Lennox CLIMATIC 40 User Manual

Providing indoor climate comfort
CLIMATIC™ 40
MUL43E-1011 10-2011 Original manual translation
User manual
1
1
9 9
10 10 10
11-13
14 14 15
16 16-17 17-18
19
20-22
23
24
25-28
INDEX
CONTENTS PAGE
• INDEX
• DESCRIPTION OF CONTROLS
1.- CLIMATIC 40 CONTROL
2.- DC40 REMOTE TERMINAL (AIRCOOLAIR)
• MENU
• REGULATION
1.- AIRCOOLAIR /COMPACTAIR / FLATAIR
2.- AIRCUBE
• ADVANCED FUNCTIONS
1.- REMOTE ON/OFF
2.- REMOTE WINTER / SUMMER CHANGEOVER
3.- DYNAMIC SET POINT
4.- BMS COMUNICATIONS
5.- LOW NOISE
6.- ANALOGUE / DIGITAL INPUT
7.- TIMING AND DELAYS
8.- DEFROST
9.- CONDENSER FAN SPEED CONTROL
10.- FREE COOLING
• PARAMETERS
• SAFETY DEVICES
• INSTRUCTIONS FOR ASSEMBLY AND INSTALLATION
• ALARMS
2
AIRCOOLAIR / COMPACTAIR / FLATAIR AIRCUBE
DC 40
BM40 BM40
ASC-ASH / ADC-ADH
CSC-CSH / CMC-CMH / CDC-CDH
FMC/FSC-FMH/FSH
KSCM/KSHM
Climatic 40 control, is an electronic device that controls Aircoolair / Compactari / Flatair units (air-air units) and Aircube units (con­densing units). The thermostat allows the following operations:
• Unit ON/OFF.
• Select system operating mode.
• Set point adjustment.
• Alarm signal relay.
• Display temperature, status of unit and pending alarms.
• Programming of time bands.
• BMS comunications.
• Possibility of remote ON/OFF.
Return / remote ambient, evaporator, temperature/pressure con­denser and outdoor temperature probes.
Proportional regulation based on remote ambient /return temperature (cooling, heating and automatic mode).
Defrost cycle (heat pump units), with pressure tranducer.
Condensing pressure control with temperature probe or pressure transducer.
Antifreeze, high and low pressure protections.
Compressors, indoor and o utdoor fans, electrical heater and freecooling (optional) management.
Condenser temperature/pressure probes.
Regulation based on remote free voltage contacts.
Defrost cycle (heat pump units), with pressure tranducer.
Condensing pressure control with temperature probe or pressure transducer.
High and low pressure protections.
Compressors, indoor (optional) and outdoor fans.
DESCRIPTION OF CONTROLS
Condenser
temperature
/pressure
Fan speed
control
Expansión
board
Return air
duct
temperature
Evaporator
temperature
Outside
temperature
Fan speed
control
Expansión
board
Free cooling
motor damper
1.- CLIMATIC 40 CONTROL
Return or
remote
ambient
temperature
3
J
I
KLA
B
C
D
E
G
F
H
A B C D E
F G H
I
L
I+L
J
K
J+K
L+J
DESCRIPTION OF CONTROLS
CLIMATIC 40 CONTROL
The gure and the table below show the symbols present on the display and on the keypad,together with their meanings:
1.1.1.- TURN ON/OFF THE UNIT
The unit is turned on by closing the On/Off contact and turned off by opening it (see section 1, advanced functions, for more details).
1.1.- AIRCUBE
The main screeen shows:
- Ambient temperature for AIRCOOLAIR / COMPACTAIR / FLATAIR.
- Unit status (On/Off) for AIRCUBE.
SYMBOL
DESCRIPTION
LED ON LED FLASHING
1 or 2
Compressor 1 and /or 2 (circuit 1) ON. Start up request.
2 or 3
Compressor 3 and /or 4 (circuit 2) ON. Start up request. At least 1 compressor ON. Indoor fan ON. Start up request. Condenser fan ON. Defrost active. Start up request. Electrical heater ON. Start up request. Alarm active. Cooling mode. Cooling mode request. Heat pump mode. Heat pump mode. Request.
BUTTON DESCRIPTION TIME
Go up a sub-group inside the programming area. Press once Access the direct parameters. Press for 5 s Select item inside the programming area / conrm changes to the parameters. Press once Program parameters afters entering password. Press for 5 s Select top item inside the programming area. Press once Increase value. Press once Switch from standby to heat pump mode and vice-versa. Press for 5 s Provides immediate access to the condenser and evaporator pressure and temperature probes. Press once Select bottom item inside the programming area. Press once Decrease value. Press once Switch from stand-by to chiller mode and vice-versa. Press for 5 s Provides immediate access to the condenser and evaporator pressure and temperature probes. Press once Manual alarm reset. Press for 5 s Immediately reset the hour counter (inside the programming area). Press for 5 s Force manual defrost on both circuits. Press for 5 s
The heating mode is selected by opening the remote changeover contact while the cooling mode is selected byclosing it (see section 2, advanced functions, for more details).
NOTE There are no set points to be made for Aircube units because the compressors are directly controlled by remote contacts.
4
2
41 3
11
7
5
6
10
9
8
POWER
Mode
MODE
FAN
SLEEP
CLOCK
TEMP.
UP/DOWN
1 7
2 8
3 9
4 10
5 11
6
DESCRIPTION OF CONTROLS
2.- DC40 REMOTE TERMINAL (AIRCOOLAIR / COMPACTAIR / FLATAIR)
The illustration and the table below show the symbols that appear on the display and on the keypad and their meanings. OFF appears in the main eld of the display if the machine is off, or the set point if the machine is working.
Secundary functions:
Display symbols:
BUTTON NAME DESCRIPTION
Switch from stand-by to ON and vice-versa.
Change operating mode (cooling, heating, automatic).
Switch the indoor fan from automatic mode to always ON and vice-versa.
ActivateS/deactivateS the sleep mode.
ActivateS/deactivateS the time bands.
ShowS the set point when the unit is OFF.
Set the temperature.
BUTTON BUTTON PRESS FUNCTION
3 seconds Sets sleep differential value of the current operating mode.
3 seconds Sets the time bands (hour, day, set point).
5 seconds Clock setting.
3 seconds Reset alarms.
SYMBOL MEANING SYMBOL MEANING
Heating mode. On/Off time bands.
Cooling mode. Sleep mode.
Automatic mode. Duration or sleep mode.
Set point. Alarm.
Day of the week (weekday, weekend). Indoor fan mode.
Hour/Temperature.
5
This function increases (in cooling mode) or decreases (in heating mode) the operating set point according to the lower level of comfort required during the night. Not possible with time bands program. ACTIVATION Press “ ” button once. The display shows “ ” symbol with “1HR” ashing.
In this way, sleep function will work for 1 hour. If you want it to work for longer, press “ ” button repeatedly while “1HR” is still ashing (each press of the button increases by
1 hour, till max 9 hours). Finally, the display shows the “ ” symbol with the number of hours you choose. DEACTIVATION Press the “ ” button once and the sleep function will be deactivated (if it was activated before). The “ ” symbol disappears from the display. DIFFERENTIAL SETTINGS Press “ ” button for 3 seconds. The sleep differential (the value by which you increase or decrease the comfort set point) appears on the display. Use the “ ” buttons to set the value, then press the “ ” button to accept. Note that cooling and heating modes have different sleep differential values, so you can modify only the current operating mode’s value.
To set current time:
1. Press the “ ” button for 6 seconds. “rtc” and current time appears on the display (hours are ashing).
2. Set the hour using the “ ” buttons.
3. Press the “ ” button to accept. Minutes start ashing on the display.
4. Set the minutes using the “ ” buttons.
5. Press the “ ” button to accept. “day” and the number of the day of the week appear on the display (Monday=1, Tuesday=2 etc.)
6. Set the day by using the “ ” buttons.
7. Press the “ ” button to accept.
2.1.- TURN ON/OFF THE UNIT WITH REMOTE CONTROL DC40 (AIRCOOLAIR / COMPACTAIR / FLATAIR)
2.2.- SELECTING THE UNIT´S OPERATING MODE
Once the unit is turned on, you can select Cooling, Heating or Automatic mode just pressing the “Mode” button. In the automatic mode you just choose the set point and the system automatically switches from cooling to heating mode, depending on the position of the ambient temperature with respect to the set point.
2.3.- SELECTING DESIRED ROOM TEMPERATURE
If unit is working, the “ ” buttons allow the desired room temperature to be select (set-point). The “↑” button allows the current set point to be increased by 0.5ºC. The “↓” button allows the current set point to be decreased by 0.5ºC.
2.4.- SELECTING THE FAN OPERATING MODE (Aircoolair)
In order to be able to select a fan operating mode, the unit’s operating mode (cooling, heating or auto) must be selected. Pressing the side button “ ” scrolls through the following modes: FAN CONSTANTLY ON, or AUTO FAN CONSTANTLY ON: Fan is ON continuously and the “ ” simbol will appear. AUTO: Fan on and off together with the compressor or with the freecooling, the “ ” symbol will appear.
2.5.- SLEEP FUNCTION
2.6.- CLOCK SETTINGS
To turn on the unit press the “ ” button. The display shows current operating mode.
DESCRIPTION OF CONTROLS
2.7.- TIME BANDS PROGRAM
This function allows you to programme time bands during the week, each one with a different set point. In this way you can adapt
the cooling/heating provided by the unit according to each moment of the day.
You can set two time bands for the weekdays and another two for the weekend.
NOTE: For units without remote control DC40, fan operating mode can be selected with parameter H05=1 (continuous operating mode) or H05=2 (automatic operating mode).
6
23ºC 23ºC
OFF
OFF
DESCRIPTION OF CONTROLS
CONFIGURATION
NOTE: You must set the DC40 clock before programming time bands. Time bands programs keep current operating mode (if it was in cool mode, it keeps working in cool mode; if it was in auto matic mode, it keeps working in automatic mode, etc.).
EXAMPLE IN SUMMER
a) Enter time bands menu. b) Set 1ST time band for weekday start hour. c) Accept.
d) Set 1ST time band of weekday start minutes. e) Accept. f) Set 1ST time band of weekday set point (on/off/tem-
perature).
g) Accept. h) Repeat steps b-c-d-e-f-g to programme 2nd time
band for weekdays.
i) Repeat steps b-c-d-e-f-g-h to programme the two
time bands for weekends.
Weekdays
Time band 1
ashing
Flashing
Flashing
Flashing
Time band 2
Weekend
Flashing
ACTIVATION
DEACTIVATION
3 sec.
Weekdays
Hour
8:00 (Time band 1)
18:00 (Time band 2)
Weekend
7
b) Set password “ 22 ” by the “ ” and “ ” buttons.
MENU
A) PROBES DISPLAY MENU
Press the “ ” button to enter probes display menu.
“ b01” or “b02”, appears on the display (depending on the unit’s conguration).
Once the probe is selected, after a few seconds, “b01” turns into its temperature/ pressure measure.
Press “ Sel ” button for 5 seconds. “ ”, appears on the display. Move inside the menu as explained below.
1 sec.
5 sec.
B) SETPOINT SETTINGS AND OPERATING HOURS DISPLAY MENU
C) PARAMETERS EDITING MENU
a) Press “ Pgr ” and “ Sel”, at the same time, for 5 seconds.
c) Press “ Sel ”, to accept.
d) Press “ Sel ”, to enter parameters Editing menu.
Go up a sub-group inside the programming area.
UP or increase valve.
Down or decrease valve.
Go down a sub-group or accept
parameter modications inside
the programming area.
5 sec.
Access to the menu:
To go to different values in the menu, proceed as above, the:
8
MENU
NOTES:
a) Parameters that have been modied without being conrmed using the “ Sel ” button will return to their previous value. b) After conrming a modication, escape up to the main menu to save it; otherwise, modications will be cancelled. c) If no operations are performed on the keypad for 60 seconds, the controller exits the parameter editing menu on timeout
and any changes are cancelled.
MENU TREE
PROBES SETTINGS
ATIFREEZE AND
ELECTRICAL HEATER
PROBES
COMPRESSORS
DEFROST
FANS
UNIT SETTING
ALARMS
REGULATION
TIMER SETTING
SOFTWARE
9
SP 8 32 23 8 32 23 8 32 23
r2 0.3 50 1 0.3 50 2 0.3 50 3 r4 0.3 50 1 0.3 50 2 0.3 50 3
r7 0.3 50 0.5 0.3 50 0.5 0.3 50 0.5 A8 0 20 1.5/2.5 0 20 1.5/3.5 0 20 1.5/4.5 A9 0.3 50 1 0.3 50 1 0.3 50 1
A11 0 20 2.5/3.5 0 20 2.5/4.5 0 20 4.5
REGULATION
1.- AIRCOOLAIR / COMPACTAIR / FLATAIR
Ambient (or return air duct) temperature is thermostatically controlled via set point and tolerance range (differential) as shown in the following diagrams:
1.1- AUTOMATIC MODE (with DC40) (Heat pump)
1.3- AFFECTED PARAMETERS
2.- AIRCUBE
Aircube is regulated by digital input. (see section 7, advanced functions, for more details).
HEAT COOL
HEAT
COOL
Ambient
temperature (ºC)
Ambient
temperature (ºC)
Par. DESCRIPTION
UNIT 1 COMPRESSOR UNIT 2 COMPRESSORS UNIT 3 COMPRESSORS
MIN. MAX. DEF. MIN. MAX. DEF. MIN. MAX. DEF.
Set point (DC40). Cooling differential. Heating differential. Dead zone. SP E.H. 1 stage (cooling only/heat pump) Differential E.H. SP E.H. 2 stages (cooling only/heat pump)
1.2- AUTOMATIC MODE (Cooling only+Electrical heater)
NOTE: With option Modbus, set point SP is managed through communications instead of DC40 (see table for Modbus parameters)
Loading...
+ 22 hidden pages