THIS APPLIANCE MUST BE INSTALLED BY A QUALIFIED TECHNICIAN.
READ MANUAL THOROUGHLY BEFORE INSTALLATION.
P/N 775006M, Rev. J, 04/01
IMPORTANT WARNINGS
CAUTION: Read this manual thoroughly before starting installation. For your safety, follow the installation, operation and maintenance instructions exactly without deviation. Failure to follow these instructions may result
in a possible fire hazard and will void the warranty. If this appliance is not properly installed, a house fire may
result. Contact local building or fire officials about restrictions and installation inspection in your area.
1. If utilizing an older chimney, it must be inspected
for adequate serviceability. Refer to the heading
Chimney Inspection on page 6.
2. Install only in masonry fireplaces, built to UBC
chapter 37 standards or listed factory built fireplaces.
3. The minimum clearances must be maintained for
all combustible surfaces and materials including;
furniture, carpet, drapes, clothing, wood, papers,
etc. Do not store firewood within this clearance
space.
4. This appliance requires a non-combustible heat
resistant approved fireplace hearth or hearth extension. This protected area must extend a minimum of 16" to the front of the fuel door opening
and 8" beyond both sides of the fuel door opening
(see floor protection on page 5 for additional infor mation).
5. Minim um ceiling height must be 7 feet (measured
from base of appliance to ceiling).
6. DO NOT CONNECT THIS UNIT TO A CHIMNEY
FLUE CONNECTED TO ANOTHER APPLIANCE.
7. Do not connect this appliance to air ducts or any air
distribution system.
8. Do not install appliance in a sleeping room.
9. PREVENT CREOSOTE FIRE: Inspect and clean
chimney frequently. Under certain conditions of
use, creosote buildup may occur rapidly. Inspect
chimney connector and chim ney twice monthly and
clean if necessary. Using green or inadequately
seasoned wood can greatly increase creosote
buildup. Use dry wood to minimize creosote
buildup.
10. USE SOLID WOOD FUEL ONLY: This appliance
is approved for burning dry seasoned natural wood
only.
11. Never use gasoline, gasoline-type lantern fuel,
kerosene, charcoal lighter fluid, or sim ilar liquids to
start or "freshen up" a fir e in this heater. Keep all
such liquids well away from the heater while it is in
use.
12. DO NOT OVERFIRE: If heater or chimney connector glows, you are overfiring. Overfiring this appliance could cause a house fire. Overfiring is a
condition where the appliance is operated at temperatures above its design capabilities. Overfiring
can be caused by improper installation, improper
operation, lack of maintenance or improper fuel
usage. Damage caused from overfiring is NOT
covered under the manufacturers limited warranty.
13. NEVER LEAVE AN UNATTENDED FIREPLACE
INSERT BURNING ON HIGH. Operation of the
fireplace insert with the primary air control at its
highest burn rate setting for extended periods can
cause dangerous overfiring conditions. The primary air control should only be positioned at the
highest setting during start-up procedures and for
short durations. When leaving the fireplace insert
unattended ensure that the primary air control is
set to the low or medium low range.
14. Us e a metal container with a tight fitting lid to dispose of ashes.
15. Burning any kind of fuel uses oxygen from the
dwelling. Be sure that you allow an adequate
source of fresh air into the room where the fireplace insert is operating (see Ventilation on page
6).
16. CAUTION: HOT WHILE IN OPERATION. An appliance hot enough to warm your home can severely burn anyone touching it. Keep children,
clothing and furniture away. Contact may cause
skin burns. Do not let children touch the applianc e.
Train them to stay a safe distance from the unit.
17. Once the fire is established, never burn the appliance with the bypass open, except when refueling
the appliance.
18. CATALYTIC COMBUSTOR: Do not operate this
appliance without the catalytic combustor assembly
(this consists of ceramics, gasket and a housing)
properly installed. Burning of metal foils , coal, plastic garbage, diesel oil and sulfur will make the
catalyst in the combustor inactive. T he combustor
is fragile; handle carefully. The per formance of the
catalytic device or its durability has not been evaluated as part of the certification.
19. Build fires directly upon the brick hearth inside the
fireplace insert. Do not use grates, irons or any
other method to elevate the fire.
20. SAVE THESE INSTRUCTIONS.
21. See the listing label located on the back of fireplace (or see Safety/Listing Label on page 26).
PAGE 2
TABLE OF CONTENTS
Important Warnings ................................................. 2
Testing / Listing, EPA, Using this Manual ............... 3
Planning Your Installation......................................4-7
Safety / Listing Label and EPA Label..................... 26
Service / Maintenance Log..................................... 27
CONGRATULATIONS ON THE PURCHASE OF YOUR
NEW WOOD BURNING FIREPLACE INSERT MANUFACTURED BY LENNOX HEARTH PRODUCTS.
When you purchased your new insert, you joined
the ranks of thousands of concerned individuals
whose answer to their home heating needs ref lects
their concern for aesthetics, ef ficien cy and ou r env ironment. We extend our continued support to help
you achieve the maximum benefit and enjoyment
available from your new insert.
It is our goal at Lennox Hearth Products to provide
you, our valued customer, with an appliance that
will ensure you years of trouble free warmth and
pleasure.
Thank you for selecting a Lennox Hearth Products
insert as the answer to your home heating needs.
Sincerely,
All of us at Lennox Hearth Products
TESTING/LISTING
Model BV4000C has been tested to UL Standards;
UL1482 for installation into residential applications . T he
listing laboratory is OMNI Environmental Services,
Beaverton, Oregon.
EPA CERTIFICATION
This fireplace insert has been tested to rigorous emissions standard, and has been certified by the Environmental Protection Agency.
PACKAGING LIST
This appliance is packaged with an accessory package,
which contains the following:
One - Installation and operation instructions manual.
One - Warranty
One -Catalytic combustor temperature probe and
sleeve.
One - Damper Hook
USING THIS MANUAL
Please read and carefully follow all of the instructions
found in this manual. Please pay special attention to the
safety instructions provided in this manual. T he Homeowner’s Care and Operation Instructions inc luded here
will assure you have many years of dependable and
enjoyable service from your appliance.
PAGE 3
PLANNING YOUR INSTALLATION
QUESTIONS TO ASK LOCAL BUILDING OFFICIAL
A correct installation is c ritical and im perative f or reducing fire hazards and perilous conditions that can arise
when wood burning appliances are improperly installed.
The installer must follow all of the manufacturers’ instructions.
The installation of a wood burning appliance m ust conform to local codes and applicable state and federal requirements. Familiarity with these requirements before
installation is essential. Impor tant considerations to discuss with local building officials include:
1. Applicable codes (i.e. Uniform Mechanic al Code,
State or Regional Codes.)?
Electrical codes: The blower system has a flexible electrical cord that must be electrically
grounded per local codes or per electrical codes:
In USA, NEC, ANSI/NFPA 70-1987.
In Canada, CSA C22.1
WARNING - Electrical Grounding Instructions: This appliance is equipped with a
three-prong (grounding) plug for your
protection against shock hazard and
should be plugged directly into a properly
grounded three-prong receptacle. Do not
cut or remove the grounding prong from
this plug.
SMOKE DETECTORS
Since there are always several potential sources of fire
in any home, we recommend installing smoke detectors.
If possible, install the sm oke detector in a hallway adjacent to the room (to reduce the pos sibility of occasional
false activation from the heat produced by the fireplace
insert). If your local code requires a smok e detector be
installed within the same room, you mus t follow the requirements of your local code. Check with your local
building department for requirements in your area.
2. Local amendments?
3. Is a permit required - cost?
(You may wish to contact your insurance company to
ask if they require this).
4. Rooms where the installation is not allowed?
PAGE 4
PLANNING YOUR INSTALLATION
FLOOR PROTECTION
This appliance requires a heat resistant noncombustible approved fireplac e hearth or hearth extension. If a hearth extension is used it must be a 3/8"
(minimum ) UL approved hearth pad or equivalent. If the
floor protection is to be stone, tile, brick , etc., it m ust be
mortared or grouted to form a continuous noncombustible surface (See Using Alternate Material AsFloor Protector on this page).
This protected area must extend a m inimum of 16" to
the front of the fuel door opening and 8" beyond both
sides of the fuel door opening
HEARTH PROTECTION
The following formulas give the means of determining
minimum thickness required of alternate materials.
Using the k formula:
Desired Thickness k value of desireMinimum thickness
of the alternate= material (per inch) x of Listed
materialk value of listedMaterial
TM (inches) = K
material (per inch)
M
x T
L
1.28
T
(inches) = 0.43* x 1”
M
1.28
Answer using k = 0.34 x 1” = 0.34 = 3/8”
3/8” thickness Micore will be required.
Using the r formula:
TM (inches) = 0.78 x T
r
M
L
TM (inches) = 0.78 x 1”
2.33*
Answer using r = 0.34 x 1” = .034 = 3/8”
3/8” thickness Micore will be required.
USING ALTERNATE MATERIAL AS A FLOOR PROTECTOR/HEARTH EXTENSION
The alternate material used as a hearth extension m ust
be constructed of a durable noncombustible material
having an equal or better insulating value (lower k value)
of k = 1.28 BTU/IN FT
that equals or exceeds r = 78 HR °F FT
2
HR °F or a thermal resistanc e
2
IN/BTU. W ith
these values, determine the minimum thickness/material required using the formula and the table
shown here (see chart - Alternative Floor ProtectionMaterials).
Note: Any noncombustible material having a thickness
of 1” whose k value is less than 1.28 or whose r value is
more than .78 is acceptable. If the alternate material
used has a higher k value or lower r value will require a
greater thickness of the material used. In some cas es , if
the k value is less or the r value higher, a thinner m aterial may be used.
Methods of determining floor protection equivalents
To determine the thickness required for any material
when either the k or r values are known:
T
= Thickness of material in inches
M
K
= K value of desired material
M
T
= Minimum listed thickness
L
Example: Micore CV230 is to be used for the floor pr otection. How thick must this material be?
At times it is important to know what combination of
materials are acceptable for use as floor pr otection. T he
“R values” are used to determ ine acceptable combinations of materials because “R values” ar e additive where
r and k values are not.
“R value” = 1 = r x thickness of material used
k
ALTERNATIVE FLOOR PROTECTION MATERIALS
ListedValuesMin. Thick
Materialk
Example: Given that the required “R value” for a suitable
floor protector used must be equal to or greater than:
“R” = r x T
= 0.78 x 1” = 0.78.
L
PAGE 5
PLANNING YOUR INSTALLATION
CHIMNEY INSPECTION
The existing fireplace should be inspected by a local fire
marshal or qualified installer for adequate serviceability
prior to installing this appliance.
Factory built fireplace: If any portion of the chim ney
system shows signs of str uctural or mechanical weak nesses, such as: cracks, leaky joints, corroded or
warped surfaces. Look f or obvious bulges in the lining,
which may indicate the need to replace that section
(use a bright flashlight. Any faulty portion must be repaired or replaced prior to installing this appliance.
Also, inspect the attic to see that the chimney has
proper clearance to combustible framing members.
Masonry fireplace: The chimney should have no
cracks, loose mortar, other signs of deterioration, or
blockage. Any necessary repairs should be done by a
qualified mason.
If the existing fireplace f lue system is dirty or has some
obstruction in it, clean it. A dirty chimney can cause your
insert to smoke when refueling, and can res ult in a chimney fire. An oversized chimney may result in less than
optimum perform ance. Installations into a large masonry
chimney may require a liner to improve performance.
CLEARANCES
WARNING: It is very important that you observe the
minimum clearances.
There are listed clearances for your fireplace inser t which
were determined in a laboratory testing and must be
maintained.
Minimum Clearance to Combustibles
Stove top to mantel:32"
Stove top to trim: 24"
Stove side to trim:9"
Stove side to sidewall:17"
DRAFT REQUIREMENTS
The appliance is mer ely one component of a larger system. The other equally important com ponent is the venting system. This is neces sary for achieving the required
flow of combustion air to the f ire chamber and for safely
removing unwanted combustion byproducts f rom the appliance. If the venting system's design does not prom ote
these ends, the system may not function properly. Poorly
functioning venting systems may create performance
problems as well as be a saf ety hazard (i.e. an oversized
chimney may result in less than optimum performance.
Installations into a large, masonry chimney may require a
liner to improve performance). A draft test should read
greater than .04' W.C. (inches water column) and less
than .08" W.C.
VENTILATION
Ventilation is essential when using a solid burning appliance. The combus tion process uses oxygen from inside
the home and it may be necessary to open a window in a
house that is well insulated.
PAGE 6
PLANNING YOUR INSTALLATION
FACTORY BUILT FIREPLA CES
This appliance is approved for installation into a listed f ac tor y
built solid fuel burning fireplace. The fireplac e firebox must
accept the insert without modification other than removing bolted or screwed together pieces such as
smoke shelf/deflectors, ash lips, screen or door tracks
and damper assem blies, that must be reinstalled to restore the fireplace to its original operating condition if
the insert is removed and not r eplaced. T he rem oval of
any part must not alter the integrity or outer shell of the
pre-engineered fireplace cabinet in any way.
Venting Requirements for factory built fireplace:
The fireplace dam per mus t be secured in the open position.
This appliance requires the use of a 6” diameter flex or
rigid, UL1777 listed 2100° HT liner or equivalent. The
liner must extend fr om the flue outlet of the appliance to
termination. Do not face seal over fireplace chimney
co o li n g a i r s ys t e m s . O ffsets c an be handled with an offset
adapter (it aligns starter pipe with fireplace flue). F or more
information on the offset adapter, see pages 9 and 25.
WARNING: Do not substitute the heat rated
2100°°°°HT liner with any other type line or a fire
may result causing property damage, personal
injury or loss of life.
MASONRY FIREPLACES
This appliance is approved for installation into a masonry
fireplace built to UBC Chapter 37 standards. Do not rem ove
brick or mortar f orm the m asonry fireplace to accom modate
this appliance.
Venting Requirements for masonry fireplace:
The fireplace dam per mus t be secured in the open position.
As a minimum , a flue extension pas t the fireplace header is
required. A preferred installation is a positive flue connection
(sealing the throat of the chimney). This appliance requires
the use of a 6” diameter flex or rigid single wall pipe,
minimum 24/25 MSG black or blued steel connector
pipe (stainless steel r ecom mended) . Offsets can be handled with an offset adapter (it aligns starter pipe with fireplace
flue). For more information on the offset adapter, see pages
9 and 25.
FIREPLACE CHIMNEY MAXIMUM SIZE TO ENSURE
PROPER DRAFT
The fireplace insert f lue size is 6 inches diameter, which
is approximately 28 square inches, the minimum. The
maximum flue size should be no more than (3) three
times the cross sectional area of the size of the fireplace
insert flue collar. In this case, that would be no larger
than a 10 inch diameter stack (area = approx. 85 sq.
inches).
Note: Formulas for calculating area:
Calculating area of a circle:
2
π
x r
= Area (π = 3.1416, r = 1/2 diameter)
PAGE 7
To calculate area of square or rectangle:
Width x Depth = Area
Notes:
! It may be necessary to use a full-length liner to
achieve adequate draft for the appliance. A draft
gauge should read more than .04 W.C.I, but less
than .08 W.C.I. for optimum performance.
! T his appliance is appro ved f or all heatf orm style
fireplaces (masonry fireplace with a metal firebox liner).
!
Measure fireplace size to make certain the insert will
fit before considering the i nstallation.
.
INSTALLATION
FIREPLACE INSTALLATION
BV4000C MINIMUM FIREPLACE DIMENSIONS
Approx. minimum Height: 21”
dimensions into fireplaceWidth: 22 ½”
Depth: 16”
CATALYTIC TEMPERATURE PROBE
Install temperature probe prior to installing insert.
To install the Catalytic Temper ature Probe locate the
plug on the top, right-hand side of the bypass c ontrol
rod. Remove the plug, install the sleeve, and place
probe in sleeve. It may be necessary to bend the
flange on the plug so it won't interfere with the probe
temperature indicator.
PAGE 8
The Catalytic Temperature Probe is provided so you
can monitor the temperature of your Catalytic Combustor. Once you have established a fire and the
Catalytic Temperature Probe indicates the temperature of your Catalytic Combustor is between 500° 600° F (approximately 20 - 25 minutes) c lose the Bypass Damper Control. Depending on the type and size
of the fuel load as well as the length of time the stove
has been burning, your Catalytic Combustor should
operate between 1000 - 1800° F.
INSTALLATION
INSTALLATION STEPS
1. Remove all ashes from the fireplace.
2. Remove all materials inside the insert and set them aside.
3. Remove the three-piece surr ound assembly (face shield)
and attach insulation material provided using a nonflammable adhesive (i.e. RTV Silicone, rated 570° F).
4. Use a large piece of cardboard or other protective material
and place it in front of the fireplace to protect floor or carpet
during installation.
5. Remove the insert from its wood pallet by removing the
screws.
6. Prepare chim ney connection system as specified f or masonry or factory built fireplaces.
7. Set the insert on the protective cardboard laid out in front of
the fireplace centered in front of the fireplace opening.
8. (Masonry Fireplace) Slide insert into the fireplace far
enough to attach the starter pipe or positive flue connection
(a minimum of a 6" starter pipe ex tending past the header
is required). See * note.
9. (Factory Built Fireplace) Slide insert into the fireplace far
enough to attach connector to flue outlet. See * note.
10. Offsets can be handled using an offset adapter (it aligns
starter pipe with flue. See Offset Adapter, page 25 for or-
dering information). Do not push insert in c ompletely until
surround assembly is installed. Care should be used to
ensure that this adjustable connector is oriented so it does
not angle downhill when positioned on the flue outlet on
top of insert.
cluded with the hardware) located at the sides of the
insert clockwise until insert is level. The leveling
bolts should be 3/8" in diameter and about three
inches in length.
12. Reaching over the top of the insert, install the starter
pipe in the stove flue, or attach the positive flue
connection to the insert. See * Note.
11. If the floor of the fireplace is lower than the hearth,
turn the adjusting bolts secured with 2 nuts (not in-
PAGE 9
Loading...
+ 19 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.