Lennox EL280UH070P24A, EL280UH070P36A, EL280UH070XP36A, EL280UH110P48C, EL280UH110XP60C Installation Instructions Manual

...
© 2017 Lennox Industries Inc.
OFF
ON
C
C
HI
I I
LO
HI
UPFLOW
HORIZONTAL LEFT HORIZONTAL RIGHT
AIR FLOW
AIR FLOWAIR FLOW
Dallas, Texas USA
INSTALLATION INSTRUCTIONS EL280UH
ELITE ® SERIES GAS FURNACE UPFL0W / HORIZONTAL AIR DISCHARGE
507333-01 11/2017 Supersedes 05/2016
THIS MANUAL MUST BE LEFT WITH THE
This is a safety alert symbol and should never be ignored. When you see this symbol on labels or in man­uals, be alert to the potential for personal injury or death
CAUTION
As with any mechanical equipment, contact with sharp sheet metal edges can result in personal injury. Take care while handling this equipment and wear gloves and protective clothing.
Contents
Unit Dimensions .............................................................2
EL280UH Gas Furnace ..................................................3
Shipping and Packing List ..............................................3
Safety Information ..........................................................3
Use of Furnace as Construction Heater .........................4
General ........................................................................... 4
Combustion, Dilution & Ventilation Air ............................5
Setting Equipment .........................................................8
Filters ............................................................................ 11
Duct System .................................................................12
Venting..........................................................................13
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a licensed professional HVAC installer or equivalent, service agency, or the gas supplier.
Gas Piping .................................................................... 21
Electrical ....................................................................... 23
Integrated Control ......................................................... 28
Unit Start Up ................................................................. 29
Gas Pressure Adjustment ............................................. 30
Proper Combustion.......................................................31
High Altitude .................................................................31
Other Unit Adjustments................................................. 32
Sequence of Operation.................................................32
Service..........................................................................34
Repair Parts List ........................................................... 36
Start-Up & Performance Checl List ..............................37
Page 1
Unit Dimensions - inches (mm)
AIR FLOW
23
(584)
(19)
3/4
(19)
1
Bottom Return
Air Opening
GAS PIPING INLET
(Either Side)
Side Return Air Opening (Either Side)
1
Bottom Return
Air Opening
FLUE OUTLET
(Top)
ELECTRICAL INLET
(Either Side)
SUPPLY AIR
OPENING
FRONT VIEW SIDE VIEW
TOP VIEW
A
B
9/16 (14)
C
D
3/4
27-3/4
(705)
19-7/16
(494)
23-1/2
(597)
1-1/2
(38)
9-1/8 (232) Right
8-5/8 (219) Left
5-3/8 (137) Right
2-3/16 (56) Left
33
(838)
3-1/8 (79)
1-15/16 (49)
14
(356)
9/16
(14)
3 (76) Right 7 (178) Left
2
FLUE OUTLET
(Either Side)
3
OPTIONAL
EXTERNAL
SIDE RETURN
AIR FILTER KIT
(Either Side)
16
(406)
14-3/4
(375)
3
OPTIONAL
EXTERNAL
SIDE RETURN
AIR FILTER KIT
(Either Side)
2
Flue outlet may be horizontal but furnace must be vented vertically
3
Optional External Side Return Air Filter Kit is not for use with the optional Return Air Base.
1
NOTE - 60C and 60D size units that require second stage air volumes over 1800 cfm (850 L/s) must have one of the following:
1. Single side return air with transition, to accommodate 20 x 25 x 1 in. (508 x 635 x 25 mm) cleanable air filter. Required to maintain proper air velocity.
2. Single side return air with optional Return Air Base
3. Bottom return air.
4. Return air from both sides.
5. Bottom and
one side return air.
See Blower Performance Ta bles for additional information.
3-1/4 (83)
5/8
(16)
1
3-1/4
(83)
23-3/4
(603)
25
(635)
1-1/2 (38)
Front Panel
EL280UH Model
070P24A 070(X)P36A
090P36A 090(X)P48B
110P48C 110(X)P60C
14-1/2 368 13-3/8 340 13 330 4-3/4 121
17-1/2 446 16-3/8 416 16 406 6-1/4 159
A B C D
in mm in mm in mm in mm
21 533 19-7/8 504 19-1/2 495 8 203
135P60D 24-1/2 622 23-3/8 546 23 584 9-3/4 248
Page 2
EL280UH Gas Furnace
The EL280UH unit is shipped ready for installation in the upow or horizontal right position (for horizontal left posi­tion the combustion air pressure switch must be moved). The furnace is shipped with the bottom panel in place. The bottom panel must be removed if the unit is to be in-
stalled in a horizontal application. The panel may also be removed in upow applications.
Shipping and Packing List
Package 1 of 1 contains
1 - Assembled EL280UH unit 1 - Bag assembly containing the following:
2 - Screws 1 - Snap bushing 1 - Snap plug 1 - Wire tie 1 -Vent warning label
1 - Owner’s manual and warranty card The following items may be ordered separately: 1 - Thermostat
1 - Suspension kit (for horizontal installations)
1 - Propane/LP changeover kit 1 - Return air base 1 - High altitude kit
1 - Side lter kit Check equipment for shipping damage. If you nd any
damage, immediately contact the last carrier.
Safety Information
DANGER
Danger of explosion. There are circumstances in which odorant used with LP/
propane gas can lose its scent. In case of a leak, LP/
propane gas will settle close to the oor and may be difcult to smell. An LP/propane leak detector should be
installed in all LP applications.
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a licensed professional installer (or equivalent), service agency or the gas supplier.
CAUTION
As with any mechanical equipment, contact with sharp sheet metal edges can result in personal injury. Take care while handling this equipment and wear gloves and protective clothing.
Certications
EL280UH units are CSA International certied to ANSI
Z21.47. In the USA, installation of gas furnaces must conform with
local building codes. In the absence of local codes, units must be installed according to the current National Fuel Gas Code (ANSI-Z223.1). The National Fuel Gas Code is available from the following address:
American National Standards Institute, Inc. 11 West 42nd Street New York, NY 10036
Clearances
Adequate clearance must be made around the air open­ings into the vestibule area. In order to ensure proper unit operation, combustion and ventilation air supply must be provided according to the current National Fuel Gas Code. Vent installations must be consistent with the vent­ing tables (in this instruction) and applicable provisions of local building codes.
This furnace is CSA International certied for installation
clearances to combustible material as listed on the unit nameplate and in the tables in gures 7 and 11. Accessi­bility and service clearances must take precedence over
re protection clearances.
NOTE - For installation on combustible oors, the furnace shall not be installed directly on carpeting, tile, or other combustible material other than wood ooring.
Installed Locations
For installation in a residential garage, the furnace must be installed so that the burner(s) and the ignition source are located no less than 18 inches (457 mm) above the
oor. The furnace must be located or protected to avoid
physical damage by vehicles. When a furnace is installed in a public garage, hangar, or other building that has a hazardous atmosphere, the furnace must be installed ac­cording to recommended good practice requirements and current National Fuel Gas Code.
Temperature Rise
NOTE - Furnace must be adjusted to obtain a tempera­ture rise within the range specied on the unit nameplate. Failure to do so may cause erratic limit operation and may result in premature heat exchanger failure.
This EL280UH furnace must be installed so that its electri­cal components are protected from water.
Page 3
Installed in Combination with a Cooling Coil
When this furnace is used with cooling units, it shall be in­stalled in parallel with, or on the upstream side of, cooling units to avoid condensation in the heating compartment.
See gure 1. With a parallel ow arrangement, a damper (or other means to control the ow of air) must adequately
prevent chilled air from entering the furnace. If the damper is manually operated, it must be equipped to prevent op­eration of either the heating or the cooling unit, unless it is in the full HEAT or COOL setting. See gure 1.
Heating Unit Installed Parallell to Air Handler Unit
Dampers
(open during heating operation only)
Gas Unit
Air Handler Unit
Dampers
(open during cooling operation only)
Use of Furnace as Construction Heater
Lennox does not recommend the use of EL280UH units as a construction heater during any phase of construc­tion. Very low return air temperatures, harmful vapors and
operation of the unit with clogged or misplaced lters will
damage the unit. EL280UH units may be used for heating of buildings or
structures under construction, if the following conditions are met:
• The vent system must be permanently installed per these installation instructions.
• A room thermostat must control the furnace. The
use of xed jumpers that will provide continuous
heating is not allowed.
• The return air duct must be provided and sealed
to the furnace.
• Return air temperature range between 60°F (16°C)
and 80°F (27°C) must be maintained.
Air lters must be installed in the system and must
be maintained during construction.
Heating Unit Installed Upstream of Cooling Unit
Gas Unit
Evaporator
FIGURE 1
When installed, this furnace must be electrically grounded according to local codes. In addition, in the United States, installation must conform with the current National Elec­tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available from the following ad­dress:
National Fire Protection Association 1 Battery March Park Quincy, MA 02269
NOTE - This furnace is designed for a minimum continu­ous return air temperature of 60°F (16°C) or an intermittent operation down to 55°F (13°C) dry bulb for cases where a night setback thermostat is used. Return air temperature must not exceed 85°F (29°C) dry bulb.
The EL280UH furnace may be installed in alcoves, clos­ets, attics, basements, garages, crawl spaces and utility
rooms in the upow or horizontal position.
This furnace design has not been CSA International
certied for installation in mobile homes, recreational
vehicles, or outdoors.
Air lters must be replaced upon construction com-
pletion.
• The input rate and temperature rise must be set
per the furnace rating plate.
• One hundred percent (100%) outdoor air must be
provided for combustion air requirements during construction. Temporary ducting may supply out­door air to the furnace. Do not connect duct direct-
ly to the furnace. Size the temporary duct following
these instructions in section for Combustion, Dilu-
tion and Ventilation Air in a conned space with air
from outside.
• The furnace heat exchanger, components, duct
system, air lters and evaporator coils must be thoroughly cleaned following nal construction
clean-up.
• All furnace operating conditions (including ignition, input rate, temperature rise and venting) must be
veried according to these installation instructions.
General
These instructions are intended as a general guide and do not supersede local codes in any way. Consult author­ities having jurisdiction before installation.
In addition to the requirements outlined previously, the following general recommendations must be considered when installing a EL280UH furnace
• Place the furnace as close to the center of the air distribution system as possible. The furnace should also be located close to the chimney or vent termi­nation point.
Page 4
• Do not install the furnace where drafts might blow directly into it. This could cause improper combus­tion and unsafe operation.
• Do not block the furnace combustion air openings with clothing, boxes, doors, etc. Air is needed for proper combustion and safe unit operation.
• When the furnace is installed in an attic or other insulated space, keep insulation away from the fur­nace.
• Please consult the manufacturer of your evaporator coil for their recommendations on distance required between the heat exchanger and their drain pan. Adequate space must be provided between the drain pan and the furnace heat exchanger.
NOTE - The Commonwealth of Massachusetts stipu­lates these additional requirements:
Gas furnaces shall be installed by a licensed
plumber or tter only.
The gas cock must be “T handle” type.
When a furnace is installed in an attic, the pas-
sageway to and service area surrounding the
equipment shall be oored.
WARNING
This product contains a chemical known to the State of California to cause cancer, birth defects, or other reproductive harm.
Combustion, Dilution & Ventilation Air
In the past, there was no problem in bringing in sufcient outdoor air for combustion. Inltration provided all the air
that was needed. In today’s homes, tight construction practices make it necessary to bring in air from outside for combustion. Take into account that exhaust fans, appli-
ance vents, chimneys, and replaces force additional air
that could be used for combustion out of the house. Un­less outside air is brought into the house for combustion, negative pressure (outside pressure is greater than inside pressure) will build to the point that a downdraft can oc­cur in the furnace vent pipe or chimney. As a result, com­bustion gases enter the living space creating a potentially dangerous situation.
In the absence of local codes concerning air for combus­tion and ventilation, use the guidelines and procedures in this section to install EL280UH furnaces to ensure ef­cient and safe operation. You must consider combustion air needs and requirements for exhaust vents and gas piping. A portion of this information has been reprinted with permission from the National Fuel Gas Code (AN­SI-Z223.1). This reprinted material is not the complete
and ofcial position of the ANSI on the referenced subject,
which is represented only by the standard in its entirety.
CAUTION
Insufcient combustion air can cause headaches, nausea, dizziness or asphyxiation. It will also cause
excess water in the heat exchanger resulting in rusting and premature heat exchanger failure. Excessive exposure to contaminated combustion air will result in safety and performance related problems. Avoid exposure to the following substances in the combustion air supply:
Permanent wave solutions Chlorinated waxes and cleaners Chlorine base swimming pool chemicals Water softening chemicals De-icing salts or chemicals Carbon tetrachloride Halogen type refrigerants Cleaning solvents (such as perchloroethylene) Printing inks, paint removers, varnishes, etc. Hydrochloric acid Cements and glues Antistatic fabric softeners for clothes dryers Masonry acid washing materials
All gas-red appliances require air for the combustion process. If sufcient combustion air is not available, the furnace or other appliances will operate inefciently and
unsafely. Enough air must be provided to meet the needs of all fuel-burning appliances and appliances such as ex­haust fans which force air out of the house. When re­places, exhaust fans, or clothes dryers are used at the same time as the furnace, much more air is necessary to ensure proper combustion and to prevent a downdraft.
Insufcient air causes incomplete combustion which can
result in carbon monoxide. In addition to providing combustion air, fresh outdoor air
dilutes contaminants in the indoor air. These contaminants may include bleaches, adhesives, detergents, solvents and other contaminants which can corrode furnace com­ponents.
The requirements for providing air for combustion and ventilation depend largely on whether the furnace is in-
stalled in an unconned or a conned space.
Unconned Space
An unconned space is an area such as a basement or
large equipment room with a volume greater than 50 cubic feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of the com­bined input rating of all appliances installed in that space. This space also includes adjacent rooms which are not separated by a door. Though an area may appear to be
un conned, it might be necessary to bring in outdoor air
for combustion if the structure does not provide enough air
by inltration. If the furnace is located in a building of tight
construction with weather stripping and caulking around the windows and doors, follow the procedures in the air from outside section.
Page 5
Conned Space
Air from Inside
A conned space is an area with a volume less than 50
cubic feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of the combined input rating of all appliances installed in that
space. This denition includes furnace closets or small
equipment rooms. When the furnace is installed so that supply ducts carry
air circulated by the furnace to areas outside the space containing the furnace, the return air must be handled by ducts which are sealed to the furnace casing and which terminate outside the space containing the furnace. This is especially important when the furnace is mounted on
a platform in a conned space such as a closet or small
equipment room. Even a small leak around the base of the unit at the plat-
form or at the return air duct connection can cause a po­tentially dangerous negative pressure condition. Air for combustion and ventilation can be brought into the con-
ned space either from inside the building or from outside
.
EQUIPMENT IN CONFINED
CHIMNEY
OR GAS
VENT
FURNACE
AIR FLOW
NOTE - Each opening shall have a free area of at least one square inch (645 mm ing of all equipment in the enclosure, but not less than 100 square inches (64516 mm
2
2
).
SPACE ALL AIR FROM INSIDE
WATER
HEATER
OPENINGS
(To Adjacent
Room)
If the conned space that houses the furnace adjoins a space categorized as unconned, air can be brought in by
providing two permanent openings between the two spac­es. Each opening must have a minimum free area of 1 square inch (645 mm2) per 1,000 Btu (.29 kW) per hour of
total input rating of all gas-red equipment in the conned
space. Each opening must be at least 100 square inches (64516 mm2). One opening shall be within 12 inches (305 mm) of the top of the enclosure and one opening within 12
inches (305 mm) of the bottom. See gure 2.
Air from Outside
If air from outside is brought in for combustion and ventila­tion, the conned space must have two permanent open­ings. One opening shall be within 12 inches (305 mm) of the top of the enclosure and one opening within 12 inches (305 mm) of the bottom. These openings must communi­cate directly or by ducts with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors or in­directly through vertical ducts. Each opening shall have a minimum free area of 1 square inch (645 mm2) per 4,000 Btu (1.17 kW) per hour of total input rating of all equipment
in the enclosure. See gures 3 and 4. When communi­cating with the outdoors through horizontal ducts, each
opening shall have a minimum free area of 1 square inch (645 mm2) per 2,000 Btu (.56 kW) per total input rating of
all equipment in the enclosure. See gure 5.
When ducts are used, they shall be of the same cross-sec­tional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be no less than 3 inches (75 mm). In calculating free area, the blocking effect of louvers, grilles, or screens must be considered. If the design and free area of protec-
tive covering is not known for calculating the size opening
required, it may be assumed that wood louvers will have 20 to 25 percent free area and metal louvers and grilles will have 60 to 75 percent free area. Louvers and grilles
must be xed in the open position or interlocked with the
equipment so that they are opened automatically during equipment operation.
FIGURE 2
Page 6
CHIMNEY OR
EQUIPMENT IN
CONFINED SPACE
ALL AIR FROM
OUTSIDE
OUTLET AIR
INLET AIR
WATER
HEATER
CHIMNEY
OR GAS
VENT
NOTE - Each air duct opening shall have a free area of at least one square inch (645 mm
2
) per 2,000 Btu (.59 kW) per hour of the total input rating of all equipment in the enclosure. If the equipment room is located against an outside wall and the air openings ing shall have a free area of at least one square inch (645 mm
2
) per 4,000 Btu (1.17 kW) per hour of the total input rating of all other equipment in the enclosure.
FURNACE
AIR FLOW
GAS VENT
FURNACE
(Inlet Air from Crawlspace and Outlet Air to Ventilated Attic)
VENTILATION LOUVERS
(Each end of attic)
EQUIPMENT IN CONFINED SPACE
ALL AIR FROM OUTSIDE
OUTLET
AIR
WATER
HEATER
CHIMNEY
OR GAS
VENT
FURNACE
VENTILATION
LOUVERS
(For unheated crawl space)
AIR FLOW
NOTE-The inlet and outlet air openings shall each have a free area of at least one square inch (645
2
mm
) per 4,000 Btu (1.17 kW) per hour of the total input rating of all equipment in the enclosure.
INLET
AIR
FIGURE 3
EQUIPMENT IN CONFINED SPACE
ALL AIR FROM OUTSIDE
(All Air Through Ventilated Attic)
VENTILATION LOUVERS
(Each end of attic)
OUTLET
AIR
INLET AIR
(Ends 12 in.
above bottom)
WATER
HEATER
AIR FLOW
NOTE-The inlet and outlet air openings shall each have a free area of at least one square inch (645 mm
ment in the enclosure.
FIGURE 4
2
) per 4,000
FIGURE 5
Page 7
Setting Equipment
WARNING
Do not install the furnace on its front or its back. Do not connect the return air ducts to the back of the furnace. Doing so will adversely affect the operation of the safety control devices, which could result in personal injury or death.
The EL280UH gas furnace can be installed as shipped in either the upow position or the horizontal position. Se­lect a location that allows for the required clearances that are listed on the unit nameplate. Also consider gas supply connections, electrical supply, vent connection, and instal­lation and service clearances [24 inches (610 mm) at unit front]. The unit must be level.
NOTE - Units with 1/3HP and 1/2HP blower motors are equipped with three exible legs and one shipping leg. See gure 6. In some units with 1/3HP blower motor, the ship­ping leg is exible with rubber mounting grommets similar to the other three mounting legs and require no modica­tion. The rest of the units with 1/3HP and 1/2HP blower motors (these blower motor housings will be tagged) have a rigid shipping leg equipped with a shipping bolt and at white plastic washer. The bolt and washer must be re- moved before the furnace is placed into operation. Af­ter the bolt and washer have been removed, the rigid leg will not touch the blower housing.
Blower motor with three exible legs and one rigid shipping leg. Blower motor housings will be tagged for shipping bolt removal
RIGID LEG
(Remove shipping bolt
and washer)
Upow Applications
Allow for clearances to combustible materials as indicated on the unit nameplate. Minimum clearances for closet or
alcove installations are shown in gure 7.
Upflow Application Installation Clearances
Top
Left Side
AIR FLOW
Bottom
Type of Vent
Connector
Top 1 in. (25 mm) 1 in. (25 mm)
*Front 2-1/4 in. (57 mm)** 2-1/4 in. (57 mm)
Back 0 0
Sides 0 0
Vent 6 in. (152 mm) 1 in. (25 mm)
Floor 0 0
*Front clearance in alcove installation must be 24 in. (610 mm). Maintain a minimum of 24 in. (610 mm) for front service access. ** 3-1/4 in. if single wall vent pipe is used. For installation on a combustible floor, do not install the furnace directly on carpeting, tile or other combustible materials other than wood flooring. Left side requires 3 inches if a single wall vent is used on 14-1/2 inch nets.
Type C Type B1
Right Side
FIGURE 6
FIGURE 7
Page 8
Return Air -- Upow Applications
Return air can be brought in through the bottom or either
side of the furnace installed in an upow application. If the
furnace is installed on a platform with bottom return, make an airtight seal between the bottom of the furnace and the platform to ensure that the furnace operates properly and safely. The furnace is equipped with a removable bottom panel to facilitate installation.
Markings are provided on both sides of the furnace cab­inet for installations that require side return air. Cut the furnace cabinet at the maximum dimensions shown on page 2.
NOTE - 60C and 60D units that require air volumes over 1800 cfm (850 L/s) must have one of the follow­ing:
1 - Single side return air with transition to accommodate
20 x 25 x 1 in. (508 x 635 x 25 mm) cleanable air
lter. (Required to maintain proper air velocity.) See gure 8.
2 - 2 - Single side return air with optional return
airbase. See gure 9.
3 - 3 - Bottom return air. 4 - 4 - Return air from both sides. 5 - 5 - Bottom and one side return air.
Refer to Engineering Handbook for additional information.
Single Side Return Air
(with transition and filter)
20” X 25” X 1”
(508mm X635mm X 25mm)
Cleanable Filter
Return Air
Plenum
AIR FLOW
Transition
FIGURE 8
Optional Return Air Base
(Upflow Applications Only -- For use with A, B, C and D cabinets)
FURNACE
FRONT
IF BASE IS USED
WITHOUT
INDOOR AIR
AIR FLOW
14−1/2” (368) A Width (65W75)
17−1/2” (446) B Width (50W98)
21”− (533) C Width (50W99)
24−1/2”− (622) D Width (51W00)
NOTE- Optional Side Return Air Filter Kits are not for use with Optional Return Air Base.
1
Both the unit return air opening and the base return air opening must be covered by a single plenum or IAQ cabinet. Minimum unit side return air opening dimensions for units requiring 1800 cfm or more of air (W x H): 23 x 11 in. (584 x 279 mm). The opening can be cut as needed to accommodate plenum or IAQ cabinet while maintaining dimensions shown. Side return air openings must be cut in the field. There are cutting guides stenciled on the cabinet for the side return air opening. The size of the opening must not extend beyond the markings on the furnace cabinet.
2
To minimize pressure drop, the largest opening height possible (up to 14 inches) is preferred.
OPTIONAL
RETURN AIR BASE
IAQ CABINET,
A SINGLE
RETURN AIR
PLENUM
MUST
COVER BOTH
UNIT AND
RETURN
AIR BASE
OPENINGS
3−1/4
(83)
7−1/4 (184)
1
23 (584)
Overall
(Maximum)
1
Unit side return air
Opening
5−5/8
(143)
SIDE RETURN
AIR OPENINGS
(Either Side)
26−7/8
(683)
SIDE VIEW
23
(584)
1
Minimum
11 (279)
2
Maximum
14 (356)
1
22−7/16
(570)
Overall
(Maximum)
3/4
(19)
FIGURE 9
Page 9
Removing the Bottom Panel
Removing the Bottom Panel
Hori
zontal Application
Horizontal Applications
Remove the two screws that secure the bottom cap to the furnace. Pivot the bottom cap down to release the bottom panel. Once the bottom panel has been removed, reinstall
the bottom cap. See gure 10.
Screw
Bottom Cap
The EL280UH furnace can be installed in horizontal ap­plications. Order horizontal suspension kit (51W10) from
Lennox, or use equivalent suspension method. Allow for clearances to combustible materials as indicated on the unit nameplate. Minimum clearances for closet or alcove
installations are shown in gure 11.
This furnace may be installed in either an attic or a crawl­space. Either suspend the furnace from roof rafters or
oor joists, as shown in gure 12, or install the furnace on a platform, as shown in gure 13.
Typical Horizontal Application
Unit Suspended in Attic or Crawlspace
Bracket
Metal Strap
Bottom Cap
3/16 inch
Air Flow
Bottom Panel
FIGURE 10
Installation Clearances
Left End
Vent Connector
Type
Top 0 0
*Front 2-1/4 in. (57 mm)** 2-14 in. (57 mm)
Back 0 0
Ends 2 in. (51 mm) 2 in. (51 mm)
Vent 6 in. (152 mm) 1 in. (25 mm)
Floor 0 0
*Front clearance in alcove installation must be 24 in. (610 mm). Maintain a minimum of 24 in. (610 mm) for front service access. ** 3-1/4 in. if single wall vent pipe is used. For installations on a combustible floor, do not install the furnace directly on carpeting, tile or other combustible materials other than wood flooring.
Top
Right
AIR FLOW
End
Bottom
Type C Type B1
FIGURE 12
NOTE - Heavy-gauge perforated sheet metal straps may be used to suspend the unit from roof rafters or ceiling oists. When straps are used to suspend the unit in this way, support must be provided for both the ends. The straps must not interfere with the plenum or exhaust pip­ing installation. Cooling coils and supply and return air
plenums must be supported separately.
NOTE - When the furnace is installed on a platform in a crawlspace, it must be elevated enough to avoid water damage and to allow the evaporator coil to drain
. Return Air -- Horizontal Applications
Return air must be brought in through the end of a fur-
nace installed in a horizontal application. The furnace is
equipped with a removable bottom panel to facilitate in-
stallation. See gure 10.
CAUTION
If this unit is being installed in a space serviced by an exhaust fan, power exhaust fan, or other device which may create a negative pressure in the space, take care
when sizing the inlet air opening. The inlet air opening must be sized to accommodate the maximum volume
of exhausted air as well as the maximum volume of combustion air required for all gas appliances serviced by this space.
FIGURE 11
Page 10
Horizontal Application
Unit Installed on Platform
Line contact is permissible
See the unit nameplate for clearances.
GAS
ENTRY
SERVICE PLATFORM
VENT
PIPE
FIGURE 13
WARNING
Improper installation of the furnace can result in personal
injury or death. Combustion and ue products must
never be allowed to enter the return air system or the living space. Use screws and joint tape to seal the return air system to the furnace.
In platform installations with bottom return air, the furnace should be sealed airtight to the return air plenum. A door must never be used as a portion of the return air duct system. The base must provide a stable support and an airtight seal to the furnace. Allow absolutely no sagging, cracks, gaps, etc. The return and supply air duct systems must never be connected to or from other
heating devices such as a replace or stove, etc. Fire,
explosion, carbon monoxide poisoning, personal injury and/or property damage could result.
WARNING
The blower access panel must be securely in place when the blower and burners are operating. Gas fumes, which could contain carbon monoxide, can be drawn into living space resulting in personal injury or death.
Filters
This unit is not equipped with a lter or rack. A eld-pro­vided high-velocity lter is required for the unit to operate properly. Table 1 lists recommended lter sizes.
A lter must be in place any time the unit is operating.
IMPORTANT
If a highefciency lter is being installed as part of this system to ensure better indoor air quality, the lter must be properly sized. Highefciency lters have a higher static pressure drop than standardefciency glass/foam lters. If the pressure drop is too great, system capacity
and performance may be reduced. The pressure drop may also cause the limit to trip more frequently during
the winter and the indoor coil to freeze in the summer,
resulting in an increase in the number of service calls.
Before using any lter with this system, check the specications provided by the lter manufacturer against
the data given in the appropriate Lennox Product
Specications bulletin. Additional information is provided
in Service and Application Note ACC002 (August 2000).
TABLE 1
Furnace Cabinet
Width
14-1/2” 16 X 25 X 1 (1) 14 X 25 X 1 (1)
17-1/2” 16 X 25 X 1 (1) 16 X 25 X 1 (1)
21” 16 X 25 X 1 (1) 20 X 25 X 1 (1)
24-1/2” 16 X 25 X 1 (2) 24 X 25 X 1 (1)
Side Return Bottom Return
Filter Size
Page 11
Duct
Use industry-approved standards (such as those pub­lished by Air Conditioning Contractors of America or Amer­ican Society of Heating, Refrigerating and Air Condition-
ing Engineers) to size and install the supply and return
air duct system. This will result in a quiet and low-static system that has uniform air distribution.
NOTE - Do not operate the furnace in the heating mode with an external static pressure that exceeds 0.5 inches w.c. Higher external static pressures may cause erratic limit operation.
Supply Air Plenum
If the furnace is installed without a cooling coil, a remov­able access panel must be installed in the supply air duct. The access panel should be large enough to permit in-
spection (either by smoke or reected light) of the heat
exchanger for leaks after the furnace is installed. The furnace access panel must always be in place when the furnace is operating and it must not allow leaks into the supply air duct system.
Return Air Plenum
NOTE - Return air must not be drawn from a roomwhere this furnace, or any other gas-fueled appliance (i.e., water heater), or carbon monoxide producing device (i.e., wood replace) is installed.
When return air is drawn from a room, a negative pressure is created in the room. If a gas appliance is operating in
a room with negative pressure, the ue products can be
pulled back down the vent pipe and into the room. This reverse ow of the ue gas may result in incomplete com­bustion and the formation of carbon monoxide gas. This toxic gas might then be distributed throughout the house by the furnace duct system.
In upow applications, the return air can be brought in
through the bottom or either side of the furnace. If a fur­nace with bottom return air is installed on a platform, make an airtight seal between the bottom of the furnace and the platform to ensure that the unit operates properly and safely. Use berglass sealing strips, caulking, or equiva­lent sealing method between the plenum and the furnace
cabinet to ensure a tight seal. If a lter is installed, size the return air duct to t the lter frame.
Page 12
Loading...
+ 26 hidden pages