Lennox CMC 025S, CMH 020S, CMH 025S, CMH 035S, CMC 040S Installation, Operating And Maintenance Manual

...
lennoxemeia.com
COMPACTAIR
CMC - CMH
Installation, operating and maintenance manual
20 à 100 kW
MIL123E-0613 11-2014
Translation of original manual
1
4 4-5 5 6 6-8 9 10 11-14 15-16
17 17 18 19 20 20 21-22 23-26
27 28-29
30 31 32
2.- INSTALLATION PAGE
3.- COMMISSIONING AND OPERATION PAGE
4.- MAINTENANCE PAGE
DATA PAGE FOR COMMISSIONING UNIT PAGE 3
TABLE OF CONTENTS
POINTS TO BEAR IN MIND PAGE 2
1.- GENERAL CHARACTERISTICS PAGE
1.1.- PHYSICAL DATA
1.2.- ELECTRICAL DATA
1.3.- OPERATING LIMITS
1.4.- INDOORFAN PERFORMANCES
1.5.- RETURN FAN PERFORMANCES
1.6.- OPTION PRESSURE DROP
1.7.- OUTDOO FAN PERFORMANCES
1.8.- PIPING DRAWINGS
1.9.- UNIT DIMENSIONS
2.1.- PRELIMINARY PREPARATIONS
2.2.- UNIT ACCEPTANCE
2.3.- OPTIONAL OPERATIONS PRIOR TO UNIT INSTALATION
2.4.- UNIT LOCATION
2.5.- INSTALLATION CLEARANCES
2.6.- DRAINS
2.7.- ELECTRICAL CONNECTIONS
2.8.- OPTIONS INSTALLATION
3.1.- PRELIMINARY CHECKS BEFORE FIRST INSTALLATION
3.2.- PRELIMINARY CHECKS AT FIRST INSTALLATION
4.1.- PREVENTIVE MAINTENANCE
4.2.- CORRECTIVE MAINTENANCE
4.3.- FAILURE DIAGNOSIS
Lennox have been providing environmental solutions since 1895, our COMPACTAIR range continues to meet the stan­dards that have made LENNOX a household name. Flexible design solutions to meet YOUR needs and uncompromi­sing attention to detail. Engineered to last, simple to maintain and Quality that comes as standard. For information on local contacts at www.lennoxeurope.com.
The manufacturing of these units is made under the requirements of the ISO 9001 and ISO 14001.
All the technical and technological information contained in this manual, including any drawing and technical descrip­tions provided by us, remain the property of Lennox and must not be used (except in the operation of this product), reproduced, issued to or made available to third parties without the prior written agreement of Lennox.
WARNING: Read this manual before installation, reparation o maintenance works.
2
Abrasive surfaces
Risk of injury by
moving objects
High
temperatures
Low
temperatures
Risk of injury by
rotating objects
Electrical
voltage
ELECTRICAL CONNECTIONS
Make sure to switch off the power before installing, repairing or carrying out maintenance on the unit, in order to prevent serious electrical injury.
Keep local and national legislation in mind when installing the unit.
Standard Guidelines to Lennox equipment
All technical data contained in these operating instructions, including the diagrams and technical description remains the property of Lennox and may not be used (except for the purpose of familiarizing the user with the equipment), reproduced, photocopied, transferred or transmitted to third parties without prior written authorization from Lennox.
The data published in the operating instructions is based on the latest information available. We reserve the right to make modifi cations without notice.
We reserve the right to modify our products without notice without obligation to modify previously supplied goods.
These operating instructions contain useful and important information for the smooth operation and maintenance of your equipment.
The instructions also include guidelines on how to avoid accidents and serious damage before commissioning the equipment and during its operation and how to ensure smooth and fault-free operation. Read the operating instructions carefully before starting the equipment, familiarize yourself with the equipment and handling of the installation and carefully follow the instructions. It is very important to be properly trained in handling the equipment. These operating instructions must be kept in a safe place near the equipment.
Like most equipment, the unit requires regular maintenance. This section concerns maintenance and management personnel.
If you have any queries or would like to receive further information on any aspect relating to your equipment, do not hesitate to contact us.
POINTS TO BEAR IN MIND
DANGER AND WARNING SIGNS
3
1 ºC 2 ºC
1 ºC 2 ºC
1 ºC 2 ºC
1 ºC 2 ºC
DATA PAGE FOR UNIT COMMISSIONING
UNIT:
INSTALLER TEL:INSTALLER:
CONTROL PANEL IDENTIFICATION CODE:
INSTALLATION ADDRESS:
SERIAL Nr:
CHECKS:
DATE OF COMMISSIONING:
SUPPLY VOLTAGE:
RATED VOLTAGE OF THE UNIT:
UNIT ON SHOCK ABSORBERS DRAINAGE WITH TRAP MAIN POWER SUPPLY CONNECTION CONTROL PANEL CONNECTION COMPRESSOR OIL LEVEL INDICATOR
YES NO
DATA INPUT:
COOLING CYCLE
Air intake temperature to the outdoor coil:
Air output temperature to the outdoor coil:
High pressure:
Low pressure:
circuit 1 circuit 2
circuit 1 circuit 2
Air intake temperature to the outdoor coil:
Air output temperature to the outdoor coil:
High pressure:
Low pressure:
circuit 1 circuit 2
circuit 1 circuit 2
HEATING CYCLE
ELECTRIC POWER CONSUMPTION (Amps)
Compressor 1
Compressor 3
Outdoor fan section 1
Outdoor fan section 2
Options installed:
Comments:
Compressor 2
Compressor 2
INSTALLER ADDRESS:
Compressor 1
Compressor 3
Outdoor fan section 1
Outdoor fan section 2
4
C M C 020 S N M 3 M
CMC CMH 020S
CMC CMH 025S
CMC CMH 030S
CMC CMH 035S
CMC CMH
040S
CMC CMH 045D
CMC CMH
055D
CMC CMH 070D
CMC CMH 085D
CMC 4300 5350 6000 7800 9000 5150 6100 7750 9250
CMH 4500 5500 6200 8050 9300 5300 6300 8000 9550
371 407 418 510 533 623 779 824 876
376 412 424 516 539 630 785 831 883
2 2 2 2 2 2 2 3 3
10 10 10 10 10 20 20 20 30
50 50 50 75 75 75 165 165 165
10 10 10 12 16 20 20 24 30
6.5 3 3 5 0 3 3 3 13
6.5 3 8 8 3 6 6 16 21
9.5 8 11 8 6 6 19 24 21
25 25 25 28 28 28 37
(1)
37
(1)
37
(1)
2 2 2 2 2 3 4 4 7
6 6 6 9 9 9 14 14 14
2 6 6 4 4 12 12 8 8
CMC CMH
020S
CMC CMH 025S
CMC CMH 030S
CMC CMH 035S
CMC CMH 040S
CMC CMH 045D
CMC CMH 055D
CMC CMH 070D
CMC CMH 085D
8.25 10.1 11.8 15.5 16.9 20.2 23.5 31 33.8
1.45 1.89 2.69 2.69 2.69 3.63 5.38 5.38 7.26
0.74 1.45 1.45 1.89 2.69 2.69 2.69 3.63 5.06
10.44 13.44 15.94 20.08 22.28 26.52 31.57 40.01 46.12
15 21 22 25.6 31 42 44 51.2 62
2.59 3.45 4.8 4.8 4.8 6.48 9.6 9.6 12.96
1.4 2.59 2.59 3.45 4.8 4.8 4.8 6.48 8.6
18.99 27.04 29.39 33.85 40.6 53.28 58.4 67.28 83.56
89.8 100.4 107.7 142.6 157.5 126.6 136.7 176 200.5
1.- GENERAL CHARACTERISTICS
1.1.- PHYSICAL DATA
Unit
COMPACTAIR
C: Cooling only
H: Heat pump
Type of refrigerant
M: R-410A
Approximate cooling
capacity in kW
M: Compact unit
S: One Circuit
D: Two Circuits
- - -
Number
of revision
M: 400V/3/50
CMC: Cooling only unit R-410A. CMH: Heat pump unit R-410A.
(1)
Weight of free-cooling and exhaust fan.
UNIDAD MODELOS
Compressor (Nr/Type) 1/Scroll 1/Scroll 1/Scroll 1/Scroll 1/Scroll 2/Scroll 2/Scroll 2/Scroll 2/Scroll
Refrigerant R-410A charge (per circuit)
Net weight
Kg.
CMC cooling only unit
CMH heat pump unit
Air sock control
Electtrical heater
Free-cooling
Hot water coil
Kit fan HP1
Kit fan HP2
Kit fan HP2
Exhaust fan
Low noise
High ! ltration level (G4 pre! ltre / F7 ! ltration)
Kit long distance
1.2.- ELECTRICAL DATA
ELECTRICAL CONSUMPTION
(*) The units are supplied with refrigerant R-410A indicated above.
UNIT MODELS
Maximum absorbed
power
(Kw)
Compressor
Fun motor outdoor
Fun motor indoor
Total power
Maximum
current
(A)
Compressor
Fun motor outdoor
Fun motor indoor
Total current
Start up current (A)
WEIGHTS OF THE UNITS AND OPTIONS
5
CIC/H 020S CIC/H 025S CIC/H 030S CIC/H 035S CIC/H 040S
0 0 0 0 0 0 0 0 0 0
0,71 1,19 0,44 0,86 44 0,86 0,8 1,35 0 0
0,71 1,19 1,24 2,21 1,24 2,21 1,74 3,03 0,94 1,68
1,15 2,05 1,24 2,21 2,18 3,89 1,74 3,03 2,37 3,8
0,51 2,6 0,51 2,6 0,51 2,6 1,33 6,8 1,33 6,8
n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a
10 14,3 10 14,3 10 14,3 15 21,5 15 21,5
15 21,5 15 21,5 15 21,5 20 28,6 20 28,6
20 28,6 20 28,6 20 28,6 27 39 27 39
CIC/H 045D CIC/H 055D CIC/H 070D CIC/H 085D CIC/H 100D
0 0 0 0 0 0 0 0 0 0
0,94 1,68 0,94 1,68 1,43 2,12 1,32 2,5 1,32 2,5
2,37 3,8 2,37 3,8 2,75 4,62 3,73 6,7 5,06 8,6
2,37 3,8 3,69 3,69 5,16 8,82 3,73 6,7 5,06 8,6
1,33 6,8 2,65 4,5 2,65 4,5 2,65 4,5 5,3 9
n/a n/a 2,69 4,8 3,63 6,5 3,63 6,5 5,06 8,6
15 21,5
20 28,6 20 28,6 20 28,6 27 39
20 28,6
27 39 27 39 27 39 40 57,8
27 39
40 57,8 40 57,8 40 57,8 50 72,3
1.- GENERAL CHARACTERISTICS
1.2 .- ELECTRICAL DATA
Electrical consumptions to add to the unit indoor and to the set
(*) With option kit low temperature 0ºC. (**) With option kit low temperature -15ºC.
DB: Dry bulb temterature WB: Wet bulb temperature
1.3.- OPERANTING LIMITS
(*) With option kit low temperature -15ºC.
OPERATING LIMITS FOR (HEATING PUMP) UNITS MAXIMUM TEMPERATURE MINIMUM TEMPERATURES
COOLING CYCLE OPERATION
INDOOR TEMPERATURE
32ºC BS / 23ºC WH 21ºC BS / 15ºCWH
OUTDOOR TEMPERATURE
45ºC (020-025-030-045-055)
47ºC (035-040-070-085)
0ºC STANDARD UNITS
-15ºC (*)
HEATING CYCLE OPERATION
INDOOR TEMPERATURE
27ºC DB 15ºC DB
OUTDOOR TEMPERATURE
27ºC (With 20ºC outdoor tem-
perature)
-12ºC (With 20ºC indoor temperatur)
OPERATING LIMITS FOR (COOLING-ONLY) UNITS MAXIMUM TEMPERATURES MINIMUM TEMPERATURES
COOLING CYCLE OPERATION
INDOOR TEMPERATURE
32ºC BS / 23ºC WH 21ºC BS / 15ºC WH
OUTDOOR TEMPERATURE
45ºC (020-025-030-045-055)
47ºC (035-040-070-085)
+15ºC STANDARD UNITS
0ºC (*) -15ºC (**)
Maximum absorbed
power (Kw)
Maximum
current (A)
Maximum absorbed
power (Kw)
Maximum
current (A)
Maximum absorbed
power (Kw)
Maximum
current (A)
Maximum absorbed
power (Kw)
Maximum
current (A)
Maximum absorbed
power (Kw)
Maximum
current (A)
Ventilador interior estándar
Kit de ventilación HP1
Kit de ventilación HP2
Kit de ventilación HP3
Ventilador de extracción
Ventilador de retorno
Batería eléctrica estándar
Batería eléctrica media
Batería eléctrica alta
Maximum absorbed
power (Kw)
Maximum
current (A)
Maximum absorbed
power (Kw)
Maximum
current (A)
Maximum absorbed
power (Kw)
Maximum
current (A)
Maximum absorbed
power (Kw)
Maximum
current (A)
Maximum absorbed
power (Kw)
Maximum
current (A)
Ventilador interior estándar
Kit de ventilación HP1
Kit de ventilación HP2
Kit de ventilación HP3
Ventilador de extracción
Ventilador de retorno
Batería eléctrica estándar
Batería eléctrica media
Batería eléctrica alta
6
085D
14000 15125 16250 16725
ASP PI ASP PI ASP PI ASP PI
755
260 3,44 255 3,77 250 4,13
715
230 3,12 225 3,43 215 3,75 212 3,90
675
202 2,82 195 3,11 183 3,41 178 3,55
635
173 2,53 165 2,80 153 3,09 145 3,22
595
145 2,27 135 2,52 120 2,79 115 2,91
055D
9950 10825 11700 12850
ASP PI ASP PI ASP PI ASP PI
755
255 2,37 257 2,56 260 2,77 260 3,05
715
230 2,11 232 2,30 234 2,48 233 2,75
675
207 1,88 208 2,05 210 2,23 207 2,48
635
184 1,67 184 1,82 184 1,99 180 2,22
595
162 1,47 162 1,61 160 1,77 155 1,98
070D
12450 13550 14650 15090
ASP PI ASP PI ASP PI ASP PI
755
260 2,93 260 3,22 258 3,52 255 3,65
715
235 2,64 233 2,91 228 3,20 225 3,32
675
208 2,37 205 2,62 198 2,90 195 3,00
635
182 2,12 176 2,36 168 2,61 165 2,72
595
157 1,89 150 2,11 140 2,35 135 2,44
ASP (Pa): PI (Kw):
020S
rpm
824 788 753 717 682
m3/h
3150 167 149 132 116 101
3425 162 143
127
109 93
3700 155 138 120 103 85
4100
127
108
90 72
025S
rpm
824 788 753 717 682
m3/h
4250 141 123 103 84 66
4625 129 109
89
69 49
5000 115 92 71 50 28
5500 89 66
42
19 n/a
030S
rpm
915 876 836 797 757
m3/h
4650 173 149 125 103 80
5050 158 133
109
84 60
5450 141 115 89 63 38
6000
84
56
28 0
035S
r pm
735 704 672 640 609
m3/h
6200 164 142 119 98 77
6650 153 130
106
83 61
7100 139 114 89 66 42
8050 102 75
48
22 n/a
040S
rpm
837 792 748 704 659
m3/h
6950 213 178 143 109 75
7550 196 158
122
86 50
8150 175 136 97 58 21
9050 136 94
53
10 n/a
045D
rpm 937 888 838 788 738
m3/h
7950 272 227 183 140 97
8675 249 201
155
109 63
9400
171 121 72 23
9750
103
51 1
055D
rpm
837 792 748 704 659
m3/h
9950 206 177 148 122 96
10825 195 166
138
110 83
11700 185 154 125 97 68
12850
136
105
75 45
070D
rpm
937 888 838 788 738
m3/h
12450 237 200 163 128 95
13550
183
145
109 73
14650
124 85 48
15090
115
75 36
085D
rpm
937 888 838 788 738
m3/h
14000 202 163 125 87 51
15125 182 142
102
62 23
16250 160 117 75 34 n/a
16725 149 105
63
20 n/a
100D
rpm
750 710 670 630 591
m3/h
17350 237 202 167 133 101
18875 223 185
149
115 81
20400
168 131 94 59
22450
100
63 25
1.- GENERAL CHARACTERISTICS
Static pressure available Absorved power
NOTA: The unit leaves factory with the pulley fi t to two
open turns
1.4.- RETURN FAN PERFORMANCES
1.5.- INDOOR FAN PERFORMANCES. STANDARD
Air fl ow (m3/h)
Return fan
(RPM)
Closed pulley
Pulley
position
1 turn
2 turns
3 vueltas
4 vueltas
Air fl ow (m3/h)
Return fan
(RPM)
Closed pulley
Pulley
position
1 turn
2 turns
3 vueltas
4 vueltas
Air fl ow (m3/h)
Return fan
(RPM)
Closed pulley
Pulley
position
1 turn
2 turns
3 vueltas
4 vueltas
CLOSED
PULLEY
1 TURN 2 TURNS 3 TURNS 4 TURNS
Available static pressure Pa.
Available static pressure Pa.
Available static pressure Pa.
Available static pressure Pa.
Available static pressure Pa.
CLOSED
PULLEY
1 TURN 2 TURNS 3 TURNS 4 TURNS
Available static pressure Pa.
Available static pressure Pa.
Available static pressure Pa.
Available static pressure Pa.
Available static pressure Pa.
7
020S
rpm
1098 1051 1003 956 909
m3/h
3150
324 294 264 237 211
3425
321 289
261
233 207
3700
317 285 257 229 202
4100
310 279
249
222 193
025S
rpm
1098 1051 1003 956 909
m3/h
4250
308 276 246 218 190
4625
301 269
239
209 180
5000
292 260 228 197 167
5500
278 244
211
178 146
030S
rpm
1098 1051 1003 956 909
m3/h
4650
290 259 228 198 169
5050
280 248
215
184 154
5450
269 235 201 169 138
6000
249 213
178
143 109
035S
r pm
937 888 838 788 738
m3/h
6200
321 281 241 203 167
6650
313 272
232
193 155
7100
306 262 221 181 142
8050
282 236
191
148 105
040S
rpm
937 888 838 788 738
m3/h
6950
298 255 214 174 135
7550
283 240
197
155 113
8150
267 221 176 132 88
9050
186
138
90 43
045D
rpm 1041 986 931 876 820
m3/h
7950 371 318 267 217 168
8675 353 298
244
190 139
9400 330 271 215 158 103
9750 316 258
199
141 84
055D
rpm 1041 986 931 876 820
m3/h
9950 357 313 272 232 194
10825 349 304
263
223 185
11700
295 253 213 173
12850
239
196 156
070D
rpm 1041 986 931 876 820
m3/h
12450 321 276 232 191 151
13550 307 262
217
174 133
14650 291 244 199 154 110
15090
236
190
145 101
085D
rpm 1041 986 931 876 820
m3/h
14000 288 242 197 155 112
15125 272 223
177
132 88
16250 253 203 154 107 60
16725 244 193
144
95 48
100D
rpm 837 792 748 704 659
m3/h
17350 323 279 236 196 157
18875 310 264
221
180 140
20400 296 248 204 162 121
22450
178
133 90
020S
rpm
1177 1126 1075 1024 974
m3/h
3150
377 342 309 278 247
3425
373 338
306
273 243
3700
369 334 302 269 239
4100
364 329
295
263 232
025S
rpm
1318 1261 1204 1147 1091
m3/h
4250
466 423 381 341 303
4625
461 418
375
335 295
5000
412 368 327 287
5500
314 273
030S
rpm 1339 1268 1197 876 1055
m3/h
4650
468 413 359 309 261
5050
462 405
352
299 250
5450
454 396 341 289 238
600
441 383
325
270 216
035S
rpm 1103 1044 986 927 869
m3/h
6200
469 414 362 313 266
6650
463 408
356
305 257
7100
458 402 348 297 247
8050
442 383
327
272 220
1.- GENERAL CHARACTERISTICS
1.5.- INDOOR FAN PERFORMANCES
CLOSED
PULLEY
1 TURN 2 TURNS 3 TURNS 4 TURNS
Available static pressure Pa.
Available static pressure Pa.
Available static pressure Pa.
Available static pressure Pa.
Available static pressure Pa.
CLOSED
PULLEY
1 TURN 2 TURNS 3 TURNS 4 TURNS
Available static pressure Pa.
Available static pressure Pa.
Available static pressure Pa.
Available static pressure Pa.
Available static pressure Pa.
VENTILATION HP1
VENTILATION HP2
CLOSED
PULLEY
1 TURN 2 TURNS 3 TURNS 4 TURNS
Available static pressure Pa.
Available static pressure Pa.
CLOSED
PULLEY
1 TURN 2 TURNS 3 TURNS 4 TURNS
Available static pressure Pa.
Available static pressure Pa.
(●) WRONG STATUS ON ACCOUNT OF MOTOR POWER LIMIT.
NOTE: With low distance option it is not suitable unit working below
nominal air fl ow.
NOMINAL FACTORY SETTING.
8
040S
rpm
1103 1044 986 927 869
m3/h
6950
449 393 340 289 239
7550
440 382
327
275 223
8150
427 370 312 257 203
9050
405 344
284
225 168
045D
rpm
1103 1044 986 927 869
m3/h
7950
432 373 317 263 211
8675
415 355
296
240 184
9400
395 332 271 211 152
9750
384 320
256
195 134
055D
rpm
1172 1109 1047 985 923
m3/h
9950
514 456 399 346 296
10825
508 448
391
338 286
11700
500 440 383 328 275
12850
369
313 258
070D
rpm 1172 1109 1047 985 923
m3/h
12450 371 421 363 307 252
13550 470 408
348
289 233
14650 457 391 329 268 208
15090 450 383
320
258 196
085D
rpm 1172 1109 1047 985 923
m3/h
14000 452 390 328 268 211
15125 438 371
307
245 183
16250 418 349 282 215 150
16725 408 338
270
202 135
100D
rpm 937 888 838 788 738
m3/h
8675 477 419 364 312 262
9437 469 410
354
299 248
10200 458 398 341 284 232
11225 440 379
319
261 206
020S
rpm
1318 1261 1204 1147 1091
m3/h
3150
483 438 397 357 319
3425
478 434
393
353 316
3700
474 430 389 349 312
4100
469 425
383
343 305
025S
rpm
1500 1420 1340 1261 1181
m3/h
4250
550 485 423 365
4625
545
480
418 359
5000
541 475 412 352
5500
532
466
402 339
030S
rpm
1500 1420 1340 1261 1181
m3/h
4650
535 469 408 349
5050
529
463
399 340
5450
521 455 391 330
6000
511
443
376 313
035S
r pm
1250 1183 1117 1051 985
m3/h
6200
548 483 421 362
6650
545
478
415 355
7100
539 472 408 347
8050
526
456
390 326
040S
rpm
1250 1183 1117 1051 985
m3/h
6950
602 530 463 399 339
7550
594 522
453
388 326
8150
586 512 442 376 311
9050
570 493
421
351 283
045D
rpm 1250 1183 1117 1051 985
m3/h
7950
589 515 446 381 317
8675
578 501 430 363 295
9400
562 485 411 340 270
9750
553 475 400 326 255
055D
rpm 1339 1268 1197 1126 1055
m3/h
9950 689 612 539 471 406
10825 683 606 533 464 398
11700 677 599 525 457 390
12850
670 590 515 444 376
070D
rpm 1339 1268 1197 1126 1055
m3/h
12450
662 582 508 437 370
13550 652 573
497
424 354
14650 641 561 484 408 336
15090 636 555
477
400 328
085D
rpm 1339 1268 1197 1126 1055
m3/h
14000
636 557 478 406 336
15125 623 542
464
387 315
16250 609 526 445 367 289
16725 602 518
436
357 279
100D
rpm 1041 986 931 876 820
m3/h
8675
606 537 469 407 346
9437 599 529
461
396 334
10200 592 519 451 384 321
11225
504
433
364 299
1.- GENERAL CHARACTERISTICS
1.5.- INDOOR FAN PERFORMANCES. VENTILATION HP2
(●) WRONG STATUS ON ACCOUNT OF MOTOR POWER LIMIT.
NOTE: With low distance option it is not suitable unit working below
nominal air fl ow.
NOMINAL FACTORY SETTING.
CLOSED PULLEY
1 TURN 2 TURNS 3 TURNS 4 TURNS
Available static pressure Pa.
Available static pressure Pa.
Available static pressure Pa.
CLOSED
PULLEY
1 TURN 2 TURNS 3 TURNS 4 TURNS
Available static pressure Pa.
Available static pressure Pa.
Available static pressure Pa.
CLOSED PULLEY
1 TURN 2 TURNS 3 TURNS 4 TURNS
Available static pressure Pa.
Available static pressure Pa.
Available static pressure Pa.
Available static pressure Pa.
Available static pressure Pa.
CLOSED PULLEY
1 TURN 2 TURNS 3 TURNS 4 TURNS
Available static pressure Pa.
Available static pressure Pa.
Available static pressure Pa.
Available static pressure Pa.
Available static pressure Pa.
VENTILATION HP3
9
020S 025S 030S
3150 3425 3700 4100 4250 4625 5000 5500 4650 5050 5450 6000
13 17 20 25 24 31 37 45 28 37 43 54
85 93 102 115 120 133 146 165 133 148 163 184
15 17 20 23 25 28 32 38 29 33 37 44
035S 040S 045D
6200 6650 7100 8050 6950 7550 8150 9050 7950 8675 9400 9750
26 30 34 43 33 38 44 52 42 48 55 58
128 140 152 178 148 164 181 208 175 197 219 230
25 29 32 39 31 35 40 47 38 44 50 54
055D 070D 085D
9950 10825 11700 12850 12450 13550 14650 15090 14000 15125 16250 16725
11 13 16 19 18 21 24 26 22 26 30 32
123 136 150 169 162 181 200 208 188 209 230 239
24 27 31 36 34 39 44 47 41 47 53 55
1.- GENERAL CHARACTERISTICS
1.6.- OPTION PRESSURE DROP (Pa)
Unit models
Airfl ow (m3/h)
Options
Free-cooling
High effi ciency fi lter
Hot water coil
Unit models
Caudal de aire (m3/h)
Options
Free-cooling
High effi ciency fi lter
Hot water coil
Unit models
Airfl ow (m3/h)
Options
Free-cooling
High effi ciency fi lter
Hot water coil
10
055D
7000 8000 9000 10000 10700
741 299 264 225 160 96 709 271 235 195 137 83 677 242 206 165 113 70 645 213 178 135 73 57 613 184 149 105 32 44
070D
7350 8400 9450 10500 11200
741 272 230 182 122 66 709 243 201 153 98 50 677 213 172 124 74 33 645 184 142 95 44 16 613 154 113 66 13 -0.4
085D
7700 8800 9900 11000 11750
751 277 235 187 126 69 719 247 199 159 101 51 686 208 162 120 71 36 654 181 139 89 24 15 621 154 112 65 12 n/a
020S
5300 6100 6850 7600 8100
751 178 156 134 104 77 719 162 140 118 89 64 686 141 118 96 67 38 654 124 101 78 47 6 621 108 86 64 35
(rpm)
(m3/h)
025S
5950 6800 8500 9100
841 223 195 126 91 805 202 174 107 74 769 177 148 88 44 732 154 125 63 7 696 135 107 40 4
(rpm)
(m3/h)
030S
7000 8000 9000 10000
934 272 234 194 142 894 246 208 168 117 854 213 175 134 84 814 186 146 106 55 773 161 123 82 36
(rpm)
(m3/h)
035S
8400 9600 10800 12000 12850
741 209 191 171 146 125 709 189 171 152 126 105 677 168 151 132 107 87 645 148 131 112 88 68 613 128 111 92 69 50
(rpm)
(m3/h)
040S
8200 9350 10525 11700 12500
741 205 188 170 148 709 185 168 150 128 110 677 163 146 128 106 89 645 143 127 109 87 68 613 126 110 91 69 51
(rpm)
(m3/h)
045D
9800 11200 12600 14000
829 237 213 183 136 794 235 187 156 111 758 233 161 130 86 722 231 135 104 72 686 229 109 77 57
(rpm)
(m3/h)
(rpm)
(m3/h)
(rpm)
(m3/h)
(rpm)
(m3/h)
1.- GENERAL CHARACTERISTICS
Closed pulley 1 turn 2 turns 3 turns 4 turns
Closed pulley 1 turn 2 turns 3 turns 4 turns
Closed pulley 1 turn 2 turns 3 turns 4 turns
Closed pulley 1 turn 2 turns 3 turns 4 turns
Closed pulley 1 turn 2 turns 3 turns 4 turns
Closed pulley 1 turn 2 turns 3 turns 4 turns
Closed pulley 1 turn 2 turns 3 turns 4 turns
Closed pulley 1 turn 2 turns 3 turns 4 turns
Closed pulley 1 turn 2 turns 3 turns 4 turns
1.7.- OUTDOOR FAN PERFORMANCE (Pressure available Pa)
STANDARD UNITS WITHOUT OPTIONS
Illegal position because of the limit of engine power
Note: The unit leaves factory with the pulley fi t to two open turns