Lennox EL280DF User Manual

INSTALLATION
E 2012 Lennox Industries Inc.
Dallas, Texas, USA
DOWNFLOW
INSTRUCTIONS EL280DF
MERIT® SERIES GAS FURNACE DOWNFLOW AIR DISCHARGE
506896−01 08/2012
This is a safety alert symbol and should never be ignored. When you see this symbol on labels or in manuals, be alert to the potential for personal injury or death.
THIS MANUAL MUST BE LEFT WITH THE
HOMEOWNER FOR FUTURE REFERENCE
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, person­al injury or loss of life. Installation and service must be performed by a licensed professional installer (or equivalent), service agency or the gas supplier.
Litho U.S.A.
Table of Contents
Unit Dimensions 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
EL280DF Gas Furnace 3. . . . . . . . . . . . . . . . . . . . . . . . . .
Shipping and Packing List 3. . . . . . . . . . . . . . . . . . . . . . . .
Safety Information 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Use of Furnace as a Construction Heater 4. . . . . . . . . . .
General 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Combustion, Dilution & Ventilation Air 5. . . . . . . . . . . . . .
Downflow Installation 8. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setting Equipment 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Filters 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Duct System 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CAUTION
As with any mechanical equipment, personal injury can result from contact with sharp sheet metal edges. Be careful when you handle this equipment.
Venting 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Gas Piping 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Integrated Control 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit Start−Up 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Gas Pressure Adjustment 25. . . . . . . . . . . . . . . . . . . . . . . .
Proper Combustion 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
High Altitude 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Other Unit Adjustments 27. . . . . . . . . . . . . . . . . . . . . . . . . .
Heating Sequence of Operation 28. . . . . . . . . . . . . . . . . . .
Service 29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Repair Parts List 30. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Start Up and Performance Checklist 31. . . . . . . . . . . . . . .
08/12
*2P0812*
Page 1
506896−01
*P506896-01*
Unit Dimensions − inches (mm)
A
B
AIR FLOW
9/16
(14)
FLUE OUTLET
(Top)
11/2 (38)
Front Panel
31/8
(79)
D
9/16
(14)
RETURN AIR
OPENING
B
197/16
(494)
9/16
(14)
TOP VIEW
273/4
(705)
197/16
(494)
9/16
(14)
9/16
(14)
ELECTRICAL INLET
33
(838)
Supply
C
Air
Model No.
EL280DF070P36A 14−1/2 368 13−3/8 340 13 330 4−3/4 121
EL280DF090P48B 17−1/2 446 16−3/8 416 16 406 6−1/4 159
EL280DF110P60C 21 533 19−7/8 504 19−1/2 495 8 203
in. mm in. mm in. mm in. mm
3/4
(19)
A B C D
53/8 (137) Right 23/16 (56) Left
65/8 (168) Right 71/8 (181) Left
(Either Side)
GAS PIPING INLET
(Either Side)
191/4
Supply
(489)
Air
Page 2
EL280DF Gas Furnace
The EL280DF gas furnace is shipped ready for installation in the downflow position fueled by natural gas. A conver­sion kit (ordered separately) is required for use in LP/Pro­pane gas applications.
Shipping and Packing List
Package 1 of 1 contains
1 − Assembled EL280DF unit 1 − Bag assembly containing the following:
2 − Screws 1 − Snap bushing 1 − Snap plug 1 − Wire tie 1 − Vent warning label 1 − Owner’s manual and warranty card
The following items may be ordered separately: 1 − Thermostat 1 − LP/Propane changeover kit 1 − Combustible flooring base 1 − High altitude kit
Check equipment for shipping damage. If you find any damage, immediately contact the last carrier.
Safety Information
DANGER
Danger of explosion.
There are circumstances in which odorant used with LP/propane gas can lose its scent. In case of a leak, LP/propane gas will settle close to the floor and may be difficult to smell. An LP/propane leak detector should be installed in all LP applications.
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, person­al injury or loss of life. Installation and service must be performed by a licensed professional installer (or equivalent), service agency or the gas supplier.
CAUTION
As with any mechanical equipment, personal injury can result from contact with sharp sheet metal edges. Be careful when you handle this equipment.
Certifications
EL280DF units are CSA International certified. In the USA, installation of gas furnaces must conform with
local building codes. In the absence of local codes, units must be installed according to the current National Fuel Gas Code (ANSI-Z223.1). The National Fuel Gas Code is available from the following address:
American National Standards Institute, Inc. 11 West 42nd Street New York, NY 10036
Clearances
Adequate clearance must be made around the air open­ings into the vestibule area. In order to ensure proper unit operation, combustion and ventilation air supply must be provided according to the current National Fuel Gas Code.
Vent installations must be consistent with the National Fuel Gas Code venting tables (in this instruction) and applicable provisions of local building codes.
This furnace is CSA International certified for installation clearances to combustible material as listed on the unit nameplate and in the tables in figure 13. Accessibility and service clearances must take precedence over fire protection clearances.
Installed Locations
For installation in a residential garage, the furnace must be installed so that the burner(s) and the ignition source are located no less than 18 inches (457 mm) above the floor. The furnace must be located or protected to avoid physical damage by vehicles. When a furnace is installed in a public garage, hangar, or other building that has a haz­ardous atmosphere, the furnace must be installed accord­ing to recommended good practice requirements and cur­rent National Fuel Gas Code.
NOTE − Furnace must be adjusted to obtain a temperature rise within the range(s) specified on the unit nameplate. Fail­ure to do so may cause erratic limit operation and may also result in premature heat exchanger failure.
This EL280DF furnace must be installed so that its electri­cal components are protected from water.
Installed in Combination with a Cooling Coil
When this furnace is used with cooling units, it shall be installed in parallel with, or on the upstream side of, cooling units to avoid condensation in the heating compartment. With a parallel flow arrangement, a damper (or other means to control the flow of air) must adequately prevent chilled air from entering the furnace (see figure 1). If the damper is manually operated, it must be equipped to pre­vent operation of either the heating or the cooling unit, un­less it is in the full HEAT or COOL setting.
Page 3
GAS UNIT
Dampers
(open during heating
operation only)
AIR HANDLER
Dampers
(open during cooling
operation only)
FIGURE 1
When installed, this furnace must be electrically grounded according to local codes. In addition, in the United States, installation must conform with the current National Elec­tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available from the following ad­dress:
National Fire Protection Association 1 Battery March Park Quincy, MA 02269
NOTE − This furnace is designed for a minimum continu­ous return air temperature of 60°F (16°C) or an intermit­tent operation down to 55°F (13°C) dry bulb for cases where a night setback thermostat is used. Return air tem­perature must not exceed 85°F (29°C) dry bulb.
The EL280DF furnace may be installed in alcoves, closets, attics, basements, garages, and utility rooms in the down­flow position.
This furnace design has not been CSA International certified for installation in mobile homes, recreational vehicles, or outdoors.
Use of Furnace as Construction Heater
Lennox does not recommend the use of EL280DF units as a construction heater during any phase of construction. Very low return air temperatures, harmful vapors and op­eration of the unit with clogged or misplaced filters will dam­age the unit.
EL280DF units may be used for heating of buildings or structures under construction, if the following conditions are met:
D The vent system must be permanently installed per
these installation instructions.
D A room thermostat must control the furnace. The use of
fixed jumpers that will provide continuous heating is not allowed.
D The return air duct must be provided and sealed to the
furnace.
D Return air temperature range between 60°F (16°C) and
80°F (27°C) must be maintained.
D Air filters must be installed in the system and must be
maintained during construction.
D Air filters must be replaced upon construction comple-
tion.
D The input rate and temperature rise must be set per the
furnace rating plate.
D One hundred percent (100%) outdoor air must be pro-
vided for combustion air requirements during construc­tion. Temporary ducting may supply outdoor air to the furnace. Do not connect duct directly to the furnace. Size the temporary duct following these instructions in section for Combustion, Dilution and Ventilation Air in a confined space with air from outside.
D The furnace heat exchanger, components, duct system,
air filters and evaporator coils must be thoroughly cleaned following final construction clean−up.
D All furnace operating conditions (including ignition, in-
put rate, temperature rise and venting) must be verified according to these installation instructions.
General
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities having jurisdiction before installation.
In addition to the requirements outlined previously, the fol­lowing general recommendations must be considered when installing a EL280DF furnace:
D Place the furnace as close to the center of the air dis-
tribution system as possible. The furnace should also be located close to the chimney or vent termination point.
D Do not install the furnace where drafts might blow direct-
ly into it. This could cause improper combustion and un­safe operation.
D Do not block the furnace combustion air openings with
clothing, boxes, doors, etc. Air is needed for proper combustion and safe unit operation.
D When the furnace is installed in an attic or other insu-
lated space, keep insulation away from the furnace.
NOTE − The Commonwealth of Massachusetts stipu­lates these additional requirements:
D Gas furnaces shall be installed by a licensed plumb-
er or fitter only.
D The gas cock must be T handle" type. D When a furnace is installed in an attic, the passage-
way to and service area surrounding the equipment shall be floored.
Page 4
WARNING
The State of California has determined that this prod­uct may contain or produce a chemical or chemicals, in very low doses, which may cause serious illness or death. It may also cause cancer, birth defects or re­productive harm.
Combustion, Dilution & Ventilation Air
In the past, there was no problem in bringing in sufficient out­door air for combustion. Infiltration provided all the air that was needed. In today’s homes, tight construction practices make it necessary to bring in air from outside for combus­tion. Take into account that exhaust fans, appliance vents, chimneys, and fireplaces force additional air that could be used for combustion out of the house. Unless outside air is brought into the house for combustion, negative pressure (outside pressure is greater than inside pressure) will build to the point that a downdraft can occur in the furnace vent pipe or chimney. As a result, combustion gases enter the liv­ing space creating a potentially dangerous situation.
In the absence of local codes concerning air for combus­tion and ventilation, use the guidelines and procedures in this section to install EL280DF furnaces to ensure efficient and safe operation. You must consider combustion air needs and requirements for exhaust vents. A portion of this information has been reprinted with permission from the National Fuel Gas Code (ANSI-Z223.1). This reprinted ma­terial is not the complete and official position of the ANSI on the referenced subject, which is represented only by the standard in its entirety.
CAUTION
Do not install the furnace in a corrosive or contami­nated atmosphere. Meet all combustion and ventila­tion air requirements, as well as all local codes.
CAUTION
Insufficient combustion air can cause headaches, nausea, dizziness or asphyxiation. It will also cause excess water in the heat exchanger resulting in rust­ing and premature heat exchanger failure. Excessive exposure to contaminated combustion air will result in safety and performance related problems. Avoid exposure to the following substances in the combus­tion air supply:
Permanent wave solutions Chlorinated waxes and cleaners Chlorine base swimming pool chemicals Water softening chemicals De-icing salts or chemicals Carbon tetrachloride Halogen type refrigerants Cleaning solvents (such as perchloroethylene) Printing inks, paint removers, varnishes, etc. Hydrochloric acid Cements and glues Antistatic fabric softeners for clothes dryers Masonry acid washing materials
All gas-fired appliances require air for the combustion pro­cess. If sufficient combustion air is not available, the fur­nace or other appliances will operate inefficiently and un­safely. Enough air must be provided to meet the needs of all fuel-burning appliances and appliances such as exhaust fans which force air out of the house. When fireplaces, ex­haust fans, or clothes dryers are used at the same time as the furnace, much more air is necessary to ensure proper combustion and to prevent a downdraft. Insufficient air causes incomplete combustion which can result in carbon monoxide.
In addition to providing combustion air, fresh outdoor air dilutes contaminants in the indoor air. These contami­nants may include bleaches, adhesives, detergents, sol­vents and other contaminants which can corrode furnace components.
The requirements for providing air for combustion and ven­tilation depend largely on whether the furnace is installed in an unconfined or a confined space.
Unconfined Space
An unconfined space is an area such as a basement or large equipment room with a volume greater than 50 cubic feet (1.42 m bined input rating of all appliances installed in that space. This space also includes adjacent rooms which are not separated by a door. Though an area may appear to be un­confined, it might be necessary to bring in outdoor air for combustion if the structure does not provide enough air by infiltration. If the furnace is located in a building of tight construction with weather stripping and caulking around the windows and doors, follow the procedures in the air from outside section.
3
) per 1,000 Btu (.29 kW) per hour of the com-
Page 5
Confined Space
A confined space is an area with a volume less than 50 cu­bic feet (1.42 m
3
) per 1,000 Btu (.29 kW) per hour of the combined input rating of all appliances installed in that space. This definition includes furnace closets or small equipment rooms.
When the furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space contain­ing the furnace, the return air must be handled by ducts which are sealed to the furnace casing and which terminate outside the space containing the furnace. This is especially important when the furnace is mounted on a platform in a confined space such as a closet or small equipment room. Even a small leak around the base of the unit at the platform or at the return air duct connection can cause a potentially dangerous negative pressure condition. Air for combustion and ventilation can be brought into the confined space either from inside the building or from outside.
EQUIPMENT IN CONFINED
CHIMNEY
OR GAS
VENT
FURNACE
NOTE − Each opening shall have a free area of at least one square inch (645 mm ing of all equipment in the enclosure, but not less than 100 square inches (64516 mm
2
) per 1,000 Btu (.29 kW) per hour of the total input rat-
2
).
SPACE ALL AIR FROM INSIDE
WATER
HEATER
OPENINGS (To Adjacent
Room)
FIGURE 2
Air from Inside
If the confined space that houses the furnace adjoins a space categorized as unconfined, air can be brought in by providing two permanent openings between the two spaces. Each opening must have a minimum free area of 1 square inch (645 mm
2
) per 1,000 Btu (.29 kW) per hour of total input rating of all gas−fired equipment in the confined space. Each opening must be at least 100 square inches (64516 mm
2
). One opening shall be within 12 inches (305 mm) of the top of the enclosure and one opening within 12 inches (305 mm) of the bottom. See figure 2.
Air from Outside
If air from outside is brought in for combustion and ventila­tion, the confined space must have two permanent open­ings. One opening shall be within 12 inches (305 mm) of the top of the enclosure and one opening within 12 inches (305 mm) of the bottom. These openings must communicate di­rectly or by ducts with the outdoors or spaces (crawl or at­tic) that freely communicate with the outdoors or indirectly through vertical ducts. Each opening shall have a minimum free area of 1 square inch (645 mm
2
) per 4,000 Btu (1.17
kW) per hour of total input rating of all equipment in the en­closure. See figures 3 and 4. When communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 square inch (645 mm
2
) per
2,000 Btu (.56 kW) per total input rating of all equipment in the enclosure. See figure 5.
When ducts are used, they shall be of the same cross−sec­tional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be no less than 3 inches (75 mm). In calculating free area, the blocking effect of louvers, grilles, or screens must be considered. If the design and free area of protective cov­ering is not known for calculating the size opening required, it may be assumed that wood louvers will have 20 to 25 per­cent free area and metal louvers and grilles will have 60 to 75 percent free area. Louvers and grilles must be fixed in the open position or interlocked with the equipment so that they are opened automatically during equipment operation.
Page 6
CHIMNEY OR
GAS VENT
FURNACE
(Inlet Air from Crawlspace and Outlet Air to Ventilated Attic)
VENTILATION LOUVERS
(Each end of attic)
EQUIPMENT IN CONFINED SPACE
ALL AIR FROM OUTSIDE
OUTLET
AIR
WATER
HEATER
CHIMNEY
OR GAS
VENT
FURNACE
VENTILATION
LOUVERS
(For unheated crawl space)
NOTE−The inlet and outlet air openings shall each have a free area of at least one square inch (645
2
mm
) per 4,000 Btu (1.17 kW) per hour of the total input rating of all equipment in the enclosure.
INLET
AIR
FIGURE 3
EQUIPMENT IN CONFINED SPACE
ALL AIR FROM OUTSIDE
(All Air Through Ventilated Attic)
VENTILATION LOUVERS
(Each end of attic)
OUTLET
AIR
INLET AIR
(Ends 12 in.
above bottom)
FURNACE
CHIMNEY
OR GAS
VENT
CONFINED SPACE
WATER
HEATER
OUTLET AIR
INLET AIR
EQUIPMENT IN
ALL AIR FROM
OUTSIDE
WATER
HEATER
NOTE−The inlet and outlet air openings shall each have a free area of at least one square inch (645 mm
2
) per 4,000 Btu (1.17 kW) per hour of the total input rating of all equip­ment in the enclosure.
FIGURE 4
Page 7
NOTE − Each air duct opening shall have a free area of at least one square inch (645 mm
2
) per 2,000 Btu (.59 kW) per hour of the total input rating of all equipment in the enclosure. If the equipment room is located against an outside wall and the air openings communicate directly with the outdoors, each open­ing shall have a free area of at least one square inch (645 mm per 4,000 Btu (1.17 kW) per hour of the total input rating of all other equipment in the enclosure.
FIGURE 5
2
)
Downflow Installation
Downflow unit installs in three ways: on non−combustible flooring, on combustible flooring using a downflow com­bustible flooring base, or on a reverse−flow cooling cabinet. Do not drag the unit across the floor.
Installation on Non−Combustible Flooring (Figure 6)
1 − Cut floor opening keeping in mind clearances listed on
unit rating plate. Also keep in mind gas supply connec­tions, electrical supply, flue and air intake connections and sufficient installation and servicing clearances. See table 1 for correct floor opening size.
2 − Flange warm air plenum and lower the plenum into the
opening.
3 − Set the unit over the plenum and seal the plenum to
the unit.
4 − Ensure that the seal is adequate.
CAUTION
The furnace and downflow combustible flooring base shall not be installed directly on carpeting, tile, or other combustible material other than wood floor­ing.
EL280DF UNIT
SUPPLY AIR PLENUM
PROPERLY
SIZED FLOOR
OPENING
DOWNFLOW
COMBUSTIBLE
FLOORING BASE
EL280DF UNIT
OPENING
SUPPLY AIR
PLENUM
FIGURE 6
TABLE 1
NON−COMBUSTIBLE FLOOR OPENING SIZE
Cabinet Width
A (14.5") 19−3/4 502 13−1/4 337
B (17.5") 19−3/4 502 16−1/4 413
C (21") 19−3/4 502 19−3/4 502
NOTE − Floor opening dimensions listed are 1/4 inch (6 mm) larger than the unit opening. See unit dimensions on page 2.
Front to Rear Side to Side
in. mm in. mm
Installation on Combustible Flooring (Figure 7)
1 − When unit is installed on a combustible floor, a down-
flow combustible flooring base must be installed be­tween the furnace and the floor. The base must be or­dered separately.
See table 2 for opening size to cut in floor.
FIGURE 7
TABLE 2
COMBUSTIBLE FLOOR OPENING SIZE
Cabinet Width
A (14.5")
B (17.5")
C (21")
Front to Rear Side to Side
in. mm in. mm
22 559 15−3/4 400
22 559 18−3/4 476
22 559 22−3/4 578
2 − After opening is cut, set combustible flooring base into
opening.
3 − Check sealing strips on combustible flooring base to
make sure they are properly glued and positioned.
4 − Lower supply air plenum into downflow combustible
flooring base until plenum flanges seal against the strips.
NOTE − Be careful not to damage sealing strips. Check for a tight seal.
5 − Set the furnace over the plenum.
6 − Ensure that the seal between the furnace and plenum
is adequate.
Installation on Cooling Cabinet (Figure 8)
1 − Refer to reverse−flow coil installation instructions for
correctly sized opening in floor and installation of cabi­net.
NOTE − Downflow combustible flooring kit is not used
2 − When cooling cabinet is in place, set and secure the
furnace according to the instructions that are provided with the cooling coil. Secure the furnace to the cabinet.
3 − Seal the cabinet and check for air leaks.
Page 8
PROPERLY
SIZED FLOOR
OPENING
EL280DF UNIT
COOLING COIL
PLENUM
Setting Equipment
WARNING
Do not install the furnace on its front, back or in the horizontal position. See figure 12. Do not connect the return air ducts to the back of the furnace. Doing so will adversely affect the operation of the safety con­trol devices, which could result in personal injury or death.
Install the EL280DF gas furnace as shipped in the down­flow position only. Do not install the furnace hori-
zontally.
FIGURE 8
Return Air Opening −− Downflow Units
The following steps should be taken when installing ple­num:
1 − Bottom edge of plenum should be flanged with a
hemmed edge (See figure 9).
PLENUM
SECURE FROM
OUTSIDE CABINET
Side View
HEMMED EDGE
SEALING STRIP
(Field Provided)
CABINET SIDE PANEL
FIGURE 9
2 − Sealing strip should be used.
3 − In all cases, plenum should be secured to top flanges
of furnace with sheet metal screws.
SECURE FROM IN-
SIDE CABINET
PLENUM
Side View
HEMMED EDGE
Select a location that allows for the required clearances that are listed on the unit nameplate. Also consider gas supply connections, electrical supply, vent connection, and installation and service clearances [24 inches (610 mm) at unit front]. The unit must be level.
NOTE − Units with 1/2 hp blower motors are equipped with three flexible legs and one rigid leg. See figure 11. The rigid leg is equipped with a shipping bolt and a flat white plastic washer (rather than the rubber mounting grommet used with a flexible mounting leg). The bolt and washer must
be removed before the furnace is placed into opera­tion. After the bolt and washer have been removed, the rig-
id leg will not touch the blower housing.
UNITS WITH 1/2 HP BLOWER MOTOR
RIGID LEG
remove shipping bolt and washer
FIBERGLASS SEALING STRIP (Field Provided)
CABINET SIDE
PANEL
FIGURE 10
4 − In closet installations, it may be impossible to install
sheet metal screws from the outside. In this case,
make plenum with a removable front and install
screws from the inside (See figure 10).
5 − Make certain that an adequate seal is made.
FIGURE 11
WARNING
The blower access panel must be securely in place when the blower and burners are operating. Gas fumes, which could contain carbon monoxide, can be drawn into living space resulting in personal inju­ry or death.
Page 9
Front
Back
FIGURE 12
Downflow Application
Allow for clearances to combustible materials as indicated on the unit nameplate. Minimum clearances for closet or al­cove installations are shown in figure 13.
Downflow Application Installation Clearances
Top
Left Side
Bottom
Type of Vent
Connector
Top 1 in. (25 mm) 1 in. (25 mm)
*Front 2−1/4 in. (57 mm)** 2−1/4 in. (57 mm)
Back 0 0
Sides 0 0
Vent 6 in. (152 mm) 1 in. (25 mm)
Floor NC†† NC††
*Front clearance in alcove installation must be 24 in. (610 mm). Maintain a minimum of 24 in. (610 mm) for front service access. ** 4−1/2 in. if a single wall vent pipe is used. †Left side requires 3 in. if a single wall vent is used on 14 −1/2 in. cab­inets, or 2 in. if a single wall vent is used on 17 − 1/2 in. cabinets. ††The furnace may be installed on a combustible wood floor if an optional additive base is installed between the furnace and the combustible floor.
Type C Type B1
Right Side
FIGURE 13
Horizontal
WARNING
Improper installation of the furnace can result in per­sonal injury or death. Combustion and flue products must never be allowed to enter the return air system or the living space. Use screws and joint tape to seal the return air system to the furnace. In platform installations with bottom return air, the furnace should be sealed airtight to the return air ple­num. A door must never be used as a portion of the return air duct system. The base must provide a stable support and an airtight seal to the furnace. Al­low absolutely no sagging, cracks, gaps, etc. The return and supply air duct systems must never be connected to or from other heating devices such as a fireplace or stove, etc. Fire, explosion, carbon monoxide poisoning, personal injury and/or proper­ty damage could result.
Filters
This unit is not equipped with a filter or rack. A field−pro­vided high−velocity filter is required for the unit to operate properly. Table 3 lists recommended filter sizes. A filter must be in place any time the unit is operating.
TABLE 3
Cabinet Width
A (14−1/2") 14 x 25 x 1 (1) B (17−1/2") 16 x 25 x 1 (1)
C (21") 20 x 25 x 1 (1)
Return Air Filter Size (inches)
Page 10
Loading...
+ 22 hidden pages