EL195UHE series units are high−efficiency gas furnaces manufactured with Lennox DuralokPlust alumi-
nized steel clamshell−type heat exchangers, with a stainless
steel condensing coil. EL195UHE units are a vailable in
heating input capacities of 44,000 to 132,000 Btuh and
cooling applications from 2 through 5 tons. Refer to Engineering Handbook for proper sizing.
Units are factory equipped for use with natural gas. A kit is
available for conversion to LP/Propane operation. All
EL195UHE units are equipped with a hot surface ignition
system. The gas valve is redundant to assure safety
shut−off as required by C.S.A.
The heat exchanger, burners and manifold assembly can be
removed for inspection and service. The maintenance section
gives a detailed description on how this is done.
All specifications are subject to change. Procedures outlined
in this manual are presented as a recommendation only
and do not supersede or replace local or state codes.
WARNING
Electric shock hazard. Can cause injury
or death. Before attempting to perform
any service or maintenance, turn the
electrical power to unit OFF at disconnect switch(es). Unit may have multiple
power supplies.
VII−Sequence of Operation and Flow Charts50. . . . . .
WARNING
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, personal injury or loss of life. Installation and service must
be performed by a licensed professional installer (or
equivalent), service agency or the gas supplier.
WARNING
Sharp edges.
Be careful when servicing unit to avoid sharp edges
which may result in personal injury.
Page 2
SPECIFICATIONS
Gas
Heating
Performance
Temperature rise range - °F25 - 5540 - 7040 - 70
Gas Manifold Pressure (in. w.g.)
Nat. Gas / LPG/Propane
High static - in. w.g.0.50.50.5
Connections
Intake / Exhaust Pipe (PVC)2 / 22 / 22 / 2
in.
Condensate Drain Trap (PVC pipe) - i.d.1/21/21/2
with furnished 90° street elbow1/2 slip x 1/2 Mipt1/2 slip x 1/2 Mipt1/2 slip x 1/2 Mipt
with eld supplied (PVC coupling) - o.d.1/2 slip x 1/2 Npt1/2 slip x 1/2 Npt1/2 slip x 1/2 Npt
Indoor
Wheel nom. dia. x width - in.10 x 810 x 810 x 10
Blower
Tons of add-on cooling1.5 - 31.5 - 32.5 - 4
Air Volume Range - cfm360 - 1345495 - 1380715 - 1740
NOTE - Filters and provisions for mounting are not furnished and must be eld provided.
1
Annual Fuel Utilization Efciency based on DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non-weatherized
furnaces.
Model No.EL195UH045XE36BEL195UH070XE36BEL195UH090XE48C
1
AFUE95%95%95%
Input - Btuh44,00066,00088,000
Output - Btuh42,00063,00085,000
3.5 / 103.5 / 103.5 / 10
Gas pipe size IPS1/21/21/2
Motor output - hp1/21/23/4
SPECIFICATIONS
Gas
Heating
Performance
Temperature rise range - °F40 - 7045 - 75
Gas Manifold Pressure (in. w.g.)
Nat. Gas / LPG/Propane
High static - in. w.g.0.50.5
Connections
Intake / Exhaust Pipe (PVC)2 / 22 / 2
in.
Condensate Drain Trap (PVC pipe) - i.d.1/21/2
with furnished 90° street elbow1/2 slip x 1/2 Mipt1/2 slip x 1/2 Mipt
with eld supplied (PVC coupling) - o.d.1/2 slip x 1/2 Npt1/2 slip x 1/2 Npt
Indoor
Wheel nom. dia. x width - in.11-1/2 x 1011-1/2 x 10
NOTE - Filters and provisions for mounting are not furnished and must be eld provided.
1
Annual Fuel Utilization Efciency based on DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non-weatherized
Single Side Return Air − Air volumes in bold require eld
fabricated transition to accommodate 20 x 25 x 1 in. air lter
in order to maintain proper air velocity.
Page 5
Page 6
Page 6
EL195UHE PARTS IDENTIFICATION
FIGURE 1
TOP CAP
BURNER BOX
ASSEMBLY
DuralokPlus
TM
HEAT EXCHANGER
ASSEMBLY
CONTROL BOX
(includes integrated ignition control, trans-
former, circuit breaker and interlock switch)
COMBUSTION AIR
INDUCER
OUTER
ACCESS
PANEL
COMBUSTION
AIR PRESSURE
SWITCH
PRIMARY LIMIT
GAS VALVE
BLOWER
ASSEMBLY
FLEXIBLE NO−HUB
EXHAUST COLLAR
COLD END
HEADER BOX
BAG ASSEMBLIES
(shipping location)
BLOWER ACCESS
PAN EL
Page 7
Page 7
I−UNIT COMPONENTS
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
CAUTION
Electrostatic discharge can affect electronic components. Take precautions to
neutralize electrostatic charge by
touching your hand and tools to metal
prior to handling the control.
EL195UHE unit components are shown in figure 1. The
combustion air inducer, gas valve and burners can be accessed by removing the outer access panel. The blower
and control box can be accessed by removing the blower access panel.
A−Control Box Components (Figure 2)
Unit transformer (T1) and integrated ignition control (A92)
are located in the control box. In addition, a door interlock
switch (S51) is located in the control box.
FIGURE 2
EL195UHE Control Box
Integrated Control
Door Interlock
Switch
Transformer
Circuit Breaker
1. Transformer (T1)
A transformer located in the control box provides power to
the low voltage section of the unit. The transformers on all
models are rated at 40VA with a 120V primary and 24V
secondary.
2. Door Interlock Switch (S51)
A door interlock switch rated 14A at 120VAC is located on
the control box. The switch is wired in series with line voltage. When the blower door is removed the unit will shut
down.
3. Circuit Breaker (CB8)
A 24V circuit breaker is also located in the control box. The
switch provides overcurrent protection to the transformer
(T1). The breaker is rated at 3A at 32V. If the current exceeds this limit the breaker will trip and all unit operation will
shutdown. The breaker can be manually reset by pressing
the button on the face.
4. Integrated Ignition Control (A92)
WARNING
Shock hazard.
Disconnect power before servicing. Control is not
field repairable. If control is inoperable, simply replace entire control.
Can cause injury or death. Unsafe operation will result if repair is attempted.
The hot surface ignition control system consisting of an integrated control (figure 3 with control terminal designations in tables 1, 2 and 3), sensor and ignitor (figure 5). The
integrated control and ignitor work in combination to ensure furnace ignition and ignitor durability. The integrated
control, controls all major furnace operations. The integrated control also features a RED LED for troubleshooting and two accessory terminals rated at (1) one amp. See
table 4 for troubleshooting diagnostic codes. The nitride
ignitor is made from a non−porous, high strength proprietary ceramic material that provides long life and trouble
free maintenance.
TABLE 1
4−Pin Terminal Designation
PIN #FUNCTION
1Combustion Air Inducer Line
2
Ignitor Line
3
Combustion Air Inducer Neutral
4
Ignitor Neutral
TABLE 2
12−Pin Terminal Designations
PIN #FUNCTION
1High Limit Output
2Not Used
324V Line
4Not Used
5Rollout Switch Out
624V Neutral
7High Limit Input
8Ground
9Gas Valve Common
10Pressure Switch In
11Rollout Switch In
12Gas Valve Out
Page 8
Page 8
TABLE 3
1/4" QUICK CONNECT TERMINALS
120HUMHumidifier 120VAC
LINE120VAC
XFMRTransformer 120VAC
CIRCIndoor blower 120VAC
EACIndoor air quality accessory 120VAC
NEUTRALSCommon 120VAC
HUM24Humidifier 24VAC
3/16" QUICK CONNECT TERMINALS
COOLCooling tap 24VAC
HEATHeating tap 24VAC
FANContinuous blower 24 VAC
PARK (no power)Park terminal for unused speed taps
FSFlame sense
24 COMCommon 24VAC
TABLE 4
The integrated control is equipped with an LED light for troubleshooting. The diagnostic codes are listed below in table 4.
RED LED
Flash Code
Diagnostic Codes / Status of Furnace
OffNo power to control or board fault detected
OnBoard fault detected,
Heartbeat
1
Control powered − displayed during all modes of operation if no errors are detected
1Reverse Line Voltage Polarity
2Improper Earth Ground
3Burner failed to light, or lost flame during heat demand
4Low Flame Signal − check flame sensor
5Watchguard − burner failed to light, exceeded maximum number of retries or recycles.
6Not Used
7
Primary or Secondary Limit Open or Watchguard Mode − Limit Switch Open longer than 3 minutes
8Rollout Switch Open
9Pressure Switch failed to close or opened during heat demand
10Watchguard − Pressure Switch opened 5 times during one heat demand
11Pressure Switch stuck closed prior to activation of combustion air inducer
12Flame Sensed without gas valve energized
13Low Line Voltage
Notes
Note 1A "Heartbeat" is indicated by a "Slow Flash" − 1 sec on 1 sec off, repeating
Note
Error codes are indicated by a "Rapid Flash" − the LED flashes X times at 1/2 sec on 1/2 sec
off, remains off for 3 sec, then repeats
Note
Last 10 error codes are stored in memory including when power is shut off to the unit. − To recall,
press and release button, most recent will be displayed first, LED off for 3 sec, then next error
code is displayed, etc. To clear error codes, depress and hold button longer than 5 seconds.
Page 9
Page 9
FIGURE 3
INTEGRATED CONTROL
(Automatic Hot Surface Ignition System)
BLOWER OFF DELAY
RED LED
RECALL BUTTON
Electronic Ignition
On a call for heat the integrated control monitors the combustion air inducer pressure switch. The control board will
not begin the heating cycle if the pressure switch is closed
(by−passed). Once the pressure switch is determined to be
open, the combustion air inducer is energized. When the
differential in the pressure switch is great enough, the pressure switch closes and a 15−second pre−purge begins. If
the pressure switch is not proven within 2−1/2 minutes, the
integrated control goes into Watchguard−Pressure Switch
mode for a 5−minute re−set period.
After the 15−second pre−purge period, the ignitor warms up
for 20 seconds during which the gas valve opens at 19 seconds for a 4−second trial for ignition. The ignitor remains
energized for the first 3 seconds during the 4 second trial. If
ignition is not proved during the 4−second period, the integrated control will try four more times with an inter purge
and warm−up time between trials of 35 seconds. After a to-
tal of five trials for ignition (including the initial trial), the integrated control goes into Watchguard−Flame Failure mode.
After a 60−minute reset period, the integrated control will
begin the ignition sequence again.
Fan Time Control
Heating Fan On Time
The fan on time of 30 seconds is not adjustable.
Heating Fan Off Time
Fan off time (time that the blower operates after the heat
demand has been satisfied) can be adjusted by moving the
jumper to a different setting. The unit is shipped with a factory fan off setting of 90 seconds. For customized comfort,
monitor the supply air temperature once the heat demand
is satisfied. Note the supply air temperature at the instant
the blower is de−energized.
Adjust the fan−off delay to achieve a supply air temperature
between 90° − 110° at the instant the blower is de−energized. (Longer delay times allow for lower air temperature,
shorter delay times allow for higher air temperature). See
figure 4.
Cooling Fan On Time
The fan on time is 2 seconds and is not adjustable.
Cooling Fan Off Time
The control has a 45 second fan off delay after cooling demand has been met. This delay is factory set and not adjustable.
HEAT FAN-OFF TIME IN SECONDS
To adjust fan−off timing, reposition jumper across pins to
achieve desired setting.
NO JUMPER
FIGURE 4
60
90
120
180
60
90
120
180
60
90
120
180
60
90
120
180
60 Second
off Time
90 Second
off Time
120 Second
off Time
180 Second
off Time
Page 10
Page 10
FIGURE 5
EL195UHE Burner Box Assembly
Gas Valve
Burner Box Front
Rollout Switch(s)
Flame Sensor
Ignitor
Burner Assembly
B−Heating Components
Combustion air inducer (B6), primary limit control (S10), ignitor, burners, flame rollout switch (S47), gas valve (GV1),
combustion air pressure switch (S18), and heat exchangers
are located in the heating compartment. The heating
compartment can be accessed by removing the outer access panel.
1. Flame Rollout Switches (Figure 5)
Flame rollout switches S47 are SPST N.C. high temperature
limits located on the left and right of the front buner box plate.
S47 is wired to the burner ignition control A92. When either of the switches sense flame rollout (indicating a
blockage in the combustion passages), the flame rollout
switch trips, and the ignition control immediately closes
the gas valve . Switch S47 in all EL195UHE units is factory
preset to open at 210_F +
12_F (99_C + 6.7_C) on a temperature rise. All flame rollout switches are manual reset. See
table 4 flash code 8 for troubleshooting.
2. Heat Exchanger (Figure 6)
EL195UHE units use an aluminized steel primary and
stainless steel secondary heat exchanger assembly.
Heat is transferred to the air stream from all surfaces of
the heat exchanger. The shape of the heat exchanger ensures maximum efficiency.
The combustion air inducer pulls fresh air through the burner box. This air is mixed with gas in the burners. The gas /
air mixture is then burned at the entrance of each clamshe ll. Combustion gases are then pulled through the primary
and secondary heat exchangers and exhausted out the exhaust vent pipe.
3. Primary Limit Control (Figure 6)
Primary limit (S10) used on EL195UHE units is located in the
heating vestibule panel. When excess heat is sensed in the
heat exchanger, the limit will open. Once the limit opens, the
furnace control energizes the supply air blower and de−energizes the gas valve. The limit automatically resets when
unit temperature returns to normal. The switch is factory
set and cannot be adjusted. For limit replacement remove
wires from limit terminals, remove mounting screws, rotate
limit switch 90 degrees and slowly remove from the vestibule panel. Install replacement limit with sam e care. See
table 4 flash code 7 for troubleshooting if limit switch
opens during operation.
Page 11
Page 11
FIGURE 6
Primary Limit Location and Heat Exchanger
Install limit face down
4. Gas Valve (Figure 7)
The EL195UHE uses an internally redundant valve to assure
safety shut-off. If the gas valve must be replaced, the same
type valve must be used.
24VAC terminals and gas control switch are located on
top of the valve. All terminals on the gas valve are connected to wires from the ignition control. 24V applied to the
terminals opens the valve.
Inlet and outlet pressure taps are located on the valve. A
manifold adjustment screw is also located on the valve. An
LP/Propane changeover kit is available.
FIGURE 7
GAS VALVE SHOWN IN ON POSITION
MANIFOLD
PRESSURE
OUTLET
PORT
INLET
PRESSURE
PORT
MANIFOLD PRESSURE
ADJUSTMENT SCREW
(under barbed fitting)
5. Flame Sensor (Figure 5)
A flame sensor is located on the left side of the burner support. The sensor is mounted on the front burner box plate
and the tip protrudes into the flame envelope of the left−
most burner. The sensor can be removed for service (use
steel wool only to clean) without removing any part of the
burners. During operation, flame is sensed by current
passed through the flame and sensing electrode. The ignition control allows the gas valve to remain open as long as
flame signal is sensed.
NOTE − The EL195UHE is polarity sensitive. Make sure
that the furnace is wired correctly and is properly grounded.
A microamp DC meter is needed to check the flame signal
on the integrated control.
Flame (microamp) signal is an electrical current which passes
from the integrated control to the sensor during unit operation.
Current passes from the sensor through the flame to ground to
complete a safety circuit.
To Measure Flame Signal − Integrated Control:
Use a digital readout meter capable of reading DC microamps. Se e fi gure 8 for flame signal check.
1 − Set the meter to the DC amps scale.
2 − Turn off supply voltage to control.
3 − Remove sensor wire from integrated control.
4 − Connect (−) lead to flame sensor wire.
5 − Connect (+) lead to Terminal FS on integrated control.
6 − Turn supply voltage on and close thermostat contacts to
cycle system.
7 − When main burners are in operation for two minutes, take
reading.
6. Ignitor (Figure 5)
EL195UHE units use a nitride ignitor made from a proprietary ceramic material. To check ignitor, measure its resistance and voltage. A value of 39 to 70 ohms indicates a
good ignitor. Voltage to the ignitor should be 102 − 132VAC.
See figure 9 for resistance and voltage checks.
Page 12
Page 12
FIGURE 8
Measuring Flame Signal
Flame Signal In Microamps
NormalLowDrop Out
1.5
0.5 − 1.4
0.4
Set Dial to DC MicroAmps
(+)
Multi−Meter
(+)
(+) To Control
Sensor Terminal
(−) T
o Flame
Terminal
Flame Sensor
Terminal
Flame Sensor
Wire
Intergrated
Control
Remove sensor from integrated
control and connect alligator clip
(−) to flame sensor lead.
Remove sensor from integrated
control and connect alligator clip
(+) to terminal on control.
Page 13
Page 13
FIGURE 9
Test 1
Check ignitor circuit for correct resistance.
Remove 4−pin plug from control.
Check ohms reading across terminals 2 and 4.
Reading should be between 39 and 70 ohms. If
value is correct, this is the only test needed.
If the reading on the meter is not correct, (0 or
infinity) then a second test is needed.
Test 2
Check ignitor for correct resistance.
Seperate the 2−pin jack−plug near the manifold and check
resistance of ignitor at the plug. Reading should be
between 39 and 70 ohms. If the reading is correct, then
the problem is with the wiring between the jack−plug and
the control. If reading is not correct, the issue is the ignitor.
Test 3
Check ignitor for correct voltage
Insert meter probes into terminals 2 and 4 (use small
diameter probes in order not to damage plug).
Check voltage during 20 second ignitor warm up period.
Voltage should read 120 volts +
10%. If voltage reads below
these values, check for correct supply voltage to furnace.
Multi−Meter
(set to ohms)
Multi−Meter
(set to ohms)
Multi−Meter
(set to VAC)
Page 14
Page 14
7. Combustion Air Inducer (B6)
& Cold End Header Box
All EL195UHE units use a combustion air inducer to
move air through the burners and heat exchanger during
heating operation. The blower uses a shaded pole
120VAC motor. The motor operates during all heating operation and is controlled by integrated control A92. Blower
operates continuously while there is a call for heat. The integrated control will not proceed with the ignition sequence
until combustion air inducer operation is sensed by the proving switches.
The combustion air inducer is installed on the cold end
header box. The cold end header box is a single piece
made of hard plastic. The box has an internal channel
where the combustion air inducer creates negative pressure at unit start up. The channel contains an orifice used
to regulate flow created by the combustion air inducer.
The box has pressure taps for the combustion air inducer
pressure switch hoses. The pressure switch measures
the pressure across the combustion air inducer orifice or
difference in the channel and the box. If replacement is
necessary the gaskets used to seal the box to the
vestibule panel and the combustion air inducer to the
box, must also be replaced.
TABLE 5
EL195UHE Unit
Combustion Air Inducer
Orifice Size
−0450.618"
−0700.810"
−0900.973"
−1101.040"
−1351.235"
8. Combustion Air Pressure Switch
(Figure 10)
EL195UHE series units are equipped with a differential
pressure switch located on the cold end header box. The
switch monitors across the combustion air inducer orifice to insure proper flow through the heat exchanger.
The switch is a SPST N.O. pressure switch electrically connected to the integrated control. The purpose of the switch is
to prevent burner operation if the combustion air inducer is not
moving enough air for proper combustion.
FIGURE 10
Pressure Switch
On start-up, the switch monitors whether the combustion air
inducer is operating. It closes a circuit to the integrated
control when the difference in pressure across the combustion air inducer orifice exceeds a non−adjustable factory
setting. If the switch does not successfully sense the required differential, the switch cannot close and the furnace cannot operate. If the flue or air inlet become obstructed during operation, the switch senses a loss of
pressure differential and opens the circuit to the integrated
control. If the condensate line is blocked, water will back up
into the header box and reduce the pressure differential
across the switch. The pressure switch opens if the differential drops below the set point. See table 6.
Checks of pressure differential can aid in troubleshooting.
When measuring the pressure differential, readings should be
taken at the pressure switch. See figure 11and table 7. Lack of
differential usually indicates problems in the intake or exhaust
piping, but may indicate problems in the heat exchanger,
condensing coil, header boxes, combustion inducer or
other components.
TABLE 6
Unit
Altitude ft.
0 − 45004501 − 75007501 − 10000
Set Point w.c. Set Point w.c Set Point w.c.
−045−0.65−0.65−0.60
−070−0.90−0.85−0.65
−090−0.90−0.80−0.65
−110−0.90−0.85−0.65
−135−0.90−0.80−0.65
*Set point is factory set and non−adjustable
Page 15
Page 15
To Cold End Header Box
Field Provided Tubing
To Pressure Switch
To Cold End Header Box
FIGURE 11
1 − Remove thermostat demand and allow unit to
cycle off.
2 − Install a tee in the negative (−) line (red tubing) and a
tee in the positive (+) line (black tubing) running from
the pressure switch to the cold end header box.
3 − Install a manometer with hose from the negative (−)
side of the manometer to the tee installed in the
negative (−) line and with hose from the positive (+)
side of the manometer to the tee in the positive (+)
line.
NOTE − Both sides of the cold end header box are negative. However the (+) port reads less negative pressure
than the (−) port.
4 − Operate unit and observe manometer reading.
Readings will change as heat exchanger warms.
a. Take one reading immediately after start-up.
b. Take a second reading after unit has reached
steady state (approximately 5 minutes). This will be
the pressure differential.
The pressure differential should be greater
than those listed in table 6.
5 − Remove thermostat demand and allow to cycle off.
6 − Remove manometer and tee’s. Reinstall combustion
air sensing hoses to the pressure switch.
Measuring Pressure Differential
Black Tubing
(positive +)
Red Tubing
(negative −)
+"
High
−"
Low
Page 16
Page 16
TABLE 7
Pressure Switch Troubleshooting Guide
ProblemCorrective Action
Pressure switch stuck closed
Check that the pressure switch is open without the combustion air inducer operating. Replace if defective.
Pressure switch does not close due to
obstruction in vent pipe.
Check for restricted vent. Remove all blockage.
Check for proper vent sizing. See table 11.
Pressure switch does not close due to
incorrect routing of the pressure
switch tubing.
Check that the pressure switch tubing is correctly routed. Correctly route pressure
witch line.
Pressure switch does not close due to
obstructions in the pressure switch
line.
Remove any obstructions from the the pressure switch line and/or taps
Pressure switch tubing damaged.Check pressure switch tubing for leaks. Replace damaged tubing if necessary.
Condensate in pressure switch tubing. Check pressure switch tubing for condensate. Remove condensate from tubing.
Pressure switch does not close due to
a low differential pressure across the
pressure switch.
Check the differential pressure across the pressure switch.
Check for restricted inlet vent. Remove all blockage.
Check for proper vent sizing and run length. See table11.
Wrong pressure switch installed in the
unit, or pressure switch is out of cal-
ibration
Check that the correct pressure switch is installed in the unit. Replace pressure
switch if necessary.
Miswiring of furnace or improper con-
nections at pressure switch.
Check for correct wiring and loose connections. Correct wiring and/or replace any
loose connections.
Pressure switch failure.
If all the above modes of failure have been checked, the pressure switch may have
failed. Replace pressure switch and determine if unit will operate.
Damaged condensate trap.Check trap for any cracks or damage and replace if necessary.
Cold end header box does not drain
properly.
Check that the furnace is set properly with a slight tilt (0 − 1/2") towards the front
if necessary. See furnace installation instruction.
Air leakage around the combustion air
inducer gasket.
Check gasket and replace if necessary.
Air leakage around the cold end head-
er box gasket.
Check gasket and replace if necessary.
Damaged cold end header box tubing. Check tubing and replace if necessary.
DEMAND
CAI
GAS VALVE
15
ON
OFF
38
IGNITOR
341
Pre −PurgeIgnitor Warm−up
Trial for
Ignition
Post
Purge
5 SEC80
*Blower on time will be 30 seconds after flame is sensed. Blower off time will depend on OFF TIME" Setting.
INDOOR BLOWER
ЙЙЙЙЙЙЙЙЙ
Blower On"*
Delay
ELECTRONIC IGNITION
FIGURE 12
Page 17
Page 17
C− Blower Compartment
IMPORTANT
Each blower is statically and dynamically balanced as an assembly before installation in the
unit.
ML195UHE units are equipped with a constant torque ECM
motor. It has a DC motor coupled to an electronic control
module both contained in the same motor housing. The motor is programmed to provide constant torque at each of the
five selectable speed taps. Each tap requires 24 volts to energize.
Input Voltage Requirements
The circuit is designed to be operated with AC voltage. To
enable a tap requires 12 to 33VAC. Expected current draw
will be less than 20mA.
Troubleshooting
Troubleshooting the motor is an easy process. Follow
steps below.
1− Shut off power to unit.
2− Remove input plugs P48 and P49 from motor. See
figure 16 for troubleshooting procedure.
If correct voltage is present in tests 1 and 2 and motor is not
operating properly, replace motor. The motor is not field repairable.
If replacing the indoor blower motor or blower wheel is necessary, placement is critical. The blower wheel must be centered in the blower housing as shown in figure 13. When replacing the indoor blower motor the set screw must be
aligned and tightened with the motor shaft as shown in figure
14.
9. Secondary Limit Controls
The secondary limit is located in the blower compartment on
the back side of the blower housing. See figure 15. When excess heat is sensed in the blower compartment, the limit will
open. If the limit is open, the furnace control energizes the supply air blower and closes the gas valve. The limit automatically
resets when unit temperature returns to normal. The secondary limit cannot be adjusted.
FIGURE 13
Center Blower Wheel
in Blower Housing
BLOWER WHEEL REPLACEMENT
FIGURE 14
Set Screw
Housing Hub
ALIGN AND TIGHTEN SET SCREW WITH
FLAT SIDE OF MOTOR SHAFT
Motor
Shaft
FIGURE 15
SECONDARY LIMIT CONTROL
Secondary Limits
Page 18
Page 18
1
2
3
4
5
C
L
G
N
Multi−Meter
(set to VAC)
P48
P49
12012
0
Turn on power to unit. Check for 120 volts across terminals
L" and N" on input plug P48. If voltage is present continue
to test 2. If voltage is not present problem may be may be upstream of plug P48 and proceed to test 3.
1
2
3
4
5
C
L
G
N
Multi−Meter
(set to VAC)
P48
P49
24
Switch thermostat to CONTINUOUS FAN MODE. Check for
24 volts across terminal C" on input plug P48and speed tap
used for continuous fan. (1, 2, 3, 4 or 5) on input plug P49. If
24 volts is not present problem may be up stream of plug P49.
Proceed to test 4.
Multi−Meter
(set to VAC)
12012
0
24
Multi−Meter
(set to VAC)
Check for 24 volts across terminals 24 COM" and FAN" terminals on the integrated control. If voltage is present, problem is with the harness. If voltage is not present problem
may be may be with the integrated control
Check for 120 volts across terminals CIRC" and Neutrals"
on the integrated control. If voltage is present, problem is
with the harness. If voltage is not present problem may be
may be with the integrated control.
Test 1
Test 2
Test 3 (if necessary)
Test 4 (if necessary)
FIGURE 16
Page 19
Page 19
II−PLACEMENT AND INSTALLATION
Pipe & Fittings Specifications
All pipe, fittings, primer and solvent cement must conform
with American National Standard Institute and the American Society for Testing and Materials (ANSI/ASTM) standards. The solvent shall be free flowing and contain no
lumps, undissolved particles or any foreign matter that adversely affects the joint strength or chemical resistance of
the cement. The cement shall show no gelation, stratification, or separation that cannot be removed by stirring. Refer to the table 8 below for approved piping and fitting materials.
CAUTION
Solvent cements for plastic pipe are flammable liquids and should be kept away from all sources of
ignition. Do not use excessive amounts of solvent
cement when making joints. Good ventilation should
be maintained to reduce fire hazard and to minimize
breathing of solvent vapors. Avoid contact of cement
with skin and eyes.
PVC/CPVC/ABS All Purpose Cement For
Fittings & Pipe of the same material
D2564, D2235, F493
ABS to PVC or CPVC Transition Solvent
Cement
D3138
CANADA PIPE & FITTING & SOLVENT
CEMENT
MARKING
PVC & CPVC Pipe and Fittings
ULCS636
PVC & CPVC Solvent Cement
ABS to PVC or CPVC Transition Cement
IMPORTANT
EL195UHE exhaust and intake connections are
made of PVC. Use PVC primer and solvent cement
when using PVC vent pipe. When using ABS vent
pipe, use transitional solvent cement to make connections to the PVC fittings in the unit.
Use PVC primer and solvent cement or ABS solvent cement
meeting ASTM specifications, refer to Table 8. As an alternate, use all purpose cement, to bond ABS, PVC, or CPVC
pipe when using fittings and pipe made of the same materials. Use transition solvent cement when bonding ABS to either PVC or CPVC.
Low temperature solvent cement is recommended during
cooler weather. Metal or plastic strapping may be used for
vent pipe hangers. Uniformly apply a liberal coat of PVC
primer for PVC or use a clean dry cloth for ABS to clean inside socket surface of fitting and male end of pipe to depth
of fitting socket.
Canadian Applications Only − Pipe, fittings, primer
and solvent cement used to vent (exhaust) this appliance must be certified to ULC S636 and supplied by a
single manufacturer as part of an approved vent (exhaust) system. In addition, the first three feet of vent
pipe from the furnace flue collar must be accessible for
inspection.
Page 20
Page 20
TABLE 9
OUTDOOR TERMINATION KITS USAGE
EL195
UNIT
VENT
PIPE
DIA.
(in.)
STANDARDCONCENTRIC
Outdoor
Exhaust
Accelerator
(Dia. X
Length)
Outdoor
Exhaust
Accelerator
(Dia. X
Length)
2" Wall Plate
Kit
3" Wall Plate
Kit
2" Wall
Ring Kit
FlushMount
Kit
1−1/2"
Concentric
Kit
2"
Concentric
Kit
3"
Concentric
Kit
1−1/2" X 12"2" X 12"
22G44
or 30G28
44J40
or 81J20
15F7451W11**
71M80
or
44W92
69M29
or
44W92
60L46
or 44W93
045
2YESYESYES*YESYESYES
2−1/2YESYESYES*YESYESYES
3YESYESYES*YESYESYES
070
2YESYESYES*YESYESYES
2−1/2YESYESYES*YESYESYES
3YESYESYES*YESYESYES
090
2YESYESYESYESYESYES
2−1/2YESYESYESYESYESYES
3YESYESYESYESYESYES
110
2YESYESYESYESYESYES
2−1/2YESYESYESYESYESYES
3YESYESYESYESYESYES
1353YESYESYESYES
*Requires field−provided and installed 1−1/2" exhaust accelerator.
** Kit 51W11 is provided with a 1−1/2" accelerator which must be used for all EL195UHXE−045, −070 and −090 installations.
Termination kits 44W92, 44W93, 30G28 and 81J20 approved for use in Canadian installations to meet CSAB149.
The 44W92 concentric kit is provided with a 1−1/2" accelerator which must be installed on the exhaust outlet when this kit is used with the EL195UHXE04536B and
EL195UHXE070P36B furnaces.
NOTE − Standard terminations include all approved non−concentric terminations.
Joint Cementing Procedure
All cementing of joints should be done according to the
specifications outlined in ASTM D 2855.
DANGER
DANGER OF EXPLOSION!
Fumes from PVC glue may ignite during system
check. Allow fumes to dissipate for at least 5 minutes
before placing unit into operation.
1 − Measure and cut vent pipe to desired length.
2 − Debur and chamfer end of pipe, removing any ridges
or rough edges. If end is not chamfered, edge of pipe
may remove cement from fitting socket and result in a
leaking joint.
NOTE − Check the inside of vent pipe thoroughly for
any obstruction that may alter furnace operation.
3 − Clean and dry surfaces to be joined.
4 − Test fit joint and mark depth of fitting on outside of pipe.
5 − Uniformly apply a liberal coat of PVC primer for PVC or
use a clean dry cloth for ABS to clean inside socket
surface of fitting and male end of pipe to depth of fitting
socket.
NOTE − Time is critical at this stage. Do not allow primer to dry before applying cement.
6 − Promptly apply solvent cement to end of pipe and in-
side socket surface of fitting. Cement should be applied lightly but uniformly to inside of socket. Take
care to keep excess cement out of socket. Apply second coat to end of pipe.
7 − Immediately after applying last coat of cement to pipe,
and while both inside socket surface and end of pipe
are wet with cement, forcefully insert end of pipe into
socket until it bottoms out. Turn PVC pipe 1/4 turn during assembly (but not after pipe is fully inserted) to distribute cement evenly. DO NOT turn ABS or cellular
core pipe.
NOTE − Assembly should be completed within 20 seconds after last application of cement. Hammer blows
should not be used when inserting pipe.
Page 21
Page 21
8 − After assembly, wipe excess cement from pipe at end
of fitting socket. A properly made joint will show a
bead around its entire perimeter. Any gaps may indicate an improper assembly due to insufficient solvent.
9 − Handle joints carefully until completely set.
Venting Practices
FIGURE 17
* See table 8 for allowable pipe.
Piping Suspension Guidelines
NOTE − Isolate piping at the point where it exits the outside wall or
roof in order to prevent transmission of vibration to the structure.
SCHEDULE 40
PVC − 5’
all other pipe* − 3’
Wall
insideoutside
24" maximum
3/4" minimum
Wall Thickness Guidelines
insulation
(if required)
10. In areas where piping penetrates joists or interior
walls, hole must be large enough to allow clearance on
all sides of pipe through center of hole using a hanger.
11. When furnace is installed in a residence where unit is
shut down for an extended period of time, such as a
vacation home, make provisions for draining condensate collection trap and lines.
CHIMNEY
OR GAS
VENT
(Check sizing
for water
heater only)
FURNACE
(Replaced
by EL195)
WATER
HEATER
OPENINGS
(To Adjacent
Room)
If an EL195UHE furnace replaces a furnace which
was commonly vented with another gas appliance,
the size of the existing vent pipe for that gas appliance must be checked. Without the heat of the
original furnace flue products, the existing vent pipe
is probably oversized for the single water heater or
other appliance. The vent should be checked for
proper draw with the remaining appliance.
FIGURE 18
REPLACING FURNACE THAT
WAS PART OF A COMMON
VENT SYSTEM
Exhaust Piping (Figures 21 and 22)
Route piping to outside of structure. Continue with installation following instructions given in piping termination section.
CAUTION
Do not discharge exhaust into an existing stack or
stack that also serves another gas appliance. If vertical discharge through an existing unused stack is required, insert PVC pipe inside the stack until the end
is even with the top or outlet end of the metal stack.
CAUTION
The exhaust vent pipe operates under positive pressure and must be completely sealed to prevent leakage of combustion products into the living space.
Page 22
Page 22
Vent Piping Guidelines
The EL195UHE can be installed as either a Non−Direct
Vent or a Direct Vent gas central furnace.
NOTE − In Non-Direct Vent installations, combustion air is
taken from indoors and flue gases are discharged outdoors.
In Direct Vent installations, combustion air is taken from outdoors and flue gases are discharged outdoors.
Intake and exhaust pipe sizing −− Size pipe according to
tables 10 and
11. Table 10 lists the minimum vent pipe
lengths permitted. Table 11 lists the maximum pipe lengths
permitted.
Regardless of the diameter of pipe used, the standard roof
and wall terminations described in section Exhaust PipingTerminations should be used. Exhaust vent termination
pipe is sized to optimize the velocity of the exhaust gas as
it exits the termination. Refer to table 14.
In some applications which permit the use of several different sizes of vent pipe, a combination vent pipe may be
used. Contact Lennox’ Application Department for assistance in sizing vent pipe in these applications.
NOTE − The exhaust collar on all models is sized to accommodate 2" Schedule 40 vent pipe. In horizontal applications, any transition to exhaust pipe larger than 2"
must be made in vertical runs of the pipe. Therefore a 2"
elbow must be added before the pipe is transitioned to
any size larger than 2". This elbow must be added to the
elbow count used to determine acceptable vent lengths.
Contact the Application Department for more information
concerning sizing of vent systems which include multiple
pipe sizes.
FIGURE 19
12" max
of straight pipe
Exhaust Pipe
12" Min.
NOTE − Exhaust pipe MUST be glued to furnace exhaust fittings.
NOTE − All horizontal runs of exhaust pipe must slope back to-
ward unit. A minimum of 1/4" (6mm) drop for each 12" (305mm)
of horizontal run is mandatory for drainage.
NOTE − Exhaust piping should be checked carefully to make
sure there are no sags or low spots.
Horizontal Application
TABLE 10
MINIMUM VENT PIPE LENGTHS
EL195UHE
MODEL
MIN. VENT LENGTH*
045, 070, 090, 110, 135
15 ft. or
5 ft. plus 2 elbows or
10 ft. plus 1 elbow
*Any approved termination may be added to the minimum length listed.
Use the following steps to correctly size vent pipe diameter.
1
2
3
4
5
6
045, 070,
090, 110
or 135 btuh
Which termination?
Standard or
Concentric?
See table 9
Intake or
exhaust
Which needs
most elbows?
How many?
2", 2 1/2"
or 3"
Desired pipe size?
Use table 11 to find
max intake or
exhaust pipe length
for all altitudes.
FIGURE 20
7
Furnace capacity?
Is the intake air
taken from a
vetilated attic or
crawl space?
NO
YES
Use table 12 to find
max pipe length for
all altitudes
(exhaust pipe only)
IMPORTANT
Do not use screens or perforated metal in exhaust or
intake terminations. Doing so will cause freeze−ups
and may block the terminations.
Page 23
Page 23
TABLE 11
Maximum Allowable Intake or Exhaust Vent Length in Feet
*Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake and Exhaust must be same pipe size.
Standard Termination at Elevation 0 − 4500 ft
Number Of
90° Elbows
Used
2" Pipe2−1/2" Pipe3" Pipe
ModelModelModel
04507009011013504507009011013504507009011 0135
181664424
n/a
1151159358
n/a
13813711 8118114
276613919110110885313313211 3113109
3715634141051058348128127108108104
4665129
n/a
100100784312312210310399
561462495957338118117989894
656411990906833113112939389
751361485856328108107888884
84631
n/a
80805823103102838379
94126757553189897787874
103621707048139392737369
Standard Termination Elevation 4500 − 10,000 ft
Number Of
90° Elbows
Used
2" Pipe2−1/2" Pipe3" Pipe
ModelModelModel
04507009011013504507009011013504507009011 0135
1816644
n/an/a
1151159358
n/a
13813711 8118114
276613911 0110885313313211311 3109
37156341051058348128127108108104
4665129100100784312312210310399
561462495957338118117989894
656411990906833113112939389
751361485856328108107888884
84631
n/a
80805823103102838379
94126757553189897787874
103621707048139392737369
Page 24
Page 24
TABLE 11 Continued
Maximum Allowable Intake or Exhaust Vent Length in Feet
*Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake and Exhaust must be same pipe size.
Concentric Termination at Elevation 0 − 4500 ft
Number Of
90° Elbows
Used
2" Pipe2−1/2" Pipe3" Pipe
ModelModelModel
045070090110135045070090110135045070090110135
173584222
n/a
1051058954
n/a
121121114114105
2685337171001008449116116109109100
3634832129595794411111110410495
4584327
n/a
90907439106106999990
553382285856934101101949485
6483317808064299696898980
7432812757559249191848475
83823
n/a
707054198686797970
93318656549148181747465
102813606044n/a7676696960
Concentric Termination Elevation 4501 − 10,000 ft
Number Of
90° Elbows
Used
2" Pipe2−1/2" Pipe3" Pipe
ModelModelModel
045070090110135045070090110135045070090110135
1735842
n/an/a
1051058954
n/a
121121114114105
26853371001008449116116109109100
36348329595794411111110410495
458432790907439106106999990
553382285856934101101949485
6483317808064299696898980
7432812757559249191848475
83823
n/a
707054198686797970
93318656549148181747465
102813606044n/a7676696960
Page 25
Page 25
TABLE 12
Maximum Allowable Exhaust Vent Lengths With Furnace Installed in a Closet or Basement Using Ventilated
Attic or Crawl Space For Intake Air in Feet
Standard Termination at Elevation 0 − 4500 ft
Number Of
90° Elbows
Used
2" Pipe2−1/2" Pipe3" Pipe
ModelModelModel
04507009011013504507009011013504507009011 0135
171563414
n/a
1001007843
n/a
118117989894
266512999595733811311 2939389
3614624490906833108107888884
4564119
n/a
85856328103102838379
5513614808058239897787874
646319857563189392737369
741264707048138887686864
83621
n/a
65654388382636359
9311660603837877585854
102611555533n/a7372535349
Standard Termination Elevation 4500 − 10,000 ft
Number Of
90° Elbows
Used
2" Pipe2−1/2" Pipe3" Pipe
ModelModelModel
04507009011013504507009011013504507009011 0135
1715634
n/an/a
1001007843
n/a
118117989894
266512995957338113112939389
361462490906833118107888884
456411985856328113102838379
5513614808058239897787874
646319858553189392737369
741264707048139887686864
83621
n/a
65654389382636359
9311660603837877585854
102611555533n/a7372535349
Page 26
Page 26
FIGURE 21
TYPICAL EXHAUST AND INTAKE PIPE CONNECTIONS IN UPFLOW DIRECT OR
NON−DIRECT VENT APPLICATIONS
TRANSITION
2”
2”
2”
3”
2”
2”
or
DO NOT transition
from smaller to larger
pipe in horizontal runs
of exhaust pipe.
EXHAUST
*2”
* When transitioning up in pipe size, use the shortest length of 2” PVC pipe possible.
INTAKE
2”
TRANSITION
3”
*2”
EXHAUSTINTAKE
FIGURE 22
TRANSITION
SIDE VIEW
2”
2”
2”
2”
or
TYPICAL EXHAUST AND INTAKE PIPE CONNECTIONS IN HORIZONTAL DIRECT OR NON−DIRECT VENT
APPLICATIONS
(RIGHT HAND DISCHARGE SHOWN)
3”
2”
45°
MAX
45°
MAX
DO NOT transition
from smaller to larger
pipe in horizontal runs
of exhaust pipe.
EXHAUST
12" max.
*2"
* When transitioning up in pipe size, use the shortest length of 2” PVC pipe possible.
2”
2”
2”
INTAKE
2”
or
2”
*2”
EXHAUST
INTAKE
*2"
3”
*2"
*2"
Page 27
Page 27
Intake Piping
The EL195UHE furnace may be installed in either direct
vent or non−direct vent applications. In non−direct vent
applications, when intake air will be drawn into the furnace
from the surrounding space, the indoor air quality must be
considered and guidelines listed in Combustion, Dilution
and Ventilation Air section must be followed.
Follow the next two steps when installing the unit in DirectVent applications, where combustion air is taken from
outdoors and flue gases are discharged outdoors. The
provided air intake screen must not be used in direct
vent applications (outdoors).
1 − Use transition solvent cement or a sheet metal screw
to secure the intake pipe to the inlet air connector.
2 − Route piping to outside of structure. Continue with
installation following instructions given in general
guidelines for piping terminations and intake and exhaust piping terminations for direct vent sections. Refer to table
11 for pipe sizes.
Follow the next two steps when installing the unit in Non-Direct Vent applications where combustion air is taken
from indoors and flue gases are discharged outdoors.
1 − Use field−provided materials and the factory−provided
air intake screen to route the intake piping as shown in
figure 23 or 24. Maintain a minimum clearance of 3"
(76mm) around the air intake opening. The air intake
opening (with the protective screen) should always be
directed forward or to either side in the upflow position,
and either straight out or downward in the horizontal
position.
The air intake piping must not terminate too close
to the flooring or a platform. Ensure that the intake
air inlet will not be obstructed by loose insulation
or other items that may clog the debris screen.
2 − If intake air is drawn from a ventilated attic (figure 25)
or ventilated crawlspace (figure 26) the exhaust vent
length must not exceed those listed in table 12. If 3" diameter pipe is used, reduce to 2" diameter pipe at the
termination point to accommodate the debris screen.
3 − Use a sheet metal screw to secure the intake pipe to
the connector, if desired.
FIGURE 23
TYPICAL AIR INTAKE PIPE CONNECTIONS
UPFLOW NON−DIRECT
VENT APPLICATIONS
INTAKE
DEBRIS
SCREEN
(Provided)
NOTE − Debris screen and elbow may be rotated, so that
screen may be positioned to face forward or to either side.
FIGURE 24
TYPICAL AIR INTAKE PIPE CONNECTIONS
HORIZONTAL NON−DIRECT VENT APPLICATIONS
(Horizontal Right−Hand Air Discharge Application Shown)
INTAKE
DEBRIS
SCREEN
(Provided)
OR
NOTE − Debris screen may be positioned straight out
(preferred) or with an elbow rotated to face down.
coupling
PVC pipe
Page 28
Page 28
CAUTION
If this unit is being installed in an application with
combustion air coming in from a space serviced by
an exhaust fan, power exhaust fan, or other device
which may create a negative pressure in the space,
take care when sizing the inlet air opening. The inlet air opening must be sized to accommodate the
maximum volume of exhausted air as well as the
maximum volume of combustion air required for
all gas appliances serviced by this space.
FIGURE 25
EQUIPMENT IN CONFINED SPACE
(Inlet Air from Ventilated Attic and Outlet Air to Outside)
NOTE−The inlet and outlet air openings shall each have a free area
of at least one square inch per 4,000 Btu (645mm
2
per 1.17kW) per
hour of the total input rating of all equipment in the enclosure.
Ventilation Louvers
Inlet Air
(Minimum
12 in.(305mm) Above
attic floor)
Roof Terminated
Exhaust Pipe
Furnace
*Intake Debris
Screen
(Provided)
* See table 12 for maximum vent lengths
FIGURE 26
NOTE−The inlet and outlet air openings shall each have a free area
of at least one square inch per 4,000 Btu (645mm
2
per 1.17kW) per
hour of the total input rating of all equipment in the enclosure.
EQUIPMENT IN CONFINED SPACE
(Inlet Air from Ventilated Crawlspace and Outlet Air to Outside)
Roof Terminated
Exhaust Pipe
Furnace
Ventilation
Louvers
(Crawl space)
*Intake Debris Screen Provided)
Inlet Air
(Minimum
12 in.(305mm)
Above crawl
space floor)
Coupling or
3 in. to 2 in.
Transition
(Field Provided)
* See table 12 for maximum vent lengths
General Guidelines for Vent Terminations
In Non-Direct Vent applications, combustion air is taken
from indoors and the flue gases are discharged to the outdoors. The EL195UHE is then classified as a non-direct
vent, Category IV gas furnace.
In Direct Vent applications, combustion air is taken from
outdoors and the flue gases are discharged to the outdoors. The EL195UHE is then classified as a direct vent,
Category IV gas furnace.
In both Non-Direct Vent and Direct Vent applications, the
vent termination is limited by local building codes. In the
absence of local codes, refer to the current National Fuel
Gas Code ANSI Z223−1/NFPA 54 in U.S.A., and current
CSA−B149 Natural Gas and Propane Installation Codes in
Canada for details.
Position termination according to location given in figure 27
or 28. In addition, position termination so it is free from any
obstructions and 12" above the average snow accumulation.
At vent termination, care must be taken to maintain
protective coatings over building materials (prolonged
exposure to exhaust condensate can destroy protective
coatings). It is recommended that the exhaust outlet not be
located within 6 feet (1.8m) of a condensing unit because
the condensate can damage the painted coating.
NOTE − See table 13 for maximum allowed exhaust pipe
length without insulation in unconditioned space during
winter design temperatures below 32°F (0°C). If required
exhaust pipe should be insulated with 1/2" (13mm) Armaflex or equivalent. In extreme cold climate areas, 3/4"
(19mm) Armaflex or equivalent may be necessary. Insulation on outside runs of exhaust pipe must be painted or
wrapped to protect insulation from deterioration. Exhaust
pipe insulation may not be necessary in some specific applications.
IMPORTANT
Do not use screens or perforated metal in exhaust
terminations. Doing so will cause freeze−ups and
may block the terminations.
IMPORTANT
For Canadian Installations Only:
In accordance to CSA International B149 installation
codes, the minimum allowed distance between the
combustion air intake inlet and the exhaust outlet of
other appliances shall not be less than 12 inches
(305mm).
Page 29
Page 29
TABLE 13
Maximum Allowable Exhaust Vent Pipe Length Without Insulation In Unconditioned Space For
Winter Design Temperatures Single − Stage High Efficiency Furnace
Winter Design
Temperatures
1
°F (°C)
Vent Pipe
Diameter
Unit Input Size
045070090110135
32 to 21
(
0 to −6)
2 in.26444424N/A
2−1/2 in.18325058N/A
3 in.1426385560
20 to 1
(−7 to −17)
2 in16284024N/A
2−1/2 in.12203044N/A
3 in.916263240
0 to −20
(−18 to −29)
2 in.10203024N/A
2−1/2 in.8142032N/A
3 in.410162630
1Refer to 99% Minimum Design Temperature table provided in the current edition of the ASHRAE Fundamentals Handbook.
NOTE − Maximum unisulated vent lengths listed cannot exceed the maximum allowable intake or exhaust vent length listed in table 11.
Page 30
Page 30
FIGURE 27
VENT TERMINATION CLEARANCES
FOR NON−DIRECT VENT INSTALLATIONS IN THE USA AND CANADA
K
D
E
L
B
C
F
G
A
B
J
A
M
I
H
INSIDE CORNER
DETAIL
VENT TERMINAL
AIR SUPPLY INLET
AREA WHERE TERMINAL
IS NOT PERMITTED
Fixed
Closed
Operable
B
Fixed
Closed
Operable
B
B
A =
B =
C =
D =
E =
F =
G =
H =
I =
J =
K =
L =
M =
US Installations
1
Canadian Installations
2
12 inches (305mm) or 12 in. (305mm)
above average snow accumulation.
12 inches (305mm) or 12 in. (305mm)
above average snow accumulation.
Clearance above grade, veranda,
porch, deck or balcony
Clearance to window or
door that may be opened
4 feet (1.2 m) below or to side of opening;
1 foot (30cm) above opening
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
Clearance to permanently
closed window
Vertical clearance to ventilated soffit
located above the terminal within a
horizontal distance of 2 feet (610 mm)
from the center line of the terminal
Clearance to unventilated soffit
Clearance to outside corner
Clearance to inside corner
Clearance to each side of center line ex-
tended above meter / regulator assembly
Clearance to service regulator
vent outlet
Clearance to non−mechanical air
supply inlet to building or the com-
bustion air inlet to any other ap-
pliance
Clearance to mechanical air sup-
ply inlet
Clearance above paved sidewalk or
paved driveway located on public property
Clearance under veranda, porch, deck or balcony
* 12"
* Equal to or greater than soffit depth.
*
* 3 feet (.9m)
* 12"
3 feet (.9m) within a height 15 feet (4.5m)
above the meter / regulator assembly
3 feet (.9m)
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
3 feet (.9m) above if within 10 feet
(3m) horizontally
6 feet (1.8m)
7 feet (2.1m)
12 inches (305mm)
1
In accordance with the current ANSI Z223.1/NFPA 54 Natural Fuel Gas Code
2
In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code
A vent shall not terminate directly above a sidewalk or paved driveway that is
located between two single family dwellings and serves both dwellings.
Permitted only if veranda, porch, deck or balcony is fully open
on a minimum of two sides beneath the floor. Lennox recommends
avoiding this location if possible.
4 feet (1.2 m) below or to side of opening;
1 foot (30 cm) above opening
7 feet (2.1m)
* Equal to or greater than soffit depth.
* Equal to or greater than soffit depth.
* Equal to or greater than soffit depth.
* No minimum to outside corner* No minimum to outside corner
3 feet (.9m) within a height 15 feet (4.5m)
above the meter / regulator assembly
*12 inches (305mm)
**
*For clearances not specified in ANSI Z223.1/NFPA 54 or CSA
B149.1, clearance will be in accordance with local installation
codes and the requirements of the gas supplier and these installation instructions."
Page 31
Page 31
FIGURE 28
VENT TERMINATION CLEARANCES
FOR DIRECT VENT INSTALLATIONS IN THE USA AND CANADA
K
D
E
L
B
C
F
G
A
B
J
A
M
I
H
INSIDE CORNER
DETAIL
VENT TERMINAL
AIR SUPPLY INLET
AREA WHERE TERMINAL
IS NOT PERMITTED
Fixed
Closed
Operable
B
Fixed
Closed
Operable
B
B
A =
B =
C =
D =
E =
F =
G =
H =
I =
J =
K =
L =
M =
US Installations
1
Canadian Installations
2
12 inches (305mm) or 12 in. (305mm)
above average snow accumulation.
12 inches (305mm) or 12 in. (305mm)
above average snow accumulation.
Clearance above grade, veranda,
porch, deck or balcony
Clearance to window or
door that may be opened
6 inches (152mm) for appliances <10,000
Btuh (3kw), 9 inches (228mm) for ap-
pliances > 10,000 Btuh (3kw) and <50,000
Btuh (15 kw), 12 inches (305mm) for ap-
pliances > 50,000 Btuh (15kw)
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
Clearance to permanently
closed window
Vertical clearance to ventilated soffit
located above the terminal within a
horizontal distance of 2 feet (610mm)
from the center line of the terminal
Clearance to unventilated soffit
Clearance to outside corner
Clearance to inside corner
Clearance to each side of center line ex-
tended above meter / regulator assembly
Clearance to service regulator
vent outlet
Clearance to non−mechanical air
supply inlet to building or the com-
bustion air inlet to any other ap-
pliance
Clearance to mechanical air sup-
ply inlet
Clearance above paved sidewalk or
paved driveway located on public property
Clearance under veranda, porch, deck or balcony
* 12"
*
*
* 7 feet (2.1m)
3 feet (.9m) within a height 15 feet (4.5m)
above the meter / regulator assembly
3 feet (.9m)
6 inches (152mm) for appliances <10,000
Btuh (3kw), 9 inches (228mm) for ap-
pliances > 10,000 Btuh (3kw) and <50,000
Btuh (15 kw), 12 inches (305mm) for ap-
pliances > 50,000 Btuh (15kw)
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
3 feet (.9m) above if within 10 feet
(3m) horizontally
6 feet (1.8m)
7 feet (2.1m)
12 inches (305mm)
1
In accordance with the current ANSI Z223.1/NFPA 54 Natural Fuel Gas Code
2
In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code
*For clearances not specified in ANSI Z223.1/NFPA 54 or CSA
B149.1, clearance will be in accordance with local installation
codes and the requirements of the gas supplier and these
installation instructions."
A vent shall not terminate directly above a sidewalk or paved driveway that is located
between two single family dwellings and serves both dwellings.
Permitted only if veranda, porch, deck or balcony is fully open on a minimum of
two sides beneath the floor. Lennox recommends avoiding this location if possible.
* 12"
* Equal to or greater than soffit depth
* Equal to or greater than soffit depth* Equal to or greater than soffit depth
* Equal to or greater than soffit depth* Equal to or greater than soffit depth
* No minimum to outside corner
* No minimum to outside corner
3 feet (.9m) within a height 15 feet (4.5m)
above the meter / regulator assembly
3 feet (.9m)
*
*12 inches (305mm)
Page 32
Page 32
Details of Intake and Exhaust Piping Terminations for
Direct Vent Installations
NOTE − In Direct Vent installations, combustion air is taken from outdoors and flue gases are discharged to outdoors.
NOTE − Flue gas may be slightly acidic and may adversely
affect some building materials. If any vent termination is
used and the flue gasses may impinge on the building material, a corrosion−resistant shield (minimum 24 inches
square) should be used to protect the wall surface. If the
optional tee is used, the protective shield is recommended.
The shield should be constructed using wood, plastic,
sheet metal or other suitable material. All seams, joints,
cracks, etc. in the affected area should be sealed using an
appropriate sealant. See figure 32.
Intake and exhaust pipes may be routed either horizontally
through an outside wall or vertically through the roof. In attic
or closet installations, vertical termination through the roof
is preferred. Figures 29 through 43 show typical terminations.
1. Intake and exhaust terminations are not required to be
in the same pressure zone. You may exit the intake on
one side of the structure and the exhaust on another
side (figure 30). You may exit the exhaust out the roof
and the intake out the side of the structure (figure 31).
2. Intake and exhaust pipes should be placed as close
together as possible at termination end (refer to illustrations). Maximum separation is 3" (76mm) on roof
terminations and 6" (152mm) on side wall terminations.
3. On roof terminations, the intake piping should terminate straight down using two 90° elbows (See figure
29).
4. Exhaust piping must terminate straight out or up as
shown. A reducer may be required on the exhaust piping at the point where it exits the structure to improve
the velocity of exhaust away from the intake piping.
See table 14.
FIGURE 29
UNCONDITIONED
ATTIC SPACE
1/2" (13mm) FOAM
INSULATION IN
UNCONDITIONED
SPACE
SIZE TERMINATION
PIPE PER TABLE 14.
3"(76mm) MAX.
12" (305mm) ABOVE
AVERAGE SNOW
ACCUMULATION
3" (76mm) OR
2" (51mm) PVC
PROVIDE SUPPORT
FOR INTAKE AND
EXHAUST LINES
8" (203mm) MIN
Inches(mm)
DIRECT VENT ROOF TERMINATION KIT
(15F75 or 44J41)
FIGURE 30
Exhaust
Pipe
Furnace
Exiting Exhaust and Intake Vent
(no common pressure zone)
Inlet Air
(Minimum 12 in.
305 MM) above
grade or snow
accumulation
FIGURE 31
Roof T
erminated
Exhaust Pipe
Furnace
Exiting Exhaust and Intake Vent
(no common pressure zone)
Inlet Air
(Minimum 12 in.
305 MM) above
grade or snow
accumulation
TABLE 14
EXHAUST PIPE TERMINATION SIZE REDUCTION
EL195UHE
MODEL
Exhaust Pipe Size
Termination
Pipe Size
*045 and 070
2" (51mm), 2−1/2" (64mm),
3" (76mm)
1−1/2" (38mm)
*0902" (51mm)
1102" (51mm)
135
3" (76mm)
2" (51mm)
*EL195UHE−045, −070 and −090 units with the flush mount
termination must use the 1−1/2"accelerator supplied with the
kit.
NOTE − Care must be taken to avoid recirculation of ex-
haust back into intake pipe.
5. On field−supplied terminations for side wall exit, exhaust piping may extend a maximum of 12 inches
(305mm) for 2" PVC and 20 inches (508mm) for 3"
(76mm) PVC beyond the outside wall. Intake piping
should be as short as possible. See figures 33 and 34.
6. On field−supplied terminations, a minimum distance
between the end of the exhaust pipe and the end of
the intake pipe without a termination elbow is 8" and a
minimum distance of 6" with a termination elbow. See
figures 33 and 34.
7. If intake and exhaust piping must be run up a side wall
to position above snow accumulation or other obstructions, piping must be supported every 24"
(610mm) as shown in figures 33 and 34. In addition,
close coupled wall termination kits must be extended
for use in this application. See figures 41 and 42.
When exhaust and intake piping must be run up an
Page 33
Page 33
outside wall, the exhaust piping must be terminated
with pipe sized per table 14.The intake piping may be
equipped with a 90° elbow turndown. Using turndown
will add 5 feet (1.5m) to the equivalent length of the
pipe.
8. A multiple furnace installation may use a group of up to
four terminations assembled together horizontally, as
shown in figure 38.
C
A
E
D
B
A
B
D
D
B
C
A
C
12"
1
1
2
2
2" (51mm)
Vent Pipe
3" (76mm)
Vent Pipe
A− Clearance above
grade or average snow
accumulation
B−Horizontal
separation between
intake and exhaust
C−Minimum from
end of exhaust to
inlet of intake
D−Exhaust pipe length
E−Wall support distance
from top of each pipe
(intake/exhaust)
12" (305MM) Min.
12" (305MM) Min.
6" (152MM) Min.
24" (610 MM) Max
9" (227MM) Min.
12" (305MM) Min.
16" (405 MM) Max.
6" (152MM) Max.
6" (152MM) Min.
24" (610 MM) Max
9" (227MM) Min.
12" (305MM) Min.
20" (508MM) Max.
6" (152MM) Max.
TABLE
15
FIGURE 32
1
The exhaust termination tee should be connected to the 2" or 3" PVC flue pipe as shown in the illustration. Do
not use an accelerator in applications that include an exhaust termination tee. The accelerator is not required.
2
As required. Flue gas may be acidic and may adversely affect some building materials. If a side wall vent
termination is used and flue gases will impinge on the building materials, a corrosion−resistant shield (24 inches
square) should be used to protect the wall surface. If optional tee is used, the protective shield is recommended. The shield should be constructed using wood, sheet metal or other suitable material. All seams, joints,
cracks, etc. in affected area, should be sealed using an appropriate sealant.
3
Exhaust pipe 45° elbow can be rotated to the side away from the combustion air inlet to direct exhaust away
from adjacent property. The exhaust must never be directed toward the combustion air inlet.
NOTE − See unit installation instructions for proper exhaust pipe termination size reduction.
Front View of
Intake and Exhaust
Intake
Exhaust
3
Intake
Exhaust
Page 34
Page 34
FIGURE 33
FIELD−SUPPLIED WALL TERMINATION OR
(15F74) WALL RING TERMINATION KIT
See venting table 11 for maximum venting lengths with this
arrangement.
* Use wall support every 24" (610 mm). Use two wall supports if
extension is greater than 24" (610 mm) but less than 48" (1219 mm).
NOTE − One wall support must be 6" (152 mm) from top of each pipe
(intake and exhaust)
2" (51mm)
Vent Pipe
3" (76mm)
Vent Pipe
A−Minimum clearance
above grade or average
snow accumulation
B−Maximum horizontal
separation between
intake and exhaust
C−Minimum from
end of exhaust to
inlet of intake
D−Maximum exhaust
pipe length
E−Maximum wall support
distance from top of each
pipe (intake/exhaust)
12" (305MM)12" (305MM)
6" (152MM)6" (152MM)
8" (203MM)8" (203MM)
12" (305MM)20" (508MM)
6" (152MM)6" (152MM)
NOTE − FIELD−PROVIDED
REDUCER MAY BE
REQUIRED TO ADAPT
LARGER VENT PIPE SIZE
TO TERMINATION
D
B
C
SIZE TERMINATION
PER TABLE 14
1/2" (13mm) ARMAFLEX
INSULATION IN UN-
CONDITIONED SPACE
STRAIGHT
APPPLICATION
B
C
A
D
* WALL
SUPPORT
1/2" (13mm) ARMAFLEX INSULATION
IN UNCONDITIONED SPACE
E
EXTENDED
APPLICATION
A
FIGURE 34
FIELD−SUPPLIED WALL TERMINATION OR
(15F74) WALL RING TERMINATION KIT
With INTAKE ELBOW
See venting table 11 for maximum venting lengths with this
arrangement.
* Use wall support every 24" (610 mm). Use two wall supports if
extension is greater than 24" (610 mm) but less than 48" (1219 mm).
NOTE − One wall support must be 6" (152 mm) from top of each pipe
(intake and exhaust)
2" (51mm)
Vent Pipe
3" (76mm)
Vent Pipe
12" (305MM)12" (305MM)
6" (152MM)6" (152MM)
6" (152MM)
12" (305MM)20" (508MM)
6" (152MM)6" (152MM)
6" (152MM)
A−Minimum clearance
above grade or average
snow accumulation
B−Maximum horizontal
separation between
intake and exhaust
C−Minimum from
end of exhaust to
inlet of intake
D−Maximum exhaust
pipe length
E−Maximum wall support
distance from top of each
pipe (intake/exhaust)
NOTE − FIELD−PROVIDED
REDUCER MAY BE
REQUIRED TO ADAPT
LARGER VENT PIPE SIZE
TO TERMINATION
D
B
C
SIZE TERMINATION
PER TABLE 14
1/2" (13mm) ARMAFLEX
INSULATION IN UN-
CONDITIONED SPACE
STRAIGHT
APPPLICATION
B
C
D
* WALL
SUPPORT
1/2" (13mm) ARMAFLEX INSULATION
IN UNCONDITIONED SPACE
E
EXTENDED
APPLICATION
A
A
Page 35
Page 35
FIGURE 35
2" EXTENSION FOR 2" PVC
PIPE1" EXTENSION FOR 3"
PVC PIPE
1−1/2" ACCELERATOR
(all −45, −070 and −090 units)
FURNACE
EXHAUST
PIPE
FURNACE
INTAKE
PIPE
4’’
GLUE EXHAUST
END FLUSH INTO
TERMINATION
FLAT
SIDE
FLUSH−MOUNT SIDE WALL TERMINATION
51W11
FIGURE 36
DIRECT VENT CONCENTRIC ROOFTOP TERMINATION
71M80, 69M29 or 60L46 (US)
44W92 or 44W93 (Canada)
Minimum
Above Average
Snow
Accumulation
SHEET METAL STRAP
(Clamp and sheet metal strap
must be field installed to support
the weight of the termination kit.)
FLASHING
(Not Furnished)
CLAMP
FIELD−PROVIDED
REDUCER MAY BE REQUIRED
TO ADAPT LARGER VENT
PIPE SIZE TO TERMINATION
1 1/2" (38mm) accelerator
provided on 71M80 & 44W92
kits for EL195UHE045P24B,
070P24B & 070P36B
12” (305mm)
INTAKE
AIR
EXHAUST
VENT
12" (305mm) Min.
above grade or
average snow
accumulation.
FIGURE 37
DIRECT VENT CONCENTRIC WALL TERMINATION
71M80, 69M29 or 60L46 (US)
44W92 or 44W93 (Canada)
INTAKE
AIR
INTAKE
AIR
INTAKE
AIR
OUTSIDE
WALL
GRADE
CLAMP
(Not Furnished)
FIELD−PROVIDED
REDUCER MAY BE REQUIRED
TO ADAPT LARGER VENT
PIPE SIZE TO TERMINATION
EXHAUST
VENT
1−1/2" (38mm) accelerator
provided on 71M80 & 44W92
kits for EL195UHE045P24B,
070P24B & 070P36B
EXHAUST
VENT
FIGURE 38
EXHAUST
VENT
INTAKE
AIR
5−1/2"
(140mm)
Front View
12"
(305mm)
5"
(127mm)
18" MAX.
(457mm)
EXHAUST VENT
INTAKE
AIR
OPTIONAL VENT TERMINATION FOR MULTIPLE UNIT
INSTALLATION OF DIRECT VENT WALL TERMINATION KIT
(22G44, 44J40, 30G28 or 81J20)
Inches (mm)
Side View
12" (305mm) Min.
above grade or
average snow
accumulation.
optional intake elbow
FIGURE 39
1/2" (13mm) Foam Insulation
in Unconditioned Space
EXHAUST VENT
INTAKE AIR
OUTSIDE WALL
EXHAUST VENT
INTAKE
AIR
Front View
Top View
DIRECT VENT WALL TERMINATION KIT
(30G28 or 81J20)
6 (152mm) MIN.
SIZE
TERMINATION
PIPE PER
TABLE 14.
FIELD−
PROVIDED
REDUCER MAY
BE REQUIRED
TO ADAPT
LARGER VENT
PIPE SIZE TO
TERMINATION
FIGURE 40
EXHAUST VENT
INTAKE
AIR
Front View
SIZE
TERMINATION
PIPE PER
TABLE 14.
Top View
1/2" (13mm) Foam Insulation
in Unconditioned Space
EXHAUST VENT
INTAKE AIR
OUTSIDE WALL
DIRECT VENT WALL TERMINATION KIT
(22G44 or 44J40)
8" (206mm) MIN.
FIELD−
PROVIDED
REDUCER MAY
BE REQUIRED
TO ADAPT
LARGER VENT
PIPE SIZE TO
TERMINATION
Page 36
Page 36
FIGURE 41
12” (305 mm) Minimum
Above Grade or Average
Snow Accumulation
1/2” (13 mm)
FOAM INSULATION
(Field−Furnished)
5” (127 mm)
5−1/2”
(140 mm)
EXHAUST
AIR
INTAKE
AIR
GRADE
12”
(305 mm)
INTAKE
AIR
EXHAUST
AIR
GRADE
12” (305 mm) Max. for 2” (51 mm) Dia. Exhaust
20” (508 mm) Max. for 3” (76 mm) Dia. Exhaust
WALL SUPPORT*
12” (305 mm) Max. for 2” (51 mm) Dia. Exhaust
20” (508 mm) Max. for 3” (76 mm) Dia. Exhaust
12” (305 mm) Minimum
Above Grade or Average
Snow Accumulation
WALL TERMINATION KITS (CLOSE−COUPLE)
EXTENDED VENT FOR GRADE CLEARANCE
2 inch (51 mm) 22G44 (US)
3 inch (76 mm) 44J40 (US)
6” (152 mm)
Maximum
8” (203 mm) Min. for 2” (51 mm) & 3” (76 mm) DIA. pipe
between the end of the exhaust pipe and intake pipe
8” (203 mm) Min.
*Use wall support every 24" (610). Use two supports if
extension is greater than 24" but less than 48".
FIELD−PROVIDED
REDUCER MAY BE REQUIRED TO ADAPT
LARGER VENT PIPE SIZE TO TERMINATION
If intake and exhaust pipe is less than 12 in. (305 mm)
above snow accumulation or other obstructions, field−
fabricated piping must be installed.
FIGURE 42
12” (305 mm) Minimum
Above Grade or Average
Snow Accumulation
1/2” (13 mm)
FOAM INSULATION
(Field−Furnished)
5” (127 mm)
5−1/2”
(140 mm)
EXHAUST
AIR
INTAKE
AIR
GRADE
12”
(305 mm)
INTAKE
AIR
EXHAUST
AIR
GRADE
WALL SUPPORT*
12” (305 mm) Minimum
Above Grade or Average
Snow Accumulation
WALL TERMINATION KITS (CLOSE−COUPLE)
EXTENDED VENT FOR GRADE CLEARANCE
2 inch (51 mm) 30G28 (WTK Canada)
3 inch (76 mm) 81J20 (WTK Canada)
See Installation Instructions for additional information.
6” (152 mm)
Maximum
If intake and exhaust pipe is less than 12 in. (305 mm)
above snow accumulation or other obstructions, field−
fabricated piping must be installed.
12” (305 mm) Max. for 2” (51 mm) Dia. Exhaust
20” (508 mm) Max. for 3” (76 mm) Dia. Exhaust
12” (305 mm) Max. for 2” (51 mm) Dia. Exhaust
20” (508 mm) Max. for 3” (76 mm) Dia. Exhaust
6” (152 mm)
Minimum
6” (152 mm)
Minimum
*Use wall support every 24" (610). Use two supports if
extension is greater than 24" but less than 48".
FIELD−PROVIDED
REDUCER MAY BE REQUIRED TO ADAPT
LARGER VENT PIPE SIZE TO TERMINATION
Page 37
Page 37
EL195UHE DIRECT VENT APPLICATION
USING EXISTING CHIMNEY
NOTE − Do not discharge exhaust gases directly into any chimney or vent stack. If vertical discharge through an existing unused chimney or stack is required, insert piping
inside chimney until the pipe open end is above top of chimney and terminate as illustrated. In any exterior portion of chimney, the exhaust vent must be insulated.
FIGURE 43
3" − 8"
(76mm−
203mm)
STRAIGHT−CUT OR
ANGLE−CUT IN DIRECTION
OF ROOF SLOPE *
EXHAUST VENT
1/2" (13mm)
WEATHERPROOF
INSULATION
SHOULDER OF FITTINGS
PROVIDE SUPPORT
OF PIPE ON TOP PLATE
ALTERNATE
INTAKE PIPE
INTAKE PIPE
INSULATION (optional)
EXTERIOR
PORTION OF
CHIMNEY
INSULATE
TO FORM
SEAL
SHEET
METAL TOP
PLATE
*SIZE TERMINATION
PIPE PER TABLE 14.
Minimum 12" (305MM)
above chimney top
plate or average snow
accumulation
8" − 12"
(203mm − 305mm)
3"−8"
(76mm−203mm)
Details of Exhaust Piping Terminations for Non-Direct
Vent Applications
Exhaust pipes may be routed either horizontally through an
outside wall or vertically through the roof. In attic or closet
installations, vertical termination through the roof is preferred. Figures 44 through 47 show typical terminations.
1. Exhaust piping must terminate straight out or up as
shown. The termination pipe must be sized as listed in
table 14.The specified pipe size ensures proper
velocity required to move the exhaust gases away
from the building.
2. On field supplied terminations for side wall exit, exhaust piping may extend a maximum of 12 inches
(305mm) for 2" PVC and 20 inches (508mm) for 3"
(76mm) PVC beyond the outside wall. See figure 45.
FIGURE 44
NON−DIRECT VENT ROOF TERMINATION KIT
(15F75 or 44J41)
UNCONDITIONED
ATTIC SPACE
3" (76mm) OR
2" (51mm) PVC
PROVIDE SUPPORT
FOR EXHAUST LINES
12" (305mm)
ABOVE AVE.
SNOW
ACCUMULATION
SIZE TERMINATION
PIPE PER TABLE
14.
1/2" (13mm) FOAM
INSULATION
FIGURE 45
1/2" (13mm) ARMAFLEX
INSULATION IN
UNCONDITIONED SPACE
PVC REDUCER
1/2" (13mm)
ARMAFLEX
INSULATION
NON−DIRECT VENT FIELD SUPPLIED WALL TERMINATION OR
(15F74) WALL TERMINATION KIT
SIZE TERMINATION
PIPE PER TABLE 14.
FIELD−PROVIDED
REDUCER MAY
BE REQUIRED TO
ADAPT LARGER
VENT PIPE SIZE
TO TERMINATION
12" MIN.
(305mm)
Above Grade or
average snow
accumulation
12" (305mm) MAX. for 2" (51mm)
20" (508mm) MAX. for 3" (76mm)
3. If exhaust piping must be run up a side wall to position
above snow accumulation or other obstructions, piping must be supported every 24 inches (610mm) as
shown in figure 46. When exhaust piping must be run
up an outside wall, any reduction in exhaust pipe size
must be done after the final elbow.
FIGURE 46
12" (305mm)
ABOVE GRADE OR
AVERAGE SNOW
ACCUMULATION
UNCONDITIONED
SPACE
1/2" (13mm) FOAM
INSULATION
1/2" (13mm) FOAM
INSULATION IN
UNCONDITIONED
SPACE
*WALL SUPPORT
OUTSIDE WALL
SIZE TERMINATION
PIPE PER
TABLE 14.
FIELD−PROVIDED
REDUCER MAY BE
REQUIRED TO
ADAPT LARGER
VENT PIPE SIZE TO
TERMINATION
*Use wall support every 24" (610). Use two supports if extension is
greater than 24" but less than 48".
12" (305mm) MAX. for 2" (51mm)
20" (508mm) MAX. for 3" (76mm)
NON−DIRECT VENT FIELD SUPPLIED WALL TERMINATION
EXTENDED OR (15F74) WALL TERMINATION VENT PIPE
EXTENDED
6" (152mm)
Max
Page 38
Page 38
NOTE − Do not discharge exhaust gases directly into any chimney or vent stack. If vertical discharge through an existing unused chimney or stack is required, insert piping
inside chimney until the pipe open end is above top of chimney and terminate as illustrated. In any exterior portion of chimney, the exhaust vent must be insulated.
FIGURE 47
STRAIGHT−CUT OR
ANGLE−CUT IN DIRECTION
OF ROOF SLOPE
EXHAUST VENT
1/2" (13mm)
WEATHERPROOF
INSULATION
SHOULDER OF FITTINGS
PROVIDE SUPPORT
OF PIPE ON TOP PLATE
EXTERIOR
PORTION OF
CHIMNEY
INSULATE
TO FORM
SEAL
SHEET
METAL TOP
PLATE
SIZE TERMINATION
PIPE PER TABLE 14.
EL195UHE NON−DIRECT VENT APPLICATION
USING EXISTING CHIMNEY
Minimum 12" (305MM)
above chimney top
plate or average snow
accumulation
Condensate Piping
This unit is designed for either right- or left-side exit of condensate piping in upflow applications. In horizontal applications, the condensate trap must extend below the unit. An
8" service clearance is required for the condensate trap.
Refer to figures 48 and 49 for condensate trap locations.
Figure 55 shows trap assembly using 1/2" PVC or 3/4"
PVC.
NOTE − If necessary the condensate trap may be installed
up to 5´ away from the furnace. Use PVC pipe to connect
trap to furnace condensate outlet. Piping from furnace
must slope down a minimum of 1/4" per ft. toward trap.
1 − Determine which side condensate piping will exit the
unit, location of trap, field−provided fittings and length of
PVC pipe required to reach available drain.
2 − Use a 3/8 allen wrench and remove plug (figure 48)
from the cold end header box at the appropriate location on the side of the unit. Install field−provided 1/2
NPT male fitting into cold end header box. Use Teflon
tape or appropriate pipe dope.
3 − Install the cap over the clean out opening at the base of
the trap. Secure with clamp. See figure 55.
4 − Install drain trap using appropriate PVC fittings, glue
all joints. Glue the provided drain trap as shown in figure 55. Route the condensate line to an open drain.
Condensate line must maintain a 1/4" downward slope
from the furnace to the drain.
FIGURE 48
CONDENSATE TRAP AND PLUG LOCATIONS
(Unit shown in upflow position)
NOTE − In upflow applications where side return
air filter is installed on same side as the condensate trap, filter rack must be installed beyond
condensate trap or trap must be re−located to
avoid interference.
Trap
(same on
right side)
Plug
(same on left side)
1−1/2 in.
5 − Figures 50 and 51 show the furnace and evaporator
coil using a separate drain. If necessary the condensate line from the furnace and evaporator coil can
drain together. See figures 52, 53 and 54.
Upflow furnace (figure 53) − In upflow furnace applications the field provided vent must be a minimum 1" to a
maximum 2" length above the condensate drain outlet
connection. Any length above 2" may result in a
flooded heat exchanger if the combined primary drain
line were to become restricted.
Horizontal furnace (figure 54) − In horizontal furnace
applications the field provided vent must be a minimum 4" to a maximum 5" length above the condensate
drain outlet connection. Any length above 5" may result in a flooded heat exchanger if the combined primary drain line were to become restricted.
NOTE − In horizontal applications it is recommended to
install a secondary drain pan underneath the unit and
trap assembly.
NOTE − Vinyl tubing may be used for condensate drain.
Tubing must be 1−1/4" OD X 1" ID and should be
attached to the drain on the trap using a hose clamp.
CAUTION
Donot use copper tubing or existing copper conden-
sate lines for drain line.
6 − If unit will be started immediately upon completion of
installation, prime trap per procedure outlined in Unit
Start−Up section.
Page 39
Page 39
Condensate line must slope downward away from the
trap to drain. If drain level is above condensate trap,
condensate pump must be used. Condensate drain
line should be routed within the conditioned space to
avoid freezing of condensate and blockage of drain
line. If this is not possible, a heat cable kit may be used
on the condensate trap and line. Heating cable kit is
available from Lennox in various lengths; 6 ft. (1.8m) −
kit no. 26K68; 24 ft. (7.3m) − kit no. 26K69; and 50 ft.
(15.2m) − kit no. 26K70.
FIGURE 49
CONDENSATE TRAP LOCATIONS
(Unit shown in upflow position with remote trap)
*5’ max.
To Drain
PVC Pipe Only
Field Provided Vent
Min. 1" Above Condensate
Drain Connection
1" Min.
Trap Can Be Installed a
Maximum 5’ From Furnace
*Piping from furnace must slope down a minimum
of 1/4" per ft. toward trap.
2" Max.
FIGURE 50
EL195UHE With Evaporator
Coil Using A Separate Drain
Field−Provided Vent
(1" min. to 2" Max. above
condensate drain connection)
Drain
Condensate trap
and evaporator coil
drain separately as
shown.
Condensate
Drain Connection
FIGURE 51
EL195UHE with Evaporatoir Coil Using a Separate Drain
(Unit shown in horizontal left−hand discharge position)
Condensate Drain
Connection
Field−Provided Vent
(4" min. to 5" Max. above
condensate drain connection)
*Piping from furnace and evaporator coil must slope down a minimum of 1/4" per ft. toward trap.
5’ max.
PVC Pipe Only
4”min
5”max
Evaporator
Coil
Drain Pan
Page 40
Page 40
IMPORTANT
When combining the furnace and evaporator
coil drains together, the A/C condensate drain
outlet must be vented to relieve pressure in order for the furnace pressure switch to operate
properly.
FIGURE 52
Condensate Trap With Optional Overflow Switch
Field−Provided Vent
(Upflow/Furnace 1" Min. to 2" Max.
Horizontal Furnace 4" Min. to 5" Max. above
condensate drain connection)
Furnace Condensate
Drain Connection
From Evaporator Coil
To Drain
Optional
Overflow Switch
FIGURE 53
EL195UHE with Evaporator
Coil Using a Common Drain
Field−Provided Vent
(1" min. to 2" Max. above
condensate drain connection)
Evaporator
Drain Line
Vent Required
Condensate
Drain Connection
FIGURE 54
Condensate Drain
Connection
EL195UHE with Evaporator Coil Using a Common Drain
(Unit shown in horizontal left−hand discharge position)
Field−Provided Vent
(4" min. to 5" Max. above
condensate drain connection)
*Piping from furnace and evaporator coil must slope down a minimum of 1/4" per ft. toward trap.
5’ max.
PVC Pipe Only
4”min
5”max
Evaporator
Coil
Drain Pan
Page 41
Page 41
FIGURE 55
TRAP / DRAIN ASSEMBLY USING 1/2" PVC OR 3/4" PVC
Adapter 1/2 inch slip X
1/2 inch mpt (Not Furnished)
Drain Trap
Assembly
(Furnished)
Vent
Drain Trap
Clean Out
5 Feet
Maximum
Coupling 1/2 inch slip X slip
(Not Furnished)
90° Elbow 1/2 inch PVC
(Not Furnished)
1/2 inch PVC Pipe
(Not Furnished)
1/2 inch PVC Pipe
(Not Furnished)
Condensate Drain
Connection In Unit
7
(178)
Drain Assembly for 1/2 inch Drain Pipe
90° Elbow
3/4 inch PVC
(Not Furnished)
Coupling 3/4 inch slip X slip
(Not Furnished)
To
Drain
To
Drain
90° Elbow
3/4 inch PVC
(Not Furnished)
To
90° Street Elbow
1/2 inch PVC
To
Drain
90° Elbow
1/2 inch PVC
(Not Furnished)
1/2 inch PVC Pipe
(Not Furnished)
Drain Assembly for 3/4 inch Drain Pipe
90° Street Elbow
1/2 inch PVC
(Not Furnished)
Condensate Drain
Connection In Unit
Adapter 1/2 inch slip X
1/2 inch mpt (Not Furnished)
Condensate Drain
Connection In Unit
Vent
To
Drain
Condensate Drain
Connection In Unit
Drain Trap Assembly with 3/4 inch Piping
Vent
To
Drain
(Furnished)
Optional Condensate Drain Connection
Optional Drain Piping From Trap
Drain Trap Assembly
(Furnished)
Drain Trap Assembly with 1/2 inch Piping
Drain Trap Assembly with 3/4 inch Piping
1/2 inch
3/4 inch
1 (25 mm) Min.
2 (50 mm) Max.
Above Top Of
Condensate Drain
Connection In Unit
1 (25 mm) Min. 2 (50 mm) Max. Above Top
Of Condensate Drain Connection In Unit
1 (25 mm) Min. 2 (50 mm) Max. Above Top
Of Condensate Drain Connection In Unit
Trap
Page 42
Page 42
III−START-UP
A−Preliminary and Seasonal Checks
1 − Inspect electrical wiring, both field and factory installed
for loose connections. Tighten as required.
2 − Check voltage at disconnect switch. Voltage must be with-
in range listed on the nameplate. If not, consult the po wer
company and have voltage condition corrected before starting unit.
3 − Inspect condition of condensate traps and drain as-
sembly. Disassemble and clean seasonally.
B−Heating Start-Up
BEFORE LIGHTING the unit, smell all around the fur-
nace area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the
floor.
The gas valve on the EL195UHE is equipped with a gas
control switch. Use only your hand to move the switch.
Never use tools. If the the switch will not move by hand,
replace the valve. Do not try to repair it. Force or attempted repair may result in a fire or explosion.
Placing the furnace into operation:
EL195UHE units are equipped with a SureLight ignition
system. Do not
attempt to manually light burners on this
furnace. Each time the thermostat calls for heat, the
burners will automatically light. The ignitor does not get
hot when there is no call for heat on units with SureLightt
ignition system.
Priming Condensate Trap
The condensate trap should be primed with water prior to
start−up to ensure proper condensate drainage. Either
pour 10 fl. oz. (300 ml) of water into the trap, or follow
these steps to prime the trap:
1 − Follow the lighting instructions to place the unit into op-
eration.
2 − Set the thermostat to initiate a heating demand.
3 − Allow the burners to fire for approximately 3 minutes.
4 − Adjust the thermostat to deactivate the heating de-
mand.
5 − Wait for the combustion air inducer to stop. Set the
thermostat to initiate a heating demand and again allow the burners to fire for approximately 3 minutes.
6 − Adjust the thermostat to deactivate the heating de-
mand and again wait for the combustion air inducer to
stop. At this point, the trap should be primed with sufficient water to ensure proper condensate drain operation.
WARNING
If you do not follow these instructions exactly, a fire
or explosion may result causing property damage,
personal injury or death.
Gas Valve Operation (Figure 56)
1 − STOP! Read the safety information at the beginning of
this section.
2 − Set the thermostat to the lowest setting.
3 − Turn off all electrical power to the unit.
4 − This furnace is equipped with an ignition device which
automatically lights the burners. Do not try to light the
burners by hand.
5 − Remove the access panel.
6 − Move gas valve switch to OFF. See figure 56.
7 − Wait five minutes to clear out any gas. If you then smell
gas, STOP! Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instructions. If you do not smell gas go to next step.
8 − Move gas valve switch to ON. See figure 56.
FIGURE 56
GAS VALVE SHOWN IN ON POSITION
MANIFOLD
PRESSURE
OUTLET
PORT
INLET
PRESSURE
PORT
MANIFOLD PRESSURE
ADJUSTMENT SCREW
(under barbed fitting)
9 − Replace the access panel.
10− Turn on all electrical power to to the unit.
11− Set the thermostat to desired setting.
NOTE − When unit is initially started, steps 1 through 11
may need to be repeated to purge air from gas line.
12− If the appliance will not operate, follow the instructions
Turning Off Gas to Unit" and call your service technician or gas supplier.
Turning Off Gas to Unit
1 − Set the thermostat to the lowest setting.
2 − Turn off all electrical power to the unit if service is to be
performed.
3 − Remove the access panel.
4 − Move gas valve switch to OFF.
5 − Replace the access panel.
Failure To Operate
If the unit fails to operate, check the following:
1 − Is the thermostat calling for heat?
2 − Are access panels securely in place?
3 − Is the main disconnect switch closed?
4 − Is there a blown fuse or tripped breaker?
5 − Is the filter dirty or plugged? Dirty or plugged filters will
cause the limit control to shut the unit off.
6 − Is gas turned on at the meter?
7 − Is the manual main shut-off valve open?
8 − Is the internal manual shut-off valve open?
9 − Is the unit ignition system in lockout? If the unit locks out
again, inspect the unit for blockages.
Page 43
Page 43
IV−HEATING SYSTEM SERVICE CHECKS
A−C.S.A. Certification
All units are C.S.A. design certified without modifications.
Refer to the EL195UHE Operation and Installation Instruction Manual Information.
B−Gas Piping
CAUTION
If a flexible gas connector is required or allowed by
the authority that has jurisdiction, black iron pipe
shall be installed at the gas valve and extend outside
the furnace cabinet. The flexible connector can then
be added between the black iron pipe and the gas
supply line.
Gas supply piping should not allow more than 0.5" W.C.
drop in pressure between gas meter and unit. Supply gas
pipe must not be smaller than unit gas connection.
Compounds used on gas piping threaded joints should be
resistant to action of liquefied petroleum gases.
C−Testing Gas Piping
IMPORTANT
In case emergency shutdown is required, turn off
the main shut-off valve and disconnect the main
power to unit. These controls should be properly
labeled by the installer.
When pressure testing gas lines, the gas valve must be disconnected and isolated. Gas valves can be damaged if
subjected to more than 0.5 psig (14" W.C.). See figure 57.
FIGURE 57
MANUAL MAIN SHUT−OFF
VALVE WILL NOT HOLD
NORMAL TEST PRESSURE
CAP
FURNACE
ISOLATE
GAS VALVE
1/8" N.P.T. PLUGGED TAP
When checking piping connections for gas leaks, use preferred means. Kitchen detergents can cause harmful corrosion on various metals used in gas piping. Use of a specialty
Gas Leak Detector is strongly recommended. It is available
through Lennox under part number 31B2001. See Corp.
8411−L10, for further details.
WARNING
Do not use matches, candles, flame or any other
source of ignition to check for gas leaks.
D−Testing Gas Supply Pressure
Gas Flow (Approximate)
TABLE 16
GAS METER CLOCKING CHART
EL195
Unit
Seconds for One Revolution
NaturalLP
1 cu ft
Dial
2 cu ft
Dial
1 cu ft
Dial
2 cu ft
DIAL
−04580160200400
−0705511 0136272
−0904182102204
−110336682164
−135275468136
Natural−1000 btu/cu ft LP−2500 btu/cu ft
Furnace should operate at least 5 minutes before checking gas flow. Determine time in seconds for two revolutions of gas through the meter. (Two revolutions assures a
more accurate time.) Divide by two and compare to time
in table 16. If manifold pressure matches table 17 and rate
is incorrect, check gas orifices for proper size and restriction. Remove temporary gas meter if installed.
NOTE − To obtain accurate reading, shut off all other gas
appliances connected to meter.
Supply Pressure Measurement
When testing supply gas pressure, use the 1/8" N.P.T.
plugged tap located on the gas valve to facilitate test gauge
connection. See figure 7. Check gas line pressure with unit
firing at maximum rate. Low pressure may result in erratic
operation or underfire. High pressure can result in permanent damage to gas valve or overfire.
On multiple unit installations, each unit should be checked
separately, with and without other units operating. Supply
pressure must fall within range listed in table 17.
Manifold Pressure Measurement
1 − Remove the threaded plug from the outlet side of the
gas valve and install a field−provided barbed fitting.
Connect to a manometer to measure manifold pressure.
2 − Start unit and allow 5 minutes for unit to reach steady
state.
3 − While waiting for the unit to stabilize, observe the
flame. Flame should be stable and should not lift from
burner. Natural gas should burn blue.
4 − After allowing unit to stabilize for 5 minutes, record
manifold pressure and compare to value given in table
17.
NOTE − Shut unit off and remove manometer as soon as an
accurate reading has been obtained. Take care to remove
barbed fitting and replace threaded plug.
TABLE 17
Supply Line and Manifold Pressure (inches w.c.)
UnitFuel
Manifold
Pressure
Supply Line
AllNat3.54.5 − 10.5
AllLP/Propane10.011.0 − 13.0
Page 44
Page 44
E−Proper Combustion
Furnace should operate minimum 15 minutes with correct
manifold pressure and gas flow rate before checking combustion. Take combustion sample beyond the flue outlet
and compare to the tables below.
TABLE 18
Unit
CO2%
For Nat
CO2%
For LP
All7.2 − 8.28.6 − 9.6
The maximum carbon monoxide reading should not exceed 50 ppm.
F−High Altitude
NOTE − In Canada, certification for installations at elevations over 4500 feet (1372 m) is the jurisdiction of local authorities.
Units installed at altitude of 4501 − 10,000 feet (1373 to
3048 m) may require a pressure switch change which can
be ordered separately. Table 19 lists conversion kit and
pressure switch requirements at varying altitudes.
The combustion air pressure switch is factory−set and requires no adjustment.
TABLE 19
LP/Propane Conversion Kit and Pressure Switch Requirements at Varying Altitudes
Unit
Natural to
LP/Propane
High Altitude
Natural Burner
Orifice Kit
High Altitude
LP/Propane Burner
Orifice Kit
High Altitude Pressure Switch
0 − 7500 ft
(0 − 2286m)
7501 − 10,000 ft
(2286 − 3038m)
7501 − 10,000 ft
(2286 − 3038m)
4501 − 7500 ft
(1373 − 2286m)
7501 −10,000 ft
(2286 − 3048m)
−045
*69W7373W37*68W68
No Change80W60
−07080W6680W59
−09080W6580W59
−11080W6680W59
−13580W6580W59
* Conversion requires installation of a gas valve manifold spring which is provided with the gas conversion kit.
Pressure switch is factory set. No adjustment necessary. All models use the factory−installed pressure switch from 0−4500 feet (0−1370 m).
Page 45
Page 45
G− Proper Ground and Voltage
A poorly grounded furnace can contribute to premature ignitor failure. Use the following procedure to check for
ground and voltage to the integrated control.
1 − Measure the AC voltage between Line Neutral (spade
terminals) and C" terminal (low voltage terminal
block) on the integrated control. See figure 58. A wide
variation in the voltage between Line Neutral and C"
as a function of load indicates a poor or partial ground.
Compare the readings to the table below. If the readings exceed the maximum shown in table 1, make repairs before operating the furnace.
2 − In addition, measure the AC voltage from Line Hot to
Line Neutral (spade terminals) on the integrated control. See figure 58. This voltage should be in the range
of 97 to 132 Vac
TABLE 20
Furnace Status
Measurement VAC
ExpectedMaximum
Power On Furnace Idle0.32
CAI / Ignitor Energized0.755
Indoor Blower EnergizedLess than 210
CHECK VOLTAGE BETWEEN LINE NEUTRAL
AND LOW VOLTAGE C" TERMINAL
Red LED
Recall
Red LED
Recall
CHECK VOLTAGE BETWEEN LINE HOT
AND LINE NEUTRAL
FIGURE 58
Page 46
Page 46
V−TYPICAL OPERATING CHARACTERISTICS
A−Blower Operation and Adjustment1
NOTE− The following is a generalized procedure and
does not apply to all thermostat controls.
1 − Blower operation is dependent on thermostat control
system.
2 − Generally, blower operation is set at thermostat sub-
base fan switch. With fan switch in ON position, blower
operates continuously. With fan switch in AUTO position,
blower cycles with demand or runs continuously while
heating or cooling circuit cycles.
3 − Depending on the type of indoor thermostat, blower
and entire unit will be off when the system switch is in
OFF position.
B−Temperature Rise (Figure 59)
Temperature rise for EL195UHE units depends on unit input, blower speed, blower horsepower and static pressure
as marked on the unit rating plate. The blower speed must
be set for unit operation within the range of TEMP. RISE
°F" listed on the unit rating plate.
FIGURE 59
TEMPERATURE RISE
Supply Duct Temperature
Return Duct Temperature
_
Temperature Rise =
SUPPLY
AIR
Temperatures
RETURN AIR
C−External Static Pressure
1 − Tap locations shown in figure 60.
2 − Punch a 1/4" diameter hole in supply and return air ple-
nums. Insert manometer hose flush with inside edge of
hole or insulation. Seal around the hose with perma-
gum. Connect the zero end of the manometer to the
discharge (supply) side of the system. On ducted sys-
tems, connect the other end of manometer to the return
duct as above.
3 − With only the blower motor running and the evaporator
coil dry, observe the manometer reading. Adjust blow-
er motor speed to deliver the air desired according to
the job requirements. For heating speed external static
pressure drop must not be more than 0.5" W.C. For
cooling speed external static pressure drop must not
be more than 0.8" W.C.
4 − Seal the hole when the check is complete.
FIGURE 61
EXTERNAL STATIC PRESSURE
Supply Duct Static
Return Duct Static +
Total Duct Static =
(dry coil)
Duct Static
or
Supply Air
Return Air
High +"
Low −"
+
−
D−Blower Speed Taps
Blower speed tap changes are made on the integrated control. See figure 3 or 58. The heating tap is connected to the
HEAT" terminal and the cooling tap is connected to the
COOL" terminal. On all units the continuous blower tap is
connected to the FAN" terminal. Unused taps must be secured on two dummy terminals labeled "PARK. To change
out existing speed tap, turn off power and switch out speed
tap with tap connected to PARK". See blower speed tap
table on unit diagram for motor tap colors for each speed.
Page 47
Page 47
VI−MAINTENANCE
WARNING
ELECTRICAL SHOCK, FIRE,
OR EXPLOSION HAZARD.
Failure to follow safety warnings exactly could result
in dangerous operation, serious injury, death or
property damage.
Improper servicing could result in dangerous operation, serious injury, death, or property damage.
Before servicing, disconnect all electrical power to
furnace.
When servicing controls, label all wires prior to disconnecting. Take care to reconnect wires correctly.
Verify proper operation after servicing.
At the beginning of each heating season, system should be
checked as follows by a qualified service technician:
Blower
Check the blower wheel for debris and clean if necessary.
The blower motors are prelubricated for extended bearing
life. No further lubrication is needed.
WARNING
The blower access panel must be securely in place
when the blower and burners are operating. Gas
fumes, which could contain carbon monoxide, can
be drawn into living space resulting in personal injury or death.
Filters
All air filters are installed external to the unit. Filters should
be inspected monthly. Clean or replace the filters when
necessary to ensure proper furnace operation. Table 21
lists recommended filter sizes.
TABLE 21
Furnace
Cabinet Width
Filter Size
Side ReturnBottom Return
17−1/2"16 X 25 X 1 (1)16 X 25 X 1 (1)
21"16 X 25 X 1 (1)20 X 25 X 1 (1)
24−1/2"16 X 25 X 1 (2)24 X 25 X 1 (1)
Exhaust and air intake pipes
Check the exhaust and air intake pipes and all connections
for tightness and to make sure there is no blockage.
NOTE − After any heavy snow, ice or frozen fog event the
furnace vent pipes may become restricted. Always check
the vent system and remove any snow or ice that may be
obstructing the plastic intake or exhaust pipes.
Electrical
1 − Check all wiring for loose connections.
2 − Check for the correct voltage at the furnace (furnace
operating). Correct voltage is 120VAC +
10%
3 − Check amp−draw using a true RMS meter on the blow-
er motor with blower access panel in place. See figure
62.
Unit Nameplate__________Actual__________
FIGURE 62
kVAr
kWh
COMMV3V1
V2
P
OFF
MR
EX
1
W
3
2
Check Motor Amp Draw
True RMS Meter
Winterizing and Condensate Trap Care
1 − Turn off power to the furnace.
2 − Have a shallow pan ready to empty condensate water.
3 − Remove the clean out cap from the condensate trap
and empty water. Inspect the trap then reinstall the
clean out cap.
Cleaning Heat Exchanger
If cleaning the heat exchanger becomes necessary, follow
the below procedures and refer to figure 1 when disassembling unit. Use papers or protective covering in front of furnace while removing heat exchanger assembly.
1 − Turn off electrical and gas supplies to the furnace.
2 − Remove the furnace access panels.
3 − Disconnect the 2 wires from the gas valve.
4 − Remove gas supply line connected to gas valve. Re-
move the burner box cover (if equipped) and remove
gas valve/manifold assembly.
5 − Remove sensor wire from sensor. Disconnect 2-pin
plug from the ignitor.
6 − Disconnect wires from flame roll−out switches.
7 − Disconnect combustion air intake pipe. It may be nec-
essary to cut the existing pipe to remove burner box
assembly.
8 − Remove four burner box screws at the vestibule panel
and remove burner box. Set burner box assembly
aside.
NOTE − If necessary, clean burners at this time. Follow
procedures outlined in Burner Cleaning section.
9 − Loosen the clamps to the flexible exhaust coupling.
10 − Disconnect condensate drain line from the cold end
Remove screws that secures the flue collar into place.
Remove flue collar. It may be necessary to cut the exit-
ing exhaust pipe for removal of the fitting.
Page 48
Page 48
12 − Mark and disconnect all combustion air pressure tub-
ing from cold end header collector box.
13 − Mark and remove wires from pressure switch assemb-
ly. Remove the assembly. Keep tubing attached to
pressure switches.
14 − Disconnect the plug from the combustion air inducer.
Remove two screws which secure combustion air inducer to collector box. Remove combustion air induc-
er assembly. Remove ground wire from vest panel.
15 − Disconnect the condensate drain line.
16 − Remove cold end header box.
17 − Remove electrical junction box from the side of the fur-
nace.
18 − Mark and disconnect any remaining wiring to heating
compartment components. Disengage strain relief
bushing and pull wiring and bushing through the hole in
the blower deck.
19 − Remove the primary limit from the vestibule panel.
20 − Remove two screws from the front cabinet flange at
the blower deck. Spread cabinet sides slightly to allow
clearance for removal of heat exchanger.
21 − Remove screws along vestibule sides and bottom
which secure vestibule panel and heat exchanger as-
sembly to cabinet. Remove two screws from blower
rail which secure bottom heat exchanger flange. Re-
move heat exchanger from furnace cabinet.
22 − Back wash heat exchanger with soapy water solution
or steam. If steam is used it must be below 275°F
(135°C) .
23 − Thoroughly rinse and drain the heat exchanger. Soap
solutions can be corrosive. Take care to rinse entire
assembly.
24 − Reinstall heat exchanger into cabinet making sure that
the clamshells of the heat exchanger assembly is en-
gaged properly into the support bracket on the blower
deck. Remove the indoor blower to view this area
through the blower opening.
25 − Re-secure the supporting screws along the vestibule
sides and bottom to the cabinet.
26 − Reinstall cabinet screws on front flange at blower
deck.
27 − Reinstall the primary limit on the vestibule panel.
28 − Route heating component wiring through hole in blow-
er deck and reinsert strain relief bushing.
29 − Reinstall electrical junction box.
30 − Reinstall the cold end header box.
31 − Reinstall the combustion air inducer. Reconnect the
plug to the wire harness.
32 − Reinstall pressure switches and reconnect pressure
switch wiring.
33 − Carefully connect combustion air pressure switch
tubing from pressure switches to proper ports on
cold end header collector box.
34 − Reconnect condensate drain line to the cold end
header box.
35 − Use securing screws to reinstall flue collar to the top
cap on the furnace. Reconnect exhaust piping and exhaust drain tubing.
36 − Replace flexible exhaust adapter on combustion air in-
ducer and flue collar. Secure using two existing hose
clamps.
37 − Reinstall burner box assembly in vestibule area. Se-
cure burner box assembly to vestibule panel using
four existing screws. Make sure burners line up in
center of burner ports
38 − Reconnect flame roll−out switch wires.
39 − Reconnect sensor wire and reconnect 2−pin plug from
ignitor.
40 − Reinstall gas valve manifold assembly. Reconnect
gas supply line to gas valve.
41 − Reconnect the combustion air intake pipe.
42 − Reinstall burner box cover.
43 − Reconnect wires to gas valve.
44 − Replace the blower compartment access panel.
45 − Reconnect gas supply piping. Turn on power and gas
supply to unit.
46− Follow lighting instructions on unit nameplate to light
and operate furnace for 5 minutes to ensure the fur-
nace is operating properly.
47− Check all piping connections, factory and field, for gas
leaks. Use a leak detecting solution or other preferred
means.
48− Replace heating compartment access panel.
CAUTION
Some soaps used for leak detection are corrosive to
certain metals. Carefully rinse piping thoroughly after leak test has been completed. Do not use
matches, candles, flame or other sources of ignition
to check for gas leaks.
Page 49
Page 49
Cleaning the Burner Assembly (if needed)
1 − Turn off electrical and gas power supplies to furnace.
Remove upper and lower furnace access panels.
2 − Disconnect the wires from the gas valve.
3 − Remove the burner box cover (if equipped).
4 − Disconnect the gas supply line from the gas valve. Re-
move gas valve/manifold assembly.
5 − Mark and disconnect sensor wire from the sensor. Dis-
connect wires from flame rollout switches.
6 − Disconnect combustion air intake pipe. It may be nec-
essary to cut the existing pipe to remove burner box
assembly.
7 − Remove four screws which secure burner box assem-
bly to vest panel. Remove burner box from the unit.
8 − Use the soft brush attachment on a vacuum cleaner to
gently clean the face of the burners. Visually inspect
the inside of the burners and crossovers for any block-
age caused by foreign matter. Remove any blockage.
9 − Reinstall the burner box assembly using the existing
four screws. Make sure that the burners line up in the
center of the burner ports.
10 − Reconnect the sensor wire and reconnect the 2−pin
plug to the ignitor wiring harness. Reconnect wires to
flame rollout switches.
11 − Reinstall the gas valve manifold assembly. Reconnect
the gas supply line to the gas valve. Reinstall the burn-
er box cover.
12 − Reconnect wires to gas valve.
13 − Replace the blower compartment access panel.
14 − Refer to instruction on verifying gas and electrical con-
nections when re−establishing supplies.
15 − Follow lighting instructions to light and operate fur-
nace for 5 minutes to ensure that heat exchanger is
clean and dry and that furnace is operating properly.
16 − Replace heating compartment access panel.
Page 50
Page 50
VII−WIRING DIAGRAM AND SEQUENCE OF OPERATION
1 −Line voltage is applied to L1 and N. the T1 low voltage transformer is energized, and line voltage is applied to B3 indoor blower.
2 −S47 rollout switch(es) must be closed in order for 24V from transformer to be output on integrated control "R" to power thermostat.
3 −When there is a call for heat, W1 of the thermostat energizes W of the furnace control with 24VAC.
4 −A92 integrated control runs a self−check. S10 primary limit and S21 secondary limit contacts are found to be closed. Call for heat can continue.
5 −A92 integrated control energizes B6 combustion air inducer. S18 combustion air pressure switch closes . Once S18 closes, a 15−second
pre−purge follows.
6 −A92 integrated control energizes R33 ignitor. A 20−second warm−up period begins.
7 −GV1 gas valve opens for a 4−second trial for ignition
8 −Flame is sensed, gas valve remains open for the heat call.
9 −After 30−second delay (from flame sensed), A92 integrated control applies 24VAC to Heat speed of B3 indoor blower.
10 − When heat demand is satisfied, W1 of the indoor thermostat de−energizes W of A92integrated control which de−energizes GV1 gas valve.
B6 combustion air inducer continues a 5−second post−purge period, and B3 indoor blower completes a selected OFF time delay.
1
8
2
4
6
7
3
9
10
1
5
5
Page 51
Page 51
Troubleshooting: Heating Sequence of Operation
HEATING SEQUENCE OF OPERATION
NORMAL HEATING MODE
ABNORMAL HEATING MODE
CONTROL SELF−CHECK OKAY?
BURNER OFF?
NORMAL OPERATION:
LED SLOW FLASH
NO
YES
YES
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER DELAY OFF.
LED SLOW FLASH
(RESET CONTROL BY TURNING MAIN POWER OFF.)
LED FLASHES CODE 1 − POLARITY
REVERSED.
POWER ON
IS POLARITY CORRECT?
ROLLOUT SWITCH CLOSED?
THERMOSTAT CALLS FOR HEAT:
LED SLOW FLASH
IS COMBUSTION AIR
PRESSURE SWITCH OPEN?
LED FLASHES CODE 8 − ROLLOUT SWITCH OPEN.
GAS VALVE OFF. COMBUSTION AIR INDUCER ON.
INDOOR BLOWER ON.
SEQUENCE HOLDS UNTIL ROLLOUT SWITCH CLOSES
AND POWER IS RESET OR T’STAT IS INTERRUPTED
FOR MINIMUM OF 1 SECOND.
LED FLASHES CODE 12 − FLAME SENSED
WITHOUT GAS VALVE ENERGIZED.
GAS VALVE OFF. COMBUSTION AIR INDUCER ON.
INDOOR BLOWER ON HEATING SPEED.
LED FLASHES CODE 11 − PRESSURE
SWITCH CLOSED.
GAS VALVE OFF COMBUSTION AIR
INDUCER OFF. INDOOR BLOWER
OFF WITH DELAY.
(Sequence holds until pressure switch
opens or thermostat resets control.)
NO
NO
YES
YES
IS VOLTAGE
ABOVE 70 VOLTS?
LED FLASHES CODE 13 − LOW LINE VOLTAGE.
CONTROL WILL NOT RESPOND TO A CALL FOR
HEATING UNTIL VOLTAGE RISES ABOVE 75 VOLTS.
NO
NO
NO
IS COMBUSTION AIR INDUCER
ENERGIZED?
HAS COMBUSTION AIR PRESSURE
SWITCH CLOSED IN 2.5 MINUTES?
YES
YES
LED FLASHES CODE 9 − PRESSURE SWITCH FAILED
TO CLOSE OR OPENED DURING HEAT DEMAND.
PRESSURE SWITCH IS IN WATCHGUARD MODE. GAS
VALVE OFF. COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF WITH DELAY. IS 5-MINUTE
RESET PERIOD COMPLETE?
NO
PRIMARY LIMIT SWITCH. CLOSED?
YES
YES
CONTINUED NEXT PAGE
LED FLASHES CODE 7 − PRIMARY
LMIT OPEN. COMBUSTION AIR
INDUCER OFF.I NDOOR BLOWER ON
NO
YES
NO
YES
IS THERE A PROPER GROUND?
YES
NO
LED FLASHES CODE 2 − IMPROPER
GROUND.
YES
YES
Page 52
Page 52
Troubleshooting: Heating Sequence of Operation (Continued)
HEATING SEQUENCE CONTINUED
NORMAL HEATING MODEABNORMAL HEATING MODE
FLAME RECTIFICATION CURRENT
CHECK. CAN FLAME BE PROVEN WITHIN
4 SECONDS AFTER GAS VALVE OPENS?
(0.5 microamps)
FLAME PRESENT?
INDOOR BLOWER ON
AFTER 30−SECOND DELAY
PRIMARY LIMIT SWITCH CLOSED?
COMBUSTION AIR PRESSURE
SWITCH CLOSED?
LED FLASHES CODE 4 − LOW
FLAME SIGNAL.
(Does not affect operation of control)
LED FLASHES CODE 7 − PRIMARY LIMIT OPEN
GAS VALVE DE−ENERGIZED.
COMBUSTION AIR INDUCER DE−ENERGIZED.
INDOOR BLOWER ON UNTIL SWITCH CLOSES.
LIMIT SWITCH CLOSED?
GAS VALVE DE−ENERGIZED.
COMBUSTION AIR INDUCER ON.
INDOOR BLOWER OFF WITH DELAY
HAS CAI SWITCH CLOSED IN 2.5 MINUTES?
15-SECOND COMBUSTION AIR INDUCER PREPURGE
INITIATED BY CLOSED PRESSURE SWITCH.
YES
IGNITOR WARM-UP −− 20 SECONDS.
YES
YES
FLAME STABILIZATION PERIOD.
GAS VALVE OFF. COMBUSTION AIR INDUCER ON.
INDOOR BLOWER OFF.
HAS CONTROL FAILED TO SENSE FLAME FOR
FIVE CONSECUTIVE TRIES DURING A SINGLE
HEAT DEMAND?
LED SIGNAL WATCHGUARD FAILURE CODE
WATCHGUARD MODE. GAS VALVE OFF.
COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF WITH DELAY
IS 60-MINUTE RESET PERIOD COMPLETE?
YES
4 SECONDS
YES
HAS CONTROL RESET IGNITION
SEQUENCE FOUR TIMES?
FLAME SIGNAL 1.5 MICROAMPS OR GREATER?
YES
YES
YES
ROLLOUT SWITCH CLOSED?
LED FLASHES CODE 8 − ROLLOUT SWITCH OPEN.
GAS VALVE POWER OFF. COMBUSTION AIR INDUCER POWER
ON. INDOOR BLOWER ON SEQUENCE HOLDS UNTIL ROLLOUT
SWITCH IS RESET AND MAIN POWER IS INTERRUPTED OR
THERMOSTAT IS CYCLED OFF/ON FOR 1 SEC. MINIMUM.
YES
THERMOSTAT DEMAND SATISFIED.
LED SLOW FLASH.
COMB. AIR INDUCER CONTINUES 5-SECOND
POST PURGE AFTER T’STAT DEMAND IS SATISFIED.
INDOOR AIR BLOWER COMPLETES SELECTED OFF"
DELAY BEFORE SHUTTING OFF.
YES
NO
5-MINUTE PRESSURE SWITCH
WATCHGUARD MODE.
YES
IS VOLTAGE ABOVE 70 VOLTS?
LED FLASHES CODE 13 −
LOW LINE VOLTAGE.
ONCE VOLTAGE IS ABOVE
75 VOLTS, HEATING
SEQUENCE RESTARTS.
NO
YES
YES
YES
NO
NO
NO
NO
NO
NO
YES
YES
NO
NO
NO
YES
YES
HAS PRIMARY LIMIT RESET
TIME EXCEEDED 3 MINUTES?
LED FLASHES CODE
7 − PRIMARY LIMIT
OPEN. GAS VALVE,
COMB. AIR INDUCER
AND INDOOR BLOW-
ER OFF. LEDs SIGNAL
LIMIT SWITCH OPEN
UNTIL MAIN
POWER IS
INTERRUPTED OR
T’STAT IS CYCLED
OFF/ON FOR 1 SEC.
MINIMUM. 60−MINUTE
WATCHGUARD PE-
RIOD STARTS AT
TIME LIMIT CLOSES.
IS 60−MIN. PERIOD
COMPLETE?
NO
YES
4-SECOND TRIAL FOR IGNITION.
GAS VALVE OPENS. IGNITOR ENERGIZED FOR
FIRST 3 SECONDS OF THE TRIAL.
LED FLASHES
CODE 10
1 HR PRESSURE
SWITCH
WATCHGUARD
MODE
HAS PRESSURE SWITCH OPENED 5
TIMES IN SAME HEAT DEMAND
NO
YES
Page 53
Page 53
Troubleshooting: Cooling Sequence of Operation
COOLING SEQUENCE OF OPERATION
NORMAL COOLING MODEABNORMAL COOLING MODE
IGNITION CONTROL MAIN POWER ON.
CONTROL SELF DIAGNOSTIC CHECK.
IS CONTROL OPERATING NORMALLY?
YES
LED FLASHES CODE 1 POLARITY REVERSED
CONTROL WILL CONTINUE TO CALL FOR COOLING IN
THIS CONDITION.
POWER ON
LED FLASHES STEADY − CIRCUIT BOARD FAILURE
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF WITH NORMAL DELAY.
INTERRUPT MAIN POWER TO RESET CONTROL.
YES
IS POLARITY CORRECT?
ROLLOUT SWITCH MONITORED CONTINUOUSLY.
IS ROLLOUT SWITCH CLOSED?
LED: SLOW FLASH RATE REMAINS UNCHANGED
THROUGHOUT COOLING CYCLE.
THERMOSTAT CALLS FOR COOLING.
COMPRESSOR CONTACTOR AND SYSTEM FAN
ENERGIZED WITH 2-SECOND DELAY
(COOLING SPEED)
COMPRESSOR OFF.
THERMOSTAT OPENS.
SYSTEM FAN AND EAC TERM. OFF
WITH 45-SECOND DELAY.
NO
NO
LED FLASHES CODE 8 ROLLOUT SWITCH OPEN. GAS
VALVE OFF. COMBUSTION AIR INDUCER ON. INDOOR
BLOWER ON. SEQUENCE HOLDS UNTIL ROLLOUT SWITCH
CLOSES AND MAIN POWER IS INTERRUPTED OR
THERMOSTAT IS CYCLED OFF/ON FOR 1 SEC. MINIMUM.
IS VOLTAGE
ABOVE 70 VOLTS?
LED FLASHES CODE 13 LOW VOLTAGE. CONTROL
WILL CONTINUE TO CALL FOR COOLING
IN THIS CONDITION.
YES
YES
NO
NO
IS THERE A PROPER GROUND?
YES
NO
LED FLASHES CODE 2 IMPROPER GROUND
CONTROL WILL CONTINUE TO CALL FOR COOLING
IN THIS CONDITION.
Page 54
Page 54
Troubleshooting: Continuous Fan / Accessories Sequence of Operation
CONTINUOUS FAN / ACCESSORIES SEQUENCE OF OPERATION
LED: SLOW FLASH RATE REMAINS
UNCHANGED THROUGHOUT SEQUENCE.
MANUAL FAN SELECTION MADE AT THERMOSTAT.
CONTROL (G) ENERGIZES SYSTEM FAN AT FAN
SPEED. EAC TERMINAL IS ENERGIZED.
THERMOSTAT CALLS FOR HEAT (W).
THERMOSTAT CALLS FOR COOLING.
THERMOSTAT OPENS.
SYSTEM FAN SWITCHED TO COOL SPEED.
EAC TERM. REMAINS ON.
THERMOSTAT OPENS.
MANUAL FAN SELECTION MADE AT THERMOSTAT.
CONTROL (G) ENERGIZES SYSTEM FAN AT FAN
SPEED. EAC TERM. ENERGIZED.
NO
YES
YES
NO
SYSTEM FAN SWITCHES TO HEAT SPEAD AFTER 30
SECOND DELAY. EAC AND HUM TERMINALS REMAIN ON.
SYSTEM FAN CONTINUES FAN SPEED WITHOUT
INTERRUPTION. EAC TERMINAL REMAIN ON.
HUM TERMINALS ARE ENERGIZED WITH
COMBUSTION AIR BLOWER.
HUM. TERMINALS OFF AFTER POST PURGE
BY COMBUSTION AIR INDUCER. SYTEM FAN
SWITCHES TO FAN SPEED AFTER BLOWER
OFF DELAY. EAC CONTINUES WITHOUT
INTERUPTION.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.