Lennox E36ODGPE, E36ODGNE, E42ODGPE-H, E36ODGPE-H, E42ODGPE User Manual

...
This appliance is only for use with the type of gas
US
Portland
indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.
INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.
INSTALLATION INSTRUCTIONS
OUTDOOR GAS FIREPLACE
ELITE® SERIES
OUTDOOR GAS FIREPLACE P/N 850,034M REV. D 04/2009
MODELS
E36ODGNE E42ODGNE
E36ODGNE-H E42ODGNE-H E36ODGPE E42ODGPE E36ODGPE-H E42ODGPE-H
INSTALLATEUR: Laissez cette notice avec l'appareil. CONSOMMATEUR: Conservez cette notice pour consula­tion ultérieure.
WARNING: IF THE INFORMATION IN THIS MANUAL IS NOT FOLLOWED EXACTLY, A FIRE OR EXPLO­SION MAY RESULT CAUSING PROPERTY DAM­AGE, PERSONAL INJURY OR LOSS OF LIFE.
Do not store or use gasoline or other flammable vapors or liquids in the vicinity of this or any other appliance.
What to do if you smell gas:
• DO NOT light any appliance.
• DO NOT touch any electrical switches, do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow your gas suppliers instructions.
• If your gas supplier cannot be reached, call the fire department.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
A French manual is available upon request. Order Form Number 850,034CF.
Ce manuel d’installation est disponible en francais, simplement en faire la demande. Numéro de la pièce 850,034CF.
AVERTISSEMENT: ASSUREZ-VOUS DE BIEN SUIVRE LES INSTRUCTIONS DONNÉES DANS CETTE NOTICE POUR RÉDUIRE AU MINIMUM LE RISQUE D’INCENDIE D’EXPLOSION OU POUR ÉVITER TOUT DOMMAGE MA­TÉRIEL, TOUTE BLESSURE OU LA MORT.
Ne pas entreposer ni utiliser d’essence ni d’autre vapeurs ou liquides inflammables dans le voisinage de cet appareil ou de tout autre appareil.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:
• Ne pas tenter d’allumer d’appareil.
• Ne touchez à aucun interrupteur. Ne pas vous servir des téléphones se trouvant dans le bátiment où vous vous trouvez.
• Appelez immédiatement votre fournisseur de gaz depuis un voisin. Suivez les instructions du fournis­seur.
• Si vous ne pouvez rejoindre le fournisseur de gaz, appelez le service des incendies.
OTL Report No. 116-F-41-5
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
L’installation et l’entretien doivent être assurés par un installeur ou un service d’entretien qualifié ou par le fournisseur de gaz.
1
Accessories
Wall Switch
Fireplace
Weatherproof Enclosure
Optional Drain Pan
TABLE OF CONTENTS
Packaging .........................................page 2
Introduction ......................................page 2
New York & Massachusetts
Requirements ................................page 3
General Information ..........................page 3
Location ............................................page 4
Waterproofing The Fireplace ............page 5
Appliance Clearances ........................page 5
Clearance Specifications ...................page 6
Fireplace Installation .........................page 7
Routing Gas Line ..............................page 7
Fireplace Specifications .....................page 8
Framing Specifications ......................page 9
Field Wiring .......................................page 10
Connecting Gas Line ........................page 11
Installing The Logs ............................page 12
Checking Appliance Operation ..........page 13
Firebox Finishes ................................page 13
Accessories And Components ..........page 14
Gas Conversion Kits .................. page 15
2 - one envelope containing the literature pack-
age which consists of the Homeowner's manual, Installation Instructions and War­ranty.
3 - three (3) bags of lave rock, envelope is
located in the firebox area.
4 - Electrical kit containing the wall switch
components, battery holder, box and cover (see Field Wiring page 10).
INTRODUCTION
These outdoor gas fireplaces are designed for exterior applications. These appliances must be installed outdoors.
The Lennox Elite® Series Outdoor Gas Fireplace is designed for outdoor use. It may also be installed in screened porches and lanais that meet these minimum requirements:
Minimum porch area - 96 square feet Minimum ceiling height - 7 feet 8 inches
A minimum of two (2) walls can be screened but must be open to outside ventilation. Minimum screen area - 64 square feet Minimum screen top height - 6 feet 8 inches
Refer to Clearance Specifications on Page 6.
Electronic appliances are designed to oper­ate on natural gas or propane. An electronic intermittent pilot ignition system provides safe, efficient operation. A battery pack is required to operate these units.
These appliances comply with National Safety Standards and are tested by Omni Test Labo­ratories (Report No. 116-F-41-5) and listed by CSA-4-96 in both USA and Canada, as outdoor gas fireplaces.
The Installation must conform to local codes or, in the absence of local codes, with the National
Fuel Gas Code, ANSI Z223.1/NFPA 54, or the Natural Gas and Propane Installation Code, CSA B149.1.
The appliance, when installed, must be electri­cally grounded in accordance with local codes or, in the absence of local codes, with the National
Electrical Code, ANSI/NFPA 70, or the Canadian Electrical Code, CSA C22.1.
DO NOT ATTEMPT TO ALTER OR MODIFY THE CONSTRUCTION OF THE APPLIANCE OR ITS COMPONENTS. ANY MODIFICATION OR ALTERATION MAY VOID THE WARRANTY, CERTIFICATION AND LISTINGS OF THIS UNIT.
This installation manual will help you obtain a safe, efficient, dependable installation for your appliance.
This manual is part of a set of two supporting this product. Refer to manual 875,032M for
Care And Operations.
Please read and understand these instructions before beginning your
installation.
PACKAGING
The assembled outdoor gas fireplace is pack­aged with the following:
1 - the logs are packaged in a carton located
within the firebox.
TYPICAL INSTALLATION
Figure 1
2
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
evlaVsaGdetaludoM-yllaunaMhtiwsledoM
saGlarutaN saGenaporP
.oNledoM
tupnI
etar
)H/UTB(
.oNledoM
tupnI
etar
)H/UTB(
GDO63E
000,05
ot
005,93
GDO63E
000,64
ot
000,73
GDO24E
000,05
ot
005,93
GDO24E
000,64
ot
000,73
Inlet Gas Supply Pressure
(all models)
Fuel # Minimum Maximum
Natural Gas
5.0" WC
(1.24 kPa)
10.5" WC
(2.61 kPa)
Propane
11.0" WC
(2.74 kPa)
13.0" WC
(3.23 kPa)
Manifold Gas Supply Pressure
(all models)
Fuel # Low High
Natural Gas
(Lo) 2.2" WC
(.55 kPa)
(Hi) 3.5" WC
(.87 kPa)
Propane
(Lo) 6.3" WC
(1.57 kPa)
(Hi) 10.0" WC
(2.49 kPa)
Model
No.
Orifice size
Elevation
Feet
(meters)
Natural
Gas
Propane
E36ODG
0.1405" (#28)
0.0785" (#47)
0-4500
(0-1372)
E42ODG
0.1405" (#28)
0.0785" (#47)
NEW YORK AND MASSACHUSETTS REQUIREMENTS
These appliances may be installed in the following USA locations with the following requirements:
Installation of these appliances are approved for installation in the US state of Massachu­setts if the following additional requirements are met -
• Installation and repair must be done by a plumber or gas fitter licensed in the Common­wealth of Massachusetts.
• The flexible gas line connectors shall not exceed 36 inches (92 centimeters) in length.
• The individual manual shut-off must be a t-handle type valve.
GENERAL INFORMATION
Gas Pressure - All Models
Tables 2 and 3 show the appliances' inlet and manifold gas pressure.
Table 2
Orifice Sizes - Sea Level To High Altitude (All Models)
These appliances are tested and approved for installation at elevations of 0-4500 feet (0-1372 meters) above sea level, using the standard burner orifice (See Table 4 ). For elevations above 4500 feet, contact your gas supplier or qualified service technician. Install the appli­ance according to the regulations of the local authorities having jurisdiction and, in the USA, the National Fuel Gas Code NFPA 54 / ANSI Z223.1 - latest edition or , in Canada, the CAN1­B149.1 and .2 codes - latest edition.
Note: Installation and repair should be per­formed by a qualified service person. The appli­ance should be inspected annually by a qualified professional service technician. More frequent inspections and cleanings may be required due to yard care, insects, etc. It is imperative that the control compartment and burners of the appliance be kept clean.
Provide adequate clearances around air open­ings and adequate accessibility clearance for service and proper operation. Never obstruct the front openings of the appliance.
These appliances are designed to operate on natural or propane gas only.
All Models -
All models have a manually modulated gas valve. Input is shown in Table 1:
Table 3
Test gage connections are provided on the front of the gas control valve identified IN for the inlet and OUT for the manifold side. A 1/8" NPT Test gauge connection is provided at the inlet and outlet side of the electronic gas control valve.
These appliances must be isolated from the gas supply piping system (by closing their individual manual shut-off valve) during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5 kPa).
These appliances and their individual shut-off valves must be disconnected from the gas sup- ply piping system during any pressure testing of that system at pressures greater than 1/2 psig (3.5 kPa).
Table 4
WARNING: PROPANE TANKS ARE AT PRESSURES THAT WILL CAUSE DAM­AGE TO VALVE COMPONENTS. VERIFY THAT THE TANKS HAVE STEP DOWN REGULATORS TO REDUCE THE PRES­SURE TO SAFE LEVELS.
Table 1
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
3
ASSEMBLY OUTLINE
LIVING SPACE
PATIO
Optional Hearth Extension
Before You Start
Check your inventory list to be sure you have all the necessary parts supplied in good us­able condition. Check also for any concealed damage.
LOCATION OF FIREPLACE
Carefully select the proper location for any obstructions, clearance to side wall(s), air availability, location and aesthetics. With proper pre-planning, a slight adjustment of a few inches can save considerable time and expense later during construction and assembly. See Figure 2 for some examples.
When locating the fireplace, consideration must be given to combustibles and final finishing. See Figure 18 and confine the final location of combustible finish materials to the "Safe Zone". Also refer to Clearance Specifications on page 6.
Consider the effects of heat when locating any object in front of or near the fireplace opening.
PRE-INSTALLATION NOTES
The fireplace may be installed directly on a combustible floor or raised on a platform of an appropriate height. Do not place the fireplace on vinyl or other soft floor coverings. It may, however, be placed on flat wood, plywood, particle board or other hard surfaces.
Position the electrical junction box as detailed in LOCATION OF FIREPLACE. (The umbilical cord is 9 feet long).
Be sure the fireplace rests on a solid continu­ous floor or platform with appropriate framing for support.
The fireplace may be positioned and then the framing built around it, or the framing may be constructed and the fireplace positioned into the opening.
ASSEMBLY STEPS
Note: The following steps represent the normal sequence of installation. Each installation is unique, however, and might require a different sequence.
1. Position firebox prior to framing or into prepared framing (non-combustible framing is recommended).
2. Position the electrical junction box as detailed in LOCATION OF FIREPLACE. (The umbilical cord is 9 feet long).
3. Waterproof the fireplace or install the optional drip pan (see Waterproofing The Fireplace and Figure 3 on page 5 ).
4. Plumb gas line. (Gas connections should only be performed by an experienced, licensed/certi­fied tradesman.)
5. Complete the installation, finish wall mate­rial, surround and hearth extension to your individual taste.
6. Assemble and attach optional accessories.
Study the three dimensional illustration (Fig- ure 1 ) to get a general idea of each element of your fireplace system.
Figure 2
When choosing a location, care must be taken to avoid places where flooding or running water may be a problem.
Identify the desired location for the battery pack/ON/OFF switch junction box location. This should be easily accessible and convenient for use and high enough on the wall to be protected from water and drifted snow.
Do not use these appliances if any part of the gas supply, control or burner has been submerged under water. Immediately call a qualified, professional service technician to inspect the appliance and to replace any parts of the control system and any gas control which have been under water.
Carefully consider the position of the fireplace opening with respect to the location of adjacent or nearby stairwells, doors, windows, walkways and over hanging trees, patios and wires.
Usually, no special floor support is needed for the fireplace, however, to be certain:
1. Estimate the total weight of the fireplace sys­tem including surround materials such as brick, stone, etc., to be installed. Shipping weights for the fireplace may be found on page 8.
2. Measure the square footage of the floor space to be occupied by the system, surrounds and hearth extensions.
3. Note the decking construction, i.e. 2 x 6’s, 2 x 8’s or 2 x 10’s, single or double joists, type and thickness of floor boards.
4. Use this information and consult your local building code to determine if you need ad­ditional support.
If you plan to raise the fireplace and hearth extension, build the platform assembly then position fireplace and hearth extension on top. Secure the platform to the floor to prevent possible shifting.
WATERPROOFING THE FIREPLACE
Although the fireplace is designed to operate safely outdoors, rain may enter the hearth area, condensation and can cause water to collect inside the fireplace bottom.
To prevent water collection, the builder must provide a means to drain water from under the fireplace by building or installing a water collector of the builders choice, before posi­tioning the fireplace in its location.
Special care must be taken when the fireplace is installed against an exterior wall. The enclosure surrounding the fireplace on the sides and back must be treated as an exterior wall.
Lennox does provide an optional drain pan to assist weatherproofing the fireplace.
H4651 DPSS36 Drain Pan for E36ODG, H4652 DPSS42 Drain Pan for E42ODG.
4
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
When Planning for the installation of the fire-
47 1/4
Drain Connector Detail
Threaded
Reducer
3/4 x 1/2
(PVC)
Threaded Elbow 3/4 @ 90° (PVC)
1/2” Airspace Clearance To Sides And Back
No Material Within The Face Opening
Noncombustables May Overlap The Face
Combustable Materials
Allowed Flush With
The Face Front
No Combustables Below The Top Spacers
Noncombustable Material Only
Only Noncombustable Material May Overlap The T
op Face
Do NOT Overlap
Material Within
The Face Opening
1/2” Airspace Clearance To Back
TOP VIEW
SIDE VIEW
5”
Combustible Material
May Overlap The
Face Bottom Up To 2”
Below The Face Opening
No Material
Allowed in
This Area
1/2” Clearance
1/2” Airspace Clearance To Sides And Back
Nailing Flange May Make Direct Contact With Combustible Framing
place, the framing height must be increased from 46-1/2 inches to 47-1/4 inches, when installing the drain pan. An additional space below the fireplace will also be required to plumb a drain line.
Step 1. Seal all joints, gaps and corners around
the bottom of the drain pan before positioning the fireplace on its location (Figure 3 ).
Step 2. On the exposed drain hole, install a PVC threaded coupling reducer, 3/4" x 1/2" going from the top of the pan down through the hole. Apply a silicone-based sealant around the base and threads before installation.
Step 3. Holding the reducer coupling with a wrench, thread a 3/4", 90 degree, PVC elbow to the reducer until it is tight to the metal.
Step 4. Add additional piping to route the drain to an appropriate location.
Note: To assure proper drainage, the fireplace must be installed on a leveled surface.
CLEARANCES
Minimum clearance to combustibles for the fireplace is as follows; sides and back – 1/2" (13mm), combustible floor – 0" (0mm), adja­cent wall 6" (152mm), ceiling – 50" (1270mm).
Refer to Figure 4 on this page and Figure 18 on page 13 for more detail.
Note: Clearance behind the nailing flange for both fireplace models is 1/2" (13mm).
Note: Adjacent wall considerations are for an adjacent wall to only a single side. Walls should not be placed at the minimum distance on both sides of the fireplace. Allow at least 4 feet on one side of the fireplace.
Figure 3
Figure 4
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
5
Loading...
+ 11 hidden pages