The display ‘DC60’ is customized for the user.
It allows an overview of the operation of the Unit and allows access to some parameters.
Depending on the setting in the Climatic, two display configurations are possible:
• Mode ‘Light’
• Mode ‘Full’
The 'DC60' is designed to be remotely connected of the Unit.
The 'DC60' is equipped with a temperature sensor.
The temperature sensor allows the acquisition of room temperature to control.
1.2 Temperature measurement
All Lennox Unit comes with a temperature sensor; it must be placed in the conditioned area.
But if the 'DC60' is placed in the area conditioned by the Unit, it is possible, in this case, to use the temperature
measurement of the 'DC60'.
DC60-DM60-ROOFTOP-IOM-1310-E - 2 -
1.3 Quick Action
1.3.1 How to See the Operation of the Unit 4 ?
Only if several units are connected to the DC60.
Turn the knob to have the text ‘Unit’.
Press the knob to switch in 'Set' mode.
Turn the knob to select number 4.
Press the knob to confirm your choice
1.3.2
Press the button a few seconds.
How to Start all Units connected at this DC60 ?
The units can not be powered On/Off by the DC60 if the service display DS60 is connected.
DC60-DM60-ROOFTOP-IOM-1310-E - 3 -
1.3.3
Only if several units are connected to the DC60.
Select the Unit 4 (see: How to See the Operation of the Unit 4 ?)
Turn the knob to have the text ‘I-O’.
Press the knob to switch in 'Set' mode.
Turn the knob to select number 1 (1 for ‘On’, 0 for ‘Off’).
Press the knob to confirm your choice
How to Start Unit 4 ?
The units can not be powered On/Off by the DC60 if the service display DS60 is connected.
1.3.4
Turn the knob to have the text ‘Set’.
The value displayed is the temperature setpoint.
How to See the Value of the Current Setpoint Temperature ?
DC60-DM60-ROOFTOP-IOM-1310-E - 4 -
1.3.5
Turn the knob to have the text ‘Set’.
Press the knob to switch in 'Set' mode.
Turn the knob to change the value.
Press the knob to confirm your choice
How to Modify the Value of the Current Setpoint Temperature ?
DC60-DM60-ROOFTOP-IOM-1310-E - 5 -
1.4 Presentation
1.4.1 Showing
1.4.2
Buttons
DC60-DM60-ROOFTOP-IOM-1310-E - 6 -
1.5 Use
1.5.1 Control operating mode.
Only for Flatair and Aqualean ranges.
Press until the desired operating mode is displayed.
Heating mode
Cooling mode
1.5.2
Only for Flatair and Aqualean ranges.
Press to select the desired speed (min, med, max) or automatic (Auto).
Minimum speed
Automatic mode
Fan Speed Management.
Median speed
Maximum speed
Automatic Speed
1.5.3
By supporting a few seconds, the button you can activate or not (On/Off) the Unit connected.
If the symbol completed by the time is displayed, the Unit is stopped and the 'DC60' in sleep mode.
To restart the unit, press the button a few seconds
If the DC60 is used with the Master/Slaves bus in this case, the 'Off' phase, stops all Rooftop connected on the Bus,
'On' phase restarts all.
On/Off unit
DC60-DM60-ROOFTOP-IOM-1310-E - 7 -
1.5.4Setting time
At initialization of the 'DC60', the Climatic™60 are synchronized time and day of week with the clock 'DC60'.
After a few seconds 'DC60' communicates the new time to the Climatic™60.
1.5.5
Information available
By rotating the knob you can view or modify the following values:
1.6 DC60 set in ‘Light’ mode
* : Unit Index selected by the ‘DC60’
: Volatile temperature set point current mode (°C)
: : Indoor (Room) temperature (°C)
: Alarms code
* : Available if the option is enabled.
: Adjustable with ‘DC60.
1.6.1
If the DC60 is used with the Master/Slaves bus this item can select or know the Unit Index selected by the 'DC60'.
1.6.2
This item allows you to view and/or modify the control temperature required for the Unit selected.
If this point is changed, this value is used until the scheduling changes mode (Day, Day I, Day II, Night, BMS).
At each change of the mode, the Climatic™60 sets the value of this set point on the preset value in the mode
concerned.
DC60-DM60-ROOFTOP-IOM-1310-E - 8 -
Unit selected
Volatile Temperature set point
1.6.3 Alarms code
This item allows you to view the code of different active alarms on the Unit.
If the Unit isn't in alarm, this item is to 0.
1.6.4
This item indicates the measured air temperature in the room conditioning.
The room temperature isn't available if the Climatic™60 is configured to supply control.
Indoor (Room) temperature
1.7 DC60 set in ‘Full’ mode
- : Unit Index selected by the ‘DC60’
- *: On/Off of the Unit selected.
- : Predetermined temperature set point current mode (°C)
- : Volatile temperature set point current mode (°C)
- : Alarms code
-
- : Supply temperature (°C)
-
- * : Indoor (Room) humidity (%hr)
- * : Indoor (Room) Air quality (ppm)
- * : Opening of fresh air damper (%)
* : Available if the option is enabled.
: Available if the level 2 is activated.
: Adjustable with ‘DC60.
* : Outdoor temperature (°C)
* : Indoor (Room) temperature (°C)
1.7.1
This item can select or know the Unit Index selected by the 'DC60'.
1.7.2
If the DC60 is used with the Master/Slaves bus this item allows you to view and/or change the status of starting or
stopping of the Unit selected.
1.7.3
This item allows you to view and/or modify the control temperature required for the Unit selected.
If this point is changed, this value is used until the scheduling changes mode (A, B, C, D, BMS).
At each change of the mode, the Climatic™60 sets the value of this set point on the preset value in the mode
concerned.
1.7.4
If level 2 is active, this item allows you to view and/or change the preset temperature control for the active mode.
Unit connected
On/Off, Power
Volatile Temperature set point
Predetermined Temperature set point
DC60-DM60-ROOFTOP-IOM-1310-E - 9 -