Lennox EL195UH040NE36B, EL195UH060NE36B, EL195UH080NE48C, EL195UH100NE60C Installation Instructions And Use

© 2018 Lennox Industries Inc.
Dallas, Texas USA
INSTALLATION INSTRUCTIONS EL195UHNE
ELITE® SERIES GAS FURNACE UPFLOW / HORIZONTAL AIR DISCHARGE
507758-02 02/2018 Supersedes 507758-01
THIS MANUAL MUST BE LEFT WITH THE
This is a safety alert symbol and should never be ignored. When you see this symbol on labels or in man­uals, be alert to the potential for personal injury or death.
CAUTION
As with any mechanical equipment, contact with sharp sheet metal edges can result in personal injury. Take care while handling this equipment and wear gloves and protective clothing.
Contents
Unit Dimensions - inches (mm) ......................................2
EL195UHNE Gas Furnace .............................................3
Shipping and Packing List ..............................................3
Safety Information ..........................................................3
Use of Furnace as Construction Heater .........................4
General ........................................................................... 5
Combustion, Dilution & Ventilation Air ............................5
Shipping Bolt Removal ...................................................8
Installation - Setting Equipment ...................................... 8
Filters ............................................................................ 13
Duct System .................................................................13
Pipe Fittings Specications...........................................13
Joint Cementing Procedure .......................................... 16
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a licensed professional HVAC installer or equivalent, service agency, or the gas supplier.
Venting Practices ..........................................................16
Vent Piping Guidelines .................................................17
Gas Piping .................................................................... 36
Electrical ....................................................................... 38
Ignition Control .............................................................41
Unit Start-Up ................................................................. 41
Gas Pressure Adjustment ............................................. 44
Proper Combustion.......................................................44
High Altitude Information .............................................. 44
Testing for Venting and Combustion Air........................45
Service..........................................................................46
Repair Parts List ........................................................... 48
Start-Up & Performance Check List .............................49
Page 1
EL195UHNE Unit Dimensions - inches (mm)
(19)
EXHAUST AIR
FRONT VIEW SIDE VIEW
1-1/2
1
NOTE - 60C size units that require air volumes over 1800 cfm must have one of the following:
1. Single side return air and Optional Return Air Base with transition that must accommodate required 20 x 25 x 1 inch (508 x 635 x 25 mm) air filter to maintain proper velocity.
2. Bottom return air.
3. Return air from both sides.
4. Bottom and one side return air. See Blower Performance Tables for additional information.
2
Optional Side Return Air Filter Kit is not for use with the Optional Return Air Base.
A
B
9/16 (14)
2
OPTIONAL
SIDE RETURN
AIR FILTER KIT
(Either Side)
14-3/4
(375)
16
(406)
33
(838)
1-7/8 (48)
COMBUSTION
AIR INTAKE
2
OPTIONAL
SIDE RETURN
AIR FILTER KIT
(Either Side)
1-1/2 (38)
Front Panel
6-5/8 (168)
12-5/8
(321)
Not Used
ELECTRICAL
INLET
(Either Side)
2-7/8
(73)
3-1/4
(83)
2-1/4
(57)
OUTLET
SUPPLY AIR
OPENING
23-3/4
(603)
25
(635)
TOP VIEW
27-3/4
(705)
19-7/16
(494)
INTAKE AIR
GAS PIPING INLET (Right Side Only)
CONDENSATE TRAP CONNECTION (Either Side)
6-1/2 (165) (Either Side)
23
(584)
1
Side Return Air Opening (Either Side)
9/16
(14)
(38)
14
(356)
AIR FLOW
3/4
C
1
Bottom Return
Air Opening
3/4
(19)
Model
EL195UH040NE36B EL195UH060NE36B
17-1/2 (446) 16-3/8 (416) 16 (406)
EL195UH080NE48C EL195UH100NE60C
in (mm)
21 (553) 19-7/8 (505) 19-1/2 (495)
A
5/8
(16)
Page 2
3-1/4
(83)
in (mm)
B
23-1/2
(597)
1
Bottom Return
Air Opening
1-15/16 (49)
C
in (mm)
EL195UHNE Gas Furnace
The EL195UHNE Category IV gas furnace is shipped ready for
installation in the upow or horizontal position. The furnace is
shipped with the bottom panel in place. The bottom panel must
be removed if the unit is to be installed in horizontal or upow
applications with bottom return air.
The EL195UHNE can be installed as either a Direct Vent or a Non-Direct Vent gas central furnace. The fur-
nace is equipped for installation in natural gas applications.
NOTE - In Direct Vent installations, combustion air is tak-
en from outdoors and ue gases are discharged outdoors.
In Non-Direct Vent installations, combustion air is taken
from indoors or ventilated attic or crawlspace and ue gases are discharged outdoors. See gures 1 and 2 for applications involving roof termination.
DIRECT VENT INSTALLATION NON-DIRECT VENT
EXHAUST OUTLET
COMBUSTION
AIR INTAKE OUTSIDE
OF HOUSE
INSTALLATION
EXHAUST
OUTLET
Shipping and Packing List
Package 1 of 1 contains
1 - Assembled EL195UHNE unit 1 - Bag assembly containing the following:
1 - Snap bushing 1 - 1/2” diameter threaded street elbow 1 - Snap plug 1 - Wire tie 1 - Condensate trap 1 - Condensate trap cap 1 - Condensate trap clamp 1 - 2” diameter debris screen 1 - 3/4” Threaded street elbow
Check equipment for shipping damage. If you nd any
damage, immediately contact the last carrier. The following items may also be ordered separately: 1 - Thermostat 1 - Return air base kit
1 - Horizontal suspension kit
Safety Information
Figure 1
NON-DIRECT VENT
INSTALLATION
EXHAUST OUTLET
COMBUSTION
AIR INTAKE INSIDE
VENTILATED
ATTIC SPACE
Figure 2
COMBUSTION
AIR INTAKE
INSIDE
OF HOUSE
NON-DIRECT VENT
INSTALLATION
EXHAUST OUTLET
COMBUSTION
AIR INTAKE INSIDE
VENTILATED
CRAWL SPACE
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a licensed professional HVAC installer or equivalent, service agency, or the gas supplier.
CAUTION
As with any mechanical equipment, contact with sharp sheet metal edges can result in personal injury. Take care while handling this equipment and wear gloves and protective clothing.
Use only the type of gas approved for use with this fur­nace. Refer to unit nameplate.
EL195UHNE units are CSA International certied to ANSI
Z21.47 and CSA 2.3 standards. Building Codes In the USA, installation of gas furnaces must conform with
local building codes. In the absence of local codes, units must be installed according to the current National Fuel Gas Code (ANSI-Z223.1/NFPA 54). The National Fuel Gas Code is available from the following address:
American National Standards Institute, Inc. 11 West 42nd Street New York, NY 10036
In Canada, installation must conform with current National Standard of Canada CSA-B149 Natural Gas and Propane Installation Codes, local plumbing or waste water codes and other applicable local codes.
Page 3
In order to ensure proper unit operation in non-direct vent
Heating Unit Installed Parallel to Air Handler Unit
Cooling Coil
applications, combustion and ventilation air supply must be provided according to the current National Fuel Gas Code or CSA-B149 standard.
Installation Locations
This furnace is CSA International certied for installation
clearances to combustible material as listed on the unit
nameplate and in the table in gure 12. Accessibility and service clearances must take precedence over re protec-
tion clearances.
NOTE - For installation on combustible oors, the furnace shall not be installed directly on carpeting, tile, or other combustible material other than wood ooring.
For installation in a residential garage, the furnace must be installed so that the burner(s) and the ignition source are located no less than 18 inches (457 mm) above the
oor. The furnace must be located or protected to avoid
physical damage by vehicles. When a furnace is installed in a public garage, hangar, or other building that has a hazardous atmosphere, the furnace must be installed ac­cording to recommended good practice requirements and current National Fuel Gas Code or CSA B149 standards.
NOTE - Furnace must be adjusted to obtain a temperature
rise within the range specied on the unit nameplate. Fail­ure to do so may cause erratic limit operation and prema­ture heat exchanger failure.
This EL195UHNE furnace must be installed so that its electrical components are protected from water.
Installed in Combination with a Cooling Coil
When this furnace is used with cooling coils (gure 3), it
shall be installed in parallel with, or on the upstream side of, cooling coils to avoid condensation in the heating com-
partment. With a parallel ow arrangement, a damper (or other means to control the ow of air) must adequately
prevent chilled air from entering the furnace. If the damp­er is manually operated, it must be equipped to prevent operation of either the heating or the cooling unit, unless it is in the full HEAT or COOL setting.
When installed, this furnace must be electrically grounded according to local codes. In addition, in the United States, installation must conform with the current National Elec­tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available from the following ad­dress:
National Fire Protection Association 1 Battery March Park Quincy, MA 02269
In Canada, all electrical wiring and grounding for the unit must be installed according to the current regulations of the Canadian Electrical Code Part I (CSA Standard C22.1)
and/or local codes.
Dampers
(open during heating operation only)
Gas Unit
AIR FLOWAIR FLOW
Air Handler Unit
Dampers
(open during cooling operation only)
Heating Unit Installed Upstream of Cooling Coil
AIR FLOW AIR FLOW
Gas Unit
Figure 3
NOTE - This furnace is designed for a minimum contin­uous return air temperature of 60°F (16°C) or an inter­mittent operation down to 55°F (13°C) dry bulb for cases where a night setback thermostat is used. Return air tem­perature must not exceed 85°F (29°C) dry bulb.
The EL195UHNE furnace may be installed in alcoves, closets, attics, basements, garages, crawl spaces and
utility rooms in the upow or horizontal position. This fur­nace design has not been CSA certied for installation in
mobile homes, recreational vehicles, or outdoors.
Use of Furnace as Construction Heater
Lennox does not recommend the use of EL195UHNE units as a construction heater during any phase of con­struction. Very low return air temperatures, harmful vapors
and operation of the unit with clogged or misplaced lters
will damage the unit. Units may be used for heating of buildings or structures
under construction, if the following conditions are met::
The vent system must be permanently installed per
these installation instructions.
A room thermostat must control the furnace. The
use of xed jumpers that will provide continuous heating is not allowed.
The return air duct must be provided and sealed to
the furnace.
Return air temperature range between 60°F (16°C)
and 80°F (27°C) must be maintained.
Air lters must be installed in the system and must
be maintained during construction.
Page 4
Air lters must be replaced upon construction com-
pletion.
The input rate and temperature rise must be set per
the furnace rating plate.
One hundred percent (100%) outdoor air must be
provided for combustion air requirements during construction. Temporary ducting may supply out­door air to the furnace. Do not connect duct directly to the furnace. Size the temporary duct following these instructions in section for Combustion, Dilu­tion and Ventilation Air in a conned space with air from outside.
The furnace heat exchanger, components, duct
system, air lters and evaporator coils must be thoroughly cleaned following nal construction clean-up.
All furnace operating conditions (including ignition,
input rate, temperature rise and venting) must be veried according to these installation instructions.
General
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities having jurisdiction before installation.
In addition to the requirements outlined previously, the following general recommendations must be considered when installing a EL195UHNE furnace:
• Place the furnace as close to the center of the air distribution system as possible. The furnace should also be located close to the vent termination point.
• When the furnace is installed in non-direct vent ap­plications, do not install the furnace where drafts might blow directly into it. This could cause improp­er combustion and unsafe operation.
• When the furnace is installed in non-direct vent ap­plications, do not block the furnace combustion air opening with clothing, boxes, doors, etc. Air is need­ed for proper combustion and safe unit operation.
• When the furnace is installed in an attic or other insulated space, keep insulation away from the fur­nace.
• When the furnace is installed in an unconditioned space, consider provisions required to prevent
freezing of condensate drain system.
• Please consult the manufacturer of your evaporator coil for their recommendations on distance required between the heat exchanger and their drain pan. Adequate space must be provided between the drain pan and the furnace heat exchanger.
CAUTION
EL195UHNE unit should not be installed in areas
normally subject to freezing temperatures.
WARNING
Insufcient combustion air can cause headaches, nausea, dizziness or asphyxiation. It will also cause
excess water in the heat exchanger resulting in rusting and premature heat exchanger failure. Excessive exposure to contaminated combustion air will result in safety and performance related problems. Avoid exposure to the following substances in the combustion air supply:
Permanent wave solutions Chlorinated waxes and cleaners Chlorine base swimming pool chemicals Water softening chemicals De-icing salts or chemicals Carbon tetrachloride Halogen type refrigerants Cleaning solvents (such as perchloroethylene) Printing inks, paint removers, varnishes, etc. Hydrochloric acid Cements and glues Antistatic fabric softeners for clothes dryers Masonry acid washing materials
Combustion, Dilution & Ventilation Air
If the EL195UHNE is installed as a Non-Direct Vent Furnace, follow the guidelines in this section.
NOTE - In Non-Direct Vent installations, combustion air is taken from indoors or ventilated attic or crawlspace and
ue gases are discharged out-doors.
In the past, there was no problem in bringing in sufcient outdoor air for combustion. Inltration provided all the air
that was needed. In today’s homes, tight construction practices make it necessary to bring in air from outside for combustion. Take into account that exhaust fans, appli-
ance vents, chimneys, and replaces force additional air
that could be used for combustion out of the house. Unless outside air is brought into the house for combus-
tion, negative pressure (outside pressure is greater than inside pressure) will build to the point that a downdraft can occur in the furnace vent pipe or chimney. As a result, combustion gases enter the living space creating a poten­tially dangerous situation.
In the absence of local codes concerning air for combus­tion and ventilation, use the guidelines and procedures in this section to install EL195UHNE furnaces to ensure efcient and safe operation. You must consider combus­tion air needs and requirements for exhaust vents and gas piping. A portion of this information has been reprinted with permission from the National Fuel Gas Code (ANSI­Z223.1/NFPA 54). This reprinted material is not the com-
plete and ofcial position of the ANSI on the referenced
subject, which is represented only by the standard in its entirety.
Page 5
In Canada, refer to the CSA B149 installation codes.
EQUIPMENT IN CONFINED SPACE - ALL AIR FROM INSIDE
(64516mm.
CAUTION
Do not install the furnace in a corrosive or contaminated atmosphere. Meet all combustion and ventilation air requirements, as well as all local codes.
All gas-red appliances require air for the combustion process. If sufcient combustion air is not available, the furnace or other appliance will operate inefciently and
unsafely. Enough air must be provided to meet the needs of all fuel-burning appliances and appliances such as ex­haust fans which force air out of the house. When replac­es, exhaust fans, or clothes dryers are used at the same time as the furnace, much more air is required to ensure proper combustion and to prevent a downdraft. Insuf­cient air causes incomplete combustion which can result in carbon monoxide.
In addition to providing combustion air, fresh outdoor air dilutes contaminants in the indoor air. These contaminants may include bleaches, adhesives, detergents, solvents and other contaminants which can corrode furnace com­ponents.
The requirements for providing air for combustion and ventilation depend largely on whether the furnace is in-
stalled in an unconned or a conned space.
Unconned Space
An unconned space is an area such as a basement or
large equipment room with a volume greater than 50 cubic feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of the com­bined input rating of all appliances installed in that space. This space also includes adjacent rooms which are not separated by a door. Though an area may appear to be
unconned, it might be necessary to bring in outdoor air
for combustion if the structure does not provide enough air
by inltration. If the furnace is located in a building of tight
construction with weather stripping and caulking around the windows and doors, follow the procedures in the Air from Outside section.
Conned Space
A conned space is an area with a volume less than 50
cubic feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of the combined input rating of all appliances installed in that
space. This denition includes furnace closets or small
equipment rooms. When the furnace is installed so that supply ducts carry
air circulated by the furnace to areas outside the space containing the furnace, the return air must be handled by ducts which are sealed to the furnace casing and which terminate outside the space containing the furnace. This is especially important when the furnace is mounted on
a platform in a conned space such as a closet or small
equipment room.
Even a small leak around the base of the unit at the plat­form or at the return air duct connection can cause a po­tentially dangerous negative pressure condition. Air for combustion and ventilation can be brought into the con-
ned space either from inside the building or from outside
.Air from Inside
If the conned space that houses the furnace adjoins a space categorized as unconned, air can be brought in by
providing two permanent openings between the two spac­es. Each opening must have a minimum free area of 1 square inch (645 mm2) per 1,000 Btu (.29 kW) per hour of
total input rating of all gas-red equipment in the conned
space. Each opening must be at least 100 square inches (64516 mm2). One opening shall be within 12 inches (305 mm) of the top of the enclosure and one opening within 12
inches (305 mm) of the bottom. See gure 4.
ROOF TERMINATED
EXHAUST PIPE
OPENINGS
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
NOTE - Each opening shall have a free area of at least one square inch per 1,000 Btu (645mm all equipment in the enclosure, but not less than 100 square inches
2).
EL296UH
V
2
per .29kW) per hour of the total input rating of
(To Adjacent
Unconfined
Space)
Figure 4
Air from Outside
If air from outside is brought in for combustion and ventila­tion, the conned space shall be provided with two perma­nent openings. One opening shall be within 12” (305mm) of the top of the enclosure and one within 12” (305mm) of the bottom. These openings must communicate directly or by ducts with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors or indirectly through vertical ducts. Each opening shall have a minimum free area of 1 square inch per 4,000 Btu (645mm2 per 1.17kW) per hour of total input rating of all equipment in the en­closure. When communicating with the outdoors through
horizontal ducts, each opening shall have a minimum free
area of 1 square inch per 2,000 Btu (645mm2 per .59kW) per total input rating of all equipment in the enclosure (See
gure 5).It is also permissible to bring in air for combustion from a ventilated attic (gure 6) or ventilated crawl space (gure 7).
Page 6
EQUIPMENT IN CONFINED SPACE - ALL AIR FROM OUTSIDE
(Inlet Air from Crawl Space and Outlet Air to Outside)
hour of the total input rating of all equipment in the enclosure.
hour of the total input rating of all equipment in the enclosure.
EQUIPMENT IN CONFINED SPACE
VENTILATION LOUVERS
OUTLET
AIR
(Each end of attic)
ROOF TERMINATED
EXHAUST PIPE
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
FURNACE
INLET
AIR
VENTILATION
LOUVERS
(For unheated
crawl space)
(Inlet Air from Ventilated Crawlspace and Outlet Air to Outside)
Roof Terminated
Exhaust Pipe
Inlet Air
(Minimum
Ventilation
Louvers
(Crawl space)
Furnace
12 in.(305mm)
Above crawl
space floor)
NOTE-The inlet and outlet air openings shall each have a free area of at least one square inch per 4,000 Btu (645mm
2
per 1.17kW) per
Figure 5
(Inlet Air from Ventilated Attic and Outlet Air to Outside)
Roof Terminated
Exhaust Pipe
NOTE-The inlet and outlet air openings shall each have a free area of at least one square inch per 4,000 Btu (645mm hour of the total input rating of all equipment in the enclosure.
EQUIPMENT IN CONFINED SPACE
Ventilation Louvers
12 in.(305mm) Above
*Intake Debris
Screen
(Provided)
Furnace
2
per 1.17kW) per
Figure 6
(Minimum
attic floor)
Inlet Air
Coupling or 3 in. to 2 in.
Transition
(Field Provided)
NOTE-The inlet and outlet air openings shall each have a free area of at least one square inch per 4,000 Btu (645mm
*Intake Debris Screen Provided)
2
per 1.17kW) per
Figure 7
If air from outside is brought in for combustion and ventila­tion, the conned space must have two permanent open­ings. One opening shall be within 12 inches (305 mm) of the top of the enclosure and one opening within 12 inches (305 mm) of the bottom. These openings must communi­cate directly or by ducts with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors or in­directly through vertical ducts. Each opening shall have a minimum free area of 1 square inch (645 mm2) per 4,000 Btu (1.17 kW) per hour of total input rating of all equipment
in the enclosure. See gures 5 and 8. When communi­cating with the outdoors through horizontal ducts, each
opening shall have a minimum free area of 1 square inch (645 mm2) per 2,000 Btu (.56 kW) per total input rating of
all equipment in the enclosure. See gure 9.
When ducts are used, they shall be of the same cross-sec­tional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be no less than 3 inches (75 mm). In calculating free area, the blocking effect of louvers, grilles, or screens must be considered. If the design and free area of protec-
tive covering is not known for calculating the size opening
required, it may be assumed that wood louvers will have 20 to 25 percent free area and metal louvers and grilles will have 60 to 75 percent free area. Louvers and grilles
must be xed in the open position or interlocked with the
equipment so that they.
Page 7
EQUIPMENT IN CONFINED SPACE - ALL AIR FROM OUTSIDE
ROOF TERMINATED
EQUIPMENT IN CONFINED SPACE -
hour of the total input rating of all other equipment in the enclosure.
EXHAUST PIPE
(All Air Through Ventilated Attic)
VENTILATION LOUVERS
(Each end of attic)
OUTLET
AIR
exible mounting leg). See gure 10. The bolt and washer
must be removed before the furnace is placed into oper­ation. After the bolt and washer have been removed, the rigid leg will not touch the blower housing.
Units with 1/2 or 3/4 HP Blower Motor
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
NOTE-The inlet and outlet air openings shall each have a free area of at least one square inch per 4,000 Btu (645mm of the total input rating of all equipment in the enclosure.
FURNACE
INLET AIR
(Ends 12” above
2
per 1.17kW) per hour
Figure 8
ALL AIR FROM OUTSIDE
ROOF TERMINATED
EXHAUST PIPE
OUTLET AIR
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
NOTE-Each air duct opening shall have a free area of at least one square inch per 2,000 Btu (645mm input rating of all equipment in the enclosure. If the equipment room
cate directly with the outdoors, each opening shall have a free area of at least 1 square inch per 4,000 Btu (645mm
FURNACE
INLET AIR
2
per .59kW) per hour of the total
2
per 1.17kW) per
Figure 9
Shipping Bolt Removal
Units with 1/2 and 3/4 hp blower motor are equipped
with three exible legs and one rigid leg. The rigid leg is equipped with a shipping bolt and a at white plastic wash-
er (rather than the rubber mounting grommet used with a
remove shipping bolt and washe
RIGID LEG
bottom)
Figure 10
Installation - Setting Equipment
WARNING
Do not connect the return air duct to the back of the furnace. Doing so will adversely affect the operation of the safety control devices, which could result in personal injury or death.
WARNING
Blower access panel must be securely in place when blower and burners are operating. Gas fumes, which could contain carbon monoxide, can be drawn into living space resulting in personal injury or death.
Upow Applications
The EL195UHNE gas furnace can be installed as shipped
in the upow position. Refer to gure 12 for clearances.
Select a location that allows for the required clearances that are listed on the unit nameplate. Also consider gas supply connections, electrical supply, vent connection, condensate trap and drain connections, and installation and service clearances [24 inches (610 mm) at unit front]. The unit must be level from side to side. The unit may be
positioned from level to ½” toward the front. See gure 11.
Allow for clearances to combustible materials as indicated on the unit nameplate.
Page 8
SETTING EQUIPMENT
END VIEW
Unit must be level side-to-side. Unit may be positioned from level to 1/2” toward the front to aid in draining.
UPFLOW APPLICATION
UNIT
FRONT
1/2” max.
SIDE VIEW
AIR FLOW
FRONT VIEW
UNIT
FRONT
SIDE VIEW
HORIZONTAL APPLICATION
AIR FLOW
FRONT VIEW
Figure 11
UNIT
FRONT
1/2”
max.
Page 9
WARNING
Installation Clearances
Top
Bottom (Floor)
Left Side
Right Side
Top/Plenum 1 in. (25 mm)
*Front 1
Back 1
Sides 1
Vent 1
Floor 0
*Front clearance in alcove installation must be 24 in. (610 mm). Maintain a minimum of 24 in. (610 mm) for front service access.
Allow proper clearances to accommodate condensate trap.For installations on a combustible floor, do not install the furnace
directly on carpeting, tile or other combustible materials other than wood flooring.
Side Return Air
Transition
Improper installation of the furnace can result in personal
injury or death. Combustion and ue products must
never be allowed to enter the return air system or air in the living space. Use sheet metal screws and joint tape to seal return air system to furnace.
In platform installations with furnace return, the furnace should be sealed airtight to the return air plenum. A door must never be used as a portion of the return air duct system. The base must provide a stable support and an airtight seal to the furnace. Allow absolutely no sagging, cracks, gaps, etc. For no reason should return and supply air duct systems ever be connected to or from
other heating devices such as a replace or stove, etc.
Fire, explosion, carbon monoxide poisoning, personal injury and/or property damage could result.
Return Air Guidelines
Return air can be brought in through the bottom or either
side of the furnace installed in an upow application. If the
furnace is installed on a platform with bottom return, make an airtight seal between the bottom of the furnace and the platform to ensure that the furnace operates properly and safely. The furnace is equipped with a removable bottom panel to facilitate installation.
Markings are provided on both sides of the furnace cabinet for installations that require side return air. Cut the furnace cabinet at the maximum dimensions shown on page 2.
Refer to Engineering Handbook for additional information.
EL195UHNE applications which include side return air and a condensate trap installed on the same side of the cabinet (trap can be installed remotely within 5
ft.) require either a return air base or eld-fabricated
transition to accommodate an optional IAQ accessory
taller than 14.5”. See gure 13.
(with transition and filter)
Figure 12
20” X 25” X 1”
(508mmX635mmX 25mm)
Air Filter
Return
Air
Plenum
Figure 13
Page 10
Optional Return Air Base
To minimize pressure drop, the largest opening height possible (up to 14 inches) is preferred.
CONDENSATE
Removing the Bottom Panel
Bottom Panel
TRAP
AIR FLOW
FURNACE
FRONT
INDOOR AIR
QUALITY CABINET
(PCO, Filter
Cabinet, etc.)
(Upflow Applications Only)
IF BASE IS USED
WITHOUT
IAQ CABINET,
A SINGLE
RETURN AIR
PLENUM
MUST
COVER BOTH
UNIT AND
RETURN
AIR BASE
OPENINGS
3−1/4
(83)
7−1/4 (184)
1
23 (584)
Overall
(Maximum)
1
Unit side return air
Opening
5−5/8 (143)
SIDE RETURN
AIR OPENINGS
(Either Side)
1
Minimum
11 (279)
2
Maximum
14 (356)
1
22−7/16
(570)
Overall
(Maximum)
17−1/2 (446) B Width (50W98) 21 (533) C Width (50W99)
24−1/2 (622) D Width (51W00)
OPTIONAL RETURN AIR BASE
23
(584)
26−7/8
(683)
SIDE VIEW
3/4
(19)
FRONT VIEW
NOTE- Optional side return air filter kits are not for use with return air base.
1
Both the unit return air opening and the base return air opening must be covered by a single plenum or IAQ cabinet. Minimum unit side return air opening dimensions for units requiring 1800 cfm or more of air (W x H): 23 x 11 in. (584 x 279 mm). The opening can be cut as needed to accommodate plenum or IAQ cabinet while maintaining dimensions shown. Side return air openings must be cut in the field. There are cutting guides stenciled on the cabinet for the side return air opening. The size of the opening must not extend beyond the markings on the furnace cabinet.
2
Figure 14
Removing the Bottom Panel
Remove the two screws that secure the bottom cap to the furnace. Pivot the bottom cap down to release the bottom panel. Once the bottom panel has been removed, reinstall
the bottom cap. See gure 15.
Horizontal Applications
WARNING
Do not install the furnace on its front or back. See gure
16.
See figure 4.
Screw
Bottom Cap
Figure 15
Page 11
Front Back
Figure 16
The EL195UHNE furnace can be installed in horizontal
Horizontal Application
Installation Clearances
dnE thgiRdnE tfeL
Right-Hand Discharge
Left-Hand Discharge
Top
Bottom (Floor)**
Bottom (Floor)**
dnE thgiRdnE tfeL
Air
Flow
Air
Flow
Air
Flow
Air
Flow
Top 1
Front* 1
Back 1
Ends 1
Vent 1
Floor 1
*Front clearance in alcove installation must be 24 in. (610 mm). Maintain a minimum of 24 in. (610 mm) for front service access. **An 8” service clearance must be maintained below the unit to provide for servicing of the condensate trap. For installations on a combustible floor, do not install the furnace directly on carpeting, tile or other combustible materials other than wood flooring.
applications with either right- or left-hand air discharge.
Refer to gure 17 for clearances in horizontal applications
.
Figure 17
Suspended Installation of Horizontal Unit
This furnace may be installed in either an attic or a crawl­space. Either suspend the furnace from roof rafters or
oor joists, as shown in gure 18, or install the furnace on a platform, as shown in gure 19. A horizontal suspension
kit (51W10) may be ordered from Lennox or use equiva­lent.
NOTE - Heavy-gauge sheet metal straps may be used to suspend the unit from roof rafters or ceiling joists. Straps are used to suspend the unit in this way, support must be provided for both the ends. The straps must not interfere with the plenum or exhaust piping installation. Cooling
coils and supply and return air plenums must be sup­ported separately.
Page 12
HORIZONTAL SUSPENSION KIT
Metal Strap
(typical)
Internal Brace
(provided with kit)
Bracket (typical)
Air
Flow
Figure 18
NOTE - When the furnace is installed on a platform or with
the horizontal suspension kit in a crawlspace, it must be elevated enough to avoid water damage, accommodate drain trap and to allow the evaporator coil to drain.
Platform Installation of Horizontal Unit
1 - Select location for unit keeping in mind service and
other necessary clearances. See gure 17.
2 - Construct a raised wooden frame and cover frame
with a plywood sheet. If unit is installed above
nished space, fabricate an auxiliary drain pan to be
installed under unit. Set unit in drain pan as shown
in gure 19. Leave 8 inches for service clearance
below unit for condensate trap.
3 - Provide a service platform in front of unit. When
installing the unit in a crawl space, a proper support platform may be created using cement blocks.
4 - Route auxiliary drain line so that water draining from
this outlet will be easily noticed by the homeowner.
5 - If necessary, run the condensate line into a condensate
pump to meet drain line slope requirements. The pump must be rated for use with condensing furnaces. Protect the condensate discharge line
from the pump to the outside to avoid freezing.
6 - Continue with exhaust, condensate and intake piping
installation according to instructions.
INTAKE PIPE
EXHAUST PIPE
*Gas connector may be used for Canadian
able by local authority having jurisdiction.
SERVICE PLATFORM
*GAS CONNECTION
RAISED
PLATFORM
Figure 19
Return Air -- Horizontal Applications
Return air may be brought in only through the end of a
furnace installed in the horizontal position. The furnace is
equipped with a removable bottom panel to facilitate in-
stallation. See gure 15.
Filters
This unit is not equipped with a lter or rack. A eld-pro­vided high velocity rated lter is required for the unit to operate properly. Table 1 lists recommended lter sizes. A lter must be in place whenever the unit is operating.
IMPORTANT
If a high-efciency lter is being installed as part of this system to ensure better indoor air quality, the lter must be properly sized. High-efciency lters have a higher static pressure drop than standard efciency glass/foam lters. If the pressure drop is too great, system capacity
and performance may be reduced The pressure drop may also cause the limit to trip more frequently during
the winter and the indoor coil to freeze in the summer,
resulting in an increase in the number of service calls.
Before using any lter with this system, check the specications provided by the lter manufacturer against
the data given in the appropriate Lennox Product
Specications bulletin. Additional information is provided
in Service and Application Note ACC002 (August 2000).
Duct System
Use industry-approved standards to size and install the
supply and return air duct system. Figure 20 shows the correct supply and return duct installation. Refer to ACCA Manual D. This will result in a quiet and low-static system that has uniform air distribution.
NOTE - This furnace is not certied for operation in heat­ing mode (indoor blower operating at selected heating speed) with an external static pressure which exceeds 0.5 inches w.c. Operation at these conditions may result in improper limit operation.
Supply Air Plenum
If the furnace is installed without a cooling coil, a remov­able access panel should be installed in the supply air duct. The access panel should be large enough to per­mit inspection of the heat exchanger. The furnace access panel must always be in place when the furnace is operat­ing and it must not allow leaks.
Return Air Plenum
NOTE - Return air must not be drawn from a room
where this furnace, or any other gas-fueled appliance (i.e., water heater), or carbon monoxide-producing de­vice (i.e., wood replace) is installed.
When return air is drawn from a room, a negative pressure is created in the room. If a gas appliance is operating in
a room with negative pressure, the ue products can be
pulled back down the vent pipe and into the room. This reverse ow of the ue gas may result in incomplete com­bustion and the formation of carbon monoxide gas. This raw gas or toxic fumes might then be distributed through­out the house by the furnace duct system.
Return air can be brought in through the bottom or either side of the furnace (return air brought into either side of
furnace allowed in upow applications only). If a furnace
with bottom return air is installed on a platform, make an airtight seal between the bottom of the furnace and the platform to ensure that the unit operates properly and safely. Use berglass sealing strips, caulking, or equiva­lent sealing method between the plenum and the furnace
cabinet to ensure a tight seal. If a lter is installed, size the return air duct to t the lter frame.
TABLE 1
Furnace
Cabinet Width
17-1/2” 16 X 25 X 1 (1) 16 X 25 X 1 (1)
21” 16 X 25 X 1 (1) 20 X 25 X 1 (1)
Side Return Bottom Return
Filter Size
Page 13
SUPPLY
AIR
Duct System and Proper Installation
SUPPLY
AIR
tinU latnoziroHtinU wolfpU
Figure 20
Pipe & Fittings Specications
All pipe, ttings, primer and solvent cement must conform
with American National Standard Institute and the Ameri­can Society for Testing and Materials (ANSI/ASTM) stan-
dards. The solvent shall be free owing and contain no
lumps, undissolved particles or any foreign matter that adversely affects the joint strength or chemical resistance of the cement. The cement shall show no gelation, strati-
cation, or separation that cannot be removed by stirring. Refer to the table 2 below for approved piping and tting
materials.
CAUTION
Solvent cements for plastic pipe are ammable liquids
and should be kept away from all sources of ignition. Do not use excessive amounts of solvent cement when making joints. Good ventilation should be maintained to
reduce re hazard and to minimize breathing of solvent
vapors. Avoid contact of cement with skin and eyes.
IMPORTANT
EL195UHNE exhaust and intake connections are made of PVC. Use PVC primer and solvent cement when using PVC vent pipe. When using ABS vent pipe, use transitional solvent cement to make connections to the
PVC ttings in the unit.
TABLE 2
PIPING AND FITTINGS SPECIFICATIONS
Schedule 40 PVC (Pipe) D1785
Schedule 40 PVC (Cellular Core Pipe) F891
Schedule 40 PVC (Fittings) D2466
Schedule 40 CPVC (Pipe) F441
Schedule 40 CPVC (Fittings) F438
SDR-21 PVC or SDR-26 PVC (Pipe) D2241
SDR-21 CPVC or SDR-26 CPVC (Pipe) F442
Schedule 40 ABS Cellular Core DWV (Pipe) F628
Schedule 40 ABS (Pipe) D1527
Schedule 40 ABS (Fittings) D2468
ABS-DWV (Drain Waste & Vent) (Pipe & Fittings)
PVC-DWV (Drain Waste & Vent) Pipe & Fittings)
PRIMER & SOLVENT CEMENT
PVC & CPVC Primer F656
PVC Solvent Cement D2564
CPVC Solvent Cement F493
ABS Solvent Cement D2235
PVC/CPVC/ABS All Purpose Cement For Fittings & Pipe of the same material
ABS to PVC or CPVC Transition Solvent Cement
PVC & ABS & NORYL Transition Solvent Cement WELD-ON 4052
CANADA PIPE & FITTING & SOLVENT
CEMENT
PVC & CPVC Pipe and Fittings
PVC & CPVC Solvent Cement
ABS to PVC or CPVC Transition Cement
POLYPROPYLENE VENTING SYSTEM
PolyPro® by Duravent
InnoFlue® by Centrotherm
D2661
D2665
ASTM
SPECIFICATION
D2564, D2235, F493
D3188
MARKING
ULCS636
Page 14
Use PVC primer and solvent cement or ABS solvent ce-
ment meeting ASTM specications, refer to Table 2. As an
alternate, use all purpose cement, to bond ABS, PVC, or
CPVC pipe when using ttings and pipe made of the same
materials. Use transition solvent cement when bonding ABS to either PVC or CPVC.
Low temperature solvent cement is recommended during cooler weather. Metal or plastic strapping may be used for vent pipe hangers. Uniformly apply a liberal coat of PVC primer for PVC or use a clean dry cloth for ABS to clean
inside socket surface of tting and male end of pipe to
Canadian Applications Only - Pipe, ttings, primer and sol-
vent cement used to vent (exhaust) this appliance must be certied to ULC S636 and supplied by a single manu­facturer as part of an approved vent (exhaust) system. In
addition, the rst three feet of vent pipe from the furnace ue collar must be accessible for inspection.
NOTE - The intake coupling on the furnace is ABS mate­rial. Use transitional solvent to make connections to PVC pipe.
NOTE - Vent pipe must be installed with provided vent adapter. See gure 23.
depth of tting socket.
TABLE 3
OUTDOOR TERMINATION USAGE*
STANDARD CONCENTRIC
Flush
Mount Kit
51W11
Input Size
Vent Pipe
Dia. in.
(US)
51W12
(CA)
040
060
080
100
NOTE - Standard Terminations do not include any vent pipe or elbows external to the structure. Any vent pipe or elbows external to the structure must be included in total vent length calculations. See vent length tables.
* Kits must be properly installed according to kit instructions.
1Requires eld-provided outdoor 1-1/2” exhaust accelerator.
2Concentric kits 71M80 and 44W92 include 1-1/2” outdoor accelerator, when uses with 040 and 060 input models. 3 Flush mount kits 51W11 and 51W12 includes 1-1/2 in. outdoor exhaust accelerator, required when used with 040, 060 and 080 input models.
4 Termination kits 30G28, 44W92, 4493 and 81J20 are certied to ULC S636 for use in Canada only.
5 See table 8 for vent accelerator requirements.
2
3
2
3
2
3
2 YES YES YES
3 YES YES
3
YES YES
3
YES YES
3
YES YES
3
YES YES
3
YES YES YES
3
YES YES YES
Wall Kit
2 inch 3 inch 2 inch
22G44
(US)
4
30G28
(CA)
44J40
(US)
4
81J20
(CA)
1
YES
1
YES
1
YES
1
YES
Wall Ring
Kit
15F74
1
YES
1
YES
1
YES
1
YES
1-1.2 inch 2 inch 3 inch
Field
Fabricated
5
YES
5
YES
5
YES
5
YES
5
YES YES YES
5
YES YES YES
5
YES YES YES
5
YES YES YES
71M80
(US)
4
44W92
(CA)
2
YES
2
YES
2
YES
2
YES
69M29
(US)
4
44W92
(CA)
60L46 (US)
4
44W93 (CA)
Page 15
Loading...
+ 35 hidden pages