instructions.
A fan-assisted furnace may be commonly vented into an
existing lined masonry chimney if the following conditions
are met:
• The chimney is currently serving at least one drafthoodequipped appliance;
• The vent connectors and chimney are sized accord-
ing to the provided venting tables.
If type B1 double-wall vent is used inside a chimney, no
otherappliance can be vented into the chimney. The out-
er wallof type B1 vent pipe must not be exposed to ue
products.
A type B1 vent or masonry chimney liner shall terminate
above the roof surface with a listed cap or a listed roof assembly according to the terms of their respective listings
and the vent manufacturer’s instructions.
When inspection reveals that an existing chimney is not
safe for the intended purpose, it shall be rebuilt to conform
to nationally recognized standards, lined or relined with
suitable materials, or replaced with a gas vent or chimney
suitable for venting EL280UH series units. The chimney
passageway must be checked periodically to ensure that
it is clear and free of obstructions.
Do not install a manual damper, barometric draft regulator,
or ue restrictor between the furnace and the chimney.
Never connect a Category I appliance to a chimney that is
servicing a solid-fuel appliance. If a replace chimney ue
is used to vent this appliance, the replace opening must
be permanently sealed.
A type B or listed chimney lining system that passes
through an unused masonry chimney ue is not considered to be exposed to the outdoors.
General Venting Requirements
Vent all EL280UH furnaces according to these instructions:
1 - Vent diameter recommendations and maximum
allowable piping runs are found in the provided
venting tables.
2 - In no case should the vent or vent connector
diameter be less than the diameter specied in the
provided venting tables.
3 - The minimum vent capacity determined by the sizing
tables must be less than the low re input rating and
the maximum vent capacity must be greater than
the high re input rating.
4 - Single appliance vents - If the vertical vent or tile-
lined chimney has a larger diameter or ow area
than the vent connector, use the vertical vent
diameter to determine the minimum vent capacity
and the vent connector diameter to determine
the maximum vent capacity. The ow area of the
vertical vent, however, shall not exceed 7 times
the ow area of the listed appliance categorized
vent area, drafthood outlet area or ue collar area
unless designed according to approved engineering
methods.
5 - Multiple appliance vents - The ow area of the
largest section of vertical vent or chimney shall
not exceed 7 times the smallest listed appliance
categorized vent area, drafthood outlet area or ue
collar area unless designed
Page 16
Page 17
Common Venting Using Tile-Lined Interior Masonry Chimney and Combined Vent Connector
MINIMUM LENGTH = AS SHORT AS PRACTICAL.
FOR MAXIMUM LENGTH SEE NOTE TO LEFT
NOTE- Refer to provided venting tables
for installations.
OTHER
APPLIANCE
AIR FLOW
FIGURE 24
6 - The entire length of single wall metal vent connector
shall be readily accessible for inspection, cleaning,
and replacement.
7 - Single appliance venting congurations with
zero lateral lengths (table 3) is assumed to have
no elbows in the vent system. For all other vent
congurations, the vent system is assumed to have
two 90° elbows. For each additional 90° elbow or
equivalent (for example two 45° elbows equal one
90° elbow) beyond two, the maximum capacity
listed in the venting table should be reduced by 10%
(0.90 x maximum listed capacity).
8 - The common venting tables (4 and 5) were generated
using a maximum horizontal vent connector length
of 1-1/2 feet (.46 m) for
TABLE 2
Connector Diameter inches (mm)
3 (76)4-1/2 (1.37)
4 (102)6 (1.83)
5 (127)7-1/2 (2.29)
6 (152)10-1/2 (3.20)
7 (178)10-1/2 (3.20)
Maximum Horizontal Connector
Length feet (m)
9 - If the common vertical vent is offset, the maximum
common vent capacity listed in the common venting
tables should be reduced by 20%, the equivalent
of two 90° elbows (0.80 x maximum common vent
capacity).The horizontal length of the offset shall
not exceed1-1/2 feet (.46 m) for each inch (25 mm)
of common vent diameter.
CONNECTOR
FURNACE
INTERIOR TILE-LINED
MASONRY CHIMNEY
NOTE - the chimney must be properly
sized per provided venting tables or
lined with listed metal lining system.
VENT
PERMANENTLY
SEALED FIREPLACE
OPENING
10 - The vent pipe should be as short as possible with
the least number of elbows and angles required to
complete the job. Route the vent connector to the
vent using the shortest possible route.
11 - A vent connector shall be supported without any
dips or sags and shall slope a minimum of 1/4 inch
(6.4 mm) per linear foot (305 mm) of connector,
back toward the appliance.
12 - Vent connectors shall be rmly attached to the
furnace ue collar by self-drilling screws or other
approved means, except vent connectors of listed
type B vent material which shall be assembled
according to the manufacturer’s instructions. Joints
between sections of single wall connector piping
shall be fastened by screws or other approved
means.
13 - When the vent connector used for Category I
appliances must be located in or pass through a
crawlspace, attic or other areas which may be cold,
that portion of the vent connector shall be constructed
of listed double-wall type B vent material or material
having equivalent insulation qualities.
14 - All venting pipe passing through oors, walls, and
ceilings must be installed with the listed clearance
to combustible materials and be re stopped
according to local codes. In absence of local codes,
refer to NFGC (Z223.1).
15 - No portion of the venting system can extend into,
or pass through any circulation air duct or plenum.
Page 17
Page 18
16 - Vent connectors serving Category I appliances shall
not be connected to any portion of mechanical draft
systems operating under positive pressure such as
Category III or IV venting systems.
17 - If vent connectors are combined prior to entering
the common vent, the maximum common vent
capacity listed in the common venting tables must
be reduced by 10%, the equivalent of one 90° elbow
(0.90 x maximum common vent capacity).
18 - The common vent diameter must always be at least
20 - Do not install a manual damper, barometric draft
regulator or ue restrictor between the furnace and
the chimney.
21 - When connecting this appliance to an existing
dedicated or common venting system, you must
inspect the venting system’s general condition
and look for signs of corrosion. The existing vent
pipe size must conform to these instructions and
the provided venting tables. If the existing venting
system does
as large as the largest vent connector diameter.
19 - In no case, shall the vent connector be sized more
than two consecutive table size diameters over the
size of the draft hood outlet or ue collar outlet.
TABLE 3
Capacity of Type B Double-Wall Vents with Type B Double-Wall Connectors
Serving a Single Category I Appliance
Height
H
(feet)
6
8
10
15
20
30
NOTE - Single appliance venting congurations with zero lateral lengths are assumed to have no elbows in the vent system. For
all other vent congurations, the vent system is assumed to have two 90° elbows. For each additional 90° elbow or equivalent (for
example two 45° elbows equal one 90° elbow) beyond two, the maximum capacity listed in the venting table should be reduced by
10 percent (0.90 x maximum listed capacity).
Appliance Input Rating in Thousands of Btu Per Hour
Page 19
Page 20
Removal of the Furnace from Common Vent
In the event that an existing furnace is removed from a
venting system commonly run with separate gas appliances, the venting system is likely to be too large to properly
vent the remaining attached appliances.
Conduct the following test while each appliance is operating and the other appliances (which are not operating)
remain connected to the common venting system. If the
venting system has been installed improperly, you must
correct the system as indicated in the general venting requirements section.
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each
appliance connected to the venting system being placed
into operation could result in carbon monoxide poisoning
or death.
The following steps shall be followed for each appliance
connected to the venting system being placed into
operation, while all other appliances connected to the
venting system are not in operation:
1 - Seal any unused openings in the common venting
system.
2 - Inspect the venting system for proper size and
horizontal pitch. Determine that there is no blockage,
restriction, leakage, corrosion, or other deciencies
which could cause an unsafe condition.
3 - Close all building doors and windows and all
doors between the space in which the appliances
remaining connected to the common venting system
are located and other spaces of the building. Turn
on clothes dryers and any appliances not connected
to the common venting system. Turn on any exhaust
fans, such as range hoods and bathroom exhausts,
so they will operate at maximum speed. Do not
operate a summer exhaust fan. Close replace
dampers.
4 - Follow the lighting instructions. Turn on the appliance
that is being inspected. Adjust the thermostat so
that the appliance operates continuously.
5 - After the burner have operated for 5 minutes, test for
leaks of ue gases at the draft hood relief opening.
Use the ame of a match or candle.
6 - After determining that each appliance connected
to the common venting system is venting properly,
(step 3) return all doors, widows, exhaust fans,
replace dampers, and any other gas-burning
appliances to their previous mode of operation.
7 - If a venting problem is found during any of the
preceding tests, the common venting system must
be modied to correct the problem.
Resize the common venting system to the minimum
vent pipe size determined by using the appropriate
tables in Appendix G. (These are in the current standards of the National Fuel Gas Code ANSI Z223.1.
Page 20
Page 21
Gas Piping
Gas supply piping should not allow more than 0.5”W.C.
drop in pressure between gas meter and unit. Supply gas
pipe must not be smaller than unit gas connection
CAUTION
If a exible gas connector is required or allowed by the
authority that has jurisdiction, black iron pipe shall be
installed at the gas valve and extend outside the furnace
cabinet. The exible connector can then be added
between the black iron pipe and the gas supply line.
Gas Supply
WARNING
Do not over torque (800 in-lbs) or under torque (350 inlbs) when attaching the gas piping to the gas valve.
1 - This unit is shipped standard for left or right side
installation of gas piping (or top entry in horizontal
applications). Connect the gas supply piping into
the gas valve. The maximum torque is 800 in lbs
and minimum torque is 350 in lbs when attaching
the gas piping to the gas valve.
2 - When connecting the gas supply piping, consider
factors such as length of run, number of ttings, and
furnace rating to avoid excessive pressure drop.
Table 6 lists recommended pipe sizes for typical
applications.
3 - The gas piping must not run in or through air ducts,
clothes chutes, gas vents or chimneys, dumb
waiters, or elevator shafts.
4 - The piping should be sloped 1/4 inch (6.4 mm) per
15 feet (4.57 m) upward toward the meter from the
furnace. The piping must be supported at proper
intervals [every 8 to 10 feet (2.44 to 3.01 m)] with
suitable hangers or straps. Install a drip leg in
vertical pipe runs to the unit.
5 - A 1/8” N.P.T. plugged tap or pressure post is located
on the gas valve to facilitate test gauge connection.
See gure 31.
6 - In some localities, codes may require the installation
of a manual main shut-off valve and union (furnished
by the installer) external to the unit. The union must
be of the ground joint type.
IMPORTANT
Compounds used on threaded joints of gas piping must
be resistant to the actions of liquied petroleum gases.
NOTE - If emergency shutoff is necessary, shut off the
main manual gas valve and disconnect main power to the
furnace. The installer should properly label these devices.
TABLE 6
Gas Pipe Capacity - ft3/hr (m3/hr)
Nominal
Iron Pipe
Size Inches
(mm)
1/2
(12.7)
3/4
(19.05)
1
(25.4)
1-1/4
(31.75)
1-1/2
(38.1)
2
(50.8)
2-1/2
(63.5)
3
(76.2)
Internal
Diameter
inches
(mm)
.622
(17.799)
.824
(20.930)
1.049
(26.645)
1.380
(35.052)
1.610
(40.894)
2.067
(52.502)
2.469
(67.713)
3.068
(77.927)
10
(3.048)
172
(4.87)
360
(10.19)
678
(19.19)
1350
(38.22)
2090
(59.18)
4020
(113.83)
6400
(181.22)
11300
(319.98)
20
(6.096)
118
(3.34)
247
(7.000)
466
(13.19)
957
(27.09)
1430
(40.49)
2760
(78.15)
4400
(124.59)
7780
(220.30)
30
(9,144)
95
(2.69)
199
(5.63)
374
(10.59)
768
(22.25)
1150
(32.56)
2220
(62.86)
3530
(99.95)
6250
(176.98)
40
(12,192)
81
(2.29)
170
(4.81)
320
(9.06)
657
(18.60)
985
(27.89)
1900
(53.80)
3020
(85.51)
5350
(151.49)
Length of Pipe - feet (m)
50
(15.240)
72
(2.03)
151
(4.23)
284
(8.04)
583
(16.50)
873
(24.72)
1680
(47.57)
2680
(75.88)
4740
(134.22)
60
(18.288)
65
(1.84)
137
(3.87)
257
(7.27)
528
(14.95)
791
(22.39)
1520
(43.04)
2480
(70.22)
4290
(121.47)
70
(21.336)
60
(1.69)
126
(3.56)
237
(6.71)
486
(13.76)
728
(20.61)
1400
(39.64)
2230
(63.14)
3950
(111.85)
80
(24.384)
56
(1.58)
117
(3.31)
220
(6.23)
452
(12.79)
677
(19.17)
1300
(36.81)
2080
(58.89)
3670
(103.92)
NOTE - Capacity given in cubic feet (m3 ) of gas per hour and based on 0.60 specic gravity gas.
90
(27.432)
52
(1.47)
110
(3.11)
207
(5.86)
424
(12.00)
635
(17.98)
1220
(34.55)
1950
(55.22)
3450
(97.69)
100
(30,480)
50
(1.42)
104
(2.94)
195
(5.52)
400
(11.33)
600
(17.00)
1160
(32.844)
1840
(52.10)
3260
(92.31)
Page 21
Page 22
MANUAL
MAIN SHUT-OFF
VALV E
(With 1/8 in. NPT
Plugged Ta p Shown)
GROUND
JOINT
UNION
Left Side Piping
(Standard)
AUTOMATIC
GAS VALV E
AUTOMATIC
GAS VALV E
MANUAL
MAIN SHUT-OFF
VALV E
(With 1/8 in. NPT
Plugged Ta p
Shown)
GROUND
JOINT
UNION
DRIP LEG
MANUAL
MAIN SHUT-OFF
VALV E
GROUND
JOINT
UNION
DRIP LEG
DRIP LEG
FIELD
PROVIDED
AND INSTALLED
NOTE - BLACK IRON PIPE ONLY TO BE ROUTED INSIDE OF CABINET
FIGURE 25
Horizontal Applications
Possible Gas Piping Configurations
MANUAL
MAIN SHUT-OFF
VALV E
GROUND
JOINT
UNION
DRIP LEG
Right Side Piping
(Alternate)
Horizontal Application
Left-Side Air Discharge
Horizontal Application
Right-Side Air Discharge
FIELD
PROVIDED
AND
INSTALLED
NOTE - BLACK IRON PIPE ONLY TO BE ROUTED INSIDE OF CABINET
FIGURE 26
Page 22
MANUAL
MAIN SHUT-OFF
VALV E
GROUND
JOINT
UNION
DRIP LEG
Page 23
Leak Check
MANUAL MAIN
SHUT-OFF VALV E
WILL NOT HOLD
NORMAL TEST
PRESSURE
CAP
ISOLATE
GAS VALV E
FURNACE
1/8 NPT PLUG
After gas piping is completed, carefully check all piping
connections (factory- and eld-installed) for gas leaks.
Use a leak detecting solution or other preferred means.
NOTE - If emergency shutoff is necessary, shut off the
main manual gas valve and disconnect the main power
to the furnace. The installer should properly label these
devices.
CAUTION
Some soaps used for leak detection are corrosive to
certain metals. Carefully rinse piping thoroughly after
leak test has been completed. Do not use matches,
candles, ame or other sources of ignition to check for
gas leaks.
The furnace must be isolated by closing its individual manual shut-off valve and disconnecting from from the gas
supply system the during any pressure testing of the gas
supply system at pressures greater than 1/2 psig (3.48
kPa, 14 inches w.c.).
WARNING
Fire Hazard. Use of aluminum wire with this product may
result in a re, causing property damage, severe injury
or death. Use copper wire only with this product.
CAUTION
Failure to use properly sized wiring and circuit breaker
may result in property damage. Size wiring and circuit
breaker(s) per Product Specications bulletin (EHB) and
unit rating plate.
The unit is equipped with a eld make-up box on the left
hand side of the cabinet. The make-up box may be moved
to the right side of the furnace to facilitate installation. If
the make-up box is moved to the right side, clip the wire
ties that bundle the wires together. The excess wire must
be pulled into the blower compartment. Secure the excess
wire to the existing harness to protect it from damage.
INTERIOR MAKE-UP BOX INSTALLATION
When testing pressure of gas lines, gas valve must be
disconnected and isolated. See gure 27. Gas valves
can be damaged if subjected to pressures greater than
1/2 psig (3.48 kPa, 14 inches w.c.).
Electrical
IMPORTANT
FIGURE 27
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
CAUTION
Electrostatic discharge can affect electronic
components. Take precautions to neutralize
electrostatic charge by touching your hand
and tools to metal prior to handling the
control.
WARNING
Electric Shock Hazard. Can cause injury or
death. Unit must be properly grounded in
accordance with national and local codes.
Right Side
BOX
FIGURE 28
Refer to gure 29 for schematic wiring diagram and troubleshooting and table 7 and gure 29 for eld wiring.
The power supply wiring must meet Class I restrictions.
Protected by either a fuse or circuit breaker, select circuit
protection and wire size according to unit nameplate.
NOTE - Unit nameplate states maximum current draw.
Maximum over-current protection allowed is 15 AMP.
Holes are on both sides of the furnace cabinet to facilitate
wiring.
Install a separate (properly sized) disconnect switch near
the furnace so that power can be turned off for servicing.
Before connecting the thermostat, check to make sure
the wires will be long enough for servicing at a later date.
Make sure that thermostat wire is long enough to facilitate
future removal of blower for service.
Page 23
Page 24
Complete the wiring connections to the equipment. Use
the provided unit wiring diagram and the eld wiring diagramshown in gure 29. Use 18-gauge wire or larger that
is suitable for Class II rating for thermostat connections.
Electrically ground the unit according to local codes or, in
the absence of local codes, according to the current National Electric Code (ANSI/NFPA No. 70). A green ground
wire is provided in the eld make-up box.
NOTE - The EL280UH furnace contains electronic components that are polarity sensitive. Make sure that the furnace is wired correctly and is properly grounded.
Accessory Terminals
One line voltage “EAC” 1/4” spade terminal is provided on
the furnace integrated control. See gure 30 for integrated
control conguration. This terminal is energized when the
indoor blower is operating. Any accessory rated up to one
amp can be connected to this terminal with the neutral leg
of the circuit being connected to one of the provided neutral terminals. If an accessory rated at greater than one
amp is connected to this terminal, it is necessary to use
an external relay.
One line voltage “HUM” 1/4” spade terminal is provided on
the furnace integrated control. See gure 30 for integrated
control conguration. This terminal is energized in the
heating mode when the combustion air inducer is operat-
ing. Any humidier rated up to one amp can be connected
to this terminal with the neutral leg of the circuit being connected to one of the provided neutral terminals.If a hu-
midier rated at greater than one amp is connected to this
terminal, it is necessary to use an external relay relay.
Generator Use - Voltage Requirements
The following requirements must be kept in mind when
specifying a generator for use with this equipment:
• The furnace requires 120 volts + 10% (Range: 108
volts to 132 volts).
• The furnace operates at 60 Hz + 5% (Range: 57 Hz
to 63 Hz).
• The furnace integrated control requires both polarity and proper ground. Both polarity and proper
grounding should be checked before attempting to
operate the furnace on either permanent or temporary power.
• Generator should have a wave form distortion of
less than 5% total harmonic distortion (THD).
Thermostat
Install the room thermostat according to the instructions
provided with the thermostat. See table 7 for thermostat
designations. If the furnace is being matched with a heat
pump, refer to the FM21 installation instruction or appropriate dual fuel thermostat instructions.
Indoor Blower Speeds
1 - When the thermostat is set to “FAN ON,” the indoor
blower will run continuously on the low speed when
there is no cooling or heating demand.
2 - When the EL280UH is operating in the high-re or
lowre heating mode, the indoor blower will run on
the corresponding heating speed.
3 - When the EL280UH is operating in the low cool or
the high cool cooling mode, the indoor blower will
run on the corresponding cooling speed.
Page 24
Page 25
Thermostat
TABLE 7
Field Wiring Applicatuions
DIP Switch Settings and On-Board Links (See figure 30)
W915
DIP Switch 1
Two-Stage
Cooling
W951
Heat Pumps
Wiring Connections
1 Heat / 1 Cool
NOTE - Use DIP
ond-stage heat ON
delay.
OFF10 minutes.
ON-15 minutes.
1 Heat / 2 Cool
NOTE - Use DIP
ond-stage heat ON
delay.
OFF-10 minutes.
ON-15 minutes.
ONIntactIntact
ONCutIntact
S1
T'STAT
S1
T'STAT
CONTROL
TERM. STRIP
CONTROL
TERM. STRIP
OUTDOOR
UNIT
OUTDOOR
UNIT
Page 25
Page 26
Thermostat
TABLE 7
Field Wiring Applicatuions
DIP Switch Settings and On-Board Links (See figure 30)
W915
DIP Switch 1
Two-Stage
Cooling
W951
Heat Pumps
Wiring Connections
2 Heat / 2 CoolOFFCutIntact
2 Heat / 1 CoolOFFIntactIntact
S1
T'STAT
S1
T'STAT
CONTROL
TERM. STRIP
CONTROL
TERM. STRIP
OUTDOOR
UNIT
OUTDOOR
UNIT
Page 26
Page 27
EL280UH Schematic Wiring Diagram
FIGURE 29
Page 27
Page 28
DIAGNOSTIC
LEDs
DIP
SWITCHES
TWO-STAGE INTEGRATED CONTROL
1/4” QUICK CONNECT TERMINALS
SENSE = 120 VAC OUTPUT TO FLAME SENSOR
NEUTRALS= 120 VAC NEUTRAL
PARK = DEAD TERMINAL FOR UNUSED BLOWER LEAD
HEAT LOW = 120 VA C OUTPUT TO CIRC BLWR -- LOW HT SPEED
1 -- 2 Stage T'statSelects t/stat type (single or two-stage)
2 -- 2nd Stage DelaySecond stage ON delay (single-stage t'stat)
3 & 4 -- Heat Off DelayHeating fan OFF delay
5 -- Cool Off DelayCooling fan OFF delay
HIGH HEAT AND LOW COOL SPEED
DIP SWITCH FUNCTIONS
NOITCNUF)SE(HCTIWS PID
FIGURE 30
Integrated Contol
EL280UH units are equipped with a two-stage integrated
control. This control manages ignition timing and fan off
delays based on selections made using the control DIP
switches. The control includes an internal watchguard
feature which automatically resets the integrated control
when it has been locked out. After one hour of continuous
thermostat demand for heat, the watchguard will break
and remake thermostat demand to the furnace and automatically reset the control to relight the furnace.
DIP Switch Settings
Switch 1 -- Thermostat Selection -- This unit may be
used with either a single-stage or two-stage thermostat.
The thermostat selection is made using a DIP switch
which must be properly positioned for the particular application. The DIP switch is factory-positioned for use with a
twostage thermostat. If a single-stage thermostat is to be
used, the DIP switch must be repositioned.
a. Select “OFF” for two-stage heating operation controlled by a
two-stage heating thermostat (factory setting);
b. Select “ON” for two-stage heating operation controlled by
a single-stage heating thermostat. This setting provides a
timed delay before second-stage heat is initiated.
Switch 2 -- Second Stage Delay (Used with SingleStage Thermostat Only) -- This switch is used to de-
termine the second stage on delay when a single-stage
thermostat is being used. The switch is factory-set in the
OFF position, which provides a 10-minute delay before
secondstage heat is initiated. If the switch is toggled to
the ON position, it will provide a 15-minute delay before
secondstage heat is initiated. This switch is only activated
when the thermostat selector jumper is positioned for SINGLEstage thermostat use.
Switches 3 and 4 -- Heating Blower-Off Delay -- The
heating blower-on delay of 30 seconds is not adjustable.
The heating blower-off delay (time that the blower oper-
ates after the heating demand has been satised) can be
adjusted by moving switches 3 and 4 on the integrated
control. The unit is shipped from the factory with a heating blower-off delay of 90 seconds. The heating blower
off delay affects comfort and is adjustable to satisfy individual applications. Adjust the blower off delay to achieve
a supply air temperature between 90° and 110°F at the
exact moment that the blower is de-energized. Longer
off delay settings provide lower supply air temperatures;
shorter settings provide higher supply air temperatures.
Table 8 provides the blower off timings that will result from
different switch settings.
Page 28
Page 29
TABLE 8
Heating Blower-Off Delay Switch Settings
Blower Off Delay
(Seconds)
60OffOn
90
factory setting
120OnOff
180OnOn
Switch 5 -- Cooling Blower-Off Delay -- The cooling
blower-off delay (time that the blower operates after the
cooling demand has been satised) can be adjusted by
moving switch 5 on the integrated control. The switch is
factory- set in the OFF position, which provides a cooling
blower- off delay of 45 seconds. If the switch is toggled to
the ON position, it will provide a 2-second cooling blower-off delay
On-Board Link W951 Heat Pump (R to O)
On-board link W951 is a clippable connection between
terminals R and O on the integrated control. W951 must
be cut when the furnace is installed in applications which
include a heat pump unit and a thermostat which features
dual fuel use. If the link is left intact, terminal “O” will re-
main energized eliminating the HEAT MODE in the heat
pump.
On-Board Link W915 2 Stage Compr (Y1 to Y2)
On-board link W915 is a clippable connection between
terminals Y1 and Y2 on the integrated control. W915 must
be cut if two-stage cooling will be used. If the link is not cut
the outdoor unit will operate in second-stage cooling only
and the indoor blower will operate on high cool speed only.
Unit Start-Up
FOR YOUR SAFETY READ BEFORE LIGHTING
Switch 3Switch 4
OffOff
WARNING
Do not use this furnace if any part has been underwater.
A ood-damaged furnace is extremely dangerous.
Attempts to use the furnace can result in re or explosion.
Immediately call a qualied service technician to inspect
the furnace and to replace all gas controls, control
system parts, and electrical parts that have been wet or
to replace the furnace, if deemed necessary.
WARNING
If overheating occurs or if gas supply fails to shut off,
shut off the manual gas valve to the appliance before
shutting off electrical supply.
CAUTION
Before attempting to perform any service or maintenance,
turn the electrical power to unit OFF at disconnect switch.
BEFORE LIGHTING smell all around the appliance area
for gas. Be sure to smell next to the oor because some
gas is heavier than air and will settle on the oor.
The gas valve on the EL280UH unit will be equipped with
a gas control switch. Use only your hand to move the
switch. Never use tools. If the switch will not turn or if the
control switch will not move by hand, do not try to repair it.
Placing the furnace into operation:
EL280UH units are equipped with an automatic ignition
system. Do not attempt to manually light burners on these
furnaces. Each time the thermostat calls for heat, the
burners will automatically light. The ignitor does not get
hot when there is
WARNING
If you do not follow these instructions exactly, a re or
explosion may result causing property damage, personal
injury or death.
Gas Valve Operation (Figure 31)
1 - STOP! Read the safety information at the beginning
of this section.
2 - Set the thermostat to the lowest setting.
3 - Turn off all electrical power to the unit.
4 - This furnace is equipped with an ignition device
which automatically lights the burners. Do not try to
light the burners by hand.
5 - Remove the upper access panel.
6 - Move switch on gas valve to OFF. Do not force. See
gure 31.
7 - Wait ve minutes to clear out any gas. If you then
smell gas, STOP! Immediately call your gas supplier
from a neighbor’s phone. Follow the gas supplier’s
instructions. If you do not smell gas go to next step
Page 29
Page 30
WHITE RODGERS GAS VALVE
INLET PRESSURE POST
GAS VALV E SHOWN IN ON POSITION
MANIFOLD
PRESSURE TAP
HIGH FIRE ADJUSTMENT
SCREW
(under cap)
FIGURE 31
8 - Move switch on gas valve to ON. Do not force. See
gure 31.
9 - Replace the upper access panel.
10 - Turn on all electrical power to to the unit.
11 - Set the thermostat to desired setting.
NOTE - When unit is initially started, steps 1 through 11
may need to be repeated to purge air from gas line.
12 - If the appliance will not operate, follow the
instructions “Turning Off Gas to Unit” and call your
service technician or gas supplier.
Turning Off Gas to Unit
1 - Set the thermostat to the lowest setting.
2 - Turn off all electrical power to the unit if service is to
be performed.
3 - Remove the upper access panel.
4 - Move switch on gas valve to OFF. Do not force.
5 - Replace the upper access panel.
Failure To Operate
If the unit fails to operate, check the following:
1 - Is the thermostat calling for heat?
2 - Are access panels securely in place?
3 - Is the main disconnect switch closed?
4 - Is there a blown fuse or tripped circuit breaker?
5 - Is the lter dirty or plugged? Dirty or plugged lters
will cause the limit control to shut the unit off.
6 - Is gas turned on at the meter?
7 - Is the manual main shut-off valve open?
8 - Is the gas valve ON/OFF switch in the ON position?
9 - Is the unit ignition system in lock out? If the unit locks
out again, call the service technician to inspect the
unit for blockages.
10 - Is pressure switch closed? Obstructed ue will
cause unit to shut off at pressure switch. Check ue
and outlet for blockages.
11 - Are ame rollout switches tripped? If ame rollout
switches are tripped, call the service technician for
inspection.
Gas Pressure Adjustment
Gas Flow (Approximate)
TABLE 9
GAS METERING CLOCKING CHART
EL280
Unit
-04580160200400
-07055110136272
-0904182102204
-110336682164
-135275468136
Natural 1000 btu/cu ftLP 2500 btu cu/cu ft
Seconds For One Revolution
1 cu ft dial 2 cu fr dial 1 cu ft Dial 2 cu ft Dial
Furnace should operate at least 5 minutes before checking gas ow. Determine time in seconds for two revolutions of gas through the meter. (Two revolutions assures
a more accurate time.) Divide by two and compare to time
in table 9 below. If manifold pressure matches table 11
and rate is incorrect, check gas orices for proper size and
restriction. Remove temporary gas meter if installed.
NOTE - To obtain accurate reading, shut off all other gas
appliances connected to meter.
Supply Pressure Measurement
An inlet post located on the gas valve provides access
to the supply pressure. See gure 31. Back out the 3/32”
hex screw one turn, connect a piece of 5/16” tubing and
connect to a manometer to measure supply pressure. See
table 11 for supply line pressure.
Manifold Pressure
A manifold pressure post located on the gas valve provides access to the manifold pressure. See gure 31.
Back out the 3/32 hex screw one turn, connect a piece
of 5/16” tubing and connect to a manometer to measure
manifold pressure.
NOTE - Pressure test adapter kit (10L34) is available from
Lennox to facilitate manifold pressure measurement.
1 - Connect test gauge to manifold pressure post
(gure 31) gas valve.
2 - Ignite unit on high re and let run for 5 minutes to
allow for steady state conditions.
3 - After allowing unit to stabilize for 5 minutes, record
manifold pressure and compare to value given in table
11.
4 - If necessary, make adjustments. Figure 31 shows
location of high re adjustment screw.
5 - If an adjustment is made on high re, re-check
manifold pressure on low re. Do not adjust low re
manifold pressure. If low re manifold pressure is
more than 1/2” above or below value specied in
table 11, replace valve.
6 - soon as an accurate reading has been obtained.
Turn the supply and manifold 3/32” hex screw one
revolution back into the gas valve.
7 - Start unit and perform leak check. Seal leaks if
found.
Page 30
Page 31
Proper Combustion
Furnace should operate minimum 15 minutes with correct
manifold pressure and gas ow rate before checking combustion. Table 10 shows acceptable combustion for ALL
EL280UH models. The maximum carbon monoxide
reading should not exceed 100 ppm
High Altitude
The manifold pressure may require adjustment and combustion air pressure switch may need replacing to ensure
proper combustion at higher altitudes. Refer to table 11
for manifold pressure and table 12 for pressure switch
change and gas conversion kits.
This is the only permissible derate for these units.
2
Natural gas high altitude orice kit required.
3
A natural to L.P. propane gas changeover kit is necessary to convert this unit. Refer to the changeover kit installation instruction for the conversion
procedure.
NOTE - Units may be installed at altitudes up to 4500 ft. above sea level without modications.
Natural1.73.51.63.41.73.54.513.0
LP/propane
3
4.910.04.910.04.910.511.013.0
Natuarl1.73.51.53.21.73.54.513.0
LP/propane
3
4.910.04.910.04.910.011.013.0
Natural1.73.51.52.81.73.54.513.0
LP/propane
Natural
LP/propane
3
4.910.04.910.04.910.011.013.0
1.73.51.52.81.73.54.513.0
3
4.910.04.910.04.910.011.013.0
TABLE 12
Pressure Switch and Gas Conversion Kits at all Altitudes
High Altitude Pressure Switch Kit
Unit Input
0-4500 ft4501- 7500 ft7501-10,000 ft7501-10,000 ft0-7500 ft
070
09091W5373W35
11091W5373W35
13573W3373W34
NOTE - A natural to L.P. propane gas changeover kit is necessary to convert this unit. Refer to the changeover kit installation instruction for the conversion procedure.
No Change
91W5373W35
High Altitude
Natural Gas Kit
73W3711K5111K4677W09
LP/Propane Gas Kit
7501 - 10,000
ft
LP/Propane to
Natural Kit
0 -7500 ft
Page 31
Page 32
Other Unit Adjustments
Primary and Secondary Limits
The primary limit is located on the heating compartment
vestibule panel. The secondary limits (if equipped) are located in the blower compartment, attached to the back
side of the blower. These auto reset limits are factory-set
and require no adjustment.
Flame Rollout Switches
Electrical
1 - Check all wiring for loose connections.
2 - Check for the correct voltage at the furnace (furnace
operating). Correct voltage is 120VAC + 10%.
3 - Check amp-draw on the blower motor with inner
blower panel in place.
Unit Nameplate__________Actual__________
Blower Speeds
This manually reset switches are located on the bafe
plate in the burner assembly.
Pressure Switch
The pressure switch is located in the heating compartment
adjacent to the combustion air inducer. The switch checks
for proper combustion air inducer operation before allowing ignition trial. The switch is factory-set and requires no
adjustment.
Temperature Rise
After the furnace has been started, and supply and return
air temperatures have been allowed to stabilize, check the
temperature rise. If necessary, adjust the blower speed
to maintain the temperature rise within the range shown
on the unit nameplate. Increase the blower speed to decrease the temperature. Decrease the blower speed to
increase the temperature rise. Failure to adjust the temperature rise may cause erratic limit operation.
Fan Control
The fan-on time of 30 seconds is not adjustable. The heat
fan-off delay (amount of time that the blower operates af-
ter the heat demand has been satised) may be adjusted
by changing DIP switches 3 and 4. See gure 32 and table
8. The unit is shipped with a factory fan-off delay setting
of 90 seconds. The fan-off delay affects comfort and is
adjustable to satisfy individual applications. Adjust the fanoff delay to achieve a supply air temperature between 90°
and 110°F at the moment that the blower is de-energized.
Longer off delay settings provide lower return air temperatures; shorter settings provide higher return air temperatures.
NOTE - Do not secure the electrical conduit directly to the
air ducts or structure.
HEAT FAN‐OFF TIME IN SECONDS
60sec.
1234512345
90sec.
Follow the steps below to change the blower speeds.
1 - Turn off electrical power to furnace.
2 - Remove blower access panel.
3 - Disconnect existing speed tap at integrated control
speed terminal.
NOTE - Termination of any unused motor leads must be
insulated.
4 - Place unused blower speed tap on integrated
control “PARK” terminal or insulate.
5 - Refer to blower speed selection chart on unit wiring
diagram for desired heating or cooling speed. See
Blower performance data beginning on the next
page.
6 - Connect selected speed tap at integrated control
speed terminal.
7 - Resecure blower access panel.
8 - Turn on electrical power to furnace.
9 - Recheck temperature rise.
Electronic Ignition
The integrated control has an added feature of an internal
Watchguard control. The feature serves as an automatic reset device for integrated control lockout caused by
ignition failure. This type of lockout is usually due to low
gas line pressure. After one hour of continuous thermostat
demand for heat, the Watchguard will break and remake
thermostat demand to the furnace and automatically reset
the integrated control to begin the ignition sequence.
Heating Sequence of Operation
When there is a call for heat, the integrated control runs a
self check. The control checks for S10 primary limit, S21
secondary limit (s) and S47 rollout switch normally closed
contacts. The control also checks for S102 high heat and
S128 low heat prove switch normally open contacts. Once
self check is complete and all safety switches are operational, heat call can continue.
Two-Stage Thermostat, Two Stage Heat. Dip Switch
set at “TWO”.
120sec.
1234512345
To adjust fan-off timing, flip dip switch to desired setting.
180sec.
FIGURE 32
1 - SureLight® control energizes combustion air inducer
B6 on low heat speed. Combustion air inducer runs
until S128 low heat prove switch contacts close
(switch must close within 2 1/2 minutes or control
goes into Watchguard Pressure Switch mode.
High heat prove switch S102 may also close). A 15
second pre-purge follows once S128 closes.
Page 32
Page 33
NOTE - If the low re pressure switch does not close the
combustion air inducer will switch to high re. After a 15
second pre-purge the high re pressure switch will close
and the unit will begin operation on high re. After 10 to
20 seconds of high re operation the unit will switch to low
re.
NOTE - If the furnace is operating on continuous fan mode
(terminal “R” and “G” are energized), the combustion air
inducer will energize on high speed, the gas valve will energize on second-stage heat and the furnace will operate
on high re. Furnace will stay on high re for 60 seconds
then switch to low re.
2 - SureLight control begins 20 second ignitor warm up
period.
3 - Gas valve opens on rst stage for a 4 second trial
for ignition. Ignitor stays energized during the trial or
until ame sensed.
4 - Flame is sensed, gas valve remains on rst stage
heat, ignitor de-energizes.
5 - After 30 second delay, indoor blower B3 is energized
on low heat speed.
The furnace will stay in this mode until rst stage
demand is satised OR a second stage heat
demand is initiated.
6 - Second stage heat demand initiated. A 30 second
second stage recognition period begins.
7 - The combustion air inducer ramps up to high heat
speed.
8 - S102 high heat prove switch closes and the gas
valve energizes second stage heat.
9 - B3 indoor blower switches to high heat speed.
Single-Stage Thermostat, Two Stage Heat. Dip
Switch set at “SINGLE”
1 - SureLight control energizes combustion air inducer
B6 on low heat speed.
Combustion air inducer runs until S128 low heat prove
switch contacts close (switch must close within 2 1/2
minutes or control goes into Watchguard Pressure
Switch mode. High heat prove switch S102 may also
close). A 15 second pre-purge follows once S128 closes.
NOTE - If the low re pressure switch does not close the
combustion air inducer will switch to high re. After a 15
second pre-purge the high re pressure switch will close
and the unit will begin operation on high re. After 10 to
20 seconds of high re operation the unit will switch to low
re.
NOTE - If the furnace is operating on continuous fan mode
(terminal “R” and “G” are energized), the combustion air
inducer will energize on high speed, the gas valve will energize on second-stage heat and the furnace will operate
on high re. Furnace will stay on high re for 60 seconds
then switch to low re.
2 - SureLight control begins 20 second ignitor warm up
period.
3 - Gas valve opens on rst stage for a 4 second trial
for ignition. Ignitor stays energized during the trial or
until ame sensed.
4 - Flame is sensed, gas valve remains on rst stage
heat, ignitor de-energizes.
5 - After 30 second delay, indoor blower B3 is energized
on low heat speed.
6 - A 10 minute (factory set) or 15 minute (eld set)
second stage heat delay period begins.
7 - After the delay the combustion air inducer ramps up
to high heat speed.
8 - S102 high heat prove switch closes and the gas
valve energizes second stage heat.
9 - B3 indoor blower switches to high heat speed.
Page 33
Page 34
Service
WARNING
ELECTRICAL SHOCK, FIRE,
OR EXPLOSION HAZARD.
Failure to follow safety warnings exactly could result in
dangerous operation, serious injury, death or property
damage.
Improper servicing could result in dangerous operation,
serious injury, death, or property damage. Before
servicing, disconnect all electrical power to furnace.
When servicing controls, label all wires prior to
disconnecting. Take care to reconnect wires correctly.
Verify proper operation after servicing.
WARNING
The blower access panel must be securely in place when
the blower and burners are operating. Gas fumes, which
could contain carbon monoxide, can be drawn into living
space resulting in personal injury or death.
Annual Furnace Maintenance
At the beginning of each heating season, and to comply
with the Lennox Limited Warranty, your system should
be checked as follows:
1 - Check wiring for loose connections, voltage at
indoor unit and amperage of indoor motor.
2 - Check the condition of the belt and shaft bearings
if applicable.
3 - Inspect all gas pipe and connections for leaks.
4 - Check the cleanliness of lters and change if
necessary (monthly).
5 - Check the condition and cleanliness of burners and
heat exchanger and clean if necessary.
6 - Check the cleanliness of blower assembly and
clean the housing, blower wheel and blower motor
if necessary
7 - Inspect the combustion air inducer and clean if
necessary.
8 - Evaluate the heat exchanger integrity by inspecting
the heat exchanger per the AHRI heat exchanger
inspection procedure. This procedure can be
viewed at www.ahrinet.org
9 - Ensure sufcient combustion air is available to the
furnace. Fresh air grilles and louvers (on the unit
and in the room where the furnace is installed)
must be properly sized, open and unobstructed to
provide combustion air.
10 - Inspect the furnace venting system to make sure
it is in place, structurally sound, and without holes,
corrosion, or blockage. Vent system must be free
and clear of obstructions and must slope upward
away from the furnace . Vent system should be
installed per the National Fuel Gas Code.
11 - Inspect the furnace return air duct connection to
ensure the duct is sealed to the furnace. Check for
air leaks on supply and return ducts and seal where
necessary.
12 - Check the condition of the furnace cabinet insulation
and repair if necessary.
13 - Perform a complete combustion analysis during the
furnace inspection to ensure proper combustion
and operation. Consult Service Literature for proper
combustion values.
14 - Verify operation of CO detectors and replace
batteries as required.
Perform a general system test. Turn on the furnace to
check operating functions such as the start-up and shutoff operation.
1 - Check the operation of the ignition system, inspect
and clean ame sensor. Check microamps before
and after. Check controls and safety devices (gas
valve, ame sensor, temperature limits). Consult
Service Manual for proper operating range. Thermal
Limits should be checked by restricting airow and
not disconnecting the indoor blower. For additional
details, please see Service and Application Note
H049.
2 - Verify that system total static pressure and airow
settings are within specic operating parameters.
3 - Clock gas meter to ensure that the unit is operating
at the specied ring rate. Check the supply
pressure and the manifold pressure. On two-stage
gas furnaces check the manifold pressure on high
re and low re. If manifold pressure adjustment is
necessary, consult the Service Literature for unit
specic information on adjusting gas pressure.
Not all gas valves are adjustable. Verify correct
temperature rise.
Page 34
Page 35
Cleaning the Burners
NOTE - Use papers or protective covering in front of the
furnace during cleaning.
1 - Turn off both electrical and gas power supplies to
furnace.
2 - Label the wires from gas valve, rollout switches,
primary limit switch and make-up box then
disconnect them.
3 - Disconnect gas supply piping. Remove the screw
securing the burner box cover and remove cover.
Remove the four screws securing the burner
manifold assembly to the vestibule panel and
remove the assembly from the unit.
4 - To clean burners, run a vacuum cleaner with a soft
brush attachment over the face of burners. Visually
inspect inside the burners and crossovers for any
blockage caused by foreign matter. Remove any
blockage. Figure 33 shows burner detail.
5 - Reinstall burner box, manifold assembly and burner
box cover.
6 - Re-install gas supply and turn on electrical pwer to
furnace.
Rollout
Switches
Sensor
Ignitor
BURNER REMOVAL
Retention Rings
Cross Over
Manifold And Gas Valve
FIGURE 33
Page 35
Page 36
Repair Parts List
The following repair parts are available through independent Lennox dealers. When ordering parts, include the complete
furnace model number listed on the CSA International nameplate -- Example: EL280UH045P24A-01. All service must be
performed by a licensed professional HVAC installer (or equivalent), service agency, or gas
supplier.
Cabinet Parts
Main access panel
Blower panel
Top cap
Control Panel Parts
Transformer
Integrated control
Door interlock switch
Circuit breaker
Blower Parts
Blower wheel
Blower housing
Motor
Motor mounting frame
Motor capacitor
Blower housing cutoff plate
Heating Parts
Flame sensor
Heat exchanger assembly
Gas manifold
Combustion air inducer
Gas valve
Main burner cluster
Main burner orices
Pressure switch
Ignitor
Primary limit control
Flame rollout switch (s)
Secondary limit
Page 36
Page 37
Start-Up & Performance Check List
Unit Model Number_______________
UNIT SET UP
(typical)
2
2
1
GAS SUPPLY
1
Natural Gas
Piping Connections Tight
Leak Tested
Serial Number___________________
Line Voltage
5
Gas Supply Pressure
1
LP/Propane Gas
SUPPLY
AIR
upflow furnace shown
3
Filter
RETURN
RETURN
AIR
4
3
DUCT SYSTEM
AIR
SUPPLY AIR DUCT
Sealed
Insulated (if necessary)
Supply Line Pressure “ W.C.________
Registers Open and Unobstructed
RETURN DUCT
VENT / EXHAUST PIPE
2
Secure to Unit
Elbows Secured to Pipe
Roof Flashing (water tight)
Sealed
Filter Installed and Clean
Grilles Unobstructed
INTEGRATED CONTROL
4
Vent Pipe Supported
DIP Switches Set (if applicable)
Appropriate Links in Place (if applicable)
5
VOLTAGE CHECK
Supply Voltage _____
Electrical Connections Tight
Page 37
Page 38
UNIT OPERATION
(typical)
Combustion CO
2
Gas Manifold Pressure
1
Blower Motor Amps
3
7
2
Thermostat
HEATING MODE
GAS MANIFOLD PRESSURE “W.C._____
1
2
COMBUSTION SAMPLE CO
INDOOR BLOWER AMPS______
3
2%______
CO PPM_______
SUPPLY
AIR
6
upflow furnace shown
RETURN
RETURN
AIR
AIR
INDOOR BLOWER AMPS______
3
TEMPERATURE DROP
4
Return Duct Temperature _________
Supply Duct Temperature
Temperatures
4
Filter
Duct Static
5
COOLING MODE
_
_______
Temperature Drop = _________
TEMPERATURE RISE
4
Supply Duct Temperature ________
Return Duct Temperature