Lennox Cambria User Manual

Page 1
INSTALLATION AND
TM
OPERATION INSTRUCTIONS
CAMBRIA™
Wood-Burning Fireplace P/N 850,057M REV. C 11/2008
MODEL
CAMBRIA
This installation manual will enable you to obtain a safe, efficient and dependable installation of your fireplace system. Please read and understand these instructions before beginning your installation or operating the fireplace.
CAUTION: Do not alter or modify the fireplace or its components under any circumstances. Any modification or alteration of the fireplace system, including but not limited to the fireplace, chimney components and accessories, may void the warranty, listings and approvals of this system and could result in an unsafe and potentially dangerous installation.
SAVE THESE INSTRUCTIONS
FOR FUTURE REFERENCE
WARNINGS
• Hot! Do not touch! The glass and surfaces of this appliance will be hot during operation and will retain heat for a while after shutting off the appli­ance. Severe burns may result.
• Carefully supervise children in the same room as appliance.
• If small children are present in the home, it is recommended that this appliance be fitted with a firescreen kit.
Listed to standards: ULC-S610 and UL-127 Report No. 3092554
Lennox Hearth Products wood-burning fireplaces are designed for use as a supplemental heater. They are not intended for continuous use as a primary heat source.
WARNINGS
• The fireplace cannot be operated without a door. Consult your dealer to select the correct door model.
• Important! To assure proper alignment of glass doors: Install this fireplace in a square and plumb condition, using shims as necessary at sides and/or bottom.
• Install the fireplace only as described in these instructions.
PICAMBRIA-A REV. 3 NOV 2008
Page 2
IMPORTANT! GENERAL SAFETY PRE CAU TIO NS. REA D AN D UNDERSTAND THESE SAFETY RULES BEFORE YOUR FIRST FIRE.
The CAMBRIA™ fireplace must be installed with an outside air kit intake, which is included with the fireplace
THE FIREPLACE MUST BE OPER­ATED WITH THE DOORS FULLY OPENED OR DOORS FULLY CLOSED. IF THE DOORS ARE LEFT PARTLY OPENED, GAS AND FLAME MAY BE DRAWN OUT OF THE FIREPLACE OPENING, CRE­ATING RISKS OF BOTH FIRE AND SMOKE. IF THE UNIT IS OPER­ATED WITH THE DOORS FULLY OPENED, THE FIRE SCREEN MUST BE USED.
For spectacular fire view and optimum efficiency of your fire­place, we recommend that the wood be placed as far back as possible in the fireplace.
NEVER use gasoline, gasoline­type lantern fuel, kerosene, charcoal lighter fluid, naphtha, engine oil or similar liquids to start or “freshen up” a fire in this fireplace. Keep any flammable liquids a safe distance from the fireplace at all times.
THIS FIREPLACE HAS NOT BEEN TESTED WITH AN UNVENTED GAS OR A FIREPLACE INSERT. TO REDUCE RISK OF FIRE OR INJURY, DO NOT INSTALL AN UNVENTED GAS LOG SET OR FIREPLACE INSERT OR OTHER PRODUCTS NOT SPECIFIED FOR USE WITH THIS FIREPLACE.
2
WARNING
WARNING
WARNING
CAUTION
WARNING
WARNING
Never leave your fireplace unat­tended while it is burning.
CAUTION
Use care when selecting window treatments for windows located near the fireplace. Avoid using combustible flowing window treatments such as curtains on nearby windows that are of sufficient length to be blown in front of an open flame when the
window is opened. Keep any combustible furniture,
materials or decorative pillows at least 48" (1219 mm) from the front fireplace opening.
IMPORTANT
When burning wood, use SOLID NATURAL DRY WELL-SEASONED WOOD ONLY. Hardwoods are recommended (soft woods tend
to burn very quickly).
• DO NOT burn treated wood, charcoal, coal, trash, card­board, driftwood, woods dipped in tar, Christmas tree greens, pitch, pine tar, creosote, chemi­cal chimney cleaners, flame colorants, polystyrene packag­ing, wood products with synthetic binders (i.e. plywood). Plywood, lumber and other misc. materi­als can produce abnormally high temperatures, sputtering and smoking fires and may contain hazardous chemicals to treat insects and fungus.
• Burning unapproved fuels can produce excessive temperatures (overfiring), beyond the design capabilities of the fireplace and may produce excess sparks or may contain hazardous chemi­cals. Burning unapproved fuels can result in a chimney fire, a house fire, personal injury, death or loss of property.
WARNING
Never leave children unattended when there is a fire burning in the fireplace.
WARNING
To avoid the risk of damaging fireplace materials and increas­ing the risk of fire, do not use the fireplace to cook or warm food.
WARNING
Be careful adding wood fuel to the fire or handling fireplace tools such as shovels, tongs or pokers.
WARNING
Never modify or alter your fire­place system in any way. To do so may create a potential fire hazard and void the warranty, listings and approvals of this system.
WARNING
The bottom refractory can be cracked by excessive abuse such as tossing heavy logs onto the grate or gouging with fireplace tools. Exercise caution when adding wood to your fireplace.
Neither the manufacturer nor the seller warrants “smoke free” operation nor are we responsible for inadequate system draft caused by mechanical systems, general construction conditions, inadequate chimney heights, adverse wind conditions and/or unusual environmental factors or conditions beyond our control.
Always ensure that the air inlet to the fireplace is free from debris and any other obstructions that can block the entrance of air.
WARNING
WARNING
Page 3
CONGRATULATIONS!
OPTIONAL EQUIPMENT
In selecting this Lennox Hearth Products wood-burning appliance you have chosen one of the finest fireplaces available. The Cambria™ fireplace is an efficient heat circulat­ing fireplace that is designed to provide you dependable service as well as warmth and enjoyment for many years to come.
Please carefully read and follow all of the instructions found in this manual. Please pay special attention to the safety instructions provided in this manual. This information will be useful to you now and in years to come, so keep the manual handy and refer to it as needed.
TABLE OF CONTENTS
Safety Rules ......................................Page 2
Introduction ......................................Page 3
Parts Required .................................Page 3
Optional Equipment ........................... Page 3
Operating The Fireplace ....................Page 3
Fuel ...................................................Page 3
Combustion Control .........................Page 4
Refueling For Best Performance .......Page 5
Smoking – Causes And
Troubleshooting ..........................Page 5
Important Cautions ...........................Page 6
Maintaining Your Fireplace ...............Page 6
Creosote ............................................ Page 6
Chimney Maintenance .......................Page 6
Dealing With A Chimney Fire .............Page 6
Disposing of Ashes ...........................Page 6
Door Finish Casing Care ....................Page 6
Refractory Replacement ....................Page 6
Door Installation ...............................Page 6
Door Adjustment ...............................Page 7
Glass Care .........................................Page 8
Gasket Replacement ........................Page 8
Andirons ...........................................Page 8
Fireplace Installation ........................Page 9
Locating The Fireplace ......................Page 9
Framing, Facing And Mantel .............. Page 10
Hearth Extension Requirements .......Page 10
Cold Climate Installations .................. Page 10
Framing Dimensions .........................Page 11
Insulated Chase Construction ...........Page 12
Mantel and Facing .............................Page 13
Optional Fireplace Blower ..................Page 13
Hot Air Ducting Installation ..............Page 14
Gravity Kit .........................................Page 14
Outside Air Kit ..................................Page 16
Chimney System ...............................Page 17
Offset Chimney Installation ...............Page 20
Angled Wall Radiation Shield ............ Page 22
Chimney Support Installation ............Page 22
Chimney Chase And
Multiple Terminations......................Page 22
Installation Accessories ....................Page 23
Chimney Components Lists ..............Page 23
Replacement Parts ............................Page 25
Specifications .................................... Page 25
Clearances ........................................Page 25
Product Reference Information .........Page 26
THE FIREPLACE
INTRODUCTION
The Cambria™ wood-burning fireplace is a mid-efficient, heat radiating fireplace. You will receive a lifetime of comfort and enjoyment from your fireplace provided it is installed, maintained and operated properly.
Please read these instructions and retain
this manual for future reference.
Before beginning the fireplace installation,
consult the local authorities to obtain your building permit and check your local building codes. Install the fireplace only as described in these instructions and using only Lennox Hearth Products components.
• These appliances are not approved for Manufactured Home installations.
• When planning a fireplace installation the following information must be determined before beginning.
1. Where the fireplace is to be installed.
2. The configuration of the chimney.
3. Optional components installation (fan, hot air ducting, etc).
4. Electrical wiring.
5. Framing and finish details.
PARTS REQUIRED
Fireplace model: Cambria
10” diameter chimney - Model Secure Temp
ASHT+,
or Nova Temp steel chimney or 10” (AC) air-cooled manu­factured by Security Chimneys International only, including:
- Chimney lengths
- Elbows (where necessary)
- Associated components as per these installation instructions
HT6103+
insulated stainless
Outside air kit (included)
5” flexible venting system (central forced
air kit) (see section 3.5.2)
UZY5 blower. The blower installation re-
quires that an electrical connection of a 120v electrical box located outside the fireplace be made prior to moving the fireplace in its final position. (see Optional Fireplace Blower on Page 13)
Gravity venting system (see Central Forced
Air Kit on Page 15)
OPERATING THE FIREPLACE
Fuel - USE SOLID NATURAL WOOD FUEL ONLY. The Cambria fireplace is designed to
work best when fueled with seasoned cordwood. Hardwoods are preferred to softwoods since the energy content of wood is relative to its density. Hardwoods will result in a longer burning fire and less frequent refuelling. A moisture content of 15% to 20% (seasoned) is recommended. Wood that has been cut and split and let to dry under a cover for a period of one year will usually meet that criteria. Excessively wet wood will be difficult to burn and will result in lower efficiency, increased creosoting and deposits on the glass and in the chimney. Excessively dry wood will burn well but will also have higher emissions and shorter burning time.
Do not burn scrap or garbage, treated wood or wood such as driftwood from the ocean which has been exposed to salt or other chemicals. Salt or chemicals can corrode the firebox and chimney. Do not burn large amounts of paper, cardboard, Christmas tree branches or build­ing construction materials. Intense firing with these materials may overheat the fireplace, causing damage to the unit, a fire or even possibly igniting a chimney fire if the chimney is creosoted.
Processed firelogs can be used. Although, do not poke or stir the logs while they are burning. Use only firelogs that have been evaluated for the application of fireplace and refer to firelog warnings and caution markings on packaging prior to use.
3
Page 4
First Fires
Before using the fireplace make sure to remove the plastic wrapping on the door. Remove all remaining glue with mild soap. Make sure the doors are properly adjusted, thus avoiding color change to finish due to overheat.
The first 5 or 6 fires should be small fires of short duration (about 30 to 60 minutes). This
will help cure the refractory bricks. The first fires may produce slight smoking (and odor) due to drying of the paint and steel and any dust ac­cumulated on the fireplace will burn off at this time. It may set off a smoke alarm located in the same room. For this reason the room should be well ventilated for the first few fires.
Chimney
Damper
(A)
Open Back
Open
Ouvert
Figure 2 -
Accelerated Combustion
Medium Combustion
Closed
Ferme
HEAT OUTPUT
The Cambria™ fireplace is a mid-efficiency fireplace. In spite of the heat that the Cambria fireplace can deliver, it should not replace the main source of heat in your home. This fireplace will bring extra warmth and ambiance to your home by distributing its heat as described further in the manual.
FOR MAXIMUM HEAT OUTPUT, WE STRONGLY RECOMMEND THE INSTALLATION OF HOT AIR DUCTING SYSTEM (See Page 14).
Combustion Control and Chimney Damper
The Cambria fireplace includes a combustion air control that sets the flow of air entering the firebox and control the fire. The fireplace also includes a chimney damper that is not a combustion control. The chimney damper must always be in fully open position when the fireplace is used and should be closed only when all ashes are cold.
The chimney damper is controlled by the handle inside the firebox (see Figure 1-A). It is in closed position when the handle is visible (front) and in the open position when not visible (pushed back). The combustion air damper is controlled by the lower handle (see Figure 1-B). The control can be moved from open position at left all the way to the close position at right.
This air combustion control should be in the closed position when the fireplace is not in operation. This will minimize air infiltration.
The combustion air control should be opened before opening the doors to minimize the possibility of back draft coming into the room (see Figure 1-A). Also see Smoking
- Causes and Troubleshooting for more details (on Page 5).
Closed
Front
Combustion Air
Control (B)
Open
Closed
Figure 1
Accelerated Combustion
The maximum heat output for the Cambria fireplace is achieved by burning with the door closed and the combustion air opened. How­ever, it will be necessary to reload with wood every hour. This is the least efficient method of burning the Cambria fireplace. Use caution when burning with the combustion air control wide open. Only burn cordwood in this manner. Small dry pieces of softwood will burn very intensely using this method and may damage the firebox.
This is the recommended mode of operating the Cambria fireplace and should be the one normally used since it will deposit the least amount of creosote on the glass and in the chimney. The combustion air control must be 3/4 closed .The precise setting will depend on many factors, including chimney length and the moisture content of the wood.
For instance, a long chimney will necessitate closing the damper more. To obtain the proper combustion, close the damper completely, then open it about 1/4” to 1/2”. Three medium size pieces of cordwood burning on a bed of hot coals will burn about 1-2 hours. Softwoods may be burned using this method but the combustion time will be substantially reduced.
FOR MAXIMUM HEAT OUTPUT, WE STRONGLY RECOMMEND THE INSTALLATION OF THE OPTIONAL HOT AIR DUCTING SYSTEM.
Open
Ouvert
Closed
Ferme
Figure 3 - Medium Combustion
WARNING: The air combustion control must be in the open position if the fire­place is operated with the doors open.
4
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 5
Building a Fire
A) To start a fire, place several crumpled up
balls of newspaper in the firebox. Place small dry pieces of kindling on top of the paper, criss-crossing the kindling so that there are air spaces in between. The kindling should be placed at the center of the firebox so as to allow for sufficient air circulation.
B) Open the dampers and light the newspaper.
Leave the doors partially opened (1 to 2 inches) to facilitate the start-up.
C) Once kindling fire is well established, cord
wood can be added. Close the doors and leave the combustion air control open in accelerated combustion position.
D) When the fire burns well set the primary
control to the desired burn level.
The unit will burn best with 2-3 pieces of
cordwood spaced 1 to 2 inches apart and allowing air to get under the fuel. Criss­crossing or arranging the fuel so that air can get underneath will help the fire to get started easily. The unit should be operated with the air control fully open long enough to get the cordwood well ignited.
WARNING: The Cambria™ fireplace was de­signed to allow a spectacular view of the fire. The Cambria fireplace should never be filled in excess (five big logs or more). Excessive fire could damage the fireplace’s hearth and refractory brick and void the warranty.
REFUELING FOR BEST PERFORMANCE
To reload the Cambria fireplace:
A) Completely open the combustion air control
(see Figure 2).
B) Open the doors about 1” and wait 5 seconds
until the airflow has stabilized. Then open the doors completely, put the logs in and close the doors.
C) Set the combustion air control to the desired
burn level.
Notes:
• For spectacular fire and optimization of the fireplace efficiency, we recommend that the wood load be placed as far back as possible.
• It may be necessary to turn off any blower(s) in operation during the refueling process in order to minimise smoking in the room. It is recommended to wait 15 to 30 minutes before turning the blower(s) back on to ensure successful rekindling.
SMOKING – CAUSES AND TROUBLESHOOTING
To reduce the likelihood of smoke coming into the room when opening the door, set the combustion air controls to the left (“Acceler­ated Combustion”) before opening the door. Your fireplace has been designed and tested to provide smoke free operation. Occasionally, there may be a small amount of smoking upon lighting the fire until the chimney heats up. If the fireplace continues to smoke it is probably
-
for one of the following reasons:
A. The doors are partially opened When you open the doors, open them com
pletely.
B. Negative pressure in the house A fire needs air to burn. This air must be
replaced through the outside air duct (see Outside Air on Page 16). When operating the Cambria fireplace, open a nearby window temporarily to check if there is adequate replacement air supply.
C. Fans operating (e.g.: range hood) Fans such as range hoods or bath fans draw
air out of the house and may actually cause a negative pressure in the house. Turn off all fans and open a nearby window to determine if this is the cause of the problem.
D. Wet wood Wet or tarred wood will smoulder and smoke
instead of burning properly. Your dealer can help you determine if you have properly seasoned wood for burning.
E. Dirty or blocked chimney Check to make sure the chimney is clear and
clean. If dirty call a certified chimney sweep or use a properly sized chimney brush to clean.
F. Chimney not long enough
The minimum chimney height is 15 feet (4.6
m) not including the fireplace height. The chimney must extend at least 3 feet (915 mm) above its point of contact with the roof and at least 2 feet (610 mm) higher than any roof or wall within 10 feet (3 m) of it. When installed with offsets, the minimum chimney height is 18 feet (5.5 m). Additional height will increase draft and will decrease the tendency to smoke.
G. Poor chimney draft
With no fire, there should be sufficient draft
to exhaust cigarette smoke introduced under the baffle. Chimneys installed against an outside wall without protection may gener­ate back draft problems which will cause start-up problems. To prevent this, open a nearby window; roll up a piece of paper, light it and hold it in the upper part of the firebox to warm up the chimney. Wait until the draft is sufficient, then start the fire.
H. Blower for central forced air kit
Make sure that the blower is at the “off”
position when you open the fireplace door for reloading.
GAS LOG INSTALLATION
This fireplace is designed to allow the installation of a gas burner. In such a case, the installation must conform with the National Gas Code ANSI Z223.1 and Z21.60. Warning: When using a
gas burner, it is mandatory to keep the chimney outside air register opened.
This fireplace has provision for the installation of a gas pipe and is intended only for connection to a decorative gas appliance incorporating an automatic shutoff device and complying with ANSI Z21.60-M96/CGA 2.26-M96, Standard for Decorative Gas Appliances for Installation in Solid-Fuel Burning Fireplaces (reference
­Clause 4.1.3 T).
1. Remove the 1 inch knock-out on the right side of the fireplace and on the right side refractory.
2. Drill a one inch hole in the hearth right side coaxial to the refractory opening.
3. Assemble a rigid 3/8” N.P.T. iron pipe with two 90º elbows. Make sure to have 5-11/16” clearance between the two pipes (see Figure
4).
4. Through the hearth bottom or back openings insert the mounted pipe through the side of the firebox and the firebrick. Make sure the top elbow is as close as possible to the hearth to keep a minimum clearance to the retractable door.
5. Insert a pipe through the 1 inch exterior knock-out and fix it to the 90º elbow already in place.
Note: In some regions, the use of a flexible gas pipe is allowed. Consult your local authority.
5-11/16” (145mm)
Figure 4
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
5
Page 6
IMPORTANT CAUTIONS
A. Do not block the hot air vents to the fire-
place as this will cause the fireplace to overheat.
B. Never use gasoline, gasoline-type lantern
fuel, kerosene, charcoal lighter fluid, or similar liquids to start or ‘freshen up’ a fire in this fireplace. Keep all such liquids well away from the fireplace while it is in use.
C. Do not burn coal. The sulphur in coal will
corrode the firebox and chimney.
D. Keep combustible materials at least 48”
(1.2 m) away from the front of the fireplace opening.
E. Never leave children unattended when
there is a fire burning in the fireplace.
F. Use only untreated wood. Wood protectors,
metallic paper, coal, plastic, waste, sulphur and/or oil will damage the fireplace.
G. Do not use the CAMBRIA as an incinerator
to burn paper, cardboard or construction material such as pressed wood, plywood or lumber. Wood protectors, metallic paper, coal, plastic, waste, sulphur and/or oil will damage the fireplace.
H. Do not burn driftwood which has been in the
ocean or salt water. The salt will corrode the firebox and chimney.
I. Do not burn wood in the area in front of the
grate.
J. Do not allow the wood to smoulder or burn
without flame, since this will produce excessive creosote in the unit.
MAINTAINING YOUR FIREPLACE
Creosote - Formation and Need for Removal
When wood is burned slowly, it produces tar and other organic vapors, which combine with expelled moisture to form creosote. The creosote vapors condense in the relatively cool chimney flue of a slow-burning fire. As a result, creosote residue accumulates on the flue lining. When ignited this creosote makes and extremely hot fire.
The chimney shall be inspected at least twice a year during the heating season to determine when a creosote buildup has occurred.
When creosote has accumulated it shall be removed to reduce the risk of a chimney fire.
When the creosote accumulation is large, a creosote fire in the chimney can damage the chimney and overheat the surrounding wood framing. Creosote formation in a chimney can be minimized by making sure there is always visible flame burning, avoid smouldering fires and by proper refuelling techniques.
Chimney Maintenance - Regular chimney inspection and maintenance combined with proper operation will prevent chimney fires. Keep your chimney clean. Do not allow more than 1/16” (1.6 mm) creosote build up in your chimney. The amount of creosote will depend on variables such as frequency of use and type of fire. We recommend that you:
6
A. Initially inspect the chimney system weekly.
From this, you will learn how often it will be necessary to clean your chimney.
B. Have your chimney cleaned by a qualified
chimney sweep. If you wish to clean it your­self, we recommend using a stiff plastic or non-metallic brush. If a metal brush is used, its size should be slightly smaller than the flue to avoid damaging the chimney. Do not use a brush that will scratch the stainless steel interior of the chimney.
Warning: The chimney damper must be opened when sweeping the chimney to avoid ash and creosote accumulation in the fireplaces air circulation area.
C. Do not expect chemical cleaners to keep
your chimney clean. The rain cap can be removed for inspection and/or cleaning of the chimney.
Dealing With a Chimney Fire
Regular chimney maintenance and inspection can prevent chimney fires. If you have a chimney fire, follow these steps:
IMPORTANT: Close the fireplace door and
1.
the combustion air controls; this will stifle the fire.
2. Alert your family of the possible danger.
3. If you require assistance, alert your fire department.
4. If possible, use a dry chemical fire extin guisher, baking soda or sand to control the fire. Do not use water as it may cause a dangerous steam explosion.
5. Ensure that sparks and hot embers coming out of the chimney are not igniting the roof.
6. Do not use the fireplace again until your chimney and fireplace have been inspected by a qualified chimney sweep, your dealer, or a fire department inspector.
DISPOSING OF ASHES
Remove ashes only when the fire is out and the ashes are cold (24 to 48 hours after the fire is out). Always use a metallic container to dispose of the ashes.
WARNING
Disposal of Ashes: Ashes should be placed in a metal container with a tight fitting lid. The closed container of ashes should be placed on a non-combustible floor or on the ground well away from all combustible materials, pending final disposal. If the ashes are disposed of by burial in soil or otherwise locally dis­persed, they should be retained in the closed container until all cinders have thoroughly cooled.
Refractory Brick Replacement (refer to Figure 6)
The intense heat of the fire will normally cause hairline cracks in the refractory brick. These cracks can be minimized by proper curing as described in First Fires on Page 4. They will not normally diminish the effectiveness of the refractory brick. If large cracks develop, then the refractory should be replaced. To replace the refractory bricks, follow these steps:
1. Remove the front refractory bricks
2. Remove the andirons
3. Remove the side refractory supports
4. Remove the side refractory bricks
5. Remove the back refractory brick
6. Remove the bottom refractory brick
To install the new refractory bricks, follow the above steps in reverse.
DOOR FRAME FINISH CARE
Use a glass cleaner and a soft cloth to polish the casing. Do not use abrasives such as steel wool, steel pads or an abrasive polish for they may scratch the frame’s finish.
Door Installation (refer to Figure 5)
­The doors on the Cambria fireplace are factory
installed. To remove the doors, remove the finishing trim, then simply pull them up from the hinges. The door adjustment has been set at the factory. If the fit is still not perfect, you can adjust the door using the hinge screws. (See Figure 8, #1)
Figure 5
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 7
1. Front Refractory Brick
2. Andirons
3. Side Refractory Supports
4. Side Refractory Bricks
5. Back Refractory Brick
6. Bottom Refractory
Figure 6
WARNINGS
• Use only a Lennox Hearth Products glass doors, spe­cifically designed for the Cambria fireplace.
• The fireplace cannot be oper­ated without a door. Consult your dealer to select the cor­rect door model.
• Important! To assure proper alignment of glass doors: Install this fireplace in a square and plumb condition, using shims as necessary at sides and/or bottom.
DOOR ADJUSTMENT
The doors are factory adjusted for proper air tightness and fit. They may need to be readjusted if the alignment has shifted in freight.
To readjust the door side to side position, un­screw the fireplace hinges or the door hinges. Move the doors side to side until the top of the two doors are aligned (Figure 7).
The gaskets’ air-tightness can be adjusted us­ing the adjustment screw located on the slider stoppers (see Figure 8). Turning the screws clockwise will shorten the travel of the slider and increase the pressure on the door side gaskets. This may lead to the doors being harder to lock, so a good adjustment must be found between a good gasket seal and easy door lock (see
Figure 8
, balloon #1).
The door lock can also be adjusted. Remove the front refractory brick and loosen the two screws in the middle front of the firebox bottom. Push or pull on the handle of the door lock. Pushing the handle will tighten the door seal in the center of the fireplace (see Figure 9).
Door
Figure 7
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Door Hinges
1. Adjustment Screw (adjusts
Figure 8
Figure 9
tightness of door seal)
2. Slider Stoppers
Door Lock Adjustment Screws
Tighten
Loosen
Door Opening Adjustment
The doors opening angle can be adjusted. This allows the doors to slide in the fireplace without interference or friction with the finishing fac­ing, which could damage the paint. The screws located under the bottom hinges (Figure 11) are used as door opening stops. Tightening or loosening these screws will keep the door handle from hitting the finishing facing and won’t allow friction between door gasket and hearth when the door is fully pushed in the fireplace.
Bearing Maintenance
The doors are assembled on retractable slid­ers using roller bearings for easy movement. Cambria fireplace has been designed to ensure that bearing maintenance is easy. Remove the decorative facing by unscrewing the four decorative caps and the four screws holding the facing. Remove the doors by lifting them up from the female hinges (see Figure 5). Remove the slider stoppers (see Figure 8) and take the slider bearing assembly out of the fireplace. Unscrew the nuts to change the bearings (see Figure 10). Original bearing contains no grease to resist heat. Adding grease or chang­ing bearings with greased bearing may cause a malfunction of the slider. Please use Lennox Hearth Products replacement parts only (see Page 25 for part numbers).
7
Page 8
GLASS CARE
Gasket Replacement
Figure 10
Unscrew the nuts to change the bearings
Glass Replacement
The glass used for the Cambria™ fireplace is a high temperature ceramic glass (1400°F). If the glass breaks or cracks, it must be replaced with an identical ceramic glass. Tempered glass or ordinary glass will not withstand the high temperatures of the Cambria fireplace. Replacement glass should be purchased from a Lennox Hearth Products dealer (see “Replace­ment Parts” on Page 25).
Do not operate the unit with cracked or broken glass.
Glass Cleaning
The Cambria fireplace is designed to keep the glass clean under normal operating condi­tions. If the Cambria fireplace is operated continuously with the combustion air controls closed, the glass will tend to get dirty unless the fuel, firebox and glass are maintained at hot temperatures. To clean the glass, there are a number of specially designed cleaners to remove creosote. Your authorized Lennox Hearth Products dealer can recommend a suit­able cleaner. Regular household glass cleaners will not clean creosote. Do not use abrasives such as steel pads, steel wool or oven cleaner as they will scratch the glass.
Remove the doors from the unit (see Door Installation on Page 6) and lay them on a clean nonabrasive surface. To replace the gasket, first remove all of the old gasket and gasket cement. Make sure that the surface is totally clean before applying new cement (a high temperature sili­cone caulking rated at 500°F / 260°C, is suitable) or adhesion problems may result. Apply gasket cement to the gasket channel and install the new gasket. This replacement part is available from your Lennox Hearth Products dealer in the dimensions shown in Table 1.
Gasket Part # Dimensions Qty
Around
the door
PR-SR1823N 58-3/4”
5/8” dia.
2
Table 1
Andirons
The Cambria fireplace is equipped with and­irons designed to keep logs from falling into the door. It must be replaced only by Lennox Hearth Products andirons available from your dealer. No other andirons, log retainer or log support is sold or recommended by Lennox Hearth Products.
Door Angle (hang) Adjustment Screw
Figure 11
DO NOT USE CHEMICAL GLASS CLEANERS ON PAINTED SURFACES AS IT MAY CAUSE THE PAINT TO PEEL.
CAUTION : DO NOT ALLOW WINDOW CLEANER TO GET IN CONTACT WITH DOOR GASKET OR PAINT ON FACADE OR DOOR. ONCE CLOSED, CONTACT OF GLASS CLEANER WITH THE FIREPLACE FACADE CAN PROVOKE PAINT PEELING OFF.
8
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 9
FIREPLACE INSTALLATION
Locating The Fireplace
The best location to install your fireplace is determined by considering the location of windows, doors, and the traffic flow in the room where the fireplace is located, allowing space in front of the unit for the hearth extension and the mantel, and taking into consideration the loca­tion of the hot air ducts (optional), outside air kit and chimney. If possible, you should choose a location where the chimney will pass through the house without cutting floor or roof joists (see fireplace dimensions on Page 11).
Marginal Location
Wind Direction
Usually, no additional floor support is needed for the fireplace. The adequacy of the floor can be checked by first estimating the weight of the fireplace system. Weights are given on
Page 25
. Next, measure the area occupied by the fireplace. Note the floor construction and consult your local building code to determine if additional support is needed.
The Cambria™ fireplace may be installed directly on the floor or on a raised base but a minimum of 7 feet 6 inches (2.3 m) measured from the base of the appliance to the ceiling is required.
Location Recommended
When selecting the location, the chimney outlet position and the direction of the wind are impor­tant factor affecting the chimney performance. To allow a maximum draft and to reduce wind turbulence, the chimney must:
• Penetrate the highest part of the roof.
• Be installed as far as possible of roof offsets, trees or any other obstructions that may cause wind turbulence and back drafts in the chimney.
• The least amount of offsets (elbows) pos sible.
-
Location Not Recommended
Outside Air Intake Facing the Wind
Figure 12
Location Not Recommended
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
9
Page 10
Framing, Facing And Mantel
The construction of the framing, facing, and mantel must be in accordance with the stan­dards and the following illustrations (Figures
15 through 20
):
A. Frame the fireplace using 2” x 3” or heavier
lumber.
B. WARNING: Combustible materials can-
not be used in the space directly above the fireplace, except for the studs above the facade that support the facing and mantel. This area must remain empty for a height of 7 feet 6 inches (2286 mm) measured from the base of the appliance.
C. Frame the fireplace with vertical studs at the
sides of the fireplace running from floor to ceiling (see Figure 15). If combustible facing is to be used, position the studs back, from the front edge of the fireplace the thickness of the facing material so that the facing can be installed flush with the fireplace facing. Frame headers between the vertical studs only as follows:
• Place 2” x 3” or 2” x 4” headers, only along the upper part of the front, side and back faces. Do not put wood or any combustible material within the area above the fireplace except on the front facing.
• Place headers only as required to support the facing and mantel.
D. WARNING: The fireplace must not be
in contact with any insulation or loose filling material. Cover the insulation with drywall panels or any other rigid material around the fireplace.
Hearth Extension Requirements -
The Cam­bria™ fireplace may be installed directly on a combustible floor; however, the combustible floor in front of the fireplace must be covered with a 1/2 inch (13 mm) of non-combustible support material (cement board, cement block or other) before applying the finish material (tile, marble, stone, etc.) (see Figures 13 and
14).
WARNING: It is important not to cover the air ventilation opening below the facade trim. (free space - Figure 13).
Tile or Marble
Fireplace
Cement
Board
v
WARNINGS:
THE HEARTH EXTENSION IS TO BE IN­STALLED ONLY AS ILLUSTRATED.
u DO NOT PA CK R EQ UIRED A IR
SPACES W ITH INSULATIO N O R OTHER MATERIALS.
vTHE CRACK BETWEEN THE FIRE-
PLACE AND THE HEARTH EXTENSION MUST BE SEALED WITH A NON­COMBUSTIBLE MATERIAL SUCH AS A NON-COMBUSTIBLE SEALING STRIP OR SAND CEMENT GROUT IN THE AREA SPECIFIED ABOVE.
Figure 13 - Hearth Extension Requirements
Combustible material allowed in the airspace above this area.
Mantel
Fireplace
v
Free Space
Tile or Marble
2 x 4 Framing
u
Minimum 1/2” Cement Board
Elevated Fireplaces
Fireplace
Platform
2”
Elevated fireplace installations require a spe­cial “Z” Metal Safety Strips (field provided), in place of the safety metal strip shown above. The safety strip should extend the full width of the fireplace. When more than one safety strip is used they must overlap by a minimum of 1”.
COLD CLIMATE INSTALLATIONS
Climates where temperatures will fall below 32° F (0° C).
The heating performance of the appliance will vary depending upon the level of insulation, house design, how the appliance is operated, etc.
If this fireplace is being installed in a cold climate, it is especially important to seal all cracks around the fireplace and wherever cold air could enter the room with noncombustible material. Also, the outside air inlet duct should be wrapped with noncombustible insulation to minimize the formation of condensation. Do not place insulation materials directly against the chimney sections. We recommend that you use the insulated wall radiation shield since it will maintain the home’s thermal barrier. AC chimney is NOT recommended in very cold climates (in areas with temperatures below 0° F (-18° C).
10
59” Min.
Hearth
18”
Non-Combustible Material
Extension
Figure 14 - Hearth Extension and Clearances
24”
45°
4”
33-3/4”
Page 11
OUTSIDE CHASE
G
C
Back Wall of Chase/Enclosure Including Finising Materials if any
Rough Framing Face (Unfinished Shown)
A
* Zero Clearance From Back Spacer to Wall
Framing Dimensions - Model Cambria™
CORNER INSTALLATION
32-7/8”
(835mm)
D
Do not fill the space above the fireplace with any material
2” x 3”
Min.
F
J
27-7/8”
E
7’ 6”
(2.3m)
B
Min.
PARALLEL / CHASE INSTALLATION
G
A
Plywood 1/2”
Rough Framing Face
(unfinished shown)
46-1/2”
FRAMING DIMENSIONS
24”
1”
Fireplace Opening Width
A
B
C
D
E
F
G
J
48-3/4’’ 1238 mm
59-3/8’’ 1508 mm
48-1/2’’ 1232 mm
23-1/4’’ 591 mm
102-1/4” 2597 mm
51-1/8” 1299 mm
28-7/8’’ 733 mm
72-5/16’’ 1837 mm
17-7/8”
12-3/8”
27-7/8”
1-3/8”
Figure 15 - Framing Dimensions
Notes
Due to Lennox Hearth Products ongoing commitment to quality, all specifications, ratings and dimensions are subject to change without notice.
All framing dimensions calculated for 1/2" dry wall at the fireplace face. If sheathing the chase or finish ing with other thickness materials, calculations will need to be made.
The fireplace must not be in contact with any insulation or loose filling material. Cover the insulation with Drywall panels around the fireplace.
35-7/8”*
(911mm)
-
28-1/4”
(718mm)
2-5/8”* (67mm)
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
27-7/8”
(708mm)
36-1/4”*
(921mm)
46-1/2”
(1181mm)
57-1/8”
(1451mm)
59-1/8”
(1502mm)
* Dimensions to tiling flange behind the trim.
11
Page 12
Insulated Chase Construction
Floor Ceiling Wall
• Must have the same firestopping resistance as adjacent wall.
• Must have the same insulation as adjacent ceiling.
• Follow local rules regarding framing construction.
Insulate Joists Same As Ceiling
Draft Stops
Firestop
CTDT Termination
Note: Non- Combustible Chase Flashing Must Be Used To Cover Chase Opening
Optional Insulation In Outside Walls Of Chase
Solid Continuous Surface
Outside Base
Insulation (Thermal Barrier)
8'
Level
Attic Radiation Shield
Note: Floor and wall below the attic must be insulated using the same insulation.
7’ 6”
(2.3 m)
7’ 10”
Min.
(2.4 m)
Min.
Roof Support
Firestop
Storm Collar
Flashing
FIREPLACE
Drywall or Any Rigid Material
8’
(2.4 m)
Level
12
Figure 16
1/2” Plywood
2” x 4”
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 13
FACING
}
}
}
IMPORTANT
The facade must be removable once installed. The facade is designed to overlap any facing material installed on the front of the fireplace. If thicker material is installed, use the facade as a template and make sure it can be easily removed for servicing.
1. Combustible material must be installed flush with the fireplace. It may not project in front of and on the fireplace (i.e. the steel facade of the fireplace) (see Figure 19).
2. Non-combustible materials such as brick, stone or ceramic tile may project in front of and onto the fireplace facing (see Figure
20).
MANTEL AND FACING
The mantel must be installed at least 59” (1500 mm) above the base of the fireplace (see Figure 18).
Fireplace Frame Section
(Top View)
1
2
1
2
6
3
4
5
3
4
7
Mantel
59”
u
v
Figure 18
Figure 19
Mantel and Facing
(Side View)
Drywall
2” x 3” Min.
Spacer
Non-Combustible
u
Panel Only
Flameproof Facing
v
Only non-combustible mate­rial should be superposed or projecting over the front of the fireplace.
Flameproof Facing
Drywall
2” X 3” Min.
Spacer
Non-Combustible Panel Only
59”
Min.
Optional Fireplace Blower (UZY5)
A heat activated blower is sold as an option. It is designed to be located in the back of the fireplace and increase the air flow around the firebox. It uses regular 120V and must be connected to the main electrical circuit by a qualified electrician. An electrical box must be installed outside the fireplace.
WARNING: Because of the fireplace size and obstructive air venting, we don’t recommend the installation of the blower unless the gravity ducting is installed on the fireplace.
If you wish to adjust the blower speed, an optional variable speed control (VRUW) can be installed in line with the wiring. Again, use a qualified electrician for installation.
To install the blower,
1- Remove the refractory bricks and the and
iron.
2- Remove the metal plates covering the bottom
and back of the hearth firebox.
3- Disconnect the main electric cable from the
blowers by unplugging its two quick connec­tors.
4- Remove the knock-out in the front right side
of the fireplace outer casing.
5- Install a
6- Install the two blowers in the back of the
7- Reconnect the main cable quick connectors
8- Install all plates, bricks and andiron.
9- Connect the blower plug into the electrical
metallic wire protector and slide the blower main electrical cable from the outside to the inside of the unit.
fireplace through the holes in the back.
Warning: Make sure there are no contact between the blowers and the door slider.
and stick (magnet) the heat activate switch under the right side of the firebox. Using
aluminum tape, make sure no wiring touch the firebox by taping it to the bottom of the fireplace panel.
box located outside the fireplace.
-
1. Fireplace
2. Front of fireplace
3. Wood frame (2” x 3” min)
4. Drywall
5. Tiles
6. Rock board or other
7. Brick
Figure 17
Metal Mesh Screwed in Board and Fireplace
Figure 20
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
13
Page 14
HOT AIR DUCTING INSTALLATION (OPTIONAL)
Different hot air ducting systems can be installed with the Cambria™ fireplace:
• Gravity kit
• Forced air kit The gravity kit is used when the rooms are on same level or floor as the fireplace or on an upper level or floor. If the heat to be distributed is on
a lower level or floor or through the central heat duct of a furnace, then the forced air kit MUST be used.
Gravity Kit
Double hot air outlet including: (See Figure 21)
• 2 ea. telescopic lengths, 8” I.D.
• 2 ea. 90º elbows, 8” I.D.
• 2 ea. hot air outlet kits (grill and frames)
• 2 ea. adaptors
See components list on Page 23.
Only the blower available with the fireplace can be used with the gravity kit.
Frame
Grill
When installing the double outlet system, the hot air outlets can be installed in the same room as the fireplace, or one or both of the outlets can be installed in adjacent or upper rooms. Installing the ducts at different elevations will tend to exhaust more heat out of the higher outlet (Figure 22).
WARNING: The outlet grills
Outlet Grill
should not be installed facing upward through a floor. Danger of burns can result if grills in floor are stepped on.
10’ Max.
13” x 13”
10’ Max.
Maintain at least 6-1/2” (160 mm) clearance from the outlet grill framing to a combustible ceiling, side wall or mantel.
Figure 22
WARNING: Both pipes of the double hot air outlet must be installed. Any oth­er installation may cause fire and void warranty.
Figure 21
The safety rules for hot air ducting gravity kit installations are the following:
Minimum height* 68” (1727 mm) Maximum length - See Figure 22
* The height of t
he louver must be measured from the base of the Cambria fireplace to the middle point of the louver.
WARNING: Both pipe of the double hot air outlet must be installed. Any other installa­tion can cause greater risk of fire and void the warranty.
14
Flashing Collar
Flashing
Attic Radiation Shield
Figure 23
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Rain Cap
Roof Support
Firestop
68” Min.
(1727 mm)
u
Combustibles are not allowed below top spacers
u
above the fireplace. Facing in front of fireplace must be non-combustible below this area.
59” Min.
(1499mm)
Non-Combustible Flameproof Facing
Page 15
The duct system must be installed respecting the following:
1. Remove the plates closing up the 8” (203mm) diameter holes on top of the fireplace. Then, cut the insulation in order to obtain two 8” (203mm) diameter openings. Fix the adap­tors on the fireplace openings by turning clockwise (see Figure 21).
2. Maintain at least a 2” (50 mm) clearance between the ducts and any combustible material; the required hole size is 13” x 13” (330 mm x 330 mm).
Exception: For the grills, the framing
can be 10-3/4” x 10-3/4” (275 mm x 275 mm) to provide the clearance as required by the integral spacers on the double outlet duct system.
3. The maximum number of elbows in a run of duct is two.
4. Maintain at least 6-1/2” (160 mm) clearance from the outlet grill framing to a combustible ceiling, side wall or mantel.
5. When traversing a combustible wall or floor, a firestop must be installed at the wall or floor penetration. The hole size must be 13” X 13” (330 mm x 330 mm).
6. Do not connect the hot air ducts to a central heating system. Malfunction of the heating system’s fan will cause the fireplace to overheat. A furnace duct is only single wall and not double wall as is required for the Cambria™ fireplace hot air exhaust.
7. Use only Lennox Hearth Products grills and components as described in this manual. Other grills or registers may be too restrictive and may overheat the fireplace or ceiling.
8. Do not use insulated flexible ducts as they will overheat.
9. Do not use tees or any other components than the ones specifically listed here.
10. All ducts must extend upwards or horizon­tally. Never route the ducting downwards.
11. The hot air outlet grills must be installed with the louvers pointing downwards in order to prevent overheating adjacent ceilings.
B) Attach the 5” flexible pipe, using the collars provided. Important: Make sure that the plastic
wrapping around the flexible pipe will not be in contact with the fireplace.
C) Route the flexible pipe to the chosen location. The ducting system can be installed either in an
upper room or in a lower room.
D) Attach the flexible pipe to the blower, using the collars (Figure 25). E) Fix the back draft damper to the blower outlet. F) Attach a flexible pipe to the fan / flexible pipe adapter (square to round) and stretch it up to the
location where the heat is required. G) At that point, the flexible pipe can be attached to any air distribution grill. H) Install the blower heating and cooling thermostat (HCTW) in that part of the house to be heated
by the hot air duct. The thermostat can be switched to a cooling thermostat and installed in
the same room as the unit. This thermostat will turn on the blower when the room where the
fireplace is located becomes too hot.
This option requires electricity. Make sure that the connections to the blower have been made ac­cording to the local codes and comply with their requirements (see instruction provided with the thermostat). For more information regarding central forced and ducting, refer to the BISFWK-1 installation sheet provided with the kit.
Adaptor
Insulated Flex Pipe
Figure 24
Central Forced Air Kit
The knock-outs provided on the back and on the sides of the Cambria fireplace allow the con­nection of insulated flexible pipe which enables you to heat adjacent rooms up to 50 feet from the fireplace hot air outlet.
The ducting system must be installed as de­scribed below:
A) Fix the adaptor at the back and/or the side
of the fireplace by twist-locking the adaptor to the fireplace. You can use more than one outlet on the fireplace (see Figure 24).
Insulation
Aluminum Tape
Figure 25
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Flex 5” Diameter
Blower
Tightening Collar
15
Page 16
OUTSIDE AIR
It is mandatory to install an outside air connec-
tion to the Cambria™ fireplace. The following components are required and are included with the fireplace:
• Outside air kit
• 4” adapter for fi
replace connection
The outside air assembly must be installed ac­cording to the following requirements:
A) Duct length should be kept to a minimum.
The maximum length of a 4” interior diam­eter (100 mm) insulated flexible duct is 20 feet (6.1 m). The duct can be extended to a maximum of 40 feet (12 m) using a 6” interior diameter (150 mm) insulated flexible duct (See note below).
B) The air intake register must not be installed
more than 10 feet (3050 mm) above the base of the fireplace.
C) The fresh air must come from outside the
house. The air intake must not draw air from the attic, basement or garage.
D) The air intake should be installed where
it is not likely to be blocked by snow or exposed to extreme wind and away from automobile exhaust fumes, gas meters and other vents.
E) The duct and register may be installed above
or below floor level.
Make a 4-1/4” (110 mm) hole in the outside wall of the house at the chosen location. From outside, place the outside air register in the hole (open side down) and fasten the register to the wall with screws as shown (see Figure 26). Slip the pipe into the insulated sleeve. Place the insulated pipe over the register tube and over the fireplace’s outside air connector (see
Figure 27
). At each end, carefully pull back the insulation and plastic cover exposing the flex­ible pipe. Using the aluminium tape provided, wrap the tape around the joint between the flexible pipe and the air inlets. Carefully push the insulation and plastic cover back over the pipe. Using aluminium tape, fasten the plastic cover in place.
Figure 26
Insulation
Figure 27
Outside Intake
Opening Facing Down
Wall
Plastic Cover
OUTSIDE CONNECTION
Aluminum Tape
Plastic Cover
Screw
Insulation
Flexible Pipe
Aluminum Tape
OUTSIDE AIR CONNECTION TO THE FIREPLACE
Fireplace Connection
Aluminum Tape
Fireplace
Flexible Pipe
Aluminum Tape
NOTE: We recommend not to exceed 20 feet (6.1 meters) of 4” flexible pipe. If you require a longer length we recommend that you use a 5” diameter flexible pipe for the complete run up to 30 feet and a 6” diameter pipe for a run of up to 40 feet.
16
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 17
THE CHIMNEY SYSTEM
Chimney Installation Notes
1. If possible, install an interior chimney as it will provide better performance. In areas with continuous temperatures below 0°F (18°C), the use of an exterior chimney in­creases the likelihood of operating problems such as low draft, high rate of creosoting, and poor start-up characteristics. Exterior chimneys are also prone to down-drafting and flow reversal. Installations which are located on lower floors in the house, such as in a basement, in combination with an outside chimney, are especially prone to flow reversal.
2. The Lennox Hearth Products fireplace model Cambria™ fireplace is listed only with Se­curity Chimneys International Ltd 10” dia. chimney systems model Secure Temp / Nova Temp
HT6103+
or AC.
ASHT+
3. A chimney venting a fireplace shall not vent any other appliance.
4. The minimum chimney height is 15 feet (4.6 m) excluding the fireplace.
5. All chimney installations must include at least one support in order to be able to take any lateral load. The maximum chimney length that can be supported by the fireplace is 12 feet (3.7 m) for Secure Temp
HT6103+
Temp
and 26 feet (8m) for AC chim-
ASHT+
/ Nova
ney. In altitude, add 18” (450 mm) to the chimney for every 2000 feet (600 m) above sea level.
6. The chimney must extend at least 3 feet (915 mm) above its point of contact with the roof and at least 2 feet (610 mm) higher than any wall, roof or building within 10 feet (3m) of it (Figure 28).
7. If the chimney extends higher than 5 feet (1500 mm) above its point of contact with the roof, it must be secured using a roof brace.
8. A rain cap must be installed on top of the chimney. Failure to install a rain cap may cause corrosion problems.
9. Cut and frame square holes in all floors, ceilings, and roof that the chimney will go through to provide a 2” (50 mm) clearance between the chimney and any combustible materials. Do not fill this 2” space with insulation or any other combustible mate­rial.
10. Portions of the chimney which may extend through accessible spaces must be enclosed to avoid contact with combustible materials or damage the chimney.
Two (2) Feet
.6 Meters Minimum
Ten (10) Feet
3.1 Meters
Three (3) Feet
.6 Meters Minimum
Figure 28
CHIMNEY INSTALLATION INSTRUCTIONS
1. Cut and frame the holes in the ceiling, floor and roof where the chimney will pass (see Figure
29). Use a plumb-bob to line up the center of the holes. The sizes are indicated in Table 2 for the floor and ceiling holes and Table 3 (Page 19) for the roof holes.
CHIMNEY MODEL SQUARE HOLE
Secure Temp
Nova Temp
Note: See Table 3 for Sloped Roof Framing
Table 2 - Flat Roof Framing
Figure 29 - Roof Framing
ASHT+
HT6103+
AC: 17 in. (432 mm)
SIZE OPENING
16-3/8 in. (416 mm)
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
17
Page 18
From below, install a firestop in each ceiling/
floor separation through which the chimney will pass. At the attic level, install an attic radiation shield from above (see Figures
30a and 30b).
2. For Secure Temp
ASHT+
/ Nova Temp
HT6103+
chimneys, place the first chimney length on the fireplace. To lock it in place, turn 1/4 of a turn clockwise. With the AC chimney, you must use a starter section before installing the first chimney length (Figure 31). Con­tinue installing chimney lengths making sure to lock each length in place.
3. Every time the chimney passes through a ceil­ing or a wall, install the appropriate firestop. When you reach the desired height, install the roof support (refer to instructions included with the support). For an AC chimney use an universal support AC10SU (H3265).
4. Put the roof flashing in place and seal the joint between the roof and the flashing with roofing pitch (see Figures 32 and 33). For sloping roofs, place the flashing under the upper shingles and on top of the lower shingles. Nail the flashing to the roof, using roofing nails.
5. Place the storm collar over the flashing, and tighten it with the bolt supplied. Finally, seal the joint between the storm collar and the chimney, using silicone caulking.
6. Install the chimney cap.
ASHT / S2100
HT6103+ / HT6000+
Chimney
Attic Radiation Shield
AC
Chimney
Figure 30b
CHIMNEY INSTALLATION
MODEL AC
ACBI7RSA
AC10RS
Radiation Shield
Rain Cap
Collar
Flashing
Attic Radiation Shield
Firestop
Universal Support
18
Figure 30a
AC Starter Section AC10SB or AC10SB30
Chimney Outside Air Intake (required when using AC chimney)
Firestop
Outside Combustion Air Kit
Note: Outside air kits must be installed for both fireplace and AC chimney.
Figure 31
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 19
CHIMNEY MODEL AC
Collar
Chimney
Flashing
Figure 32
Figure 33
Roof Down Slope Hole Size
10”
ASHT+
HT6103+
AC
10”
Degree
Of Slope
Roof Pitch
2/12 16-5/8” (422 mm) 17-1/4” (438 mm)
4/12 17-1/4” (439 mm) 18” (457 mm)
6/12 18-3/8” (466 mm) 19” (482 mm)
8/12 19-3/4” (500 mm) 20-1/2” (520 mm)
10/12 21-3/8” (542 mm) 22-1/8” (562 mm)
12/12 23-1/8” (588 mm) 24” (611 mm)
Secure Temp
Nova Temp
0 * 16-3/8” (416 mm) 17” (432 mm)
Table 3 * Cross Slope Hole Size
OFFSET CHIMNEY INSTALLATION
After reaching the location requiring the elbow, proceed as follows. The minimum chimney height when using elbows is:
Minimum Chimney Height
When Using Elbows
Fireplace Model Cambria™
Chimney Model Secure Temp
Vertical Installation 15 feet (4.57 meters)
Two (2) Elbows 18 feet (5.49 meters)
Four (4) Elbows 20 feet (6.10 meters)
Temp
Table 4
Note: Must return to vertical before penetrating
ceiling or floor.
After reaching the location requiring the elbow, proceed as follows:
Secure Temp
ASHT+
/ Nova Temp
1. Install the first elbow; turn it in the required direction. Fasten it to the chimney with the three (3) 1/2” (13 mm) metal screws provided with the elbow.
2. Install the necessary chimney lengths to achieve the required offset. Lock the chimney lengths together: it is recommended to use three (3) 1/2” (13 mm) screws. If the offset length is made of two (2) chimney lengths or more, use an offset support halfway up the offset. If penetrating a wall, install a wall radiation shield (see Figures 36 and 37).
HT6103+
HT6103+
ASHT+
/ Nova
/ AC
Chimneys
3. Use another elbow to turn the chimney vertically. Secure the elbow, using three (3) 1/2” (13 mm) screws (provided with the elbow).
4. Use a plumb-bob to line up the center of the hole. Cut a hole for the chimney in the ceiling/floor. Frame this hole as described previously (see Chimney Installation Instruc- tions on Page 17).
5. From below, install a firestop (See Figure
30a).
6. A support (ST or SO) must be used on the first 15 feet section (5 m).
7. Continue with the regular installation.
AC Chimney
1. Install the first elbow. Turn it in the required direction. To lock it in place, turn 1/8 of a turn. Fasten the straps attached to the elbow to the surrounding frame, using nails or drywall screws (Figure 35).
2. Install the necessary chimney lengths to achieve the required offset. Lock the chimney lengths together. If penetrating a wall, use a wall radiation shield.
3. Use another elbow to turn the chimney vertically. Lock it to the chimney. Fasten the straps attached to the elbow to the surrounding framing using nails or drywall screws.
4. Use a plumb-bob to line up the center of the hole. Cut a hole for the chimney in the ceiling. Frame this hole as described previously.
5. From below, install a radiation shield (see Figure 30b).
6. Continue with the regular installation.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
19
Page 20
Offset Dimensions
B
Total Height
Chimney Elbow
Offset &
Height
A
15º
B
ASHT+
HT6103+
10”
30º
A
B
45º
C
anada Only
Chimney Elbow Offset &
A
B
Height
A
15º
B
AC
10”
A
30º
B
A
One Length Between Elbows Two Lengths Between Elbows
8” 12” 18” 24” 36” 48” 8” & 48” 12” & 48” 18” & 48” 24” & 48” 36” & 48” 48” & 48”
3”
(76mm)
16-1/2”
(419mm)
7-1/2”
(191mm)
20-3/4”
(527mm)
10-1/2”
(267mm)
18-1/2”
(470mm)
4-1/4”
(108mm)
20-1/4”
(514mm)
9-1/2”
(241mm)
24-1/4”
(641mm)
13-1/2”
(343mm)
21-1/4”
(540mm)
--- 12” 18” 36” 48” --- --- 12” & 48” 18” & 48” 36” & 48” 48” & 48” ---
----
4-1/4”
----
(108 mm)
----
20-1/4”
----
(514 mm)
----
9-1/2”
----
(241 mm)
----
24-1/4”
----
(641 mm)
5-3/4”
(146mm)
26-1/4”
(749mm)
12-1/2”
(318mm)
29-1/2”
(749mm)
17-3/4”
(451mm)
25-1/2”
(648mm)
One Length Between Elbows Two Lengths Between Elbows
5-3/4”
(146 mm)
26-1/4”
(667 mm)
12-1/2”
(318 mm)
29-1/2”
(749 mm)
7-1/4”
(184mm)
32”
(813mm)
15-1/2”
(394mm)
34-3/4”
(883mm)
22”
(559mm)
29-3/4”
(756mm)
7-1/4”
(184 mm)
(813 mm)
15-1/2”
(594 mm)
34-3/4”
(883 mm)
10-1/4”
(260mm)
43-1/2”
(1105mm)
21-1/2”
(546mm)
45”
(1143mm)
30-1/2”
(775mm)
38-1/4”
(972mm)
32”
Horizontal Offset
13-1/4”
(337mm)
55-1/2”
(1410mm)
27-1/2”
(699mm)
56-1/4”
(1429mm)
(991mm)
46-3/4”
(1187mm)
10-1/4”
(260 mm)
43-1/2”
(1105 mm)
21-1/2”
(546 mm)
45”
(1143 mm)
39”
----
----
----
----
----
----
----
----
15-1/4”
(387mm)
62”
(1575mm)
31”
(787mm)
62-1/2”
(1588mm)
44”
(1118mm)
51-3/4”
(1314mm)
----
----
----
----
----
----
----
----
16-1/4”
(413mm)
65-3/4”
(1670mm)
33”
(838mm)
65-3/4”
(1670mm)
46-3/4”
(1187mm)
54-3/4”
(1391mm)
16-1/4”
(413 mm)
65-3/4”
(1670 mm)
33”
(838 mm)
65”
(1651 mm)
17-3/4”
(451mm)
71-1/2”
(1816mm)
36”
(914mm)
71-1/4”
(1810mm)
51”
(1295mm)
59”
(1499mm)
17-3/4”
(451 mm)
71-1/2”
(1816 mm)
36”
(914 mm)
70-1/4”
(1784 mm)
19-1/4”
(489mm)
77-1/4”
(1962mm)
39”
(991mm)
76-1/2”
(1943mm)
55-1/4”
(1403mm)
63-1/4”
(1607mm)
22-1/2”
(572 mm)
89”
(2261 mm)
45”
(1143 mm)
85-3/4”
(2178 mm)
22-1/2”
(572mm)
89”
(2261mm)
45”
(1143mm)
86-3/4”
(2203mm)
63-3/4”
(1619mm)
71-3/4”
(1822mm)
25-1/2”
(648 mm)
100-1/2”
(2553 mm)
(1295 mm)
(2438 mm)
(648mm)
100-1/2”
(2552mm)
(1295mm)
(2489mm)
(1835mm)
(2038mm)
51”
96”
25-1/2”
51”
98”
72-1/4”
80-1/4”
----
----
----
----
----
----
----
----
20
Figure 34
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 21
OFFSET CHIMNEY INSTALLATION
Figure 35
Straps
Support
Straps
Chimney AC
AC Starter Section
Note: This illustration is not to scale. It represents how the chimney must be supported. A 30 degree offset only is allowed in the USA and a 45 degree maximum offset is allowed in Canada.
OFFSET CHIMNEY INSTALLATION WITH WALL PENETRATION
Rain Cap
Collar
Roof Support
Outside Wall
Framing 2” x 3”
Roof Flashing
Offset Support
Insulated Wall Radiation Shield
Note: In cold areas it is recommended to protect the chimney in a insulated chase.
Figure 36
IF THE CEILING IS 9 FEET OR LESS THIS INSTALLATION CAN ONLY BE ACHIEVED USING 45° ELBOWS. SINCE ONLY 30° ELBOWS ARE ALLOWED. IN THE U.S. THE OFFSET MUST BE DONE ABOVE THE CEILING.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
21
Page 22
ANGLED WALL RADIATION SHIELD (RSMI30, RSMI45, AC10RSMI30)
When traversing a combustible wall with the chimney at a 30º or 45º angle, an angled firestop or wall radiation shield must be installed. Only one is required.
Note: 45º angle for Canada only
In cold climate locations, we recommend that you use the insulated wall radiation shield since it will maintain the home’s thermal barrier.
RSMI30, RSMI45, AC10RSMI30
Chimney (10” dia.) Angle Hole Dimension
Secure Temp
Nova Temp
Secure Temp
Nova Temp
AC 30º
ASHT+
HT6103+
ASHT+
HT6103+
Canada
30º
45º
only
17-9/16” x 45-
3/4” (446 mm x
1162 mm)
17-1/2” x 30”
(444 mm x 762
mm)
17” x 42-1/2”
(432 mm x
1080 mm)
Table 5
Insulated Wall
4.5 CHIMNEY SUPPORT INSTALLATION
Universal Roof Support
This support has three possible uses:
1. For Secure Temp
ASHT+
/ Nova Temp
HT6103+
it must be used on a roof to support the chimney.
2. It may be used on a floor, ceiling or roof above an offset to support the chimney above the offset.
3. It may be used on a floor, ceiling or roof as a supplementary support when the chimney height exceeds 12 feet (3.7 m).
Table 6 gives maximum height of supported chimney.
NOTE: For the AC chimney, a support section (AC10SL) must be used every 20 feet (6 m) or an universal support every 15 feet (4.5 m) instead of the universal roof support (ST).
For roof support installation, refer to the instruc­tions provided with the support.
UNIVERSAL OFFSET SUPPORT
This support is used to support the chimney above an offset. When the chimney offset is used to traverse a wall this support may be used on the wall to support the chimney. The maximum heights are given in Table 6. For offset support installation, refer to the instructions provided with the support.
CHIMNEY MAXIMUM HEIGHT OF
SUPPORTED CHIMNEY
,
10” diameter Offset Support Roof Support
AC
ASHT+
HT6103+
14 Feet
(4.3 meters)
30 Feet
(9.15 meters)
(12.16 meters)
Secure Temp
Nova Temp
Table 6
CHIMNEY CHASE AND MULTIPLE TERMI­NATIONS
For the purpose of this manual, a chimney chase is considered a part of the chimney system rather than part of a building. The termination must be placed a minimum of 18” (460 mm) above the chase.
For installations where more than one chimney is located in the same chase or within the same area, we suggest that their terminations be separated by at least 16” (410 mm) horizontally, and 18” (460 mm) vertically. This separation is to prevent smoke migrating from one chimney to another (see Figure 38).
20 Feet
(6.1 meters)
40 Feet
22
Drywall
Figure 37
Insulated Wall Radiation Shield
18” (460 mm)
16” (410 mm)
Figure 38
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
18” (460 mm)
16” (410 mm)
18” (460 mm)
Page 23
OPTIONAL INSTALLATION ACCESSORIES
CHIMNEY - PARTS AND COMPONENTS LISTS
Installation Accessories
Description Cat./Part No.
Outside Air Kit (included with fireplace)
Outside air kit, UZI UZI
UZI outside air kit fireplace adaptor, UZIAD UZIAD
Gravity Kit
Gravity Kit, Complete double ducting system including: 2 elbows 90º, 2 telescopic lengths, 2 grill supports and 2 black grills, 7B30ZK-1
7B30ZK-1
Gravity Kit Accessories
Black grill with support, 7B30ZO 7B30ZO
Brass grill (for 7B30ZK-1), 7B30ZGB 7B30ZGB
Elbow 90º, 8” dia., 7B26ZE90 7B26ZE90
Elbow 45º, 8” dia., 7B26ZE45 7B26ZE45
Telescopic length, 8” dia., 7B26ZLA 7B26ZLA
Adjustable length, 8” dia. (2” - 5”), 7B26ZL2A 7B26ZL2A
Radiation shield (for grill), 7B26ZR 7B26ZR
Central Forced Air Kit Accessories
Central Forced Air Kit, Central forced air kit including: blower (BISZY), flex adaptor (BISAF), 2 clamps, variable speed control (VRUW), thermo-disk (VTU), fan to flexible pipe adapter (BISAVF), back draft damper (BISBD), aluminium tape, BISFWK-1
Fireplace to Flex adaptor and 2 clamps, BISAF BISAF
Flexible pipe 5” I.D. x 15 ft. Long, 5FLEX15 5FLEX15
Flexible pipe 5” I.D. x 30 ft. Long, 5FLEX25 5FLEX25
Blower 250 CFM for central forced air kit, BISZY BISZY
Blower variable speed control with decorative wall plate for (BISZY), VRUW
Thermo-disk, on/off blower control (for BISZY), VTU VTU
Blower to flexible pipe adaptor, BISAVF BISAVF
Heating and cooling thermostat, HCTW HCTW
Backdraft damper, BISBD BISBD
BISFWK-1
VRUW
Fireplace Blower Kit
Two blower kit with thermostatic control, UZY5 UZY5
Fireplace Model Cambria™ - Approved Venting Components manu­factured by Security Chimneys International only.
• 10” diameter chimney - AC (air cooled), Secure Temp™ ASHT+ (or Nova
Temp™ HT6103+).
AC Chimney*
(10” Diameter AC - Air Cooled)
* AC Chimney is NOT recommended at elevations above 4,000 feet or in cold climates
(climates where temperatures will fall below 32° F / 0° C).
Description Cat./Part No.
One of the following adaptors is required
if installing an AC chimney system
Starter Section, 10” Dia., AC10SB H3776
Offset Starter Section 30º, 10” Dia., AC10SB30 H3777
The following outside air kit is required if installing an AC chimney system
Outside air kit (chimney) (flex, insulation, outside register and coupling), ACZI
H1967
Lengths and Misc. Chimney Components
12” Length, 10” Dia., AC10L12 H3765
18” Length, 10” Dia., AC10L18 H3766
36” Length, 10” Dia., AC10L36 H3767
48” Length, 10” Dia., AC10L48 H3768
15º Elbow, 10” Dia., AC10E15 H3760
30º Elbow, 10” Dia., AC10E30 H3761
Rain Termination Cap (regular), 10” Dia., AC10CPR H3759
Spark Arrester Screen, PE+ H0479
Wall Band, XBM XBM
Supports
Support section (10”), AC10SL H3778
Universal support, AC10SU H3265
Roof Flashings
Flat roof flashing (includes spacer & collar), ACBI7FR H3275
Roof Flashing, Adjustable, 1/12 - 7/12 (5º - 30º) (in­cludes spacer & collar), ACBI7FAR
Roof Flashing, Adjustable, 8/12 - 12/12 (30º - 45º) (includes spacer & collar), ACBI7FBR
H3276
H3277
Misc.
Firestop, AC10BF H3758
Radiation Shield, AC10RS H3769
Attic Radiation Shield, ACBI7RSA H3270
Telescopic Attic Radiation Shield, AC10RST H3775
Insulated Wall Radiation Shield 30º, AC10RSMI30 H3272
Insulated wall radiation shield 45º, AC10RSMI45 H3774
Outside air coupler for air kit, UACZI H3274
Storm Collar, AC10FC H3278
Notes:
1. (Projet NovaTemp ) HT6103+ is equivalent to ASHT+
2. AC Chimney is Not recommended at elevations above 4000 feet or in cold climates where temperatures are likely to fall below 32° F (0° C). When using AC chimney, an AC10SB (H3776) starter section must be used before installing an elbow. When an offset is needed immediately off the top of the fireplace, a starter section H3777 is available.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
23
Page 24
CHIMNEY - PARTS AND COMPONENTS LISTS
Secure Temp ASHT+ 1” High Temp. Insulated Stainless Steel Chimney
10” I.D., Double-Wall Stainless Steel, Listed to CAN/UCL-S604 & UL-103HT
Description Part/Cat. No.
Lengths and Misc. Chimney Components
8” length, 10” Dia., 10L8-N 10L8-N
12” length, 10” Dia., 10L12-N 10L12-N
18” length, 10” Dia., 10L18-N 10L18-N
24” length, 10” Dia., 10L24-N 10L24-N
36” length, 10” Dia., 10L36-N 10L36-N
48” length, 10” Dia., 10L48-N 10L48-N
Adjustable Length 12”, 10” Dia., 10LA 10LA
15º elbow, 10” Dia., 10E15 10E15
30º elbow, 10” Dia., 10E30 10E30
Rain Termination Cap, 10” Dia., 10CC 10CC
Spark Arrester Screen (universal spark arrester band), PE PE
Wall Band, XBM XBM
Supports
Offset Support, XSO XSO
Roof Support, XST XST
Roof Brace, BS2 BS2
Firestops
Firestop, 10BF 10BF
Radiation Shield, 10RS 10RS
Insulated Attic Radiation Shield, 10RSA2 10RSA2
Insulated Wall Radiation Shield, 10RSM 10RSM
Insulated Wall Radiation Shield, 30º, 10RSMI30 10RSMI30
Uninsulated Wall Radiation Shield, 30º, 10RSM30 10RSM30
Roof Flashings
Flat Roof Flashing, 10FR 10FR
1/12 - 7/12 (5º - 30º), 10FAR 10FAR
8/12 - 12/12 (30º - 45º), 10FBR 10FBR
Storm Collar, 10FC 10FC
Anchor Plate, 10SP 10SP
24
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Page 25
REPLACEMENT PARTS LIST
SPECIFICATIONS
Cambria™ - Replacement Parts
Description Cat./Part No.
Front Edge Refractory Brick PR-SR2693
Back Refractory Brick PR-SR2821
Right Side Refractory Brick PR-SR2823
Left Side Refractory Brick PR-SR2822
Bottom Refractory Brick PR-SR2692
Wooden Door Handle PR-SR2722
Decorative Screw Caps (2) PR-SACBTFBK2
Ceramic Glass (1) PR-SR2677
Andiron (2) PR-SR2824
Black Metallic Paint “Forrest Paint” Can 70K99
Door Gasket: 58-3/4” 5/8” Dia., (order 1 per door) PR-SR1823N
Right Door Assembly PR-SR2678
Left Door Assembly PR-SR2679
Finishing Facade PR-SR2701
Door Lock Tab PR-SR2715
Bearing PR-SR2674
Chimney Damper Control Handle And Rod PR-SR2762
Chimney Damper Plate And Pivot Rod PR-SR2665
Fire Screen PR-SR2723
Fire Screen Support Rod PR-SR2779
Left Slider Assembly PR-SR2680G
Right Slider Assembly PR-SR2680D
Slider Stopping Plate PR-SR2714
Right Hinge PR-SR1800DLV
Left Hinge PR-SR1800GLV
Fireplace Top Panel PR-SR2661
Fireplace Left Side Panel PR-SR2659
Fireplace Right Side Panel PR-SR2660
Fireplace Back Panel PR-SR2658
Cat. No. Model
H6998 Cambria
Product Reference Information
Weight w/ crate 675 lbs
Weight w/out crate and
refractory bricks
Height 59” (1499mm)
Width 48-1/2” (1232mm)
Depth 29” (737mm)
Chimney weight ASHT+ (10” dia.) 8-1/2 lb/ft.
Chimney weight AC (10” dia.) 4 lb/ft
500 lbs
CLEARANCE TO COMBUSTIBLES
The following clearances meet the minimum requirements for a safe installation:
Side wall (fireplace front): 24” (457 mm) measured from the fireplace door.
Ceiling: 7’ 6” (2286 mm) measured from the base of the fireplace
Fireplace enclosure:
Bottom: 0” Side: 0” to spacer Back: 0” to spacer Top: Do not fill the space above the fireplace with any material
(Except the wood framing. See Figure 15)
Chimney: 2” (50 mm)
• Mantel: 59” (1422 mm) measured from the base of the fireplace.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
25
Page 26
WARRANTY
Your fireplace is covered by a limited warranty. Please read the warranty to be familiar with its coverage.
Retain this manual. File it with your other documents for future refer­ence.
PRODUCT REFERENCE INFORMATION
We recommend that you record the following important information about your fireplace. Please contact your Lennox Hearth Products dealer for any questions or concerns. For the number of your nearest Lennox Hearth Products dealer, please call 1-800-9-LENNOX.
REPLACEMENT PARTS
See Page 25 for a complete replacement parts list. Use only parts sup­plied from the manufacturer.
Your Fireplace's Model Number ________________________________________
Normally, all parts should be ordered through your Lennox Hearth Products distributor or dealer. Parts will be shipped at prevailing prices at time of order.
When ordering repair parts, always give the following information:
1. The model number of the appliance.
2. The serial number of the appliance.
3. The part number.
4. The description of the part.
5. The quantity required.
6. The installation date of the appliance.
If you encounter any problems or have any questions concerning the installation or application of this system, please contact your dealer.
LENNOX HEARTH PRODUCTS 1110 West Taft Avenue Orange, CA 92865 Visit us at www.Lennox.com
Your Fireplace's Serial Number ________________________________________
The Date On Which Your Fireplace Was Installed ___________________________
Your Dealer's Name _________________________________________________
Your Dealer's Phone Number __________________________________________
Lennox Hearth Products reserves the right to make changes at any time, without notice, in design, materials, specifications, prices and also to discontinue colors, styles and products. Consult your local distributor for fireplace code information.
Printed in Canada © 2008 by Lennox Hearth Products
P/N 850,057M REV. C 11/2008
26