Lennox EBVPFPM-B, EBVPFNE-B, EBVSTPM-B, EBVSTNM-B, EBVSTNE-B Installation Instructions Manual

...
Page 1
INSTALLATION INSTRUCTIONS
AVERTISSEMENT : Assurez-vous de bien suivre les instructions données dans cette notice pour réduire au minimum le risque d’incindie ou d’explosion ou pour éviter tout dommage matériel, toute blessure ou la mort.
WARNING: If the information in these instructions is not followed exactly, a fire or explosion may result, causing property damage, personal injury, or death.
WARNING /AVERTISSEMENT/AVISO
HOT GLASS WILL
CAUSE BURNS.
DO NOT TOUCH GLASS
UNTIL COOLED
NEVER ALLOW CHILDREN
TO TOUCH GLASS.
UNE SURFACE VITRÉE CHAUDE
PEUT CAUSER DES BRÛLURES.
LAISSER REFROIDIR LA SURFACE
VITRÉE AVANT D'Y TOUCHER.
NE PERMETTEZ JAMAIS À UN ENFANT
DE TOUCHER LA SURFACE VITRÉE.
EL VIDRIO CALIENTE
CAUSARÁ QUEMADURAS.
USTED DEBE NUNCA
TOCAR EL VIDRIO CALIENTE.
LOS NIÑOS DEBEN NUNCA
TOCAR EL VIDRIO.
- Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
- WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any
phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire
department.
- Installation and service must be performed by a qualified installer, service agency or the gas supplier.
- Ne pas entreposer ni utilizer d’essence ni d’autres vapeurs ou liquides inflammables dans le voisinage de cet appareil ou de tout autre appareil.
- QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ :
• Ne pas tenter d’allumer d’appareil.
• Ne touchez à aucan interrupteur. Ne pas vous servir des
téléphones se trouvant dans le bâtiment où vous trouvez.
• Appelez immédiatement votre fournisseur de gaz depuis
un voisin. Suivez les instructions du fournisseur.
• Si vous ne pouvez rejoindre le fournisseur de gaz,
appelez le service des incindies.
- L’installation et l’entretien doivent être assurés par un installateur ou un service d’entretien qualifié ou par le fournisseur de gaz.
EBVST & EBVPF B-Vent Gas Fireplaces
P/N 850025M Rev. F 04/2013
This manual is one of a set of two supporting this product. Refer to P/N 875026M for Care and Operation Instructions.
Ce manuel est disponible en francais, simplement en faire la demande. Numéro de la pièce 850025CF.
INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.
INSTALLATEUR : Laissez cette notice avec l’appareil. CONSOMMATEUR : Conservez cette notice pour consultation ultérieure.
MODELS
Decorative Product: Not for use as a heating appliance.
NOTICE: Fireplace is not to be operated by a thermostat.
MILLIVOLT:
OTL Report No. 116-F-07A-5
ELECTRONIC:
EBVSTPM-B EBVPFPM-B
Portland
US
EBVSTNE-B EBVPFNE-B
Page 2
TABLE OF CONTENTS
Packaging .........................................Page 2
Introduction ......................................Page 2
General Information ..........................Page 2
Requirements for the Commonwealth of Massachusetts .Page 4
Cold Climate Insulation .....................Page 5
Location ............................................Page 5
Vent Termination Clearances ............Page 6
Appliance and Vent Clearances .........Page 7
Pre-Installation Steps ........................Page 8
Typical Installation Sequence ...........Page 8
Step 1. Framing .................................Page 9
Fireplace Specifications .....................Page 10
Step 2. Routing Gas Line ..................Page 11
Step 3. Install The Venting System ...Page 11
Step 4. Field Wiring .........................Page 12
Step 5. Connecting Gas Line ...........Page 14
Step 6. Outside Air Kit .....................Page 15
Step 7. Verifying Appliance Operation Page 16
Step 8. Installing Logs ...................Page 17
Step 9. Remove/Install Glass Door .Page 20
Step 10. Burner Adjustments ............Page 20
Step 11. Hood Installation .................Page 21
Finishing Requirements ....................Page 21
Step 12. Spillage Test/Safety Switch .Page 22
Step 13. Attaching Safety-in-
Operation Warnings .......................Page 23
Gas Conversion Kits .........................Page 24
Please read and understand these instructions before beginning your
installation.
PACKAGING
The assembled vented gas fireplace is pack­aged with:
1 - One log set located within the firebox. 2 - One plastic bag containing the literature
package, which consists of the care and operation manual, installation instructions, warning labels and warranty, 8 (EBVST), 4 (EBVPF) nailing flanges; plastic bag is located on top of the fireplace.
3 - Two hoods (EBVST), or three hoods (EBVPF)
taped to the top of the fireplace.
4 - One plastic bag of glowing embers, one
plastic bag of decorative volcanic stone and one bag of vermiculite is located in the bottom compartment.
INTRODUCTION
The Millivolt appliances have a millivolt gas control valve with piezo ignition system. If any optional accessories that will require electrical power are to be installed, the electrical power must be provided at the time of appliance installation.
The Electronic appliances are designed to op­erate on natural or propane gas. An electronic intermittent pilot ignition system provides safe, efficient operation. External electrical power is required to operate these units.
These vented gas fireplaces are designed for residential applications. They must be installed with approved type-B, 6" double wall vent pipe systems routed to the outside atmosphere.
GENERAL INFORMATION
WARNING
WARNING
Young children should be care­fully supervised when they are in the same room as the appli­ance. Toddlers, young children and others may be susceptible to accidental contact burns. A physical barrier is recommended if there are at risk individuals in the house. To restrict access to a fireplace or stove, install an adjustable safety gate to keep toddlers, young children and other at risk individuals out of the room and away from hot surfaces.
AVERTISSEMENT
Les jeunes enfants devraient être surveillés étroitement lorsqu’ils se trouvent dans la même pièce que l’appareil. Les tout petits, les jeunes enfants ou les adultes peuvent subir des brûlures s’ils viennent en contact avec la sur­face chaude. Il est recommandé d’installer une barrière physique si des personnes à risques habi­tent la maison. Pour empêcher l’accès à un foyer ou à un poêle, installez une barrière de sécu­rité; cette mesure empêchera les tout petits, les jeunes enfants et toute autre personne à risque d’avoir accès à la pièce et aux surfaces chaudes.
B-Vent appliances are not designed to operate in negatively pressured environments (pres­sure within the home is less than
Children and adults should be alerted to the hazards of high surface temperature and should stay away to avoid burns or clothing ignition.
pressures outside). Significant negatively pressured environ­ments caused by weather, home design, or other devices may impact the operation of these appliances. Negative pres­sures may result in poor flame appearance, sooting, damage to property and/or severe personal injury. Do not operate these appliances in negatively pres-
Les enfants et les adultes devraient être infor­més des dangers que posent les températures de surface élevées et se tenir à distance afin d’éviter des brûlures ou que leurs vêtements ne s’enflamment.
DO NOT ATTEMPT TO ALTER OR MODIFY THE CONSTRUCTION OF THE APPLIANCE OR ITS COMPONENTS. ANY MODIFICATION OR ALTERATION MAY VOID THE WARRANTY, CER­TIFICATION AND LISTINGS OF THIS UNIT.
sured environments.
2
Page 3
WARNING
Improper installation, adjust­ment, alteration, service or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information consult a qualified installer, service agency or the gas supplier.
WARNING
Failure to comply with these installation instructions will result in an improperly installed and operating appliance, voiding its warranty. Any change to this appli­ance and/or its operating controls is dangerous.
WARNING
Clothing or other flammable material should not be placed on or near the appliance.
AVERTISSEMENT
On ne devrait pas placer de vêtements ni d’autres matières inflammables sur l’appareil ni à proximité.
WARNING
Any safety screen or guard removed for servicing the appli­ance must be replaced prior to operating the appliance.
AVERTISSEMENT
Tout écran ou protecteur retiré pour permettre l’entretien de l’appareil doit être remis en place avant de mettre l’appareil en marche.
WARNING
THIS APPLIANCE MAY ONLY BE FITTED WITH DOORS CERTIFIED FOR USE WITH THE APPLIANCE.
WARNING
Failure to position the parts in accordance with these diagrams or failure to use only parts specifically approved with this appliance may result in property damage or personal injury.
AVERTISSEMENT
Risque de dommages ou de blessures si les pièces ne sont pas installées conformément à ces schémas et ou si des pièces autres que celles spécifiquement approuvées avec cet appareil sont utilisées.
Note: Installation and repair should be done by a qualified service person. The appliance should be inspected before use and at least annually by a professional service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etcetera. It is imperative that control compartments, burners and circulating air passageways of the appliance be kept clean.
Remarque: L’installation et la réparation devrait être confiées à un technicien qualifié. L’appareil devrait faire l’objet d’une inspection par un technicien professionnel avant d’être utilisé et au moins une fois l’an par la suite. Des nettoyages plus fréquents peuvent être nécessaires si les tapis, la literie, et cetera produisent une quantité importante de pous­sière. Il est essentiel que les compartiments abritant les commandes, les brûleurs et les conduits de circulation d’air de l’appareil soient tenus propres.
Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
Ne pas utiliser cet appareil s’il a été plongé, même partiellement, dans l’eau. Ap­peler un technicien qualifié pour inspecter l’appareil et remplacer toute partie du système de commande et toute commande qui a été plongée dans l’eau.
Only trim kit(s) supplied by the manufacturer shall be used in the installation of this ap­pliance.
Seules les trousses de garniture fournies par le fabricant doivent être utilisées pour l’installation de cet appareil.
These appliances comply with National Safety Standards and are tested and listed by OMNI-Test Laboratories, Inc. (Report No. 116-F-07A-5) to ANSI Z21.50 (in Canada, CSA-2.22), and CAN/ CGA-2.17-M91 in both USA and Canada, as vented gas fireplaces.
Both millivolt and electronic versions of these appliances may be used in bedrooms (USA only) when the room is an "unconfined space" as defined by the National Fuel Gas Code. Use in bedrooms may not be allowed by your local building codes. You should obtain prior approval from the Authority having jurisdiction prior to installation.
Misc. Codes / Standards -
The Installation must conform to local codes or, in the absence of local codes, with the National
Fuel Gas Code, ANSI Z223.1/NFPA 54 - latest edition (In Canada, the current CAN/CGA-B149.1
installation code). The appliance, when installed, must be electri-
cally grounded and wired in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/NFPA
70 - latest edition, or the Canadian Electrical Code, CSA C22.1 - latest edition.
Provide adequate clearances around air open­ings and adequate accessibility clearance for service and proper operation. Never obstruct the front or back openings of the appliance.
These appliances are designed to operate on natural or propane gas only. The use of other fuels or combination of fuels will degrade the performance of this system and may be dangerous.
These fireplaces are designed as decorative appliances and are not intended for use as area heaters. They must Not be equipped with wall thermostats or remote controls with thermostat functions.
These appliances must not be connected to a chimney or flue serving a separate solid fuel burning appliance.
The appliance area be kept clear and free from combustible materials, gasoline and other flammable vapors and liquids.
Millivolt Models - The millivolt appliances are
manually controlled and feature a spark igniter (piezo) that allows the appliance's pilot gas to be lit without the use of matches or batteries. This system provides continued service in the event of a power outage. A manually-modulated gas valve is stan dard. Flame appearance and heat output can be controlled at the gas valve. The BTU Input for these appliances is shown in Table 1.
Electronic Models - Electronic models have a fixed rate gas valve. Input of electronic models is shown in Table 1.
Input (BTU) Gas Valves (all models)
All Models Fuel Type Input Rate (BTU / HR)
Millivolt Natural 37,500 high - 30,000 low
Millivolt Propane 34,000 high - 27,000 low Electronic Natural 37,500 Electronic Propane 34,000
Table 1
3
Page 4
Gas Pressure - All Models
Tables 2 and 3 show the appliances' inlet and manifold gas pressure requirements:
Inlet Gas Supply Pressure
(all models)
Fuel # Minimum Maximum
Natural Gas
Propane
4.5" WC
(1.12 kPa)
11.0" WC
(2.74 kPa)
10.5" WC
(2.62 kPa)
13.0" WC
(3.24 kPa)
Table 2
Manifold Gas Supply Pressure
(all models)
Fuel # Low High
Natural
Gas
Propane
(Lo) 2.2" WC
(0.55 kPa)
(Lo) 6.3" WC
(1.57 kPa)
(Hi) 3.5" WC
(0.87 kPa)
(Hi) 10.0" WC
(2.49 kPa)
Table 3
Test gauge connections are provided on the front of the millivolt and electronic gas control valve (identified IN for the inlet and OUT for the manifold side). The control valves have a 3/8" (10mm) NPT thread inlet and outlet side of the valve (refer to Figures 1 and 2).
Propane tanks are at pressures that will cause damage to valve components. Verify that the tanks have step down regulators to reduce the pressure to safe levels.
The appliance and its appliance main gas valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psi (3.5 kPa).
The appliance must be isolated from the gas supply piping system by closing its equipment shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psi (3.5 kPa).
Orifice Sizes - Sea Level to High Altitude (All Models)
These appliances are tested and approved for installation at elevations of 0-4500 feet (0-1372 meters) above sea level using the standard burner orifice sizes (marked with an "*" in Table 4). For elevations above 4500 feet, contact your gas supplier or qualified service technician.
Deration - At higher elevations, the amount of BTU fuel value delivered must be reduced by either:
• Usinggasthathasbeenderatedbythegas
company.
• Bychanging theburneroricetoasmaller
size as regulated by the local authorities having jurisdiction and by the (USA) National Fuel Gas Code NFPA 54/ANSI Z223.1 - latest edition or, in Canada, the CAN/CGA-B149.1 codes - latest edition.
Install the appliance according to the regulations of the local authorities having jurisdiction and, in the USA, the National Fuel Gas Code NFPA 54 / ANSI Z223.1 - latest edition or, in Canada, the CAN/CGA-B149.1 - latest edition.
Flame breadth, height and width will diminish 4% for every 1,000 feet of altitude.
In Canada - CAN/CGA-2.17-M91 (R2009) (high altitude): THE CONVERSION SHALL BE CAR­RIED OUT BY A MANUFACTURER’S AUTHO­RIZED REPRESENTATIVE, IN ACCORDANCE WITH THE REQUIREMENTS OF THE MANU­FACTURER, PROVINCIAL OR TERRITORIAL AUTHORITIES HAVING JURISDICTION AND IN ACCORDANCE WITH THE REQUIREMENTS OF THE CAN/CGA-B149.1 OR CAN/CGA-B149.2 INSTALLATION CODES.
Burner Orifice Sizes (all models)
Elevation
Feet (meters)
0-4500
(0-1372)
Table 4
• Part /Cat. Number
Natural
Gas
drill size (inches)
#32 (0.116")
37L82 •
* Standard size installed at factory
*
Propane
Gas
drill size (inches)
#50 (0.070")
H4873 •
*
Gas Valve Diagrams
See Figure 1 for Millivolt models and Figure 2 For Electronic Models.
HI/LO Variable
Flame Height
Adjustment
HTPTHTPT
I
L
O
T
Pilot Adjustment
Screw
Manifold Pressure Tap
P
Inlet Pressure Tap
IN
OUT
I
H
L
O
W
F
F
O
P
I
L
it
O
T
O
N
Main Gas Control Knob
OFF/PILOT/ON
Figure 1 - SIT Millivolt Gas Valve
OFF
ON
ON/OFF Switch
IN
PSI
Inlet Pressure Port
Electronic Gas Control Valve
Manifold Pressure Port
CONTROL
IGNITER
Honeywell Electronic
Figure 2
Gas Valve
REQUIREMENTS FOR THE COMMON­WEALTH OF MASSACHUSETTS
These fireplaces are approved for installation in the US state of Massachusetts if the following additional requirements are met:
• Install this appliance in accordance with
Massachusetts Rules and Regulations 248
C.M.R.
• Installation andrepair must be doneby a
plumber or gas fitter licensed in the Com-
monwealth of Massachusetts.
• The exiblegas line connectorused shall
not exceed 36 inches (92 centimeters) in
length.
• The individualmanual shut-offmustbe a
T-handle type valve.
4
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 5
COLD CLIMATE INSULATION
For cold climate installations, seal all cracks around your appliance with noncombustible material and wherever cold air could enter the room. It is especially important to insulate outside chase cavity between studs and under floor on which appliance rests, if floor is above ground level. Gas line holes and other open­ings should be caulked or stuffed with unfaced fiberglass insulation.
If the fireplace is being installed on a cement slab in cold climates, a sheet of plywood or other raised platform can be placed underneath to prevent cold transfer to the fireplace and into the room. It also helps to sheetrock inside surfaces and tape for maximum air tightness and caulk firestops.
MANUFACTURED HOUSING
B-Vent Fireplaces are not approved for use in OEM or aftermarket manufactured housing built to HUD standards.
LOCATION
In selecting the location, the aesthetic and functional use of the appliance are primary concerns. However, vent system routing to the exterior and access to the fuel supply are also important.
Due to high temperatures, the appliance should be located out of traffic and away from furniture and draperies (Figure 3).
En raison des températures élevées, l’appareil devrait être installé dans un endroit où il y a peu de circulation et loin du mobilier et des tentures (Figure 3).
The location should also be free of electrical, plumbing or other heating/air conditioning ducting.
Be aware that this is a heat producing ap­pliance. Objects placed above the unit are exposed to elevated temperatures.
Vertical Venting
Peninsula
(EBVPF)
Figure 3 - Typical Locations
**See-Through (EBVST)
* See-Through
(EBVST) - one side flush with a wall
Offset Venting
** When the see-through fireplace (EBVST) is installed in the middle of a room, do not extend side walls beyond either viewing side of the fireplace.
* When the see-through fireplace (EBVST) is installed with one side flush with a wall, the opposite wall must not extend beyond either viewing side of the fireplace.
Do not insulate the space between the appli­ance and the area above it.
The appliance must be mounted on a fully sup­ported base extending the full width and depth of the unit. The appliance may be located on or near conventional construction materials. However, if installed on combustible materials, such as carpeting, vinyl tile or other combustible material other than wood flooring, the appliance shall be installed on a metal or wood panel extending the full width and depth of the appliance.
5
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 6
VENT TERMINATION CLEARANCES
These instructions should be used as a guideline and do not supersede local codes in any way. Install venting according to local codes, these instructions, the current National Fuel Gas Code (ANSI-Z223.1) in the USA or the current standards of CAN/CGA-B149.1 in Canada.
Vertical Vent Termination Clearances
Gas Vent Rule – Gas vent caps are not permitted
within 8 ft. (2.4 m) of a vertical wall or similar obstruction. Gas vent caps that are located 8 ft. or more from a portion of a building which extends at an angle greater than 45° upward from the horizontal may terminate in accordance with Figure 4 , provided that in no case shall any discharge opening on the cap be less than 2 ft. (.6 m) horizontally from the roof surface (National Fuel Gas Code ANSI Z223.1 (NFPA
54) (CAN/CGA B149.1).
Multiple Terminations
These appliances may vent adjacent to and at the same level with any other gas appliances (including direct-vent appliances) provided that there is at least 2 ft. (0.6m) between the proximal edges of the vent caps. These appliances may be vented adjacent to a chimney vent servicing a solid fuel fireplace provided the B-vent cap is at least 2 ft. (0.6m) away from the nearest point of the chimney opening.
Vertical Vent Termination Clearances
X
12
Roof Pitch is X/12
Minimum Height from Roof to Lowest Discharge Opening
The vent / air intake termination clearances above the high side of an angled roof is as shown in the following chart:
Figure 4
Termination Heights For Vents
Above Flat Or Sloped Roofs Ref. NFPA 54 / ANSI Z223.1
Roof Pitch * Feet * Meters
Flat to 6/12 1.0 0.3 6/12 to 7/12 1.25 0.38 7/12 to 8/12 1.5 0.46 8/12 to 9/12 2.0 0.61
9/12 to 10/12 2.5 0.76 10/12 to 11/12 3.25 0.99 11/12 to 12/12 4.0 1.22 12/12 to 14/12 5.0 1.52 14/12 to 16/12 6.0 1.83 16/12 to 18/12 7.0 2.13 18/12 to 20/12 7.5 2.29 20/12 to 21/12 8.0 2.44
Multiple Terminations
2 ft.
(0.6m)
Minimum
6
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 7
MINIMUM CLEARANCES TO COMBUSTIBLES
Appliance And Vent Clearances
The appliance is approved with zero clearance to combustible materials on all sides (as detailed in Table 5), with the following exception: When
the unit is installed with one side flush with a wall, the wall on the other side of the unit must not extend beyond the front edge of the unit (see Figure 3).
14 (356)
12 (305)
10 (254)
8 (203)
6 (152)
Mantel Depth
inches (millimeters)
Top of
Appliance
MINIMUM CLEARANCES* Inches (millimeters)
Back and Sides 1/2" (13)
0 (0) from Spacers Or Dimples **
Top Spacers 0 (0)
Floor 0 (0)
From Bottom of Unit To Ceiling 64 (1626)
Vent 3 (76)
Top * / 1 (25.4) Sides & Bottom
SERVICE CLEARANCES Feet (meters)
Front, Back, Sides 3 feet (0.9 meters)
Table 5
*NOTE: 3" (75 mm) above any inclined vent component.
**NOTE: See Page 9, Step 1 and Figure 8 for clearance requirements to the nailing flange located at each side of the unit and any screw
heads adjacent to it.
Hearth Extension - A hearth extension is not required with this appliance.
If a hearth extension is used, do not block the lower control compartment door. Any hearth extension used is for appearance only and does not have to conform to standard hearth extension installation requirements.
Wall Finishes / Surrounds / Mantels
Note: Combustible wall finish materials and/or surround materials must not be allowed to encroach the area defined by the appliance front face (black sheet metal). Never allow combustible materials to be positioned
in front of or overlapping the appliance face (see Figure 6 on Page 7 and Figure 32 on Page 22).
4 (102)
12
(305)
8
10
(203)
(254)
Front or Rear Face
of Appliance
(152)
6
(102)
2
4
(51)
Figure 5 - Minimum Mantel Clearances
Combustible Materials Allowed In Shaded Area Safe Zone
12"
45°
17"
Side Wall
Side Wall
14"
Min. Distance To Unprotected Side Wall
5"
8-1/4"
Top View of
Fireplace
Min. Distance To Protected Side Wall
Figure 6 - Minimum Distance to Unprotected Side Wall
Non-combustible materials, such as surrounds and other appliance trim, may be installed on the appliance face with these exceptions: they must not cover any portion of the removable glass panel or control compartment.
Vertical installation clearances to combustible mantels vary according to the depth of the mantel. See Figure 5. Mantels constructed of non­combustible materials may be installed at any height above the appliance opening; however, do not allow anything to hang below the fireplace hood.
Minimum clearance requirements include any projections such as shelves, window sills, mantels, etc. above the appliance.
Note: We recommend the use of high temperature paint (rated 175° F or higher) on the underside of the mantel.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
7
Page 8
Top Radiant Panel
Top Bustle
Bottom
Bustle
Control Compartment Access Panel
Turn tabs down and secure to the floor with 8d nails or other appropriate fasteners on all sides of the unit which do not have viewing glass panels.
EDVST SHOWN
(EDVPF - NO NAILING FLANGES
ON END WITH GLASS PANEL)
EDVCL SHOWN
(FOR EDVCR VIEW, INTERCHANGE SIDES)
Remove these two screws and use them when installing the nailing flanges.
Nailing Flanges
Note: The nailing flanges, combustible members and screw heads located in areas directly adjacent to the nailing
PRE-INSTALLATION STEPS
Figure 7 - Unit Parts Identication
The appliance is shipped with all gas controls and components installed and pre-wired.
1. Remove the shipping carton.
2. Remove the top radiant panel (refer to Figure 7).
3. Open the control compartment access panel,
by actuating the spring-loaded magnetic catches securing the panel, gently depress­ing the outer top corners of the panel until the catches "pop" the panel free and allowing it to swing out and down to open.
4. Remove the bottom control compart­ment access panel by compressing the spring-loaded hinge pin on the left side until it disengages from the left cabinet panel hole. Pull the panel away from the fireplace.
5. Remove the modesty panel by pulling the bottom right corner of the modesty panel out slightly to disengage the snap-fit fea­ture; lift the modesty panel by the tab on the panel's right end, pull the right end of the panel away from the cabinet and then pull the panel diagonally out of the left side cabinet panel slots. Remove the modesty panel carefully, so that none of the wires become loose or disconnected.
6. Open the latch (located under the firebox floor) securing the glass enclosure panel. Remove the panel by tilting it outward at the bottom and lifting it up. Set the door aside protecting it from inadvertent damage.
See Figure 29 on Page 20.
7. Remove log set box from firebox. Next, remove embers, vermiculite and volcanic stone from control compartment. Handle logs carefully to prevent breakage.
TYPICAL INSTALLATION SEQUENCE
Step 5. (Page 14) Make connection to gas
supply.
The typical sequence of installation is outlined below. However, each installation is unique and may result in variations to the steps described.
See the page numbers references in the follow­ing steps for detailed procedures.
Step 1. (Page 9) Construct the appliance framing. Position the appliance within the framing and secure with nailing brackets and floor anchor tabs.
Step 2. (Page 11) Route gas supply line to appliance location.
Step 3. (Page 11) Install the vent system and exterior termination.
Step 4. (Page 12) Field Wiring
a. Millivolt Appliances – The operating control
switch is factory installed.
Step 6. (Page 15) Install and verify outside air kit operation.
Step 7. (Page 16) Checkout appliance opera­tion.
Step 8. (Page 17) Install the log set, vermicu- lite, volcanic stone and glowing embers.
Step 9. (Page 20) Removing and Installing glass enclosure panels.
Step 10. (Page 20) Adjust burner primary air shutter to achieve proper flame appearance.
Step 11. (Page 21) Install the hoods.
Step 12. (Page 22) Conduct limit switch
spillage test.
Step 13. (Page 23) Attach safety in operation warnings.
b. Electronic Appliances – Connect 120 VAC
electrical power to the appliance receptacle.
(EBVPF - NO NAILING FLANGES ON END WITH GLASS PANEL)
Nailing
Flanges
flanges, are EXEMPT from the 1/2” clearance to combustible requirements for the firebox outer wrapper Combustible framing may be in screw heads and the firebox wrapper in areas adjacent to the nailing flanges. Frame the opening to the exact dimensions specified in the framing details of this manual.
direct contact with the nailing flanges and may be located closer than 1/2” from
EBVST SHOWN
Remove these two screws and use them when installing the nailing flanges.
Turn tabs down and secure to the floor with 8d nails or other appropriate fasteners on all sides of the unit which do not have viewing glass panels.
.
Figure 8 - Nailing Flanges
8
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 9
Step 1. FRAMING
Frame these appliances as illustrated in Figures 9 (EBVST) or 10 (EBVPF). All framing details must allow for a minimum clearance to combus­tible framing members as shown inTable 5 on Page 7. If the appliance is to be elevated above floor level, a solid continuous platform must be constructed. Headers may be in direct contact with the appliance top spacers but must not
be supported by them or notched to fit around them. All construction above the appliance must be self supporting, DO NOT use the appliance for structural support.
Side Nailing Flanges
The fireplace should be secured to the framing at the side(s) and/or rear of the unit using the factory-provided nailing flanges. Install the nailing flanges - 8 (EBVST), 4 (EBVPF) - as shown in Figure 8 using the existing screws.
Position the fireplace within the framing. When required, the flanges may be bent 90 degrees by hand or with the assistance of a hammer. Use wood screws to secure the nailing flanges to the framing. See Table 5 on Page 7 for clear- ances of framing members to cabinet parts in the nailing flange area. The nailing flange itself is exempt from these clearances.
Floor Nailing Tabs
Secure the fireplace to the floor as shown in
Figure 8.
EBVST (See-Through)
inches (millimeters)
Gas Line
Center of gas line
is 3 in. (76 mm)
up from floor.
41-1/2 (1054)
*This dimension can be reduced to 41 inches (1041 mm). This results in 0 in. (0 mm) clearance between framing and unit framing spacers. (The 41-1/2 in. dimension permits easier fireplace installation, if unit is installed after framing is erected.)
**Based on 5/8” drywall. Use 23” for 1/2” drywall.
Minimum Framing Stud size is 2 x 4
6-1/4 (159)
22-3/4**
(578)
*41-1/2
(1054)
Figure 9 - Fireplace Framing Specifications
EBVPF (Peninsula)
inches (millimeters)
Gas Line
Center of gas line
is 3 in. (76 mm)
up from floor.
40-1/8 (1019)
*This dimension can be reduced to 41 inches (1041 mm). This results in 0 in. (0 mm) clearance between framing and unit framing spacers. (The 41-1/2 in. dimension permits easier fireplace installation, if unit is installed after framing is erected.)
**Based on 5/8” drywall. Use 23” for 1/2” drywall.
Minimum Framing Stud size is 2 x 4
6-1/4 (159)
22-3/4**
(578)
*41-1/2
(1054)
Figure 10 - Fireplace Framing Specications
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
9
Page 10
FIREPLACE SPECIFICATIONS
EBVST (See-Through)
DETAIL OF FINISH WALL BRACKET
ELECTRICAL INLETS
GAS INLET
3 (76)
Figure 11
1/2
(13)
6-7/8 (175)
24
(610)
FINISH WALL BRACKET
(Front and back edge of unit top)
FRAMING SPACERS
(Top and Both Sides)
4 (102)
41
(1041)
(940)
4-9/16 (116)
20-1/16
(510)
Inches (millimeters)
A
40-1/8 (1019)
B
12 (305)
A - 6 (152) DIA. FLUE OUTLET B - 8 (203) DIA. FLUE COLLAR
TOP VIEW
3 (76)
2-3/4 (70)
6-7/8 (175)
RIGHT SIDE VIEWLEFT SIDE VIEW
12
(305)
OUTSIDE AIR SHUTTER
ELECTRICAL INLETS
GAS INLET
1/2 (13)
37
40-1/8
(1019)
FRONT VIEW
1/2 (13)
CONTROL COMPARTMENT ACCESS PANEL
4-9/16
(116)
10
Figure 12
EBVPF (Peninsula)
24
(610)
LEFT SIDE VIEW
FINISH WALL BRACKET
(Front, back, and left edge of unit top)
41
(1041)
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
B
A
40-1/8
(1019)
TOP VIEW
FRONT VIEW
20-1/16
(510)
CONTROL COMPARTMENT ACCESS PANEL
1/2
(13)
4 (102)
37
(940)
FRAMING SPACERS (Top and Side)
12 (305)
OUTSIDE AIR SHUTTER
ELECTRICAL INLETS
GAS INLET
3 (76)
Inches (millimeters)
A - 6 (152) DIA. FLUE OUTLET B - 8 (203) DIA. FLUE COLLAR
DETAIL OF
FINISH WALL BRACKET
1/2
(13)
6-7/8 (175)
2-3/4
(70)
12
(305)
RIGHT SIDE VIEW
4-9/16
(116)
Page 11
Step 2. ROUTING GAS LINE
Route a 1/2" (13 mm) gas line to the left side of the appliance as shown in Figure 13. Gas lines must be routed, constructed and made of materials that are in strict accordance with local codes and regulations. All appliances are factory-equipped with a flexible gas line connector and 1/2" shutoff valve. (See Step
5 on Page 14).
Schedule 40
Black Iron Pipe
Inside Diameter (Inches)
Schedule 40 Pipe
Length (feet)
Natural
Gas
0-10 1/2 3/8
10-40 1/2 1/2
40-100 1/2 1/2 100-150 3/4 1/2 150-200 3/4 1/2
Table 6
Propane
Gas
Step 3. INSTALL THE VENT SYSTEM
General Information
These instructions should be used as a guideline and do not supersede local codes in any way. Install venting according to local codes, these instructions, the current National Fuel Gas Code (ANSI-Z223.1) in the USA or the current standards of CAN/CGA-B149.1 in Canada.
Ensure clearances are in accordance with local installation codes and the requirements of the gas supplier.
3"
3-1/8"
(79 mm)
(76)
6-7/8"
5-5/8"
(143 mm)
(175)
Also see Figures 9 through 12
Figure 13 - Route Gas Line
Proper Sizing of Gas Line
Properly size and route the gas supply line from the supply regulator to the area where the appliance is to be installed per requirements outlined in the National Fuel Gas Code, NFPA 54 - latest edition (USA) or CAN/CGA-B149.1
- latest edition (Canada).
Never use galvanized or plastic pipe. Refer to Table 6 for proper sizing of the gas supply line, if black iron pipe is being used. Gas lines must be routed, constructed and made of materials that are in strict accordance with local codes and regulations. We recommend that a qualified individual such as a plumber or gas fitter be hired to correctly size and route the gas supply line to the appliance.
Installing a gas supply line from the fuel supply to the appliance involves numerous considerations of materials, protection, sizing, locations, con­trols, pressure, sediment, and more. Certainly no one unfamiliar and unqualified should attempt sizing or installing gas piping.
Notes:
• All appliancesarefactory-equippedwitha
flexible gas line connector and 1/2" shutoff valve.
• SeeMassachusetts Requirements on Page 4 for additional requirements for installations
in the state of Massachusetts in the USA.
• ThegassupplylineshouldNotbeconnected
to the appliance until Step 5 (Page 14).
• Apipejointcompoundratedforgasshouldbe
used on the threaded joints. Ensure propane resistant compounds are used in propane applications. Be very careful that the pipe
compound does not get inside the pipe.
• It is recommended to install a sediment
trap in the supply line as close as possible to the appliance. Appliances using Propane should have a sediment trap at the base of the tank.
• Check withlocal buildingofcialfor local
code requirements (i.e. are below grade penetrations of the gas line allowed?, etc).
IMPORTANT: If propane is used, be aware that if tank size is too small (i.e. under 100-lbs, if
this is the only gas appliance in the dwelling.
Ref. NPFA 58), there may be loss of pressure,
resulting in insufficient fuel delivery (which can result in sooting, severe delayed ignition
or other malfunctions). Any damage resulting
from an improper installation, such as this, is not covered under the limited warranty.
Dégagement conforme aux codes d'installation locaux et aux exigences du foumisseunde gaz.
These fireplaces must be vented directly to the outside.
The vent system may not service multiple appliances, and must never be connected to a flue serving a solid fuel burning appliance. The vent pipe is tested to be run inside an enclosed wall (such as a chase). There is no requirement for inspection openings in the enclosing wall at any of the joints in the vent pipe.
In the United States, vent installation must conform with local building codes. In the ab­sence of local codes, vents must be installed in accordance with the current edition of the National Fuel Gas Code (ANSI-Z223.1).
In Canada, vent installation must conform with local building codes. In the absence of local codes, vents must be installed in accordance with the current edition of the National Stan­dard of Canada CAN/CGA-B149.1 or B149.2 Installation Code.
This gas fireplace must be vertically vented using listed 6" type-B, double-walled vent pipe and a listed vent termination.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
11
Page 12
10 ft.
Minimum
12 ft.
Minimum
60 degrees
max.
Step 4. FIELD WIRING
H
I
L
O
W
P
I
L
O
T
O
N
ti
O
F
F
IN
OUT
CAUTION
Refer to Section A for millivolt appliances and Section B for electronic appliances. The gas valve is set in place and pre-wired at the factory on both models.
Figure 14
Ground supply lead must be con­nected to the wire attached to the green ground screw located on the outlet box. See
Figure 17. Failure to
do so will result in a potential safety hazard. The appliance must be electrically grounded in accordance with local codes or, in the absence of local codes, the National Electrical Code, ANSI/NFPA 70-latest edition.
(In Canada, the current CSA C22.1 Canadian Electrical Code).
CAUTION: Label all wires prior to disconnec­tion when servicing controls. Wiring errors can cause improper and dangerous operation.
ATTENTION: Au moment de l'entretien des commandes, étiquetez tous les fils avant de les débrancher. Des erreurs de cáblage peu­vent entraîner un fonctionnement inadéquat et dangereux.
Verify proper operation after servicing.
A. Millivolt Wiring (See Figure 16)
Install Optional Control Switch (OFF/ON wall
switch or remote control receiver). Install snap bushing (provided in Electrical Outlet Kit) into control switch knock-out in side panel (see Figures 11,12 and 18). Wire the optional control switch within the millivolt control circuit (as shown in Figure 16) using the 15 feet of 2 conductor wire supplied (route wires through the snap bushing to the optional control switch). Mount the optional control switch in a convenient location on a wall near the fireplace.
CAUTION
Do not connect optional control switch to 120 VAC power supply.
Figure 15
Slip the first 6" (152 mm) section of B-Vent over the fireplace flue outlet and secure with four sheet-metal screws (# 8 or larger), and install the remainder of the B-Vent to the outside. Minimum overall height of the vent system and appliance must be 10' (2.54 m) vertical - no offset (see Figure 14); or 12' (3.7 m) when an offset up to 60 degrees from the vertical is used - this offset may start at the fireplace flue collar (see Figure 15). The maximum overall
height of the vent system and appliance should not exceed 40 feet.
Install the B-vent system in accordance with the vent manufacturer's instructions.
CAUTION: THIS APPLIANCE CANNOT BE VENTED HORIZONTALLY.
Note: Refer to the vent manufacturers instal-
lation instructions for variations of venting techniques. If common venting of several units is contemplated, it should be discussed with an architect and the local Building Department.
Do not place insulation materials within 1" of the gas vent system.
12
S'assurer que l'appareil fonctionne adé­quatement une fois l'entretien terminé.
THERMOPILE
GAS CONTROL VALVE
HIGH LIMIT SWITCH
CONTROL SWITCH*
If any of the original wire as supplied must be replace, it must be replaced with type AWM 105° C - 18 gage wire.
VERIFY PROPER OPERATION AFTER SERVICING.
Schematic Representation Only
* Control Switches: Wall On/Off Switch or Timer, Unit
TERMINALS
T
TP HTP
TH
Mounted On/Off Switch, or Remote Control Switch. If an optional control switch is installed, turn the appliance­mounted ON/OFF burner control switch to the OFF position.
Figure 16 - Millivolt Wiring Diagram
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 13
B. Electronic Wiring (See Figure 19)
0.375"
0.375"
0.25" Ø
NOT FOR USE WITH SOLID FUEL
CAUTION:
Hot while in operation. Do not touch. Severe Burns may result. Keep children, clothing, furniture, gasoline and other liquids having flammable vapors away.
CAUTION:
Do not operate the appliance with factory installed refractory panel(s) removed, cracked or broken. Replacement of the factory installed refractory panel(s) should be completed by a licensed or qualified service person.
WARNING:
Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to the owner’s information manual provided with this appliance. For assistance or additional information consult a qualified installer, service agency or the gas supplier.
Due to high temperatures, keep children, and furniture away.
Keep burner and control compartment clean. See installation and operating instructions accompanying appliance.
WARNING:
Do not connect 120 V AC to the control valve.
THIS APPLIANCE MUST BE INSTALLED IN ACCORDANCE WITH LOCAL CODES, IF ANY; IF NONE, FOLLOW THE NATIONAL FUEL GAS CODE, ANSI Z223.1, OR NATURAL GAS AND PROPANE INSTALLATION CODE, CSA B149.1.
If not installed, and maintained in accordance with the manufacturer's instructions, this product could expose you to substances in fuel or fuel combustion which are known to the state of California to cause cancer, birth defects, or other reproductive harm.
* For a copy of the homeowner’s care and operation manual, go to www.lennox.com or call 1-800-9-lennox.
B-VENTED APPLIANCES NEED FRESH AIR FOR SAFE OPERATION AND MUST BE INSTALLED SO THERE ARE PROVISIONS FOR ADEQUATE COMBUSTION AND VENTILATION AIR.
DIRECT VENTED APPLIANCES MUST NOT BE OPERATED WITHOUT THE FRONT GLASS PANEL(S) INSTALLED.
DO NOT OPERATE APPLIANCE WITH BROKEN, CRACKED OR MISSING GLASS DOORS OR ENCLOSURE PANEL(S).
ELECTRONIC IGNITION WIRING DIAGRAM
Optional Blower**
Junction Box
Break Off Tab
Junction Box
J-Box Wiring
WITH Optional Blower Switch
J-Box Wiring
WITHOUT Optional Blower Switch
BK W
G
CAV 021
BK W
G
CAV 021
Switch, Unit Mounted On/Off Switch, Wall Thermostat (Direct-Vent Units Only) or Remote Control Switch.
Some models are not approved for use with an optional blower. See Care and Operation manual for approved
Schematic Representation Only
W
GR
BK
BK
R
1. If any of the original wire as supplied must be replaced, use Type AWM
2. 120 VAC, 60 Hz - Less than 3 Amps. CAUTION: label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper
0.375"
0.375"
J-Box Wiring
WITHOUT Optional Blower Switch
Note: The electronic appliance must be con­nected to the main 120 VAC power supply.
Ground Wire Connection
1. Locate the Electrical Outlet Kit provided
(packaged in firebox - contents: junction box, 2 screws, receptacle outlet, OFF/ON rocker switch -for millivolt units only, and a snap bushing).
Note: The junction box can be installed in any of the 4 outside corners of the control compartment (outlet installed in front left corner is shown in Figure 18).
2. Route a 3-wire, 120 VAC, 60 Hz, 1 ph power
supply to the location on appliance where junction box is to be installed.
3. Open the control compartment access panel.
4. Wire and install the outlet receptacle to
junction box, then install into the chosen corner of the control compartment as shown in Figures 17, 18 and 19.
5. After the receptacle/junction box wiring is
complete, install the field-provided metal junction box cover plate (see Figure 18).
6. Install the snap bushing (provided in kit) into
the selected cabinet knockout opening in side cabinets (see Figures 11, 12 and 18). The snap bushing provides protection for the wires (see note below) passing through side cabinet going to an optional burner control switch wire in the burner control switch to the low voltage circuit as shown in Figure
19.
Note: The supplied 15 feet of 2 conductor wire
has one end of each conductor connected to the gas valve circuit and the other end of each conductor placed loose on top of the appliance.
Important Note: The gas valve OFF/ON switch is shown in Figure 19. It is integral with the gas valve and should be set to the ON position.
Note: Supply wires may be alternatively con­nected to the outlet using the screw terminals, however the black supply wire must be wired to a terminal that is opposite (across the outlet) the point where the white supply wire is connected.
Figure 17
Remove the carton support from the control compartment before operating the appliance.
WARNING
Electronic models of these appli­ances are equipped with a three­prong (grounding) plug utilized in connecting the electronic components to the junction box in the lower compartment. This grounding plug provides protec­tion against shock hazard and should be plugged directly into the properly grounded three­prong receptacle. DO NOT cut or remove the grounding prong from the plug.
Figure 19
Receptacle, Junction Box
and Cover Plate Installation
Outlet Receptacle
White (supply)
Bipolar
Black (supply)
Terminal Screw
View Of Left Bottom Corner Of Unit
CAUTION
Field-provided Metal Junction Box Cover Plate With Screw
Junction Box knock-out (2 places each side)
Press snap bushing into the knock-out for control switch wires.
Figure 18
OFF/ON Switch
Pilot Burner Assembly
BL
BL
BK
BK = BLACK BL = BLUE R = RED W = WHITE G = GREEN
Control Switch *
DAMPER SWITCH
B-Vent appliances only - one or both of these switches must be factory installed in series as shown. If wires to these switches are replaced, wires must be Type AWM 200°C - 18 gage wire ONLY.
NOTES:
1. If any of the original wire as supplied must be replaced, use Type AWM 105°C - 18 gage wire ONLY.
2. 120 VAC, 60 Hz - Less than 3 Amps. CAUTION: label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and
dangerous operation. Verify proper operation after servicing.
* Control Switches: Wall On/Off Switch or Timer, Unit Mounted On/Off Switch, or Remote Control Switch. If an
optional control switch is installed, turn the appliance-mounted ON/OFF burner control switch to the OFF position.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
(Integral with Gas Valve)
Honeywell Electronic Gas Valve
Igniter Connector
BK
HIGH LIMIT
SWITCH
ELECTRONIC IGNITION WIRING DIAGRAM
24 V
Secondary
GROUND
120 VAC Primary
Field Wired Factory
Wired
R
BK
Transformer
BL
BK
Control Switches: Wall On/Off
*
**
accessories.
NOTES:
105°C - 18 gage wire ONLY.
operation after servicing.
Junction Box
Latching magnet not shown
Fireplace
Side
J-Box Wiring
BK W
Junction Box
Valve Access Side
CAV 021
G
13
Page 14
Gas Stub
1/2" x 3/8" Flare
Shut-Off Valve
3/8" Flex Tubing
3/8" NPT x 3/8"
Flare Fitting
3/8" Nipple
3/8" Union
3/8" Close Nipple
3/8" Shut-Off Valve
1/2" x 3/8"
Reducer
Gas Valve
Optional Gas Flex-Line Connector
STEP 5. CONNECTING GAS LINE
Make gas line connections. All codes require a shut-off valve mounted in the supply line. Figure 20 illustrates two methods for connecting the gas supply. The flex-line method is acceptable in the U.S., however, Canadian requirements vary depending on locality. Installation must be in compliance with local codes.
A sediment trap is recommended in the gas piping within the home to prevent moisture and debris in the line from damaging the valve.
These appliances are equipped with a gas flex line for use (where permitted) in connecting the unit to the gas line. A gas flex line is provided to aid in attaching the appliance to the gas supply. The gas flex line can only be used where local codes permit.
The flex line is rated for both natural and propane gas. A manual shut off valve is also provided with the flex line. The gas control valve is located in the lower control compartment.
To access the valve open the lower control compartment door (see Figure 22 ) by pushing in the right top corner of the door. (The door is hinged at the bottom). Remove the bottom compartment door by sliding the hinge pin, located at the door’s left side, to the right until it disengages from the left corner post hole. Pull the door diagonally to the left, away from the fireplace.
TEST ALL CONNECTIONS FOR GAS LEAKS (FACTORY AND FIELD):
WARNING
Never use an open flame to check for leaks.
Turn on gas supply and test for gas leaks, us­ing a gas leak test solution (also referred to as bubble leak solution).
Note: Using a soapy water solution is an effective leak test solution but it is not recom­mended, because the soap residue that is left on the pipes/fittings can result in corrosion over time.
A. Light the appliance (refer to the lighting
instructions label in the control compartment or in the Care and Operation Instructions manual).
B. Brush all joints and connections with the gas
leak test solution to check for leaks. If bubbles are formed, or gas odor is detected, turn the gas control knob (off/pilot/on) to the “OFF” position. Either tighten or refasten the leaking connection, then retest as described above.
C. When the gas lines are tested and leak free,
be sure to rinse off the leak testing solution.
14
The lower control compartment door on the side opposite the valve lifts on and off.
The millivolt control valve has a 3/8" (10 mm) NPT thread inlet port. The electronic control valve has a 1/2" (13 mm) NPT thread inlet port and is fitted with a 1/2" x 3/8" (13 mm x 10 mm) NPT fitting.
Secure all joints tightly using appropriate tools and sealing compounds (ensure propane resistant compounds are used in propane applications).
All codes require a shut-off valve mounted in the supply line. The orientation of the shut-off valve should face the front. Figure 20 illustrates two methods for connecting the gas supply.
A sediment Trap is recommended to prevent moisture and debris in the gas line for damag­ing the valve.
Figure 20 - GAS CONNECTION
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 15
Step 6. OUTSIDE AIR KITS
Optional outside make-up air kits, Model FOAK-4 or FAOK-4LD, may be used with these appliances. Refer to the installation instructions packaged with the air kits for specific installation information. If used, the outside air kit must be installed before the fireplace is framed and enclosed in the finished wall.
Outside air drawn into the fireplace supplies air to the fire for combustion. Only one outside air duct is necessary, if installed. See the Figures 11 and 12 for the location of the units outside air inlet.
If additional length of duct is necessary, pur­chase locally available U.L. Class 0 or Class 1 metallic ducting. The duct may extend up to 50' (15.24 m) in any direction.
NOTE: When installing the air duct vertically, DO NOT terminate the duct closer than 3' below
the chimney top.
Outside combustion air ducting may be run upwards or vertically through framing and ceil­ing joists, with the hood installed through an outside wall and 3' (1 m) below the termination. Ducting may also be run downward through floor Joists and under the home to a ventilated crawlspace not considered part of the living area of the home.
NOTE: Do not terminate outside air kit in attic space under any circumstances.
CAUTION: NEVER LOCATE INLET WHERE IT CAN BE BLOCKED BY SHRUBS, SNOW DRIFTS, ETC. NEVER LOCATE INLET IN GARAGE OR ANY AREA WHERE THERE IS ANOTHER FUEL BURNING APPLIANCE OR PRODUCTS EMIT­TING COMBUSTIBLE GASES SUCH AS PAINT, GASOLINE, ETC. IN COLD CLIMATES, IT IS RECOMMENDED THE COMBUSTION AIR DUCT BE INSULATED.
After completing the installation of the optional outside air vent system, the outside air control lever must be put in service and tested to ensure proper operation before completing any enclo­sure around the firebox. Failure to do so may result in extensive and costly rework.
Before the operation of the vent system can be tested, the lever securing screw must be removed. See Figure 21.
The hand operated outside air control lever is located on the right side of the fireplace opening. See Figure 21.
To open the outside air shutter, open the bottom control access panel, reach into the gap between the firebox bottom and the modesty panel, and pull the outside air control lever all the way out.
The outside air shutter should be fully open when the fireplace is in use and completely closed when the fireplace is not being used. Closing it when not in use will prevent outside cold air from entering the dwelling.
Operate the actuator through several cycles including the closed position. Ensuring proper operation and freedom of movement. Return the actuator arm to the closed position.
Outside Air Control Lever with Stop Behind
Securing Screw
Outside Air Shutter in the Closed Position
Control Compartment Access Panel
Outside Air Control Lever
and Securing Screw Location
(EBVST and EBVPF Units Shown)
Figure 21
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
15
Page 16
Piezo Igniter
Gas Valve
Modesty Panel
Control Compartment Access panel
ON/OFF Switch
Hinge Pin
MILLIVOLT
Thermocouple
Hood Igniter Rod
3/8" Min (9 mm)
Thermopile
Pilot Nozzels
ELECTRONIC
Proper Flame
Adjustment
Pilot Nozzle
3/8” to 1/2”
(9 mm to 13 mm)
Ground Electrode
Flame Rod
Hot Surface
Igniter
Step 7. VERIFYING APPLIANCE OPERA­TION
Turn on burner and observe the individual tongues of flame on the burner. Make sure all ports are open and producing flame evenly across the burner. If any ports are blocked, or partially blocked, clean out the ports.
With gas line installed run initial system checkout before closing up the front of the unit. Follow the pilot lighting instructions provided in the Care and Operation Instructions manual. For piezo igniter location see Figure
22 (millivolt appliances only).
Figure 23
Note: Lighting Instructions are also found on
the literature tag tied to the gas piping next to the gas valve. To access the tag, open the lower control compartment door (Figure 22) by pushing in simultaneously the left and right top corners of the door. (The door is hinged at the bottom). Remove the bottom compartment door by sliding the hinge pin, located at the door’s left side, to the right until it disengages from the left corner post hole. Remove the modesty panel. To remove the modesty panel, slide the panel forward until it contacts the cabinet bot­tom panel, then lift straight up and tilt forward. Remove the modesty panel carefully, so that none of the wires become loose or disconnected.
When first lighting the appliance, it will take a few minutes for the line to purge itself of air. Once purging is complete, the pilot and burner will light and operate as indicated in the instruc­tion manual.
Subsequent lighting of the appliance will not require such purging. Inspect the pilot flame (re­move logs, if necessary, handling carefully).
Figure 22
Millivolt Appliance Checkout
The pilot flame should be steady, not lifting or floating. Flame should be blue in color with traces of orange at the outer edge.
The top 3/8" (10 mm) at the pilot generator (thermopile) and the top 1/8" minimum (tip) of the quick drop out thermocouple should be engulfed in the pilot flame.
The flame should project 1" (25 mm) beyond the hood at all three ports (see Figure 23). Replace logs if removed for pilot inspection.
To light the burner; turn “ON” the remote wall switch and rotate the gas valve control knob counterclockwise to the “ON” position (“ON” will be at the top side of the valve).
Electronic Appliance Checkout
To light the burner, turn ‘ON’ the unit mounted On/Off switch or the optional remote wall switch. Ensure the igniter lights the pilot. The pilot flame should engulf the flame rod as shown in Figure 24.
Figure 24
16
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 17
Step 8. INSTALL VERMICULITE, GLOWING EMBERS AND LOGS
Glowing Embers
NOTE: Turn off all electricity to the appliance before you install vermiculite, embers and logs. DO NOT attempt to install the logs until the appliance installation has been completed, the gas line connected and tested for leaks and the initial burner operation has been checked out.
INSTALLATION STEPS:
READ WARNINGS ON THIS PAGE BEFORE PROCEEDING. FOLLOW THE LOG PLACEMENT INSTRUCTIONS EXACTLY
1. Remove the front glass enclosure panel (see Glass Enclosure Panel
Removal and Installation Instructions, Page 20).
2. Remove the following from firebox; log set, bag of embers and bag of vermiculite. Handle logs carefully to prevent breakage.
3. Ensure the Grate is properly installed in the firebox with the 4 legs of the grate fitting into the 4 dimples on the firebox floor.
4. Placement of Glowing Embers -
Separate the Embers (rockwool) into pieces about the size of a quarter
(see Figure 25). Keep the pieces fluffed up, not matted. Distribute these pieces over the surface of the burner, as shown in Figure 26. Do not use more than is necessary. Ensure that the main burner ports remain uncovered by the ember material.
5. Place Volcanic Stone - Spread volcanic stone evenly over firebox floor.
6. Install Vermiculite - Place some vermiculite on the firebox floor around the grate (the entire bag of vermiculite will NOT be used). See Figure 26.
DO NOT PLACE ANY VERMICULITE ON THE BURNER.
Note: This appliance is provided with enough Glowing Embers for several applications, do not use all that is in a new bag at one time. For best glowing effect, replace the ember material annually. Replacement Glowing Embers are available (order Catalog Number 88L53).
Figure 25
REFERENCE
Firebox Accessories / Parts
Cat. No. Model No. Description
88L53 FGE Bag of Glowing Embers 80L42 FDVS Bag of Decorative Volcanic Stone H6319 ---- Bag of Vermiculite
Figure 26
WARNING
DO NOT attempt to install the logs until the appli­ance installation has been completed, the gas line connected and tested for leaks and the initial burner operation has been checked out.
The size and position of the log set was engineered
to give the appliance a safe, reliable and attrac­tive flame pattern. Any attempt to use a different log set in the fireplace will void the warranty and will result in incomplete combustion, sooting, and poor flame quality.
Logs get very hot and will remain hot up to one
hour after gas supply is turned off. Handle only when logs are cool. Turn off all electricity to the appliance before you install grate, volcanic stone, vermiculite, embers and logs.
This appliance is not designed to burn wood. Any
attempt to do so could cause irreparable damage to the appliance and prove hazardous to your safety.
If logs are not installed according to the log
installation instructions, flame impingement and improper combustion could occur and result in soot and/or excessive production of carbon monoxide (CO), a colorless, odorless, toxic gas.
17
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 18
EBVPF AND EBVST LOG PLACEMENT
2
STEP 1
6
4
Log Part Number Description Number
1 Log, Corner 55M18 2 Log, Rear/Left 55M19 3 Log, Front/Left 55M20 4 Log, Rear/Right 55M21 5 Log, Front/Center 55M22 6 Log, Center/Top 55M23
Catalog Number for the entire log set: 55M04
3
5
1
STEP 3
Log (3) Lays Over Logs
3
1 And 2
1
Position Groove At The Bottom Of Log (1) Over The Burner Log Support Bracket
Position The Groove At The Bottom Of Log (1) Over The Grate And Slide It Forward Against The Grate Here
Position Log (2) Over The Grate Bar And Slide It Against The Back
STEP 2
2
Of The Grate Here
Position Groove At The Bottom Of Log (2) Over The Grate Here And Slide It Against The Back Of The Grate
Place Bottom Hole Of Log (3) On Pin In Log (2). Position Grooves At The Bottom Of Log (3) Over The Grate.
1
STEP 4
Position And Slide Log (4) Against The Back Of The Grate
4
Place Log (4) Over The Flat Spot On Log (1) Here
18
Figure 27
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 19
EBVPF AND EBVST LOG PLACEMENT (CONTINUED)
Log Part
2
6
4
Number Description Number
1 Log, Corner 55M18 2 Log, Rear/Left 55M19 3 Log, Front/Left 55M20 4 Log, Rear/Right 55M21 5 Log, Front/Center 55M22 6 Log, Center/Top 55M23
Catalog Number for the entire log set: 55M04
STEP 5
Grate
Assembly
3
5
1
Position Small End Of Log (6) On The Notch Of Log (3) Here
3
Position The Groove In The Back Of Log (3) Against The Grate
Position The Round End Of Log (6)
6
5
Against The Notch Of Log (4) Here. Two Charred Spots Face The Front
Log (5) Sits In Front Of The Grate
4
Rest Log (5) Against The Grate Here
Figure 28
19
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 20
Step 9. REMOVING AND INSTALLING THE
Glass Door Latch
Control Compartment Access Panel and Hinge
Front Glass Enclosure Panel
Firebox Floor
Bottom Vee-flange
Glass Door Frame
Top Flange Glass Door Frame
GLASS DOOR
WARNING
Do not attempt to substitute the
materials used on these doors, or replace cracked or broken glass.
• Handle this glass with extreme
care! Glass is susceptible to damage – Do not scratch or handle roughly while reinstall­ing the glass door frame.
• The glass door(s) of this appli­ance must only be replaced as a complete unit as provided by the manufacturer. Do not attempt to replace broken, cracked or chipped glass sepa­rately.
Do not attempt to touch the
front enclosure glass with your hands while the fireplace is in use.
WARNING
Do not operate appliance with the glass front removed, cracked or broken.
AVERTISSEMENT
Ne pas utiliser l'appareil si le panneau frontal en verre n'est pas en place, est craqué ou brisé.
Only doors certified with the appliance shall be used.
Removing Glass Enclosure Panel (see Figure 29)
Remove the top louver assembly or radiant panel.
To access the glass door securing latch, first open the lower control compartment door (Figure 29 ) by pushing in simultaneously the left and right top corners of the door (the door is hinged at the bottom).
Remove the bottom compartment door by sliding the hinge pin, located at the door’s left side, to the right until it disengages from the left corner post hole. Pull the door diagonally to the left, away from the fireplace.
Locate the latch at the top of the control com­partment and disengage them from the door frame bottom vee-flange, pulling down on its handle to open it.
Installing Glass Enclosure Panel (see Figure 29)
Retrieve the glass door. Visually inspect the gasket on the backside of the frame. Gasket surface must be clean, free of irregularities and seated firmly.
Position the door in front of the firebox opening with the bottom of the door held away from the fireplace (Figure 29). Hook the top flange of the door frame over the top of the firebox frame.
Let the bottom of the door frame swing gently in towards the fireplace ensuring that the gasket seats evenly as the door frame draws shut. Fasten the latch located underneath the firebox floor to the door's vee-flange. Close the latch securely.
Step 10. BURNER ADJUSTMENTS
Flame Appearance and sooting
Proper flame appearance is a flame which is blue at the base and becomes yellowish-orange in the body of the flame.
When the appliance is first lit, the entire flame may be blue and will gradually turn yellowish-orange during the first 15 minutes of operation. If the flame remains blue, or if the flame is orange with evidence of sooting (black tip), the air shutter opening may need to be adjusted.
If the air shutter opening is closed too far, sooting may develop. Sooting is indicated by black puffs developing at the tips of very long orange flames. Sooting results in black deposits forming on the logs, appliance inside surfaces and on exterior surfaces adjacent to the vent termination.
Sooting is caused by incomplete combustion in the flames and lack of combustion air enter­ing the air shutter opening. To achieve a warm yellowish-orange flame with an orange body that does not soot, the shutter opening must be adjusted between these two extremes.
Air Shutter Adjustment Guidelines
• Ifthereissmokeorsootpresent,rstcheck
the log set positioning to ensure that the flames are not impinging on any of the logs. If the log set is properly positioned and a sooting condition still exists, then the air shutter opening should be increased.
• Themoreoffsetsintheventsystem,thelarger
the air shutter opening will need to be.
• An applianceoperatedwiththeairshutter
opened too far, may have flames that appear blue and transparent. These weak, blue and transparent flames are termed anemic.
• Propanemodelsmayexhibitameswhich
candle or appear stringy. If this is present and persists, adjust the air shutter to a more closed position, then operate the appliance for a few more minutes to ensure that the flame normalizes and the flames do not appear sooty.
Seules des portes certifiées pour cet appareil doivent être utilisées.
20
WARNING: DO NOT abuse glass door by striking or slamming shut.
These are B-vent appliances. They are designed to operate only when the glass enclosure panels are installed. Generally the glass enclosure panels should not be removed except to gain access to the components within the firebox.
NOTE: When installing the glass door, ensure the spacing on both sides is even and equal.
Figure 29
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
EBVST SHOWN
The following chart is provided to aid you in achieving the correct air shutter adjustment for your installation.
Air Shutter Adjustment Guidelines:
Amount of
Primary Air
If air shutter is closed too far
If air shutter is open too far
Flame
Color
Flame will be orange
Flame will be blue
Air Shutter
Adjustment
Air shutter gap should be increased
Air shutter gap should be decreased
Page 21
Air Shutter
Adjusting
Rod
Orifice
Increase Shutter Opening In This
Direction
Decrease Shutter
Opening In This
Direction
Note - Burners are omitted in this view for clarity.
FG
FG
(1
7)
Burner Adjustment Procedure
WARNING
Air shutter adjustment should
only be performed by a quali­fied professional service tech­nician.
Ensure glass enclosure panels
are in place and sealed during adjustment.
CAUTION
Soot will be produced if the
air shutter is closed too much. Any damage due to sooting, resulting from improperly setting the air shutter, is not covered under the warranty.
The air shutter door and
nearby appliance surfaces are hot. Exercise caution to avoid injury while adjusting flame appearance.
1. Refer to Figure 30 for proper flame ap-
pearance. To adjust the flame, rotate the adjustment rod toward the back or toward the front of the fireplace (rod located in the lower control area). Position the air shutter to the factory setting as shown in the table in Figure 31.
2. Light appliance (follow lighting procedure
on lighting label in control compartment or see the Care and Operation Manual).
3. Allow the burner to operate for at least 15
minutes while observing the flame continu­ously to ensure that the proper flame ap­pearance has been achieved. If the following conditions are present, adjust accordingly.
 • Ifameappearsweakorsooty, adjust
the air shutter, incrementally, to a more open position until the proper flame appearance is achieved.
 • If ame remains blue, adjust the air
shutter, incrementally, to a more closed position until the proper flame appear­ance is achieved.
4. Leave the control knob (off/pilot/on) in the
ON position (millivolt appliances) and the burner OFF/ON switch OFF (and remote switches, if applicable).
Glowing Embers (rockwool)
Figure 30 - Burner Flame Appearance
5. When satisfied that the burner flame ap-
pearance is normal, re-install the lower control compartment door then proceed to finish the installation.
RENRUBNIAM
GNITTESRETTUHSYROTCA
NITTESRETTUHSYROTCAF
GNITTESRETTUHSYROTCA
NITTESRETTUHSYROTCAF
GNITTESRETTUHSYROTCAF
saGlarutaN
sledoM
sehcni )mm(
TSVBE FPVBE
Adjustment Rod Positions (when viewed from above)
61/1)5.1
enaporP
saG
sehcni
)mm(
1(61/
Figure 31
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Step 11. HOOD INSTALLATION
Refer to Figure 32. All of these appliances
must have hoods installed prior to operating.
On all clean face units, slide the hoods into the slots on the lower edges of the radiant panels (Figure 32).
FINISHING REQUIREMENTS
- Wall Details
Complete finished interior wall. To install the appliance facing flush with the finished wall, position framework to accommodate the thick­ness of the finished wall (Figure 32)
See Page 5 for
Cold Climate Insulation and
Page 7 for Clearances
Combustible Wall
Framing
Combustible
Wall Framing
Spacer
Combustible Finished Wall Materials May Touch Top of Unit
Hood must be installed as shown.
Clean Face Models
Figure 32 - Finishing Requirements
This Area Must Remain Clear of Combustible Materials
1" Min (25 mm)
Top of Appliance
Radiant panel
Top of Door Frame
21
Page 22
Step 12. Spillage Test and Safety Limit Switch Operation
Spillage Test
After appliance installation, perform this spillage test to verify that proper venting conditions exist:
1 - Place unit in its normally-operated condi-
tion, that is, with the glass enclosure panels in place.
2 - Close all doors and windows in the room.
Turn on all exhaust fans in the house.
3 - Light the appliance. 4 - Wait 15 minutes. 5 - To check for venting action, start by holding
a smoke producing device within an inch of one edge (side edge, not top or bottom edge) of one glass enclosure panel. The smoke should be drawn toward the edge of the glass enclosure panel. Continue the test by moving the smoke producing device along the entire length of both side-edges of the glass door. Repeat the test for all glass enclosure panels.
6 - If the smoke is not drawn towards the edges
of the glass door turn off the appliance and call a qualified service technician.
Manually-Reset Safety Limit Switch
This appliance is equipped with a manually-reset blocked flue safety limit switch. Refer to Figure 33 for its location. If, during appliance operation, the flame goes out (independently of the burner
on/off wall switch), it may be due to the operation of this safety limit switch. First allow the appli­ance to cool, then reset the safety switch by pushing the red reset button on the back of the switch.
To access the blocked flue safety limit switch refer to Figure 33:
A - To access the blocked flue safety switch when top radiant panel is not covered with non-
combustible material:
1 - Lift up and remove top radiant panel/eyebrow assembly on the control side of unit. 2 - Reach between the cabinet side and the firebox side wall and locate the blocked flue safety
switch.
3 - Push the red reset button on the switch.
The appliance should then relight and remain lit. If this does not occur, turn off the appliance and
call a qualified service technician.
B - To access the blocked flue safety switch when top radiant panel is covered with non-combus-
tible material:
NOTE - This procedure should only be performed by a qualified service technician. Important - Turn electrical power off before beginning this procedure.
1 - Open the lower bottom hinged panel on the control side of the fireplace. Remove the modesty
panel and glass enclosure panel as described on Pages 8 and 20. 2 - Remove the side baffle securing screws (5) and then remove the baffle. 3 - Remove the safety switch bracket securing screws (2), and pull the switch/bracket assembly
through the side panel slot.
4 - Push the red reset button on the switch. 5 - Reinstall the switch/bracket assembly. 6 - Reinstall the side baffle. 7 - Reinstall front glass door. 8 - Raise the bottom hinged panel.
The appliance should then relight and remain lit. If this does not occur, check unit for a blocked flue condition.
SAFETY SWITCH LOCATION (EBVST and EBVPF Safety Switch Location Shown)
FIREBOX SIDE BAFFLE SECURING SCREW
FIREBOX SIDE BAFFLE
MANUALLY-RESET SAFETY LIMIT SWITCH
FIREBOX
SIDE WALL
TOP RADIANT PANEL
AND EYEBROW
BRACKET
SECURING SCREW
SAFETY SWITCH
CABINET
SIDE WALL
Figure 33
22
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 23
STEP 13. ATTACHING SAFETY IN OPERATION WARNINGS It is the installers responsibility to ensure these warnings are properly affixed during installation. These warning labels are a
critical step in informing consumers of safe operation of this appliance.
ATTACHING SAFETY IN OPERATION WARNINGS
It is required that the safety instruction labels fur­nished with the fireplace be affixed to the operation and control point of the fireplace. A safety instruction label must be affixed to the wall switch plate where the fireplace is turned on and off (See Figure A) and if used on the remote control handheld transmitter (Figure B). To properly complete the installation of this fireplace, locate the multi-lingual adhesive labels provided with the Care and Operation Instructions and proceed as follows:
1. Locate the wall switch that controls the fireplace (verify the switch operates the fireplace by turn­ing it on and off). Clean the wall switch plate thoroughly to remove any dust and oils. Affix the label to the surface of the plate of the wall switch that controls the fireplace (Figure A). Choose the language primarily spoken in the home. If unknown, affix the English language label.
2. If a remote control is used to control the fireplace, locate the transmitter and clean it thoroughly to remove any dust and oils. Affix the label to the surface of handheld transmitter (Figure B). Choose the language primarily spoken in the home. If unknown, affix the English language label.
3. If you are unable to locate the labels, please call Lennox Hearth Products or your nearest Lennox Hearth Products dealer to receive additional safety instruction labels free of charge.
Cat. No. H8024 Replacement Label Kit
LENNOX HEARTH PRODUCTS 1-800-655-2008
Note: English is red text on clear label. French and Spanish are white text on black label.
APPOSITION DES MISES EN GARDE RELATIVES À LA SÉCURITÉ D’UTILISATION
Il est impératif que les étiquettes de sécurité fournies avec le foyer soient collées à côté des dispositifs de contrôle du foyer. Une étiquette de sécurité doit être collée sur la plaque de l’interrupteur contrôlant l’allumage du foyer (voir Figure A) et, le cas échéant, sur le boîtier de la télécommande (Figure B). Pour achever l’installation correcte de ce foyer, procédez comme suit avec les étiquettes adhésives en langues étrangères fournies avec les instructions d’utilisation et d’entretien :
1. Repérez l’interrupteur qui contrôle le foyer (vérifiez que l’interrupteur contrôle le fonctionnement du foyer en le faisant basculer de Marche à Arrêt, et vice-versa). Nettoyez soigneusement la plaque murale de l’interrupteur pour éliminer la poussière et les traces de graisse ou d’huile. Collez l’étiquette sur la surface de la plaque de l’interrupteur mural qui contrôle le foyer (Figure A). Choisissez la langue qui est principalement parlée dans la résidence du propriétaire. En cas de doute, collez l’étiquette en anglais.
2. Si une télécommande est utilisée pour contrôler le foyer, nettoyez la soigneusement pour éliminer la poussière et les traces de graisse ou d’huile. Collez l’étiquette sur le boîtier de la télécommande (Figure B). Choisissez la langue qui est principale­ment parlée dans la résidence du propriétaire. En cas de doute, collez l’étiquette en anglais.
3. Si vous ne trouvez pas les étiquettes, veuillez appeler Lennox Hearth Products ou votre distribu­teur Lennox Hearth Products local pour recevoir gratuitement des étiquettes supplémentaires.
Étiquettes de remplacement, n° cat. H8024
LENNOX HEARTH PRODUCTS 1-800-655-2008
Remarque : Le texte anglais est rouge sur un support transparent. Le texte français et espagnol est blanc sur un support noir.
COLOCACIÓN DE ADVERTENCIAS DE SEGURIDAD EN OPERACIÓN
Se requiere que las etiquetas de instrucciones de seguridad incluidas con la chimenea se coloquen en el punto de operación y control de la misma. Se debe colocar una etiqueta de instrucciones de seguridad en la placa del interruptor de pared desde el cual se enciende y se apaga la chimenea (ver la Figura A) y en el transmisor de control remoto (Figura B) si se usa. Para completar correctamente la instalación de esta chimenea, encuentre las etiquetas adhesivas multilingües incluidas con las instrucciones de cuidado y operación y haga lo siguiente:
1. Identifique el interruptor de pared que controla la chimenea (verifique que el interruptor opera la chimenea encendiéndola y apagándola). Limpie bien la placa del interruptor de pared para quitar el polvo y aceite. Pegue la etiqueta en la superficie de la placa del interruptor que controla la chimenea (Figura A). Seleccione el idioma que más se habla en la casa. Si no sabe cuál es, use la etiqueta en inglés.
2. Si se usa un control remoto para controlar la chimenea, encuentre el transmisor y límpielo bien para quitar el polvo y aceite. Pegue la etiqueta en la superficie del transmisor (Figura B). Seleccione el idioma que más se habla en la casa. Si no sabe cuál es, use la etiqueta en inglés.
3. Si no puede encontrar las etiquetas, sírvase llamar a Lennox Hearth Products o al distribuidor de Lennox Hearth Products más cercano para recibir etiquetas de instrucciones de seguridad adicionales gratuitas.
Juego de etiquetas de repuesto - Nº de cat. H8024
LENNOX HEARTH PRODUCTS 1-800-655-2008
Nota: La etiqueta en inglés es transparente con texto rojo. Las etiquetas en francés y español son negras con texto blanco.
SAFETY LABEL
DIAGRAMS
Illustrations are for example only.
Your accessories may be different.
Les illustrations sont par exemple uniquement. Vos accessoires peuvent être différents.
Las ilustraciones son sólo ejemplos. Tu accesorios pueden ser diferentes.
DIAGRAMMES DES ÉTIQUETTES
DE SÉCURITÉ
Figure A
DIAGRAMAS DE ETIQUETAS
DE SEGURIDAD
Figure B
23
Page 24
GAS CONVERSION KITS
WARNING
This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer’s instructions and all applicable codes and requirements of the authority having jurisdiction. If the information in these instruction is not followed exactly, a fire, explosion or production of carbon monoxide may result causing property damage, personal injury or loss of life. The qualified service agency is responsible for the proper installation of this kit. The installation is not proper and complete until the operation of the converted appliance is checked as specified in the manu­facturer’s instructions supplied with the kit. The qualified service agency performing this installation assumes responsibility for this conversion.
AVERTISSEMENT
Cette trousse de conversion doit être installée par un technicien agréé, selon les instructions du fabricant et selon toutes les exigences et tous les codes pertinents de l’autorité compétente. Assurez-vous de bien suivre les instructions dans cette notice pour réduire au minimum le risque d’incendie, d’explosion ou la production de monoxyde de carbone pouvant causer des dommages matériels, des blessures ou la mort. Le tecnicien agréé est responsable de l’installation de cette trousse. L’installation n’est pas adéquate ni complète tant que le bon fonctionnement de l’appareil converti n’a pas été vérifié selon les instructions du fabricant fournies avec la trousse. Le fournisseur de service qualifié ayant réalisé l'installation assume les responsabilités liées à la conversion.
In Canada: THE CONVERSION SHALL BE CARRIED OUT IN ACCORDANCE WITH THE REQUIRE­MENTS OF THE PROVINCIAL AUTHORITIES HAVING JURISDICTION AND IN ACCOR­DANCE WITH THE REQUIREMENTS OF THE CAN/CGA-B149.1 INSTALLATION CODE.
LA CONVERSION DEVRA ÊTRE EFFECTUÉE CONFORMÉMENT AUX RECOMMANDA­TIONS DES AUTORITÉS PROVINCIALES AYANT JURIDICTION ET CONFORMÉMENT AUX EXIGENCES DU CODE D'INSTALLATION CAN/CGA-B149.1.
Gas conversion kits are available to adapt your appliance from the use of one type of gas to the use of another. These kits contain all the necessary components needed to complete the task including labeling that must be affixed to ensure safe operation.
Kit part numbers are listed here and the following steps detail the conversion procedure. Refer to the instructions provided with the conversion kit when performing any gas conversion.
Natural to Propane Gas Conversion Kit
Model No. Unit Type Cat. No.
EBVST / EBVPF
Propane to Natural Gas Conversion Kit
Model No. Unit Type Cat. No.
EBVST / EBVPF
Millivolt H2198
Electronic H2200
Millivolt H2199
Electronic H2201
INSTALLATION INSTRUCTIONS
Step 1. TURN OFF THE GAS SUPPLY TO THE
APPLIANCE and disconnect power supply at the circuit breaker. Ensure appliance is cold.
CAUTION: THE GAS SUPPLY SHALL BE SHUT OFF PRIOR TO DISCONNECTING THE ELECTRICAL POWER, BEFORE PROCEED­ING WITH THE CONVERSION.
ATTENTION: AVANT D’EFFECTUER LA CONVERSION, COUPEZ D’ABORD L’ALIMENTATION EN GAZ, ENSUITE, COUPEZ L’ALIMENTATION ÉLECTRIQUE.
a. Open the control compartment access panel,
by actuating the spring-loaded magnetic catches securing the panel, gently depressing the outer top corners of the panel until the catches "pop" the panel free and allowing it to swing out and down to open.
b. Remove the bottom control compartment ac-
cess panel by compressing the spring-loaded hinge pin on the left side until it disengages from the left cabinet panel hole. Pull the panel away from the fireplace.
c. Remove the modesty panel by pulling the
bottom right corner of the modesty panel out slightly to disengage the snap-fit feature; lift the modesty panel by the tab on the panel's right end, pull the right end of the panel away from the cabinet and then pull the panel diagonally out of the left side cabinet panel slots. Remove the modesty panel carefully, so that none of the wires become loose or disconnected.
24
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 25
d. Locate the latch at the top of the control
FRONT OF FIREPLACE
PAN BURNER
VENTURI TUBE ARM
AIR SHUTTER
ADJUSTMENT LEVER
FIREBOX SUBFLOOR
Spring
Adjusting Screw
Slotted Cap
PSI
OFFION
CONTROL
IGNITE
Manifold Pressure Test Port
Inlet Pressure Test Port
Pressure Regulator
Remove These Components
Retaining
Clip
Igniter Assembly
Pilot Assembly
Pilot Orifice
Flare Nut
compartment. To disengage the latch from the bottom vee-flange of the glass enclosure panel, reach for the handle located towards the back of the latch and pull the handle down toward the front of the unit. See Figure 29 on Page 20.
e. Swing the bottom of the door out and raise
it slightly to lift the top flange of the door frame away from the appliance.
Step 2. Carefully remove the log set. Exercise care as not to break the log set.
Step 3. Referring to Figure 34, remove the
burner.
Figure 35
Step 5. Attach manometer to the manifold side pressure test fitting and verify manifold pressure reads 3.5" water column (0.87 kPa) for natural gas, and 10.0" water column (2.49 kPa) for propane gas.
Step 6. Refer to Figure 36 and remove the pilot hood assembly to access the hexed pilot orifice. Remove and replace the orifice with the one provided with the kit.
Pilot
Orifice
Figure 37
Exercise extreme care to prevent damage to or breakage of the igniter assembly.
Remove the screw securing the pilot assembly to its mounting bracket. Back off the flare nut at the end of the pilot gas line to free the pilot assembly from the gas line. Remove the pilot orifice and replace it with the one provided with the conversion kit. Reinstall the pilot assembly by reversing the steps detailed here.
When reinstalling the igniter assembly, use extreme care to prevent damage and break­age. Do not apply any leverage to the igniter assembly while restoring the retainer clip to its original position.
Millivolt Appliances
Step 4. Refer to Figure 35 and the instruc-
tions provided with the kit. Using a Torx T20, remove and discard the three pressure regulator mounting screws. Remove the pressure regu­lator, spring, poppet, diaphragm and bushing. Discard all removed components. Ensure the rubber gasket installed on the back of the replacement pressure regulator is properly positioned and install the new pressure regula­tor using the new screws supplied with the kit. Tighten screws to 25 in-lbs of torque.
Figure 34
Figure 36
Electronic Appliances
Step 7. Honeywell Electronic Valves - See
Figure 37 and the instructions provided with the kit. Remove the slotted cap screw, o-ring, pressure-regulating adjusting screw and spring. Retain all parts for possible later use. Install new components from the kit. Black cap and red spring for propane gas units. Silver cap and stainless steel spring for natural gas units. Before installing the cap, attach manometer to the manifold side pressure test fitting and adjust screw until pressure reads 3.5" water column (0.87 kPa) for natural gas, and 10.0" water column (2.49 kPa) for propane gas.
See Figure 38 and replace the pilot orifice as follows: Remove the igniter assembly retainer clip, and carefully remove the igniter assembly.
Note: If the igniter is damaged, a replacement kit is available, order Catalog No. 87L54.
Figure 38
All Models
Step 8. (Refer to Figure 34)
A. Remove the orifice from the manifold and
replace it with the one provided in the kit. The following table shows the orifice sizes for natural and propane models. Figure 39 illustrates the orifice. Always check and verify correct orifice size.
25
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 26
B. Install the burner as shown in Figure 40.
BURNER POSITIONING
PAN
BURNER
PILOT ASSEMBLY
Ensure that the arm of the venturi of the burner is hooked onto the air shutter adjustment lever (refer to Figure 34 on Page 25).The primary air opening can be adjusted by rotating the adjustment lever from beneath the firebox floor. Refer to Figure 31 on Page 21 for the recom- mended minimum primary air opening setting.
Figure 39
Step 9. Reassemble the remaining components by reversing the procedures outlined in the preceding steps.
Use pipe joint compound or Teflon tape on all pipe fittings before installing (ensure propane resistant compounds are used in propane ap­plications, do not use pipe joint compounds on flare fittings).
Burner Orifice Sizes (all models)
Elevation
Feet (meters)
0-4500
(0-1372)
Table 7
• Part /Cat. Number
Natural
Gas
drill size (inches)
#32 (0.116")
* Standard size installed at factory
37L82 •
*
Propane
Gas
drill size (inches)
#50 (0.070")
H4873 •
Step 10. Attach the conversion label provided in the conversion kit to the rating plate on the appliance.
Step 11. Turn on gas supply and test for gas
*
leaks.
ALWAYS TEST PRESSURE WITH THE VALVE REGULATOR CONTROL AT THE HIGHEST SETTING
Figure 40
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Lennox Hearth Products reserves the right to make changes at any time, without notice, in design, materials, specifications, prices and also to discontinue colors, styles and products. Consult your local distributor for fireplace code information.
LENNOX®, the LENNOX design, DAVE LENNOX, the image of DAVE LENNOX and other related LENNOX marks are registered or common law trademarks of Lennox Industries Inc. and are used with permission.
Printed in U.S.A. © 2004 Lennox Hearth Products LLC
P/N 850025M REV. F 04/2013
26
1508 Elm Hill Pike, Suite 108 • Nashville, TN 37210
Loading...