Lennox DC40, DC41 User Manual

Providing indoor climate comfort
CLIMATIC™ 40
MUL37E-0607 12-2009 Original manual translation
User manual
1
1
4
10 10 10
11 11 11 12 12
13 13-14 14-15
15
16
17
18-20
21
22-23
24-27
INDEX
CONTENTS PAGE
• INDEX
• DESCRIPTION OF CONTROLS
1.- CLIMATIC 40 CONTROL
2.- DC41 TERMINAL (ECOLEAN)
3.- DC40 REMOTE TERMINAL (AIRCOOLAIR)
• MENU
• REGULATION
1.- ECOLEAN
2.- AIRCOOLAIR
3.- AIRCUBE
• ADVANCED FUNCTIONS
1.- REMOTE ON/OFF
2.- REMOTE WINTER / SUMMER CHANGEOVER
3.- DYNAMIC SET POINT
4.- BMS COMUNICATIONS
5.- TIME BANDS PROGRAM (ECOLEAN)
6.- LOW NOISE
7.- ANALOGUE / DIGITAL INPUT
8.- TIMING AND DELAYS
9.- DEFROST
10.- CONDENSER FAN SPEED CONTROL
11.- FREE COOLING
• PARAMETERS
• SAFETY DEVICES
• INSTRUCTIONS FOR ASSEMBLY AND INSTALLATION
• ALARMS
2
PWM
DC 41
BM40
ECOLEAN AIRCOOLAIR AIRCUBE
PWM
DC 40
BM40
PWM
BM40
EAC/EAR-SM ANCM/ANHM KSCM/KSHM
Climatic 40 control, is an electronic device that controls Ecolean EAC/EAR units (chiller units), Aircoolair ANCM/ANHM units (air-air units) and Aircube KSCM/KSHM units (condensing units). The thermostat allows the following operations:
• Unit ON/OFF.
• Select system operating mode.
• Set point adjustment.
• Alarm signal relay.
• Display temperature, status of unit and pending alarms.
• Programming of time bands.
• BMS comunications.
• Possibility of remote ON/OFF.
Inlet and outlet water, temperature/pres­sure condenser and outdoor temperature probes (optional).
Proportional regulation based on inlet water temperature (cooling and heating mode).
Defrost cycle (heat pump units), with pres­sure tranducer.
Condensing pressure control with tempe­rature probe or pressure transducer.
Flow switch, antifreeze, high and low pres­sure protections.
Compressors, water pump, fans and elec­trical heater management.
Return / remote ambient, evaporator, tem­perature/pressure condenser and outdoor temperature probes (optional).
Proportional regulation based on remote ambient /return temperature (cooling, heating and automatic mode).
Defrost cycle (heat pump units), with pres­sure tranducer.
Condensing pressure control with tempe­rature probe or pressure transducer.
Antifreeze, high and low pressure protections.
Compressors, indoor and o utdoor fans, electrical heater and freecooling (optional) management.
Condenser temperature/pressure probes.
Regulation based on remote free voltage contacts.
Defrost cycle (heat pump units), with pres­sure tranducer.
Condensing pressure control with tempe­rature probe or pressure transducer.
High and low pressure protections.
Compressors, indoor (optional) and outdo­or fans.
DESCRIPTION OF CONTROLS
Condenser
temperature
/pressure
Inlet water
temperature
Outlet water temperature
Outside
temperature
(optional)
Fan speed
control
Expansión
board
Condenser
temperature
/pressure
Fan speed
control
Expansión
board
Return air
duct
temperature
Evaporator
temperature
Outside
temperature
(optional)
Fan speed
control
Expansión
board
Free cooling
motor damper
1.- CLIMATIC 40 CONTROL
Return or
remote
ambient
temperature
3
H
F
G
E
D
C
B
A L K
I
J
A B C D E
F G H
I
L
I+L
J
K
J+K
L+J
DESCRIPTION OF CONTROLS
CLIMATIC 40 CONTROL
The gure and the table below show the symbols present on the display and on the keypad,together with their meanings:
The main screeen shows: inlet water temperature for ECOLEAN, ambient temperature for AIRCOOLAIR and unit status (On/Off) for AIRCUBE.
SYMBOL
DESCRIPTION
LED ON LED FLASHING
1 or 2
Compressor 1 and /or 2 (circuit 1) ON. Start up request.
2 or 3
Compressor 3 and /or 4 (circuit 2) ON. Start up request. At least 1 compressor ON. Water pump/Indoor fan ON. Start up request. Condenser fan ON. Defrost active. Start up request. Electrical heater ON. Start up request. Alarm active. Cooling mode. Cooling mode request. Heat pump mode. Heat pump mode. Request.
BUTTON DESCRIPTION TIME
Go up a sub-group inside the programming area. Press once Access the direct parameters. Press for 5 s Select item inside the programming area / conrm changes to the parameters. Press once Program parameters afters entering password. Press for 5 s Select top item inside the programming area. Press once Increase value. Press once Switch from standby to heat pump mode and vice-versa. Press for 5 s Provides immediate access to the condenser and evaporator pressure and temperature probes. Press once Select bottom item inside the programming area. Press once Decrease value. Press once Switch from stand-by to chiller mode and vice-versa. Press for 5 s Provides immediate access to the condenser and evaporator pressure and temperature probes. Press once Manual alarm reset. Press for 5 s Immediately reset the hour counter (inside the programming area). Press for 5 s Force manual defrost on both circuits. Press for 5 s
4
J
L
K
I
I+L
J+K
DESCRIPTION OF CONTROLS
DC41 terminal is an optional keypad that allows the Climatic 40 controller to be managed remotely. The buttons and indications on
the display faithfully reproduce the Climatic 40 user interface.
1.1.1.- TURN ON/OFF THE UNIT
In order to turn on the unit, press the “ ” button for 5 seconds, for the heat pump mode, or the “ ” button, for the cooling mode.
The display shows unit’s operating mode together with the symbols of the working elements (compressors, water pump etc.). In order to turn off the unit, press the “ ” button for 5 seconds (if the unit is working in heat pump mode) or the “ ” button (if the unit is working in the cooling mode).
1.1.2.- SELECTING THE UNIT´S OPERATING MODE
If the unit is on stand-by, the operating mode is selected at start-up (as explained above).
If the unit is working in cooling or heating mode, in order to change the operating mode, you rst have to turn the unit off, and only
then can you turn it on in the operating mode you want.
1.1.3.- SELECTING THE WATER TEMPERATURE OF THE SYSTEM
To modify unit’s working set point, you have to change parameter r1 (cool set point) or parameter r3 (heat set point). To see how to change a parameter, see chapter 3 MENU (SETTINGS AND OPERATING HOURS DISPLAY MENU paragraph).
1.2.1.- TURN ON/OFF THE UNIT
The unit is turned on by closing the On/Off contact and turned off by opening it (see section 1, advanced functions, for more details).
1.2.2.- SELECTING THE UNIT´S OPERATING MODE
The heating mode is selected by opening the remote changeover contact while the cooling mode is selected byclosing it (see section 2, advanced functions, for more details).
NOTE There are no set points to be made for Aircube units because the compressors are directly controlled by remote contacts.
1.2.- AIRCUBE
1.1.- ECOLEAN
1.- CLIMATIC 40 CONTROL
2.- DC41 REMOTE CONTROL (ECOLEAN)
OPTION
5
2
41 3
11
7
5
6
10
9
8
POWER
Mode
MODE
FAN
SLEEP
CLOCK
TEMP.
UP/DOWN
1 7
2 8
3 9
4 10
5 11
6
DESCRIPTION OF CONTROLS
3.- DC40 REMOTE TERMINAL (AIRCOOLAIR)
The illustration and the table below show the symbols that appear on the display and on the keypad and their meanings. OFF appears in the main eld of the display if the machine is off, or the set point if the machine is working.
Secundary functions:
Display symbols:
BUTTON NAME DESCRIPTION
Switch from stand-by to ON and vice-versa.
Change operating mode (cooling, heating, automatic).
Switch the indoor fan from automatic mode to always ON and vice-versa.
ActivateS/deactivateS the sleep mode.
ActivateS/deactivateS the time bands.
ShowS the set point when the unit is OFF.
Set the temperature.
BUTTON BUTTON PRESS FUNCTION
3 seconds Sets sleep differential value of the current operating mode.
3 seconds Sets the time bands (hour, day, set point).
5 seconds Clock setting.
3 seconds Reset alarms.
SYMBOL MEANING SYMBOL MEANING
Heating mode. On/Off time bands.
Cooling mode. Sleep mode.
Automatic mode. Duration or sleep mode.
Set point. Alarm.
Day of the week (weekday, weekend). Indoor fan mode.
Hour/Temperature.
6
This function increases (in cooling mode) or decreases (in heating mode) the operating set point according to the lower level of comfort required during the night. Not possible with time bands program. ACTIVATION Press “ ” button once. The display shows “ ” symbol with “1HR” ashing.
In this way, sleep function will work for 1 hour. If you want it to work for longer, press “ ” button repeatedly while “1HR” is still ashing (each press of the button increases by
1 hour, till max 9 hours). Finally, the display shows the “ ” symbol with the number of hours you choose. DEACTIVATION Press the “ ” button once and the sleep function will be deactivated (if it was activated before). The “ ” symbol disappears from the display. DIFFERENTIAL SETTINGS Press “ ” button for 3 seconds. The sleep differential (the value by which you increase or decrease the comfort set point) appears on the display. Use the “ ” buttons to set the value, then press the “ ” button to accept. Note that cooling and heating modes have different sleep differential values, so you can modify only the current operating mode’s value.
To set current time:
1. Press the “ ” button for 6 seconds. “rtc” and current time appears on the display (hours are ashing).
2. Set the hour using the “ ” buttons.
3. Press the “ ” button to accept. Minutes start ashing on the display.
4. Set the minutes using the “ ” buttons.
5. Press the “ ” button to accept. “day” and the number of the day of the week appear on the display (Monday=1, Tuesday=2 etc.)
6. Set the day by using the “ ” buttons.
7. Press the “ ” button to accept.
3.1.- TURN ON/OFF THE UNIT WITH REMOTE CONTROL DC40 (AIRCOOLAIR)
3.2.- SELECTING THE UNIT´S OPERATING MODE
Once the unit is turned on, you can select Cooling, Heating or Automatic mode just pressing the “Mode” button. In the automatic mode you just choose the set point and the system automatically switches from cooling to heating mode, depending on the position of the ambient temperature with respect to the set point.
3.3.- SELECTING DESIRED ROOM TEMPERATURE
If unit is working, the “ ” buttons allow the desired room temperature to be select (set-point). The “↑” button allows the current set point to be increased by 0.5ºC. The “↓” button allows the current set point to be decreased by 0.5ºC.
3.4.- SELECTING THE FAN OPERATING MODE (Aircoolair)
In order to be able to select a fan operating mode, the unit’s operating mode (cooling, heating or auto) must be selected. Pressing the side button “ ” scrolls through the following modes: FAN CONSTANTLY ON, or AUTO FAN CONSTANTLY ON: Fan is ON continuously and the “ ” simbol will appear. AUTO: Fan on and off together with the compressor or with the freecooling, the “ ” symbol will appear.
3.5.- SLEEP FUNCTION
3.6.- CLOCK SETTINGS
To turn on the unit press the “ ” button. The display shows current operating mode.
DESCRIPTION OF CONTROLS
3.7.- TIME BANDS PROGRAM
This function allows you to programme time bands during the week, each one with a different set point. In this way you can adapt
the cooling/heating provided by the unit according to each moment of the day.
You can set two time bands for the weekdays and another two for the weekend.
7
22ºC 25ºC
OFF
OFF
DESCRIPTION OF CONTROLS
CONFIGURATION
NOTE: You must set the DC40 clock before programming time bands. Time bands programs keep current operating mode (if it was in cool mode, it keeps working in cool mode; if it was in auto matic mode, it keeps working in automatic mode, etc.).
EXAMPLE IN SUMMER
a) Enter time bands menu. b) Set 1ST time band for weekday start hour. c) Accept.
d) Set 1ST time band of weekday start minutes. e) Accept. f) Set 1ST time band of weekday set point (on/off/tem-
perature).
g) Accept. h) Repeat steps b-c-d-e-f-g to programme 2nd time
band for weekdays.
i) Repeat steps b-c-d-e-f-g-h to programme the two
time bands for weekends.
Weekdays
Time band 1
ashing
Flashing
Flashing
Flashing
Time band 2
Weekend
Flashing
ACTIVATION
DEACTIVATION
3 sec.
Weekdays
Hour
8:00 (Time band 1)
18:00 (Time band 2)
Weekend
8
b) Set password “ 22 ” by the “ ” and “ ” buttons.
MENU
A) PROBES DISPLAY MENU
Press the “ ” button to enter probes display menu. “ b01”, “b02”, “b04”, “b06” ,“b07” ,“b08” ,“b021”, appears on the display (depending
on the unit’s conguration).
Once the probe is selected, after a few seconds, “b01” turns into its temperature/ pressure measure.
Press “ Sel ” button for 5 seconds. “ ”, appears on the display. Move inside the menu as explained below.
1 sec.
5 sec.
B) SETPOINT SETTINGS AND OPERATING HOURS DISPLAY MENU
C) PARAMETERS EDITING MENU
a) Press “ Pgr ” and “ Sel”, at the same time, for 5 seconds.
c) Press “ Sel ”, to accept.
d) Press “ Sel ”, to enter parameters Editing menu.
Go up a sub-group inside the programming area.
UP or increase valve.
Down or decrease valve.
Go down a sub-group or accept
parameter modications inside
the programming area.
5 sec.
Access to the menu:
To go to different values in the menu, proceed as above, the:
9
MENU
NOTES:
a) Parameters that have been modied without being conrmed using the “ Sel ” button will return to their previous value. b) After conrming a modication, escape up to the main menu to save it; otherwise, modications will be cancelled. c) If no operations are performed on the keypad for 60 seconds, the controller exits the parameter editing menu on timeout
and any changes are cancelled.
MENU TREE
PROBES SETTINGS
ATIFREEZE AND
ELECTRICAL HEATER
PROBES
COMPRESSORS
DEFROST
FANS
UNIT SETTING
ALARMS
REGULATION
TIMER SETTING
SOFTWARE
10
r1
r2
r3
r4
CM2
CM1
r4
r7
CM1
CM2
r7 r2
SP
EH2
EH1
A11
CM1
CM2
r7 r2
SP
A9
A9
A8
r1 10 22 11 9 22 10 8 22 9 8 22 9 r2 0.3 50 2 0.3 50 3 0.3 50 4 0.3 50 4 r3 20 45 41 20 45 42 20 45 43 20 45 43 r4 0.3 50 2 0.3 50 3 0.3 50 4 0.3 50 4
SP 8 32 23 8 32 23 8 32 23
r2 0.3 50 1 0.3 50 2 0.3 50 4 r4 0.3 50 1 0.3 50 2 0.3 50 4
r7 0.3 50 0.5 0.3 50 0.5 0.3 50 0.5 A8 0 20 1.5/2.5 0 20 1.5/3.5 0 20 1.5/4.5 A9 0.3 50 1 0.3 50 1 0.3 50 1
A11 0 20 2.5 0 20 2.5 0 20 2.5
REGULATION
1.- ECOLEAN
Inlet water temperature is thermostatically controlled via set point and tolerance range (differential) as shown in the following diagrams:
1.1- COOLING OPERATING MODE 1.2- HEATING OPERATING MODE
1.3- AFFECTED PARAMETERS
2.- AIRCOOLAIR
STEP 1
STEP 2
Unit 2 CM
STEP 2 STEP 1
Unit. 2 CM
Ambient (or return air duct) temperature is thermostatically controlled via set point and tolerance range (differential) as shown in the following diagrams:
2.1- AUTOMATIC MODE (Heat pump)
2.2- AUTOMATIC MODE (Cooling only+Electrical heater)
2.3- AFFECTED PARAMETERS
3.- AIRCUBE
Aircube is regulated by digital input. (see section 7, advanced functions, for more details).
HEAT COOL
HEAT COOL
Inlet water
temperature (ºC)
Inlet water
temperature (ºC)
Ambient
temperature (ºC)
Ambient
temperature (ºC)
Par. DESCRIPTION
VALUE UNIT 1CM. VALUE UNIT 2CM. VALUE UNIT 3CM. VALUE UNIT 4CM.
MIN. MAX. DEF. MIN. MAX. DEF. MIN. MAX. DEF. MIN. MAX. DEF.
Cooling set point Cooling differential. Heating set point. Heating differential
Par. DESCRIPTION
UNIT 1 COMPRESSOR UNIT 2 COMPRESSORS UNIT 3 COMPRESSORS
MIN. MAX. DEF. MIN. MAX. DEF. MIN. MAX. DEF.
Set point (DC40). Cooling differential. Heating differential. Dead zone. SP E.H. 1 cool / SP E.H. 1 heat Differential E.H. SP E.H. 2 cool.
11
r19
r18
r1
r20
r18
r3
11ºC
SP
14ºC
25ºC 35ºC
r1 = 14ºC
r17 = -0.3
r18 = 3ºC
r19 = 25ºC
r3 = 38ºC
r18 = 3ºC
r20 = 12ºC
r31 = -0.5
SP
38ºC
41ºC
6ºC 12ºC
SP (DC40) = 24ºC
r17 = 0.2
r18 = 2ºC
r19 = 35ºC
SP (DC40) = 21ºC
r18 = 2ºC
r20 = 6ºC
r31 = 0.2
SP
19ºC
21ºC
-4ºC 6ºC
SP
24ºC
26ºC
35ºC 45ºC
r18
SP (DC40)
r20
r18
SP (DC40)
r19
ADVANCED FUNCTIONS
1.- REMOTE ON/OFF
This function allows you to turn the unit on/off by a simply remote contact (contacts 95-96 in ECOLEAN and AIRCOOLAIR
units;contacts 88-89 in AIRCUBE units). Close contact = ON; Open contact = OFF.
2.- REMOTE CHANGEOVER WINTER/SUMMER
On heat pump units (also in Aircoolair cooling only + electrical heater), cooling or heating mode can be selected by a remote con­tact (contacts 97-98).
Close contact = Cooling.; Open contact = Heating.
To activate this function set parameter H06=1.
3.- DYNAMIC SET POINT
With this function, which needs to incorporate an additional outdoor temperature probe, it’s possible to adjust the set point dynamically based on ambient temperature. The set point value can be increased or decreased when the external conditions are more advantageous, thus achieving extra energy saving. Dynamic set point must be activated in the factory. The user must set the parameters as shown in the graphics below:
ECOLEAN
AIRCOOAIR
WARNING
On Aircoolair units, remote changeover doesn’t work if the automatic mode has been selected by DC40.
Set point ºC
COOL
SP = r1 + (T.ext. - r19) x r17
EXAMPLE
Set point ºC
HEAT
SP = r3 + (T.ext. - r20) x r31
Set point ºC
COOL
Set point ºC
HEAT
SP = SP(DC40) + (T.ext. - r19) x r17
EXAMPLE
SP = SP(DC40) + (T.ext. - r20) x r31
EXAMPLE
EXAMPLE
OPTION
Outdoor temp.. ºC
Outdoor temp.. ºC
Outdoor temp.. ºC
Outdoor temp.. ºC
Outdoor temp.. ºC
Outdoor temp.. ºC
Outdoor temp.. ºC
Outdoor temp.. ºC
12
ECOLEAN
AIRCOOLAIR
MODBUS
8:00-18:00 11ºC 11ºC 11ºC 11ºC 11ºC 11ºC 11ºC
18:00-8:00
(t06:t07-t08-t09)
16ºC 16ºC 16ºC 16ºC 16ºC 16ºC 16ºC
ADVANCED FUNCTIONS
4.- BMS COMMUNICATIONS
Given the growing and unstoppable trend towards Building Automation, driven by powerful and ever-evolving connectivity, the Climatic 40 controller offers the possibility of communicating with Building Management Systems (BMS) via Modbus protocol. The Modbus standard interface is integrated into the control, so you don’t need any sort of gateway, router, etc. In order for you to connect to the RS485 serial line, we provide the TTL-RS485 converter as an option for Ecolean and Aircube units. Aircoolair units don’t need the converter (it’s integrated) but they do need the ambient or duct remote sensor option.
5.- TIME BANDS PROGRAM (Ecolean)
The Climatic 40 controller allows 2 time bands to be programmed for each day, each with a different set point. The setting parameters are explained in the following table:**
For further information, please see BMS communication manual.
EXAMPLE (Cooling):
WARNING
Set internal clock before programming time bands (t01=hour, t02=minutes, t03=day, t04=month, t05=year).
To deactivate time bands programme, set start time = end time.
OPTION
COOLING HEATING
TIME SET POINT TIME SET POINT
1st TIME BAND
Rest of the day r1 Rest of the day r3
2nd TIME BAND
Start
(hour:minutes)
t06:t07
r21
Start
(hour:minutes)
t10:t11
r22
End
(hour:minutes)
t08:t09
End
(hour:minutes)
t12:t13
HOUR Monday Tuesday Wednesday Thursday Friday Saturday Sunday
13
40%
100%
18 18.5 20 23 23.5 25 26 31
ECOLEAN AIRCOOLAIR AIRCUBE
EAC EAR ANCM ANHM KSCM KSHM
DC40 (b21)
b1 b2
b3*
b4
b6
b7*
b8
_______
- - - - - - -
ADVANCED FUNCTIONS
6.- LOW NOISE
This function is available only in the following units:
ECOLEAN EAC + kit -15ºC y EAR 251-812 SM AIRCOOLAIR ANCM + kit -15ºC y ANHM 22E-86D AIRCUBE KSCM + kit -15ºC y KSHM 22E-86D This function moves the condensing pressure set point in order to lower the fan speed and thus reduce noise (specically at night). If low noise is active during cooling, the condenser control set points are increased by 5º bar. If low noise is active in heating, the set points are reduced by 1º bar.
Set F15=3 to active this function. Also set the following parameters:
Low noise cooling mode shift is illustrated in the following picture.
7.- ANALOGIC / DIGITAL INPUT
PROBES TABLE
* Except: EAC 1003-1103-1303-1403-1604-1804-SM ANCM 112D-128D-152D. KSCM 112D-128D-152D-214D
NOTE:
Optional kits could change probes settings.
PROBE
Ambient temperature
Inlet water temperature Return or remote ambient temperature **
Outlet water temperature 1st Circuit evaporator temperature
1st Circuit condenser
temperature
Outdoor
temperature **
1st Circuit condenser
temperature
Outdoor
temperature **
1st Circuit condenser
temperature
Outdoor
temperature **
1st Circuit condenser
pressure
Outdoor
temperature **
1st Circuit condenser
pressure
1st Circuit condenser
pressure
2st Circuit evaporator temperature
2st Circuit condenser
temperature
2st Circuit condenser
temperature
2st Circuit condenser
pressure
2st Circuit condenser
pressure
2st Circuit condenser
pressure
** Optional elements.
SPEED FAN
CONDENSER PRESSURE (bar)
COOLING HEATING
TIME FAN TIME FAN
Rest of day Standard Rest of day Standard
Start
(hour:minutes)
t14:t15
LOW
NOISE
Start
(hour:minutes)
t18:t19
LOW
NOISE
End
(hour:minutes)
t16:t17
End
(hour:minutes)
t20:t21
Standard “Low noise”
14
ON
ON
ECOLEAN AIRCOOLAIR AIRCUBE
EAC EAR ANCM ANHM KSCM KSHM
ID1
ID2
ID3
ID4
ID5
ID6
ID7
ID8
ID9
ID10
120 2
3005
ON
ON
ON
ON
CM2
CM1
ADVANCED FUNCTIONS
DIGITAL INPUT TABLE
COMPRESSOR
8.- TIMING AND DELAYS
In order to protect compressors from destructively cycling on and off, following protection delays have been set:
Time
(sec.)
unit
COMPRESSOR- WATER PUMP (ECOLEAN) In both heating and cooling modes, the compressors start 150 seconds after the water pump has started, in order to stabilize the water system.
In addition to that, the water pump stops 4 minutes after the last compressor has stopped, in order to take advantage of the
remaining thermal energy in the exchanger.
Compressor
Water pump
240 s.
150 s.
DIGITAL INPUT
Flow switch Termal overload fan ON/OFF
Cool/Heat Cool/Heat Cool/Heat Cool/Heat
High pressure circuit 1
Low pressure circuit 1
ON/OFF ON/OFF Step 1
Step 3
Step 2
High pressure circuit 2
Low pressure circuit 2
Step 4
15
150” 5” 90” 150”90”150”
30/35
5.7
30” 30”
The defrosting process is activated during heating mode in the heat pump units, when the outside temperature is low and the
outdoor coil is likely to be frozen. To melt the ice, the defrosting function will switch the unit to cooling operation for a short period.
During defrosting mode, the low pressure is at minimum level, so the pressure switch is disabled in this mode. The defrost cycle is illustrated in the following picture.
9.- DEFROST
ADVANCED FUNCTIONS
WATER PUMP- WATER FLOW SWITCH (ECOLEAN)
The water ow switch ensures that the water pump does not work when there is no water ow. At rst, there is a by-pass during the rst 150 seconds of water pump operation which operates according to the water ow switch signal. When the alarm has been
activated, the water pump is stopped. The water pump starts again every 90 seconds for 150 seconds, in order to try to reset the alarm. This procedure is repeated 5 times and after that the pump remains stopped until the alarm is reset manually.
ALARM
PUMP
close
open
ow
If the pressure does not reach 30/35 bars within 8 minutes from the start of the defrost cycle, the cycle nishes because of maxi­mum time and the display shows “dF1” or “dF2” (according to the circuit). The time between two defrost cycles for the same circuit is 40 minutes. The time between two defrost cycles of the two circuits is 10 minutes.
Condenser pressure (bar)
Compressors
Reverse valve
HEAT
DEFROST
HEAT
16
40%
100%
18 18.5 20 26
40%
100%
18 19 28 40
0ºC
22 bar
15ºC
28 bar
30ºC
30 bar
35ºC
37 bar
+7ºC
ADVANCED FUNCTIONS
The function of the fan speed control is to prevent very low condensing temperatures during cooling mode operation at outside
temperatures of between 0ºC and 46ºC.
Depending on the unit, this function could be:
1.1.- PROPORTIONAL CONTROL BASED ON PRESSURE
Models: ECOLEAN: EAC + kit -15ºC and EAR 251-812 SM AIRCOOLAIR: ANCM + kit -15ºC and ANHM 22E-86D AIRCUBE: KSCM + kit -15ºC and KSHM 22E-86D
In this case, it is a proportional fan speed control, which varies the fan voltage supplied to the fan.
10.- CONDENSER FAN SPEED CONTROL
FAN
SPEED
CONDENSER
PRESSURE (bar)
NOTE
At start-up the fan works at maximum speed for 20 seconds,
so as to overcome the mechanical inertia of the motor.
1.2.- PROPORTIONAL CONTROL BASED ON PRESSURE TEMPERATURE Models: ECOLEAN: EAC 251-812 SM AIRCOOLAIR: ANCM 22E-86D AIRCUBE: KSCM 22E-86D In this case too, it is a proportional fan speed control, which varies the voltage supplied to the fan.
FAN
SPEED
CONDENSER
TEMPERATURE (ºC)
NOTA
At start-up, the fan works at maximum speed for 20 seconds,
so as to overcome the mechanical inertia of the motor. The same time is observed with regard to compressor start-up (irrespective of the condensing temperature) in order to improve temperatures probes reading.
1.3.- ON/OFF CONTROL BASED ON PRESSURE Models: ECOLEAN: EAR* 1003-1804 SM AIRCOOLAIR: ANHM* 112D-152D AIRCUBE: KSHM* 112D-214D ON/OFF, through the control and change between high and low fan speed through pressure switches.
The fans for these models incorporate 2 speeds. The fans work on high or low speed according to:
COOLING MODE: The on/off and low/high fan speed is managed according to the condensing pressure. See the illustration below:
HEATING MODE (heat pump units only). The low/high fan speed is managed according to the outdoor temperature thermostat. See the illustration below:
High speed
Low speed
High speed
Low speed
Outdoor temperature ºC
COOLING MODE
HEATING MODE
Approx. outside temperature ºC
Condensing pressure
NOTE*: In these same models, but in cooling only version, the fan speed management is the same, apart from that, the ON/OFF signal is provide by a pressure switch instead of the control.
17
CM2
CM3
CM1
23 23.5 24 26
SP
24.5
R02/4
23
23.5 25
r40 0 9 1
r41 0 100 20
ADVANCED FUNCTIONS
11.- FREE COOLING
This option takes advantage of external conditions for cooling mode. Freecooling is enabled when outdoor temperature is 1ºC lower than indoor temperature; when the former is:
- < 10ºC, the compressors are deactivated and the air intake gate fully opened in order to refresh with outdoor air only (sufcient under
these conditions).
- >10ºC, the air intake gate opens and delays the compressors, which turn on only if there would be insufcient outdoor fresh air
to achieve the comfort setpoint. The illustration below shows freecooling regulation.
With free cooling
Open air damper. Close air damper.
Without freecooling
Stop air damper.
Ambient temperature (ºC)
Ambient temperature (ºC)
OPTION
To get a constant air renewal, when freecoling conditions are satised, the damper is mantained opened partially (20%), according to
the following values.
Par. DESCRIPTION Min. Max. Def.
This indicates when to carry out the minimum opening of the damper.
0= Never.
1= with freecooling.
2= with freeheating.
3= with freecooling and freeheating
4= always, except with freecooling y freeheating.
5= always, except with freeheating.
6= always, except with freecooling.
7= always
8= only for cooling mode.
9= only for heating mode.
% minimum percentage opening damper.
18
A01 A7 A4 0.1 ºC 3,0 2 ------
A02 0,3 122 0.1 ºC 5,0 5 ------
A03 0 150 1 0 30 ------
A04 A1 R16 0.1 ºC 4,5 ------ ------
A05 0,3 50 0.1 ºC 1,0 ------ ------
A08
A1 R16 0.1 ºC 35 ------ ------
0 20 0.1 ºC ------
1.5 (ANCM)
------
2.5 (ANHM 22E-43E)
3.5 (ANHM 52D-86D)
4.5 (ANHM 112D-152D)
A9 0 20 0.1 ºC 1 1 ------
A11
A1 R16 0.1 ºC 33 ------ ------
0 20 0.1 ºC ------ 2.5 (ANCM 52D-86D) ------
A13 A7 R16 0.1 ºC ------ 7 ------
b0 0 11 1 N 0 11 10
b1 ------ ------ ------ ºC
b2 ------ ------ ------ ºC
b3 ------ ------ ------ ºC
b4 ------ ------ ------ ºC/bar
b5 ------ ------ ------ ºC
b6 ------ ------ ------ ºC
b7 ------ ------ ------ ºC
b8 ------ ------ ------ ºC/bar
b21 ------ ------ ------ ºC
C01 0 999 1 0 0 0
C02 0 999 1 120 120 120
C03 0 999 1 300 300 300
C04 0 999 1 2 2 2
C05 0 999 1 0 0 0
C06 0 999 1 5 5 5
C07 0 999 1 150 0 0
C08 0 150 1 4 0 0
C10 0 8000 100
C11 0 8000 100
C12 0 8000 100
C13 0 8000 100
C14 0 100 100 0 0 0
C15 0 8000 100
C17 0 150 1
0 0 0
C18 0 150 1
0 1 0
PARAMETERS
PAR.
DESCRIPTION MIN. MAX. VAR. UD.
BY DEFAULT
ECOLEAN AIRCOOLAIR AIRCUBE
Antifreeze and electrical heater
Antifreeze alarm set point.
Antifreeze differential.
By-pass time for antifreeze alarm. sec.
Antifreeze heater set point.
Antifreeze heater differential.
Auxiliary heater absolute set point (1st step).
Auxiliary heater relative set point (1st step).
Auxiliary heater differential.
Auxiliary heater absolute set point (2st step).
Auxiliary heater relative set point (1st step).
Lower discharge air temperature in freecooling.
Probes
Cong. of probe to be shown on the display:
0= probe B1. 1= probe B2
2= probe B3. 3= probe B4
4= probe B5. 5= probe B6
6= probe B7. 7= probe B8
8= Set point without compensation.
9= Dynamic set point with possible compensation.
10= Remote ON/OFF digital input status.
11= Terminal DC40 probe.
Probe B1.
Probe B2.
Probe B3.
Probe B4
Probe B5.
Probe B6.
Probe B7.
Probe B8.
Probe DC40.
Timming and delays
Min. compressor ON time. sec.
Min. compressor OFF time. sec.
Delay between 2 starts of the same compressor. sec.
Delay between starts of the 2 compressor. sec.
Delay between 2 shut-downs of the 2 compressors. sec.
Delay at start up. sec.
Delay in switching on the compressor after switching on the pump.
sec.
Delay in switching off the compressor after switching off the pump. min.
Compressor 1 timer. hours
Compressor 2 timer. hours
Compressor 3 timer. hours
Compressor 4 timer. hours
Compressor operation timer threshold (0=not used). hours
Evaporator pump timer. hours
Minimum time between 2 pump starts.
min.
Minimum pump/indoor fan ON time.
min.
19
d01 0 1 1 ag 1 1 1
d03 1 D04 0.1 bar 5.7 5.7 5.7
d04 D03 /12 0.1 bar 35 30 30
d05 10 150 1 60 60 60
d06 0 150 1 0 0 0
d07 1 150 1 8 8 8
d08 10 150 1 40 40 40
d09 0 150 1 10 10 10
F02 0 3 1 int.
1 (EAC 1003-1804) 1 (ANCM 112D-152D) 1 (KSCM 112D-214D)
2 (EAR 1003-1804) 2 (ANHM 112D-152D) 2 (KSHM 112D-214D)
3 (EAC/EAR 251-812) 3 (ANCM/HM 22E-86D) 3 (KSCM/HM 22E-86D)
F05
-40 176 0.1 ºC 28 28 28
/11 /12 0.1 bar
F06
0 50 0.1 ºC 12 12 12
0 30 0.1 bar 6 6 6
F07
0 50 0.1 ºC 10 10 10
0 F5 0.1 bar 2 2 2
F08
-40 176 0.1 ºC 30 30 30
/11 /12 0.1 bar
F09
0 50 0.1 ºC 1 1 1
0 30 0.1 bar 5 5 5
F10
0 50 0.1 ºC 0 0 0
0 F8 0.1 bar 13 13 13
F11 0 120 1 20 20 20
F15 0 3 1 ag 0 0 0
F16 0 50 0.1 bar 5 5 5
F17 0 50 0.1 bar 1 1 1
H06 0 1 1 ag 0 0 0 (KSCM) 1 (KSHM)
H07 0 1 1 ag 1 1 1
H10 1 200 1 ud. 1 1 1
H23 0 1 1 ag 0 0 0
H97 0 999 1 ag
H99 0 999 1 ag
P04 0 3 1 ag 1 1 1
PARAMETERS
PAR.
DESCRIPTION MIN. MAX. VAR. UD.
BY DEFAULT
ECOLEAN AIRCOOLAIR AIRCUBE
Defrost
Defrosting cycle activation.
Start defrosting pressure.
End defrosting pressure.
Min. time to start a defrosting cycle. sec.
Min. duration of a defrosting cycle. sec.
Max. duration of a defrosting cycle. min.
Delay between 2 defrosting cycle requests with in the same circuit.
min.
Defrosting delay between the 2 circuits. min.
Fan
Fan operating mode:
0= Always ON.
1= Depending on compressor (in parallel operating mode).
2= Depending on compressors in ON/OFF control.
3= Depending on compressors in speed control mode.
Temp. value for min. speed cooling.
Pressure value for min. speed cooling. 20 (if F2=3) / 22 (if F2=2) 20 (if F2=3) / 22 (if F2=2) 20 (if F2=3) / 22 (if F2=2)
Differential value for max. speed in cooling mode (temp).
Differential value for max. speed in cooling mode (pres).
Fan shut-down differential in cooling mode (temp).
Fan shut-down differential in cooling mode (pres).
Temperature value for min. speed in heating mode.
Pressure value for min speed cooling. 12 (if F3=3) / 22 (if F3=2) 12 (if F3=3) / 22 (if F3=2) 12 (if F3=3) / 22 (if F3=2)
Differential value for max. speed in heating mode (temp).
Differential value for max. speed in heating mode (pres).
Fan shut-down differential in heating mode (temp).
Fan shut-down differential in heating mode (pres).
Fan starting time.
Activation Low Noise:
0= Deactivate.
1= Activate only in cooling mode.
2= Activate only in heating mode.
3= Activate both in cooling and heating mode.
Differential Low Noise in cooling mode.
Differential Low Noise in heating mode.
Setting
Activate remote change over:
0= Deactivate.
1= Activate.
ON/OFF remoto:
0= Deactivate.
1= Activate.
Serial address.
Activate Modbus.
Expansion board software version.
Software version.
Alarms
Enable part load in high pressure:
0= Capacity control deactivated.
1= Capacity control activated for high pressure.
2= Capacity control activated for low pressure.
3= Capacity control activated for high and low pres.
20
r1 R13 R14 0.1 ºC
11 (EAC/EAR 251-431)
24 ------10 (EAC/EAR 472-812)
9 (EAC/EAR 1003-1804)
r2 0.3 50 0.1 ºC
2 (EAC/EAR 251-431) 1 (ANCM/HM 22E-43E)
------3 (EAC/EAR 472-812) 2 (ANCM/HM 52D-86D)
4 (EAC/EAR 1003-1804) 4 (ANCM/HM 112D-152D)
r3 R15 R16 0.1 ºC
41 (EAC/EAR 251-431)
22 ------42 (EAC/EAR 472-812)
43 (EAC/EAR 1003-1804)
r4 0.3 50 0.1 ºC
2 (EAC/EAR 251-431) 1 (ACHM 22E-43E)
------3 (EAC/EAR 472-812) 2 (ANHM 52D-86D)
4 (EAC/EAR 1003-1804) 4 (ANHM 112D-152D)
r7 1 50 0.1 ºC ------ 0.5 ------
r17 -5 5 0.1 ------ 0 0 ------
r18 0.3 20 0.1 ºC 3 2 ------
r19 -40 176 0.1 ºC 25 35 ------
r20 -40 176 0.1 ºC 12 6 ------
r21 R13 R14 0.1 ºC 16 28 ------
r22 R15 R16 0.1 ºC 35 18 ------
r23 0 8 1 ag 0 0 ------
r24 R15 R16 0.1 ºC ------ 23 ------
r25 -40 80 0.1 ºC -15 -15 -15
r31 -5 5 0.1 ------ 0 0 0
t01 0 23 1 ------
t02 0 59 1 ------
t03 1 31 1 ------
t04 1 12 1 ------
t05 0 99 1 ------
t06 0 23 1 ------ 0 0 0
t07 0 59 1 ------ 0 0 0
t08 0 23 1 ------ 0 0 0
t09 0 59 1 ------ 0 0 0
t10 0 23 1 ------ 0 0 0
t11 0 59 1 ------ 0 0 0
t12 0 23 1 ------ 0 0 0
t13 0 59 1 ------ 0 0 0
t14 0 23 1 ------ 0 0 0
t15 0 59 1 ------ 0 0 0
t16 0 23 1 ------ 0 0 0
t17 0 59 1 ------ 0 0 0
t18 0 23 1 ------ 0 0 0
t19 0 59 1 ------ 0 0 0
t20 0 23 1 ------ 0 0 0
t21 0 59 1 ------ 0 0 0
PARAMETERS
WARNING
Default values could vary depending on optional kits or improvements.
PAR.
DESCRIPTION MIN. MAX. VAR. UD.
BY DEFAULT
ECOLEAN AIRCOOLAIR AIRCUBE
Regulation
Cooling set point.
Differential in cooling mode.
Heating set point.
Differential in heating mode.
Dead zone.
Cooling compensation constant.
Maximum distance from the set point.
Start compensation temerature in cooling mode.
Start compensation temerature in heating mode.
Second cooling set point.
Second heating set point.
Select automatic change over probe.
Automatic change over set point.
Outside temp. set point to stop compressors.
Heating compensation constant.
Clock
Real Time Clock (RTC) hours.
Real Time Clock (RTC) minutes.
Real Time Clock (RTC) days.
Real Time Clock (RTC) month.
Real Time Clock (RTC) years.
Start hours for 2nd set point in cooling.
Start mimutes for 2nd set point in cooling.
End hours for 2nd set point in cooling.
End minutes for 2nd set point in cooling.
Start hours for 2nd set point in heating.
Start mimutes for 2nd set point in heating.
End hours for 2nd set point in heating.
End minutes for 2nd set point in heating.
Start hours for 2nd low noise cooling.
Start mimutes for 2nd low noise in cooling.
End hours for 2nd low noise in cooling.
End minutes for 2nd low noise in cooling.
Start hours for 2nd low noise in heating.
Start mimutes for 2nd low noise in heating.
End hours for 2nd low noise in heating.
End minutes for 2nd low noise in heating.
21
SAFETY DEVICES
This protection is activated by the control of the unit when the outlet water temperature probe (b2), located inside the water
exchanger, measures +4.5ºC and deactivates when the outlet water temperature probe reaches +5.5ºC again.
When the protection is activated, the following occurs:
- If the unit is operating in STAND-BY mode: the water pump goes on, as does the electrical heater for the water exchanger
and the electrical heater of the water tank (if included).
ANTIFREEZE PROTECTION (ECOLEAN).
DO NOT TURN OFF THE POWER TO THE UNIT. WHEN THE POWER IS OFF THE ANTI FREEZE PROTECTION
WILL NOT OPERATE.
- If the unit is operating on cooling mode: it powers the electrical heater of the water tank, the electrical heater of the water
exchanger, and it activates the hot gas injection valve (if the unit incorporates these options).
This alarm is activated when the outlet water temperature probe (b2) measures a value of + 3 ºC (in standard unit). The unit is stopped. The alarm can be reset manually when the outlet water temperature reaches + 8ºC (in standard unit).
LOW WATER TEMPERATURE ALARM (ECOLEAN).
The unit is protected by means of a temperature probe located in the indoor piping, when the indoor temperature goes drops 2ºC:
WITHOUT FREECOOLING
- The compressors shut down and the antifreeze alarm goes on.
- The alarm is reset automatically when the temperature reaches 7ºC.
WITH FREECOOLING
- Air intake gate closes,
- Once the gate is completely closed, the compressors shut down and the antifreeze alarm goes on.
When the air intake gate is closing, if the temperature in the indoor piping goes up 2ºC, the gate stops and stays in the position reached; then, if the temperature reaches goes over 7ºC, the air damper starts to open or, if the temperature goes down 2ºC, the
damper start to close again.
ANTIFREEZE PROTECTION (AIRCOOLAIR).
In addition to that, in order to prevent frozen air discharging when freecooling without the compressors working (outdoor temp. <10ºC), if the temperature in the indoor piping goes down 7ºC, the air intake gate starts to mix outdoor air with return air, thus
increasing the temperature of the discharge air.
NOTE: Low water temperature options can change the values of antifreeze protection and low water temperature alarm.
22
GND
TX+ TX-
GO G
ASSEMBLY AND INSTALLATION INSTRUCTIONS
DC40.
Installation instructions
1. Separate the cover of the instrument from the bodypart using a screwdriver as shown in Fig. 8.1.
2. Open the instrument with a “hinge” movement, pivoting the cover of the instrument upwards.
Lower view
Fig. 8.1
Fig. 8.2
3. Fix the rear part to the wall, taking care that the connection cables pass through the hole in the centre of the rear casing. The distances between the fastening holes are designed so as to be able to t the DC40 to a ush-mounting connection box
compliant with the CEI C.431 - IEC 670 standards. If this is not available, use the fastening holes on the casing as a guide
for drilling the holes in the wall, and then use the kit of screws and plugs supplied.
4. Connect the cables to the terminals located in the casing as indicated in the casing itself or in the electrical diagram.
5. Once the installation is complete, t the terminal onto the casing by pivoting the cover with a “hinge” movement and close it. When closing, make sure that the pins on the board t into the corresponding terminals.
Installation warnings
- Disconnect the power supply before working on the DC40 during operations of assembly, maintenance and replacement.
- The terminal must be fastened to the wall in such a way as to allow the circulation of air through the slits on the rear casing.
- Avoid installing the boards in environments with the following characteristics:
- Avoid locations where there is a great variation in room temperature.
- Near doors leading to the outside.
- On outside walls.
- Where it will be exposed to direct sunlight or to conditioned air ow.
- Where there are strong magnetic and/or radio frequency interference (for example, near transmitting antennae).
Keep the DC40’s inductive load cables separate from those of any power devices (contactors, etc.) in order to prevent electromagnetic interference. Do not lay power and communications cables together
- Run a connection from the electrical box in the outdoor unit to the DC40 device:
. 91 and 92 terminal blocks respectively to Tx+ and Tx-
(Twisted pair for communications).
. 93 and 94 terminal blocks respectively to GO and G.
(Twisted pair for 24VAC power). . 90 to GND. (shield).
2 x TWISTED PAIR
SCREEN WIRE AWG20
L.max=100m
1 x TWISTED PAIR
SCREEN WIRE AWG20
+ 2 x 1,5 mm
2
L.max=200m
23
156.2
A
RJ12 – Power supply
RS485 24 Va
c
G
G0
– +
GND
DC41
Max. L=10m.
92 91 90
93 94
DT41
ASSEMBLY AND INSTALLATION INSTRUCTIONS
Installation instructions:
1. Pass the telephone cable through the hole in the rear of the casing.
2. Fasten the rear of the casing to the box using the round-head screws.
3. Connect the telephone cable to the RJ12 terminal of the DC41.
4. Rest the front panel on the rear of the casing and fasten the assembly using the countersunk screws, as shown in Fig. 8.3.
5. Finally, click the frame in place.
DC41.
Electrical connections:
1. Disconnect the power supply before working on the DC41 during operations of assembly, maintenance and replacement.
2. Make the connection between the “DT41” power supply and the DC41 terminal using the telephone cable (80 cm)
supplied. If the cable is not long enough, use a pin-to-pin telephone cable with a maximum length of 10 m.
Fig. 8.3
Fig. 8.4
Thelefone cable
Max. L.=200m. AWG20.
Keep the DC41’s inductive load cables separate from those of any power devices (contactors, etc.) in order to prevent electromagnetic interference. Do not lay power and communications cables together
- Connect from the electrical box in the outdoor unit to DT41 device:
. 91 and 92 terminal blocks respectively to Tx+ and Tx -. (Twisted pair for communications). . 93 and 94 terminal blocks respectively to GO and G. (Twisted pair for power 24VAC).
. 90 to GND. (shield).
Max. L.=200m Ø=1,5mm
2
2 x TWISTED PAIR
SCREEN WIRE AWG20
Max. L.=100m
1 x TWISTED PAIR
SCREEN WIRE AWG20
+ 2 x 1,5 mm
2
Max. L.=200m
Insert 120Ω terminal resistor between + y - of DT40 device (see electrical drawing) for lines longer then 20m.
24
CLIMATIC 40
DC 40
DC 41
ALARMS
The unit self-protects by means of safety devices; when any of these safety devices detects an anomaly, this is shown on
the Climatic 40 display and, in Aircoolair units only, also on the DC41 display (even if it has a different alarm code), in order to warn the operator. Depending on the type of anomaly, Climatic 40 shows:
• Alarm. Serious anomaly. This is one that has a direct effect on the operation of the unit.
• Warning. Non-serious anomaly. This is one that has no direct effect on the operation of the unit.
The activation of an alarm results in:
- Alarm code being shown on Climatic 40 display alternately with the main menu.
- Only in Aircoolair units, an alarm code (different from the one for the Climatic 40) being shown on the DC40 display alternately with the main menu.
- A red bell appears on the Climatic 40 display and the alarm relay is activated. (contacts 99-100).
- In some cases, depending on the type of alarm, some of the outputs may be blocked, thus stopping the unit.
The activation of a warning results in:
- A warning code being shown only on the Climatic 40 display, alternately with the main menu.
ALARMS/WARNINGS DISPLAY
Some alarms are reset automatically. When the cause is no longer present, they disappear from the display. Others alarms are reset manually and, once the alarm conditions have disappeared, they need to be reset by the user as shown below:
ALARM/WARNING RESET
5 Sec.
5 Sec.
3 Sec.
25
HP1
HP
HP2
LP1
LP
LP2
TP
T TC1 ------ -----­TC2 ------ ------
LA ------ ------ ------
FL ------
FLb ------ ------ ------
E1
E00
E2
E3
E4
E5 ------ ------
E6
E7
E8
Hcl-4 Hc ------
EPr ------
------
Epb ------
ESP ESP
EL1-2 ------
dF1-2 ------ ------
d1-2 ------ ------ ------
ALARMS
ALARMS/WARNINGS CODES
DISP
CL40/
DC41
DISP
DC40
DESCRIPTION EFFECT RE ACTION
High pressure switch alarm, circuit 1. This alarm may indicate the following problems:
- High pressure switch protection.
- Compressor stopped.
- Excessive refrigerant charge.
- Insufcient water ow in heating cycle (Ecolean).
Circuit 1
compressors
stop
AUTO/
MAN.
After 3
times in
1 hour
Reset and check:
- Coil is clean and not blocked.
- Water ow on the heating cycle (Ecolean).
- Outdoor fan during cooling cycle.
- Indoor fan during heating cycle (Aircoolair).
- Compressor protection.
- Condenser air temperature is very high.
- Refrigerant charge.
High pressure switch alarm, circuit 2. The same as previous alarm but this time referring to circuit 2.
Circuit 2
compressors
stop
AUTO/
MAN.
After 3t/h
The same as previous alarm but this time referring to circuit 2.
Low pressure switch alarm, circuit 1. This alarm may indicate the following problems:
- Low refrigerant.
- Low water ow in cooling cycle (Ecolean).
- Outdoor fan stopped.
- Low pressure switch protection.
Circuit 1
compressors
stop
AUTO/
MAN.
After 3
times in
1 hour
Reset and check:
- Coil is clean and not blocked.
- Water ow on the cooling cycle (Ecolean).
- Outdoor fan during heating cycle.
- Indoor fan during cooling cycle.
- Fuses of the fan.
- Evaporation air temperature is very low.
- Check refrigerant charge.
- Expansion valve.
Low pressure switch alarm, circuit 2. The same as previous alarm but this time referring to circuit 2.
Circuit 2
compressors
stop
AUTO/
MAN.
After 3t/h
The same as previous alarm but this time referring to circuit 2.
Indoor fan thermal protection alarm. (Aircoolair only):
- Fan thermal protection open.
- Faulty power supply.
Unit stops MAN.
Reset and check:
- Fan.
- Power supply. Not used. Call Technical Service. Not used. Call Technical Service. Not used. Call Technical Service.
Water ow switch alarm. This indicates low water ow in the unit. (Ecolean) only.
After 5 minutes it automatically requires to be reset manually.
Unit stops
AUTO/
MAN.
- Check water circuit is not blocked.
- Check water lter.
- Check water pump operation.
Not used. Call Technical Service. B1 probe error. Faulty probe or connection.
Unit stops AUTO
Check connection of B1 probe (see electrical diagram), check continui-
ty and change the faulty component. B2 probe error. Faulty probe or connection.
Unit stops AUTO
Check connection of B2 probe (see electrical diagram), check continui-
ty and change the faulty component. B3 probe error. Faulty probe or connection.
Unit stops AUTO
Check connection of B3 probe (see electrical diagram), check continui-
ty and change the faulty component.
B4 probe/pressure transducer error. Faulty probe or connection.
Unit stops AUTO
Check connection of B4 probe/pressure transducer (see electrical
diagram), check continuity and change the faulty component.
Not used. Call Technical Service. B6 probe error. Faulty probe or connection.
Unit stops AUTO
Check connection of B6 probe(see electrical diagram), check continuity
and change the faulty component. B7 probe error. Faulty probe or connection.
Unit stops AUTO
Check connection of B7 probe (see electrical diagram), check continui-
ty and change the faulty component.
B8 probe/pressure transducer error. Faulty probe or connection.
Unit stops AUTO
Check connection of B8 probe/pressure transducer (see electrical
diagram), check continuity and change the faulty component.
Warning. Compressor operating time limit exceeded. AUTO
Check:
- Compressor operating time (parameter C10).
- Compressor operating time limit (par. C15). Disabled by default.
Warning. Climatic 40 hardware error.
AUTO Call Technical Service.
Warning. Climatic 40 hardware error.
Unit stops AUTO Call Technical Service.
Expansion board error. Unit stops AUTO
Check:
- Green LED is on inside the board.
- J4-J9 connections (see electrical diagram).
Call Technical Service.
Warning. Condensing fan speed control hardware error.
Outdoor fan at
maximum
speed.
AUTO
- Check CFM board connections (see electrical diagram).
Call Technical Service.
Warning. Circuit 1-2 defrost ends due to maximum time (8 mi­nutes).
AUTO
Warning. Circuit 1-2 defrosting.
26
A1
A12
A2
Ht ------ ------
Lt ------ ------ ------
AHt ------ ------ -----­HLt ------ ------ ------
ELS ------ ------
EHS ------
Ed1 ------ ------ ------
Ed2 ------ ------ -----­SH1 ------ ------ -----­SH2 ------ ------ -----­nO1 ------ ------ -----­nO2 ------ ------ -----­LO1 ------ ------ -----­LO2 ------ ------ -----­HA1 ------ ------ -----­HA2 ------ ------ -----­EP1 ------ ------ -----­EP2 ------ ------ -----­ES1 ------ ------ -----­ES2 ------ ------ -----­EU1 ------ ------ -----­EU3 ------ ------ ------
Eb1 ------ ------ ------
Eb2 ------ ------ ------
L ------ ------ -----­Ed1 ------ ------ -----­Ed2 ------ ------ ------
PH1 ------ ------ -----­PH2 ------ ------ -----­SUL ------ ------ ------
tEr OcH
AcH ------ ------
Ahu ------ ------
AtE ------ ------
CEr ------ -----­UEr ------ ------
ALARMS
ALARMS/WARNINGS CODES
DISP
CL40/
DC41
DISP
DC40
DESCRIPTION EFFECT RE ACTION
Antifreeze alarm.
- ECOLEAN Outlet temperature < 3ºC. Reset MAN.
- AIRCOOLAIR circuit 1 indoor piping temperature <
2ºC. Reset AUTO.
-ECOLEAN
compressors
stop.
- AIRCOOLAIR
Close freecooling
air dumper and
stops circuit 1
compressors 1
MAN/ AUTO
ECOLEAN: Reset and check:
- Check the water lter.
- Check water ow.
- Check that the water pump is connected to the unit’s power supply. AIRCOOLAIR: Check:
- Indoor unit air lter.
- Air damper working correctly.
Antifreeze alarm, circuit 2. (Aircoolair only).
Circuit 2 indoor piping temperature < 2ºC. Reset
AUTO.
Close
freecooling air
dumper and
stops circuit 1
compressors 2
AUTO
Check:
- Indoor unit air lter.
- Air damper working correctly.
High ambient temperature warning.
Ambient temperature > 40ºC.
AUTO
Check location of ambient probe; avoid places where measurement of
the ambient temperature by the internal sensor may be altered.
Warning the low ambient temperature. Disabled by default.
Call Technical Service.
Not used. Call Technical Service. Not used. Call Technical Service. Low power supply warning. Power supply < 20.4V. AUTO Check power supply of controller = 24V (see electrical diagram).
High power supply warning. Power supply > 26.4V. Unit stops AUTO Check power supply of controller = 24V (see electrical diagram).
Not used. Call Technical Service. Not used. Call Technical Service. Not used. Call Technical Service. Not used. Call Technical Service. Not used. Call Technical Service. Not used. Call Technical Service. Not used. Call Technical Service. Not used. Call Technical Service. Not used. Call Technical Service. Not used. Call Technical Service. Not used. Call Technical Service. Not used. Call Technical Service. Not used. Call Technical Service. Not used. Call Technical Service. Not used. Call Technical Service. Not used. Call Technical Service. Not used. Call Technical Service. Not used. Call Technical Service. Not used. Call Technical Service. Not used. Call Technical Service. Not used. Call Technical Service. Not used. Call Technical Service. Not used. Call Technical Service. Not used. Call Technical Service. Alarm, faulty communication between DC40 and Climatic 40. (Aircoolair only).
Unit stops AUTO
- DC40 connections (see electrical diagrams). Call Technical Service.
Generic alarm. Some active alarms on Climatic 40.
Check Climatic 40 alarm code and act by accordingly.
Not used. Call Technical Service. DC40 internal probe alarm.
Faulty internal probe.
Call Technical Service.
DC40 setting error. Call Technical Service. DC40 hardware error. Call Technical Service.
27
ALARMS
ALARM LOG
The Climatic 40 has a log where signicant events that stop (alarms) or limit (warnings) the operation of the unit are saved.
In order to enter the Alarm Log menu, proceed as explained in chapter 3 MENU in the paragraph PARAMETERS EDITING MENU, entering the password 44 instead of 22. Up to 25 events can be saved, highlighting in order: event code, start hours, start minutes, start day, start month, end hours, end minutes, end day, end month.
WARNING
The alarm log is active and operative only if the clock board is tted.
If there are no alarms saved, “noH” is displayed.
EVENT CODE
START MONTHS
END MONTHS
START HOURS START MINUTES START DAYS
END HOURS END MINUTES END DAYS
28
NOTES
29
NOTES
30
NOTES
www.lennoxeurope.com
www.lennoxbelgium.com
www.lennox.cz
www.lennoxfrance.com
www.lennoxdeutschland.com
www.lennoxuk.com
www.lennoxnederland.com
www.lennoxpolska.com
www.lennoxportugal.com
www.lennoxrussia.com
www.lennoxdistribution.com
www.lennoxspain.com
www.lennoxrussia.com
www.lennoxdistribution.com
Due to Lennox’s ongoing commitment to quality,
the Specifications, Ratings and Dimensions are
subject to change without notice and without
incurring liability.
Improper installation, adjustment, alteration,
service or maintenance can cause property
damage or personal injury.
Installation and service must be performed by a
qualified installer and servicing agency.
MUL37E-0607 12-2009 Original manual translation
BELGIUM, LUXEMBOURG
CZECH REPUBLIC
FRANCE
GERMANY
GREAT BRITAIN
NETHERLANDS
POLAND
PORTUGAL
RUSSIA
SLOVAKIA
SPAIN
UKRAINE
OTHER COUNTRIES
Loading...