AVERTISSEMENT : Assurez-vous de bien suivre les
instructions données dans cette notice pour réduire au
minimum le risque d’incindie ou d’explosion ou pour
éviter tout dommage matériel, toute blessure ou la mort.
WARNING: If the information in these instructions
is not followed exactly, a fire or explosion may
result, causing property damage, personal injury,
or death.
WARNING /AVERTISSEMENT/AVISO
HOT GLASS WILL
CAUSE BURNS.
DO NOT TOUCH GLASS
UNTIL COOLED
NEVER ALLOW CHILDREN
TO TOUCH GLASS.
UNE SURFACE VITRÉE CHAUDE
PEUT CAUSER DES BRÛLURES.
LAISSER REFROIDIR LA SURFACE
VITRÉE AVANT D'Y TOUCHER.
NE PERMETTEZ JAMAIS À UN ENFANT
DE TOUCHER LA SURFACE VITRÉE.
EL VIDRIO CALIENTE
CAUSARÁ QUEMADURAS.
USTED DEBE NUNCA
TOCAR EL VIDRIO CALIENTE.
LOS NIÑOS DEBEN NUNCA
TOCAR EL VIDRIO.
- Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other
appliance.
- WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any
phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
• If you cannot reach your gas supplier, call the fire
department.
- Installation and service must be performed by a
qualified installer, service agency or the gas supplier.
- Ne pas entreposer ni utilizer d’essence ni d’autres vapeurs
ou liquides inflammables dans le voisinage de cet appareil
ou de tout autre appareil.
- QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ :
• Ne pas tenter d’allumer d’appareil.
• Ne touchez à aucan interrupteur. Ne pas vous servir des
téléphones se trouvant dans le bâtiment où vous trouvez.
• Appelez immédiatement votre fournisseur de gaz depuis
un voisin. Suivez les instructions du fournisseur.
• Si vous ne pouvez rejoindre le fournisseur de gaz,
appelez le service des incindies.
- L’installation et l’entretien doivent être assurés par un
installateur ou un service d’entretien qualifié ou par le
fournisseur de gaz.
EBVST & EBVPF
B-Vent Gas Fireplaces
P/N 850025M Rev. F 04/2013
This manual is one of a set of two supporting this product.
Refer to P/N 875026M for Care and Operation Instructions.
Ce manuel est disponible en francais, simplement
en faire la demande. Numéro de la pièce 850025CF.
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future reference.
INSTALLATEUR : Laissez cette notice avec l’appareil.
CONSOMMATEUR : Conservez cette notice pour
consultation ultérieure.
MODELS
EBVSTNM-B
EBVPFNM-B
Decorative Product: Not for use as a heating appliance.
NOTICE: Fireplace is not to be operated by a thermostat.
Gas Conversion Kits .........................Page 24
Please read and understand these
instructions before beginning your
installation.
PACKAGING
The assembled vented gas fireplace is packaged with:
1 - One log set located within the firebox.
2 - One plastic bag containing the literature
package, which consists of the care and
operation manual, installation instructions,
warning labels and warranty, 8 (EBVST), 4
(EBVPF) nailing flanges; plastic bag is located
on top of the fireplace.
3 - Two hoods (EBVST), or three hoods (EBVPF)
taped to the top of the fireplace.
4 - One plastic bag of glowing embers, one
plastic bag of decorative volcanic stone
and one bag of vermiculite is located in the
bottom compartment.
INTRODUCTION
The Millivolt appliances have a millivolt gas
control valve with piezo ignition system. If any
optional accessories that will require electrical
power are to be installed, the electrical power
must be provided at the time of appliance
installation.
The Electronic appliances are designed to operate on natural or propane gas. An electronic
intermittent pilot ignition system provides safe,
efficient operation. External electrical power is
required to operate these units.
These vented gas fireplaces are designed for
residential applications. They must be installed
with approved type-B, 6" double wall vent pipe
systems routed to the outside atmosphere.
GENERAL INFORMATION
WARNING
WARNING
Young children should be carefully supervised when they are
in the same room as the appliance. Toddlers, young children
and others may be susceptible
to accidental contact burns. A
physical barrier is recommended
if there are at risk individuals in
the house. To restrict access to
a fireplace or stove, install an
adjustable safety gate to keep
toddlers, young children and
other at risk individuals out of
the room and away from hot
surfaces.
AVERTISSEMENT
Les jeunes enfants devraient être
surveillés étroitement lorsqu’ils
se trouvent dans la même pièce
que l’appareil. Les tout petits,
les jeunes enfants ou les adultes
peuvent subir des brûlures s’ils
viennent en contact avec la surface chaude. Il est recommandé
d’installer une barrière physique
si des personnes à risques habitent la maison. Pour empêcher
l’accès à un foyer ou à un poêle,
installez une barrière de sécurité; cette mesure empêchera les
tout petits, les jeunes enfants et
toute autre personne à risque
d’avoir accès à la pièce et aux
surfaces chaudes.
B-Vent appliances are not
designed to operate in negatively
pressured environments (pressure within the home is less than
Children and adults should be alerted to the
hazards of high surface temperature and
should stay away to avoid burns or clothing
ignition.
pressures outside). Significant
negatively pressured environments caused by weather, home
design, or other devices may
impact the operation of these
appliances. Negative pressures may result in poor flame
appearance, sooting, damage to
property and/or severe personal
injury. Do not operate these
appliances in negatively pres-
Les enfants et les adultes devraient être informés des dangers que posent les températures
de surface élevées et se tenir à distance afin
d’éviter des brûlures ou que leurs vêtements
ne s’enflamment.
DO NOT ATTEMPT TO ALTER OR MODIFY
THE CONSTRUCTION OF THE APPLIANCE OR
ITS COMPONENTS. ANY MODIFICATION OR
ALTERATION MAY VOID THE WARRANTY, CERTIFICATION AND LISTINGS OF THIS UNIT.
sured environments.
2
Page 3
WARNING
Improper installation, adjustment, alteration, service or
maintenance can cause injury
or property damage. Refer to
this manual. For assistance or
additional information consult
a qualified installer, service
agency or the gas supplier.
WARNING
Failure to comply with these
installation instructions will result
in an improperly installed and
operating appliance, voiding its
warranty. Any change to this appliance and/or its operating controls
is dangerous.
WARNING
Clothing or other flammable
material should not be placed
on or near the appliance.
AVERTISSEMENT
On ne devrait pas placer de
vêtements ni d’autres matières
inflammables sur l’appareil ni à
proximité.
WARNING
Any safety screen or guard
removed for servicing the appliance must be replaced prior to
operating the appliance.
AVERTISSEMENT
Tout écran ou protecteur retiré
pour permettre l’entretien de
l’appareil doit être remis en
place avant de mettre l’appareil
en marche.
WARNING
THIS APPLIANCE MAY ONLY BE FITTED
WITH DOORS CERTIFIED FOR USE
WITH THE APPLIANCE.
WARNING
Failure to position the parts in
accordance with these diagrams
or failure to use only parts
specifically approved with this
appliance may result in property
damage or personal injury.
AVERTISSEMENT
Risque de dommages ou de
blessures si les pièces ne sont
pas installées conformément à
ces schémas et ou si des pièces
autres que celles spécifiquement
approuvées avec cet appareil
sont utilisées.
Note: Installation and repair should be done
by a qualified service person. The appliance
should be inspected before use and at least
annually by a professional service person.
More frequent cleaning may be required due
to excessive lint from carpeting, bedding
material, etcetera. It is imperative that control
compartments, burners and circulating air
passageways of the appliance be kept clean.
Remarque: L’installation et la réparation
devrait être confiées à un technicien qualifié.
L’appareil devrait faire l’objet d’une inspection
par un technicien professionnel avant d’être
utilisé et au moins une fois l’an par la suite.
Des nettoyages plus fréquents peuvent être
nécessaires si les tapis, la literie, et cetera
produisent une quantité importante de poussière. Il est essentiel que les compartiments
abritant les commandes, les brûleurs et les
conduits de circulation d’air de l’appareil
soient tenus propres.
Do not use this appliance if any part has
been under water. Immediately call a
qualified service technician to inspect the
appliance and to replace any part of the
control system and any gas control which
has been under water.
Ne pas utiliser cet appareil s’il a été plongé,
même partiellement, dans l’eau. Appeler un technicien qualifié pour inspecter
l’appareil et remplacer toute partie du
système de commande et toute commande
qui a été plongée dans l’eau.
Only trim kit(s) supplied by the manufacturer
shall be used in the installation of this appliance.
Seules les trousses de garniture fournies
par le fabricant doivent être utilisées pour
l’installation de cet appareil.
These appliances comply with National Safety
Standards and are tested and listed by OMNI-Test
Laboratories, Inc. (Report No. 116-F-07A-5) to
ANSI Z21.50 (in Canada, CSA-2.22), and CAN/
CGA-2.17-M91 in both USA and Canada, as
vented gas fireplaces.
Both millivolt and electronic versions of these
appliances may be used in bedrooms (USA
only) when the room is an "unconfined space"
as defined by the National Fuel Gas Code.
Use in bedrooms may not be allowed by your
local building codes. You should obtain prior
approval from the Authority having jurisdiction
prior to installation.
Misc. Codes / Standards -
The Installation must conform to local codes or,
in the absence of local codes, with the National
Fuel Gas Code, ANSI Z223.1/NFPA 54 - latest
edition (In Canada, the current CAN/CGA-B149.1
installation code).
The appliance, when installed, must be electri-
cally grounded and wired in accordance with
local codes or, in the absence of local codes,
with the National Electrical Code, ANSI/NFPA
70 - latest edition, or the Canadian Electrical
Code, CSA C22.1 - latest edition.
Provide adequate clearances around air openings and adequate accessibility clearance for
service and proper operation. Never obstruct
the front or back openings of the appliance.
These appliances are designed to operate on
natural or propane gas only. The use of other
fuels or combination of fuels will degrade
the performance of this system and may be
dangerous.
These fireplaces are designed as decorative
appliances and are not intended for use as area
heaters. They must Not be equipped with wall
thermostats or remote controls with thermostat
functions.
These appliances must not be connected to a
chimney or flue serving a separate solid fuel
burning appliance.
The appliance area be kept clear and free from
combustible materials, gasoline and other
flammable vapors and liquids.
Millivolt Models - The millivolt appliances are
manually controlled and feature a spark igniter
(piezo) that allows the appliance's pilot gas to
be lit without the use of matches or batteries.
This system provides continued service in the
event of a power outage. A manually-modulated
gas valve is stan dard. Flame appearance and heat
output can be controlled at the gas valve. The BTU
Input for these appliances is shown in Table 1.
Electronic Models - Electronic models have a
fixed rate gas valve. Input of electronic models
is shown in Table 1.
Input (BTU) Gas Valves (all models)
All ModelsFuel TypeInput Rate (BTU / HR)
MillivoltNatural37,500 high - 30,000 low
MillivoltPropane34,000 high - 27,000 low
ElectronicNatural37,500
ElectronicPropane34,000
Table 1
3
Page 4
Gas Pressure - All Models
Tables 2 and 3 show the appliances' inlet and
manifold gas pressure requirements:
Inlet Gas Supply Pressure
(all models)
Fuel #MinimumMaximum
Natural Gas
Propane
4.5" WC
(1.12 kPa)
11.0" WC
(2.74 kPa)
10.5" WC
(2.62 kPa)
13.0" WC
(3.24 kPa)
Table 2
Manifold Gas Supply Pressure
(all models)
Fuel #LowHigh
Natural
Gas
Propane
(Lo) 2.2" WC
(0.55 kPa)
(Lo) 6.3" WC
(1.57 kPa)
(Hi) 3.5" WC
(0.87 kPa)
(Hi) 10.0" WC
(2.49 kPa)
Table 3
Test gauge connections are provided on the
front of the millivolt and electronic gas control
valve (identified IN for the inlet and OUT for the
manifold side). The control valves have a 3/8"
(10mm) NPT thread inlet and outlet side of the
valve (refer to Figures 1 and 2).
Propane tanks are at pressures that will cause
damage to valve components. Verify that the
tanks have step down regulators to reduce the
pressure to safe levels.
The appliance and its appliance main gas
valve must be disconnected from the gas
supply piping system during any pressure
testing of that system at test pressures in
excess of 1/2 psi (3.5 kPa).
The appliance must be isolated from the
gas supply piping system by closing its
equipment shutoff valve during any pressure
testing of the gas supply piping system at
test pressures equal to or less than 1/2 psi
(3.5 kPa).
Orifice Sizes - Sea Level to High Altitude
(All Models)
These appliances are tested and approved for
installation at elevations of 0-4500 feet (0-1372
meters) above sea level using the standard burner
orifice sizes (marked with an "*" in Table 4). For
elevations above 4500 feet, contact your gas
supplier or qualified service technician.
Deration - At higher elevations, the amount
of BTU fuel value delivered must be reduced
by either:
• Usinggasthathasbeenderatedbythegas
company.
• Bychanging theburneroricetoasmaller
size as regulated by the local authorities
having jurisdiction and by the (USA) National
Fuel Gas Code NFPA 54/ANSI Z223.1 - latest
edition or, in Canada, the CAN/CGA-B149.1
codes - latest edition.
Install the appliance according to the regulations
of the local authorities having jurisdiction and,
in the USA, the National Fuel Gas Code NFPA
54 / ANSI Z223.1 - latest edition or, in Canada,
the CAN/CGA-B149.1 - latest edition.
Flame breadth, height and width will diminish
4% for every 1,000 feet of altitude.
In Canada - CAN/CGA-2.17-M91 (R2009) (high
altitude): THE CONVERSION SHALL BE CARRIED OUT BY A MANUFACTURER’S AUTHORIZED REPRESENTATIVE, IN ACCORDANCE
WITH THE REQUIREMENTS OF THE MANUFACTURER, PROVINCIAL OR TERRITORIAL
AUTHORITIES HAVING JURISDICTION AND
IN ACCORDANCE WITH THE REQUIREMENTS
OF THE CAN/CGA-B149.1 OR CAN/CGA-B149.2
INSTALLATION CODES.
Burner Orifice Sizes (all models)
Elevation
Feet (meters)
0-4500
(0-1372)
Table 4
• Part /Cat. Number
Natural
Gas
drill size (inches)
#32 (0.116")
37L82 •
* Standard size installed at factory
*
Propane
Gas
drill size (inches)
#50 (0.070")
H4873 •
*
Gas Valve Diagrams
See Figure 1 for Millivolt models and Figure 2
For Electronic Models.
HI/LO Variable
Flame Height
Adjustment
HTPTHTPT
I
L
O
T
Pilot Adjustment
Screw
Manifold Pressure Tap
P
Inlet Pressure Tap
IN
OUT
I
H
L
O
W
F
F
O
P
I
L
it
O
T
O
N
Main Gas Control Knob
OFF/PILOT/ON
Figure 1 - SIT Millivolt Gas Valve
OFF
ON
ON/OFF Switch
IN
PSI
Inlet
Pressure
Port
Electronic
Gas Control
Valve
Manifold Pressure Port
CONTROL
IGNITER
Honeywell Electronic
Figure 2
Gas Valve
REQUIREMENTS FOR THE COMMONWEALTH OF MASSACHUSETTS
These fireplaces are approved for installation in
the US state of Massachusetts if the following
additional requirements are met:
For cold climate installations, seal all cracks
around your appliance with noncombustible
material and wherever cold air could enter
the room. It is especially important to insulate
outside chase cavity between studs and under
floor on which appliance rests, if floor is above
ground level. Gas line holes and other openings should be caulked or stuffed with unfaced
fiberglass insulation.
If the fireplace is being installed on a cement
slab in cold climates, a sheet of plywood or
other raised platform can be placed underneath
to prevent cold transfer to the fireplace and into
the room. It also helps to sheetrock inside
surfaces and tape for maximum air tightness
and caulk firestops.
MANUFACTURED HOUSING
B-Vent Fireplaces are not approved for use in
OEM or aftermarket manufactured housing built
to HUD standards.
LOCATION
In selecting the location, the aesthetic and
functional use of the appliance are primary
concerns. However, vent system routing to
the exterior and access to the fuel supply are
also important.
Due to high temperatures, the appliance
should be located out of traffic and away from
furniture and draperies (Figure 3).
En raison des températures élevées,
l’appareil devrait être installé dans un endroit
où il y a peu de circulation et loin du mobilier
et des tentures (Figure 3).
The location should also be free of electrical,
plumbing or other heating/air conditioning
ducting.
Be aware that this is a heat producing appliance. Objects placed above the unit are
exposed to elevated temperatures.
Vertical Venting
Peninsula
(EBVPF)
Figure 3 - Typical Locations
**See-Through
(EBVST)
* See-Through
(EBVST) - one
side flush with
a wall
Offset Venting
** When the see-through
fireplace (EBVST) is installed
in the middle of a room, do
not extend side walls beyond
either viewing side of the
fireplace.
* When the see-through
fireplace (EBVST) is installed
with one side flush with a
wall, the opposite wall must
not extend beyond either
viewing side of the fireplace.
Do not insulate the space between the appliance and the area above it.
The appliance must be mounted on a fully supported base extending the full width and depth of
the unit. The appliance may be located on or near
conventional construction materials. However,
if installed on combustible materials, such as
carpeting, vinyl tile or other combustible material
other than wood flooring, the appliance shall be
installed on a metal or wood panel extending the
full width and depth of the appliance.
5
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 6
VENT TERMINATION CLEARANCES
These instructions should be used as a
guideline and do not supersede local codes
in any way. Install venting according to local
codes, these instructions, the current National
Fuel Gas Code (ANSI-Z223.1) in the USA or
the current standards of CAN/CGA-B149.1
in Canada.
Vertical Vent Termination Clearances
Gas Vent Rule – Gas vent caps are not permitted
within 8 ft. (2.4 m) of a vertical wall or similar
obstruction. Gas vent caps that are located 8
ft. or more from a portion of a building which
extends at an angle greater than 45° upward
from the horizontal may terminate in accordance
with Figure 4 , provided that in no case shall
any discharge opening on the cap be less than
2 ft. (.6 m) horizontally from the roof surface
(National Fuel Gas Code ANSI Z223.1 (NFPA
54) (CAN/CGA B149.1).
Multiple Terminations
These appliances may vent adjacent to and at
the same level with any other gas appliances
(including direct-vent appliances) provided that
there is at least 2 ft. (0.6m) between the proximal
edges of the vent caps. These appliances may
be vented adjacent to a chimney vent servicing
a solid fuel fireplace provided the B-vent cap
is at least 2 ft. (0.6m) away from the nearest
point of the chimney opening.
Vertical Vent Termination Clearances
X
12
Roof Pitch is X/12
Minimum Height from Roof
to Lowest Discharge Opening
The vent / air intake termination clearances
above the high side of an angled roof is as
shown in the following chart:
Flat to 6/121.00.3
6/12 to 7/121.250.38
7/12 to 8/121.50.46
8/12 to 9/122.00.61
9/12 to 10/122.50.76
10/12 to 11/123.250.99
11/12 to 12/124.01.22
12/12 to 14/125.01.52
14/12 to 16/126.01.83
16/12 to 18/127.02.13
18/12 to 20/127.52.29
20/12 to 21/128.02.44
Multiple Terminations
2 ft.
(0.6m)
Minimum
6
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 7
MINIMUM CLEARANCES TO COMBUSTIBLES
Appliance And Vent Clearances
The appliance is approved with zero clearance to combustible materials
on all sides (as detailed in Table 5), with the following exception: When
the unit is installed with one side flush with a wall, the wall on the
other side of the unit must not extend beyond the front edge of the
unit (see Figure 3).
14 (356)
12 (305)
10 (254)
8 (203)
6 (152)
Mantel Depth
inches (millimeters)
Top of
Appliance
MINIMUM CLEARANCES* Inches (millimeters)
Back and Sides1/2" (13)
0 (0) from Spacers Or Dimples **
Top Spacers0 (0)
Floor0 (0)
From Bottom of Unit To Ceiling64 (1626)
Vent3 (76)
Top * / 1 (25.4) Sides & Bottom
SERVICE CLEARANCES Feet (meters)
Front, Back, Sides3 feet (0.9 meters)
Table 5
*NOTE: 3" (75 mm) above any inclined vent component.
**NOTE: See Page 9, Step 1 and Figure 8 for clearance requirements
to the nailing flange located at each side of the unit and any screw
heads adjacent to it.
Hearth Extension- A hearth extension is not required with this appliance.
If a hearth extension is used, do not block the lower control compartment
door. Any hearth extension used is for appearance only and does not
have to conform to standard hearth extension installation requirements.
Wall Finishes / Surrounds / Mantels
Note: Combustible wall finish materials and/or surround materials must
not be allowed to encroach the area defined by the appliance front face
(black sheet metal). Never allow combustible materials to be positioned
in front of or overlapping the appliance face (see Figure 6 on Page 7
and Figure 32 on Page 22).
4 (102)
12
(305)
8
10
(203)
(254)
Front or Rear Face
of Appliance
(152)
6
(102)
2
4
(51)
Figure 5 - Minimum Mantel Clearances
Combustible Materials Allowed
In Shaded Area Safe Zone
12"
45°
17"
Side
Wall
Side
Wall
14"
Min. Distance To
Unprotected Side Wall
5"
8-1/4"
Top View of
Fireplace
Min. Distance To
Protected Side Wall
Figure 6 - Minimum Distance to Unprotected Side Wall
Non-combustible materials, such as surrounds and other appliance trim,
may be installed on the appliance face with these exceptions: they must not
cover any portion of the removable glass panel or control compartment.
Vertical installation clearances to combustible mantels vary according
to the depth of the mantel. See Figure 5. Mantels constructed of noncombustible materials may be installed at any height above the appliance
opening; however, do not allow anything to hang below the fireplace hood.
Minimum clearance requirements include any projections such as shelves,
window sills, mantels, etc. above the appliance.
Note: We recommend the use of high temperature paint (rated 175° F
or higher) on the underside of the mantel.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
7
Page 8
Top Radiant
Panel
Top Bustle
Bottom
Bustle
Control
Compartment
Access Panel
Turn tabs down and secure to the floor with8d nails or other appropriate fastenerson all sides of the unit which do not haveviewing glass panels.
EDVST SHOWN
(EDVPF - NO NAILING FLANGES
ON END WITH GLASS PANEL)
EDVCL SHOWN
(FOR EDVCR VIEW, INTERCHANGE SIDES)
Remove these two screws anduse them when installingthe nailing flanges.
Nailing Flanges
Note: The nailing flanges, combustible members and screw heads located in areas directly adjacent to the nailing
PRE-INSTALLATION STEPS
Figure 7 - Unit Parts Identication
The appliance is shipped with all gas controls
and components installed and pre-wired.
1. Remove the shipping carton.
2. Remove the top radiant panel (refer to Figure 7).
3. Open the control compartment access panel,
by actuating the spring-loaded magnetic
catches securing the panel, gently depressing the outer top corners of the panel until
the catches "pop" the panel free and allowing
it to swing out and down to open.
4. Remove the bottom control compartment access panel by compressing the
spring-loaded hinge pin on the left side
until it disengages from the left cabinet
panel hole. Pull the panel away from the
fireplace.
5. Remove the modesty panel by pulling the
bottom right corner of the modesty panel
out slightly to disengage the snap-fit feature; lift the modesty panel by the tab on
the panel's right end, pull the right end of
the panel away from the cabinet and then
pull the panel diagonally out of the left side
cabinet panel slots. Remove the modesty
panel carefully, so that none of the wires
become loose or disconnected.
6. Open the latch (located under the firebox
floor) securing the glass enclosure panel.
Remove the panel by tilting it outward at
the bottom and lifting it up. Set the door
aside protecting it from inadvertent damage.
See Figure 29 on Page 20.
7. Remove log set box from firebox. Next,
remove embers, vermiculite and volcanic
stone from control compartment. Handle
logs carefully to prevent breakage.
TYPICAL INSTALLATION SEQUENCE
Step 5. (Page 14) Make connection to gas
supply.
The typical sequence of installation is outlined
below. However, each installation is unique
and may result in variations to the steps
described.
See the page numbers references in the following steps for detailed procedures.
Step 1. (Page 9) Construct the appliance
framing. Position the appliance within the
framing and secure with nailing brackets and
floor anchor tabs.
Step 2. (Page 11) Route gas supply line to
appliance location.
Step 3. (Page 11) Install the vent system and
exterior termination.
Step 4. (Page 12) Field Wiring
a. Millivolt Appliances – The operating control
switch is factory installed.
Step 6. (Page 15) Install and verify outside
air kit operation.
Step 7. (Page 16) Checkout appliance operation.
Step 8. (Page 17) Install the log set, vermicu-
lite, volcanic stone and glowing embers.
Step 9. (Page 20) Removing and Installing
glass enclosure panels.
Step 10. (Page 20) Adjust burner primary air
shutter to achieve proper flame appearance.
Step 11. (Page 21) Install the hoods.
Step 12. (Page 22) Conduct limit switch
spillage test.
Step 13. (Page 23) Attach safety in operation
warnings.
b. Electronic Appliances – Connect 120 VAC
electrical power to the appliance receptacle.
(EBVPF - NO NAILING FLANGES ON END WITH GLASS PANEL)
Nailing
Flanges
flanges, are EXEMPT from the 1/2” clearance to combustible requirements for the firebox outer wrapper
Combustible framing may be in
screw heads and the firebox wrapper in areas adjacent to the nailing flanges. Frame the opening to the exact
dimensions specified in the framing details of this manual.
direct contact with the nailing flanges and may be located closer than 1/2” from
EBVST SHOWN
Remove these two screws and
use them when installing
the nailing flanges.
Turn tabs down and secure to the floor with
8d nails or other appropriate fasteners on all sides
of the unit which do not have viewing glass panels.
.
Figure 8 - Nailing Flanges
8
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 9
Step 1. FRAMING
Frame these appliances as illustrated in Figures 9 (EBVST) or 10 (EBVPF). All framing details
must allow for a minimum clearance to combustible framing members as shown inTable 5 on Page 7. If the appliance is to be elevated above
floor level, a solid continuous platform must be
constructed. Headers may be in direct contact
with the appliance top spacers but must not
be supported by them or notched to fit around
them. All construction above the appliance must
be self supporting, DO NOT use the appliance for
structural support.
Side Nailing Flanges
The fireplace should be secured to the framing
at the side(s) and/or rear of the unit using the
factory-provided nailing flanges. Install the nailing
flanges - 8 (EBVST), 4 (EBVPF) - as shown in
Figure 8 using the existing screws.
Position the fireplace within the framing. When
required, the flanges may be bent 90 degrees by
hand or with the assistance of a hammer. Use
wood screws to secure the nailing flanges to
the framing. See Table 5 on Page 7 for clear-
ances of framing members to cabinet parts in
the nailing flange area. The nailing flange itself
is exempt from these clearances.
Floor Nailing Tabs
Secure the fireplace to the floor as shown in
Figure 8.
EBVST
(See-Through)
inches (millimeters)
Gas Line
Center of gas line
is 3 in. (76 mm)
up from floor.
41-1/2
(1054)
*This dimension can be reduced to 41 inches (1041 mm). This results in 0 in. (0
mm) clearance between framing and unit framing spacers. (The 41-1/2 in. dimension
permits easier fireplace installation, if unit is installed after framing is erected.)
**Based on 5/8” drywall. Use 23” for 1/2” drywall.
Minimum Framing
Stud size is 2 x 4
6-1/4
(159)
22-3/4**
(578)
*41-1/2
(1054)
Figure 9 - Fireplace Framing Specifications
EBVPF
(Peninsula)
inches (millimeters)
Gas Line
Center of gas line
is 3 in. (76 mm)
up from floor.
40-1/8
(1019)
*This dimension can be reduced to 41 inches (1041 mm). This results in 0 in. (0
mm) clearance between framing and unit framing spacers. (The 41-1/2 in. dimension
permits easier fireplace installation, if unit is installed after framing is erected.)
**Based on 5/8” drywall. Use 23” for 1/2” drywall.
Minimum Framing
Stud size is 2 x 4
6-1/4
(159)
22-3/4**
(578)
*41-1/2
(1054)
Figure 10 - Fireplace Framing Specications
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
9
Page 10
FIREPLACE SPECIFICATIONS
EBVST (See-Through)
DETAIL OF
FINISH WALL BRACKET
ELECTRICAL
INLETS
GAS INLET
3 (76)
Figure 11
1/2
(13)
6-7/8
(175)
24
(610)
FINISH WALL BRACKET
(Front and back edge of unit top)
FRAMING SPACERS
(Top and Both Sides)
4 (102)
41
(1041)
(940)
4-9/16
(116)
20-1/16
(510)
Inches (millimeters)
A
40-1/8
(1019)
B
12 (305)
A - 6 (152) DIA. FLUE OUTLET
B - 8 (203) DIA. FLUE COLLAR
TOP VIEW
3 (76)
2-3/4
(70)
6-7/8
(175)
RIGHT SIDE VIEWLEFT SIDE VIEW
12
(305)
OUTSIDE AIR
SHUTTER
ELECTRICAL
INLETS
GAS INLET
1/2 (13)
37
40-1/8
(1019)
FRONT VIEW
1/2 (13)
CONTROL
COMPARTMENT
ACCESS PANEL
4-9/16
(116)
10
Figure 12
EBVPF (Peninsula)
24
(610)
LEFT SIDE VIEW
FINISH WALL BRACKET
(Front, back, and left edge of unit top)
41
(1041)
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
B
A
40-1/8
(1019)
TOP VIEW
FRONT VIEW
20-1/16
(510)
CONTROL COMPARTMENT
ACCESS PANEL
1/2
(13)
4 (102)
37
(940)
FRAMING SPACERS
(Top and Side)
12 (305)
OUTSIDE AIR
SHUTTER
ELECTRICAL
INLETS
GAS INLET
3 (76)
Inches (millimeters)
A - 6 (152) DIA. FLUE OUTLET
B - 8 (203) DIA. FLUE COLLAR
DETAIL OF
FINISH WALL BRACKET
1/2
(13)
6-7/8
(175)
2-3/4
(70)
12
(305)
RIGHT SIDE VIEW
4-9/16
(116)
Page 11
Step 2. ROUTING GAS LINE
Route a 1/2" (13 mm) gas line to the left side
of the appliance as shown in Figure 13. Gas
lines must be routed, constructed and made
of materials that are in strict accordance with
local codes and regulations. All appliances
are factory-equipped with a flexible gas line
connector and 1/2" shutoff valve. (See Step
5 on Page 14).
Schedule 40
Black Iron Pipe
Inside Diameter (Inches)
Schedule 40 Pipe
Length (feet)
Natural
Gas
0-101/23/8
10-401/21/2
40-1001/21/2
100-1503/41/2
150-2003/41/2
Table 6
Propane
Gas
Step 3. INSTALL THE VENT SYSTEM
General Information
These instructions should be used as a
guideline and do not supersede local codes
in any way. Install venting according to local
codes, these instructions, the current National
Fuel Gas Code (ANSI-Z223.1) in the USA or
the current standards of CAN/CGA-B149.1
in Canada.
Ensure clearances are in accordance with
local installation codes and the requirements
of the gas supplier.
3"
3-1/8"
(79 mm)
(76)
6-7/8"
5-5/8"
(143 mm)
(175)
Also see Figures 9 through 12
Figure 13 - Route Gas Line
Proper Sizing of Gas Line
Properly size and route the gas supply line
from the supply regulator to the area where the
appliance is to be installed per requirements
outlined in the National Fuel Gas Code, NFPA
54 - latest edition (USA) or CAN/CGA-B149.1
- latest edition (Canada).
Never use galvanized or plastic pipe. Refer to
Table 6 for proper sizing of the gas supply line,
if black iron pipe is being used. Gas lines must
be routed, constructed and made of materials
that are in strict accordance with local codes
and regulations. We recommend that a qualified
individual such as a plumber or gas fitter be
hired to correctly size and route the gas supply
line to the appliance.
Installing a gas supply line from the fuel supply to
the appliance involves numerous considerations
of materials, protection, sizing, locations, controls, pressure, sediment, and more. Certainly no
one unfamiliar and unqualified should attempt
sizing or installing gas piping.
Notes:
• All appliancesarefactory-equippedwitha
flexible gas line connector and 1/2" shutoff
valve.
• SeeMassachusetts Requirements on Page
4 for additional requirements for installations
in the state of Massachusetts in the USA.
• ThegassupplylineshouldNotbeconnected
to the appliance until Step 5 (Page 14).
• Apipejointcompoundratedforgasshouldbe
used on the threaded joints. Ensure propane
resistant compounds are used in propane
applications. Be very careful that the pipe
compound does not get inside the pipe.
• It is recommended to install a sediment
trap in the supply line as close as possible
to the appliance. Appliances using Propane
should have a sediment trap at the base of
the tank.
code requirements (i.e. are below grade
penetrations of the gas line allowed?, etc).
IMPORTANT: If propane is used, be aware that
if tank size is too small (i.e. under 100-lbs, if
this is the only gas appliance in the dwelling.
Ref. NPFA 58), there may be loss of pressure,
resulting in insufficient fuel delivery (which
can result in sooting, severe delayed ignition
or other malfunctions). Any damage resulting
from an improper installation, such as this, is
not covered under the limited warranty.
Dégagement conforme aux codes d'installation
locaux et aux exigences du foumisseunde gaz.
These fireplaces must be vented directly
to the outside.
The vent system may not service multiple
appliances, and must never be connected to a
flue serving a solid fuel burning appliance. The
vent pipe is tested to be run inside an enclosed
wall (such as a chase). There is no requirement
for inspection openings in the enclosing wall at
any of the joints in the vent pipe.
In the United States, vent installation must
conform with local building codes. In the absence of local codes, vents must be installed
in accordance with the current edition of the
National Fuel Gas Code (ANSI-Z223.1).
In Canada, vent installation must conform with
local building codes. In the absence of local
codes, vents must be installed in accordance
with the current edition of the National Standard of Canada CAN/CGA-B149.1 or B149.2
Installation Code.
This gas fireplace must be vertically vented
using listed 6" type-B, double-walled vent
pipe and a listed vent termination.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
11
Page 12
10 ft.
Minimum
12 ft.
Minimum
60 degrees
max.
Step 4. FIELD WIRING
H
I
L
O
W
P
I
L
O
T
O
N
ti
O
F
F
IN
OUT
CAUTION
Refer to Section A for millivolt appliances and
Section B for electronic appliances. The gas
valve is set in place and pre-wired at the factory
on both models.
Figure 14
Ground supply lead must be connected to the wire attached to the
green ground screw located on the
outlet box. See
Figure 17. Failure to
do so will result in a potential safety
hazard. The appliance must be
electrically grounded in accordance
with local codes or, in the absence of
local codes, the National Electrical
Code, ANSI/NFPA 70-latest edition.
(In Canada, the current CSA C22.1
Canadian Electrical Code).
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can
cause improper and dangerous operation.
ATTENTION: Au moment de l'entretien des
commandes, étiquetez tous les fils avant de
les débrancher. Des erreurs de cáblage peuvent entraîner un fonctionnement inadéquat
et dangereux.
Verify proper operation after servicing.
A. Millivolt Wiring (See Figure 16)
Install Optional Control Switch (OFF/ON wall
switch or remote control receiver). Install snap
bushing (provided in Electrical Outlet Kit) into
control switch knock-out in side panel (see
Figures 11,12and 18). Wire the optional
control switch within the millivolt control circuit
(as shown in Figure 16) using the 15 feet of 2
conductor wire supplied (route wires through
the snap bushing to the optional control
switch). Mount the optional control switch in a
convenient location on a wall near the fireplace.
CAUTION
Do not connect optional control
switch to 120 VAC power supply.
Figure 15
Slip the first 6" (152 mm) section of B-Vent over
the fireplace flue outlet and secure with four
sheet-metal screws (# 8 or larger), and install
the remainder of the B-Vent to the outside.
Minimum overall height of the vent system and
appliance must be 10' (2.54 m) vertical - no
offset (see Figure 14); or 12' (3.7 m) when
an offset up to 60 degrees from the vertical is
used - this offset may start at the fireplace flue
collar (see Figure 15). The maximum overall
height of the vent system and appliance should
not exceed 40 feet.
Install the B-vent system in accordance with
the vent manufacturer's instructions.
CAUTION: THIS APPLIANCE CANNOT BE
VENTED HORIZONTALLY.
Note: Refer to the vent manufacturers instal-
lation instructions for variations of venting
techniques. If common venting of several units
is contemplated, it should be discussed with an
architect and the local Building Department.
Do not place insulation materials within 1" of
the gas vent system.
12
S'assurer que l'appareil fonctionne adéquatement une fois l'entretien terminé.
THERMOPILE
GAS CONTROL VALVE
HIGH LIMIT SWITCH
CONTROL SWITCH*
If any of the original wire as supplied must be replace, it
must be replaced with type AWM 105° C - 18 gage wire.
VERIFY PROPER OPERATION AFTER SERVICING.
Schematic Representation Only
* Control Switches: Wall On/Off Switch or Timer, Unit
TERMINALS
T
TP HTP
TH
Mounted On/Off Switch, or Remote Control Switch. If an
optional control switch is installed, turn the appliancemounted ON/OFF burner control switch to the OFF position.
Figure 16 - Millivolt Wiring Diagram
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 13
B. Electronic Wiring (See Figure 19)
0.375"
0.375"
0.25" Ø
NOT FOR USE WITH SOLID FUEL
CAUTION:
Hot while in operation. Do nottouch. Severe Burns may result. Keep children, clothing, furniture, gasoline and other liquids having flammablevapors away.
CAUTION:
Do not operate the appliance withfactory installed refractory panel(s) removed, cracked or broken. Replacement of the factory installed refractory panel(s) should be completed by a licensed or qualified service person.
WARNING:
Improper installation, adjustment, alteration, service or maintenance can cause injuryor property damage. Refer to the owner’s informationmanual provided with this appliance. For assistanceor additional information consult a qualified installer,service agency or the gas supplier.
Due to high temperatures, keep children, and furnitureaway.
Keep burner and control compartment clean. Seeinstallation and operating instructions accompanyingappliance.
WARNING:
Do not connect 120 V AC to the control valve.
THIS APPLIANCE MUST BE INSTALLED IN ACCORDANCE WITH LOCAL CODES, IF ANY; IF NONE, FOLLOW THENATIONAL FUEL GAS CODE, ANSI Z223.1, OR NATURAL GAS AND PROPANE INSTALLATION CODE, CSA B149.1.
If not installed, and maintained in accordance with themanufacturer's instructions, this product could exposeyou to substances in fuel or fuel combustion which are known to the state of California to cause cancer, birthdefects, or other reproductive harm.
* For a copy of the homeowner’s care and operationmanual, go to www.lennox.com or call 1-800-9-lennox.
B-VENTED APPLIANCES NEED FRESH AIR FOR SAFEOPERATION AND MUST BE INSTALLED SO THEREARE PROVISIONS FOR ADEQUATE COMBUSTION ANDVENTILATION AIR.
DIRECT VENTED APPLIANCES MUST NOT BE OPERATED WITHOUT THE FRONT GLASS PANEL(S) INSTALLED.
DO NOT OPERATE APPLIANCE WITH BROKEN,CRACKED OR MISSING GLASS DOORS OR ENCLOSURE PANEL(S).
ELECTRONIC IGNITION WIRING DIAGRAM
Optional Blower**
Junction Box
Break Off Tab
Junction Box
J-Box Wiring
WITH Optional Blower Switch
J-Box Wiring
WITHOUT Optional Blower Switch
BKW
G
CAV021
BKW
G
CAV021
Switch, Unit Mounted On/Off Switch, Wall Thermostat (Direct-Vent Units Only) or Remote Control Switch.
Some models are not approved foruse with an optional blower. See Care and Operation manual for approved
Schematic Representation Only
W
GR
BK
BK
R
1. If any of the original wire as supplied must be replaced, use Type AWM
2. 120 VAC, 60 Hz - Less than 3 Amps. CAUTION: label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper
0.375"
0.375"
J-Box Wiring
WITHOUT Optional Blower Switch
Note: The electronic appliance must be connected to the main 120 VAC power supply.
Ground Wire
Connection
1. Locate the Electrical Outlet Kit provided
(packaged in firebox - contents: junction
box, 2 screws, receptacle outlet, OFF/ON
rocker switch -for millivolt units only, and
a snap bushing).
Note: The junction box can be installed in
any of the 4 outside corners of the control
compartment (outlet installed in front left
corner is shown in Figure 18).
2. Route a 3-wire, 120 VAC, 60 Hz, 1 ph power
supply to the location on appliance where
junction box is to be installed.
3. Open the control compartment access panel.
4. Wire and install the outlet receptacle to
junction box, then install into the chosen
corner of the control compartment as shown
in Figures 17, 18 and 19.
5. After the receptacle/junction box wiring is
complete, install the field-provided metal
junction box cover plate (see Figure 18).
6. Install the snap bushing (provided in kit) into
the selected cabinet knockout opening in side
cabinets (see Figures 11, 12and 18). The
snap bushing provides protection for the
wires (see note below) passing through side
cabinet going to an optional burner control
switch wire in the burner control switch to
the low voltage circuit as shown in Figure
19.
Note: The supplied 15 feet of 2 conductor wire
has one end of each conductor connected to
the gas valve circuit and the other end of each
conductor placed loose on top of the appliance.
Important Note: The gas valve OFF/ON switch
is shown in Figure 19. It is integral with the
gas valve and should be set to the ON position.
Note: Supply wires may be alternatively connected to the outlet using the screw terminals,
however the black supply wire must be wired to
a terminal that is opposite (across the outlet) the
point where the white supply wire is connected.
Figure 17
Remove the carton support from
the control compartment before
operating the appliance.
WARNING
Electronic models of these appliances are equipped with a threeprong (grounding) plug utilized
in connecting the electronic
components to the junction box
in the lower compartment. This
grounding plug provides protection against shock hazard and
should be plugged directly into
the properly grounded threeprong receptacle. DO NOT cut
or remove the grounding prong
from the plug.
Figure 19
Receptacle, Junction Box
and Cover Plate Installation
Outlet Receptacle
White
(supply)
Bipolar
Black
(supply)
Terminal
Screw
View Of Left
Bottom Corner Of Unit
CAUTION
Field-provided Metal Junction Box
Cover Plate With Screw
Junction Box
knock-out (2
places each side)
Press snap
bushing into the
knock-out for
control switch
wires.
Figure 18
OFF/ON Switch
Pilot Burner
Assembly
BL
BL
BK
BK = BLACK BL = BLUE
R = RED W = WHITE
G = GREEN
Control
Switch *
DAMPER
SWITCH
B-Vent appliances only - one or both of these switches must
be factory installed in series as shown. If wires to these switches
are replaced, wires must be Type AWM 200°C - 18 gage wire ONLY.
NOTES:
1. If any of the original wire as supplied must be replaced, use Type AWM 105°C - 18 gage wire ONLY.
2. 120 VAC, 60 Hz - Less than 3 Amps.
CAUTION: label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and
dangerous operation. Verify proper operation after servicing.
* Control Switches: Wall On/Off Switch or Timer, Unit Mounted On/Off Switch, or Remote Control Switch. If an
optional control switch is installed, turn the appliance-mounted ON/OFF burner control switch to the OFF position.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
(Integral with
Gas Valve)
Honeywell
Electronic
Gas
Valve
Igniter
Connector
BK
HIGH LIMIT
SWITCH
ELECTRONIC IGNITION WIRING DIAGRAM
24 V
Secondary
GROUND
120 VAC
Primary
Field Wired
Factory
Wired
R
BK
Transformer
BL
BK
Control Switches: Wall On/Off
*
**
accessories.
NOTES:
105°C - 18 gage wire ONLY.
operation after servicing.
Junction Box
Latching magnet
not shown
Fireplace
Side
J-Box Wiring
BK
W
Junction Box
Valve Access Side
CAV 021
G
13
Page 14
Gas
Stub
1/2" x 3/8" Flare
Shut-Off Valve
3/8" Flex Tubing
3/8" NPT x 3/8"
Flare Fitting
3/8" Nipple
3/8" Union
3/8" Close Nipple
3/8" Shut-Off Valve
1/2" x 3/8"
Reducer
Gas
Valve
Optional Gas Flex-Line Connector
STEP 5. CONNECTING GAS LINE
Make gas line connections. All codes require a
shut-off valve mounted in the supply line. Figure 20 illustrates two methods for connecting the
gas supply. The flex-line method is acceptable
in the U.S., however, Canadian requirements
vary depending on locality. Installation must
be in compliance with local codes.
A sediment trap is recommended in the gas
piping within the home to prevent moisture
and debris in the line from damaging the valve.
These appliances are equipped with a gas flex
line for use (where permitted) in connecting the
unit to the gas line. A gas flex line is provided to
aid in attaching the appliance to the gas supply.
The gas flex line can only be used where local
codes permit.
The flex line is rated for both natural and propane
gas. A manual shut off valve is also provided with
the flex line. The gas control valve is located in
the lower control compartment.
To access the valve open the lower control
compartment door (see Figure 22 ) by pushing
in the right top corner of the door. (The door
is hinged at the bottom). Remove the bottom
compartment door by sliding the hinge pin,
located at the door’s left side, to the right until
it disengages from the left corner post hole.
Pull the door diagonally to the left, away from
the fireplace.
TEST ALL CONNECTIONS FOR GAS LEAKS
(FACTORY AND FIELD):
WARNING
Never use an open flame to
check for leaks.
Turn on gas supply and test for gas leaks, using a gas leak test solution (also referred to as
bubble leak solution).
Note: Using a soapy water solution is an
effective leak test solution but it is not recommended, because the soap residue that is left
on the pipes/fittings can result in corrosion
over time.
A. Light the appliance (refer to the lighting
instructions label in the control compartment
or in the Care and Operation Instructions
manual).
B. Brush all joints and connections with the gas
leak test solution to check for leaks. If bubbles
are formed, or gas odor is detected, turn the
gas control knob (off/pilot/on) to the “OFF”
position. Either tighten or refasten the leaking
connection, then retest as described above.
C. When the gas lines are tested and leak free,
be sure to rinse off the leak testing solution.
14
The lower control compartment door on the
side opposite the valve lifts on and off.
The millivolt control valve has a 3/8"
(10 mm) NPT thread inlet port. The electronic
control valve has a 1/2" (13 mm) NPT thread
inlet port and is fitted with a 1/2" x 3/8" (13 mm x
10 mm) NPT fitting.
Secure all joints tightly using appropriate
tools and sealing compounds (ensure propane
resistant compounds are used in propane
applications).
All codes require a shut-off valve mounted in
the supply line. The orientation of the shut-off
valve should face the front. Figure 20 illustrates
two methods for connecting the gas supply.
A sediment Trap is recommended to prevent
moisture and debris in the gas line for damaging the valve.
Figure 20 - GAS CONNECTION
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 15
Step 6. OUTSIDE AIR KITS
Optional outside make-up air kits, Model
FOAK-4 or FAOK-4LD, may be used with these
appliances. Refer to the installation instructions
packaged with the air kits for specific installation
information. If used, the outside air kit must
be installed before the fireplace is framed and
enclosed in the finished wall.
Outside air drawn into the fireplace supplies air
to the fire for combustion. Only one outside air
duct is necessary, if installed. See the Figures 11 and 12 for the location of the units outside
air inlet.
If additional length of duct is necessary, purchase locally available U.L. Class 0 or Class 1
metallic ducting. The duct may extend up to 50'
(15.24 m) in any direction.
NOTE: When installing the air duct vertically,
DO NOT terminate the duct closer than 3' below
the chimney top.
Outside combustion air ducting may be run
upwards or vertically through framing and ceiling joists, with the hood installed through an
outside wall and 3' (1 m) below the termination.
Ducting may also be run downward through
floor Joists and under the home to a ventilated
crawlspace not considered part of the living
area of the home.
NOTE: Do not terminate outside air kit in attic
space under any circumstances.
CAUTION: NEVER LOCATE INLET WHERE IT
CAN BE BLOCKED BY SHRUBS, SNOW DRIFTS,
ETC. NEVER LOCATE INLET IN GARAGE OR
ANY AREA WHERE THERE IS ANOTHER FUEL
BURNING APPLIANCE OR PRODUCTS EMITTING COMBUSTIBLE GASES SUCH AS PAINT,
GASOLINE, ETC. IN COLD CLIMATES, IT IS
RECOMMENDED THE COMBUSTION AIR DUCT
BE INSULATED.
After completing the installation of the optional
outside air vent system, the outside air control
lever must be put in service and tested to ensure
proper operation before completing any enclosure around the firebox. Failure to do so may
result in extensive and costly rework.
Before the operation of the vent system can
be tested, the lever securing screw must be
removed. See Figure 21.
The hand operated outside air control lever
is located on the right side of the fireplace
opening. See Figure 21.
To open the outside air shutter, open the bottom
control access panel, reach into the gap between
the firebox bottom and the modesty panel, and
pull the outside air control lever all the way out.
The outside air shutter should be fully open when
the fireplace is in use and completely closed
when the fireplace is not being used. Closing
it when not in use will prevent outside cold air
from entering the dwelling.
Operate the actuator through several cycles
including the closed position. Ensuring proper
operation and freedom of movement. Return
the actuator arm to the closed position.
Outside Air Control Lever with Stop Behind
Securing Screw
Outside Air Shutter in the
Closed Position
Control Compartment Access Panel
Outside Air Control Lever
and Securing Screw Location
(EBVST and EBVPF Units Shown)
Figure 21
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
15
Page 16
Piezo Igniter
Gas Valve
Modesty Panel
Control
Compartment
Access panel
ON/OFF
Switch
Hinge Pin
MILLIVOLT
Thermocouple
HoodIgniter Rod
3/8" Min
(9 mm)
Thermopile
Pilot
Nozzels
ELECTRONIC
Proper Flame
Adjustment
Pilot
Nozzle
3/8” to 1/2”
(9 mm to 13 mm)
Ground
Electrode
Flame Rod
Hot Surface
Igniter
Step 7. VERIFYING APPLIANCE OPERATION
Turn on burner and observe the individual
tongues of flame on the burner. Make sure
all ports are open and producing flame evenly
across the burner. If any ports are blocked, or
partially blocked, clean out the ports.
With gas line installed run initial system
checkout before closing up the front of the
unit. Follow the pilot lighting instructions
provided in the Care and Operation Instructions
manual. For piezo igniter location see Figure
22 (millivolt appliances only).
Figure 23
Note: Lighting Instructions are also found on
the literature tag tied to the gas piping next
to the gas valve. To access the tag, open the
lower control compartment door (Figure 22) by
pushing in simultaneously the left and right top
corners of the door. (The door is hinged at the
bottom). Remove the bottom compartment door
by sliding the hinge pin, located at the door’s
left side, to the right until it disengages from
the left corner post hole. Remove the modesty
panel. To remove the modesty panel, slide the
panel forward until it contacts the cabinet bottom panel, then lift straight up and tilt forward.
Remove the modesty panel carefully, so that
none of the wires become loose or disconnected.
When first lighting the appliance, it will take a
few minutes for the line to purge itself of air.
Once purging is complete, the pilot and burner
will light and operate as indicated in the instruction manual.
Subsequent lighting of the appliance will not
require such purging. Inspect the pilot flame (remove logs, if necessary, handling carefully).
Figure 22
Millivolt Appliance Checkout
The pilot flame should be steady, not lifting
or floating. Flame should be blue in color with
traces of orange at the outer edge.
The top 3/8" (10 mm) at the pilot generator
(thermopile) and the top 1/8" minimum (tip)
of the quick drop out thermocouple should be
engulfed in the pilot flame.
The flame should project 1" (25 mm) beyond
the hood at all three ports (see Figure 23).
Replace logs if removed for pilot inspection.
To light the burner; turn “ON” the remote wall
switch and rotate the gas valve control knob
counterclockwise to the “ON” position (“ON”
will be at the top side of the valve).
Electronic Appliance Checkout
To light the burner, turn ‘ON’ the unit mounted
On/Off switch or the optional remote wall switch.
Ensure the igniter lights the pilot. The pilot
flame should engulf the flame rod as shown
in Figure 24.
Figure 24
16
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 17
Step 8. INSTALL VERMICULITE, GLOWING EMBERS AND LOGS
Glowing Embers
NOTE: Turn off all electricity to the appliance before you install vermiculite,
embers and logs. DO NOT attempt to install the logs until the appliance
installation has been completed, the gas line connected and tested for
leaks and the initial burner operation has been checked out.
INSTALLATION STEPS:
READ WARNINGS ON THIS PAGE BEFORE PROCEEDING. FOLLOW THE
LOG PLACEMENT INSTRUCTIONS EXACTLY
1. Remove the front glass enclosure panel (see Glass Enclosure Panel
Removal and Installation Instructions, Page 20).
2. Remove the following from firebox; log set, bag of embers and bag
of vermiculite. Handle logs carefully to prevent breakage.
3. Ensure the Grate is properly installed in the firebox with the 4 legs
of the grate fitting into the 4 dimples on the firebox floor.
4.Placement of Glowing Embers -
Separate the Embers (rockwool) into pieces about the size of a quarter
(see Figure 25). Keep the pieces fluffed up, not matted. Distribute
these pieces over the surface of the burner, as shown in Figure 26.
Do not use more than is necessary. Ensure that the main burner ports
remain uncovered by the ember material.
5. Place Volcanic Stone - Spread volcanic stone evenly over firebox
floor.
6. Install Vermiculite - Place some vermiculite on the firebox floor around
the grate (the entire bag of vermiculite will NOT be used). See Figure 26.
DO NOT PLACE ANY VERMICULITE ON THE BURNER.
Note: This appliance is provided with enough Glowing Embers for several
applications, do not use all that is in a new bag at one time. For best
glowing effect, replace the ember material annually. Replacement Glowing
Embers are available (order Catalog Number 88L53).
Figure 25
REFERENCE
Firebox Accessories / Parts
Cat. No.Model No.Description
88L53FGEBag of Glowing Embers
80L42FDVSBag of Decorative Volcanic Stone
H6319----Bag of Vermiculite
Figure 26
WARNING
• DO NOT attempt to install the logs until the appliance installation has been completed, the gas
line connected and tested for leaks and the initial
burner operation has been checked out.
•
The size and position of the log set was engineered
to give the appliance a safe, reliable and attractive flame pattern. Any attempt to use a different
log set in the fireplace will void the warranty and
will result in incomplete combustion, sooting,
and poor flame quality.
•
Logs get very hot and will remain hot up to one
hour after gas supply is turned off. Handle only
when logs are cool. Turn off all electricity to the
appliance before you install grate, volcanic stone,
vermiculite, embers and logs.
•
This appliance is not designed to burn wood. Any
attempt to do so could cause irreparable damage
to the appliance and prove hazardous to your
safety.
•
If logs are not installed according to the log
installation instructions, flame impingement
and improper combustion could occur and result
in soot and/or excessive production of carbon
monoxide (CO), a colorless, odorless, toxic gas.
Position Small End Of Log (6)
On The Notch Of Log (3) Here
3
Position The Groove In The Back
Of Log (3) Against The Grate
Position The Round End Of Log (6)
6
5
Against The Notch Of Log (4) Here.
Two Charred Spots Face The Front
Log (5) Sits In Front
Of The Grate
4
Rest Log (5) Against
The Grate Here
Figure 28
19
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 20
Step 9. REMOVING AND INSTALLING THE
Glass
Door Latch
Control Compartment Access Panel and Hinge
Front Glass
Enclosure Panel
Firebox Floor
Bottom Vee-flange
Glass Door Frame
Top Flange
Glass Door Frame
GLASS DOOR
WARNING
• Do not attempt to substitute the
materials used on these doors,
or replace cracked or broken
glass.
• Handle this glass with extreme
care! Glass is susceptible to
damage – Do not scratch or
handle roughly while reinstalling the glass door frame.
• The glass door(s) of this appliance must only be replaced as
a complete unit as provided
by the manufacturer. Do not
attempt to replace broken,
cracked or chipped glass separately.
• Do not attempt to touch the
front enclosure glass with your
hands while the fireplace is in
use.
WARNING
Do not operate appliance with
the glass front removed, cracked
or broken.
AVERTISSEMENT
Ne pas utiliser l'appareil si le
panneau frontal en verre n'est
pas en place, est craqué ou
brisé.
Only doors certified with the appliance
shall be used.
Removing Glass Enclosure Panel
(see Figure 29)
Remove the top louver assembly or radiant
panel.
To access the glass door securing latch, first
open the lower control compartment door
(Figure 29 ) by pushing in simultaneously the
left and right top corners of the door (the door
is hinged at the bottom).
Remove the bottom compartment door by
sliding the hinge pin, located at the door’s left
side, to the right until it disengages from the
left corner post hole. Pull the door diagonally
to the left, away from the fireplace.
Locate the latch at the top of the control compartment and disengage them from the door
frame bottom vee-flange, pulling down on its
handle to open it.
Installing Glass Enclosure Panel
(see Figure 29)
Retrieve the glass door. Visually inspect the
gasket on the backside of the frame. Gasket
surface must be clean, free of irregularities
and seated firmly.
Position the door in front of the firebox opening
with the bottom of the door held away from the
fireplace (Figure 29). Hook the top flange of the
door frame over the top of the firebox frame.
Let the bottom of the door frame swing gently
in towards the fireplace ensuring that the
gasket seats evenly as the door frame draws
shut. Fasten the latch located underneath the
firebox floor to the door's vee-flange. Close the
latch securely.
Step 10. BURNER ADJUSTMENTS
Flame Appearance and sooting
Proper flame appearance is a flame which is
blue at the base and becomes yellowish-orange
in the body of the flame.
When the appliance is first lit, the entire
flame may be blue and will gradually turn
yellowish-orange during the first 15 minutes
of operation. If the flame remains blue, or if
the flame is orange with evidence of sooting
(black tip), the air shutter opening may need
to be adjusted.
If the air shutter opening is closed too far,
sooting may develop. Sooting is indicated by
black puffs developing at the tips of very long
orange flames. Sooting results in black deposits
forming on the logs, appliance inside surfaces
and on exterior surfaces adjacent to the vent
termination.
Sooting is caused by incomplete combustion
in the flames and lack of combustion air entering the air shutter opening. To achieve a warm
yellowish-orange flame with an orange body
that does not soot, the shutter opening must be
adjusted between these two extremes.
Air Shutter Adjustment Guidelines
• Ifthereissmokeorsootpresent,rstcheck
the log set positioning to ensure that the
flames are not impinging on any of the logs.
If the log set is properly positioned and a
sooting condition still exists, then the air
shutter opening should be increased.
opened too far, may have flames that appear
blue and transparent. These weak, blue and
transparent flames are termed anemic.
• Propanemodelsmayexhibitameswhich
candle or appear stringy. If this is present
and persists, adjust the air shutter to a more
closed position, then operate the appliance
for a few more minutes to ensure that the
flame normalizes and the flames do not
appear sooty.
Seules des portes certifiées pour cet
appareil doivent être utilisées.
20
WARNING: DO NOT abuse glass door by
striking or slamming shut.
These are B-vent appliances. They are designed
to operate only when the glass enclosure panels
are installed. Generally the glass enclosure panels
should not be removed except to gain access to
the components within the firebox.
NOTE: When installing the glass door, ensure the
spacing on both sides is even and equal.
Figure 29
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
EBVST SHOWN
The following chart is provided to aid you in
achieving the correct air shutter adjustment
for your installation.
Air Shutter Adjustment Guidelines:
Amount of
Primary Air
If air shutter is
closed too far
If air shutter is
open too far
Flame
Color
Flame will
be orange
Flame will
be blue
Air Shutter
Adjustment
Air shutter
gap should be
increased
Air shutter
gap should be
decreased
Page 21
Air Shutter
Adjusting
Rod
Orifice
Increase Shutter
Opening In This
Direction
Decrease Shutter
Opening In This
Direction
Note - Burners are omitted in this view for clarity.
FG
FG
(1
7)
Burner Adjustment Procedure
WARNING
• Air shutter adjustment should
only be performed by a qualified professional service technician.
• Ensure glass enclosure panels
are in place and sealed during
adjustment.
CAUTION
• Soot will be produced if the
air shutter is closed too much.
Any damage due to sooting,
resulting from improperly
setting the air shutter, is not
covered under the warranty.
• The air shutter door and
nearby appliance surfaces
are hot. Exercise caution to
avoid injury while adjusting
flame appearance.
1. Refer to Figure 30 for proper flame ap-
pearance. To adjust the flame, rotate the
adjustment rod toward the back or toward
the front of the fireplace (rod located in the
lower control area). Position the air shutter
to the factory setting as shown in the table
in Figure 31.
2. Light appliance (follow lighting procedure
on lighting label in control compartment or
see the Care and Operation Manual).
3. Allow the burner to operate for at least 15
minutes while observing the flame continuously to ensure that the proper flame appearance has been achieved. If the following
conditions are present, adjust accordingly.
• Ifameappearsweakorsooty, adjust
the air shutter, incrementally, to a more
open position until the proper flame
appearance is achieved.
• If ame remains blue, adjust the air
shutter, incrementally, to a more closed
position until the proper flame appearance is achieved.
4. Leave the control knob (off/pilot/on) in the
ON position (millivolt appliances) and the
burner OFF/ON switch OFF (and remote
switches, if applicable).
Glowing Embers (rockwool)
Figure 30 - Burner Flame Appearance
5. When satisfied that the burner flame ap-
pearance is normal, re-install the lower
control compartment door then proceed
to finish the installation.
RENRUBNIAM
GNITTESRETTUHSYROTCA
NITTESRETTUHSYROTCAF
GNITTESRETTUHSYROTCA
NITTESRETTUHSYROTCAF
GNITTESRETTUHSYROTCAF
saGlarutaN
sledoM
sehcni
)mm(
TSVBE
FPVBE
Adjustment Rod Positions (when viewed from above)
61/1)5.1
enaporP
saG
sehcni
)mm(
1(61/
Figure 31
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Step 11.HOOD INSTALLATION
Refer to Figure 32. All of these appliances
must have hoods installed prior to operating.
On all clean face units, slide the hoods into
the slots on the lower edges of the radiant
panels (Figure 32).
FINISHING REQUIREMENTS
- Wall Details
Complete finished interior wall. To install the
appliance facing flush with the finished wall,
position framework to accommodate the thickness of the finished wall (Figure 32)
See Page 5 for
Cold Climate Insulation and
Page 7 for Clearances
Combustible Wall
Framing
Combustible
Wall Framing
Spacer
Combustible
Finished Wall
Materials May
Touch Top of
Unit
Hood must be installed as shown.
Clean Face Models
Figure 32 - Finishing Requirements
This Area Must Remain Clear
of Combustible Materials
1" Min
(25 mm)
Top of Appliance
Radiant panel
Top of Door Frame
21
Page 22
Step 12. Spillage Test and Safety Limit
Switch Operation
Spillage Test
After appliance installation, perform this spillage
test to verify that proper venting conditions exist:
1 - Place unit in its normally-operated condi-
tion, that is, with the glass enclosure panels
in place.
2 - Close all doors and windows in the room.
Turn on all exhaust fans in the house.
3 - Light the appliance.
4 - Wait 15 minutes.
5 - To check for venting action, start by holding
a smoke producing device within an inch
of one edge (side edge, not top or bottom
edge) of one glass enclosure panel. The
smoke should be drawn toward the edge
of the glass enclosure panel. Continue the
test by moving the smoke producing device
along the entire length of both side-edges of
the glass door. Repeat the test for all glass
enclosure panels.
6 - If the smoke is not drawn towards the edges
of the glass door turn off the appliance and
call a qualified service technician.
Manually-Reset Safety Limit Switch
This appliance is equipped with a manually-reset blocked flue safety limit switch. Refer to Figure
33 for its location. If, during appliance operation, the flame goes out (independently of the burner
on/off wall switch), it may be due to the operation of this safety limit switch. First allow the appliance to cool, then reset the safety switch by pushing the red reset button on the back of the switch.
To access the blocked flue safety limit switch refer to Figure 33:
A - To access the blocked flue safety switch when top radiant panel is not covered with non-
combustible material:
1 - Lift up and remove top radiant panel/eyebrow assembly on the control side of unit.
2 - Reach between the cabinet side and the firebox side wall and locate the blocked flue safety
switch.
3 - Push the red reset button on the switch.
The appliance should then relight and remain lit. If this does not occur, turn off the appliance and
call a qualified service technician.
B - To access the blocked flue safety switch when top radiant panel is covered with non-combus-
tible material:
NOTE - This procedure should only be performed by a qualified service technician.
Important - Turn electrical power off before beginning this procedure.
1 - Open the lower bottom hinged panel on the control side of the fireplace. Remove the modesty
panel and glass enclosure panel as described on Pages 8 and20.
2 - Remove the side baffle securing screws (5) and then remove the baffle.
3 - Remove the safety switch bracket securing screws (2), and pull the switch/bracket assembly
through the side panel slot.
4 - Push the red reset button on the switch.
5 - Reinstall the switch/bracket assembly.
6 - Reinstall the side baffle.
7 - Reinstall front glass door.
8 - Raise the bottom hinged panel.
The appliance should then relight and remain lit. If this does not occur, check unit for a blocked
flue condition.
SAFETY SWITCH LOCATION (EBVST and EBVPF Safety Switch Location Shown)
FIREBOX SIDE BAFFLE SECURING SCREW
FIREBOX SIDE BAFFLE
MANUALLY-RESET
SAFETY LIMIT SWITCH
FIREBOX
SIDE WALL
TOP RADIANT PANEL
AND EYEBROW
BRACKET
SECURING SCREW
SAFETY SWITCH
CABINET
SIDE WALL
Figure 33
22
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 23
STEP 13. ATTACHING SAFETY IN OPERATION WARNINGS
It is the installers responsibility to ensure these warnings are properly affixed during installation. These warning labels are a
critical step in informing consumers of safe operation of this appliance.
ATTACHING SAFETY IN OPERATION WARNINGS
It is required that the safety instruction labels furnished with the fireplace be affixed to the operation
and control point of the fireplace. A safety instruction
label must be affixed to the wall switch plate where
the fireplace is turned on and off (See Figure A) and
if used on the remote control handheld transmitter
(Figure B). To properly complete the installation of
this fireplace, locate the multi-lingual adhesive labels
provided with the Care and Operation Instructions
and proceed as follows:
1. Locate the wall switch that controls the fireplace
(verify the switch operates the fireplace by turning it on and off). Clean the wall switch plate
thoroughly to remove any dust and oils. Affix the
label to the surface of the plate of the wall switch
that controls the fireplace (Figure A). Choose
the language primarily spoken in the home. If
unknown, affix the English language label.
2. If a remote control is used to control the fireplace,
locate the transmitter and clean it thoroughly
to remove any dust and oils. Affix the label to
the surface of handheld transmitter (Figure B).
Choose the language primarily spoken in the
home. If unknown, affix the English language
label.
3. If you are unable to locate the labels, please call
Lennox Hearth Products or your nearest Lennox
Hearth Products dealer to receive additional
safety instruction labels free of charge.
Cat. No. H8024 Replacement Label Kit
LENNOX HEARTH PRODUCTS
1-800-655-2008
Note: English is red text on clear label. French and
Spanish are white text on black label.
APPOSITION DES MISES EN GARDE RELATIVES
À LA SÉCURITÉ D’UTILISATION
Il est impératif que les étiquettes de sécurité fournies avec
le foyer soient collées à côté des dispositifs de contrôle
du foyer. Une étiquette de sécurité doit être collée sur la
plaque de l’interrupteur contrôlant l’allumage du foyer
(voir Figure A) et, le cas échéant, sur le boîtier de la
télécommande (Figure B). Pour achever l’installation
correcte de ce foyer, procédez comme suit avec les
étiquettes adhésives en langues étrangères fournies
avec les instructions d’utilisation et d’entretien :
1. Repérez l’interrupteur qui contrôle le foyer (vérifiez
que l’interrupteur contrôle le fonctionnement du
foyer en le faisant basculer de Marche à Arrêt, et
vice-versa). Nettoyez soigneusement la plaque
murale de l’interrupteur pour éliminer la poussière
et les traces de graisse ou d’huile. Collez l’étiquette
sur la surface de la plaque de l’interrupteur mural
qui contrôle le foyer (Figure A). Choisissez la
langue qui est principalement parlée dans la
résidence du propriétaire. En cas de doute, collez
l’étiquette en anglais.
2. Si une télécommande est utilisée pour contrôler
le foyer, nettoyez la soigneusement pour éliminer
la poussière et les traces de graisse ou d’huile.
Collez l’étiquette sur le boîtier de la télécommande
(Figure B). Choisissez la langue qui est principalement parlée dans la résidence du propriétaire. En
cas de doute, collez l’étiquette en anglais.
3. Si vous ne trouvez pas les étiquettes, veuillez
appeler Lennox Hearth Products ou votre distributeur Lennox Hearth Products local pour recevoir
gratuitement des étiquettes supplémentaires.
Étiquettes de remplacement, n° cat. H8024
LENNOX HEARTH PRODUCTS
1-800-655-2008
Remarque : Le texte anglais est rouge sur un support
transparent. Le texte français et espagnol est blanc
sur un support noir.
COLOCACIÓN DE ADVERTENCIAS DE SEGURIDAD
EN OPERACIÓN
Se requiere que las etiquetas de instrucciones de
seguridad incluidas con la chimenea se coloquen en
el punto de operación y control de la misma. Se debe
colocar una etiqueta de instrucciones de seguridad
en la placa del interruptor de pared desde el cual se
enciende y se apaga la chimenea (ver la Figura A) y
en el transmisor de control remoto (Figura B) si se
usa. Para completar correctamente la instalación de
esta chimenea, encuentre las etiquetas adhesivas
multilingües incluidas con las instrucciones de cuidado
y operación y haga lo siguiente:
1. Identifique el interruptor de pared que controla
la chimenea (verifique que el interruptor opera la
chimenea encendiéndola y apagándola). Limpie bien
la placa del interruptor de pared para quitar el polvo
y aceite. Pegue la etiqueta en la superficie de la placa
del interruptor que controla la chimenea (Figura A).
Seleccione el idioma que más se habla en la casa.
Si no sabe cuál es, use la etiqueta en inglés.
2. Si se usa un control remoto para controlar la
chimenea, encuentre el transmisor y límpielo bien
para quitar el polvo y aceite. Pegue la etiqueta en
la superficie del transmisor (Figura B). Seleccione
el idioma que más se habla en la casa. Si no sabe
cuál es, use la etiqueta en inglés.
3. Si no puede encontrar las etiquetas, sírvase llamar a
Lennox Hearth Products o al distribuidor de Lennox
Hearth Products más cercano para recibir etiquetas
de instrucciones de seguridad adicionales gratuitas.
Juego de etiquetas de repuesto - Nº de cat. H8024
LENNOX HEARTH PRODUCTS
1-800-655-2008
Nota: La etiqueta en inglés es transparente con texto
rojo. Las etiquetas en francés y español son negras
con texto blanco.
SAFETY LABEL
DIAGRAMS
Illustrations are for example only.
Your accessories may be different.
Les illustrations sont par exemple
uniquement. Vos accessoires
peuvent être différents.
Las ilustraciones son sólo ejemplos.
Tu accesorios pueden ser diferentes.
DIAGRAMMES DES ÉTIQUETTES
DE SÉCURITÉ
Figure A
DIAGRAMAS DE ETIQUETAS
DE SEGURIDAD
Figure B
23
Page 24
GAS CONVERSION KITS
WARNING
This conversion kit shall be installed by a qualified service agency in
accordance with the manufacturer’s instructions and all applicable codes
and requirements of the authority having jurisdiction. If the information in
these instruction is not followed exactly, a fire, explosion or production of
carbon monoxide may result causing property damage, personal injury
or loss of life. The qualified service agency is responsible for the proper
installation of this kit. The installation is not proper and complete until the
operation of the converted appliance is checked as specified in the manufacturer’s instructions supplied with the kit. The qualified service agency
performing this installation assumes responsibility for this conversion.
AVERTISSEMENT
Cette trousse de conversion doit être installée par un technicien agréé,
selon les instructions du fabricant et selon toutes les exigences et tous les
codes pertinents de l’autorité compétente. Assurez-vous de bien suivre
les instructions dans cette notice pour réduire au minimum le risque
d’incendie, d’explosion ou la production de monoxyde de carbone pouvant
causer des dommages matériels, des blessures ou la mort. Le tecnicien
agréé est responsable de l’installation de cette trousse. L’installation n’est
pas adéquate ni complète tant que le bon fonctionnement de l’appareil
converti n’a pas été vérifié selon les instructions du fabricant fournies avec
la trousse. Le fournisseur de service qualifié ayant réalisé l'installation
assume les responsabilités liées à la conversion.
In Canada:
THE CONVERSION SHALL BE CARRIED OUT IN ACCORDANCE WITH THE REQUIREMENTS OF THE PROVINCIAL AUTHORITIES HAVING JURISDICTION AND IN ACCORDANCE WITH THE REQUIREMENTS OF THE CAN/CGA-B149.1 INSTALLATION CODE.
LA CONVERSION DEVRA ÊTRE EFFECTUÉE CONFORMÉMENT AUX RECOMMANDATIONS DES AUTORITÉS PROVINCIALES AYANT JURIDICTION ET CONFORMÉMENT
AUX EXIGENCES DU CODE D'INSTALLATION CAN/CGA-B149.1.
Gas conversion kits are available to adapt your appliance from the use of one type of gas to the
use of another. These kits contain all the necessary components needed to complete the task
including labeling that must be affixed to ensure safe operation.
Kit part numbers are listed here and the following steps detail the conversion procedure. Refer
to the instructions provided with the conversion kit when performing any gas conversion.
Natural to Propane Gas Conversion Kit
Model No.Unit TypeCat. No.
EBVST / EBVPF
Propane to Natural Gas Conversion Kit
Model No.Unit TypeCat. No.
EBVST / EBVPF
MillivoltH2198
ElectronicH2200
MillivoltH2199
ElectronicH2201
INSTALLATION INSTRUCTIONS
Step 1. TURN OFF THE GAS SUPPLY TO THE
APPLIANCE and disconnect power supply at the
circuit breaker. Ensure appliance is cold.
CAUTION: THE GAS SUPPLY SHALL BE
SHUT OFF PRIOR TO DISCONNECTING THE
ELECTRICAL POWER, BEFORE PROCEEDING WITH THE CONVERSION.
ATTENTION: AVANT D’EFFECTUER
LA CONVERSION, COUPEZ D’ABORD
L’ALIMENTATION EN GAZ, ENSUITE,
COUPEZ L’ALIMENTATION ÉLECTRIQUE.
a. Open the control compartment access panel,
by actuating the spring-loaded magnetic
catches securing the panel, gently depressing
the outer top corners of the panel until the
catches "pop" the panel free and allowing it
to swing out and down to open.
b. Remove the bottom control compartment ac-
cess panel by compressing the spring-loaded
hinge pin on the left side until it disengages
from the left cabinet panel hole. Pull the panel
away from the fireplace.
c. Remove the modesty panel by pulling the
bottom right corner of the modesty panel out
slightly to disengage the snap-fit feature; lift
the modesty panel by the tab on the panel's
right end, pull the right end of the panel away
from the cabinet and then pull the panel
diagonally out of the left side cabinet panel
slots. Remove the modesty panel carefully,
so that none of the wires become loose or
disconnected.
24
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 25
d. Locate the latch at the top of the control
FRONT OF FIREPLACE
PAN BURNER
VENTURI TUBE ARM
AIR SHUTTER
ADJUSTMENT LEVER
FIREBOX SUBFLOOR
Spring
Adjusting
Screw
Slotted
Cap
PSI
OFFION
CONTROL
IGNITE
Manifold
Pressure
Test Port
Inlet Pressure Test Port
Pressure
Regulator
Remove
These
Components
Retaining
Clip
Igniter
Assembly
Pilot
Assembly
Pilot
Orifice
Flare Nut
compartment. To disengage the latch from
the bottom vee-flange of the glass enclosure
panel, reach for the handle located towards
the back of the latch and pull the handle down
toward the front of the unit. See Figure 29
on Page 20.
e. Swing the bottom of the door out and raise
it slightly to lift the top flange of the door
frame away from the appliance.
Step 2. Carefully remove the log set. Exercise
care as not to break the log set.
Step 3. Referring to Figure 34, remove the
burner.
Figure 35
Step 5. Attach manometer to the manifold
side pressure test fitting and verify manifold
pressure reads 3.5" water column (0.87 kPa)
for natural gas, and 10.0" water column (2.49
kPa) for propane gas.
Step 6. Refer to Figure 36 and remove the
pilot hood assembly to access the hexed pilot
orifice. Remove and replace the orifice with the
one provided with the kit.
Pilot
Orifice
Figure 37
Exercise extreme care to prevent damage to
or breakage of the igniter assembly.
Remove the screw securing the pilot assembly
to its mounting bracket. Back off the flare nut
at the end of the pilot gas line to free the pilot
assembly from the gas line. Remove the pilot
orifice and replace it with the one provided with
the conversion kit. Reinstall the pilot assembly
by reversing the steps detailed here.
When reinstalling the igniter assembly, use
extreme care to prevent damage and breakage. Do not apply any leverage to the igniter
assembly while restoring the retainer clip to
its original position.
Millivolt Appliances
Step 4. Refer to Figure 35 and the instruc-
tions provided with the kit. Using a Torx T20,
remove and discard the three pressure regulator
mounting screws. Remove the pressure regulator, spring, poppet, diaphragm and bushing.
Discard all removed components. Ensure
the rubber gasket installed on the back of the
replacement pressure regulator is properly
positioned and install the new pressure regulator using the new screws supplied with the kit.
Tighten screws to 25 in-lbs of torque.
Figure 34
Figure 36
Electronic Appliances
Step 7. Honeywell Electronic Valves - See
Figure 37 and the instructions provided with
the kit. Remove the slotted cap screw, o-ring,
pressure-regulating adjusting screw and spring.
Retain all parts for possible later use. Install
new components from the kit. Black cap and
red spring for propane gas units. Silver cap
and stainless steel spring for natural gas units.
Before installing the cap, attach manometer to
the manifold side pressure test fitting and adjust
screw until pressure reads 3.5" water column
(0.87 kPa) for natural gas, and 10.0" water
column (2.49 kPa) for propane gas.
See Figure 38 and replace the pilot orifice as
follows: Remove the igniter assembly retainer
clip, and carefully remove the igniter assembly.
Note: If the igniter is damaged, a replacement kit
is available, order Catalog No. 87L54.
Figure 38
All Models
Step 8. (Refer to Figure 34)
A. Remove the orifice from the manifold and
replace it with the one provided in the kit.
The following table shows the orifice sizes
for natural and propane models. Figure 39
illustrates the orifice. Always check and verify
correct orifice size.
25
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 26
B. Install the burner as shown in Figure 40.
BURNER POSITIONING
PAN
BURNER
PILOT ASSEMBLY
Ensure that the arm of the venturi of the burner
is hooked onto the air shutter adjustment lever
(refer to Figure 34 on Page 25).The primary
air opening can be adjusted by rotating the
adjustment lever from beneath the firebox floor.
Refer to Figure 31 on Page 21 for the recom-
mended minimum primary air opening setting.
Figure 39
Step 9. Reassemble the remaining components
by reversing the procedures outlined in the
preceding steps.
Use pipe joint compound or Teflon tape on all
pipe fittings before installing (ensure propane
resistant compounds are used in propane applications, do not use pipe joint compounds
on flare fittings).
Burner Orifice Sizes (all models)
Elevation
Feet (meters)
0-4500
(0-1372)
Table 7
• Part /Cat. Number
Natural
Gas
drill size (inches)
#32 (0.116")
* Standard size installed at factory
37L82 •
*
Propane
Gas
drill size (inches)
#50 (0.070")
H4873 •
Step 10. Attach the conversion label provided
in the conversion kit to the rating plate on the
appliance.
Step 11. Turn on gas supply and test for gas
*
leaks.
ALWAYS TEST PRESSURE WITH THE VALVE
REGULATOR CONTROL AT THE HIGHEST
SETTING
Figure 40
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Lennox Hearth Products reserves the right to make changes at any time, without notice, in design,
materials, specifications, prices and also to discontinue colors, styles and products.
Consult your local distributor for fireplace code information.
LENNOX®, the LENNOX design, DAVE LENNOX, the image of DAVE LENNOX and other related
LENNOX marks are registered or common law trademarks of Lennox Industries Inc. and are used
with permission.