Lennox EL195UHE, EL195UH045XE36B, EL195UH110XE60C, EL195UH135XE60D, EL195UH070XE36B Unit Information

...
Page 1
Page 1
© 2011 Lennox Industries Inc.
Litho U.S.A.
Corp. 1118−L4
Revised 11/2011
EL195UHE
Service Literature
EL195UHE series units are high−efficiency gas fur­naces manufactured with Lennox DuralokPlust alumi- nized steel clamshell−type heat exchangers, with a stainless steel condensing coil. EL195UHE units are a vailable in heating input capacities of 44,000 to 132,000 Btuh and cooling applications from 2 through 5 tons. Refer to Engineer­ing Handbook for proper sizing.
Units are factory equipped for use with natural gas. A kit is available for conversion to LP/Propane operation. All EL195UHE units are equipped with a hot surface ignition system. The gas valve is redundant to assure safety shut−off as required by C.S.A.
The heat exchanger, burners and manifold assembly can be removed for inspection and service. The maintenance section gives a detailed description on how this is done.
All specifications are subject to change. Procedures outlined in this manual are presented as a recommendation only and do not supersede or replace local or state codes.
WARNING
Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at discon­nect switch(es). Unit may have multiple power supplies.
Table of Contents
Specifications 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Optional Accessories 3. . . . . . . . . . . . . . . . . . . . . . . . . .
Blower Performance Data 4. . . . . . . . . . . . . . . . . . . . . .
I−Unit Components 7. . . . . . . . . . . . . . . . . . . . . . . . . . . .
II Placement and Installation 19. . . . . . . . . . . . . . . . . . . .
III−Start−Up 42. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
IV−Heating System Service Checks 43. . . . . . . . . . . . . .
V−Typical Operating Conditions 46. . . . . . . . . . . . . . . . .
VI−Maintenance 47. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
VII−Sequence of Operation and Flow Charts 50. . . . . .
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, person­al injury or loss of life. Installation and service must be performed by a licensed professional installer (or equivalent), service agency or the gas supplier.
WARNING
Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury.
Page 2
SPECIFICATIONS
Gas Heating Performance
Temperature rise range - °F 25 - 55 40 - 70 40 - 70
Gas Manifold Pressure (in. w.g.)
Nat. Gas / LPG/Propane
High static - in. w.g. 0.5 0.5 0.5
Connections
Intake / Exhaust Pipe (PVC) 2 / 2 2 / 2 2 / 2
in.
Condensate Drain Trap (PVC pipe) - i.d. 1/2 1/2 1/2
with furnished 90° street elbow 1/2 slip x 1/2 Mipt 1/2 slip x 1/2 Mipt 1/2 slip x 1/2 Mipt
with eld supplied (PVC coupling) - o.d. 1/2 slip x 1/2 Npt 1/2 slip x 1/2 Npt 1/2 slip x 1/2 Npt
Indoor
Wheel nom. dia. x width - in. 10 x 8 10 x 8 10 x 10
Blower
Tons of add-on cooling 1.5 - 3 1.5 - 3 2.5 - 4
Air Volume Range - cfm 360 - 1345 495 - 1380 715 - 1740
Electrical Data Voltage 120 volts - 60 hertz - 1 phase
Blower motor full load amps 6.8 6.8 8.4
Maximum overcurrent protection 12 12 12
Shipping Data lbs. - 1 package 129 136 160
NOTE - Filters and provisions for mounting are not furnished and must be eld provided.
1
Annual Fuel Utilization Efciency based on DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non-weatherized
furnaces.
Model No. EL195UH045XE36B EL195UH070XE36B EL195UH090XE48C
1
AFUE 95% 95% 95%
Input - Btuh 44,000 66,000 88,000
Output - Btuh 42,000 63,000 85,000
3.5 / 10 3.5 / 10 3.5 / 10
Gas pipe size IPS 1/2 1/2 1/2
Motor output - hp 1/2 1/2 3/4
SPECIFICATIONS
Gas Heating Performance
Temperature rise range - °F 40 - 70 45 - 75
Gas Manifold Pressure (in. w.g.)
Nat. Gas / LPG/Propane
High static - in. w.g. 0.5 0.5
Connections
Intake / Exhaust Pipe (PVC) 2 / 2 2 / 2
in.
Condensate Drain Trap (PVC pipe) - i.d. 1/2 1/2
with furnished 90° street elbow 1/2 slip x 1/2 Mipt 1/2 slip x 1/2 Mipt
with eld supplied (PVC coupling) - o.d. 1/2 slip x 1/2 Npt 1/2 slip x 1/2 Npt
Indoor
Wheel nom. dia. x width - in. 11-1/2 x 10 11-1/2 x 10
Blower
Tons of add-on cooling 3 - 5 3.5 - 5
Air Volume Range - cfm 1010 - 2220 1235 - 2405
Electrical Data Voltage 120 volts - 60 hertz - 1 phase
Blower motor full load amps 10.9 10.9
Maximum overcurrent protection 12 12
Shipping Data lbs. - 1 package 170 187
NOTE - Filters and provisions for mounting are not furnished and must be eld provided.
1
Annual Fuel Utilization Efciency based on DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non-weatherized
furnaces.
Model No. EL195UH110XE60C EL195UH135XE60D
1
AFUE 95% 95%
Input - Btuh 110,000 132,000
Output - Btuh 105,000 126,000
3.5 / 10 3.5 / 10
Gas pipe size IPS 1/2 1/2
Motor output - hp 1 1
Page 2
Page 3
OPTIONAL ACCESSORIES - MUST BE ORDERED EXTRA
“B” Width
Models
CABINET ACCESSORIES
Horizontal Suspension Kit - Horizontal only 51W10 51W10 51W10
Return Air Base - Upow only 50W98 50W99 51W00
CONDENSATE DRAIN KITS
Condensate Drain Heat Cable 6 ft. 26K68 26K68 26K68
24 ft. 26K69 26K69 26K69
50 ft. 26K70 26K70 26K70
Heat Cable Tape Fiberglass - 1/2 in. x 66 ft. 36G53 36G53 36G53
Aluminum foil - 2 in. x 60 ft. 16P89 16P89 16P89
Crawl Space Vent Drain Kit 51W18 51W18 51W18
FILTER KITS
1
Air Filter and
Rack Kit
Horizontal (end) Size of lter - in. 87L96 - 18 x 25 x 1 87L97 - 20 x 25 x 1 87L98 - 25 x 25 x 1
Side Return Single 44J22 44J22 44J22
Ten Pack 66K63 66K63 66K63
Size of lter - in. 16 x 25 x 1 16 x 25 x 1 16 x 25 x 1
NIGHT SERVICE KIT
Night Service Kit 84W84 84W84 84W84
Safety Service Kit 89W20 89W20 89W20
TERMINATION KITS
See Installation Instructions for specic venting information.
Termination Kits ­Direct Vent Applications Only
Termination Kits ­Direct or Non­Direct vent
Roof Termination Flashing Kit - Direct or
Non-Direct Vent (2 ashings)
1
Cleanable polyurethane frame type lter.
2
Kits contain enough parts for two, non−direct vent installations.
3
Non−direct vent only.
NOTE - Termination Kits 44W92, 44W93, 30G28, 81J20 are certied to ULC S636 standard for use in Canada only.
Concentric US - 2 in. 71M80 69M29 - - -
3 in. - - - 60L46 60L46
Canada - 2 in. 44W92 44W92 - - -
3 in. - - - 44W93 44W93
Flush-Mount 2, 2-1/2 or 3 in. 51W11 51W11 51W11
Wall - Close
Couple
Wall - Close
Couple WTK
US - 2 in. 22G44 - - - - - -
3 in. 44J40 44J40 44J40
Canada - 2 in. 30G28 - - - - - -
3 in. 81J20 81J20 81J20
Roof 2 in. 15F75 15F75 - - -
Wall Ring Kit 2 in. 15F74
2 in. 44J41 44J41 44J41
“C” Width
“D” Width
Models
3
15F74 - - -
Models
GAS HEAT ACCESSORIES
High Altitude
Input
045 No Change 80W60 69W73 73W81 73W37 68W68
070 80W66 80W59 69W73 73W81 73W37 68W68
090 80W65 80W59 69W73 73W81 73W37 68W68
110 80W66 80W59 69W73 73W81 73W37 68W68
135 80W65 80W59 69W73 73W81 73W37 68W68
Pressure Switch Kit
4501 - 7500 ft. 7501 - 10,000 ft. 0 - 7500 ft. 0 - 7500 ft. 7501- 10,000 ft. 7501- 10,000 ft.
Natural Gas to
LPG/Propane Kit
Page 3
LPG/Propane
to Natural Gas Kit
Natural Gas
High Altitude
Orice Kit
LPG/Propane
High Altitude
Orice Kit
Page 4
BLOWER DATA
EL195UH045XE36B PERFORMANCE (Less Filter)
External
Static
Pressure
in. w.g.
0.00 1345 340 1255 245 1150 185 895 105 845 95
0.10 1305 345 1225 250 1105 200 855 11 0 810 95
0.20 1290 360 1190 260 1080 205 825 120 780 105
0.30 1275 370 1150 270 1045 215 785 125 720 110
0.40 1220 385 1120 280 1015 220 735 135 690 120
0.50 1215 390 1090 290 980 230 705 140 635 125
0.60 1190 395 1060 300 950 240 650 150 600 135
0.70 1140 390 1015 300 900 250 620 155 555 140
0.80 1100 380 1000 310 870 260 580 160 520 145
0.90 970 345 930 305 825 260 535 165 460 150
EL195UH070XE36B PERFORMANCE (Less Filter)
External
Static
Pressure
in. w.g.
0.00 1380 315 1305 250 1190 200 965 105 920 100
0.10 1360 325 1270 255 1180 205 915 11 5 865 100
0.20 1310 335 1250 265 1130 215 880 120 815 11 0
0.30 1275 340 1205 275 1100 225 835 125 775 11 5
0.40 1250 355 1175 280 1065 230 795 135 730 125
0.50 1215 370 1145 295 1045 240 745 145 670 130
0.60 1200 380 1100 310 995 245 705 150 640 140
0.70 1145 380 1070 310 960 255 670 160 585 145
0.80 1070 370 1035 320 925 265 610 165 550 155
0.90 1015 365 1005 330 880 270 580 175 495 155
High Medium-High Medium Medium-Low Low
cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts
High Medium-High Medium Medium-Low Low
cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts
Air Volume / Watts at Various Blower Speeds
Air Volume / Watts at Various Blower Speeds
EL195UH090XE48C PERFORMANCE (Less Filter)
External
Static
Pressure
in. w.g.
0.00 1740 370 1505 250 1370 195 1285 160 1135 125
0.10 1695 390 1470 265 1325 205 1240 170 1090 135
0.20 1660 405 1435 280 1290 220 1195 185 1045 145
0.30 1615 415 1390 295 1240 235 1140 200 995 160
0.40 1590 425 1350 305 1200 245 1110 210 945 165
0.50 1560 440 1310 320 1155 260 1055 225 895 175
0.60 1525 455 1255 335 1105 270 1005 230 855 190
0.70 1475 470 1220 340 1065 285 960 245 805 200
0.80 1410 470 1170 355 1010 295 920 255 760 210
0.90 1305 430 1130 370 985 305 875 265 715 220
High Medium-High Medium Medium-Low Low
cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts
Air Volume / Watts at Various Blower Speeds
Page 4
Page 5
BLOWER DATA
EL195UH110XE60C PERFORMANCE (Less Filter)
Air Volume / Watts at Different Blower Speeds
External
Static
Pressure
in. w.g.
0.00 2220 645 1940 435 1765 335 1635 280 1435 200 2185 655 1915 440 1745 340 1620 275 1430 195
0.10 2170 660 1920 460 1715 350 1595 290 1380 205 2160 660 1880 460 1705 345 1570 285 1380 205
0.20 2130 680 1865 475 1670 370 1560 305 1345 220 2115 680 1835 470 1670 365 1535 305 1325 220
0.30 2095 700 1835 490 1640 390 1525 325 1285 230 2060 705 1795 495 1630 380 1505 320 1285 230
0.40 2065
0.50 2030 740 1755 525 1560 415 1425 355 1215 260 2000 740 1720 530 1535 415 1410 345 1195 260
0.60 1995 760 1705 550 1525 435 1380 370 1150 270 1955 760 1685 550 1505 435 1380 365 1145 275
0.70 1955 770 1660 560 1475 450 1350 375 1100 290 1935 775 1650 555 1455 450 1325 375 1100 285
0.80 1930 790 1635 575 1445 460 1300 395 1050 305 1890 790 1610 575 1425 460 1285 390 1055 295
0.90 1865 775 1580 595 1400 480 1250 410 1025 310 1840 780 1565 585 1390 475 1240 395 1010 310
Bottom Return Air, Side Return Air with Optional Return Air Base, Return Air from Both Sides or Return Air from Bottom and One Side.
High Med-High Medium Med-Low Low High Med-High Medium Med-Low Low
cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts
720 1785 510 1600 405 1465 335 1250 245 2050 720 1760 510 1570 400 1455 330 1235 245
Single Side Return Air − Air volumes in bold require eld
fabricated transition to accommodate 20 x 25 x 1 in. air lter in order to maintain proper air velocity.
EL195UH135XE60D PERFORMANCE (Less Filter)
Air Volume / Watts at Different Blower Speeds
External
Static
Pressure
in. w.g.
0.00 2405 940 2235 735 2070 545 1830 390 1620 280 2395 925 2235 710 2020 550 1800 380 1610 275
0.10 2365 960 2210 745 2020 565 1770 400 1585 295 2360 935 2175 735 2005 555 1760 395 1550 295
0.20 2330 975 2180 770 1950 580 1745 420 1535 315 2350 955 2160 760 1955 565 1725 415 1510 300
0.30 2295 1000 2120 785 1925 595 1690 435 1480 325 2290 990 2095 775 1890 590 1700 435 1420 325
0.40 2275
0.50 2225 1025 2035 815 1845 630 1605 475 1395 360 2230 1010 2040 815 1845 625 1590 470 1375 360
0.60 2185 1010 2020 835 1815 645 1565 485 1330 365 2170 1025 2000 820 1795 640 1580 485 1335 370
0.70 2085 1005 1940 850 1735 665 1520 500 1310 385 2125 1010 1935 845 1725 660 1520 500 1295 385
0.80 2010 970 1890 860 1715 680 1465 510 1285 400 2025 980 1880 855 1705 680 1470 510 1260 405
0.90 1925 935 1830 840 1660 700 1415 530 1235 410 1945 935 1860 855 1695 695 1435 525 1220 410
Bottom Return Air, Side Return Air with Optional Return Air Base, Return Air from Both Sides or Return Air from Bottom and One Side.
High Med-High Medium Med-Low Low High Med-High Medium Med-Low Low
cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts
1015 2075 805 1885 615 1640 460 1445 340 2255 995 2060 795 1850 615 1635 445 1390 340
Single Side Return Air − Air volumes in bold require eld
fabricated transition to accommodate 20 x 25 x 1 in. air lter in order to maintain proper air velocity.
Page 5
Page 6
Page 6
EL195UHE PARTS IDENTIFICATION
FIGURE 1
TOP CAP
BURNER BOX
ASSEMBLY
DuralokPlus
TM
HEAT EXCHANGER
ASSEMBLY
CONTROL BOX
(includes integrated ignition control, trans-
former, circuit breaker and interlock switch)
COMBUSTION AIR
INDUCER
OUTER
ACCESS
PANEL
COMBUSTION
AIR PRESSURE
SWITCH
PRIMARY LIMIT
GAS VALVE
BLOWER
ASSEMBLY
FLEXIBLE NO−HUB EXHAUST COLLAR
COLD END
HEADER BOX
BAG ASSEMBLIES
(shipping location)
BLOWER ACCESS
PAN EL
Page 7
Page 7
I−UNIT COMPONENTS
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
CAUTION
Electrostatic discharge can affect elec­tronic components. Take precautions to neutralize electrostatic charge by touching your hand and tools to metal prior to handling the control.
EL195UHE unit components are shown in figure 1. The combustion air inducer, gas valve and burners can be ac­cessed by removing the outer access panel. The blower and control box can be accessed by removing the blow­er access panel.
A−Control Box Components (Figure 2)
Unit transformer (T1) and integrated ignition control (A92) are located in the control box. In addition, a door interlock switch (S51) is located in the control box.
FIGURE 2
EL195UHE Control Box
Integrated Control
Door Interlock
Switch
Transformer
Circuit Breaker
1. Transformer (T1)
A transformer located in the control box provides power to the low voltage section of the unit. The transformers on all models are rated at 40VA with a 120V primary and 24V secondary.
2. Door Interlock Switch (S51)
A door interlock switch rated 14A at 120VAC is located on the control box. The switch is wired in series with line volt­age. When the blower door is removed the unit will shut down.
3. Circuit Breaker (CB8)
A 24V circuit breaker is also located in the control box. The switch provides overcurrent protection to the transformer (T1). The breaker is rated at 3A at 32V. If the current ex­ceeds this limit the breaker will trip and all unit operation will shutdown. The breaker can be manually reset by pressing the button on the face.
4. Integrated Ignition Control (A92)
WARNING
Shock hazard. Disconnect power before servicing. Control is not
field repairable. If control is inoperable, simply re­place entire control.
Can cause injury or death. Unsafe operation will re­sult if repair is attempted.
The hot surface ignition control system consisting of an in­tegrated control (figure 3 with control terminal designa­tions in tables 1, 2 and 3), sensor and ignitor (figure 5). The integrated control and ignitor work in combination to en­sure furnace ignition and ignitor durability. The integrated control, controls all major furnace operations. The inte­grated control also features a RED LED for troubleshoot­ing and two accessory terminals rated at (1) one amp. See table 4 for troubleshooting diagnostic codes. The nitride ignitor is made from a non−porous, high strength propri­etary ceramic material that provides long life and trouble free maintenance.
TABLE 1
4−Pin Terminal Designation
PIN # FUNCTION
1 Combustion Air Inducer Line
2
Ignitor Line
3
Combustion Air Inducer Neutral
4
Ignitor Neutral
TABLE 2
12−Pin Terminal Designations
PIN # FUNCTION
1 High Limit Output
2 Not Used
3 24V Line
4 Not Used
5 Rollout Switch Out
6 24V Neutral
7 High Limit Input
8 Ground
9 Gas Valve Common
10 Pressure Switch In
11 Rollout Switch In
12 Gas Valve Out
Page 8
Page 8
TABLE 3
1/4" QUICK CONNECT TERMINALS
120HUM Humidifier 120VAC
LINE 120VAC
XFMR Transformer 120VAC
CIRC Indoor blower 120VAC
EAC Indoor air quality accessory 120VAC
NEUTRALS Common 120VAC
HUM24 Humidifier 24VAC
3/16" QUICK CONNECT TERMINALS
COOL Cooling tap 24VAC
HEAT Heating tap 24VAC
FAN Continuous blower 24 VAC
PARK (no power) Park terminal for unused speed taps
FS Flame sense
24 COM Common 24VAC
TABLE 4
The integrated control is equipped with an LED light for troubleshooting. The diagnostic codes are listed below in table 4.
RED LED
Flash Code
Diagnostic Codes / Status of Furnace
Off No power to control or board fault detected
On Board fault detected,
Heartbeat
1
Control powered − displayed during all modes of operation if no errors are detected
1 Reverse Line Voltage Polarity
2 Improper Earth Ground
3 Burner failed to light, or lost flame during heat demand
4 Low Flame Signal − check flame sensor
5 Watchguard − burner failed to light, exceeded maximum number of retries or recycles.
6 Not Used
7
Primary or Secondary Limit Open or Watchguard Mode − Limit Switch Open longer than 3 min­utes
8 Rollout Switch Open
9 Pressure Switch failed to close or opened during heat demand
10 Watchguard − Pressure Switch opened 5 times during one heat demand
11 Pressure Switch stuck closed prior to activation of combustion air inducer
12 Flame Sensed without gas valve energized
13 Low Line Voltage
Notes
Note 1 A "Heartbeat" is indicated by a "Slow Flash" − 1 sec on 1 sec off, repeating
Note
Error codes are indicated by a "Rapid Flash" − the LED flashes X times at 1/2 sec on 1/2 sec off, remains off for 3 sec, then repeats
Note
Last 10 error codes are stored in memory including when power is shut off to the unit. − To recall, press and release button, most recent will be displayed first, LED off for 3 sec, then next error code is displayed, etc. To clear error codes, depress and hold button longer than 5 seconds.
Page 9
Page 9
FIGURE 3
INTEGRATED CONTROL
(Automatic Hot Surface Ignition System)
BLOWER OFF DELAY
RED LED
RECALL BUTTON
Electronic Ignition
On a call for heat the integrated control monitors the com­bustion air inducer pressure switch. The control board will not begin the heating cycle if the pressure switch is closed (by−passed). Once the pressure switch is determined to be open, the combustion air inducer is energized. When the differential in the pressure switch is great enough, the pres­sure switch closes and a 15−second pre−purge begins. If the pressure switch is not proven within 2−1/2 minutes, the integrated control goes into Watchguard−Pressure Switch mode for a 5−minute re−set period. After the 15−second pre−purge period, the ignitor warms up for 20 seconds during which the gas valve opens at 19 sec­onds for a 4−second trial for ignition. The ignitor remains energized for the first 3 seconds during the 4 second trial. If ignition is not proved during the 4−second period, the inte­grated control will try four more times with an inter purge and warm−up time between trials of 35 seconds. After a to-
tal of five trials for ignition (including the initial trial), the inte­grated control goes into Watchguard−Flame Failure mode. After a 60−minute reset period, the integrated control will begin the ignition sequence again.
Fan Time Control
Heating Fan On Time
The fan on time of 30 seconds is not adjustable.
Heating Fan Off Time
Fan off time (time that the blower operates after the heat demand has been satisfied) can be adjusted by moving the jumper to a different setting. The unit is shipped with a fac­tory fan off setting of 90 seconds. For customized comfort, monitor the supply air temperature once the heat demand is satisfied. Note the supply air temperature at the instant the blower is de−energized. Adjust the fan−off delay to achieve a supply air temperature between 90° − 110° at the instant the blower is de−ener­gized. (Longer delay times allow for lower air temperature, shorter delay times allow for higher air temperature). See figure 4.
Cooling Fan On Time
The fan on time is 2 seconds and is not adjustable.
Cooling Fan Off Time
The control has a 45 second fan off delay after cooling de­mand has been met. This delay is factory set and not ad­justable.
HEAT FAN-OFF TIME IN SECONDS
To adjust fan−off timing, reposition jumper across pins to
achieve desired setting.
NO JUMPER
FIGURE 4
60
90
120
180
60
90
120
180
60
90
120
180
60
90
120
180
60 Second
off Time
90 Second
off Time
120 Second
off Time
180 Second
off Time
Page 10
Page 10
FIGURE 5
EL195UHE Burner Box Assembly
Gas Valve
Burner Box Front
Rollout Switch(s)
Flame Sensor
Ignitor
Burner Assembly
B−Heating Components
Combustion air inducer (B6), primary limit control (S10), ig­nitor, burners, flame rollout switch (S47), gas valve (GV1), combustion air pressure switch (S18), and heat exchangers are located in the heating compartment. The heating compartment can be accessed by removing the outer ac­cess panel.
1. Flame Rollout Switches (Figure 5)
Flame rollout switches S47 are SPST N.C. high temperature limits located on the left and right of the front buner box plate. S47 is wired to the burner ignition control A92. When ei­ther of the switches sense flame rollout (indicating a blockage in the combustion passages), the flame rollout switch trips, and the ignition control immediately closes the gas valve . Switch S47 in all EL195UHE units is factory preset to open at 210_F +
12_F (99_C + 6.7_C) on a tem­perature rise. All flame rollout switches are manual reset. See table 4 flash code 8 for troubleshooting.
2. Heat Exchanger (Figure 6)
EL195UHE units use an aluminized steel primary and stainless steel secondary heat exchanger assembly. Heat is transferred to the air stream from all surfaces of the heat exchanger. The shape of the heat exchanger en­sures maximum efficiency.
The combustion air inducer pulls fresh air through the burn­er box. This air is mixed with gas in the burners. The gas / air mixture is then burned at the entrance of each clam­she ll. Combustion gases are then pulled through the primary and secondary heat exchangers and exhausted out the ex­haust vent pipe.
3. Primary Limit Control (Figure 6)
Primary limit (S10) used on EL195UHE units is located in the heating vestibule panel. When excess heat is sensed in the heat exchanger, the limit will open. Once the limit opens, the furnace control energizes the supply air blower and de−en­ergizes the gas valve. The limit automatically resets when unit temperature returns to normal. The switch is factory set and cannot be adjusted. For limit replacement remove wires from limit terminals, remove mounting screws, rotate limit switch 90 degrees and slowly remove from the vesti­bule panel. Install replacement limit with sam e care. See table 4 flash code 7 for troubleshooting if limit switch opens during operation.
Page 11
Page 11
FIGURE 6
Primary Limit Location and Heat Exchanger
Install limit face down
4. Gas Valve (Figure 7)
The EL195UHE uses an internally redundant valve to assure safety shut-off. If the gas valve must be replaced, the same type valve must be used. 24VAC terminals and gas control switch are located on top of the valve. All terminals on the gas valve are con­nected to wires from the ignition control. 24V applied to the terminals opens the valve. Inlet and outlet pressure taps are located on the valve. A manifold adjustment screw is also located on the valve. An LP/Propane changeover kit is available.
FIGURE 7
GAS VALVE SHOWN IN ON POSITION
MANIFOLD
PRESSURE
OUTLET
PORT
INLET
PRESSURE
PORT
MANIFOLD PRESSURE
ADJUSTMENT SCREW
(under barbed fitting)
5. Flame Sensor (Figure 5)
A flame sensor is located on the left side of the burner sup­port. The sensor is mounted on the front burner box plate and the tip protrudes into the flame envelope of the left− most burner. The sensor can be removed for service (use steel wool only to clean) without removing any part of the burners. During operation, flame is sensed by current passed through the flame and sensing electrode. The igni­tion control allows the gas valve to remain open as long as flame signal is sensed.
NOTE − The EL195UHE is polarity sensitive. Make sure that the furnace is wired correctly and is properly grounded.
A microamp DC meter is needed to check the flame signal on the integrated control.
Flame (microamp) signal is an electrical current which passes from the integrated control to the sensor during unit operation. Current passes from the sensor through the flame to ground to complete a safety circuit.
To Measure Flame Signal − Integrated Control:
Use a digital readout meter capable of reading DC micro­amps. Se e fi gure 8 for flame signal check.
1 − Set the meter to the DC amps scale. 2 − Turn off supply voltage to control. 3 − Remove sensor wire from integrated control. 4 − Connect (−) lead to flame sensor wire. 5 − Connect (+) lead to Terminal FS on integrated control. 6 − Turn supply voltage on and close thermostat contacts to
cycle system.
7 − When main burners are in operation for two minutes, take
reading.
6. Ignitor (Figure 5)
EL195UHE units use a nitride ignitor made from a propri­etary ceramic material. To check ignitor, measure its resist­ance and voltage. A value of 39 to 70 ohms indicates a good ignitor. Voltage to the ignitor should be 102 − 132VAC. See figure 9 for resistance and voltage checks.
Page 12
Page 12
FIGURE 8
Measuring Flame Signal
Flame Signal In Microamps
Normal Low Drop Out
1.5
0.5 − 1.4
0.4
Set Dial to DC MicroAmps
(+)
MultiMeter
(+)
(+) To Control
Sensor Terminal
() T
o Flame
Terminal
Flame Sensor
Terminal
Flame Sensor
Wire
Intergrated
Control
Remove sensor from integrated
control and connect alligator clip
() to flame sensor lead.
Remove sensor from integrated control and connect alligator clip
(+) to terminal on control.
Page 13
Page 13
FIGURE 9
Test 1
Check ignitor circuit for correct resistance.
Remove 4−pin plug from control.
Check ohms reading across terminals 2 and 4.
Reading should be between 39 and 70 ohms. If
value is correct, this is the only test needed.
If the reading on the meter is not correct, (0 or
infinity) then a second test is needed.
Test 2
Check ignitor for correct resistance.
Seperate the 2−pin jack−plug near the manifold and check
resistance of ignitor at the plug. Reading should be
between 39 and 70 ohms. If the reading is correct, then
the problem is with the wiring between the jack−plug and
the control. If reading is not correct, the issue is the ignitor.
Test 3
Check ignitor for correct voltage
Insert meter probes into terminals 2 and 4 (use small
diameter probes in order not to damage plug).
Check voltage during 20 second ignitor warm up period.
Voltage should read 120 volts +
10%. If voltage reads below
these values, check for correct supply voltage to furnace.
MultiMeter
(set to ohms)
MultiMeter
(set to ohms)
MultiMeter
(set to VAC)
Page 14
Page 14
7. Combustion Air Inducer (B6)
& Cold End Header Box
All EL195UHE units use a combustion air inducer to move air through the burners and heat exchanger during heating operation. The blower uses a shaded pole 120VAC motor. The motor operates during all heating op­eration and is controlled by integrated control A92. Blower operates continuously while there is a call for heat. The in­tegrated control will not proceed with the ignition sequence until combustion air inducer operation is sensed by the prov­ing switches.
The combustion air inducer is installed on the cold end header box. The cold end header box is a single piece made of hard plastic. The box has an internal channel where the combustion air inducer creates negative pres­sure at unit start up. The channel contains an orifice used to regulate flow created by the combustion air inducer. The box has pressure taps for the combustion air inducer pressure switch hoses. The pressure switch measures the pressure across the combustion air inducer orifice or difference in the channel and the box. If replacement is
necessary the gaskets used to seal the box to the vestibule panel and the combustion air inducer to the box, must also be replaced.
TABLE 5
EL195UHE Unit
Combustion Air Inducer
Orifice Size
−045 0.618"
−070 0.810"
−090 0.973"
−110 1.040"
−135 1.235"
8. Combustion Air Pressure Switch
(Figure 10)
EL195UHE series units are equipped with a differential pressure switch located on the cold end header box. The switch monitors across the combustion air inducer orifice to in­sure proper flow through the heat exchanger.
The switch is a SPST N.O. pressure switch electrically con­nected to the integrated control. The purpose of the switch is to prevent burner operation if the combustion air inducer is not moving enough air for proper combustion.
FIGURE 10
Pressure Switch
On start-up, the switch monitors whether the combustion air inducer is operating. It closes a circuit to the integrated control when the difference in pressure across the com­bustion air inducer orifice exceeds a non−adjustable factory setting. If the switch does not successfully sense the re­quired differential, the switch cannot close and the fur­nace cannot operate. If the flue or air inlet become ob­structed during operation, the switch senses a loss of pressure differential and opens the circuit to the integrated control. If the condensate line is blocked, water will back up into the header box and reduce the pressure differential across the switch. The pressure switch opens if the differ­ential drops below the set point. See table 6.
Checks of pressure differential can aid in troubleshooting. When measuring the pressure differential, readings should be taken at the pressure switch. See figure 11and table 7. Lack of differential usually indicates problems in the intake or exhaust piping, but may indicate problems in the heat exchanger, condensing coil, header boxes, combustion inducer or other components.
TABLE 6
Unit
Altitude ft.
0 − 4500 4501 − 7500 7501 − 10000
Set Point w.c. Set Point w.c Set Point w.c.
−045 −0.65 −0.65 −0.60
−070 −0.90 −0.85 −0.65
−090 −0.90 −0.80 −0.65
−110 −0.90 −0.85 −0.65
−135 −0.90 −0.80 −0.65
*Set point is factory set and non−adjustable
Page 15
Page 15
To Cold End Header Box
Field Provided Tubing
To Pressure Switch
To Cold End Header Box
FIGURE 11
1 − Remove thermostat demand and allow unit to
cycle off.
2 − Install a tee in the negative (−) line (red tubing) and a
tee in the positive (+) line (black tubing) running from the pressure switch to the cold end header box.
3 − Install a manometer with hose from the negative (−)
side of the manometer to the tee installed in the negative (−) line and with hose from the positive (+) side of the manometer to the tee in the positive (+) line.
NOTE − Both sides of the cold end header box are nega­tive. However the (+) port reads less negative pressure than the (−) port.
4 − Operate unit and observe manometer reading.
Readings will change as heat exchanger warms.
a. Take one reading immediately after start-up. b. Take a second reading after unit has reached steady state (approximately 5 minutes). This will be the pressure differential.
The pressure differential should be greater than those listed in table 6.
5 − Remove thermostat demand and allow to cycle off.
6 − Remove manometer and tee’s. Reinstall combustion
air sensing hoses to the pressure switch.
Measuring Pressure Differential
Black Tubing
(positive +)
Red Tubing
(negative −)
+"
High
−"
Low
Page 16
Page 16
TABLE 7
Pressure Switch Troubleshooting Guide
Problem Corrective Action
Pressure switch stuck closed
Check that the pressure switch is open without the combustion air inducer operat­ing. Replace if defective.
Pressure switch does not close due to
obstruction in vent pipe.
Check for restricted vent. Remove all blockage. Check for proper vent sizing. See table 11.
Pressure switch does not close due to
incorrect routing of the pressure
switch tubing.
Check that the pressure switch tubing is correctly routed. Correctly route pressure witch line.
Pressure switch does not close due to
obstructions in the pressure switch
line.
Remove any obstructions from the the pressure switch line and/or taps
Pressure switch tubing damaged. Check pressure switch tubing for leaks. Replace damaged tubing if necessary.
Condensate in pressure switch tubing. Check pressure switch tubing for condensate. Remove condensate from tubing.
Pressure switch does not close due to
a low differential pressure across the
pressure switch.
Check the differential pressure across the pressure switch. Check for restricted inlet vent. Remove all blockage. Check for proper vent sizing and run length. See table11.
Wrong pressure switch installed in the
unit, or pressure switch is out of cal-
ibration
Check that the correct pressure switch is installed in the unit. Replace pressure switch if necessary.
Miswiring of furnace or improper con-
nections at pressure switch.
Check for correct wiring and loose connections. Correct wiring and/or replace any loose connections.
Pressure switch failure.
If all the above modes of failure have been checked, the pressure switch may have failed. Replace pressure switch and determine if unit will operate.
Damaged condensate trap. Check trap for any cracks or damage and replace if necessary.
Cold end header box does not drain
properly.
Check that the furnace is set properly with a slight tilt (0 − 1/2") towards the front if necessary. See furnace installation instruction.
Air leakage around the combustion air
inducer gasket.
Check gasket and replace if necessary.
Air leakage around the cold end head-
er box gasket.
Check gasket and replace if necessary.
Damaged cold end header box tubing. Check tubing and replace if necessary.
DEMAND
CAI
GAS VALVE
15
ON
OFF
38
IGNITOR
341
Pre −Purge Ignitor Warm−up
Trial for Ignition
Post
Purge
5 SEC80
*Blower on time will be 30 seconds after flame is sensed. Blower off time will depend on OFF TIME" Setting.
INDOOR BLOWER
ЙЙЙЙЙЙЙЙЙ
Blower On"*
Delay
ELECTRONIC IGNITION
FIGURE 12
Page 17
Page 17
C− Blower Compartment
IMPORTANT
Each blower is statically and dynamically bal­anced as an assembly before installation in the unit.
ML195UHE units are equipped with a constant torque ECM motor. It has a DC motor coupled to an electronic control module both contained in the same motor housing. The mo­tor is programmed to provide constant torque at each of the five selectable speed taps. Each tap requires 24 volts to en­ergize.
Input Voltage Requirements
The circuit is designed to be operated with AC voltage. To enable a tap requires 12 to 33VAC. Expected current draw will be less than 20mA.
Troubleshooting
Troubleshooting the motor is an easy process. Follow steps below.
1− Shut off power to unit.
2− Remove input plugs P48 and P49 from motor. See
figure 16 for troubleshooting procedure. If correct voltage is present in tests 1 and 2 and motor is not operating properly, replace motor. The motor is not field re­pairable.
If replacing the indoor blower motor or blower wheel is nec­essary, placement is critical. The blower wheel must be cen­tered in the blower housing as shown in figure 13. When re­placing the indoor blower motor the set screw must be aligned and tightened with the motor shaft as shown in figure
14.
9. Secondary Limit Controls
The secondary limit is located in the blower compartment on the back side of the blower housing. See figure 15. When ex­cess heat is sensed in the blower compartment, the limit will open. If the limit is open, the furnace control energizes the sup­ply air blower and closes the gas valve. The limit automatically resets when unit temperature returns to normal. The secon­dary limit cannot be adjusted.
FIGURE 13
Center Blower Wheel
in Blower Housing
BLOWER WHEEL REPLACEMENT
FIGURE 14
Set Screw
Housing Hub
ALIGN AND TIGHTEN SET SCREW WITH
FLAT SIDE OF MOTOR SHAFT
Motor
Shaft
FIGURE 15
SECONDARY LIMIT CONTROL
Secondary Limits
Page 18
Page 18
1
2
3
4
5
C
L
G
N
MultiMeter (set to VAC)
P48
P49
12012
0
Turn on power to unit. Check for 120 volts across terminals L" and N" on input plug P48. If voltage is present continue to test 2. If voltage is not present problem may be may be up­stream of plug P48 and proceed to test 3.
1
2
3
4
5
C
L
G
N
MultiMeter
(set to VAC)
P48
P49
24
Switch thermostat to CONTINUOUS FAN MODE. Check for 24 volts across terminal C" on input plug P48and speed tap used for continuous fan. (1, 2, 3, 4 or 5) on input plug P49. If 24 volts is not present problem may be up stream of plug P49. Proceed to test 4.
MultiMeter
(set to VAC)
12012
0
24
MultiMeter
(set to VAC)
Check for 24 volts across terminals 24 COM" and FAN" ter­minals on the integrated control. If voltage is present, prob­lem is with the harness. If voltage is not present problem may be may be with the integrated control
Check for 120 volts across terminals CIRC" and Neutrals" on the integrated control. If voltage is present, problem is with the harness. If voltage is not present problem may be may be with the integrated control.
Test 1
Test 2
Test 3 (if necessary)
Test 4 (if necessary)
FIGURE 16
Page 19
Page 19
II−PLACEMENT AND INSTALLATION
Pipe & Fittings Specifications
All pipe, fittings, primer and solvent cement must conform with American National Standard Institute and the Ameri­can Society for Testing and Materials (ANSI/ASTM) stan­dards. The solvent shall be free flowing and contain no lumps, undissolved particles or any foreign matter that ad­versely affects the joint strength or chemical resistance of the cement. The cement shall show no gelation, stratifica­tion, or separation that cannot be removed by stirring. Re­fer to the table 8 below for approved piping and fitting ma­terials.
CAUTION
Solvent cements for plastic pipe are flammable liq­uids and should be kept away from all sources of ignition. Do not use excessive amounts of solvent cement when making joints. Good ventilation should be maintained to reduce fire hazard and to minimize breathing of solvent vapors. Avoid contact of cement with skin and eyes.
TABLE 8
PIPING AND FITTINGS SPECIFICATIONS
Schedule 40 PVC (Pipe) D1785 Schedule 40 PVC (Cellular Core Pipe) F891
Schedule 40 PVC (Fittings) D2466
Schedule 40 CPVC (Pipe) F441
Schedule 40 CPVC (Fittings) F438
SDR−21 PVC or SDR−26 PVC (Pipe) D2241
SDR−21 CPVC or SDR−26 CPVC (Pipe) F442
Schedule 40 ABS Cellular Core DWV (Pipe) F628
Schedule 40 ABS (Pipe) D1527
Schedule 40 ABS (Fittings) D2468
ABS−DWV (Drain Waste & Vent) (Pipe & Fittings)
D2661
PVC−DWV (Drain Waste & Vent) Pipe & Fittings)
D2665
PRIMER & SOLVENT CEMENT
ASTM
SPECIFICATION
PVC & CPVC Primer F656 PVC Solvent Cement D2564
CPVC Solvent Cement F493
ABS Solvent Cement D2235
PVC/CPVC/ABS All Purpose Cement For Fittings & Pipe of the same material
D2564, D2235, F493
ABS to PVC or CPVC Transition Solvent Cement
D3138
CANADA PIPE & FITTING & SOLVENT
CEMENT
MARKING
PVC & CPVC Pipe and Fittings
ULCS636
PVC & CPVC Solvent Cement
ABS to PVC or CPVC Transition Cement
IMPORTANT
EL195UHE exhaust and intake connections are made of PVC. Use PVC primer and solvent cement when using PVC vent pipe. When using ABS vent pipe, use transitional solvent cement to make con­nections to the PVC fittings in the unit.
Use PVC primer and solvent cement or ABS solvent cement meeting ASTM specifications, refer to Table 8. As an alter­nate, use all purpose cement, to bond ABS, PVC, or CPVC pipe when using fittings and pipe made of the same materi­als. Use transition solvent cement when bonding ABS to ei­ther PVC or CPVC.
Low temperature solvent cement is recommended during cooler weather. Metal or plastic strapping may be used for vent pipe hangers. Uniformly apply a liberal coat of PVC primer for PVC or use a clean dry cloth for ABS to clean in­side socket surface of fitting and male end of pipe to depth of fitting socket.
Canadian Applications Only − Pipe, fittings, primer and solvent cement used to vent (exhaust) this ap­pliance must be certified to ULC S636 and supplied by a single manufacturer as part of an approved vent (ex­haust) system. In addition, the first three feet of vent pipe from the furnace flue collar must be accessible for inspection.
Page 20
Page 20
TABLE 9
OUTDOOR TERMINATION KITS USAGE
EL195
UNIT
VENT
PIPE
DIA.
(in.)
STANDARD CONCENTRIC
Outdoor Exhaust
Accelerator
(Dia. X
Length)
Outdoor Exhaust
Accelerator
(Dia. X
Length)
2" Wall Plate
Kit
3" Wall Plate
Kit
2" Wall
Ring Kit
Flush­Mount
Kit
1−1/2"
Concentric
Kit
2"
Concentric
Kit
3"
Concentric
Kit
1−1/2" X 12" 2" X 12"
22G44
or 30G28
44J40
or 81J20
15F74 51W11**
71M80
or
44W92
69M29
or
44W92
60L46
or 44W93
045
2 YES YES YES* YES YES YES
2−1/2 YES YES YES* YES YES YES
3 YES YES YES* YES YES YES
070
2 YES YES YES* YES YES YES
2−1/2 YES YES YES* YES YES YES
3 YES YES YES* YES YES YES
090
2 YES YES YES YES YES YES
2−1/2 YES YES YES YES YES YES
3 YES YES YES YES YES YES
110
2 YES YES YES YES YES YES
2−1/2 YES YES YES YES YES YES
3 YES YES YES YES YES YES
135 3 YES YES YES YES
*Requires field−provided and installed 1−1/2" exhaust accelerator. ** Kit 51W11 is provided with a 1−1/2" accelerator which must be used for all EL195UHXE−045, −070 and −090 installations.  Termination kits 44W92, 44W93, 30G28 and 81J20 approved for use in Canadian installations to meet CSAB149.  The 44W92 concentric kit is provided with a 1−1/2" accelerator which must be installed on the exhaust outlet when this kit is used with the EL195UHXE04536B and
EL195UHXE070P36B furnaces. NOTE − Standard terminations include all approved non−concentric terminations.
Joint Cementing Procedure
All cementing of joints should be done according to the specifications outlined in ASTM D 2855.
DANGER
DANGER OF EXPLOSION!
Fumes from PVC glue may ignite during system check. Allow fumes to dissipate for at least 5 minutes before placing unit into operation.
1 − Measure and cut vent pipe to desired length. 2 − Debur and chamfer end of pipe, removing any ridges
or rough edges. If end is not chamfered, edge of pipe may remove cement from fitting socket and result in a leaking joint.
NOTE − Check the inside of vent pipe thoroughly for any obstruction that may alter furnace operation.
3 − Clean and dry surfaces to be joined. 4 − Test fit joint and mark depth of fitting on outside of pipe.
5 − Uniformly apply a liberal coat of PVC primer for PVC or
use a clean dry cloth for ABS to clean inside socket surface of fitting and male end of pipe to depth of fitting socket.
NOTE − Time is critical at this stage. Do not allow prim­er to dry before applying cement.
6 − Promptly apply solvent cement to end of pipe and in-
side socket surface of fitting. Cement should be ap­plied lightly but uniformly to inside of socket. Take care to keep excess cement out of socket. Apply sec­ond coat to end of pipe.
7 − Immediately after applying last coat of cement to pipe,
and while both inside socket surface and end of pipe are wet with cement, forcefully insert end of pipe into socket until it bottoms out. Turn PVC pipe 1/4 turn dur­ing assembly (but not after pipe is fully inserted) to dis­tribute cement evenly. DO NOT turn ABS or cellular core pipe.
NOTE − Assembly should be completed within 20 sec­onds after last application of cement. Hammer blows should not be used when inserting pipe.
Page 21
Page 21
8 − After assembly, wipe excess cement from pipe at end
of fitting socket. A properly made joint will show a bead around its entire perimeter. Any gaps may indi­cate an improper assembly due to insufficient sol­vent.
9 − Handle joints carefully until completely set.
Venting Practices
FIGURE 17
* See table 8 for allowable pipe.
Piping Suspension Guidelines
NOTE − Isolate piping at the point where it exits the outside wall or roof in order to prevent transmission of vibration to the structure.
SCHEDULE 40
PVC − 5’
all other pipe* − 3’
Wall
inside outside
24" maximum 3/4" minimum
Wall Thickness Guidelines
insulation
(if required)
10. In areas where piping penetrates joists or interior
walls, hole must be large enough to allow clearance on all sides of pipe through center of hole using a hanger.
11. When furnace is installed in a residence where unit is
shut down for an extended period of time, such as a vacation home, make provisions for draining conden­sate collection trap and lines.
CHIMNEY
OR GAS
VENT
(Check sizing
for water
heater only)
FURNACE
(Replaced by EL195)
WATER
HEATER
OPENINGS (To Adjacent
Room)
If an EL195UHE furnace replaces a furnace which was commonly vented with another gas appliance, the size of the existing vent pipe for that gas ap­pliance must be checked. Without the heat of the original furnace flue products, the existing vent pipe is probably oversized for the single water heater or other appliance. The vent should be checked for proper draw with the remaining appliance.
FIGURE 18
REPLACING FURNACE THAT
WAS PART OF A COMMON
VENT SYSTEM
Exhaust Piping (Figures 21 and 22)
Route piping to outside of structure. Continue with installa­tion following instructions given in piping termination sec­tion.
CAUTION
Do not discharge exhaust into an existing stack or stack that also serves another gas appliance. If verti­cal discharge through an existing unused stack is re­quired, insert PVC pipe inside the stack until the end is even with the top or outlet end of the metal stack.
CAUTION
The exhaust vent pipe operates under positive pres­sure and must be completely sealed to prevent leak­age of combustion products into the living space.
Page 22
Page 22
Vent Piping Guidelines
The EL195UHE can be installed as either a Non−Direct Vent or a Direct Vent gas central furnace.
NOTE − In Non-Direct Vent installations, combustion air is taken from indoors and flue gases are discharged outdoors. In Direct Vent installations, combustion air is taken from out­doors and flue gases are discharged outdoors.
Intake and exhaust pipe sizing −− Size pipe according to
tables 10 and
11. Table 10 lists the minimum vent pipe
lengths permitted. Table 11 lists the maximum pipe lengths permitted.
Regardless of the diameter of pipe used, the standard roof and wall terminations described in section Exhaust Piping Terminations should be used. Exhaust vent termination pipe is sized to optimize the velocity of the exhaust gas as it exits the termination. Refer to table 14.
In some applications which permit the use of several differ­ent sizes of vent pipe, a combination vent pipe may be used. Contact Lennox’ Application Department for assis­tance in sizing vent pipe in these applications.
NOTE − The exhaust collar on all models is sized to ac­commodate 2" Schedule 40 vent pipe. In horizontal ap­plications, any transition to exhaust pipe larger than 2" must be made in vertical runs of the pipe. Therefore a 2" elbow must be added before the pipe is transitioned to any size larger than 2". This elbow must be added to the elbow count used to determine acceptable vent lengths. Contact the Application Department for more information concerning sizing of vent systems which include multiple pipe sizes.
FIGURE 19
12" max
of straight pipe
Exhaust Pipe
12" Min.
NOTE − Exhaust pipe MUST be glued to furnace exhaust fittings.
NOTE − All horizontal runs of exhaust pipe must slope back to-
ward unit. A minimum of 1/4" (6mm) drop for each 12" (305mm) of horizontal run is mandatory for drainage.
NOTE − Exhaust piping should be checked carefully to make sure there are no sags or low spots.
Horizontal Application
TABLE 10
MINIMUM VENT PIPE LENGTHS
EL195UHE
MODEL
MIN. VENT LENGTH*
045, 070, 090, 110, 135
15 ft. or
5 ft. plus 2 elbows or
10 ft. plus 1 elbow
*Any approved termination may be added to the minimum length listed.
Use the following steps to correctly size vent pipe diameter.
1
2
3
4
5
6
045, 070, 090, 110 or 135 btuh
Which termination?
Standard or Concentric? See table 9
Intake or exhaust
Which needs most elbows?
How many?
2", 2 1/2" or 3"
Desired pipe size?
Use table 11 to find max intake or exhaust pipe length for all altitudes.
FIGURE 20
7
Furnace capacity?
Is the intake air taken from a vetilated attic or crawl space?
NO
YES
Use table 12 to find max pipe length for all altitudes
(exhaust pipe only)
IMPORTANT
Do not use screens or perforated metal in exhaust or intake terminations. Doing so will cause freeze−ups and may block the terminations.
Page 23
Page 23
TABLE 11
Maximum Allowable Intake or Exhaust Vent Length in Feet
*Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake and Exhaust must be same pipe size.
Standard Termination at Elevation 0 − 4500 ft
Number Of 90° Elbows
Used
2" Pipe 2−1/2" Pipe 3" Pipe
Model Model Model
045 070 090 110 135 045 070 090 110 135 045 070 090 11 0 135
1 81 66 44 24
n/a
115 115 93 58
n/a
138 137 11 8 118 114
2 76 61 39 19 110 110 88 53 133 132 11 3 113 109
3 71 56 34 14 105 105 83 48 128 127 108 108 104
4 66 51 29
n/a
100 100 78 43 123 122 103 103 99
5 61 46 24 95 95 73 38 118 117 98 98 94
6 56 41 19 90 90 68 33 113 112 93 93 89
7 51 36 14 85 85 63 28 108 107 88 88 84
8 46 31
n/a
80 80 58 23 103 102 83 83 79
9 41 26 75 75 53 18 98 97 78 78 74
10 36 21 70 70 48 13 93 92 73 73 69
Standard Termination Elevation 4500 − 10,000 ft
Number Of 90° Elbows
Used
2" Pipe 2−1/2" Pipe 3" Pipe
Model Model Model
045 070 090 110 135 045 070 090 110 135 045 070 090 11 0 135
1 81 66 44
n/a n/a
115 115 93 58
n/a
138 137 11 8 118 114
2 76 61 39 11 0 110 88 53 133 132 113 11 3 109
3 71 56 34 105 105 83 48 128 127 108 108 104
4 66 51 29 100 100 78 43 123 122 103 103 99
5 61 46 24 95 95 73 38 118 117 98 98 94
6 56 41 19 90 90 68 33 113 112 93 93 89
7 51 36 14 85 85 63 28 108 107 88 88 84
8 46 31
n/a
80 80 58 23 103 102 83 83 79
9 41 26 75 75 53 18 98 97 78 78 74
10 36 21 70 70 48 13 93 92 73 73 69
Page 24
Page 24
TABLE 11 Continued
Maximum Allowable Intake or Exhaust Vent Length in Feet
*Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake and Exhaust must be same pipe size.
Concentric Termination at Elevation 0 − 4500 ft
Number Of
90° Elbows
Used
2" Pipe 2−1/2" Pipe 3" Pipe
Model Model Model
045 070 090 110 135 045 070 090 110 135 045 070 090 110 135
1 73 58 42 22
n/a
105 105 89 54
n/a
121 121 114 114 105
2 68 53 37 17 100 100 84 49 116 116 109 109 100
3 63 48 32 12 95 95 79 44 111 111 104 104 95
4 58 43 27
n/a
90 90 74 39 106 106 99 99 90
5 53 38 22 85 85 69 34 101 101 94 94 85
6 48 33 17 80 80 64 29 96 96 89 89 80
7 43 28 12 75 75 59 24 91 91 84 84 75
8 38 23
n/a
70 70 54 19 86 86 79 79 70
9 33 18 65 65 49 14 81 81 74 74 65
10 28 13 60 60 44 n/a 76 76 69 69 60
Concentric Termination Elevation 4501 − 10,000 ft
Number Of
90° Elbows
Used
2" Pipe 2−1/2" Pipe 3" Pipe
Model Model Model
045 070 090 110 135 045 070 090 110 135 045 070 090 110 135
1 73 58 42
n/a n/a
105 105 89 54
n/a
121 121 114 114 105
2 68 53 37 100 100 84 49 116 116 109 109 100
3 63 48 32 95 95 79 44 111 111 104 104 95
4 58 43 27 90 90 74 39 106 106 99 99 90
5 53 38 22 85 85 69 34 101 101 94 94 85
6 48 33 17 80 80 64 29 96 96 89 89 80
7 43 28 12 75 75 59 24 91 91 84 84 75
8 38 23
n/a
70 70 54 19 86 86 79 79 70
9 33 18 65 65 49 14 81 81 74 74 65
10 28 13 60 60 44 n/a 76 76 69 69 60
Page 25
Page 25
TABLE 12
Maximum Allowable Exhaust Vent Lengths With Furnace Installed in a Closet or Basement Using Ventilated
Attic or Crawl Space For Intake Air in Feet
Standard Termination at Elevation 0 − 4500 ft
Number Of 90° Elbows
Used
2" Pipe 2−1/2" Pipe 3" Pipe
Model Model Model
045 070 090 110 135 045 070 090 110 135 045 070 090 11 0 135
1 71 56 34 14
n/a
100 100 78 43
n/a
118 117 98 98 94
2 66 51 29 9 95 95 73 38 113 11 2 93 93 89
3 61 46 24 4 90 90 68 33 108 107 88 88 84
4 56 41 19
n/a
85 85 63 28 103 102 83 83 79
5 51 36 14 80 80 58 23 98 97 78 78 74
6 46 31 9 85 75 63 18 93 92 73 73 69
7 41 26 4 70 70 48 13 88 87 68 68 64
8 36 21
n/a
65 65 43 8 83 82 63 63 59
9 31 16 60 60 38 3 78 77 58 58 54
10 26 11 55 55 33 n/a 73 72 53 53 49
Standard Termination Elevation 4500 − 10,000 ft
Number Of 90° Elbows
Used
2" Pipe 2−1/2" Pipe 3" Pipe
Model Model Model
045 070 090 110 135 045 070 090 110 135 045 070 090 11 0 135
1 71 56 34
n/a n/a
100 100 78 43
n/a
118 117 98 98 94
2 66 51 29 95 95 73 38 113 112 93 93 89
3 61 46 24 90 90 68 33 118 107 88 88 84
4 56 41 19 85 85 63 28 113 102 83 83 79
5 51 36 14 80 80 58 23 98 97 78 78 74
6 46 31 9 85 85 53 18 93 92 73 73 69
7 41 26 4 70 70 48 13 98 87 68 68 64
8 36 21
n/a
65 65 43 8 93 82 63 63 59
9 31 16 60 60 38 3 78 77 58 58 54
10 26 11 55 55 33 n/a 73 72 53 53 49
Page 26
Page 26
FIGURE 21
TYPICAL EXHAUST AND INTAKE PIPE CONNECTIONS IN UPFLOW DIRECT OR
NON−DIRECT VENT APPLICATIONS
TRANSITION
2”
2”
2”
3”
2”
2”
or
DO NOT transition
from smaller to larger
pipe in horizontal runs
of exhaust pipe.
EXHAUST
*2”
* When transitioning up in pipe size, use the shortest length of 2” PVC pipe possible.
INTAKE
2”
TRANSITION
3”
*2”
EXHAUST INTAKE
FIGURE 22
TRANSITION
SIDE VIEW
2”
2”
2”
2”
or
TYPICAL EXHAUST AND INTAKE PIPE CONNECTIONS IN HORIZONTAL DIRECT OR NON−DIRECT VENT
APPLICATIONS
(RIGHT HAND DISCHARGE SHOWN)
3”
2”
45°
MAX
45°
MAX
DO NOT transition
from smaller to larger
pipe in horizontal runs
of exhaust pipe.
EXHAUST
12" max.
*2"
* When transitioning up in pipe size, use the shortest length of 2” PVC pipe possible.
2”
2”
2”
INTAKE
2”
or
2”
*2”
EXHAUST
INTAKE
*2"
3”
*2"
*2"
Page 27
Page 27
Intake Piping
The EL195UHE furnace may be installed in either direct vent or non−direct vent applications. In non−direct vent
applications, when intake air will be drawn into the furnace from the surrounding space, the indoor air quality must be considered and guidelines listed in Combustion, Dilution and Ventilation Air section must be followed.
Follow the next two steps when installing the unit in Direct Vent applications, where combustion air is taken from outdoors and flue gases are discharged outdoors. The
provided air intake screen must not be used in direct vent applications (outdoors).
1 − Use transition solvent cement or a sheet metal screw
to secure the intake pipe to the inlet air connector.
2 − Route piping to outside of structure. Continue with
installation following instructions given in general guidelines for piping terminations and intake and ex­haust piping terminations for direct vent sections. Re­fer to table
11 for pipe sizes.
Follow the next two steps when installing the unit in Non- Direct Vent applications where combustion air is taken from indoors and flue gases are discharged outdoors.
1Use field−provided materials and the factory−provided
air intake screen to route the intake piping as shown in figure 23 or 24. Maintain a minimum clearance of 3" (76mm) around the air intake opening. The air intake opening (with the protective screen) should always be directed forward or to either side in the upflow position, and either straight out or downward in the horizontal position.
The air intake piping must not terminate too close to the flooring or a platform. Ensure that the intake air inlet will not be obstructed by loose insulation or other items that may clog the debris screen.
2 − If intake air is drawn from a ventilated attic (figure 25)
or ventilated crawlspace (figure 26) the exhaust vent length must not exceed those listed in table 12. If 3" di­ameter pipe is used, reduce to 2" diameter pipe at the termination point to accommodate the debris screen.
3 − Use a sheet metal screw to secure the intake pipe to
the connector, if desired.
FIGURE 23
TYPICAL AIR INTAKE PIPE CONNECTIONS
UPFLOW NON−DIRECT
VENT APPLICATIONS
INTAKE
DEBRIS
SCREEN
(Provided)
NOTE − Debris screen and elbow may be rotated, so that screen may be positioned to face forward or to either side.
FIGURE 24
TYPICAL AIR INTAKE PIPE CONNECTIONS
HORIZONTAL NONDIRECT VENT APPLICATIONS
(Horizontal RightHand Air Discharge Application Shown)
INTAKE
DEBRIS
SCREEN
(Provided)
OR
NOTE − Debris screen may be positioned straight out (preferred) or with an elbow rotated to face down.
coupling
PVC pipe
Page 28
Page 28
CAUTION
If this unit is being installed in an application with combustion air coming in from a space serviced by an exhaust fan, power exhaust fan, or other device which may create a negative pressure in the space, take care when sizing the inlet air opening. The in­let air opening must be sized to accommodate the maximum volume of exhausted air as well as the maximum volume of combustion air required for all gas appliances serviced by this space.
FIGURE 25
EQUIPMENT IN CONFINED SPACE
(Inlet Air from Ventilated Attic and Outlet Air to Outside)
NOTE−The inlet and outlet air openings shall each have a free area of at least one square inch per 4,000 Btu (645mm
2
per 1.17kW) per
hour of the total input rating of all equipment in the enclosure.
Ventilation Louvers
Inlet Air
(Minimum
12 in.(305mm) Above
attic floor)
Roof Terminated
Exhaust Pipe
Furnace
*Intake Debris
Screen
(Provided)
* See table 12 for maximum vent lengths
FIGURE 26
NOTE−The inlet and outlet air openings shall each have a free area of at least one square inch per 4,000 Btu (645mm
2
per 1.17kW) per
hour of the total input rating of all equipment in the enclosure.
EQUIPMENT IN CONFINED SPACE
(Inlet Air from Ventilated Crawlspace and Outlet Air to Outside)
Roof Terminated
Exhaust Pipe
Furnace
Ventilation
Louvers
(Crawl space)
*Intake Debris Screen Provided)
Inlet Air
(Minimum
12 in.(305mm)
Above crawl
space floor)
Coupling or 3 in. to 2 in.
Transition
(Field Provided)
* See table 12 for maximum vent lengths
General Guidelines for Vent Terminations
In Non-Direct Vent applications, combustion air is taken from indoors and the flue gases are discharged to the out­doors. The EL195UHE is then classified as a non-direct vent, Category IV gas furnace.
In Direct Vent applications, combustion air is taken from outdoors and the flue gases are discharged to the out­doors. The EL195UHE is then classified as a direct vent, Category IV gas furnace.
In both Non-Direct Vent and Direct Vent applications, the vent termination is limited by local building codes. In the absence of local codes, refer to the current National Fuel Gas Code ANSI Z223−1/NFPA 54 in U.S.A., and current CSA−B149 Natural Gas and Propane Installation Codes in Canada for details.
Position termination according to location given in figure 27 or 28. In addition, position termination so it is free from any obstructions and 12" above the average snow accumula­tion.
At vent termination, care must be taken to maintain protective coatings over building materials (prolonged exposure to exhaust condensate can destroy protective coatings). It is recommended that the exhaust outlet not be located within 6 feet (1.8m) of a condensing unit because the condensate can damage the painted coating.
NOTE − See table 13 for maximum allowed exhaust pipe length without insulation in unconditioned space during winter design temperatures below 32°F (0°C). If required exhaust pipe should be insulated with 1/2" (13mm) Arma­flex or equivalent. In extreme cold climate areas, 3/4" (19mm) Armaflex or equivalent may be necessary. Insula­tion on outside runs of exhaust pipe must be painted or wrapped to protect insulation from deterioration. Exhaust pipe insulation may not be necessary in some specific ap­plications.
IMPORTANT
Do not use screens or perforated metal in exhaust terminations. Doing so will cause freeze−ups and may block the terminations.
IMPORTANT
For Canadian Installations Only: In accordance to CSA International B149 installation codes, the minimum allowed distance between the combustion air intake inlet and the exhaust outlet of other appliances shall not be less than 12 inches (305mm).
Page 29
Page 29
TABLE 13
Maximum Allowable Exhaust Vent Pipe Length Without Insulation In Unconditioned Space For
Winter Design Temperatures Single − Stage High Efficiency Furnace
Winter Design
Temperatures
1
°F (°C)
Vent Pipe
Diameter
Unit Input Size
045 070 090 110 135
32 to 21
(
0 to −6)
2 in. 26 44 44 24 N/A
2−1/2 in. 18 32 50 58 N/A
3 in. 14 26 38 55 60
20 to 1
(−7 to −17)
2 in 16 28 40 24 N/A
2−1/2 in. 12 20 30 44 N/A
3 in. 9 16 26 32 40
0 to −20
(−18 to −29)
2 in. 10 20 30 24 N/A
2−1/2 in. 8 14 20 32 N/A
3 in. 4 10 16 26 30
1Refer to 99% Minimum Design Temperature table provided in the current edition of the ASHRAE Fundamentals Handbook. NOTE − Maximum unisulated vent lengths listed cannot exceed the maximum allowable intake or exhaust vent length listed in table 11.
Page 30
Page 30
FIGURE 27
VENT TERMINATION CLEARANCES
FOR NON−DIRECT VENT INSTALLATIONS IN THE USA AND CANADA
K
D
E
L
B
C
F
G
A
B
J
A
M
I
H
INSIDE CORNER
DETAIL
VENT TERMINAL
AIR SUPPLY INLET
AREA WHERE TERMINAL IS NOT PERMITTED
Fixed
Closed
Operable
B
Fixed
Closed
Operable
B
B
A =
B =
C =
D =
E =
F =
G =
H =
I =
J =
K =
L =
M =
US Installations
1
Canadian Installations
2
12 inches (305mm) or 12 in. (305mm)
above average snow accumulation.
12 inches (305mm) or 12 in. (305mm)
above average snow accumulation.
Clearance above grade, veranda,
porch, deck or balcony
Clearance to window or
door that may be opened
4 feet (1.2 m) below or to side of opening;
1 foot (30cm) above opening
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
Clearance to permanently
closed window
Vertical clearance to ventilated soffit
located above the terminal within a
horizontal distance of 2 feet (610 mm)
from the center line of the terminal
Clearance to unventilated soffit
Clearance to outside corner
Clearance to inside corner
Clearance to each side of center line ex-
tended above meter / regulator assembly
Clearance to service regulator
vent outlet
Clearance to non−mechanical air
supply inlet to building or the com-
bustion air inlet to any other ap-
pliance
Clearance to mechanical air sup-
ply inlet
Clearance above paved sidewalk or
paved driveway located on public property
Clearance under veranda, porch, deck or balcony
* 12"
* Equal to or greater than soffit depth.
*
* 3 feet (.9m)
* 12"
3 feet (.9m) within a height 15 feet (4.5m)
above the meter / regulator assembly
3 feet (.9m)
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
3 feet (.9m) above if within 10 feet
(3m) horizontally
6 feet (1.8m)
7 feet (2.1m)
12 inches (305mm)
1
In accordance with the current ANSI Z223.1/NFPA 54 Natural Fuel Gas Code
2
In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code  A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.
 Permitted only if veranda, porch, deck or balcony is fully open on a minimum of two sides beneath the floor. Lennox recommends avoiding this location if possible.
4 feet (1.2 m) below or to side of opening;
1 foot (30 cm) above opening
7 feet (2.1m)
* Equal to or greater than soffit depth.
* Equal to or greater than soffit depth.
* Equal to or greater than soffit depth.
* No minimum to outside corner * No minimum to outside corner
3 feet (.9m) within a height 15 feet (4.5m)
above the meter / regulator assembly
*12 inches (305mm)
**
*For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B149.1, clearance will be in accordance with local installation codes and the requirements of the gas supplier and these installa­tion instructions."
Page 31
Page 31
FIGURE 28
VENT TERMINATION CLEARANCES
FOR DIRECT VENT INSTALLATIONS IN THE USA AND CANADA
K
D
E
L
B
C
F
G
A
B
J
A
M
I
H
INSIDE CORNER
DETAIL
VENT TERMINAL
AIR SUPPLY INLET
AREA WHERE TERMINAL IS NOT PERMITTED
Fixed
Closed
Operable
B
Fixed
Closed
Operable
B
B
A =
B =
C =
D =
E =
F =
G =
H =
I =
J =
K =
L =
M =
US Installations
1
Canadian Installations
2
12 inches (305mm) or 12 in. (305mm)
above average snow accumulation.
12 inches (305mm) or 12 in. (305mm)
above average snow accumulation.
Clearance above grade, veranda,
porch, deck or balcony
Clearance to window or
door that may be opened
6 inches (152mm) for appliances <10,000
Btuh (3kw), 9 inches (228mm) for ap-
pliances > 10,000 Btuh (3kw) and <50,000
Btuh (15 kw), 12 inches (305mm) for ap-
pliances > 50,000 Btuh (15kw)
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
Clearance to permanently
closed window
Vertical clearance to ventilated soffit
located above the terminal within a
horizontal distance of 2 feet (610mm)
from the center line of the terminal
Clearance to unventilated soffit
Clearance to outside corner
Clearance to inside corner
Clearance to each side of center line ex-
tended above meter / regulator assembly
Clearance to service regulator
vent outlet
Clearance to non−mechanical air
supply inlet to building or the com-
bustion air inlet to any other ap-
pliance
Clearance to mechanical air sup-
ply inlet
Clearance above paved sidewalk or
paved driveway located on public property
Clearance under veranda, porch, deck or balcony
* 12"
*
*
* 7 feet (2.1m)
3 feet (.9m) within a height 15 feet (4.5m)
above the meter / regulator assembly
3 feet (.9m)
6 inches (152mm) for appliances <10,000
Btuh (3kw), 9 inches (228mm) for ap-
pliances > 10,000 Btuh (3kw) and <50,000
Btuh (15 kw), 12 inches (305mm) for ap-
pliances > 50,000 Btuh (15kw)
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
3 feet (.9m) above if within 10 feet
(3m) horizontally
6 feet (1.8m)
7 feet (2.1m)
12 inches (305mm)
1
In accordance with the current ANSI Z223.1/NFPA 54 Natural Fuel Gas Code
2
In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code
*For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B149.1, clearance will be in accordance with local installation codes and the requirements of the gas supplier and these installation instructions."
 A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.
 Permitted only if veranda, porch, deck or balcony is fully open on a minimum of two sides beneath the floor. Lennox recommends avoiding this location if possible.
* 12"
* Equal to or greater than soffit depth
* Equal to or greater than soffit depth* Equal to or greater than soffit depth
* Equal to or greater than soffit depth * Equal to or greater than soffit depth
* No minimum to outside corner
* No minimum to outside corner
3 feet (.9m) within a height 15 feet (4.5m)
above the meter / regulator assembly
3 feet (.9m)
*
*12 inches (305mm)
Page 32
Page 32
Details of Intake and Exhaust Piping Terminations for Direct Vent Installations
NOTE − In Direct Vent installations, combustion air is tak­en from outdoors and flue gases are discharged to out­doors.
NOTE − Flue gas may be slightly acidic and may adversely affect some building materials. If any vent termination is used and the flue gasses may impinge on the building ma­terial, a corrosion−resistant shield (minimum 24 inches square) should be used to protect the wall surface. If the optional tee is used, the protective shield is recommended. The shield should be constructed using wood, plastic, sheet metal or other suitable material. All seams, joints, cracks, etc. in the affected area should be sealed using an appropriate sealant. See figure 32.
Intake and exhaust pipes may be routed either horizontally through an outside wall or vertically through the roof. In attic or closet installations, vertical termination through the roof is preferred. Figures 29 through 43 show typical termina­tions.
1. Intake and exhaust terminations are not required to be in the same pressure zone. You may exit the intake on one side of the structure and the exhaust on another side (figure 30). You may exit the exhaust out the roof and the intake out the side of the structure (figure 31).
2. Intake and exhaust pipes should be placed as close together as possible at termination end (refer to il­lustrations). Maximum separation is 3" (76mm) on roof terminations and 6" (152mm) on side wall termina­tions.
3. On roof terminations, the intake piping should termi­nate straight down using two 90° elbows (See figure
29).
4. Exhaust piping must terminate straight out or up as shown. A reducer may be required on the exhaust pip­ing at the point where it exits the structure to improve the velocity of exhaust away from the intake piping. See table 14.
FIGURE 29
UNCONDITIONED
ATTIC SPACE
1/2" (13mm) FOAM
INSULATION IN
UNCONDITIONED
SPACE
SIZE TERMINATION
PIPE PER TABLE 14.
3"(76mm) MAX.
12" (305mm) ABOVE
AVERAGE SNOW ACCUMULATION
3" (76mm) OR
2" (51mm) PVC
PROVIDE SUPPORT
FOR INTAKE AND
EXHAUST LINES
8" (203mm) MIN
Inches(mm)
DIRECT VENT ROOF TERMINATION KIT
(15F75 or 44J41)
FIGURE 30
Exhaust
Pipe
Furnace
Exiting Exhaust and Intake Vent
(no common pressure zone)
Inlet Air (Minimum 12 in. 305 MM) above
grade or snow
accumulation
FIGURE 31
Roof T
erminated
Exhaust Pipe
Furnace
Exiting Exhaust and Intake Vent
(no common pressure zone)
Inlet Air
(Minimum 12 in.
305 MM) above
grade or snow
accumulation
TABLE 14
EXHAUST PIPE TERMINATION SIZE REDUCTION
EL195UHE
MODEL
Exhaust Pipe Size
Termination
Pipe Size
*045 and 070
2" (51mm), 2−1/2" (64mm),
3" (76mm)
1−1/2" (38mm)
*090 2" (51mm)
110 2" (51mm) 135
3" (76mm)
2" (51mm)
*EL195UHE−045, −070 and −090 units with the flush mount termination must use the 1−1/2"accelerator supplied with the kit. NOTE − Care must be taken to avoid recirculation of ex-
haust back into intake pipe.
5. On field−supplied terminations for side wall exit, ex­haust piping may extend a maximum of 12 inches (305mm) for 2" PVC and 20 inches (508mm) for 3" (76mm) PVC beyond the outside wall. Intake piping should be as short as possible. See figures 33 and 34.
6. On field−supplied terminations, a minimum distance between the end of the exhaust pipe and the end of the intake pipe without a termination elbow is 8" and a minimum distance of 6" with a termination elbow. See figures 33 and 34.
7. If intake and exhaust piping must be run up a side wall to position above snow accumulation or other ob­structions, piping must be supported every 24" (610mm) as shown in figures 33 and 34. In addition, close coupled wall termination kits must be extended for use in this application. See figures 41 and 42. When exhaust and intake piping must be run up an
Page 33
Page 33
outside wall, the exhaust piping must be terminated with pipe sized per table 14.The intake piping may be equipped with a 90° elbow turndown. Using turndown will add 5 feet (1.5m) to the equivalent length of the pipe.
8. A multiple furnace installation may use a group of up to four terminations assembled together horizontally, as shown in figure 38.
C
A
E
D
B
A
B
D
D
B
C
A
C
12"
1
1
2
2
2" (51mm)
Vent Pipe
3" (76mm)
Vent Pipe
A− Clearance above
grade or average snow
accumulation
B−Horizontal
separation between
intake and exhaust
C−Minimum from
end of exhaust to
inlet of intake
D−Exhaust pipe length
E−Wall support distance
from top of each pipe
(intake/exhaust)
12" (305MM) Min.
12" (305MM) Min.
6" (152MM) Min.
24" (610 MM) Max
9" (227MM) Min.
12" (305MM) Min. 16" (405 MM) Max.
6" (152MM) Max.
6" (152MM) Min.
24" (610 MM) Max
9" (227MM) Min.
12" (305MM) Min. 20" (508MM) Max.
6" (152MM) Max.
TABLE 15
FIGURE 32
1
The exhaust termination tee should be connected to the 2" or 3" PVC flue pipe as shown in the illustration. Do
not use an accelerator in applications that include an exhaust termination tee. The accelerator is not required.
2
As required. Flue gas may be acidic and may adversely affect some building materials. If a side wall vent
termination is used and flue gases will impinge on the building materials, a corrosion−resistant shield (24 inches square) should be used to protect the wall surface. If optional tee is used, the protective shield is recommende­d. The shield should be constructed using wood, sheet metal or other suitable material. All seams, joints, cracks, etc. in affected area, should be sealed using an appropriate sealant.
3
Exhaust pipe 45° elbow can be rotated to the side away from the combustion air inlet to direct exhaust away
from adjacent property. The exhaust must never be directed toward the combustion air inlet.
NOTE − See unit installation instructions for proper exhaust pipe termination size reduction.
Front View of
Intake and Exhaust
Intake
Exhaust
3
Intake
Exhaust
Page 34
Page 34
FIGURE 33
FIELD−SUPPLIED WALL TERMINATION OR
(15F74) WALL RING TERMINATION KIT
See venting table 11 for maximum venting lengths with this arrangement.
* Use wall support every 24" (610 mm). Use two wall supports if extension is greater than 24" (610 mm) but less than 48" (1219 mm). NOTE − One wall support must be 6" (152 mm) from top of each pipe (intake and exhaust)
2" (51mm)
Vent Pipe
3" (76mm)
Vent Pipe
A−Minimum clearance
above grade or average
snow accumulation
B−Maximum horizontal separation between
intake and exhaust
C−Minimum from
end of exhaust to
inlet of intake
D−Maximum exhaust
pipe length
E−Maximum wall support
distance from top of each
pipe (intake/exhaust)
12" (305MM) 12" (305MM)
6" (152MM) 6" (152MM)
8" (203MM) 8" (203MM)
12" (305MM) 20" (508MM)
6" (152MM) 6" (152MM)
NOTE − FIELD−PROVIDED
REDUCER MAY BE
REQUIRED TO ADAPT
LARGER VENT PIPE SIZE
TO TERMINATION
D
B
C
SIZE TERMINATION
PER TABLE 14
1/2" (13mm) ARMAFLEX
INSULATION IN UN-
CONDITIONED SPACE
STRAIGHT
APPPLICATION
B
C
A
D
* WALL
SUPPORT
1/2" (13mm) ARMAFLEX INSULATION
IN UNCONDITIONED SPACE
E
EXTENDED
APPLICATION
A
FIGURE 34
FIELD−SUPPLIED WALL TERMINATION OR
(15F74) WALL RING TERMINATION KIT
With INTAKE ELBOW
See venting table 11 for maximum venting lengths with this arrangement.
* Use wall support every 24" (610 mm). Use two wall supports if extension is greater than 24" (610 mm) but less than 48" (1219 mm). NOTE − One wall support must be 6" (152 mm) from top of each pipe (intake and exhaust)
2" (51mm)
Vent Pipe
3" (76mm)
Vent Pipe
12" (305MM) 12" (305MM)
6" (152MM) 6" (152MM)
6" (152MM)
12" (305MM) 20" (508MM)
6" (152MM) 6" (152MM)
6" (152MM)
A−Minimum clearance
above grade or average
snow accumulation
B−Maximum horizontal
separation between
intake and exhaust
C−Minimum from
end of exhaust to
inlet of intake
D−Maximum exhaust
pipe length
E−Maximum wall support
distance from top of each
pipe (intake/exhaust)
NOTE − FIELD−PROVIDED
REDUCER MAY BE
REQUIRED TO ADAPT
LARGER VENT PIPE SIZE
TO TERMINATION
D
B
C
SIZE TERMINATION
PER TABLE 14
1/2" (13mm) ARMAFLEX
INSULATION IN UN-
CONDITIONED SPACE
STRAIGHT
APPPLICATION
B
C
D
* WALL
SUPPORT
1/2" (13mm) ARMAFLEX INSULATION
IN UNCONDITIONED SPACE
E
EXTENDED
APPLICATION
A
A
Page 35
Page 35
FIGURE 35
2" EXTENSION FOR 2" PVC PIPE1" EXTENSION FOR 3" PVC PIPE
1−1/2" ACCELERATOR
(all −45, −070 and −090 units)
FURNACE EXHAUST
PIPE
FURNACE
INTAKE
PIPE
4’’
GLUE EXHAUST
END FLUSH INTO
TERMINATION
FLAT SIDE
FLUSH−MOUNT SIDE WALL TERMINATION
51W11
FIGURE 36
DIRECT VENT CONCENTRIC ROOFTOP TERMINATION
71M80, 69M29 or 60L46 (US)
44W92 or 44W93 (Canada)
Minimum
Above Average
Snow
Accumulation
SHEET METAL STRAP
(Clamp and sheet metal strap must be field installed to support the weight of the termination kit.)
FLASHING
(Not Furnished)
CLAMP
FIELD−PROVIDED
REDUCER MAY BE REQUIRED
TO ADAPT LARGER VENT
PIPE SIZE TO TERMINATION
1 1/2" (38mm) accelerator
provided on 71M80 & 44W92
kits for EL195UHE045P24B,
070P24B & 070P36B
12” (305mm)
INTAKE
AIR
EXHAUST
VENT
12" (305mm) Min.
above grade or
average snow accumulation.
FIGURE 37
DIRECT VENT CONCENTRIC WALL TERMINATION
71M80, 69M29 or 60L46 (US)
44W92 or 44W93 (Canada)
INTAKE
AIR
INTAKE
AIR
INTAKE
AIR
OUTSIDE
WALL
GRADE
CLAMP
(Not Furnished)
FIELD−PROVIDED
REDUCER MAY BE REQUIRED
TO ADAPT LARGER VENT
PIPE SIZE TO TERMINATION
EXHAUST
VENT
1−1/2" (38mm) accelerator
provided on 71M80 & 44W92
kits for EL195UHE045P24B,
070P24B & 070P36B
EXHAUST
VENT
FIGURE 38
EXHAUST
VENT
INTAKE
AIR
5−1/2"
(140mm)
Front View
12"
(305mm)
5"
(127mm)
18" MAX.
(457mm)
EXHAUST VENT
INTAKE
AIR
OPTIONAL VENT TERMINATION FOR MULTIPLE UNIT
INSTALLATION OF DIRECT VENT WALL TERMINATION KIT
(22G44, 44J40, 30G28 or 81J20)
Inches (mm)
Side View
12" (305mm) Min.
above grade or
average snow
accumulation.
optional intake elbow
FIGURE 39
1/2" (13mm) Foam Insulation
in Unconditioned Space
EXHAUST VENT
INTAKE AIR
OUTSIDE WALL
EXHAUST VENT
INTAKE
AIR
Front View
Top View
DIRECT VENT WALL TERMINATION KIT
(30G28 or 81J20)
6 (152mm) MIN.
SIZE
TERMINATION
PIPE PER
TABLE 14.
FIELD−
PROVIDED
REDUCER MAY
BE REQUIRED
TO ADAPT
LARGER VENT
PIPE SIZE TO
TERMINATION
FIGURE 40
EXHAUST VENT
INTAKE
AIR
Front View
SIZE
TERMINATION
PIPE PER
TABLE 14.
Top View
1/2" (13mm) Foam Insulation
in Unconditioned Space
EXHAUST VENT
INTAKE AIR
OUTSIDE WALL
DIRECT VENT WALL TERMINATION KIT
(22G44 or 44J40)
8" (206mm) MIN.
FIELD−
PROVIDED
REDUCER MAY
BE REQUIRED
TO ADAPT
LARGER VENT
PIPE SIZE TO
TERMINATION
Page 36
Page 36
FIGURE 41
12” (305 mm) Minimum
Above Grade or Average
Snow Accumulation
1/2” (13 mm)
FOAM INSULATION
(FieldFurnished)
5” (127 mm)
51/2”
(140 mm)
EXHAUST
AIR
INTAKE
AIR
GRADE
12”
(305 mm)
INTAKE
AIR
EXHAUST
AIR
GRADE
12” (305 mm) Max. for 2” (51 mm) Dia. Exhaust 20” (508 mm) Max. for 3” (76 mm) Dia. Exhaust
WALL SUPPORT*
12” (305 mm) Max. for 2” (51 mm) Dia. Exhaust 20” (508 mm) Max. for 3” (76 mm) Dia. Exhaust
12” (305 mm) Minimum
Above Grade or Average
Snow Accumulation
WALL TERMINATION KITS (CLOSE−COUPLE)
EXTENDED VENT FOR GRADE CLEARANCE
2 inch (51 mm) 22G44 (US)
3 inch (76 mm) 44J40 (US)
6” (152 mm)
Maximum
8” (203 mm) Min. for 2” (51 mm) & 3” (76 mm) DIA. pipe
between the end of the exhaust pipe and intake pipe
8” (203 mm) Min.
*Use wall support every 24" (610). Use two supports if
extension is greater than 24" but less than 48".
FIELD−PROVIDED
REDUCER MAY BE REQUIRED TO ADAPT
LARGER VENT PIPE SIZE TO TERMINATION
If intake and exhaust pipe is less than 12 in. (305 mm) above snow accumulation or other obstructions, field fabricated piping must be installed.
FIGURE 42
12” (305 mm) Minimum
Above Grade or Average
Snow Accumulation
1/2” (13 mm)
FOAM INSULATION
(FieldFurnished)
5” (127 mm)
51/2”
(140 mm)
EXHAUST
AIR
INTAKE
AIR
GRADE
12”
(305 mm)
INTAKE
AIR
EXHAUST
AIR
GRADE
WALL SUPPORT*
12” (305 mm) Minimum
Above Grade or Average
Snow Accumulation
WALL TERMINATION KITS (CLOSE−COUPLE)
EXTENDED VENT FOR GRADE CLEARANCE
2 inch (51 mm) 30G28 (WTK Canada) 3 inch (76 mm) 81J20 (WTK Canada)
See Installation Instructions for additional information.
6” (152 mm)
Maximum
If intake and exhaust pipe is less than 12 in. (305 mm) above snow accumulation or other obstructions, field fabricated piping must be installed.
12” (305 mm) Max. for 2” (51 mm) Dia. Exhaust 20” (508 mm) Max. for 3” (76 mm) Dia. Exhaust
12” (305 mm) Max. for 2” (51 mm) Dia. Exhaust 20” (508 mm) Max. for 3” (76 mm) Dia. Exhaust
6” (152 mm)
Minimum
6” (152 mm)
Minimum
*Use wall support every 24" (610). Use two supports if
extension is greater than 24" but less than 48".
FIELD−PROVIDED
REDUCER MAY BE REQUIRED TO ADAPT
LARGER VENT PIPE SIZE TO TERMINATION
Page 37
Page 37
EL195UHE DIRECT VENT APPLICATION
USING EXISTING CHIMNEY
NOTE − Do not discharge exhaust gases directly into any chimney or vent stack. If ver­tical discharge through an existing unused chimney or stack is required, insert piping inside chimney until the pipe open end is above top of chimney and terminate as illus­trated. In any exterior portion of chimney, the exhaust vent must be insulated.
FIGURE 43
3" − 8"
(76mm−
203mm)
STRAIGHT−CUT OR
ANGLE−CUT IN DIRECTION
OF ROOF SLOPE *
EXHAUST VENT
1/2" (13mm)
WEATHERPROOF
INSULATION
SHOULDER OF FITTINGS
PROVIDE SUPPORT
OF PIPE ON TOP PLATE
ALTERNATE
INTAKE PIPE
INTAKE PIPE
INSULATION (optional)
EXTERIOR
PORTION OF
CHIMNEY
INSULATE TO FORM
SEAL
SHEET
METAL TOP
PLATE
*SIZE TERMINATION PIPE PER TABLE 14.
Minimum 12" (305MM)
above chimney top
plate or average snow
accumulation
8" − 12"
(203mm − 305mm)
3"−8"
(76mm−203mm)
Details of Exhaust Piping Terminations for Non-Direct Vent Applications
Exhaust pipes may be routed either horizontally through an outside wall or vertically through the roof. In attic or closet installations, vertical termination through the roof is pre­ferred. Figures 44 through 47 show typical terminations.
1. Exhaust piping must terminate straight out or up as shown. The termination pipe must be sized as listed in table 14.The specified pipe size ensures proper velocity required to move the exhaust gases away from the building.
2. On field supplied terminations for side wall exit, ex­haust piping may extend a maximum of 12 inches (305mm) for 2" PVC and 20 inches (508mm) for 3" (76mm) PVC beyond the outside wall. See figure 45.
FIGURE 44
NON−DIRECT VENT ROOF TERMINATION KIT
(15F75 or 44J41)
UNCONDITIONED
ATTIC SPACE
3" (76mm) OR
2" (51mm) PVC
PROVIDE SUPPORT
FOR EXHAUST LINES
12" (305mm) ABOVE AVE.
SNOW
ACCUMULATION
SIZE TERMINATION
PIPE PER TABLE
14.
1/2" (13mm) FOAM
INSULATION
FIGURE 45
1/2" (13mm) ARMAFLEX
INSULATION IN
UNCONDITIONED SPACE
PVC REDUCER
1/2" (13mm)
ARMAFLEX
INSULATION
NON−DIRECT VENT FIELD SUPPLIED WALL TERMINATION OR
(15F74) WALL TERMINATION KIT
SIZE TERMINATION
PIPE PER TABLE 14.
FIELD−PROVIDED
REDUCER MAY
BE REQUIRED TO
ADAPT LARGER
VENT PIPE SIZE
TO TERMINATION
12" MIN.
(305mm)
Above Grade or
average snow
accumulation
12" (305mm) MAX. for 2" (51mm) 20" (508mm) MAX. for 3" (76mm)
3. If exhaust piping must be run up a side wall to position above snow accumulation or other obstructions, pip­ing must be supported every 24 inches (610mm) as shown in figure 46. When exhaust piping must be run up an outside wall, any reduction in exhaust pipe size must be done after the final elbow.
FIGURE 46
12" (305mm)
ABOVE GRADE OR
AVERAGE SNOW ACCUMULATION
UNCONDITIONED
SPACE
1/2" (13mm) FOAM
INSULATION
1/2" (13mm) FOAM
INSULATION IN
UNCONDITIONED
SPACE
*WALL SUPPORT
OUTSIDE WALL
SIZE TER­MINATION PIPE PER TABLE 14.
FIELD−PROVIDED
REDUCER MAY BE
REQUIRED TO
ADAPT LARGER
VENT PIPE SIZE TO
TERMINATION
*Use wall support every 24" (610). Use two supports if extension is
greater than 24" but less than 48".
12" (305mm) MAX. for 2" (51mm) 20" (508mm) MAX. for 3" (76mm)
NON−DIRECT VENT FIELD SUPPLIED WALL TERMINATION
EXTENDED OR (15F74) WALL TERMINATION VENT PIPE
EXTENDED
6" (152mm)
Max
Page 38
Page 38
NOTE − Do not discharge exhaust gases directly into any chimney or vent stack. If ver­tical discharge through an existing unused chimney or stack is required, insert piping inside chimney until the pipe open end is above top of chimney and terminate as illus­trated. In any exterior portion of chimney, the exhaust vent must be insulated.
FIGURE 47
STRAIGHT−CUT OR
ANGLE−CUT IN DIRECTION
OF ROOF SLOPE
EXHAUST VENT
1/2" (13mm)
WEATHERPROOF
INSULATION
SHOULDER OF FITTINGS
PROVIDE SUPPORT
OF PIPE ON TOP PLATE
EXTERIOR
PORTION OF
CHIMNEY
INSULATE TO FORM
SEAL
SHEET
METAL TOP
PLATE
SIZE TERMINATION
PIPE PER TABLE 14.
EL195UHE NON−DIRECT VENT APPLICATION
USING EXISTING CHIMNEY
Minimum 12" (305MM)
above chimney top
plate or average snow
accumulation
Condensate Piping
This unit is designed for either right- or left-side exit of con­densate piping in upflow applications. In horizontal applica­tions, the condensate trap must extend below the unit. An 8" service clearance is required for the condensate trap. Refer to figures 48 and 49 for condensate trap locations. Figure 55 shows trap assembly using 1/2" PVC or 3/4" PVC.
NOTE − If necessary the condensate trap may be installed up to 5´ away from the furnace. Use PVC pipe to connect trap to furnace condensate outlet. Piping from furnace must slope down a minimum of 1/4" per ft. toward trap.
1 − Determine which side condensate piping will exit the
unit, location of trap, field−provided fittings and length of PVC pipe required to reach available drain.
2 − Use a 3/8 allen wrench and remove plug (figure 48)
from the cold end header box at the appropriate loca­tion on the side of the unit. Install field−provided 1/2 NPT male fitting into cold end header box. Use Teflon tape or appropriate pipe dope.
3 − Install the cap over the clean out opening at the base of
the trap. Secure with clamp. See figure 55.
4 − Install drain trap using appropriate PVC fittings, glue
all joints. Glue the provided drain trap as shown in fig­ure 55. Route the condensate line to an open drain.
Condensate line must maintain a 1/4" downward slope from the furnace to the drain.
FIGURE 48
CONDENSATE TRAP AND PLUG LOCATIONS
(Unit shown in upflow position)
NOTE − In upflow applications where side return air filter is installed on same side as the conden­sate trap, filter rack must be installed beyond condensate trap or trap must be re−located to avoid interference.
Trap
(same on
right side)
Plug
(same on left side)
1−1/2 in.
5 − Figures 50 and 51 show the furnace and evaporator
coil using a separate drain. If necessary the conden­sate line from the furnace and evaporator coil can drain together. See figures 52, 53 and 54. Upflow furnace (figure 53) − In upflow furnace applica­tions the field provided vent must be a minimum 1" to a maximum 2" length above the condensate drain outlet connection. Any length above 2" may result in a flooded heat exchanger if the combined primary drain line were to become restricted. Horizontal furnace (figure 54) − In horizontal furnace applications the field provided vent must be a mini­mum 4" to a maximum 5" length above the condensate drain outlet connection. Any length above 5" may re­sult in a flooded heat exchanger if the combined pri­mary drain line were to become restricted.
NOTE − In horizontal applications it is recommended to install a secondary drain pan underneath the unit and trap assembly.
NOTE − Vinyl tubing may be used for condensate drain. Tubing must be 1−1/4" OD X 1" ID and should be attached to the drain on the trap using a hose clamp.
CAUTION
Do not use copper tubing or existing copper conden- sate lines for drain line.
6 − If unit will be started immediately upon completion of
installation, prime trap per procedure outlined in Unit Start−Up section.
Page 39
Page 39
Condensate line must slope downward away from the trap to drain. If drain level is above condensate trap, condensate pump must be used. Condensate drain line should be routed within the conditioned space to avoid freezing of condensate and blockage of drain line. If this is not possible, a heat cable kit may be used on the condensate trap and line. Heating cable kit is available from Lennox in various lengths; 6 ft. (1.8m) − kit no. 26K68; 24 ft. (7.3m) − kit no. 26K69; and 50 ft. (15.2m) − kit no. 26K70.
FIGURE 49
CONDENSATE TRAP LOCATIONS
(Unit shown in upflow position with remote trap)
*5’ max.
To Drain
PVC Pipe Only
Field Provided Vent
Min. 1" Above Condensate
Drain Connection
1" Min.
Trap Can Be Installed a
Maximum 5’ From Furnace
*Piping from furnace must slope down a minimum of 1/4" per ft. toward trap.
2" Max.
FIGURE 50
EL195UHE With Evaporator Coil Using A Separate Drain
Field−Provided Vent
(1" min. to 2" Max. above
condensate drain connection)
Drain
Condensate trap
and evaporator coil
drain separately as
shown.
Condensate
Drain Connection
FIGURE 51
EL195UHE with Evaporatoir Coil Using a Separate Drain
(Unit shown in horizontal left−hand discharge position)
Condensate Drain
Connection
Field−Provided Vent
(4" min. to 5" Max. above
condensate drain connection)
*Piping from furnace and evaporator coil must slope down a minimum of 1/4" per ft. toward trap.
5’ max.
PVC Pipe Only
4”min
5”max
Evaporator
Coil
Drain Pan
Page 40
Page 40
IMPORTANT
When combining the furnace and evaporator coil drains together, the A/C condensate drain outlet must be vented to relieve pressure in or­der for the furnace pressure switch to operate properly.
FIGURE 52
Condensate Trap With Optional Overflow Switch
Field−Provided Vent
(Upflow/Furnace 1" Min. to 2" Max.
Horizontal Furnace 4" Min. to 5" Max. above
condensate drain connection)
Furnace Condensate
Drain Connection
From Evaporator Coil
To Drain
Optional
Overflow Switch
FIGURE 53
EL195UHE with Evaporator Coil Using a Common Drain
Field−Provided Vent
(1" min. to 2" Max. above
condensate drain connection)
Evaporator
Drain Line
Vent Required
Condensate
Drain Connection
FIGURE 54
Condensate Drain
Connection
EL195UHE with Evaporator Coil Using a Common Drain
(Unit shown in horizontal left−hand discharge position)
Field−Provided Vent
(4" min. to 5" Max. above
condensate drain connection)
*Piping from furnace and evaporator coil must slope down a minimum of 1/4" per ft. toward trap.
5’ max.
PVC Pipe Only
4”min
5”max
Evaporator
Coil
Drain Pan
Page 41
Page 41
FIGURE 55
TRAP / DRAIN ASSEMBLY USING 1/2" PVC OR 3/4" PVC
Adapter 1/2 inch slip X
1/2 inch mpt (Not Furnished)
Drain Trap
Assembly
(Furnished)
Vent
Drain Trap Clean Out
5 Feet
Maximum
Coupling 1/2 inch slip X slip
(Not Furnished)
90° Elbow 1/2 inch PVC
(Not Furnished)
1/2 inch PVC Pipe
(Not Furnished)
1/2 inch PVC Pipe
(Not Furnished)
Condensate Drain
Connection In Unit
7
(178)
Drain Assembly for 1/2 inch Drain Pipe
90° Elbow
3/4 inch PVC
(Not Furnished)
Coupling 3/4 inch slip X slip
(Not Furnished)
To
Drain
To
Drain
90° Elbow
3/4 inch PVC
(Not Furnished)
To
90° Street Elbow
1/2 inch PVC
To
Drain
90° Elbow
1/2 inch PVC
(Not Furnished)
1/2 inch PVC Pipe
(Not Furnished)
Drain Assembly for 3/4 inch Drain Pipe
90° Street Elbow
1/2 inch PVC
(Not Furnished)
Condensate Drain
Connection In Unit
Adapter 1/2 inch slip X
1/2 inch mpt (Not Furnished)
Condensate Drain
Connection In Unit
Vent
To
Drain
Condensate Drain
Connection In Unit
Drain Trap Assembly with 3/4 inch Piping
Vent
To
Drain
(Furnished)
Optional Condensate Drain Connection
Optional Drain Piping From Trap
Drain Trap Assembly
(Furnished)
Drain Trap Assembly with 1/2 inch Piping
Drain Trap Assembly with 3/4 inch Piping
1/2 inch
3/4 inch
1 (25 mm) Min. 2 (50 mm) Max. Above Top Of Condensate Drain Connection In Unit
1 (25 mm) Min. 2 (50 mm) Max. Above Top Of Condensate Drain Connection In Unit
1 (25 mm) Min. 2 (50 mm) Max. Above Top Of Condensate Drain Connection In Unit
Trap
Page 42
Page 42
III−START-UP
A−Preliminary and Seasonal Checks
1 − Inspect electrical wiring, both field and factory installed
for loose connections. Tighten as required.
2 − Check voltage at disconnect switch. Voltage must be with-
in range listed on the nameplate. If not, consult the po wer company and have voltage condition corrected be­fore starting unit.
3 − Inspect condition of condensate traps and drain as-
sembly. Disassemble and clean seasonally.
B−Heating Start-Up
BEFORE LIGHTING the unit, smell all around the fur-
nace area for gas. Be sure to smell next to the floor be­cause some gas is heavier than air and will settle on the floor.
The gas valve on the EL195UHE is equipped with a gas control switch. Use only your hand to move the switch. Never use tools. If the the switch will not move by hand, replace the valve. Do not try to repair it. Force or at­tempted repair may result in a fire or explosion.
Placing the furnace into operation:
EL195UHE units are equipped with a SureLight ignition system. Do not
attempt to manually light burners on this furnace. Each time the thermostat calls for heat, the burners will automatically light. The ignitor does not get hot when there is no call for heat on units with SureLightt ignition system.
Priming Condensate Trap
The condensate trap should be primed with water prior to start−up to ensure proper condensate drainage. Either pour 10 fl. oz. (300 ml) of water into the trap, or follow these steps to prime the trap:
1 − Follow the lighting instructions to place the unit into op-
eration.
2 − Set the thermostat to initiate a heating demand.
3 − Allow the burners to fire for approximately 3 minutes. 4 − Adjust the thermostat to deactivate the heating de-
mand.
5 − Wait for the combustion air inducer to stop. Set the
thermostat to initiate a heating demand and again al­low the burners to fire for approximately 3 minutes.
6 − Adjust the thermostat to deactivate the heating de-
mand and again wait for the combustion air inducer to stop. At this point, the trap should be primed with suffi­cient water to ensure proper condensate drain opera­tion.
WARNING
If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or death.
Gas Valve Operation (Figure 56)
1 − STOP! Read the safety information at the beginning of
this section.
2 − Set the thermostat to the lowest setting. 3 − Turn off all electrical power to the unit. 4 − This furnace is equipped with an ignition device which
automatically lights the burners. Do not try to light the burners by hand.
5 − Remove the access panel. 6 − Move gas valve switch to OFF. See figure 56. 7 − Wait five minutes to clear out any gas. If you then smell
gas, STOP! Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instruc­tions. If you do not smell gas go to next step.
8 − Move gas valve switch to ON. See figure 56.
FIGURE 56
GAS VALVE SHOWN IN ON POSITION
MANIFOLD
PRESSURE
OUTLET
PORT
INLET
PRESSURE
PORT
MANIFOLD PRESSURE ADJUSTMENT SCREW
(under barbed fitting)
9 − Replace the access panel.
10− Turn on all electrical power to to the unit.
11− Set the thermostat to desired setting.
NOTE − When unit is initially started, steps 1 through 11 may need to be repeated to purge air from gas line.
12− If the appliance will not operate, follow the instructions
Turning Off Gas to Unit" and call your service techni­cian or gas supplier.
Turning Off Gas to Unit
1 − Set the thermostat to the lowest setting.
2 − Turn off all electrical power to the unit if service is to be
performed.
3 − Remove the access panel.
4 − Move gas valve switch to OFF.
5 − Replace the access panel.
Failure To Operate
If the unit fails to operate, check the following: 1 − Is the thermostat calling for heat? 2 − Are access panels securely in place? 3 − Is the main disconnect switch closed? 4 − Is there a blown fuse or tripped breaker? 5 − Is the filter dirty or plugged? Dirty or plugged filters will
cause the limit control to shut the unit off. 6 − Is gas turned on at the meter? 7 − Is the manual main shut-off valve open? 8 − Is the internal manual shut-off valve open? 9 − Is the unit ignition system in lockout? If the unit locks out
again, inspect the unit for blockages.
Page 43
Page 43
IV−HEATING SYSTEM SERVICE CHECKS
A−C.S.A. Certification
All units are C.S.A. design certified without modifications. Refer to the EL195UHE Operation and Installation Instruc­tion Manual Information.
B−Gas Piping
CAUTION
If a flexible gas connector is required or allowed by the authority that has jurisdiction, black iron pipe shall be installed at the gas valve and extend outside the furnace cabinet. The flexible connector can then be added between the black iron pipe and the gas supply line.
Gas supply piping should not allow more than 0.5" W.C. drop in pressure between gas meter and unit. Supply gas pipe must not be smaller than unit gas connection.
Compounds used on gas piping threaded joints should be resistant to action of liquefied petroleum gases.
C−Testing Gas Piping
IMPORTANT
In case emergency shutdown is required, turn off the main shut-off valve and disconnect the main power to unit. These controls should be properly labeled by the installer.
When pressure testing gas lines, the gas valve must be dis­connected and isolated. Gas valves can be damaged if subjected to more than 0.5 psig (14" W.C.). See figure 57.
FIGURE 57
MANUAL MAIN SHUT−OFF
VALVE WILL NOT HOLD
NORMAL TEST PRESSURE
CAP
FURNACE
ISOLATE
GAS VALVE
1/8" N.P.T. PLUGGED TAP
When checking piping connections for gas leaks, use pre­ferred means. Kitchen detergents can cause harmful corro­sion on various metals used in gas piping. Use of a specialty Gas Leak Detector is strongly recommended. It is available through Lennox under part number 31B2001. See Corp. 8411−L10, for further details.
WARNING
Do not use matches, candles, flame or any other source of ignition to check for gas leaks.
D−Testing Gas Supply Pressure Gas Flow (Approximate)
TABLE 16
GAS METER CLOCKING CHART
EL195
Unit
Seconds for One Revolution
Natural LP
1 cu ft
Dial
2 cu ft
Dial
1 cu ft
Dial
2 cu ft
DIAL
−045 80 160 200 400
−070 55 11 0 136 272
−090 41 82 102 204
−110 33 66 82 164
−135 27 54 68 136
Natural−1000 btu/cu ft LP−2500 btu/cu ft
Furnace should operate at least 5 minutes before check­ing gas flow. Determine time in seconds for two revolu­tions of gas through the meter. (Two revolutions assures a more accurate time.) Divide by two and compare to time in table 16. If manifold pressure matches table 17 and rate is incorrect, check gas orifices for proper size and re­striction. Remove temporary gas meter if installed.
NOTE − To obtain accurate reading, shut off all other gas appliances connected to meter.
Supply Pressure Measurement
When testing supply gas pressure, use the 1/8" N.P.T. plugged tap located on the gas valve to facilitate test gauge connection. See figure 7. Check gas line pressure with unit firing at maximum rate. Low pressure may result in erratic operation or underfire. High pressure can result in perma­nent damage to gas valve or overfire.
On multiple unit installations, each unit should be checked separately, with and without other units operating. Supply pressure must fall within range listed in table 17.
Manifold Pressure Measurement
1 − Remove the threaded plug from the outlet side of the
gas valve and install a field−provided barbed fitting. Connect to a manometer to measure manifold pres­sure.
2 − Start unit and allow 5 minutes for unit to reach steady
state.
3 − While waiting for the unit to stabilize, observe the
flame. Flame should be stable and should not lift from burner. Natural gas should burn blue.
4 − After allowing unit to stabilize for 5 minutes, record
manifold pressure and compare to value given in table
17.
NOTE − Shut unit off and remove manometer as soon as an accurate reading has been obtained. Take care to remove barbed fitting and replace threaded plug.
TABLE 17
Supply Line and Manifold Pressure (inches w.c.)
Unit Fuel
Manifold
Pressure
Supply Line
All Nat 3.5 4.5 − 10.5
All LP/Propane 10.0 11.0 − 13.0
Page 44
Page 44
E−Proper Combustion
Furnace should operate minimum 15 minutes with correct manifold pressure and gas flow rate before checking com­bustion. Take combustion sample beyond the flue outlet and compare to the tables below.
TABLE 18
Unit
CO2%
For Nat
CO2%
For LP
All 7.2 − 8.2 8.6 − 9.6
The maximum carbon monoxide reading should not exceed 50 ppm.
F−High Altitude
NOTE − In Canada, certification for installations at eleva­tions over 4500 feet (1372 m) is the jurisdiction of local au­thorities.
Units installed at altitude of 4501 − 10,000 feet (1373 to 3048 m) may require a pressure switch change which can be ordered separately. Table 19 lists conversion kit and pressure switch requirements at varying altitudes.
The combustion air pressure switch is factory−set and re­quires no adjustment.
TABLE 19
LP/Propane Conversion Kit and Pressure Switch Requirements at Varying Altitudes
Unit
Natural to
LP/Propane
High Altitude
Natural Burner
Orifice Kit
High Altitude
LP/Propane Burner
Orifice Kit
High Altitude Pressure Switch
0 − 7500 ft
(0 − 2286m)
7501 − 10,000 ft
(2286 − 3038m)
7501 − 10,000 ft
(2286 − 3038m)
4501 − 7500 ft
(1373 − 2286m)
7501 −10,000 ft
(2286 − 3048m)
−045
*69W73 73W37 *68W68
No Change 80W60
−070 80W66 80W59
−090 80W65 80W59
−110 80W66 80W59
−135 80W65 80W59
* Conversion requires installation of a gas valve manifold spring which is provided with the gas conversion kit. Pressure switch is factory set. No adjustment necessary. All models use the factory−installed pressure switch from 0−4500 feet (0−1370 m).
Page 45
Page 45
G− Proper Ground and Voltage
A poorly grounded furnace can contribute to premature ig­nitor failure. Use the following procedure to check for ground and voltage to the integrated control. 1 − Measure the AC voltage between Line Neutral (spade
terminals) and C" terminal (low voltage terminal block) on the integrated control. See figure 58. A wide variation in the voltage between Line Neutral and C" as a function of load indicates a poor or partial ground. Compare the readings to the table below. If the read­ings exceed the maximum shown in table 1, make re­pairs before operating the furnace.
2 − In addition, measure the AC voltage from Line Hot to
Line Neutral (spade terminals) on the integrated con­trol. See figure 58. This voltage should be in the range of 97 to 132 Vac
TABLE 20
Furnace Status
Measurement VAC
Expected Maximum
Power On Furnace Idle 0.3 2
CAI / Ignitor Energized 0.75 5
Indoor Blower Energized Less than 2 10
CHECK VOLTAGE BETWEEN LINE NEUTRAL
AND LOW VOLTAGE C" TERMINAL
Red LED
Recall
Red LED
Recall
CHECK VOLTAGE BETWEEN LINE HOT
AND LINE NEUTRAL
FIGURE 58
Page 46
Page 46
V−TYPICAL OPERATING CHARACTERISTICS
A−Blower Operation and Adjustment1
NOTE− The following is a generalized procedure and does not apply to all thermostat controls.
1 − Blower operation is dependent on thermostat control
system.
2 − Generally, blower operation is set at thermostat sub-
base fan switch. With fan switch in ON position, blower operates continuously. With fan switch in AUTO position, blower cycles with demand or runs continuously while heating or cooling circuit cycles.
3 − Depending on the type of indoor thermostat, blower
and entire unit will be off when the system switch is in OFF position.
B−Temperature Rise (Figure 59)
Temperature rise for EL195UHE units depends on unit in­put, blower speed, blower horsepower and static pressure as marked on the unit rating plate. The blower speed must be set for unit operation within the range of TEMP. RISE °F" listed on the unit rating plate.
FIGURE 59
TEMPERATURE RISE
Supply Duct Temperature
Return Duct Temperature
_
Temperature Rise =
SUPPLY
AIR
Temperatures
RETURN AIR
C−External Static Pressure
1 − Tap locations shown in figure 60. 2 − Punch a 1/4" diameter hole in supply and return air ple-
nums. Insert manometer hose flush with inside edge of
hole or insulation. Seal around the hose with perma-
gum. Connect the zero end of the manometer to the
discharge (supply) side of the system. On ducted sys-
tems, connect the other end of manometer to the return
duct as above.
3 − With only the blower motor running and the evaporator
coil dry, observe the manometer reading. Adjust blow-
er motor speed to deliver the air desired according to
the job requirements. For heating speed external static
pressure drop must not be more than 0.5" W.C. For
cooling speed external static pressure drop must not
be more than 0.8" W.C.
4 − Seal the hole when the check is complete.
FIGURE 61
EXTERNAL STATIC PRESSURE
Supply Duct Static
Return Duct Static +
Total Duct Static = (dry coil)
Duct Static
or
Supply Air
Return Air
High +"
Low −"
+
D−Blower Speed Taps
Blower speed tap changes are made on the integrated con­trol. See figure 3 or 58. The heating tap is connected to the HEAT" terminal and the cooling tap is connected to the COOL" terminal. On all units the continuous blower tap is connected to the FAN" terminal. Unused taps must be se­cured on two dummy terminals labeled "PARK. To change out existing speed tap, turn off power and switch out speed tap with tap connected to PARK". See blower speed tap table on unit diagram for motor tap colors for each speed.
Page 47
Page 47
VI−MAINTENANCE
WARNING
ELECTRICAL SHOCK, FIRE,
OR EXPLOSION HAZARD.
Failure to follow safety warnings exactly could result in dangerous operation, serious injury, death or property damage. Improper servicing could result in dangerous opera­tion, serious injury, death, or property damage. Before servicing, disconnect all electrical power to furnace. When servicing controls, label all wires prior to dis­connecting. Take care to reconnect wires correctly. Verify proper operation after servicing.
At the beginning of each heating season, system should be checked as follows by a qualified service technician:
Blower
Check the blower wheel for debris and clean if necessary. The blower motors are prelubricated for extended bearing life. No further lubrication is needed.
WARNING
The blower access panel must be securely in place when the blower and burners are operating. Gas fumes, which could contain carbon monoxide, can be drawn into living space resulting in personal inju­ry or death.
Filters
All air filters are installed external to the unit. Filters should be inspected monthly. Clean or replace the filters when necessary to ensure proper furnace operation. Table 21 lists recommended filter sizes.
TABLE 21
Furnace
Cabinet Width
Filter Size
Side Return Bottom Return
17−1/2" 16 X 25 X 1 (1) 16 X 25 X 1 (1)
21" 16 X 25 X 1 (1) 20 X 25 X 1 (1)
24−1/2" 16 X 25 X 1 (2) 24 X 25 X 1 (1)
Exhaust and air intake pipes
Check the exhaust and air intake pipes and all connections for tightness and to make sure there is no blockage.
NOTE − After any heavy snow, ice or frozen fog event the furnace vent pipes may become restricted. Always check the vent system and remove any snow or ice that may be obstructing the plastic intake or exhaust pipes.
Electrical
1 − Check all wiring for loose connections.
2 − Check for the correct voltage at the furnace (furnace
operating). Correct voltage is 120VAC +
10%
3 − Check amp−draw using a true RMS meter on the blow-
er motor with blower access panel in place. See figure
62. Unit Nameplate__________Actual__________
FIGURE 62
kVAr
kWh
COMMV3V1
V2
P
OFF
MR
EX
1
W 3
2
Check Motor Amp Draw
True RMS Meter
Winterizing and Condensate Trap Care
1 − Turn off power to the furnace.
2 − Have a shallow pan ready to empty condensate water.
3 − Remove the clean out cap from the condensate trap
and empty water. Inspect the trap then reinstall the clean out cap.
Cleaning Heat Exchanger
If cleaning the heat exchanger becomes necessary, follow the below procedures and refer to figure 1 when disassem­bling unit. Use papers or protective covering in front of fur­nace while removing heat exchanger assembly.
1 − Turn off electrical and gas supplies to the furnace. 2 − Remove the furnace access panels. 3 − Disconnect the 2 wires from the gas valve. 4 − Remove gas supply line connected to gas valve. Re-
move the burner box cover (if equipped) and remove gas valve/manifold assembly.
5 − Remove sensor wire from sensor. Disconnect 2-pin
plug from the ignitor. 6 − Disconnect wires from flame roll−out switches. 7 − Disconnect combustion air intake pipe. It may be nec-
essary to cut the existing pipe to remove burner box
assembly. 8 − Remove four burner box screws at the vestibule panel
and remove burner box. Set burner box assembly
aside.
NOTE − If necessary, clean burners at this time. Follow
procedures outlined in Burner Cleaning section.
9 − Loosen the clamps to the flexible exhaust coupling. 10 − Disconnect condensate drain line from the cold end
header box. 11 − Disconnect condensate drain tubing from flue collar.
Remove screws that secures the flue collar into place.
Remove flue collar. It may be necessary to cut the exit-
ing exhaust pipe for removal of the fitting.
Page 48
Page 48
12 − Mark and disconnect all combustion air pressure tub-
ing from cold end header collector box.
13 − Mark and remove wires from pressure switch assemb-
ly. Remove the assembly. Keep tubing attached to pressure switches.
14 − Disconnect the plug from the combustion air inducer.
Remove two screws which secure combustion air in­ducer to collector box. Remove combustion air induc-
er assembly. Remove ground wire from vest panel. 15 − Disconnect the condensate drain line. 16 − Remove cold end header box. 17 − Remove electrical junction box from the side of the fur-
nace. 18 − Mark and disconnect any remaining wiring to heating
compartment components. Disengage strain relief
bushing and pull wiring and bushing through the hole in
the blower deck. 19 − Remove the primary limit from the vestibule panel. 20 − Remove two screws from the front cabinet flange at
the blower deck. Spread cabinet sides slightly to allow
clearance for removal of heat exchanger. 21 − Remove screws along vestibule sides and bottom
which secure vestibule panel and heat exchanger as-
sembly to cabinet. Remove two screws from blower
rail which secure bottom heat exchanger flange. Re-
move heat exchanger from furnace cabinet.
22 − Back wash heat exchanger with soapy water solution
or steam. If steam is used it must be below 275°F
(135°C) .
23 − Thoroughly rinse and drain the heat exchanger. Soap
solutions can be corrosive. Take care to rinse entire
assembly. 24 − Reinstall heat exchanger into cabinet making sure that
the clamshells of the heat exchanger assembly is en-
gaged properly into the support bracket on the blower
deck. Remove the indoor blower to view this area
through the blower opening. 25 − Re-secure the supporting screws along the vestibule
sides and bottom to the cabinet. 26 − Reinstall cabinet screws on front flange at blower
deck. 27 − Reinstall the primary limit on the vestibule panel. 28 − Route heating component wiring through hole in blow-
er deck and reinsert strain relief bushing. 29 − Reinstall electrical junction box.
30 − Reinstall the cold end header box. 31 − Reinstall the combustion air inducer. Reconnect the
plug to the wire harness.
32 − Reinstall pressure switches and reconnect pressure
switch wiring.
33 − Carefully connect combustion air pressure switch
tubing from pressure switches to proper ports on cold end header collector box.
34 − Reconnect condensate drain line to the cold end
header box.
35 − Use securing screws to reinstall flue collar to the top
cap on the furnace. Reconnect exhaust piping and ex­haust drain tubing.
36 − Replace flexible exhaust adapter on combustion air in-
ducer and flue collar. Secure using two existing hose clamps.
37 − Reinstall burner box assembly in vestibule area. Se-
cure burner box assembly to vestibule panel using four existing screws. Make sure burners line up in
center of burner ports
38 − Reconnect flame roll−out switch wires. 39 − Reconnect sensor wire and reconnect 2−pin plug from
ignitor.
40 − Reinstall gas valve manifold assembly. Reconnect
gas supply line to gas valve. 41 − Reconnect the combustion air intake pipe. 42 − Reinstall burner box cover. 43 − Reconnect wires to gas valve. 44 − Replace the blower compartment access panel. 45 − Reconnect gas supply piping. Turn on power and gas
supply to unit. 46− Follow lighting instructions on unit nameplate to light
and operate furnace for 5 minutes to ensure the fur-
nace is operating properly. 47− Check all piping connections, factory and field, for gas
leaks. Use a leak detecting solution or other preferred means.
48− Replace heating compartment access panel.
CAUTION
Some soaps used for leak detection are corrosive to certain metals. Carefully rinse piping thoroughly af­ter leak test has been completed. Do not use matches, candles, flame or other sources of ignition to check for gas leaks.
Page 49
Page 49
Cleaning the Burner Assembly (if needed)
1 − Turn off electrical and gas power supplies to furnace.
Remove upper and lower furnace access panels.
2 − Disconnect the wires from the gas valve.
3 − Remove the burner box cover (if equipped).
4 − Disconnect the gas supply line from the gas valve. Re-
move gas valve/manifold assembly.
5 − Mark and disconnect sensor wire from the sensor. Dis-
connect wires from flame rollout switches.
6 − Disconnect combustion air intake pipe. It may be nec-
essary to cut the existing pipe to remove burner box assembly.
7 − Remove four screws which secure burner box assem-
bly to vest panel. Remove burner box from the unit.
8 − Use the soft brush attachment on a vacuum cleaner to
gently clean the face of the burners. Visually inspect the inside of the burners and crossovers for any block-
age caused by foreign matter. Remove any blockage.
9 − Reinstall the burner box assembly using the existing
four screws. Make sure that the burners line up in the center of the burner ports.
10 − Reconnect the sensor wire and reconnect the 2−pin
plug to the ignitor wiring harness. Reconnect wires to flame rollout switches.
11 − Reinstall the gas valve manifold assembly. Reconnect
the gas supply line to the gas valve. Reinstall the burn-
er box cover. 12 − Reconnect wires to gas valve. 13 − Replace the blower compartment access panel. 14 − Refer to instruction on verifying gas and electrical con-
nections when re−establishing supplies. 15 − Follow lighting instructions to light and operate fur-
nace for 5 minutes to ensure that heat exchanger is
clean and dry and that furnace is operating properly. 16 − Replace heating compartment access panel.
Page 50
Page 50
VII−WIRING DIAGRAM AND SEQUENCE OF OPERATION
1 − Line voltage is applied to L1 and N. the T1 low voltage transformer is energized, and line voltage is applied to B3 indoor blower.
2 − S47 rollout switch(es) must be closed in order for 24V from transformer to be output on integrated control "R" to power thermostat.
3 − When there is a call for heat, W1 of the thermostat energizes W of the furnace control with 24VAC.
4 − A92 integrated control runs a self−check. S10 primary limit and S21 secondary limit contacts are found to be closed. Call for heat can continue. 5 − A92 integrated control energizes B6 combustion air inducer. S18 combustion air pressure switch closes . Once S18 closes, a 15−second
pre−purge follows.
6 − A92 integrated control energizes R33 ignitor. A 20−second warm−up period begins.
7 − GV1 gas valve opens for a 4−second trial for ignition
8 − Flame is sensed, gas valve remains open for the heat call.
9 − After 30−second delay (from flame sensed), A92 integrated control applies 24VAC to Heat speed of B3 indoor blower.
10 − When heat demand is satisfied, W1 of the indoor thermostat de−energizes W of A92integrated control which de−energizes GV1 gas valve.
B6 combustion air inducer continues a 5−second post−purge period, and B3 indoor blower completes a selected OFF time delay.
1
8
2
4
6
7
3
9
10
1
5
5
Page 51
Page 51
Troubleshooting: Heating Sequence of Operation
HEATING SEQUENCE OF OPERATION
NORMAL HEATING MODE
ABNORMAL HEATING MODE
CONTROL SELF−CHECK OKAY?
BURNER OFF?
NORMAL OPERATION:
LED SLOW FLASH
NO
YES
YES
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER DELAY OFF.
LED SLOW FLASH
(RESET CONTROL BY TURNING MAIN POWER OFF.)
LED FLASHES CODE 1 − POLARITY
REVERSED.
POWER ON
IS POLARITY CORRECT?
ROLLOUT SWITCH CLOSED?
THERMOSTAT CALLS FOR HEAT:
LED SLOW FLASH
IS COMBUSTION AIR
PRESSURE SWITCH OPEN?
LED FLASHES CODE 8 − ROLLOUT SWITCH OPEN.
GAS VALVE OFF. COMBUSTION AIR INDUCER ON.
INDOOR BLOWER ON.
SEQUENCE HOLDS UNTIL ROLLOUT SWITCH CLOSES
AND POWER IS RESET OR T’STAT IS INTERRUPTED
FOR MINIMUM OF 1 SECOND.
LED FLASHES CODE 12 − FLAME SENSED
WITHOUT GAS VALVE ENERGIZED.
GAS VALVE OFF. COMBUSTION AIR INDUCER ON.
INDOOR BLOWER ON HEATING SPEED.
LED FLASHES CODE 11 − PRESSURE
SWITCH CLOSED.
GAS VALVE OFF COMBUSTION AIR
INDUCER OFF. INDOOR BLOWER
OFF WITH DELAY.
(Sequence holds until pressure switch
opens or thermostat resets control.)
NO
NO
YES
YES
IS VOLTAGE
ABOVE 70 VOLTS?
LED FLASHES CODE 13 − LOW LINE VOLTAGE.
CONTROL WILL NOT RESPOND TO A CALL FOR
HEATING UNTIL VOLTAGE RISES ABOVE 75 VOLTS.
NO
NO
NO
IS COMBUSTION AIR INDUCER
ENERGIZED?
HAS COMBUSTION AIR PRESSURE
SWITCH CLOSED IN 2.5 MINUTES?
YES
YES
LED FLASHES CODE 9 − PRESSURE SWITCH FAILED
TO CLOSE OR OPENED DURING HEAT DEMAND.
PRESSURE SWITCH IS IN WATCHGUARD MODE. GAS
VALVE OFF. COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF WITH DELAY. IS 5-MINUTE
RESET PERIOD COMPLETE?
NO
PRIMARY LIMIT SWITCH. CLOSED?
YES
YES
CONTINUED NEXT PAGE
LED FLASHES CODE 7 − PRIMARY
LMIT OPEN. COMBUSTION AIR
INDUCER OFF.I NDOOR BLOWER ON
NO
YES
NO
YES
IS THERE A PROPER GROUND?
YES
NO
LED FLASHES CODE 2 − IMPROPER
GROUND.
YES
YES
Page 52
Page 52
Troubleshooting: Heating Sequence of Operation (Continued)
HEATING SEQUENCE CONTINUED
NORMAL HEATING MODE ABNORMAL HEATING MODE
FLAME RECTIFICATION CURRENT
CHECK. CAN FLAME BE PROVEN WITHIN
4 SECONDS AFTER GAS VALVE OPENS?
(0.5 microamps)
FLAME PRESENT?
INDOOR BLOWER ON
AFTER 30−SECOND DELAY
PRIMARY LIMIT SWITCH CLOSED?
COMBUSTION AIR PRESSURE
SWITCH CLOSED?
LED FLASHES CODE 4 − LOW
FLAME SIGNAL.
(Does not affect operation of control)
LED FLASHES CODE 7 − PRIMARY LIMIT OPEN
GAS VALVE DE−ENERGIZED.
COMBUSTION AIR INDUCER DE−ENERGIZED.
INDOOR BLOWER ON UNTIL SWITCH CLOSES.
LIMIT SWITCH CLOSED?
GAS VALVE DE−ENERGIZED.
COMBUSTION AIR INDUCER ON.
INDOOR BLOWER OFF WITH DELAY
HAS CAI SWITCH CLOSED IN 2.5 MINUTES?
15-SECOND COMBUSTION AIR INDUCER PREPURGE
INITIATED BY CLOSED PRESSURE SWITCH.
YES
IGNITOR WARM-UP −− 20 SECONDS.
YES
YES
FLAME STABILIZATION PERIOD.
GAS VALVE OFF. COMBUSTION AIR INDUCER ON.
INDOOR BLOWER OFF.
HAS CONTROL FAILED TO SENSE FLAME FOR
FIVE CONSECUTIVE TRIES DURING A SINGLE
HEAT DEMAND?
LED SIGNAL WATCHGUARD FAILURE CODE
WATCHGUARD MODE. GAS VALVE OFF.
COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF WITH DELAY
IS 60-MINUTE RESET PERIOD COMPLETE?
YES
4 SECONDS
YES
HAS CONTROL RESET IGNITION
SEQUENCE FOUR TIMES?
FLAME SIGNAL 1.5 MICROAMPS OR GREATER?
YES
YES
YES
ROLLOUT SWITCH CLOSED?
LED FLASHES CODE 8 − ROLLOUT SWITCH OPEN.
GAS VALVE POWER OFF. COMBUSTION AIR INDUCER POWER ON. INDOOR BLOWER ON SEQUENCE HOLDS UNTIL ROLLOUT
SWITCH IS RESET AND MAIN POWER IS INTERRUPTED OR
THERMOSTAT IS CYCLED OFF/ON FOR 1 SEC. MINIMUM.
YES
THERMOSTAT DEMAND SATISFIED.
LED SLOW FLASH.
COMB. AIR INDUCER CONTINUES 5-SECOND
POST PURGE AFTER T’STAT DEMAND IS SATISFIED.
INDOOR AIR BLOWER COMPLETES SELECTED OFF"
DELAY BEFORE SHUTTING OFF.
YES
NO
5-MINUTE PRESSURE SWITCH
WATCHGUARD MODE.
YES
IS VOLTAGE ABOVE 70 VOLTS?
LED FLASHES CODE 13 −
LOW LINE VOLTAGE.
ONCE VOLTAGE IS ABOVE
75 VOLTS, HEATING
SEQUENCE RESTARTS.
NO
YES
YES
YES
NO
NO
NO
NO
NO
NO
YES
YES
NO
NO
NO
YES
YES
HAS PRIMARY LIMIT RESET
TIME EXCEEDED 3 MINUTES?
LED FLASHES CODE
7 − PRIMARY LIMIT
OPEN. GAS VALVE, COMB. AIR INDUCER AND INDOOR BLOW-
ER OFF. LEDs SIGNAL
LIMIT SWITCH OPEN
UNTIL MAIN
POWER IS INTERRUPTED OR T’STAT IS CYCLED
OFF/ON FOR 1 SEC.
MINIMUM. 60−MINUTE
WATCHGUARD PE-
RIOD STARTS AT
TIME LIMIT CLOSES.
IS 60−MIN. PERIOD
COMPLETE?
NO
YES
4-SECOND TRIAL FOR IGNITION.
GAS VALVE OPENS. IGNITOR ENERGIZED FOR
FIRST 3 SECONDS OF THE TRIAL.
LED FLASHES
CODE 10
1 HR PRESSURE
SWITCH
WATCHGUARD
MODE
HAS PRESSURE SWITCH OPENED 5
TIMES IN SAME HEAT DEMAND
NO
YES
Page 53
Page 53
Troubleshooting: Cooling Sequence of Operation
COOLING SEQUENCE OF OPERATION
NORMAL COOLING MODE ABNORMAL COOLING MODE
IGNITION CONTROL MAIN POWER ON.
CONTROL SELF DIAGNOSTIC CHECK.
IS CONTROL OPERATING NORMALLY?
YES
LED FLASHES CODE 1 POLARITY REVERSED
CONTROL WILL CONTINUE TO CALL FOR COOLING IN
THIS CONDITION.
POWER ON
LED FLASHES STEADY − CIRCUIT BOARD FAILURE
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF WITH NORMAL DELAY.
INTERRUPT MAIN POWER TO RESET CONTROL.
YES
IS POLARITY CORRECT?
ROLLOUT SWITCH MONITORED CONTINUOUSLY.
IS ROLLOUT SWITCH CLOSED?
LED: SLOW FLASH RATE REMAINS UNCHANGED
THROUGHOUT COOLING CYCLE.
THERMOSTAT CALLS FOR COOLING.
COMPRESSOR CONTACTOR AND SYSTEM FAN
ENERGIZED WITH 2-SECOND DELAY
(COOLING SPEED)
COMPRESSOR OFF.
THERMOSTAT OPENS.
SYSTEM FAN AND EAC TERM. OFF
WITH 45-SECOND DELAY.
NO
NO
LED FLASHES CODE 8 ROLLOUT SWITCH OPEN. GAS
VALVE OFF. COMBUSTION AIR INDUCER ON. INDOOR
BLOWER ON. SEQUENCE HOLDS UNTIL ROLLOUT SWITCH
CLOSES AND MAIN POWER IS INTERRUPTED OR
THERMOSTAT IS CYCLED OFF/ON FOR 1 SEC. MINIMUM.
IS VOLTAGE
ABOVE 70 VOLTS?
LED FLASHES CODE 13 LOW VOLTAGE. CONTROL
WILL CONTINUE TO CALL FOR COOLING
IN THIS CONDITION.
YES
YES
NO
NO
IS THERE A PROPER GROUND?
YES
NO
LED FLASHES CODE 2 IMPROPER GROUND
CONTROL WILL CONTINUE TO CALL FOR COOLING
IN THIS CONDITION.
Page 54
Page 54
Troubleshooting: Continuous Fan / Accessories Sequence of Operation
CONTINUOUS FAN / ACCESSORIES SEQUENCE OF OPERATION
LED: SLOW FLASH RATE REMAINS
UNCHANGED THROUGHOUT SEQUENCE.
MANUAL FAN SELECTION MADE AT THERMOSTAT.
CONTROL (G) ENERGIZES SYSTEM FAN AT FAN
SPEED. EAC TERMINAL IS ENERGIZED.
THERMOSTAT CALLS FOR HEAT (W).
THERMOSTAT CALLS FOR COOLING.
THERMOSTAT OPENS.
SYSTEM FAN SWITCHED TO COOL SPEED.
EAC TERM. REMAINS ON.
THERMOSTAT OPENS.
MANUAL FAN SELECTION MADE AT THERMOSTAT.
CONTROL (G) ENERGIZES SYSTEM FAN AT FAN
SPEED. EAC TERM. ENERGIZED.
NO
YES
YES
NO
SYSTEM FAN SWITCHES TO HEAT SPEAD AFTER 30
SECOND DELAY. EAC AND HUM TERMINALS REMAIN ON.
SYSTEM FAN CONTINUES FAN SPEED WITHOUT
INTERRUPTION. EAC TERMINAL REMAIN ON.
HUM TERMINALS ARE ENERGIZED WITH
COMBUSTION AIR BLOWER.
HUM. TERMINALS OFF AFTER POST PURGE BY COMBUSTION AIR INDUCER. SYTEM FAN
SWITCHES TO FAN SPEED AFTER BLOWER
OFF DELAY. EAC CONTINUES WITHOUT
INTERUPTION.
Loading...