Lennox EL195UH040NE36B, EL195UH060NE36B, EL195UH080NE48C, EL195UH100NE60C Installation Instructions And Use

Page 1
© 2018 Lennox Industries Inc.
Dallas, Texas USA
INSTALLATION INSTRUCTIONS EL195UHNE
ELITE® SERIES GAS FURNACE UPFLOW / HORIZONTAL AIR DISCHARGE
507758-02 02/2018 Supersedes 507758-01
THIS MANUAL MUST BE LEFT WITH THE
This is a safety alert symbol and should never be ignored. When you see this symbol on labels or in man­uals, be alert to the potential for personal injury or death.
CAUTION
As with any mechanical equipment, contact with sharp sheet metal edges can result in personal injury. Take care while handling this equipment and wear gloves and protective clothing.
Contents
Unit Dimensions - inches (mm) ......................................2
EL195UHNE Gas Furnace .............................................3
Shipping and Packing List ..............................................3
Safety Information ..........................................................3
Use of Furnace as Construction Heater .........................4
General ........................................................................... 5
Combustion, Dilution & Ventilation Air ............................5
Shipping Bolt Removal ...................................................8
Installation - Setting Equipment ...................................... 8
Filters ............................................................................ 13
Duct System .................................................................13
Pipe Fittings Specications...........................................13
Joint Cementing Procedure .......................................... 16
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a licensed professional HVAC installer or equivalent, service agency, or the gas supplier.
Venting Practices ..........................................................16
Vent Piping Guidelines .................................................17
Gas Piping .................................................................... 36
Electrical ....................................................................... 38
Ignition Control .............................................................41
Unit Start-Up ................................................................. 41
Gas Pressure Adjustment ............................................. 44
Proper Combustion.......................................................44
High Altitude Information .............................................. 44
Testing for Venting and Combustion Air........................45
Service..........................................................................46
Repair Parts List ........................................................... 48
Start-Up & Performance Check List .............................49
Page 1
Page 2
EL195UHNE Unit Dimensions - inches (mm)
(19)
EXHAUST AIR
FRONT VIEW SIDE VIEW
1-1/2
1
NOTE - 60C size units that require air volumes over 1800 cfm must have one of the following:
1. Single side return air and Optional Return Air Base with transition that must accommodate required 20 x 25 x 1 inch (508 x 635 x 25 mm) air filter to maintain proper velocity.
2. Bottom return air.
3. Return air from both sides.
4. Bottom and one side return air. See Blower Performance Tables for additional information.
2
Optional Side Return Air Filter Kit is not for use with the Optional Return Air Base.
A
B
9/16 (14)
2
OPTIONAL
SIDE RETURN
AIR FILTER KIT
(Either Side)
14-3/4
(375)
16
(406)
33
(838)
1-7/8 (48)
COMBUSTION
AIR INTAKE
2
OPTIONAL
SIDE RETURN
AIR FILTER KIT
(Either Side)
1-1/2 (38)
Front Panel
6-5/8 (168)
12-5/8
(321)
Not Used
ELECTRICAL
INLET
(Either Side)
2-7/8
(73)
3-1/4
(83)
2-1/4
(57)
OUTLET
SUPPLY AIR
OPENING
23-3/4
(603)
25
(635)
TOP VIEW
27-3/4
(705)
19-7/16
(494)
INTAKE AIR
GAS PIPING INLET (Right Side Only)
CONDENSATE TRAP CONNECTION (Either Side)
6-1/2 (165) (Either Side)
23
(584)
1
Side Return Air Opening (Either Side)
9/16
(14)
(38)
14
(356)
AIR FLOW
3/4
C
1
Bottom Return
Air Opening
3/4
(19)
Model
EL195UH040NE36B EL195UH060NE36B
17-1/2 (446) 16-3/8 (416) 16 (406)
EL195UH080NE48C EL195UH100NE60C
in (mm)
21 (553) 19-7/8 (505) 19-1/2 (495)
A
5/8
(16)
Page 2
3-1/4
(83)
in (mm)
B
23-1/2
(597)
1
Bottom Return
Air Opening
1-15/16 (49)
C
in (mm)
Page 3
EL195UHNE Gas Furnace
The EL195UHNE Category IV gas furnace is shipped ready for
installation in the upow or horizontal position. The furnace is
shipped with the bottom panel in place. The bottom panel must
be removed if the unit is to be installed in horizontal or upow
applications with bottom return air.
The EL195UHNE can be installed as either a Direct Vent or a Non-Direct Vent gas central furnace. The fur-
nace is equipped for installation in natural gas applications.
NOTE - In Direct Vent installations, combustion air is tak-
en from outdoors and ue gases are discharged outdoors.
In Non-Direct Vent installations, combustion air is taken
from indoors or ventilated attic or crawlspace and ue gases are discharged outdoors. See gures 1 and 2 for applications involving roof termination.
DIRECT VENT INSTALLATION NON-DIRECT VENT
EXHAUST OUTLET
COMBUSTION
AIR INTAKE OUTSIDE
OF HOUSE
INSTALLATION
EXHAUST
OUTLET
Shipping and Packing List
Package 1 of 1 contains
1 - Assembled EL195UHNE unit 1 - Bag assembly containing the following:
1 - Snap bushing 1 - 1/2” diameter threaded street elbow 1 - Snap plug 1 - Wire tie 1 - Condensate trap 1 - Condensate trap cap 1 - Condensate trap clamp 1 - 2” diameter debris screen 1 - 3/4” Threaded street elbow
Check equipment for shipping damage. If you nd any
damage, immediately contact the last carrier. The following items may also be ordered separately: 1 - Thermostat 1 - Return air base kit
1 - Horizontal suspension kit
Safety Information
Figure 1
NON-DIRECT VENT
INSTALLATION
EXHAUST OUTLET
COMBUSTION
AIR INTAKE INSIDE
VENTILATED
ATTIC SPACE
Figure 2
COMBUSTION
AIR INTAKE
INSIDE
OF HOUSE
NON-DIRECT VENT
INSTALLATION
EXHAUST OUTLET
COMBUSTION
AIR INTAKE INSIDE
VENTILATED
CRAWL SPACE
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a licensed professional HVAC installer or equivalent, service agency, or the gas supplier.
CAUTION
As with any mechanical equipment, contact with sharp sheet metal edges can result in personal injury. Take care while handling this equipment and wear gloves and protective clothing.
Use only the type of gas approved for use with this fur­nace. Refer to unit nameplate.
EL195UHNE units are CSA International certied to ANSI
Z21.47 and CSA 2.3 standards. Building Codes In the USA, installation of gas furnaces must conform with
local building codes. In the absence of local codes, units must be installed according to the current National Fuel Gas Code (ANSI-Z223.1/NFPA 54). The National Fuel Gas Code is available from the following address:
American National Standards Institute, Inc. 11 West 42nd Street New York, NY 10036
In Canada, installation must conform with current National Standard of Canada CSA-B149 Natural Gas and Propane Installation Codes, local plumbing or waste water codes and other applicable local codes.
Page 3
Page 4
In order to ensure proper unit operation in non-direct vent
Heating Unit Installed Parallel to Air Handler Unit
Cooling Coil
applications, combustion and ventilation air supply must be provided according to the current National Fuel Gas Code or CSA-B149 standard.
Installation Locations
This furnace is CSA International certied for installation
clearances to combustible material as listed on the unit
nameplate and in the table in gure 12. Accessibility and service clearances must take precedence over re protec-
tion clearances.
NOTE - For installation on combustible oors, the furnace shall not be installed directly on carpeting, tile, or other combustible material other than wood ooring.
For installation in a residential garage, the furnace must be installed so that the burner(s) and the ignition source are located no less than 18 inches (457 mm) above the
oor. The furnace must be located or protected to avoid
physical damage by vehicles. When a furnace is installed in a public garage, hangar, or other building that has a hazardous atmosphere, the furnace must be installed ac­cording to recommended good practice requirements and current National Fuel Gas Code or CSA B149 standards.
NOTE - Furnace must be adjusted to obtain a temperature
rise within the range specied on the unit nameplate. Fail­ure to do so may cause erratic limit operation and prema­ture heat exchanger failure.
This EL195UHNE furnace must be installed so that its electrical components are protected from water.
Installed in Combination with a Cooling Coil
When this furnace is used with cooling coils (gure 3), it
shall be installed in parallel with, or on the upstream side of, cooling coils to avoid condensation in the heating com-
partment. With a parallel ow arrangement, a damper (or other means to control the ow of air) must adequately
prevent chilled air from entering the furnace. If the damp­er is manually operated, it must be equipped to prevent operation of either the heating or the cooling unit, unless it is in the full HEAT or COOL setting.
When installed, this furnace must be electrically grounded according to local codes. In addition, in the United States, installation must conform with the current National Elec­tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available from the following ad­dress:
National Fire Protection Association 1 Battery March Park Quincy, MA 02269
In Canada, all electrical wiring and grounding for the unit must be installed according to the current regulations of the Canadian Electrical Code Part I (CSA Standard C22.1)
and/or local codes.
Dampers
(open during heating operation only)
Gas Unit
AIR FLOWAIR FLOW
Air Handler Unit
Dampers
(open during cooling operation only)
Heating Unit Installed Upstream of Cooling Coil
AIR FLOW AIR FLOW
Gas Unit
Figure 3
NOTE - This furnace is designed for a minimum contin­uous return air temperature of 60°F (16°C) or an inter­mittent operation down to 55°F (13°C) dry bulb for cases where a night setback thermostat is used. Return air tem­perature must not exceed 85°F (29°C) dry bulb.
The EL195UHNE furnace may be installed in alcoves, closets, attics, basements, garages, crawl spaces and
utility rooms in the upow or horizontal position. This fur­nace design has not been CSA certied for installation in
mobile homes, recreational vehicles, or outdoors.
Use of Furnace as Construction Heater
Lennox does not recommend the use of EL195UHNE units as a construction heater during any phase of con­struction. Very low return air temperatures, harmful vapors
and operation of the unit with clogged or misplaced lters
will damage the unit. Units may be used for heating of buildings or structures
under construction, if the following conditions are met::
The vent system must be permanently installed per
these installation instructions.
A room thermostat must control the furnace. The
use of xed jumpers that will provide continuous heating is not allowed.
The return air duct must be provided and sealed to
the furnace.
Return air temperature range between 60°F (16°C)
and 80°F (27°C) must be maintained.
Air lters must be installed in the system and must
be maintained during construction.
Page 4
Page 5
Air lters must be replaced upon construction com-
pletion.
The input rate and temperature rise must be set per
the furnace rating plate.
One hundred percent (100%) outdoor air must be
provided for combustion air requirements during construction. Temporary ducting may supply out­door air to the furnace. Do not connect duct directly to the furnace. Size the temporary duct following these instructions in section for Combustion, Dilu­tion and Ventilation Air in a conned space with air from outside.
The furnace heat exchanger, components, duct
system, air lters and evaporator coils must be thoroughly cleaned following nal construction clean-up.
All furnace operating conditions (including ignition,
input rate, temperature rise and venting) must be veried according to these installation instructions.
General
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities having jurisdiction before installation.
In addition to the requirements outlined previously, the following general recommendations must be considered when installing a EL195UHNE furnace:
• Place the furnace as close to the center of the air distribution system as possible. The furnace should also be located close to the vent termination point.
• When the furnace is installed in non-direct vent ap­plications, do not install the furnace where drafts might blow directly into it. This could cause improp­er combustion and unsafe operation.
• When the furnace is installed in non-direct vent ap­plications, do not block the furnace combustion air opening with clothing, boxes, doors, etc. Air is need­ed for proper combustion and safe unit operation.
• When the furnace is installed in an attic or other insulated space, keep insulation away from the fur­nace.
• When the furnace is installed in an unconditioned space, consider provisions required to prevent
freezing of condensate drain system.
• Please consult the manufacturer of your evaporator coil for their recommendations on distance required between the heat exchanger and their drain pan. Adequate space must be provided between the drain pan and the furnace heat exchanger.
CAUTION
EL195UHNE unit should not be installed in areas
normally subject to freezing temperatures.
WARNING
Insufcient combustion air can cause headaches, nausea, dizziness or asphyxiation. It will also cause
excess water in the heat exchanger resulting in rusting and premature heat exchanger failure. Excessive exposure to contaminated combustion air will result in safety and performance related problems. Avoid exposure to the following substances in the combustion air supply:
Permanent wave solutions Chlorinated waxes and cleaners Chlorine base swimming pool chemicals Water softening chemicals De-icing salts or chemicals Carbon tetrachloride Halogen type refrigerants Cleaning solvents (such as perchloroethylene) Printing inks, paint removers, varnishes, etc. Hydrochloric acid Cements and glues Antistatic fabric softeners for clothes dryers Masonry acid washing materials
Combustion, Dilution & Ventilation Air
If the EL195UHNE is installed as a Non-Direct Vent Furnace, follow the guidelines in this section.
NOTE - In Non-Direct Vent installations, combustion air is taken from indoors or ventilated attic or crawlspace and
ue gases are discharged out-doors.
In the past, there was no problem in bringing in sufcient outdoor air for combustion. Inltration provided all the air
that was needed. In today’s homes, tight construction practices make it necessary to bring in air from outside for combustion. Take into account that exhaust fans, appli-
ance vents, chimneys, and replaces force additional air
that could be used for combustion out of the house. Unless outside air is brought into the house for combus-
tion, negative pressure (outside pressure is greater than inside pressure) will build to the point that a downdraft can occur in the furnace vent pipe or chimney. As a result, combustion gases enter the living space creating a poten­tially dangerous situation.
In the absence of local codes concerning air for combus­tion and ventilation, use the guidelines and procedures in this section to install EL195UHNE furnaces to ensure efcient and safe operation. You must consider combus­tion air needs and requirements for exhaust vents and gas piping. A portion of this information has been reprinted with permission from the National Fuel Gas Code (ANSI­Z223.1/NFPA 54). This reprinted material is not the com-
plete and ofcial position of the ANSI on the referenced
subject, which is represented only by the standard in its entirety.
Page 5
Page 6
In Canada, refer to the CSA B149 installation codes.
EQUIPMENT IN CONFINED SPACE - ALL AIR FROM INSIDE
(64516mm.
CAUTION
Do not install the furnace in a corrosive or contaminated atmosphere. Meet all combustion and ventilation air requirements, as well as all local codes.
All gas-red appliances require air for the combustion process. If sufcient combustion air is not available, the furnace or other appliance will operate inefciently and
unsafely. Enough air must be provided to meet the needs of all fuel-burning appliances and appliances such as ex­haust fans which force air out of the house. When replac­es, exhaust fans, or clothes dryers are used at the same time as the furnace, much more air is required to ensure proper combustion and to prevent a downdraft. Insuf­cient air causes incomplete combustion which can result in carbon monoxide.
In addition to providing combustion air, fresh outdoor air dilutes contaminants in the indoor air. These contaminants may include bleaches, adhesives, detergents, solvents and other contaminants which can corrode furnace com­ponents.
The requirements for providing air for combustion and ventilation depend largely on whether the furnace is in-
stalled in an unconned or a conned space.
Unconned Space
An unconned space is an area such as a basement or
large equipment room with a volume greater than 50 cubic feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of the com­bined input rating of all appliances installed in that space. This space also includes adjacent rooms which are not separated by a door. Though an area may appear to be
unconned, it might be necessary to bring in outdoor air
for combustion if the structure does not provide enough air
by inltration. If the furnace is located in a building of tight
construction with weather stripping and caulking around the windows and doors, follow the procedures in the Air from Outside section.
Conned Space
A conned space is an area with a volume less than 50
cubic feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of the combined input rating of all appliances installed in that
space. This denition includes furnace closets or small
equipment rooms. When the furnace is installed so that supply ducts carry
air circulated by the furnace to areas outside the space containing the furnace, the return air must be handled by ducts which are sealed to the furnace casing and which terminate outside the space containing the furnace. This is especially important when the furnace is mounted on
a platform in a conned space such as a closet or small
equipment room.
Even a small leak around the base of the unit at the plat­form or at the return air duct connection can cause a po­tentially dangerous negative pressure condition. Air for combustion and ventilation can be brought into the con-
ned space either from inside the building or from outside
.Air from Inside
If the conned space that houses the furnace adjoins a space categorized as unconned, air can be brought in by
providing two permanent openings between the two spac­es. Each opening must have a minimum free area of 1 square inch (645 mm2) per 1,000 Btu (.29 kW) per hour of
total input rating of all gas-red equipment in the conned
space. Each opening must be at least 100 square inches (64516 mm2). One opening shall be within 12 inches (305 mm) of the top of the enclosure and one opening within 12
inches (305 mm) of the bottom. See gure 4.
ROOF TERMINATED
EXHAUST PIPE
OPENINGS
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
NOTE - Each opening shall have a free area of at least one square inch per 1,000 Btu (645mm all equipment in the enclosure, but not less than 100 square inches
2).
EL296UH
V
2
per .29kW) per hour of the total input rating of
(To Adjacent
Unconfined
Space)
Figure 4
Air from Outside
If air from outside is brought in for combustion and ventila­tion, the conned space shall be provided with two perma­nent openings. One opening shall be within 12” (305mm) of the top of the enclosure and one within 12” (305mm) of the bottom. These openings must communicate directly or by ducts with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors or indirectly through vertical ducts. Each opening shall have a minimum free area of 1 square inch per 4,000 Btu (645mm2 per 1.17kW) per hour of total input rating of all equipment in the en­closure. When communicating with the outdoors through
horizontal ducts, each opening shall have a minimum free
area of 1 square inch per 2,000 Btu (645mm2 per .59kW) per total input rating of all equipment in the enclosure (See
gure 5).It is also permissible to bring in air for combustion from a ventilated attic (gure 6) or ventilated crawl space (gure 7).
Page 6
Page 7
EQUIPMENT IN CONFINED SPACE - ALL AIR FROM OUTSIDE
(Inlet Air from Crawl Space and Outlet Air to Outside)
hour of the total input rating of all equipment in the enclosure.
hour of the total input rating of all equipment in the enclosure.
EQUIPMENT IN CONFINED SPACE
VENTILATION LOUVERS
OUTLET
AIR
(Each end of attic)
ROOF TERMINATED
EXHAUST PIPE
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
FURNACE
INLET
AIR
VENTILATION
LOUVERS
(For unheated
crawl space)
(Inlet Air from Ventilated Crawlspace and Outlet Air to Outside)
Roof Terminated
Exhaust Pipe
Inlet Air
(Minimum
Ventilation
Louvers
(Crawl space)
Furnace
12 in.(305mm)
Above crawl
space floor)
NOTE-The inlet and outlet air openings shall each have a free area of at least one square inch per 4,000 Btu (645mm
2
per 1.17kW) per
Figure 5
(Inlet Air from Ventilated Attic and Outlet Air to Outside)
Roof Terminated
Exhaust Pipe
NOTE-The inlet and outlet air openings shall each have a free area of at least one square inch per 4,000 Btu (645mm hour of the total input rating of all equipment in the enclosure.
EQUIPMENT IN CONFINED SPACE
Ventilation Louvers
12 in.(305mm) Above
*Intake Debris
Screen
(Provided)
Furnace
2
per 1.17kW) per
Figure 6
(Minimum
attic floor)
Inlet Air
Coupling or 3 in. to 2 in.
Transition
(Field Provided)
NOTE-The inlet and outlet air openings shall each have a free area of at least one square inch per 4,000 Btu (645mm
*Intake Debris Screen Provided)
2
per 1.17kW) per
Figure 7
If air from outside is brought in for combustion and ventila­tion, the conned space must have two permanent open­ings. One opening shall be within 12 inches (305 mm) of the top of the enclosure and one opening within 12 inches (305 mm) of the bottom. These openings must communi­cate directly or by ducts with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors or in­directly through vertical ducts. Each opening shall have a minimum free area of 1 square inch (645 mm2) per 4,000 Btu (1.17 kW) per hour of total input rating of all equipment
in the enclosure. See gures 5 and 8. When communi­cating with the outdoors through horizontal ducts, each
opening shall have a minimum free area of 1 square inch (645 mm2) per 2,000 Btu (.56 kW) per total input rating of
all equipment in the enclosure. See gure 9.
When ducts are used, they shall be of the same cross-sec­tional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be no less than 3 inches (75 mm). In calculating free area, the blocking effect of louvers, grilles, or screens must be considered. If the design and free area of protec-
tive covering is not known for calculating the size opening
required, it may be assumed that wood louvers will have 20 to 25 percent free area and metal louvers and grilles will have 60 to 75 percent free area. Louvers and grilles
must be xed in the open position or interlocked with the
equipment so that they.
Page 7
Page 8
EQUIPMENT IN CONFINED SPACE - ALL AIR FROM OUTSIDE
ROOF TERMINATED
EQUIPMENT IN CONFINED SPACE -
hour of the total input rating of all other equipment in the enclosure.
EXHAUST PIPE
(All Air Through Ventilated Attic)
VENTILATION LOUVERS
(Each end of attic)
OUTLET
AIR
exible mounting leg). See gure 10. The bolt and washer
must be removed before the furnace is placed into oper­ation. After the bolt and washer have been removed, the rigid leg will not touch the blower housing.
Units with 1/2 or 3/4 HP Blower Motor
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
NOTE-The inlet and outlet air openings shall each have a free area of at least one square inch per 4,000 Btu (645mm of the total input rating of all equipment in the enclosure.
FURNACE
INLET AIR
(Ends 12” above
2
per 1.17kW) per hour
Figure 8
ALL AIR FROM OUTSIDE
ROOF TERMINATED
EXHAUST PIPE
OUTLET AIR
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
NOTE-Each air duct opening shall have a free area of at least one square inch per 2,000 Btu (645mm input rating of all equipment in the enclosure. If the equipment room
cate directly with the outdoors, each opening shall have a free area of at least 1 square inch per 4,000 Btu (645mm
FURNACE
INLET AIR
2
per .59kW) per hour of the total
2
per 1.17kW) per
Figure 9
Shipping Bolt Removal
Units with 1/2 and 3/4 hp blower motor are equipped
with three exible legs and one rigid leg. The rigid leg is equipped with a shipping bolt and a at white plastic wash-
er (rather than the rubber mounting grommet used with a
remove shipping bolt and washe
RIGID LEG
bottom)
Figure 10
Installation - Setting Equipment
WARNING
Do not connect the return air duct to the back of the furnace. Doing so will adversely affect the operation of the safety control devices, which could result in personal injury or death.
WARNING
Blower access panel must be securely in place when blower and burners are operating. Gas fumes, which could contain carbon monoxide, can be drawn into living space resulting in personal injury or death.
Upow Applications
The EL195UHNE gas furnace can be installed as shipped
in the upow position. Refer to gure 12 for clearances.
Select a location that allows for the required clearances that are listed on the unit nameplate. Also consider gas supply connections, electrical supply, vent connection, condensate trap and drain connections, and installation and service clearances [24 inches (610 mm) at unit front]. The unit must be level from side to side. The unit may be
positioned from level to ½” toward the front. See gure 11.
Allow for clearances to combustible materials as indicated on the unit nameplate.
Page 8
Page 9
SETTING EQUIPMENT
END VIEW
Unit must be level side-to-side. Unit may be positioned from level to 1/2” toward the front to aid in draining.
UPFLOW APPLICATION
UNIT
FRONT
1/2” max.
SIDE VIEW
AIR FLOW
FRONT VIEW
UNIT
FRONT
SIDE VIEW
HORIZONTAL APPLICATION
AIR FLOW
FRONT VIEW
Figure 11
UNIT
FRONT
1/2”
max.
Page 9
Page 10
WARNING
Installation Clearances
Top
Bottom (Floor)
Left Side
Right Side
Top/Plenum 1 in. (25 mm)
*Front 1
Back 1
Sides 1
Vent 1
Floor 0
*Front clearance in alcove installation must be 24 in. (610 mm). Maintain a minimum of 24 in. (610 mm) for front service access.
Allow proper clearances to accommodate condensate trap.For installations on a combustible floor, do not install the furnace
directly on carpeting, tile or other combustible materials other than wood flooring.
Side Return Air
Transition
Improper installation of the furnace can result in personal
injury or death. Combustion and ue products must
never be allowed to enter the return air system or air in the living space. Use sheet metal screws and joint tape to seal return air system to furnace.
In platform installations with furnace return, the furnace should be sealed airtight to the return air plenum. A door must never be used as a portion of the return air duct system. The base must provide a stable support and an airtight seal to the furnace. Allow absolutely no sagging, cracks, gaps, etc. For no reason should return and supply air duct systems ever be connected to or from
other heating devices such as a replace or stove, etc.
Fire, explosion, carbon monoxide poisoning, personal injury and/or property damage could result.
Return Air Guidelines
Return air can be brought in through the bottom or either
side of the furnace installed in an upow application. If the
furnace is installed on a platform with bottom return, make an airtight seal between the bottom of the furnace and the platform to ensure that the furnace operates properly and safely. The furnace is equipped with a removable bottom panel to facilitate installation.
Markings are provided on both sides of the furnace cabinet for installations that require side return air. Cut the furnace cabinet at the maximum dimensions shown on page 2.
Refer to Engineering Handbook for additional information.
EL195UHNE applications which include side return air and a condensate trap installed on the same side of the cabinet (trap can be installed remotely within 5
ft.) require either a return air base or eld-fabricated
transition to accommodate an optional IAQ accessory
taller than 14.5”. See gure 13.
(with transition and filter)
Figure 12
20” X 25” X 1”
(508mmX635mmX 25mm)
Air Filter
Return
Air
Plenum
Figure 13
Page 10
Page 11
Optional Return Air Base
To minimize pressure drop, the largest opening height possible (up to 14 inches) is preferred.
CONDENSATE
Removing the Bottom Panel
Bottom Panel
TRAP
AIR FLOW
FURNACE
FRONT
INDOOR AIR
QUALITY CABINET
(PCO, Filter
Cabinet, etc.)
(Upflow Applications Only)
IF BASE IS USED
WITHOUT
IAQ CABINET,
A SINGLE
RETURN AIR
PLENUM
MUST
COVER BOTH
UNIT AND
RETURN
AIR BASE
OPENINGS
3−1/4
(83)
7−1/4 (184)
1
23 (584)
Overall
(Maximum)
1
Unit side return air
Opening
5−5/8 (143)
SIDE RETURN
AIR OPENINGS
(Either Side)
1
Minimum
11 (279)
2
Maximum
14 (356)
1
22−7/16
(570)
Overall
(Maximum)
17−1/2 (446) B Width (50W98) 21 (533) C Width (50W99)
24−1/2 (622) D Width (51W00)
OPTIONAL RETURN AIR BASE
23
(584)
26−7/8
(683)
SIDE VIEW
3/4
(19)
FRONT VIEW
NOTE- Optional side return air filter kits are not for use with return air base.
1
Both the unit return air opening and the base return air opening must be covered by a single plenum or IAQ cabinet. Minimum unit side return air opening dimensions for units requiring 1800 cfm or more of air (W x H): 23 x 11 in. (584 x 279 mm). The opening can be cut as needed to accommodate plenum or IAQ cabinet while maintaining dimensions shown. Side return air openings must be cut in the field. There are cutting guides stenciled on the cabinet for the side return air opening. The size of the opening must not extend beyond the markings on the furnace cabinet.
2
Figure 14
Removing the Bottom Panel
Remove the two screws that secure the bottom cap to the furnace. Pivot the bottom cap down to release the bottom panel. Once the bottom panel has been removed, reinstall
the bottom cap. See gure 15.
Horizontal Applications
WARNING
Do not install the furnace on its front or back. See gure
16.
See figure 4.
Screw
Bottom Cap
Figure 15
Page 11
Front Back
Figure 16
Page 12
The EL195UHNE furnace can be installed in horizontal
Horizontal Application
Installation Clearances
dnE thgiRdnE tfeL
Right-Hand Discharge
Left-Hand Discharge
Top
Bottom (Floor)**
Bottom (Floor)**
dnE thgiRdnE tfeL
Air
Flow
Air
Flow
Air
Flow
Air
Flow
Top 1
Front* 1
Back 1
Ends 1
Vent 1
Floor 1
*Front clearance in alcove installation must be 24 in. (610 mm). Maintain a minimum of 24 in. (610 mm) for front service access. **An 8” service clearance must be maintained below the unit to provide for servicing of the condensate trap. For installations on a combustible floor, do not install the furnace directly on carpeting, tile or other combustible materials other than wood flooring.
applications with either right- or left-hand air discharge.
Refer to gure 17 for clearances in horizontal applications
.
Figure 17
Suspended Installation of Horizontal Unit
This furnace may be installed in either an attic or a crawl­space. Either suspend the furnace from roof rafters or
oor joists, as shown in gure 18, or install the furnace on a platform, as shown in gure 19. A horizontal suspension
kit (51W10) may be ordered from Lennox or use equiva­lent.
NOTE - Heavy-gauge sheet metal straps may be used to suspend the unit from roof rafters or ceiling joists. Straps are used to suspend the unit in this way, support must be provided for both the ends. The straps must not interfere with the plenum or exhaust piping installation. Cooling
coils and supply and return air plenums must be sup­ported separately.
Page 12
HORIZONTAL SUSPENSION KIT
Metal Strap
(typical)
Internal Brace
(provided with kit)
Bracket (typical)
Air
Flow
Figure 18
NOTE - When the furnace is installed on a platform or with
the horizontal suspension kit in a crawlspace, it must be elevated enough to avoid water damage, accommodate drain trap and to allow the evaporator coil to drain.
Platform Installation of Horizontal Unit
1 - Select location for unit keeping in mind service and
other necessary clearances. See gure 17.
2 - Construct a raised wooden frame and cover frame
with a plywood sheet. If unit is installed above
nished space, fabricate an auxiliary drain pan to be
installed under unit. Set unit in drain pan as shown
in gure 19. Leave 8 inches for service clearance
below unit for condensate trap.
3 - Provide a service platform in front of unit. When
installing the unit in a crawl space, a proper support platform may be created using cement blocks.
4 - Route auxiliary drain line so that water draining from
this outlet will be easily noticed by the homeowner.
5 - If necessary, run the condensate line into a condensate
pump to meet drain line slope requirements. The pump must be rated for use with condensing furnaces. Protect the condensate discharge line
from the pump to the outside to avoid freezing.
6 - Continue with exhaust, condensate and intake piping
installation according to instructions.
Page 13
INTAKE PIPE
EXHAUST PIPE
*Gas connector may be used for Canadian
able by local authority having jurisdiction.
SERVICE PLATFORM
*GAS CONNECTION
RAISED
PLATFORM
Figure 19
Return Air -- Horizontal Applications
Return air may be brought in only through the end of a
furnace installed in the horizontal position. The furnace is
equipped with a removable bottom panel to facilitate in-
stallation. See gure 15.
Filters
This unit is not equipped with a lter or rack. A eld-pro­vided high velocity rated lter is required for the unit to operate properly. Table 1 lists recommended lter sizes. A lter must be in place whenever the unit is operating.
IMPORTANT
If a high-efciency lter is being installed as part of this system to ensure better indoor air quality, the lter must be properly sized. High-efciency lters have a higher static pressure drop than standard efciency glass/foam lters. If the pressure drop is too great, system capacity
and performance may be reduced The pressure drop may also cause the limit to trip more frequently during
the winter and the indoor coil to freeze in the summer,
resulting in an increase in the number of service calls.
Before using any lter with this system, check the specications provided by the lter manufacturer against
the data given in the appropriate Lennox Product
Specications bulletin. Additional information is provided
in Service and Application Note ACC002 (August 2000).
Duct System
Use industry-approved standards to size and install the
supply and return air duct system. Figure 20 shows the correct supply and return duct installation. Refer to ACCA Manual D. This will result in a quiet and low-static system that has uniform air distribution.
NOTE - This furnace is not certied for operation in heat­ing mode (indoor blower operating at selected heating speed) with an external static pressure which exceeds 0.5 inches w.c. Operation at these conditions may result in improper limit operation.
Supply Air Plenum
If the furnace is installed without a cooling coil, a remov­able access panel should be installed in the supply air duct. The access panel should be large enough to per­mit inspection of the heat exchanger. The furnace access panel must always be in place when the furnace is operat­ing and it must not allow leaks.
Return Air Plenum
NOTE - Return air must not be drawn from a room
where this furnace, or any other gas-fueled appliance (i.e., water heater), or carbon monoxide-producing de­vice (i.e., wood replace) is installed.
When return air is drawn from a room, a negative pressure is created in the room. If a gas appliance is operating in
a room with negative pressure, the ue products can be
pulled back down the vent pipe and into the room. This reverse ow of the ue gas may result in incomplete com­bustion and the formation of carbon monoxide gas. This raw gas or toxic fumes might then be distributed through­out the house by the furnace duct system.
Return air can be brought in through the bottom or either side of the furnace (return air brought into either side of
furnace allowed in upow applications only). If a furnace
with bottom return air is installed on a platform, make an airtight seal between the bottom of the furnace and the platform to ensure that the unit operates properly and safely. Use berglass sealing strips, caulking, or equiva­lent sealing method between the plenum and the furnace
cabinet to ensure a tight seal. If a lter is installed, size the return air duct to t the lter frame.
TABLE 1
Furnace
Cabinet Width
17-1/2” 16 X 25 X 1 (1) 16 X 25 X 1 (1)
21” 16 X 25 X 1 (1) 20 X 25 X 1 (1)
Side Return Bottom Return
Filter Size
Page 13
Page 14
SUPPLY
AIR
Duct System and Proper Installation
SUPPLY
AIR
tinU latnoziroHtinU wolfpU
Figure 20
Pipe & Fittings Specications
All pipe, ttings, primer and solvent cement must conform
with American National Standard Institute and the Ameri­can Society for Testing and Materials (ANSI/ASTM) stan-
dards. The solvent shall be free owing and contain no
lumps, undissolved particles or any foreign matter that adversely affects the joint strength or chemical resistance of the cement. The cement shall show no gelation, strati-
cation, or separation that cannot be removed by stirring. Refer to the table 2 below for approved piping and tting
materials.
CAUTION
Solvent cements for plastic pipe are ammable liquids
and should be kept away from all sources of ignition. Do not use excessive amounts of solvent cement when making joints. Good ventilation should be maintained to
reduce re hazard and to minimize breathing of solvent
vapors. Avoid contact of cement with skin and eyes.
IMPORTANT
EL195UHNE exhaust and intake connections are made of PVC. Use PVC primer and solvent cement when using PVC vent pipe. When using ABS vent pipe, use transitional solvent cement to make connections to the
PVC ttings in the unit.
TABLE 2
PIPING AND FITTINGS SPECIFICATIONS
Schedule 40 PVC (Pipe) D1785
Schedule 40 PVC (Cellular Core Pipe) F891
Schedule 40 PVC (Fittings) D2466
Schedule 40 CPVC (Pipe) F441
Schedule 40 CPVC (Fittings) F438
SDR-21 PVC or SDR-26 PVC (Pipe) D2241
SDR-21 CPVC or SDR-26 CPVC (Pipe) F442
Schedule 40 ABS Cellular Core DWV (Pipe) F628
Schedule 40 ABS (Pipe) D1527
Schedule 40 ABS (Fittings) D2468
ABS-DWV (Drain Waste & Vent) (Pipe & Fittings)
PVC-DWV (Drain Waste & Vent) Pipe & Fittings)
PRIMER & SOLVENT CEMENT
PVC & CPVC Primer F656
PVC Solvent Cement D2564
CPVC Solvent Cement F493
ABS Solvent Cement D2235
PVC/CPVC/ABS All Purpose Cement For Fittings & Pipe of the same material
ABS to PVC or CPVC Transition Solvent Cement
PVC & ABS & NORYL Transition Solvent Cement WELD-ON 4052
CANADA PIPE & FITTING & SOLVENT
CEMENT
PVC & CPVC Pipe and Fittings
PVC & CPVC Solvent Cement
ABS to PVC or CPVC Transition Cement
POLYPROPYLENE VENTING SYSTEM
PolyPro® by Duravent
InnoFlue® by Centrotherm
D2661
D2665
ASTM
SPECIFICATION
D2564, D2235, F493
D3188
MARKING
ULCS636
Page 14
Page 15
Use PVC primer and solvent cement or ABS solvent ce-
ment meeting ASTM specications, refer to Table 2. As an
alternate, use all purpose cement, to bond ABS, PVC, or
CPVC pipe when using ttings and pipe made of the same
materials. Use transition solvent cement when bonding ABS to either PVC or CPVC.
Low temperature solvent cement is recommended during cooler weather. Metal or plastic strapping may be used for vent pipe hangers. Uniformly apply a liberal coat of PVC primer for PVC or use a clean dry cloth for ABS to clean
inside socket surface of tting and male end of pipe to
Canadian Applications Only - Pipe, ttings, primer and sol-
vent cement used to vent (exhaust) this appliance must be certied to ULC S636 and supplied by a single manu­facturer as part of an approved vent (exhaust) system. In
addition, the rst three feet of vent pipe from the furnace ue collar must be accessible for inspection.
NOTE - The intake coupling on the furnace is ABS mate­rial. Use transitional solvent to make connections to PVC pipe.
NOTE - Vent pipe must be installed with provided vent adapter. See gure 23.
depth of tting socket.
TABLE 3
OUTDOOR TERMINATION USAGE*
STANDARD CONCENTRIC
Flush
Mount Kit
51W11
Input Size
Vent Pipe
Dia. in.
(US)
51W12
(CA)
040
060
080
100
NOTE - Standard Terminations do not include any vent pipe or elbows external to the structure. Any vent pipe or elbows external to the structure must be included in total vent length calculations. See vent length tables.
* Kits must be properly installed according to kit instructions.
1Requires eld-provided outdoor 1-1/2” exhaust accelerator.
2Concentric kits 71M80 and 44W92 include 1-1/2” outdoor accelerator, when uses with 040 and 060 input models. 3 Flush mount kits 51W11 and 51W12 includes 1-1/2 in. outdoor exhaust accelerator, required when used with 040, 060 and 080 input models.
4 Termination kits 30G28, 44W92, 4493 and 81J20 are certied to ULC S636 for use in Canada only.
5 See table 8 for vent accelerator requirements.
2
3
2
3
2
3
2 YES YES YES
3 YES YES
3
YES YES
3
YES YES
3
YES YES
3
YES YES
3
YES YES YES
3
YES YES YES
Wall Kit
2 inch 3 inch 2 inch
22G44
(US)
4
30G28
(CA)
44J40
(US)
4
81J20
(CA)
1
YES
1
YES
1
YES
1
YES
Wall Ring
Kit
15F74
1
YES
1
YES
1
YES
1
YES
1-1.2 inch 2 inch 3 inch
Field
Fabricated
5
YES
5
YES
5
YES
5
YES
5
YES YES YES
5
YES YES YES
5
YES YES YES
5
YES YES YES
71M80
(US)
4
44W92
(CA)
2
YES
2
YES
2
YES
2
YES
69M29
(US)
4
44W92
(CA)
60L46 (US)
4
44W93 (CA)
Page 15
Page 16
Joint Cementing Procedure
All cementing of joints should be done according to the
specications outlined in ASTM D 2855.
Venting Practices
Piping Suspension Guidelines
DANGER
DANGER OF EXPLOSION!
Fumes from PVC glue may ignite during system check. Allow fumes to dissipate for at least 5 minutes before placing unit into operation.
1 - Measure and cut vent pipe to desired length. 2 - Debur and chamfer end of pipe, removing any ridges
or rough edges. If end is not chamfered, edge of pipe
may remove cement from tting socket and result in
a leaking joint.
NOTE - Check the inside of vent pipe thoroughly for any obstruction that may alter furnace operation.
3 - Clean and dry surfaces to be joined.
4 - Test t joint and mark depth of tting on outside of
pipe.
5 - Uniformly apply a liberal coat of PVC primer for PVC
or use a clean dry cloth for ABS to clean inside socket
surface of tting and male end of pipe to depth of tting socket.
NOTE - Time is critical at this stage. Do not allow primer to dry before applying cement.
6 - Promptly apply solvent cement to end of pipe and
inside socket surface of tting. Cement should be
applied lightly but uniformly to inside of socket. Take care to keep excess cement out of socket. Apply second coat to end of pipe.
7 - Immediately after applying last coat of cement to
pipe, and while both inside socket surface and end of pipe are wet with cement, forcefully insert end of pipe into socket until it bottoms out. Turn PVC pipe 1/4 turn during assembly (but not after pipe is fully inserted) to distribute cement evenly. DO NOT turn ABS or cellular core pipe.
NOTE - Assembly should be completed within 20 seconds after last application of cement. Hammer blows should not be used when inserting pipe.
8 - After assembly, wipe excess cement from pipe at
end of tting socket. A properly made joint will show
a bead around its entire perimeter. Any gaps may
indicate an improper assembly due to insufcient
solvent.
9 - Handle joints carefully until completely set.
SCHEDULE 40
PVC - 5'
all other pipe* - 3'
* See Piping and Fittings Specifications table
NOTE - Isolate piping at the point where it exits the outside wall or roof in order to prevent transmission of vibration to the structure.
Wall Thickness Guidelines
24” maximum 3/4” minimum
Wall
Figure 21
1 - In areas where piping penetrates joists or interior
walls, hole must be large enough to allow clearance on all sides of pipe through center of hole using a hanger.
2 - When furnace is installed in a residence where unit
is shut down for an extended period of time, such as a vacation home, make provisions for draining condensate collection trap and lines.
edistuoedisni
Page 16
Page 17
appliance.
REPLACING FURNACE THAT WAS PART OF A
CHIMNEY
OR GAS
VENT
(Check sizing
for water
heater only)
FURNACE
(Replaced)
If replacing a furnace which was commonly vented with another gas appliance, the size of the existing vent pipe for that gas appliance must be checked. Without the heat of the original furnace flue products, the existing vent pipe is probably oversized for the single water heater or other appliance. The vent should be checked for proper draw with the remaining
COMMON VENT SYSTEM
WATER
HEATER
OPENINGS
(To Adjacent
Room)
Figure 22
Exhaust Piping (Figures 23, 26 and 27)
The vent adapter must be attached to the exhaust cou­pling on the furnace top panel. Use provided bands. See steps below.
1 - Remove the caution tag from vent adapter. 2 - Fully insert vent adapter with both bands loosely
attached on the furnace exhaust coupling
3 - Insert PVC exhaust pipe through vent adapter. Ensure
vent pipe is fully seated into exhaust coupling.
4 - Tighten both top and bottom bands to 40in-lbs.
NOTE - PVC / ABS / NORYL transition solvent cement WELD-ON 4052 (or equivalent) must be used for con­necting PVC exhaust pipe to NORYL furnace exhaust coupling.
Route piping to outside of structure. Continue with instal­lation following instructions given in piping termination section.
CAUTION
Do not discharge exhaust into an existing stack or stack that also serves another gas appliance. If vertical discharge through an existing unused stack is required, insert PVC pipe inside the stack until the end is even with the top or outlet end of the metal stack.
CAUTION
The exhaust vent pipe operates under positive pressure and must be completely sealed to prevent leakage of combustion products into the living space.
Vent Adaptor To Exhaust Coupling
PVC
Exhaust Pipe
Top Band
(torque to 40in-lbs)
Bottom Band
(torque to 40in-lbs)
Vent
Adaptor
Furnace
Exhaust Coupling
Furnace
Top Panel
Figure 23
Vent Piping Guidelines
NOTE - Lennox has approved the use of DuraVent® and Centrotherm manufactured vent pipe and terminations as an option to PVC. When using the PolyPro® by DuraVent or InnoFlue® by Centrotherm venting system the vent pipe requirements stated in the unit installation instruc­tion – minimum & maximum vent lengths, termination clearances, etc. – apply and must be followed. Follow the instructions provided with PoyPro by DuraVent and Inno­Flue by Centrotherm venting system for assembly or if re­quirements are more restrictive. The PolyPro by Duravent and InnoFlue by Centrotherm venting system must also follow the uninsulated and unconditioned space criteria listed in table 7.
The EL195UHNE can be installed as either a Non-Di­rect Vent or a Direct Vent gas central furnace.
NOTE - In Non-Direct Vent installations, combustion air
is taken from indoors and ue gases are discharged out­doors. In Direct Vent installations, combustion air is taken from outdoors and ue gases are discharged outdoors.
Intake and exhaust pipe sizing -- Size pipe according to
tables 4 and 5. Count all elbows inside and outside the home. Table 4 lists the minimum vent pipe lengths per­mitted. Table 5 lists the maximum pipe lengths permitted. Regardless of the diameter of pipe used, the standard roof and wall terminations described in section Exhaust Piping Terminations should be used. Exhaust vent termi-
nation pipe is sized to optimize the velocity of the exhaust
gas as it exits the termination. Refer to table 8. In some applications which permit the use of several dif-
ferent sizes of vent pipe, a combination vent pipe may be
used. Contact Lennox’ Application Department for assis-
tance in sizing vent pipe in these applications.
Page 17
Page 18
NOTE - The exhaust collar on all models is sized to ac-
Pipe Size Process
commodate 2” Schedule 40 vent pipe. In horizontal ap­plications, any transition to exhaust pipe larger than 2” must be made in vertical runs of the pipe. Therefore a 2” elbow must be added before the pipe is transitioned to any size larger than 2”. This elbow must be added to the elbow count used to determine acceptable vent lengths. Contact the Application Department for more information concerning sizing of vent systems which include multiple pipe sizes.
Horizontal Installation Offset Requirements
Exhaust Pipe
Use the following steps to correctly size vent pipe diam­eter.
What is the
furnace capacity?
1
040, 060, 080, or
100?
Which style termination
2
being used?
Standard or concentric?
See table 3..
Horizontal
Gas Furnace
NOTE -
ward unit. A minimum of 1/4” (6mm) drop for each 12” (305mm) of horizontal run is mandatory for drainage.
NOTE - Exhaust pipe MUST be glued to furnace exhaust fittings.
NOTE - Exhaust piping should be checked carefully to make
sure there are no sags or low spots.
12” ma x
of straight pip
e
12”Min.
Figure 24
TABLE 4
MINIMUM VENT PIPE LENGTHS
ML195UH Model MIN. VENT LENGTH*
040, -060, -080, 100
*Any approved termination may be added to the minimum length listed.
15 ft. or 5 ft. plus 2 elbows
or 10 ft. plus 1 elbow
Which needs
3
most elbows?
Intake or exhaust?
How many elbows? Count all elbows inside
4
and outside house.
Desired pipe size?
5
2” or 3”
What is the altitude of
6
the furnace installation?
Use table 5 or 6 to find max intake or exhaust pipe
7
length. Includes all vent pipe and elbows inside and outside the house.
Figure 25
CAUTION
Do not use screens or perforated metal in exhaust or
intake terminations. Doing so will cause freeze-ups and
may block the terminations.
Page 18
Page 19
TABLE 5
NOTE - Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake and Exhaust must be same pipe size.
NOTE - Additional vent pipe and elbows used to terminate the vent pipe outside the structure must be included in the total vent length calculation.
Standard Termination at Elevation 0 - 4500 ft
2” Pipe 3” Pipe
Number Of 90° Elbows
Model Model
040 060 080 100 040 060 080 100
1 81 66 44 24 138 137 118 118
2 76 61 39 19 133 132 113 113
3 71 56 34 14 128 127 108 108
4 66 51 29
5 61 46 24 118 117 98 98
6 56 41 19 113 112 93 93
7 51 36 14 108 107 88 88
8 46 31
9 41 26 98 97 78 78
10 36 21 93 92 73 73
n/a
n/a
123 122 103 103
103 102 83 83
Concentric Termination at Elevation 0 - 4500 ft
2” Pipe 3” Pipe
Number Of 90° Elbows
Model Model
040 060 080 100 040 060 080 100
1 73 58 42 22 121 121 11 4 114
2 68 53 37 17 116 116 109 109
3 63 48 32 12 111 111 104 104
4 58 43 27
5 53 38 22 101 101 94 94
6 48 33 17 96 96 89 89
7 43 28 12 91 91 84 84
8 38 23
9 33 18 81 81 74 74
10 28 13 76 76 69 69
n/a
n/a
106 106 99 99
86 86 79 79
Page 19
Page 20
TABLE 6
Maximum Allowable Exhaust Vent Lengths With Furnace Installed in a Closet or Basement Using Ventilated
Attic or Crawl Space For Intake Air in Feet
NOTE - Additional vent pipe and elbows used to terminate the vent pipe outside the structure must be included in the total vent length calculation.
Standard Termination at Elevation 0 - 4500 ft
2” Pipe 3” Pipe
Number Of 90° Elbows
Model Model
040 060 080 100 040 060 080 100
1 71 56 34 14 118 117 98 98
2 66 51 29 9 113 112 93 93
3 61 46 24 4 108 107 88 88
4 56 41 19
5 51 36 14 98 97 78 78
6 46 31 9 93 92 73 73
7 41 26 4 88 87 68 68
8 36 21
9 31 16 78 77 58 58
10 26 11 73 72 53 53
n/a
n/a
103 102 83 83
83 82 63 63
Page 20
Page 21
TYPICAL EXHAUST AND INTAKE PIPE CONNECTIONS IN UPFLOW DIRECT OR
NON-DIRECT VENT APPLICATIONS
* When transitioning up in pipe size, use the shortest length of 2” PVC pipe possible.
EXHAUST
2”
Appliance Adaptor
2”
INTAKE
EXHAUSTINTAKE
TRANSITION
3”
*2”
Appliance Adaptor
*2”
TRANSITION
Figure 26
2”
2”
2”
or
2”
DO NOT transition
from smaller to larger
3”
pipe in horizontal runs
of exhaust pipe.
TYPICAL EXHAUST AND INTAKE PIPE CONNECTIONS IN HORIZONTAL DIRECT OR NON-DIRECT VENT
APPLICATIONS
12” max.
EXHAUST
2”
2”
INTAKE
2”
DO NOT transition
from smaller to larger
pipe in horizontal runs
of exhaust pipe.
* When transitioning up in pipe size, use the shortest length of 2” PVC pipe possible.
(RIGHT HAND DISCHARGE SHOWN)
2”
or
2”
2”
2”
Appliance Adaptor
45°
MAX
SIDE VIEW
45°
MAX
EXHAUST
2”
2”
3”
*2”
*2”
Appliance Adaptor
INTAKE
Figure 27
Page 21
Page 22
Intake Piping
TYPICAL AIR INTAKE PIPE CONNECTIONS
The EL195UHNE furnace may be installed in either direct vent or non-direct vent applications. In non-direct vent
applications, when intake air will be drawn into the furnace from the surrounding space, the indoor air quality must be considered and guidelines listed in Combustion, Dilution and Ventilation Air section must be followed.
Follow the next two steps when installing the unit in Direct Vent applications, where combustion air is taken from
outdoors and ue gases are discharged outdoors. The provided air intake screen must not be used in direct vent applications (outdoors).
1 - Use transition solvent cement or a sheet metal screw
to secure the intake pipe to the inlet air connector.
2 - Route piping to outside of structure. Continue with
installation following instructions given in general guidelines for piping terminations and intake and exhaust piping terminations for direct vent sections.
Refer to table 5 for pipe sizes.
Follow the next two steps when installing the unit in Non­Direct Vent applications where combustion air is taken
from indoors and ue gases are discharged outdoors.
1 - Use eld-provided materials and the factory-provided
air intake screen to route the intake piping as shown
in gure 28 or 29. Maintain a minimum clearance
of 3” (76mm) around the air intake opening. The air intake opening (with the protective screen) should always be directed forward or to either side in the
upow position, and either straight out or downward in the horizontal position. The air intake piping must not terminate too close to the ooring or a platform.
Ensure that the intake air inlet will not be obstructed by loose insulation or other items that may clog the debris screen.
2 - If intake air is drawn from a ventilated attic (gure
30) or ventilated crawlspace (gure 31) the exhaust
vent length must not exceed those listed in table 6. If 3” diameter pipe is used, reduce to 2” diameter pipe at the termination point to accommodate the debris screen.
3 - Use a sheet metal screw to secure the intake pipe to
the connector, if desired.
TYPICAL AIR INTAKE PIPE CONNECTIONS
UPFLOW NON−DIRECT
VENT APPLICATIONS
INTAKE
DEBRIS
SCREEN
(Provided)
NOTE - Debris screen and elbow may be rotated, so that screen may be positioned to face forward or to either side.
Figure 28
HORIZONTAL NON−DIRECT VENT APPLICATIONS
(Horizontal Right−Hand Air Discharge Application Shown)
INTAKE
DEBRIS
SCREEN
(Provided)
NOTE - Debris screen may be positioned with elbow rotated to face down or face up.
Figure 29
Page 22
Page 23
CAUTION
hour of the total input rating of all equipment in the enclosure.
EQUIPMENT IN CONFINED SPACE
If this unit is being installed in an application with combustion air coming in from a space serviced by an exhaust fan, power exhaust fan, or other device which may create a negative pressure in the space, take care
when sizing the inlet air opening. The inlet air opening must be sized to accommodate the maximum volume
of exhausted air as well as the maximum volume of combustion air required for all gas appliances serviced by this space.
(Inlet Air from Ventilated Attic and Outlet Air to Outside)
Roof Terminated
Exhaust Pipe
NOTE-The inlet and outlet air openings shall each have a free area of at least one square inch per 4,000 Btu (645mm hour of the total input rating of all equipment in the enclosure.
(Inlet Air from Ventilated Crawlspace and Outlet Air to Outside)
Roof Terminated
Exhaust Pipe
Ventilation
Louvers
(Crawl space)
EQUIPMENT IN CONFINED SPACE
*Intake Debris
Furnace
Figure 30
Furnace
Coupling or 3 in. to 2 in.
Transition
(Field Provided)
*Intake Debris Screen Provided)
Ventilation Louvers
12 in.(305mm) Above
Screen
(Provided)
2
per 1.17kW) per
Inlet Air
(Minimum
12 in.(305mm)
Above crawl
space floor)
Inlet Air
(Minimum
attic floor)
General Guidelines for Vent Terminations
In Non-Direct Vent applications, combustion air is taken
from indoors and the ue gases are discharged to the out­doors. The EL195UHNE is then classied as a non-direct
vent, Category IV gas furnace. In Direct Vent applications, combustion air is taken from
outdoors and the ue gases are discharged to the out­doors. The EL195UHNE is then classied as a direct vent,
Category IV gas furnace. In both Non-Direct Vent and Direct Vent applications, the
vent termination is limited by local building codes. In the absence of local codes, refer to the current National Fuel Gas Code ANSI Z223-1/NFPA 54 in U.S.A., and current CSA-B149 Natural Gas and Propane Installation Codes in Canada for details.
Position termination according to location given in gure
33 or 34. In addition, position termination so it is free from any obstructions and 12” above the average snow accu­mulation.
At vent termination, care must be taken to maintain protec­tive coatings over building materials (prolonged exposure to exhaust condensate can destroy protective coatings). It is recommended that the exhaust outlet not be located within 6 feet (1.8m) of an outdoor AC unit because the condensate can damage the painted coating.
NOTE - See table 7 for maximum allowed exhaust pipelength without insulation in unconditioned space during winter design temperatures below 32°F (0°C). If re­quired exhaust pipe should be insulated with 1/2” (13mm) Armaex or equivalent. In extreme cold climate areas, 3/4” (19mm) Armaex or equivalent may be necessary. Insulation must be protected from deterioration. Armaex with UV protection is permissible. Basements or other en­closed areas that are not exposed to the outdoor ambient temperature and are above 32 degrees F (0°C) are to be considered conditioned spaces.
IMPORTANT
Do not use screens or perforated metal in exhaust
terminations. Doing so will cause freeze-ups and may
block the terminations.
IMPORTANT
For Canadian Installations Only: In accordance to CSA International B149 installation
codes, the minimum allowed distance between the combustion air intake inlet and the exhaust outlet of other appliances shall not be less than 12 inches (305mm).
NOTE-The inlet and outlet air openings shall each have a free area of at least one square inch per 4,000 Btu (645mm
Figure 31
2
per 1.17kW) per
Page 23
Page 24
TABLE 7
Maximum Allowable Exhaust Vent Pipe Length (in ft.) Without Insulation In Unconditioned Space For
Winter Design Temperatures Single - Stage High Efciency Furnace
Winter Design
Temp1 °F (°C)
32 to 21
(0 to -6)
20 to 1
(-7 to -17)
0 to -20
(-18 to -29)
1Refer to 99% Minimum Design Temperature table provided in the current edition of the ASHRAE Fundamentals Handbook.
2 Poly-Propylene vent pipe (PP) by Duravent and Centrotherm.
NOTE - Concentric terminations are the equivalent of 5’ and should be considered when measuring pipe length.
NOTE - Maximum uninsulated vent lengths listed may include the termination(vent pipe exterior to the structure) and cannot exceed 5 linear feet or the maximum allowable intake or exhaust vent length listed in table 5 or 6 which ever is less.
NOTE - - If insulation is required in an unconditioned space, it must be located on the pipe closest to the furnace. See gure32.
Vent
Pipe Diam
2 in 18 16 31 28 50 48 30 30
3 in 9 9 18 18 35 35 47 47
2 in 9 8 18 16 32 29 30 30
3 in N/A 8 8 19 19 26 26
2 in 5 12 10 22 19 30 27
3 in N/A N/A N/A 10 10 16 16
040 060 080 100
PVC
2
PP
PVC
Unit Input Size
2
PP
PVC
2
PP
PVC
2
PP
Conditioned
Space
Conditioned
Space
Figure 32
Pipe Insulation
Unconditioned
Space
Exhaust
Pipe
Intake
Pipe
Page 24
Page 25
VENT TERMINATION CLEARANCES
FOR NON-DIRECT VENT INSTALLATIONS IN THE US AND CANADA
INSIDE CORNER
DETAIL
G
D
A
E
B
L
C
Fixed
F
Closed
Operable
B
Operable
B
B
VENT TERMINAL
AIR SUPPLY INLET
US Installations
A =
Clearance above grade, veranda,
porch, deck or balcony
B =
C =
D =
E =
F =
G =
H =
I =
J =
Clearance to window or
door that may be opened
Clearance to permanently
closed window
Vertical clearance to ventilated soffit
located above the terminal within a
horizontal distance of 2 feet (610 mm)
from the center line of the terminal
Clearance to unventilated soffit
Clearance to outside corner
Clearance to inside corner
tended above meter / regulator assembly
Clearance to service regulator
vent outlet
Clearance to non-mechanical air
12 inches (305mm) or 12 in. (305mm)
above average snow accumulation.
4 feet (1.2 m) below or to side of opening;
1 foot (30cm) above opening
* 12”
* Equal to or greater than soffit depth.
* Equal to or greater than soffit depth.
* No minimum to outside corner * No minimum to outside corner
3 feet (.9m) within a height 15 feet (4.5m)
*
above the meter / regulator assembly
* 3 feet (.9m)
4 feet (1.2 m) below or to side of opening;
1 foot (30 cm) above opening
pliance
K =
L =
Clearance above paved sidewalk or
paved driveway located on public property
M =
Clearance under veranda, porch, deck or balcony
1
In accordance with the current ANSI Z223.1/NFPA 54 Natural Fuel Gas Code
2
In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code † A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.
‡ Permitted only if veranda, porch, deck or balcony is fully open on a minimum of two sides beneath the floor. Lennox recommends avoiding this location if possible.
ply inlet
3 feet (.9m) above if within 10 feet
(3m) horizontally
7 feet (2.1m)†
*12 inches (305mm)‡
H
B
Fixed
Closed
A
J
AREA WHERE TERMINAL IS NOT PERMITTED
1
12 inches (305mm) or 12 in. (305mm)
above average snow accumulation.
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
I
M
Canadian Installations
* 12”
* Equal to or greater than soffit depth.
* Equal to or greater than soffit depth.
**
3 feet (.9m) within a height 15 feet (4.5m)
above the meter / regulator assembly
3 feet (.9m)
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
6 feet (1.8m)
7 feet (2.1m)†
12 inches (305mm)‡
*For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B149.1, clearance will be in accordance with local installation codes and the requirements of the lation instructions.”
K
2
Figure 33
Page 25
Page 26
VENT TERMINATION CLEARANCES
FOR DIRECT VENT INSTALLATIONS IN THE US AND CANADA
INSIDE CORNER
DETAIL
G
D
A
E
B
L
C
Fixed
F
Closed
Operable
B
Operable
B
B
VENT TERMINAL
AIR SUPPLY INLET
US Installations
A =
Clearance above grade, veranda,
porch, deck or balcony
B =
Clearance to window or
door that may be opened
12 inches (305mm) or 12 in. (305mm)
above average snow accumulation.
6 inches (152mm) for appliances <10,000
pliances > 10,000 Btuh (3kw) and <50,000
pliances > 50,000 Btuh (15kw)
C =
D =
E =
F =
G =
H =
I =
J =
K =
L =
M =
1
In accordance with the current ANSI Z223.1/NFPA 54 Natural Fuel Gas Code
2
In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code
† A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.
‡ Permitted only if veranda, porch, deck or balcony is fully open on a minimum of two sides beneath the floor. Lennox recommends avoiding this location if possible.
Clearance to permanently
closed window
Vertical clearance to ventilated soffit
located above the terminal within a
horizontal distance of 2 feet (610mm)
from the center line of the terminal
Clearance to unventilated soffit
Clearance to outside corner
Clearance to inside corner
tended above meter / regulator assembly
Clearance to service regulator
vent outlet
3 feet (.9m) within a height 15 feet (4.5m)
Clearance to non-mechanical air
pliance
pliances > 10,000 Btuh (3kw) and <50,000
ply inlet
Clearance above paved sidewalk or
paved driveway located on public property
Clearance under veranda, porch, deck or balcony
* Equal to or greater than soffit depth
* Equal to or greater than soffit depth* Equal to or greater than soffit depth
* No minimum to outside corner
above the meter / regulator assembly
6 inches (152mm) for appliances <10,000
pliances > 50,000 Btuh (15kw)
3 feet (.9m) above if within 10 feet
* 12”
*
*
3 feet (.9m)
(3m) horizontally
* 7 feet (2.1m)
*12 inches (305mm)‡
H
B
Fixed
Closed
A
J
AREA WHERE TERMINAL IS NOT PERMITTED
1
12 inches (305mm) or 12 in. (305mm)
above average snow accumulation.
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
I
M
Canadian Installations
K
2
* 12”
* Equal to or greater than soffit depth* Equal to or greater than soffit depth
* No minimum to outside corner
*
3 feet (.9m) within a height 15 feet (4.5m)
above the meter / regulator assembly
3 feet (.9m)
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
6 feet (1.8m)
7 feet (2.1m)†
12 inches (305mm)‡
*For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B149.1, clearance will be in accordance with local installation codes and the requirements of the gas supplier and these installation instructions.”
Figure 34
Page 26
Page 27
Details of Intake and Exhaust Piping Terminations for
(15F75 or 44J41)
Direct Vent Installations
Inches(mm)
3”(76mm) MAX.
NOTE - In Direct Vent installations, combustion air is taken
from outdoors and ue gases are discharged to outdoors. NOTE - Flue gas may be slightly acidic and may adverse-
ly affect some building materials. If any vent termination is used and the ue gasses may impinge on the building material, a corrosion-resistant shield (minimum 24 inches square) should be used to protect the wall surface. If the optional tee is used, the protective shield is recommend­ed. The shield should be constructed using wood, plastic, sheet metal or other suitable material. All seams, joints, cracks, etc. in the affected area should be sealed using an appropriate sealant. See gure 43.
Intake and exhaust pipes may be routed either horizon­tally through an outside wall or vertically through the roof. In attic or closet installations, vertical termination through the roof is preferred. Figures 35 through 42 show typical terminations.
1 - Intake and exhaust terminations are not required
to be in the same pressure zone. You may exit the
intake on one side of the structure and the exhaust
on another side (gure 36). You may exit the
exhaust out the roof and the intake out the side of
the structure (gure 37).
2 - Intake and exhaust pipes should be placed as close
together as possible at termination end (refer to illustrations). Maximum separation is 3” (76mm) on roof terminations and 6” (152mm) on side wall terminations.
NOTE - When venting in different pressure zones, the maximum separation requirement of intake and exhaust pipe DOES NOT apply.
3 - On roof terminations, the intake piping should
terminate straight down using two 90° elbows (See
gure 35).
4 - Exhaust piping must terminate straight out or up as
shown. A reducer may be required on the exhaust piping at the point where it exits the structure to improve the velocity of exhaust away from the intake piping. See table 8.
NOTE - Care must be taken to avoid recirculation of exhaust back into intake pipe.
5 - On eld-supplied terminations for side wall exit,
exhaust piping may extend a maximum of 12 inches (305mm) for 2” PVC and 20 inches (508mm) for 3” (76mm) PVC beyond the outside wall. Intake piping
should be as short as possible. See gure 43.
6 - On eld-supplied terminations, a minimum distance
between the end of the exhaust pipe and the end of the intake pipe without a termination elbow is 8” and a minimum distance of 6” with a termination elbow.
See gure 43.
UNCONDITIONED
8” (203mm) MIN
12” (305mm) ABOVE
AVERAGE SNOW ACCUMULATION
3” (76mm) OR
2” (51mm) PVC
PROVIDE SUPPORT
FOR INTAKE AND
EXHAUST LINES
DIRECT VENT ROOF TERMINATION KIT
ATTIC SPACE
Figure 35
Exiting Exhaust and Intake Vent
(different pressure zone)
Exhaust
Pipe
Furnace
Inlet Air
(Minimum 12 in.
305 MM) above
grade or snow
accumulation
Figure 36
Exiting Exhaust and Intake Vent
(different pressure zone)
Roof T
erminated
Exhaust Pipe
Inlet Air
Furnace
(Minimum 12 in. 305 MM) above
grade or snow
accumulation
Figure 37
TABLE 8
EXHAUST PIPE TERMINATION SIZE REDUCTION
EL195UHNE Model Termination Pipe Size
*040, *060 1-1/2” (38mm)
*080
100
*Use the provided 1-1/2” accelerator if matched with the ushmount termination.
2” (51mm)
Page 27
Page 28
7 - If intake and exhaust piping must be run up a side
51W11 (US) or 51W12 (Canada)
41W92 or 41W93 (Canada)
FIELD-PROVIDED
(30G28 or 81J20)
DIRECT VENT APPLICATION
wall to position above snow accumulation or other obstructions, piping must be supported. At least one bracket must be used within 6” from the top of the
elbow and then every 24” (610mm) as shown in gure
43, to prevent any movement in any direction. When exhaust and intake piping must be run up an outside wall, the exhaust piping must be terminated with pipe
sized per table 8.The intake piping may be equipped
with a 90° elbow turndown. Using turndown will add 5 feet (1.5m) to the equivalent length of the pipe.
8 - A multiple furnace installation may use a group of up
to four terminations assembled together horizontally, as shown in gure 41.
2” EXTENSION FOR 2” PVC PIPE1” EXTENSION FOR 3” PVC PIPE
4''
FURNACE EXHAUST
PIPE
QUIRED TO ADAPT
LARGER VENT PIPE
SIZE TO TERMINATION.
EXHAUST
AIR
INTAKE
AIR
OUTSIDE
WALL
CLAMP
(Not Furnished)
INTAKE
AIR
INTAKE
AIR
DIRECT VENT CONCENTRIC WALL TERMINATION
71M80, 69M29 or 60L46 (US)
Figure 40
EXHAUST
AIR
12” (305mm) Min.
above grade or
cumulation.
GRADE
FURNACE
INTAKE
PIPE
FLUSH-MOUNT SIDE WALL TERMINATION KIT
Figure 38
12” (305mm)
Minimum
Above Average
Snow
Accumulation
CLAMP
DIRECT VENT CONCENTRIC ROOFTOP TERMINATION
71M80, 69M29 or 60L46 (US)
44W92 or 44W93 (Canada)
GLUE EXHAUST
END FLUSH INTO
TERMINATION
FLAT SIDE
INTAKE
1-1/2” ACCELERATOR
FLASHING
(Not Furnished)
SHEET METAL STRAP
(Clamp and sheet metal strap must be field−installed to support the weight of the termination kit.)
FIELD-PROVIDED
REDUCER MAY BE REQUIRED
TO ADAPT LARGER VENT
PIPE SIZE TO TERMINATION
EXHAUST
VENT
5”
(127mm)
5-1/2”
(140mm)
12”
(305mm)
INTAKE
AIR
18” MAX.
(457mm)
Front View
EXHAUST VENT
12” (305mm) Min.
above grade or
Inches (mm)
INTAKE
cumulation.
AIR
optional intake elbow
Side View
OPTIONAL VENT TERMINATION FOR MULTIPLE UNIT
INSTALLATION OF DIRECT VENT WALL TERMINATION KIT
Figure 41
USING EXISTING CHIMNEY
8” - 12”
(203mm - 305mm)
Minimum 12” (305MM)
above chimney top
plate or average snow
accumulation
INTAKE PIPE
INSULATION (optional)
SHEET
METAL TOP
PLATE
INSULATE
TO FORM
SEAL
3” - 8”
(76mm-
203mm)
STRAIGHT-CUT OR
ANGLE-CUT IN DIRECTION
OF ROOF SLOPE *
SHOULDER OF FITTINGS
PROVIDE SUPPORT
OF PIPE ON TOP PLATE
3” - 8” (76mm­203mm)
ALTERNATE INTAKE PIPE
EXTERIOR
PORTION OF
CHIMNEY
Figure 39
Page 28
NOTE - Do tical discharge through an existing unused chimney or stack is required, insert piping inside trated. In any exterior portion of chimney, the exhaust vent must be insulated.
Figure 42
Page 29
NOTE − FIELD−PROVIDED
REQUIRED TO ADAPT
LARGER VENT PIPE SIZE
* WALL
SUPPORT
C1
B
2
B
2
FIELD FABRICATED WALL TERMINATION
REDUCER MAY BE
TO TERMINATION
C1
E
D
B
A
STRAIGHT
APPPLICATION
A
EXTENDED
APPLICATION
D
Intake
C2
Elbow
D
B
E
C2
B
A
D
B
A
A− Minimum clearance
above grade or average
snow accumulation
B− Maximum horizontal separation between
intake and exhaust
C1 -Minimum from end of
exhaust to inlet of intake
C2 -Minimum from end of
exhaust to inlet of intake
D− Maximum exhaust
pipe length
E− Maximum wall support
distance from top of each
pipe (intake/exhaust)
See maximum allowable venting tables for venting lengths with this arrangement.
* Use wall support every 24” (610 mm). Use two wall supports if extension is greater than
24” (610 mm) but less than 48” (1219 mm). NOTE − One wall support must be within 6” (152 mm) from top of each pipe (intake and exhaust) to prevent movement in any direction.
ALTERNATE TERMINATIONS (TEE & FORTY−FIVE DEGREE ELBOWS ONLY)
D
B
Exhaust
D
1
C
A
D
E
12”
C
A
1
The exhaust termination tee should be connected to the 2” or 3” PVC flue pipe as shown in the illustration. In horizontal tee applications there must be be a minimum of 3 ft away from covered patios or any living ares and
cannot be within 3 ft of a window. Do not use an accelerator in applications that include an exhaust termination tee. The accelerator is not required.
2
As required. Flue gas may be acidic and may adversely affect some building materials. If a side wall vent termination is used and flue gases will impinge on the building materials, a corrosion−resistant shield (24 inches square) should be used to protect the wall surface. If optional tee is used, the protective shield is recommended. The shield should be constructed using wood, sheet metal or other suitable material. All seams, joints, cracks, etc. in affected area, should be sealed using an appropriate sealant.
3
Exhaust pipe 45° elbow can be rotated to the side away from the combustion air inlet to direct exhaust away from adjacent property. The exhaust must never be directed toward the combustion air inlet.
Intake Elbow
1
C
A
E
B
2
A
3
D
1
12”
C
A− Clearance above
grade or average snow
accumulation
B− Horizontal
separation between
intake and exhaust
C− Minimum from
end of exhaust to
inlet of intake
D− Exhaust pipe length
E− Wall support distance
from top of each pipe
(intake/exhaust)
Front View of
Intake and Exhaust
Intake
Exhaust
2” (51mm)
Vent Pipe
12” (305 mm)
12” (305 mm)
6” (152 mm)
2” (51MM)
Vent Pipe
12” (305 mm) Min.12” (305 mm) Min.
6” (152 mm) Min. 24” (610 mm) Max.
9” (227 mm) Min.
12” (305 mm) Min. 16” (405 mm) Max.
6” (152 mm) Max.
3” (76mm)
Vent Pipe
12” (305 mm)
6” (152 mm)6” (152 mm)
8” (203 mm)8” (203 mm)
6” (152 mm)6” (152 mm)
20” (508 mm)
6” (152 mm)
3” (76MM)
Vent Pipe
6” (152 mm) Min. 24” (610 mm) Max.
9” (227 mm) Min.
12” (305 mm) Min. 20” (508 mm) Max.
6” (152 mm) Max.
Figure 43
Page 29
Page 30
Details of Exhaust Piping Terminations for Non-Direct
(15F75 or 44J41)
trated. In any exterior portion of chimney, the exhaust vent must be insulated.
NON-DIRECT VENT APPLICATION
Vent Applications
Exhaust pipes may be routed either horizontally through
an outside wall or vertically through the roof. In attic or closet installations, vertical termination through the roof is preferred. Figures 44 and 45 show typical terminations.
1 - Exhaust piping must terminate straight out or up as
shown. The termination pipe must be sized as listed in table 8.The specied pipe size ensures proper
velocity required to move the exhaust gases away from the building.
2 - On eld supplied terminations for side wall exit,
exhaust piping may extend a maximum of 12 inches (305mm) for 2” PVC and 20 inches (508mm) for 3” (76mm) PVC beyond the outside wall.
3 - If exhaust piping must be run up a side wall to position
above snow accumulation or other obstructions, piping must be supported every 24 inches (610mm). When exhaust piping must be run up an outside wall,
any reduction in exhaust pipe size must be done after the nal elbow.
4 - Distance between exhaust pipe terminations on
multiple furnaces must meet local codes.
USING EXISTING CHIMNEY
STRAIGHT-CUT OR
ANGLE-CUT IN DIRECTION
OF ROOF SLOPE
Minimum 12” (305MM)
above chimney top
plate or average snow
accumulation
SHEET
METAL TOP
PLATE
INSULATE
TO FORM
SEAL
NOTE - Do tical discharge through an existing unused chimney or stack is required, insert piping inside
SHOULDER OF FITTINGS
PROVIDE SUPPORT
OF PIPE ON TOP PLATE
EXTERIOR
PORTION OF
CHIMNEY
Figure 45
12” (305mm) ABOVE AVE.
SNOW
ACCUMULATION
3” (76mm) OR
2” (51mm) PVC
PROVIDE SUPPORT
FOR EXHAUST LINES
NON-DIRECT VENT ROOF TERMINATION KIT
UNCONDITIONED
ATTIC SPACE
Figure 44
Crawl Space and Extended Horizontal Venting
Lennox provides kit 51W18 (USA) kit 15Z70 (Canada) to
install 2” or 3” PVC exhaust piping through the oor joists and into the crawl space. See gure 46. This kit can also
be used as a supplemental drain for installations with con-
densate run back in the vent pipe (ie. long horizontal runs,
unconditioned spaces, etc.).
Venting In A Crawl Space
Basement Floor
KIT 51W18
(USA)
KIT 15Z70
(CANADA)
Figure 46
Condensate Piping
This unit is designed for either right- or left-side exit of
condensate piping in upow applications. In horizontal
applications, the condensate trap must extend below the unit. An 8” service clearance is required for the conden­sate trap.
Page 30
Page 31
Refer to gures 47 and 49 for condensate trap locations.
CONDENSATE TRAP AND PLUG LOCATIONS
avoid interference.
Field Provided Drain Components
Figure 55 shows trap assembly using 1/2” PVC or 3/4” PVC.
NOTE - If necessary the condensate trap may be installed up to 5’ away from the furnace. Use PVC pipe to connect trap to furnace condensate outlet. Piping from furnace must slope down a minimum of 1/4” per ft. toward trap.
1 - Determine which side condensate piping will exit
the unit, location of trap, eld-provided ttings and
length of PVC pipe required to reach available drain.
2 - Use a large at head screw driver or a 1/2” drive
socket extension and remove plug (gure 47) from
the cold end header box at the appropriate location on the side of the unit. Install provided 3/4 NPT street
elbow tting into cold end header box. Use Teon
tape or appropriate pipe dope.
NOTE - Cold end header box drain plugs are facto­ry installed. Check the unused plug for tightness to prevent leakage.
3 - Install the cap over the clean out opening at the base
of the trap. Secure with clamp. See gure 55.
5 - Figures 50 and 52 show the furnace and evaporator oil
using a separate drain. If necessary the condensate line from the furnace and evaporator coil can drain
together. See gures 51, 53 and 54. Upow furnace (gure 53) - In upow furnace applications the eld
provided vent must be a minimum 1” to a maximum 2” length above the condensate drain outlet connection.
Any length above 2” may result in a ooded heat
exchanger if the combined primary drain line were to become restricted. Horizontal furnace (gure 54)
- In horizontal furnace applications the eld provided
vent must be a minimum 4” to a maximum 5” length above the condensate drain outlet connection.
Any length above 5” may result in a ooded heat
exchanger if the combined primary drain line were to become restricted.
NOTE - In horizontal applications it is recommended to install a secondary drain pan underneath the unit and trap assembly.
NOTE - Appropriately sized tubing and barbed t­ting may be used for condensate drain. Attach to the drain on the trap using a hose clamp. See gure 48.
(Unit shown in upflow position)
Trap
(same on
right side)
1-1/2 in.
Plug
(same on left side)
NOTE - In upflow applications where side return
sate trap, filter rack must be installed beyond condensate trap or trap must be re-located to
Figure 47
4 - Install drain trap using appropriate PVC ttings, glue
all joints. Glue the provided drain trap as shown in
gure 55. Route the condensate line to an open drain.
Condensate line must maintain a 1/4” downward slope from the furnace to the drain.
IMPORTANT
Do not use copper tubing or existing copper condensate lines for drain line.
Elbow
Barbed Fitting
Tubing
Hose Clamp
Figure 48
6 - If unit will be started immediately upon completion of
installation, prime trap per procedure outlined in Unit Start-Up section. Condensate line must slope down­ward away from the trap to drain. If drain level is above condensate trap, condensate pump must be used. Condensate drain line should be routed within the con-
ditioned space to avoid freezing of condensate and
blockage of drain line. If this is not possible, a heat cable kit may be used on the condensate trap and line. Heating cable kit is available from Lennox in various lengths; 6 ft. (1.8m) - kit no. 26K68 and 24 ft. (7.3m) ­kit no. 26K69.
Page 31
Page 32
(Unit shownin upflow position withremote trap)
CONDENSATE TRAP LOCATIONS
minimum 1/4” per ft. toward trap
FieldProvidedVent
Min.1” AboveCondensate
Connection
Drain
Min.
1”
2” Max.
*5’ max.
PVCPipe Only
Trap CanBeInstalleda
Maximum 5’ From Furnac
e
To Drain
Condensate Trap With Optional Overflow Switch
From Evaporator Coil
HorizontalFurnace4 ” Min.to5” Max.above
condensatedrain connection)
FurnaceCondensate
Connection
Drain
Optional
*Piping from furnace must slope down a
Figure 49
Furnace With Evaporator Coil Using A Separate Drain
(Trap at coil is optional)
Field Provided Vent (1” min. 2” max. above condensate connection)
Condensate
Drain
Connection
Figure 51
Evaporator drain
line required
Figure 50
Page 32
Page 33
Furnace with Evaporator Coil Using a Separate Drain
(Unit shown in horizontal left-hand discharge position)
Furnace with Evaporator Coil Using a Common Drain
(1” min.to2” Max.above
condensatedrain connection)
Condensate
Drain
Connection
Evaporator drain
line required
(Trap at coil is optional)
Furnace with Evaporator Coil Using a Common Drain
Drain
(Trap at coil is optional)
Pan
Piping from furnace and evaporator coil must slope down a minimum 1/4” per ft. toward trap
Evaporator
Coil
Field Provided Vent (4” min. to 5” max. above condensate connection)
4”min
5”max
5’ max.
PVC Pipe Only
Condensate
DrainConnection
Figure 52
IMPORTANT
When combining the furnace and evaporator coil drains together, the A/C condensate drain outlet must be vented to relieve pressure in order for the furnace pressure switch to operate properly.
Figure 53
(Unit shown in horizontal left−hand discharge position)
Evaporator
Coil
Drain
Pan
(Trap at coil is optional)
Piping from furnace and evaporator coil must slope
down a minimum 1/4” per ft. toward trap
Condensate Drain
Connection
Figure 54
5’ max.
PVC Pipe Only
Page 33
4”min
5”max
(4” min.to5” Max.above
condensatedrain
connection)
Page 34
Optional Condensate Drain Connection
TRAP / DRAIN ASSEMBLY USING 1/2” PVC OR 3/4” PVC
Adapter 3/4 inch slip X
3/4 inch mpt (not furnished)
90° Street Elbow 3/4 inch PVC (not furnished)
Condensate Drain
Connection In Unit
90° Street Elbow 3/4 inch PVC ( furnished)
To
Trap
Optional DrainPipingFrom Trap
Drain Assembly for 1/2 inch Drain Pipe
1/2 inch PVC Pipe
(Not Furnished)
90° Elbow
1/2 inch PVC
(Not Furnished)
To
Drain
Drain Assembly for 3/4 inch Drain Pipe
1(25 mm) Min. 2 (50 mm) Max. AboveTop Of Condensate Drain Connection In Unit
Elbow 3/4 inch PVC
90°
(Not Furnished)
1/2 inch PVC Pipe
(Not Furnished)
Adapter 3/4 inch slip X
3/4 inch mpt (not furnished)
V
ent
5 Feet
Maximum
3/4 inch PVC Pipe
(Not Furnished)
Coupling 3/4 inch slip X slip
Drain Trap
Assembly
(Furnished)
Condensate Drain Connection In Unit
(Not Furnished)
90° Elbow
3/4 inch PVC
(Not Furnished)
To
Drain
DrainTrapAssembly
(Furnished)
7
(178)
Drain Trap
Clean Out
90° Elbow
3/4 inch PVC
(Not Furnished)
T
o
Coupling 3/4 inch slip X slip
Drain
DrainTrap Assembly with 1/2 inch Piping
1 (25 mm) Min. 2 (50 mm) Max. AboveTop Of Condensate Drain Connection In Unit
(Not Furnished)
Vent
1/2 inch
Condensate Drain Connection In Unit
To
Drain
Figure 55
DrainTr ap Assembly with 3/4 inch Piping
1 (25 mm) Min. 2 (50 mm) Max. AboveTop Of Condensate Drain Connection In Unit
Vent
3/4 inch
Condensate Drain
Connection In Unit
To
Drain
Page 34
Page 35
Gas Piping
Gas supply piping should not allow more than 0.5”W.C. drop in pressure between gas meter and unit. Supply gas pipe must not be smaller than unit gas connection.
6 - In some localities, codes may require installation of a
manual main shut-off valve and union (furnished by installer) external to the unit. Union must be of the ground joint type.
CAUTION
If a exible gas connector is required or allowed by the
authority that has jurisdiction, black iron pipe shall be installed at the gas valve and extend outside the furnace
cabinet. The exible connector can then be added
between the black iron pipe and the gas supply line.
WARNING
Do not over torque (800 in-lbs) or under torque (350 in­lbs) when attaching the gas piping to the gas valve.
1 - Gas piping may be routed into the unit through the
right-hand side only. Supply piping enters into the gas valve from the side of the valve as shown in
gure 57. Connect the gas supply piping into the
gas valve. The maximum torque is 800 in lbs and minimum torque is 350 in lbs when attaching the gas piping to the gas valve.
2 - When connecting gas supply, factors such as length
of run, number of ttings and furnace rating must
be considered to avoid excessive pressure drop.
Table 9 lists recommended pipe sizes for typical
applications.
NOTE - Use two wrenches when connecting gas piping to avoid transferring torque to the manifold.
3 - Gas piping must not run in or through air ducts,
clothes chutes, chimneys or gas vents, dumb waiters or elevator shafts. Center gas line through piping hole. Gas line should not touch side of unit. See
gures 57 and 58.
4 - Piping should be sloped 1/4 inch per 15 feet (6mm
per 5.6m) upward toward the gas meter from the furnace. The piping must be supported at proper intervals, every 8 to 10 feet (2.44 to 3.05m), using suitable hangers or straps. Install a drip leg in vertical pipe runs to serve as a trap for sediment or condensate.
5 - A 1/8” N.P.T. plugged tap or pressure post is located
on the gas valve to facilitate test gauge connection.
See gure 62.
IMPORTANT
Compounds used on threaded joints of gas piping must
be resistant to the actions of liquied petroleum gases.
Leak Check
After gas piping is completed, carefully check all piping
connections (factory- and eld-installed) for gas leaks.
Use a leak detecting solution or other preferred means.
Never use an open ame to test for gas leaks. Check all
connections using a commercially available soap solution
made specically for leak detection.
The furnace must be isolated from the gas supply system by closing its individual manual shut-off valve during any pressure testing of the gas supply system at pressures greater than or equal to 1/2 psig (3.48 kPa, 14 inches w.c.).
Manual Main Shut-Off Valve Will
Not Hold Normal Test Pressure
1/8” N.P.T. Plugged Tap
Isolate Gas Valve
Cap
Figure 56
IMPORTANT
When testing pressure of gas lines, gas valve must be
disconnected and isolated. See gure 56. Gas valves
can be damaged if subjected to pressures greater than 1/2 psig (3.48 kPa).
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings exactly could result in serious injury, death, or property damage. Never use
an open ame to test for gas leaks. Check all connections
using a commercially available soap solution made
specically for leak detection. Some soaps used for leak
detection are corrosive to certain metals. Carefully rinse piping thoroughly after leak test has been completed.
Page 35
Page 36
Right Side Piping
NOTE - BLACK IRON PIPE ONLY TO BE ROUTED INSIDE OF CABINET
MANUAL
MAIN SHUT-OFF
VALV E
GROUND
JOINT
UNION
DRIP LEG
Gas Valve
FIELD
PROVIDED
AND INSTALLED
Figure 57
Horizontal Applications
Possible Gas Piping Configurations
Horizontal Application
Right-Side Air Discharge
Gas Valve
MANUAL
MAIN SHUT-OFF
VALV E
GROUND
JOINT
UNION
DRIP LEG
FIELD
PROVIDED
AND INSTALLED
Figure 58
MANUAL
MAIN SHUT-OFF
VALV E
Horizontal Application
Left-Side Air Discharge
GROUND
JOINT
UNION
DRIP LEG
Gas Valve
NOTE - BLACK IRON PIPE ONLY TO BE ROUTED INSIDE OF CABINET
Page 36
Page 37
TABLE 9
Gas Pipe Capacity - ft3/hr (m3/hr)
Nominal
Iron Pipe
Size Inches
(mm)
1/2
(12.7)
3/4
(19.05)
1
(25.4)
1-1/4
(31.75)
1-1/2
(38.1)
2
(50.8)
2-1/2
(63.5)
Internal
Diameter
inches
(mm)
.622
(17.799)
.824
(20.930)
1.049
(26.645)
1.380
(35.052)
1.610
(40.894)
2.067
(52.502)
2.469
(67.713)
10
(3.048)
172
(4.87)
360
(10.19)
678
(19.19)
1350
(38.22)
2090
(59.18)
4020
(113.83)
6400
(181.22)
20
(6.096)
118
(3.34)
247
(7.000)
466
(13.19)
957
(27.09)
1430
(40.49)
2760
(78.15)
4400
(124.59)
30
(9,144)
95
(2.69)
199
(5.63)
374
(10.59)
768
(22.25)
1150
(32.56)
2220
(62.86)
3530
(99.95)
40
(12,192)
81
(2.29)
170
(4.81)
320
(9.06)
657
(18.60)
985
(27.89)
1900
(53.80)
3020
(85.51)
Length of Pipe - feet (m)
50
(15.240)
72
(2.03)
151
(4.23)
284
(8.04)
583
(16.50)
873
(24.72)
1680
(47.57)
2680
(75.88)
60
(18.288)
65
(1.84)
137
(3.87)
257
(7.27)
528
(14.95)
791
(22.39)
1520
(43.04)
2480
(70.22)
70
(21.336)
60
(1.69)
126
(3.56)
237
(6.71)
486
(13.76)
728
(20.61)
1400
(39.64)
2230
(63.14)
80
(24.384)
56
(1.58)
117
(3.31)
220
(6.23)
452
(12.79)
677
(19.17)
1300
(36.81)
2080
(58.89)
NOTE - Capacity given in cubic feet (m3 ) of gas per hour and based on 0.60 specic gravity gas.
90
(27.432)
52
(1.47)
110
(3.11)
207
(5.86)
424
(12.00)
635
(17.98)
1220
(34.55)
1950
(55.22)
100
(30,480)
50
(1.42)
104
(2.94)
195
(5.52)
400
(11.33)
600
(17.00)
1160
(32.844)
1840
(52.10)
Removal of the Furnace from Common Vent
In the event that an existing furnace is removed from a venting system commonly run with separate gas applianc­es, the venting system is likely to be too large to properly vent the remaining attached appliances. Conduct the fol­lowing test while each appliance is operating and the oth­er appliances (which are not operating) remain connected to the common venting system. If the venting system has been installed improperly, you must correct the system as indicated in the general venting requirements section.
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death. The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation:
1 - Seal any unused openings in the common venting
system.
2 - Inspect the venting system for proper size and
horizontal pitch. Determine that there is no blockage, restriction, leakage, corrosion, or other deciencies
which could cause an unsafe condition.
3 - Close all building doors and windows and all
doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliances not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not
operate a summer exhaust fan. Close replace
dampers.
4 - Follow the lighting instructions. Turn on the appliance
that is being inspected. Adjust the thermostat so that the appliance operates continuously.
5 - After the main burner has operated for 5 minutes,
test for leaks of ue gases at the draft hood relief opening. Use the ame of a match or candle.
6 - After determining that each appliance connected to
the common venting system is venting properly, (step
3) return all doors, widows, exhaust fans, replace
dampers, and any other gas-burning appliances to their previous mode of operation.
7 - If a venting problem is found during any of the
preceding tests, the common venting system must
be modied to correct the problem.
Resize the common venting system to the minimum vent pipe size determined by using the appropriate
tables in Appendix G. (These are in the current stan­dards of the National Fuel Gas Code ANSI Z223.1.
Page 37
Page 38
Electrical
INTERIOR MAKE-UP BOX INSTALLATION
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
CAUTION
Electrostatic discharge can affect electronic components.
Take precautions to neutralize electrostatic charge by
touching your hand and tools to metal prior to handling the control.
The unit is equipped with a eld make-up box. The make­up box may be moved to the right side of the furnace to fa­cilitate installation. Secure the excess wire to the existing harness to protect it from damage.
Refer to gure 60 for eld wiring, schematic wiring dia­gram and troubleshooting.
The power supply wiring must meet Class I restrictions. Protected by either a fuse or circuit breaker, select circuit
protection and wire size according to unit nameplate.
NOTE - Unit nameplate states maximum current draw. Maximum Over-Current Protection allowed is 15 AMP.
WARNING
Electric Shock Hazard. Can cause injury or
death. Unit must be properly grounded in accordance with national and local codes.
WARNING
Fire Hazard. Use of aluminum wire with this product may result in a re, causing property damage, severe injury
or death. Use copper wire only with this product.
MAKE-UP
BOX
Right Side
Figure 59
CAUTION
Failure to use properly sized wiring and circuit breaker may result in property damage. Size wiring and circuit breaker(s) per Product Specications bulletin (EHB) and
unit rating plate.
Holes are on both sides of the furnace cabinet to facilitate wiring.
Install a separate (properly sized) disconnect switch near
the furnace so that power can be turned off for servicing. Before connecting the thermostat check to make sure
the wires will be long enough for servicing at a later date. Make sure that thermostat wire is long enough to facilitate future removal of blower for service.
Complete the wiring connections to the equipment. Use
the provided unit wiring diagram and the eld wiring dia­gram shown in gure 60. Use 18-gauge wire or larger that
is suitable for Class II rating for thermostat connections. Electrically ground the unit according to local codes or,
in the absence of local codes, according to the current National Electric Code (ANSI/NFPA No. 70) for the USA and current Canadian Electric Code part 1 (CSA standard C22.1) for Canada. A green ground wire is provided in the
eld make-up box.
NOTE - The EL195UHNE furnace contains electronic components that are polarity sensitive. Make sure that the furnace is wired correctly and is properly grounded.
Page 38
Page 39
Accessory Terminals
Indoor Blower Speeds
One line voltage “EAC” 1/4” spade terminal is provided on
the furnace integrated control. See gure 61 for integrated control conguration. This terminal is energized when the
indoor blower is operating. Any accessory rated up to one amp can be connected to this terminal with the neutral leg of the circuit being connected to one of the provided neu­tral terminals. If an accessory rated at greater than one amp is connected to this terminal, it is necessary to use an external relay.
One line voltage “120 HUM” 1/4” spade terminal is pro-
vided on the furnace integrated control. See gure 61 for integrated control conguration. This terminal is energized
in the heating mode when the combustion air inducer is operating. Any humidier rated up to one amp can be con­nected to this terminal with the neutral leg of the circuit being connected to one of the provided neutral terminals.
If a humidier rated at greater than one amp is connected
to this terminal, it is necessary to use an external relay One 24V ”H” 1/4” spade terminal is provided on the fur-
nace integrated control. See gure 61 for integrated con­trol conguration. The terminal is energized in the heating
mode when the combustion air inducer is operating and
the pressure switch is closed. Any humidier rated up to
0.5 amp can be connected to this terminal with the ground leg of the circuit connected to ground or the ”C” terminal. Install the room thermostat according to the instructions
provided with the thermostat. See gure 60 for thermostat
designations. If the furnace is being matched with a heat pump, refer to the FM21 installation instruction or appro­priate dual fuel thermostat instructions.
1 - When the thermostat is set to “FAN ON,” the indoor
blower will run continuously on the fan speed (FAN) when there is no cooling or heating demand.
2 - When the EL195UHNE is running in the heating
mode, the indoor blower will run on the heating speed (HEAT).
3 - When there is a cooling demand, the indoor blower
will run on the cooling speed (COOL).
Generator Use - Voltage Requirements
The following requirements must be kept in mind when specifying a generator for use with this equipment:
• The furnace requires 120 volts + 10% (Range: 108 volts to 132 volts).
The furnace operates at 60 Hz + 5% (Range: 57
Hz to 63 Hz).
• The furnace integrated control requires both po­larity and proper ground. Both polarity and proper grounding should be checked before attempting to operate the furnace on either permanent or tempo­rary power.
• Generator should have a wave form distortion of less than 5% THD (total harmonic distortion).
Page 39
Page 40
TYPICAL EL195UHNE WIRING DIAGRAM
Figure 60
Page 40
Page 41
INTEGRATED CONTROL
(Automatic Hot Surface Ignition System)
RECALL BUTTON
BLOWER OFF DELAY
Electrical
FOR YOUR SAFETY READ BEFORE OPERATING
WARNING
Do not use this furnace if any part has been underwater.
A ood-damaged furnace is extremely dangerous. Attempts to use the furnace can result in re or explosion. Immediately call a qualied service technician to inspect
the furnace and to replace all gas controls, control system parts, and electrical parts that have been wet or to replace the furnace, if deemed necessary.
WARNING
Danger of explosion. Can cause injury or product or property damage. If overheating occurs or if gas supply fails to shut off, shut off the manual gas valve to the appliance before shutting off electrical supply.
CAUTION
Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch.
Figure 61
TABLE 10
1/4” QUICK CONNECT TERMINALS
120HUM Humidier 120VAC
LINE 120VAC
XFMR Transformer 120VAC
CIRC Indoor blower 120VAC
EAC Indoor air quality accessory 120VAC
NEUTRAL Common 120VAC
HUM24 Humidier 24VAC
3/16” QUICK CONNECT TERMINALS
COOL Cooling tap 24VAC
HEAT Heating tap 24VAC
FAN Continuous blower 24 VAC
PARK (no power) Park terminal for speed taps
FLAME / FS Flame Sense
24 COM Common 24VAC
BEFORE LIGHTING the unit, smell all around the furnace
area for gas. Be sure to smell next to the oor because some gas is heavier than air and will settle on the oor.
The gas valve on the EL195UHNE is equipped with a gas control switch (lever). Use only your hand to move switch. Never use tools. If the switch will not move by hand, do not try to repair it. Force or attempted repair may result in
a re or explosion.
Placing the furnace into operation:
EL195UHNE units are equipped with an automatic hot surface ignition system. Do not attempt to manually light burners on this furnace. Each time the thermostat calls for heat, the burners will automatically light. The ignitor does not get hot when there is no call for heat on these units.
Page 41
Page 42
Diagnostic Codes / Status of Furnace
RED LED
Flash Code
TABLE 11
2
Off No power to control or board fault detected
Heartbeat
1
Normal Operation - Idle, Continuous Fan, Cool
Continuous Rapid Flash Call For Heat / Burner Operation
1 Reverse Line Voltage Polarity
2 Improper Earth Ground
3 Burner failed to light, or lost ame during heat demand
4 Low Flame Signal - check ame sensor
5
Watchguard - burner failed to light, exceeded maximum number of retries or recycles.
6 Not Used
7
Primary or Secondary Limit Open or Watchguard Mode - Limit Switch Open longer than 3 minutes
8 Rollout Switch Open
9 Pressure Switch failed to close or opened during heat demand
10 Watchguard - Pressure Switch opened 5 times during one heat demand
11 Pressure Switch stuck closed prior to activation of combustion air inducer
12 Flame Sensed without gas valve energized
13 Low Line Voltage
Notes
Note - 1 A ”Heartbeat” is indicated by a ”Slow Flash” - 1 sec on 1 sec off, repeating
Note - 2
Error codes are indicated by a “rapid ash” - the LED ashes X times at ½ second on ½
second off, remains off for 3 seconds then repeats.
Last 10 error codes are stored in memory including when power is shut off to the
Note - 3
unit. - To recall, press and release button, most recent will be displayed rst, LED off for 3
sec, then next error code is displayed, etc. To clear error codes, depress and hold button longer than 5 seconds.
Page 42
Page 43
Priming Condensate Trap
GAS VALV E
The condensate trap should be primed with water prior to start-up to ensure proper condensate drainage. Either
pour 10 . oz. (300 ml) of water into the trap, or follow
these steps to prime the trap:
1 - Follow the lighting instructions to place the unit into
operation.
2 - Set the thermostat to initiate a heating demand.
3 - Allow the burners to re for approximately 3 minutes.
4 - Adjust the thermostat to deactivate the heating
demand.
5 - Wait for the combustion air inducer to stop. Set the
thermostat to initiate a heating demand and again
allow the burners to re for approximately 3 minutes.
6 - Adjust the thermostat to deactivate the heating
demand and wait for the combustion air inducer to stop. At this point, the trap should be primed with
sufcient water to ensure proper condensate drain
operation.
WARNING
If you do not follow these instructions exactly, a re or
explosion may result causing property damage, personal injury or death.
Gas Valve Operation (Figure 62)
1 - STOP! Read the safety information at the beginning
of this section. 2 - Set the thermostat to the lowest setting. 3 - Turn off all electrical power to the unit. 4 - This furnace is equipped with an ignition device
which automatically lights the burners. Do not try to light the burners by hand.
5 - Remove the access panel.
6 - Move gas valve switch to OFF. See gure 62. 7 - Wait ve minutes to clear out any gas. If you then
smell gas, STOP! Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions. If you do not smell gas go to next step.
8 - Move gas valve switch to ON. See gure 62.
NEGATIVE AIR
PRESSURE PORT
INLET
SUPPLY
PRESSURE
TAP
GAS VALVE SHOWN IN THE ON POSITION
Figure 62
POSITIVE AIR
PRESSURE PORT
MANIFOLD
PRESSURE TAP
OUTLET
9 - Replace the access panel. 10- Turn on all electrical power to the unit. 11- Set the thermostat to desired setting.
NOTE - When unit is initially started, steps 1 through 11 may need to be repeated to purge air from gas line.
12- If the appliance will not operate, follow the
instructions “Turning Off Gas to Unit” and call your service technician or gas supplier.
Turning Off Gas to Unit
1 - Set the thermostat to the lowest setting. 2 - Turn off all electrical power to the unit if service is to
be performed. 3 - Remove the access panel. 4 - Move gas valve switch to OFF. 5 - Replace the access panel.
Failure To Operate
If the unit fails to operate, check the following:
1 - Is the thermostat calling for heat? 2 - Are access panels securely in place? 3 - Is the main disconnect switch closed? 4 - Is there a blown fuse or tripped breaker?
5 - Is the lter dirty or plugged? Dirty or plugged lters
will cause the limit control to shut the unit off. 6 - Is gas turned on at the meter? 7 - Is the manual main shut-off valve open? 8 - Is the internal manual shut-off valve open? 9 - Is the unit ignition system in lockout? If the unit locks
out again, inspect the unit for blockages.
Heating Sequence Of Operation
1 - When thermostat calls for heat, combustion air
inducer starts.
2 - Combustion air pressure switch proves blower
operation. Switch is factory set and requires no
adjustment. 3 - After a 15-second prepurge, the hot surface ignitor
energizes.
4 - After a 20-second ignitor warm-up period, the gas
valve solenoid opens. A 4-second trial for ignition
period begins.”
5 - Gas is ignited, ame sensor proves the ame, and
the combustion process continues.
6 - If ame is not detected after rst ignition trial, the
ignition control will repeat steps 3 and 4 four
more times before locking out the gas valve
(“WATCHGUARD” ame failure mode). The ignition
control will then automatically repeat steps 1 through
6 after 60 minutes. To interrupt the 60-minute
“WATCHGUARD” period, move thermostat from
“Heat” to “OFF” then back to “Heat”. Heating
sequence then restarts at step 1.
Page 43
Page 44
Gas Pressure Adjustment
Gas Flow (Approximate)
TABLE 12
GAS METER CLOCKING CHART
EL195 Unit
-040 90 180
-060 60 120
-080 45 90
-100 36 72
Natural-1000 btu/cu ft
Seconds For One Revolution
1 cu ft Dial 2 cu ft Dial
Furnace should operate at least 5 minutes before check­ing gas ow. Determine time in seconds for two revolu- tions of gas through the meter. (Two revolutions assures a more accurate time.) Divide by two and compare to time in table 12 below. If manifold pressure matches table 13
and rate is incorrect, check gas orices for proper size and
restriction. Remove temporary gas meter if installed. NOTE - To obtain accurate reading, shut off all other gas
appliances connected to meter.
Supply Pressure Measurement
A threaded plug on the inlet side of the gas valve provides access to the supply pressure tap. Remove the threaded
plug, install a eld-provided barbed tting and connect a
manometer to measure supply pressure. On multiple unit installations, each unit should be checked
separately, with and without units operating. Supply pres­sure must fall within range listed in table 13.
Check Manifold Pressure
To correctly measure manifold pressure, follow the steps below
1 - Remove the threaded plug from the outlet side of
the gas valve and install a eld-provided barbed tting. Connect measuring device “+” connection to barbed tting to measure manifold pressure.
2 - Start unit and allow 5 minutes for unit to reach steady
state.
3 - After allowing unit to stabilize for 5 minutes, record
manifold pressure and compare to value given in
Table 18. 4 - Shut unit off and remove manometer as soon as an
accurate reading has been obtained. Take care to
remove barbed tting and replace threaded plug.
5 - Start unit and perform leak check. Seal leaks if found.
IMPORTANT
For safety, connect a shut-off valve between the manometer and the gas tap to permit shut off of gas pressure to the manometer.
TABLE 13
Supply Line and Manifold Pressure (inches w.c.)
Unit Fuel
All Nat 3.5 4.5 - 10.5
Proper Combustion
Furnace should operate minimum 15 minutes with correct
manifold pressure and gas ow rate before checking com­bustion. Take combustion sample beyond the ue outlet
and compare to the tables below.
EL195
Model
040 6.3 - 7.8
060 6.5 - 8.2
080 7.2 - 8.4
100 7.3 - 8.5
The maximum carbon monoxide reading should not exceed 100ppm.
High Altitude Information
Units are NOT approved for installations over 4500 ft.
Manifold
Pressure
TABLE 14
Line Pressure
CO2% For Nat
Page 44
Page 45
Testing for Proper Venting and Sufcient Combus­tion Air for Non-Direct Vent Applications
WARNING
CARBON MONOXIDE POISONING HAZARD!
Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death.
The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation.
After the EL195UHNE gas furnace has been started, the following test should be conducted to ensure proper vent-
ing and sufcient combustion air has been provided to the EL195UHNE as well as to other gas-red appliances
which are separately vented. If a EL195UHNE furnace replaces a Category I furnace
which was commonly vented with another gas appliance,
the size of the existing vent pipe for that gas appliance
must be checked. Without the heat of the original furnace
ue products, the existing vent pipe is probably oversized
for the single water heater or other appliance. The vent should be checked for proper draw with the remaining ap­pliance.
The test should be conducted while all appliances (both in operation and those not in operation) are connected to the venting system being tested. If the venting system has been installed improperly, or if provisions have not been
made for sufcient amounts of combustion air, corrections
must be made as outlined in the previous section.
1 - Seal any unused openings in the venting system.
2 - Visually inspect the venting system for proper size and
horizontal pitch. Determine there is no blockage or restriction, leakage, corrosion, or other deciencies
which could cause an unsafe condition.
3 - To the extent that it is practical, close all building
doors and windows and all doors between the space in which the appliances connected to the venting system are located and other spaces of the building.
4 - Close replace dampers.
5 - Turn on clothes dryers and any appliances not
connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan.
6 - Follow the lighting instruction to place the appliance
being inspected into operation. Adjust thermostat so appliance will operate continuously.
7 - Use the ame of match or candle to test for spillage
of ue gases at the draft hood relief opening after 5
minutes of main burner operation.
8 - If improper venting is observed during any of the
above tests, the venting system must be corrected or
sufcient combustion/make-up air must be provided. The venting system should be re-sized to approach the minimum size as determined by using the appropriate
tables in appendix G in the current standards of the National Fuel Gas Code ANSI-Z223.1/NPFA 54 in the U.S.A., and the appropriate Natural Gas and Propane
appliances venting sizing tables in the current
standard of the CSA-B149 Natural Gas and Propane Installation Codes in Canada.
9 - After determining that each appliance remaining
connected to the common venting system properly
vents when tested as indicated in step 3, return
doors, windows, exhaust fans, replace dampers
and any other gas-burning appliance to their previous
condition of use.
Other Unit Adjustments
Primary Limit.
The primary limit is located on the heating compartment vestibule panel. This limit is factory set and requires no adjustment.
Rollout Switch
This auto-reset switch is located on the front of the intake air elbow.
Pressure Switch
The pressure switch is located in the heating compartment on the cold end header box. This switch checks for proper combustion air inducer operation before allowing ignition trial. The switch is factory-set and must not be adjusted.
Temperature Rise
After the furnace has been started and supply and return
air temperatures have been allowed to stabilize, check the
temperature rise. If necessary, adjust the blower speed to maintain the temperature rise within the range shown on the unit nameplate. Increase the blower speed to de­crease. The temperature. Decrease the blower speed to increase the temperature rise. Failure to adjust the tem­perature rise may cause erratic limit operation.
Electrical
1 - Check all wiring for loose connections. 2 - Check for the correct voltage at the furnace operating).
Correct voltage is 120VAC + 10% 3 - Check amp-draw on the blower motor with blower
access panel in place.
Unit Nameplate__________Actual__________
Page 45
Page 46
Fan Control
Electronic Ignition
Fan On Delay
The heat fan on time of 30 seconds is not adjustable. The cool fan on delay is 2 seconds and not adjustable.
Fan Off Delay
The heat fan off delay (amount of time that the blower
operates after the heat demand has been satised) may
be adjusted by changing the jumper position across the
ve pins on the integrated control. The unit is shipped with
a factory fan off setting of 90 seconds. The fan off delay affects comfort and is adjustable to satisfy individual ap­plications. Adjust the fan off delay to achieve a supply air temperature between 90° and 110°F at the moment that the blower is de-energized. Longer off delay settings pro­vide lower return air temperatures; shorter settings pro-
vide higher return air temperatures. See gure 63. The
cool fan off delay (amount of time that the blower operates
after the cool demand has been satised) is 45 seconds
and not adjustable.
Blower Speeds
Follow the steps below to change the blower speeds.
1 - Turn off electrical power to furnace. 2 - Remove blower access panel. 3 - Disconnect existing speed tap at integrated control
speed terminal.
NOTE - Termination of any unused motor leads must be insulated.
HEAT FANOFF TIME IN SECONDS
The integrated control has an added feature of an internal Watchguard control. The feature serves as an automat­ic reset device for integrated control lockout caused by ignition failure. This type of lockout is usually due to low gas line pressure. After one hour of continuous thermostat demand for heat, the Watchguard will break and remake thermostat demand to the furnace and automatically reset the integrated control to begin the ignition sequence.
Service
WARNING
ELECTRICAL SHOCK, FIRE,
OR EXPLOSION HAZARD.
Failure to follow safety warnings exactly could result in dangerous operation, serious injury, death or property damage.
Improper servicing could result in dangerous operation, serious injury, death, or property damage. Before servicing, disconnect all electrical power to furnace.
When servicing controls, label all wires prior to disconnecting. Take care to reconnect wires correctly. Verify proper operation after servicing.
WARNING
The blower access panel must be securely in place when the blower and burners are operating. Gas fumes, which could contain carbon monoxide, can be drawn into living space resulting in personal injury or death.
NO JUMPER
To adjust fan-off timing, reposition jumper across pins to
60 Second
off Time
60
90
120
180
achieve desired setting.
90 Second
off Time
60
90
120
180
120 Second
off Time
60
90
120
180
180 Second
off Time
60
90
120
180
Figure 63
4 - Place unused blower speed tap on integrated control
“PARK” terminal or insulate.
5 - Refer to blower speed selection chart on unit wiring
diagram for desired heating or cooling speed.
See Product Specications Bulletin for blower
performance data.
6 - Connect selected speed tap at integrated control
speed terminal. 7 - Resecure blower access panel. 8 - Turn on electrical power to furnace. 9 - Recheck temperature rise.
Annual Furnace Maintenance
At the beginning of each heating season, and to comply with the Lennox Limited Warranty, your system should be checked as follows:
NOTE - Burner inspection and service is not recommend­ed for annual furnace maintenance.
1 - Check wiring for loose connections, voltage at
indoor unit and amperage of indoor motor.
2- Inspect all gas pipe and connections for leaks.
3- Check the cleanliness of lters and change if
necessary (monthly).
4- Check the cleanliness of blower assembly and
clean the housing, blower wheel and blower motor if necessary .
5- Inspect the condensate drain and trap for leaks and
cracks. Check any additional traps such as in the crawl space exhaust. The drain and trap must also be cleaned and the trap must be primed with water.
Page 46
Page 47
6- Remove the rubber hoses from the cold end header
box and inspect for any blockage, clean as needed. If strainers are installed in the hoses remember to remove and clean before reinstalling the hoses.
7- Evaluate the heat exchanger and combustion
chamber integrity by inspecting the heat exchanger per the AHRI heat exchanger inspection procedure. This can be viewed at www.ahrinet.org. See “Induced­draft Furnace Heat Exchanger Inspection Procedure.
8- Ensure sufcient combustion air is available to the
furnace. Fresh air grilles and louvers (on unit and in the room where the furnace is installed) must be
properly sized, open and unobstructed to provide
combustion air.
9- Inspect the furnace intake and exhaust pipes to make
sure they are in place, structurally sound, without holes, blockage or leakage and the exhaust pipe is sloped toward the furnace. Inspect terminations to ensure they are free of obstructions and are structurally sound. If applicable, inspect and clean air intake screen. Inspect the furnace return air duct connection to ensure the duct is sealed to the furnace.
10- Inspect the furnace return air duct connection to
ensure the duct is sealed to the furnace. Check for air leaks on supply and return ducts and seal where necessary.
11- Check the condition of the furnace cabinet insulation
and repair if necessary.
12- Perform a complete combustion analysis during the
furnace inspection to ensure proper combustion and operation. Consult Service Literature for proper combustion values.
13- Verify operation of smoke detectors and CO
detectors and replace batteries as required.
Perform a general system test. Turn on the furnace to check operating functions such as the start-up and shut­off operation.
1 - Check the operation of the ignition system, inspect
and clean ame sensor. Check microamps before
and after. Check controls and safety devices (gas
valve, ame sensor, temperature limits). Consult
Service Manual for proper operating range. Thermal
Limits should be checked by restricting airow and
not disconnecting the indoor blower. For additional details, please see Service and Application Note H049.
2 - Verify that system total static pressure and airow
settings are within specic operating parameters.
3 - Clock gas meter to ensure that the unit is operating
at the specied ring rate. Check the supply
pressure and the manifold pressure. If manifold pressure adjustment is necessary, consult the
Service Literature for unit specic information
on adjusting gas pressure. Not all gas valves are adjustable. Verify correct temperature rise.
Winterizing and Condensate Trap Care
1 - Turn off power to the furnace. 2 - Have a shallow pan ready to empty condensate
water.
3 - Remove the clean out cap from the condensate trap
and empty water. Inspect the trap then reinstall the clean out cap.
Page 47
Page 48
Repair Parts List
The following repair parts are available through Lennox dealers. When ordering parts, include the complete fur­nace model number listed on the CSA nameplate -- Ex­ample: EL195UH040NE36B-01. All service must be
performed by a licensed professional installer (or equivalent), service agency, or gas supplier.
Cabinet Parts
Outer access panel Blower access panel Top Cap
Control Panel Parts
Transformer Integrated control board Door interlock switch
Blower Parts
Blower wheel Motor Motor mounting frame Blower housing cutoff plate
Heating Parts
Flame Sensor Heat exchanger assembly Gas manifold Assembly Combustion air inducer Gas valve Burner assembly Pressure switch Ignitor Primary limit control Rollout switch
Page 48
Page 49
Start-Up & Performance Check List
Furnace: Model Number_______________
Serial Number_________________
2
1
GAS SUPPLY
UNIT SET UP
Line Voltage
4
SUPPLY
AIR
Natural Gas
Piping Connections Tight
Leak Tested
2
2
INTAKE / EXHAUST PIPE
Supply Line Pressure “W.C.________
1
All Joints Primed and Glued
LP Propane Gas
Gas Supply Pressure
1
DUCT SYSTEM
3
SUPPLY AIR DUCT
Sealed
Insulated (if necessary)
RETURN DUCT
Sealed
3
Flter
RETURN AIR
Terminations Installed Properly
Horizontal Pipes Sloped (if applicable)
Condensate Trap Primed / Line Sloped
Pipes Supported
Heat Cable Installed and Operable (if applicable)
Page 49
Filter Installed and Clean
Grilles Unobstructed
VOLTAGE CHECK
4
Supply Voltage _____
Electrical Connections Tight
Page 50
Contractor's: Name_________________________Telephone_____________Checklist Completed____________________
Job Address_____-________________________________Technician's Name___________________________________
1
HEATING MODE
GAS MANIFOLD PRESSURE “W.C._____
COMBUSTION SAMPLE CO
2%______
CO PPM_______
2
INDOOR BLOWER AMPS______
3
TEMPERATURE RISE
4
Supply Duct Temperature ________ Return Duct Temperature
_
_____
Temperature Rise = ________
TOTAL EXTERNAL STATIC
5
Supply External Static _______
Return External Static + ______
Total External Static = _______
CONDENSATE LINE
6
Leak Free
VENT PIPE
7
Leak Free
COOLING MODE
INDOOR BLOWER AMPS______
3
TEMPERATURE DROP
Return Duct Temperature _________ Supply Duct Temperature
_
_______
Temperature Drop = _________
4
DRAIN LINE
8
Leak Free
THERMOSTAT
Adjusted and Programmed
Explained Operation to Owner
9
SUPPLY
AIR
Blower Motor Amps
Duct Static
Thermostat
Gas Manifold Pressure
1
2
3
4
5
6
7
8
9
Temperatures
RETURN AIR
Combustion CO
2
UNIT OPERATION
TOTAL EXTERNAL STATIC (dry coil)
Supply External Static _______
Return External Static + ______
Total External Static = _______
5
Page 50
Loading...