This EL16XC1 outdoor air conditioner with all-aluminum
coil is designed for use with HFC-410A refrigerant only.
This unit must be installed with an approved indoor air han
dler or coil. See the Lennox EL16XC1 Product Specifica
tions bulletin (EHB) for approved indoor component match
ups.
These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
having jurisdiction before installation.
IMPORTANT: Special procedures are required for clean
ing the aluminum coil in this unit. See page 15 in this in
struction for information.
INSTRUCTIONS
Elite® Series EL16XC1 Units
AIR CONDITIONER
507525-01
08/2016
WARNING
Improper installation, adjustment, alteration, service or
maintenance can cause property damage, personal inju
ry or loss of life.
Installation and service must be performed by a licensed
professional installer (or equivalent) or service agency.
CAUTION
As with any mechanical equipment, contact with sharp
sheet metal edges can result in personal injury. Take care
while handling this equipment and wear gloves and pro
tective clothing.
NOTICE !
For more in-depth information, consult the Installa
tion and Service Procedures manual, available as
Corp. 1503-L7 on LennoxPROs.com or through the
Technical Support department at 800-453-6669.
STEP 1 -- SETTING THE UNIT -- Clearances
See NOTES
See
NOTES
See NOTES
NOTICE: Specific applications may require adjustment of the listed installation clearances to provide protection for
the unit from physical damage or to avoid conditions which limit operating efficiency. (Example: Clearances may
have to be increased to prevent snow or ice from falling on the top of the unit. Additional clearances may also be
required to prevent air recirculation when the unit is installed under a deck or in another tight space.)
See
NOTES
Control
Box
NOTES:
Service clearance of 30 in. must be maintained on one of the sides
adjacent to the control box.
Clearance to one of the other three sides must be 36 in.
Clearance to one of the remaining two sides may be 12 in. and the
final side may be 6 in.
A clearance of 24 in. must be maintained between two units.
Roof Damage!
This system contains both refrigerant and oil. Some
rubber roofing material may absorb oil, causing the
rubber to degrade. Failure to follow this notice could
result in damage to roof surface.
IMPORTANT !
Exhaust vents from dryers, water heaters and
furnaces should be directed away from the outdoor
unit. Prolonged exposure to exhaust gases and the
chemicals contained within them may cause
condensation to form on the steel cabinet and other
metal components of the outdoor unit. This will
diminish unit performance and longevity.
PLACEMENT
Install unit away from windows.
ELEVATED SLAB MOUNTING USING FEET
EXTENDERS
2” (50.8MM) SCH 40
FEMALE THREADED
ADAPTER
2” (50.8MM)
SCH 40 MALE
THREADED
ADAPTER
LEG DETAIL
Use additional 2” SCH 40 male
threaded adapters which can
be threaded into the female
threaded adapters to make
additional adjustments to the
level of the unit.
BASE
FIGURE 4
CAUTION
TWO 90° ELBOWS INSTALLED IN LINE SET
WILL REDUCE LINE SET VIBRATION.
FIGURE 2
SLAB MOUNTING
Install unit level or, if on a slope, maintain slope tolerance of 2
degrees (or 2 inches per 5 feet [50 mm per 1.5 m]) away from
building structure.
BUILDING
STRUCTURE
MOUNTING
SLAB
GROUND LEVEL
Before attempting to perform any service or mainte
nance, turn the electrical power to unit OFF at disconnect
switch.
STABILIZING UNIT ON UNEVEN SURFACES
#10 X 1/2” LONG
SELF-DRILLING
SHEET METAL
SCREWS
STABILIZING BRACKET
(18 GAUGE METAL — 2”
WIDTH; HEIGHT AS
REQUIRED)
#10 X 1-1/4” LONG
HEX HD SCREW AND
FLAT WASHER
Concrete slab — use two
plastic anchors (hole drill 1/4”)
!
IMPORTANT !
CORNER POST
COIL
BASE PAN
Unit Stabilizer Bracket Use
(field-provided):
Always use stabilizers when unit is raised above
the factory height.
(Elevated units could become unstable in gusty
wind conditions.)
Stabilizers may be used on any unit installed on
unstable and uneven surfaces.
FIGURE 3
FIGURE 5
Page 3
EL16XC1 SERIES
Page 4
WARNING
To prevent personal injury, as well as damage to panels,
unit or structure, observe the following:
While installing or servicing this unit, carefully stow all
removed panels so that the panels will not cause injury
to personnel, objects or nearby structures. Also, take
care to store panels where they will not be subject to
damage (e.g., being bent or scratched).
While handling or stowing the panels, consider any
weather conditions (especially wind) that may cause
panels to be blown around and damaged.
STEP 2 -- REFRIGERANT PIPING —
Flushing Existing Line Set & Indoor Coil
Flush the existing line set per the following instruc
tions. For more information, refer to the Installation
and Service Procedures manual available on DaveNet.
CAUTION - DO NOT attempt to flush and re-use exist
ing line sets or indoor coil when the system contains
contaminants (i.e., compressor burn out).
IMPORTANT !
If this unit is being matched with an approved line
set or indoor unit coil that was previously charged
with mineral oil, or if it is being matched with a coil
which was manufactured before January of 1999,
the coil and line set must be flushed prior to installa
tion. Take care to empty all existing traps. Polyol es
ter (POE) oils are used in Lennox units charged with
HFC-410A refrigerant. Residual mineral oil can act
as an insulator, preventing proper heat transfer. It
can also clog the expansion device and reduce sys
tem performance and capacity.
Failure to properly flush the system per this instruc
tion and the detailed Installation and Service Proce
dures manual will void the warranty.
WARNING
When using a high pressure gas such as
nitrogen to pressurize a refrigeration or air
conditioning system, use a regulator that
can control the pressure down to 1 or 2 psig
(6.9 to 13.8 kPa).
WARNING
Refrigerant can be harmful if it is inhaled. Refrigerant
must be used and recovered responsibly.
Failure to follow this warning may result in personal injury
or death.
WARNING
Fire, Explosion and Personal Safety Haz
ard. Failure to follow this warning could re
sult in damage, personal injury or death.
Never use oxygen to pressurize or purge
refrigeration lines. Oxygen, when exposed
to a spark or open flame, can cause fire
and/or an explosion, that could result in
property damage, personal injury or death.
WARNING
Polyol ester (POE) oils used with HFC-410A
refrigerant absorb moisture very quickly. It is very
important that the refrigerant system be kept closed
as much as possible. DO NOT remove line set caps
or service valve stub caps until you are ready to make
connections.
NOTE - When installing refrigerant lines longer than 50 feet, refer to the Refrigerant Piping Design and Fabrication Guidelines manual
available on DaveNet (Corp. 9351-L9), or contact the Technical Support Department Product Application group for assistance.
NOTE - For new or replacement line set installation, refer to Service and Application Note - Corp. 9112-L4 (C-91-4).
Liquid LineSuction Line
3/8” (10 mm)3/4” (19 mm)
3/8” (10 mm)7/8” (22 mm)
* Applicable to all minor revision numbers unless otherwise specified.
** Some applications may require a field-provided 1-1/8” to 7/8” adapter.
1 - On fully cased coils, remove the coil access and plumbing panels.
2 - Remove any shipping clamps from the liquid line and distributor
assembly.
3 - Disconnect the equalizer line from the expansion valve equalizer
line fitting on the suction line.
4 - Remove the suction line sensing bulb.
5 - Disconnect the liquid line from the expansion valve at the liquid line
assembly.
6 - Disconnect the expansion valve from the liquid line orifice housing.
Take care not to twist or damage distributor tubes during this
process.
7 - Remove and discard expansion valve and the two Teflon® rings.
8 - Use a field-provided fitting to temporarily reconnect the liquid line to
the indoor unit's liquid line orifice housing.
FLUSHING LINE SET
The line set and indoor unit coil must be flushed with at least the same
3
amount of clean refrigerant* that previously charged the system.
Check the charge in the flushing cylinder before proceeding.
1 - Set the recovery machine for liquid recovery and start the recovery
machine. Open the gauge set valves to allow the recovery
machine to pull a vacuum on the existing system line set and indoor
unit coil.
2 - Position the cylinder of clean HCFC-22* for delivery of liquid
3 - After all of the liquid refrigerant has been recovered, switch the
4 - Close the valve on the inverted HCFC-22 drum and the gauge set
B
refrigerant and open its valve to allow liquid refrigerant to flow into
the system through the suction line valve. Allow the refrigerant to
pass from the cylinder and through the line set and the indoor unit
coil before it enters the recovery machine.
recovery machine to vapor recovery so that all of the HCFC-22
vapor is recovered. Allow the recovery machine to pull the system
down to 0.
valves. Pump the remaining refrigerant out of the recovery
machine and turn the machine off.
*IMPORTANT - Clean refrigerant is any refrigerant in a system that has not had compressor burn out. If the system
has experienced burn out, it is recommended that the existing line set and indoor coil be replaced.
Cut ends of the refrigerant lines square (free from nicks or dents)
1
and debur the ends. The pipe must remain round. Do not crimp end
of the line.
CUT AND DEBUR
LINE SET SIZE MATCHES
SERVICE VALVE CONNECTION
SERVICE VALVE
COPPER TUBE
REDUCER
CONNECTION
STUB
LINE SET SIZE IS SMALLER
THAN CONNECTION
REFRIGERANT LINE
DO NOT CRIMP SERVICE VALVE
CONNECTOR WHEN PIPE IS
SMALLER THAN CONNECTION
CAP AND CORE REMOVAL
Remove service cap and core from
2
both the suction / vapor and liquid line
service ports.
SERVICE PORT
CAP
SERVICE
PORT
CORE
LIQUID LINE SERVICE
VALV E
SUCTION LINE SERVICE
ATTACH THE MANIFOLD GAUGE SET FOR BRAZING LIQUID AND SUCTION LINE SERVICE VALVES
3
Flow regulated nitrogen (at 1 to 2 psig) through the low-side refrigeration gauge set into the liquid line service port valve, and out of the suction
line service port valve.
1 - Connect gauge set low pressure side to
liquid line service valve (service port).
2 - Connect gauge set center port to bottle of
nitrogen with regulator.
3 - Remove core from valve in suction line
service port to allow nitrogen to escape.
ATTACH
GAUGES
HIGHLOW
USE REGULATOR TO FLOW
NITROGEN AT 1 TO 2 PSIG.
VALV E
SERVICE
PORT
CORE
SERVICE
PORT CAP
SUCTION SERVICE PORT MUST BE OPEN TO
ALLOW EXIT POINT FOR NITROGEN
SUCTION LINE
INDOOR
UNIT
LIQUID LINE
C
LIQUID LINE SERVICE
VALV E
CAUTION
Brazing alloys and flux contain materials which are
hazardous to your health.
Avoid breathing vapors or fumes from brazing
operations. Perform operations only in well-ventilated
areas.
Wear gloves and protective goggles or face shield to
protect against burns.
Wash hands with soap and water after handling brazing
alloys and flux.
SUCTION
LINE
SERVICE
VALV E
FIGURE 7
B
OUTDOOR
UNIT
WHEN BRAZING LINE SET TO
A
SERVICE VALVES, POINT FLAME
AWAY FROM SERVICE VALVE.
Danger of fire. Bleeding the refrigerant
charge from only the high side may result
in pressurization of the low side shell and
suction tubing. Application of a brazing
torch to a pressurized system may result
in ignition of the refrigerant and oil
mixture. Check the high and low
pressures before applying heat.
NITROGEN
WARNING
Page 6
EL16XC1 SERIES
Page 7
WRAP SERVICE VALVES
To help protect service valve seals during brazing, wrap water-saturated cloths around service valve bodies and copper tube stubs. Use
4
additional water-saturated cloths underneath the valve body to protect the base paint.
FLOW NITROGEN
Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration gauge set into the valve stem port connection on the liquid service valve and
5
out of the suction valve stem port. See steps 3A, 3B and 3C on manifold gauge set connections.
BRAZE LINE SET
Wrap both service valves with water-saturated cloths as illustrated here and as mentioned in step 4, before brazing to line set. Cloths must
6
remain water-saturated throughout the brazing and cool-down process.
LIQUID LINE SERVICE VALVE
WHEN BRAZING LINE SET TO
SERVICE VALVES, POINT FLAME
AWAY FROM SERVICE VALVE.
IMPORTANT - Allow braze joint to cool. Apply additional
water-saturated cloths to help cool brazed joint. Do not
remove water-saturated cloths until piping has cooled.
Temperatures above 250ºF will damage valve seals.
LIQUID LINE
WATER-SATURATED
CLOTH
WARNING
FIRE, PERSONAL INJURY, OR PROPERTY DAMAGE
may result if you do not wrap a water-saturated cloth around
both liquid and suction line service valve bodies and copper
tube stub while brazing the line set! The braze, when
complete, must be quenched with water to absorb any
residual heat.
Do not open service valves until refrigerant lines and
indoor coil have been leak-tested and evacuated. Refer
to Installation and Service Procedures manual found on
DAVENET.
SUCTION LINE
PREPARATION FOR NEXT STEP
After all connections have been brazed, disconnect manifold gauge set from service ports. Apply additional water-saturated cloths to both
7
services valves to cool piping. Once piping is cool, remove all water-saturated cloths.
This outdoor unit is designed for use in systems that use a expansion valve metering device. See the EL16XC1 Product
Specifications bulletin (EHB) for approved expansion valve kit match-ups and application information. The expansion valve
can be installed internal or external to the indoor coil. In applications where an uncased coil is being installed in a field-pro
vided plenum, install the expansion valve in a manner that will provide access for future field service of the expansion valve.
Refer to below illustration for reference during installation of expansion valve.
INDOOR EXPANSION VALVE INSTALLATION
TWO PIECE
PATCH PLATE
(UNCASED
COIL ONLY)
DISTRIBUTOR
TUBES
DISTRIBUTOR
ASSEMBLY
MALE EQUALIZER LINE
FITTING (SEE
EQUALIZER LINE
INSTALLATION FOR
FURTHER DETAILS)
(Uncased Coil Shown)
LIQUID LINE
ORIFICE
HOUSING
STUB
END
TEFLON
RING
EQUALIZER
LINE
SUCTION
EXPANSION
VALV E
®
LIQUID LINE
ASSEMBLY WITH
LINE
TEFLON
RING
SENSING
BRASS NUT
LIQUID LINE
Sensing bulb insulation is required if
mounted external to the coil casing. sensing
bulb installation for bulb positioning.
EQUALIZER LINE INSTALLATION
1 - Remove and discard either the flare seal cap or flare nut with
copper flare seal bonnet from the equalizer line port on the
suction line as illustrated in the figure below.
2 - Remove the field-provided fitting that temporarily recon
nected the liquid line to the indoor unit's distributor assembly.
®
LINE
3 - Install one of the provided Teflon® rings around the
stubbed end of the expansion valve and lightly lubricate
the connector threads and expose surface of the Teflon
ring with refrigerant oil.
4 - Attach the stubbed end of the expansion valve to the
liquid line orifice housing. Finger tighten and use an
appropriately sized wrench to turn an additional 1/2 turn
clockwise as illustrated in the figure above, or tighten to
20 ft-lb.
5 - Place the remaining Teflon® washer around the other
end of the expansion valve. Lightly lubricate connector
threads and expose surface of the Teflon® ring with
refrigerant oil.
6 - Attach the liquid line assembly to the expansion valve.
Finger tighten and use an appropriately sized wrench to
turn an additional 1/2 turn clockwise as illustrated in the
figure above or tighten to 20 ft-lb.
SENSING BULB INSTALLATION
1 - Attach the suction line sensing bulb in the proper
orientation as illustrated to the right using the clamp and
screws provided.
NOTE - Confirm proper thermal contact between the suction
line and expansion bulb before insulating the sensing bulb
once installed.
2 - Connect the equalizer line from the expansion valve to
the equalizer suction port on the suction line. Finger
tighten the flare nut plus 1/8 turn (7 ft-lbs) as illustrated
below.
SUCTION LINE
BULB
12
ON LINES SMALLER THAN
7/8”, MOUNT SENSING
BULB AT EITHER THE 3 OR
9 O'CLOCK POSITION.
BULB
®
1/2 Turn
11
10
9
8
7
1/8 Turn
11
10
9
8
7
12
1
2
3
4
5
6
12
1
2
3
4
5
6
FLARE SEAL CAP
OR
FLARE NUT
COPPER FLARE
SEAL BONNET
MALE BRASS EQUALIZER
LINE FITTING
SUCTION LINE
FIGURE 8
Page 8
SUCTION LINE
12
BULB
NOTE - NEVER MOUNT THE SENSING BULB ON
BOTTOM OF LINE.
BULB
ON 7/8” AND LARGER LINES,
MOUNT SENSING BULB AT
EITHER THE 4 OR 8 O'CLOCK
POSITION. NEVER MOUNT
THE SENSING BULB ON
BOTTOM OF LINE.
EL16XC1 SERIES
Page 9
STEP 3 -- LEAK TEST AND EVACUATION
HIGHLOW
MANIFOLD GAUGE SET
OUTDOOR UNIT
B
TO SUCTION
SERVICE VALVE
NOTE - Position
canister to deliver
liquid refrigerant.
NITROGEN
CONNECT GAUGE SET
A - Connect the high pressure hose of an HFC-410A manifold gauge set to the suction valve service
1
2
port.
NOTE - Normally, the high pressure hose is connected to the liquid line port. However, connecting it
to the suction port better protects the manifold gauge set from high pressure damage.
B - With both manifold valves closed, connect the cylinder of HFC-410A refrigerant to the center port of
the manifold gauge set.
NOTE - Later in the procedure, the HFC-410A container will be replaced by the nitrogen container.
TEST FOR LEAKS
After the line set has been connected to the indoor and outdoor units, check the line set connections
and indoor unit for leaks. Use the following procedure to test for leaks:
A - With both manifold valves closed, connect the cylinder of HFC-410A refrigerant to the center port of
the manifold gauge set. Open the valve on the HFC-410A cylinder (vapor only).
B - Open the high pressure side of the manifold to allow HFC-410A into the line set and indoor unit.
Weigh in a trace amount of HFC-410A. [A trace amount is a maximum of two ounces (57 g) refrigerant or three pounds (31 kPa) pressure.] Close the valve on the HFC-410A cylinder and the valve on
the high pressure side of the manifold gauge set. Disconnect the HFC-410A cylinder.
C - Connect a cylinder of nitrogen with a pressure regulating valve to the center port of the manifold
gauge set.
D - Adjust nitrogen pressure to 150 psig (1034 kPa). Open the valve on the high side of the manifold gauge
set in order to pressurize the line set and the indoor unit.
E - After a few minutes, open one of the service valve ports and verify that the refrigerant added to the
system earlier is measurable with a leak detector.
F - After leak testing, disconnect gauges from service ports.
HFC-410A
A
FIGURE 9
Page 9
EL16XC1 SERIES
Page 10
STEP 3 -- LEAK TEST AND EVACUATION (Continued)
CONNECT GAUGE SET
NOTE - Remove cores from service valves (if not already done).
3
A - Connect low side of manifold gauge set with
1/4 SAE in-line tee to suction line service
valve
B - Connect high side of manifold gauge set to
liquid line service valve
C - Connect available micron gauge connector
on the 1/4 SAE in-line tee.
D - Connect the vacuum pump (with vacuum
gauge) to the center port of the manifold
gauge set. The center port line will be used
later for both the HFC-410A and nitrogen
containers.
NITROGEN
NOTE - Position
canister to deliver
liquid refrigerant.
HFC-410A
VACUUM PUMP
OUTDOOR
UNIT
EVACUATION
A
B
1/4 SAE TEE WITH SWIVEL
COUPLER
500
C
MICRON
GAUGE
GAUGE SET
TO SUCTION
SERVICE VALVE
TO LIQUID LINE
SERVICE VALVE
LOW
MANIFOLD
D
EVACUATE THE SYSTEM
4
A - Open both manifold valves and start the vacuum pump.
B - Evacuate the line set and indoor unit to an absolute pressure of 23,000 microns (29.01 inches of mercury).
NOTE - During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once. A rapid rise in pressure indicates a
relatively large leak. If this occurs, repeat the leak testing procedure.
NOTE - The term absolute pressure means the total actual pressure above absolute zero within a given volume or system. Absolute pressure
in a vacuum is equal to atmospheric pressure minus vacuum pressure.
C - When the absolute pressure reaches 23,000 microns (29.01 inches of mercury),
perform the following:
● Close manifold gauge valves.
● Close valve on vacuum pump.
● Turn off vacuum pump.
● Disconnect manifold gauge center port hose from vacuum pump.
● Attach manifold center port hose to a nitrogen cylinder with pressure
regulator set to 150 psig (1034 kPa) and purge the hose.
● Open manifold gauge valves to break the vacuum in the line set and indoor
unit.
● Close manifold gauge valves.
D - Shut off the nitrogen cylinder and remove the manifold gauge hose from the cylinder. Open the manifold gauge valves to release the nitrogen
from the line set and indoor unit.
E - Reconnect the manifold gauge to the vacuum pump, turn the pump on, and continue to evacuate the line set and indoor unit until the absolute
pressure does not rise above 500 microns (29.9 inches of mercury) within a 20-minute period after shutting off the vacuum pump and closing
the manifold gauge valves.
F - When the absolute pressure requirement above has been met, disconnect the manifold hose from the vacuum pump and connect it to a
cylinder of HFC-410A positioned to deliver liquid refrigerant. Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line
set and indoor unit.
G - Perform the following:
● Close manifold gauge valves.
● Shut off HFC-410A cylinder.
● Reinstall service valve cores by removing manifold hose from service valve. Quickly install cores with core
tool while maintaining a positive system pressure.
● Replace stem caps and finger tighten them, then tighten an additional one-sixth (1/6) of a turn as illustrated.
Possible equipment damage.
Avoid deep vacuum operation. Do not use
compressors to evacuate a system.
Extremely low vacuum can cause internal
arcing and compressor failure. Damage
caused by deep vacuum operation will void
warranty.
WARNING !
RECOMMEND
MINIMUM 3/8” HOSE
1/6 TURN
12
11
10
9
8
7
6
HIGH
1
2
3
4
5
FIGURE 10
Page 10
EL16XC1 SERIES
Page 11
STEP 4 -- ELECTRICAL -- Circuit Sizing and Wire Routing
In the U.S.A., wiring must conform with current local codes
and the current National Electric Code (NEC). In Canada,
wiring must conform with current local codes and the current
Canadian Electrical Code (CEC).
Refer to the furnace or air handler installation instructions
for additional wiring application diagrams and refer to unit
Fire Hazard. Use of aluminum wire with this product
may result in a fire, causing property damage, severe
injury or death. Use copper wire only with this product.
nameplate for minimum circuit ampacity and maximum
overcurrent protection size.
24VAC TRANSFORMER
Use the transformer provided with the furnace or air han
dler for low‐voltage control power (24VAC - 40 VA mini
mum)
Failure to use properly sized wiring and circuit breaker
may result in property damage. Size wiring and circuit
breaker(s) per Product Specifications bulletin (EHB) and
unit rating plate.
WARNING
Electric Shock Hazard. Can cause injury
or death. Unit must be properly grounded
in accordance with national and local
codes.
Line voltage is present at all components
when unit is not in operation on units with
single‐pole contactors. Disconnect all
remote electric power supplies before
opening access panel. Unit may have
multiple power supplies.
IMPORTANT !
If unit is equipped with a crankcase heater, it should
be energized 24 hours before unit start-up to prevent
compressor damage as a result of slugging.
ELECTROSTATIC
DISCHARGE
(ESD)
Precautions and
Procedures
WARNING
CAUTION
CAUTION
Electrostatic discharge can affect
electroniccomponents.Takecareduring
unit installation and service to protect the
unit's electronic controls. Precautions
will help to avoid control exposure to
electrostatic discharge by putting the
unit, the control and the technician at the
same electrostatic potential. Touch hand
and all tools on an unpainted unit surface
beforeperforminganyserviceprocedure
to neutralize electrostatic charge.
SIZE CIRCUIT AND INSTALL SERVICE
DISCONNECT SWITCH
Refer to the unit nameplate for minimum circuit ampacity, and maximum
fuse or circuit breaker (HACR per NEC). Install power wiring and properly
sized disconnect switch.
NOTE - Units are approved for use only with copper conductors.
Ground unit at disconnect switch or connect to an earth ground.
MAIN FUSE
BOX/BREAKER
PANEL
DISCONNECT
SWITCH
FIGURE 11
Install room thermostat (ordered separately) on an inside wall
INSTALL THERMOSTAT
approximately in the center of the conditioned area and 5 feet (1.5m)
from the floor. It should not be installed on an outside wall or where it
can be affected by sunlight or drafts.
THERMOSTAT
5 FEET
(1.5M)
NOTE - 24VAC, Class II circuit connections are made in the control
panel.
Page 11
EL16XC1 SERIES
Page 12
STEP 4 -- ELECTRICAL (CONTINUED) -- Field Wiring
Unit Low Voltage Wiring
C
WIRE NUTS
BLACK
CUTOUT WITH
GROMMET
A
24V CONTROL WIRES
24VAC Control Wiring Diagrams (Field Installed)
ML180
B
YELLOW
D
TIGHTEN WIRE TIE
FIGURE 12
EL280, EL295, EL296
HIGH VOLTAGE FIELD WIRING
FACTORY WIRING
LOW VOLTAGE (24V) FIELD WIRING
WIRE RUN LENGTHAWG# INSULATION TYPE
LESS THAN 100' (30 METERS)18 TEMPERATURE RATING
MORE THAN 100' (30 METERS)16 35ºC MINIMUM.
A -Run 24VAC control wires through cutout with grommet.
B -Run 24VAC control wires through wire tie.
C -Make 24VAC control wire connections using field-provided
wire nuts.
D -Tighten wire tie to security 24V control wiring.
NOTE - FOR PROPER VOLTAGES, SELECT THERMOSTAT WIRE (CONTROL WIRES)
GAUGE PER TABLE ABOVE.
NOTE - WIRE TIE PROVIDES LOW VOLTAGE WIRE STRAIN RELIEF AND MAINTAINS
SEPARATION OF FIELD-INSTALLED LOW AND HIGH VOLTAGE CIRCUITS.
NOTE - DO NOT BUNDLE ANY EXCESS 24VAC CONTROL WIRES INSIDE CONTROL
BOX.
SLP98, SL28UH, SL280DF
XC14XC14XC14
CBX25
XC14
XC14
NOTE - Refer to furnace, blower coil and accessory instructions for
additional wiring configurations with other optional controls.
XC14
CBX40UHV
2
XC14
RED
3
BROWN
BLUE
Air handler shipped with jumpers installed between W1 and W2
1
and W2 and W3.
R connection required for air conditioner with LSOM. Resistor kit
2
(CAT #47W97) required when connection ComfortSense 7000
with LSOM 2.
L connection wired on units with LSOM.
3
1
FIGURE 13
Page 12
EL16XC1 SERIES
Page 13
STEP 5 -- UNIT START-UP
IMPORTANT
If unit is equipped with a crankcase heater, it should be
energized 24 hours before unit start-up to prevent
compressor damage as a result of slugging.
1 - Rotate fan to check for binding.
2 - Inspect all factory- and field-installed wiring for loose
connections.
3 - After evacuation is complete, open the liquid line and
suction line service valve stems to release the refriger
ant charge (contained in outdoor unit) into the system.
4 - Replace the stem caps and tighten to the value listed
in table 2.
5 - Check voltage supply at the disconnect switch. The
voltage must be within the range listed on the unit's
nameplate. If not, do not start the equipment until you
have consulted with the power company and the volt
age condition has been corrected.
6 - Connect manifold gauge set for testing and charging
using figure 11 as a guideline.
7 - Set the thermostat for a cooling demand. Turn on pow
er to the indoor indoor unit and close the outdoor unit
disconnect switch to start the unit.
8 - Recheck voltage while the unit is running. Power must
be within range shown on the unit nameplate.
9 - Check system for sufficient refrigerate using the pro
cedures outlined in under System Refrigerant.
OPERATING MANIFOLD GAUGE SET AND SERVICE
VALVES
The liquid and suction line service valves are used for re
moving refrigerant, flushing, leak testing, evacuating,
checking charge and charging.
Each valve is equipped with a service port which has a fac
tory-installed valve stem. Figures 14 and 15 provide infor
mation on how to access and operate both angle- and balltype service valves.
Torque Requirements
When servicing or repairing heating, ventilating, and air
conditioning components, ensure the fasteners are appro
priately tightened. Table 2 lists torque values for fasteners.
TABLE 2
TORQUE REQUIREMENTS
PartsRecommended Torque
Service valve cap8 ft.- lb.11 NM
Sheet metal screws16 in.- lb.2 NM
Machine screws #1028 in.- lb.3 NM
Compressor bolts90 in.- lb.10 NM
Gauge port seal cap8 ft.- lb.11 NM
Using Manifold Gauge Set
When checking the system charge, only use a manifold
gauge set that features low loss anti-blow back fittings.
Manifold gauge set used with HFC-410A refrigerant sys
tems must be capable of handling the higher system oper
ating pressures. The gauges should be rated for use with
pressures of 0 - 800 psig on the high side and a low side of
30” vacuum to 250 psig with dampened speed to 500 psi.
Gauge hoses must be rated for use at up to 800 psig of
pressure with a 4000 psig burst rating.
OPERATING BALL-TYPE SERVICE VALVE:
1 - Remove stem cap with an appropriately sized wrench.
2 - Use an appropriately sized wrenched to open. To open valve,
rotate stem counterclockwise 90°. To close rotate stem
clockwise 90°.
TO OPEN ROTATE STEM
COUNTERCLOCKWISE 90°.
TO CLOSE ROTATE STEM
CLOCKWISE 90°.
SERVICE PORT
SERVICE PORT
SERVICE PORT
CORE
CAP
BALL (SHOWN
CLOSED)
VALV E
STEM
STEM CAP
FIGURE 14
OPERATING ANGLE-TYPE SERVICE VALVE:
1 - Remove stem cap with an appropriately sized wrench.
2 - Use a service wrench with a hex-head extension (3/16” for liquid
line valve sizes and 5/16” for suction line valve sizes) to back the
stem out counterclockwise as far as it will go.
SERVICE PORT CAP
SERVICE PORT CORE
(VALVE STEM SHOWN OPEN)
INSERT HEX WRENCH HERE
STEM CAP
ANGLE-TYPE SERVICE VALVE
(BACK-SEATED OPENED)
When service valve is OPEN, the service port is
open to line set, indoor and outdoor unit.
(VALVE STEM SHOWN CLOSED)
INSERT HEX WRENCH HERE
ANGLE-TYPE SERVICE VALVE
(FRONT-SEATED CLOSED)
IMPORTANT
To prevent stripping of the various caps used, the
appropriately sized wrench should be used and fitted
snugly over the cap before tightening.
When service valve is CLOSED, the service port is
open to the line set and indoor unit.
NOTE - A label with specific torque requirements may be affixed to the
stem cap. If the label is present, use the specified torque.
FIGURE 15
Page 13
EL16XC1 SERIES
Page 14
TO ACCESS SERVICE PORT:
A service port cap protects the service port core from contamination
and serves as the primary leak seal.
1 - Remove service port cap with an appropriately sized wrench.
2 - Connect gauge set to service port.
3 - When testing is completed, replace service port cap and tighten
as follows:
●With torque wrench: Finger tighten and
torque cap per table 2.
●Without torque wrench: Finger tighten and
use an appropriately sized wrench to turn
an additional 1/6 turn clockwise.
10
9
8
Reinstall Stem Cap:
Stem cap protects the valve stem from damage and serves as the
primary seal. Replace the stem cap and tighten as follows:
●With Torque Wrench: Finger tighten
and then torque cap per table 2.
●Without Torque Wrench: Finger
tighten and use an appropriately
sized wrench to turn an addition
al 1/12 turn clockwise.
11
10
9
8
7
11
7
1/12 TURN
12
6
12
6
1
5
1/6 TURN
1
2
3
4
5
2
3
4
FIGURE 16
Checking and Adding System Charge
The EL16XC1 unit is factory-charged with enough
HFC-410A refrigerant to accommodate a 15-foot length of
refrigerant piping. Charge should be checked and adjusted
using the tables provided on the charging procedure stick
er on the unit access panel. Detailed information is given in
the EL16XC1 Installation and Service Procedures manual
(Corp1503-L7), which is available on DaveNet.
IMPORTANT !
Some scroll compressors have an internal vacuum
protector that will unload scrolls when suction pres
sure goes below 20 psig. A hissing sound will be
heard when the compressor is running unloaded.
Protector will reset when low pressure in system is
raised above 40 psig. DO NOT REPLACE COMPRES
SOR.
High Pressure Switch (S4)
This unit is equipped with a high pressure switch which is
located on the liquid line. The SPST, normally closed pres
sure switch opens when liquid line pressure rises above the
factory setting of 590 + 15 psig and automatically resets at
418 + 15 psig.
Homeowner Information
CAUTION
Before attempting to perform any service or mainte
nance, turn the electrical power to unit OFF at dis
connect switch.
WARNING
This product contains a chemical known to the State of
California to cause cancer, birth defects, or other repro
ductive harm.
In order to ensure peak performance, your system must be
properly maintained. Clogged filters and blocked airflow
prevent your unit from operating at its most efficient level.
The system should be inspected and serviced before each
cooling season by a licensed professional HVAC service
technician (or equivalent).
Homeowner Maintenance
The following maintenance may be performed by the
homeowner.
● Contact a licensed professional HVAC technician to
schedule a yearly inspection and maintenance appoint
ment for your equipment.
● Check the indoor unit filter each month and replace the
filter, if necessary.
Have your Lennox dealer show you where your indoor
unit filter is located. It will be either at the indoor unit
(installed internal or external to the cabinet) or behind a
return air grille in the wall or ceiling. Check the filter
monthly and clean or replace it as needed.
Disposable filters should be replaced with a filter of the
same type and size.
● Check the indoor unit drain line for obstructions monthly
during the cooling season.
The indoor evaporator coil is equipped with a drain pan
to collect condensate formed as your system removes
humidity from the inside air. Have your dealer show you
the location of the drain line and how to check for obstruc
tions. (This would also apply to an auxiliary drain, if
installed.)
● Check the area around the outdoor unit monthly and re
move any obstructions that may restrict airflow to the
outdoor unit. This would include grass clippings, leaves,
or papers that may have settled around the unit.
● Trim shrubbery away from the unit and periodically check
for debris which collects around the unit.
● During the winter months, keep the snow level below the
louvered panels.
NOTE- The filter and all access panels must be in place
any time the unit is in operation. If you are unsure about the
filter required for your system, call your Lennox dealer for
assistance.
IMPORTANT !
Sprinklers and soaker hoses should not be installed
where they could cause prolonged exposure to the
outdoor unit by treated water. Prolonged exposure
of the unit to treated water (i.e., sprinkler systems,
soakers, waste water, etc.) will corrode the surface
of steel and aluminum parts, diminish performance
and affect longevity of the unit.
Page 14
EL16XC1 SERIES
Page 15
Thermostat Operation
See the thermostat owner's manual for instructions on how
to operate your thermostat.
Preservice Check
If your system fails to operate, check the following before
calling for service:
●Verify room thermostat settings are correct.
●Verify that all electrical disconnect switches are ON.
●Check for any blown fuses or tripped circuit breakers.
●Verify unit access panels are in place.
●Verify air filter is clean.
●If service is needed, locate and write down the unit
model number and have it handy before calling.
Professional Maintenance
Your heating and air conditioning system should be inspec
ted and maintained twice each year (before the start of the
heating and cooling seasons) by a licensed professional
HVAC technician. You can expect the technician to check
the following items. These checks may only be conduc
ted by a licensed professional HVAC technician.
Outdoor Unit
1 - Inspect component wiring for loose, worn or damaged
connections. Also check for any rubbing or pinching of
wires. Confirm proper voltage plus amperage for out
door unit.
NOTICE !
Failure to follow instructions will cause damage to
the unit.
This unit is equipped with an aluminum coil. Alu
minum coils may be damaged by exposure to solu
tions with a pH below 5 or above 9. The aluminum
coil should be cleaned using potable water at a mod
erate pressure (less than 50psi). If the coil cannot be
cleaned using water alone, Lennox recommends
use of a coil cleaner with a pH in the range of 5 to 9.
The coil must be rinsed thoroughly after cleaning.
In coastal areas, the coil should be cleaned with
potable water several times per year to avoid corro
sive buildup (salt).
Indoor Unit (Air Handler or Furnace)
1 - Inspect component wiring for loose, worn or damaged
connections. Confirm proper voltage plus amperage
for indoor unit.
2 - Inspect and clean or replace air filters in indoor unit.
3 - Check the cleanliness of indoor blower and clean
blower, if necessary.
4 - Inspect the evaporator coil (Indoor) drain pans and
condensate drains for rust, debris, obstructions, leaks
or cracks. Pour water in pans to confirm proper drain
age from the pan through to the outlet of the pipe.
Clean or replace as necessary.
5 - Inspect and clean evaporator (indoor) coil, if neces
sary.
2 - Check the cleanliness of outdoor fan and blade assem
blies. Check condition of fan blades (cracks). Clean or
replace them, if necessary.
3 - Inspect base pan drains for debris and clean as neces
sary.
4 - Inspect the condition of refrigerant piping and confirm
that pipes are not rubbing copper-to-copper. Also,
check the condition of the insulation on the refrigerant
lines. Repair, correct, or replace as necessary.
5 - Test capacitor. Replace as necessary.
6 - Inspect contactor contacts for pitting or burn marks.
Replace as necessary.
7 - Check outdoor fan motor for worn bearings/bushings.
Replace as necessary.
8 - Inspect and clean outdoor coils, if necessary and note
any damage to coils or signs of leakage.
6 - Inspect the condition of the refrigerant lines and con
firm that pipes are not rubbing copper-to-copper. Also,
ensure that refrigerant pipes are not being affected by
indoor air contamination. Check condition of insulation
on the refrigerant lines. Repair, correct, or replace as
necessary.
7 - Inspect the duct system for leaks or other problems.
Repair or replace as necessary.
8 - Check for bearing/bushing wear on indoor blower mo
tor. Replace as necessary.
9 - Indoor unit inspections of gas- or oil-fired furnaces will
also include inspection and cleaning of the burners and
and a full inspection of the gas valve, heat exchanger
and flue (exhaust) system.
General System Test with System Operating
1 - Your technician should perform a general system test.
He will turn on the air conditioner to check operating
functions such as the startup and shutoff operation.
He will also check for unusual noises or odors, and
measure indoor/outdoor temperatures and system
pressures as needed. He will check the refrigerant
charge per the charging sticker information on the out
door unit.
2 - Verify that system total static pressure and airflow set
tings are within specific operating parameters.
3 - Verify correct temperature drop across indoor coil.
Page 15
EL16XC1 SERIES
Page 16
EL16XC1 Start-Up and Performance Checklist
Customer Address
Indoor Unit ModelSerial
Outdoor Unit ModelSerial
Notes:
START UP CHECKS
Refrigerant Type:
Rated Load Amps: Actual AmpsRated Volts
Actual Volts
Condenser Fan Full Load AmpsActual Amps:
COOLING MODE
Suction Pressure: Liquid Pressure:
Supply Air Temperature:Ambient Temperature:Return Air: Temperature:
System Refrigerant Charge (Refer to manufacturer's information on unit or installation instructions for required
subcooling and approach temperatures.)
Subcooling:
A—B=SUBCOOLING
Saturated Condensing Temperature (A)
minus Liquid Line Temperature (B)
Approach:
A—B=APPROACH
Liquid Line Temperature (A)
minus Outdoor Air Temperature (B)
Indoor Coil Temperature Drop (18 to 22°F)
A—B= COIL TEMP DROP
Return Air Temperature (A)
minus Supply Air Temperature (B)
Page 16
EL16XC1 SERIES
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.