THE UNIT MUST BE INSTALLED IN ACCORDANCE WITH LOCAL SAFETY
CODES AND REGULATIONS AND CAN ONLY BE USED IN WELL
VENTILLATED AREA.
PLEASE READ CAREFULLY THE MANUFACTURER'S INSTRUCTIONS
BEFORE STARTING THIS UNIT.
THIS MANUAL IS ONLY VALID FOR UNITS DISPLAYING THE FOLLOWING
CODES: GB IR GR DA NO FI IS
In case these symbols are not displayed on the unit, please refer to the
technical documentation which will eventually detail any modifications required
to the installation of the unit in a particular country.
LENNOX have been providing environmental solutions since 1895, our range of Baltic
standards that have made LENNOX a household name. Flexible design solutions to meet YOUR needs and
uncompromising attention to detail. Engineered to last, simple to maintain and Quality that comes as standard. Information on local contacts at www.lennoxeurope.com.
All the technical and technological information contained in this manual, including any drawing and technical descriptions provided by us, remain the property of Lennox and must not be utilised (except in operation of this product),
reproduced, issued to or made available to third parties without the prior written agreement of Lennox.
The technical information and specifications contained in this manual are for reference only. The manufacturer reserves
the right to modify these without warning and without obligation to modify equipment already sold.
MAINTENANCE PLAN .............................................................................................................. 146
CERTIFICA TES
IOM / ROOFTOP BALTIC Series - 0704-E Page 3
IMPORTANT NOTICE
All Baltic units are compliant with the PED directive 97-23CE.
The following note must be followed carefully.
IMPORTANT NOTICE
All work on the unit must be carried out by a qualified and authorised employee.
Non-compliance with the following instructions may result in injury or serious accidents.
Work on the unit:
• The unit shall be isolated from the electrical supply by disconnection and locking using the
main isolating switch.
• Workers shall wear the appropriate personal protective equipment (helmet, gloves,
glasses, etc.).
Work on the electrical system:
• Work on electric components shall be performed with the power off (see below) by
employees having valid electrical qualification and authorisation.
Work on the refrigerating circuit(s):
• Monitoring of the pressures, draining and filling of the system under pressure shall be
carried out using connections provided for this purpose and suitable equipment.
• To prevent the risk of explosion due to spraying of coolant and oil, the relevant circuit shall
be drained and at zero pressure before any disassembly or unbrazing of the refrigerating
parts takes place.
• There is a residual risk of pressure build-up by degassing the oil or by heating the
exchangers after the circuit has been drained. Zero pressure shall be maintained by
venting the drain connection to the atmosphere on the low pressure side.
• The brazing shall be carried out by a qualified brazer. The brazing shall comply with the
standard NF EN1044 (minimum 30% silver).
Replacing components:
• In order to maintain CE marking compliance, replacement of components shall be carried
out using spare parts, or using parts approved by Lennox.
• Only the coolant shown on the manufacturer's nameplate shall be used, to the exclusion of
all other products (mix of coolants, hydrocarbons, etc.).
CAUTION:
In the event of fire, refrigerating circuits can cause an explosion and spray coolant gas and oil.
Page 4 - IOM / ROOFTOP BALTIC Series - 0704 - E
COMMISSIONING REPORT
Site details / Informations site
Site / Site
Unit Ref/ N° Affaire
Installer/ Installateur
………………………………………
……………………………………....
………………………………………
Controller/ Contrôleur
Model/Model
Serial No/ No Série
Refrigerant / Réfrigérant
(2) CONNECTIONS CHECK / VERIFICATIONS DE RACCORDEMENTS
Phase check/ Vérification des Phases
Yes / Oui No / Non
Voltage between Phases
Tension entre Phases
1 / 2
……………….
2 / 3
……………….
1 / 3
……………….
(3)CLIMATIC CONFIGURATION CHECK / VERIFIER LA CONFIGURATION CLIMATIC
CLIMATIC 50 Configured according to the Options and Specifications / CLIMATIC 50 configuré en fonction des options et des
spécifications: Yes/Oui No/ Non
Type / Type:
Power displayed on plate / Puissance affichée sur la plaque:
Voltage displayed on plate / Tension affichée sur la plaque:
Current displayed on plate / Intensité affichée sur la plaque:
Fan Type / Type de Ventilateur: Forward / Action
Displayed Belt Length / Longueur Courroie affichée:
Tension Checked/ Tension Vérifiée: Yes/Oui No/ Non Yes/Oui No/ Non
Alignment Checked / Alignement Vérifié: Yes/Oui No/ Non Yes/Oui No/ Non
Motor Pulley Dia/ Poulie Moteur Dia: DM mm …………………… ……………………
Fan Pulley Dia/ Poulie Ventilateur Dia: DP mm …………………… ……………………
Fan Speed / Vitesse rotation Ventilateur = Motor rpm x DM / DP
Averaged Measured Amps / Intensité Mesurée moyenne:
Shaft Mechanical Power (Refer to airflow balancing)
Puissance Mécanique à l’Arbre (Voir section réglage débit)
Operating point checked / Vérif. Point de fonctionnement: Yes/Oui No/ Non Yes/Oui No/ Non
Measured pressure drop / Pertes de charge au pressostat
…………………………… mbar
Set Points Adjusted / Changement des consignes:
Yes/Oui No/ Non
If Yes enter new values/ Si oui noter les nouvelles consignes:
3410: ………… 3411: ………… 3412: …………
(6) EXTERNAL SENSOR CHECKS / VERIFICATION DES CAPTEURS EXTERNES
Check electrical connections / Vérification des
connections électriques: Yes/Oui No/ Non
Supply Temperature / Température Soufflage ………………………..°C ………………………..°C
Return Temperature / Température reprise ………………………..°C ………………………..°C
Outdoor Temperature / Température extérieure ………………………..°C ………………………..°C
Check and record temp. in menu 2110 / Vérifier et mesurer les
températures. Dans menu 2110: Yes/Oui No/ Non
100% Fresh Air / 100% Air neuf 100% return Air / 100% Air repris
(7) MIXING AIR DAMPERS CHECKS / VERIFICATIONS VOLETS DE MELANGE
Dampers open & close freely/
Volets s’ouvrent et se ferment OK
Yes/Oui No/ Non ……………..% Yes/Oui No/ Non Yes/Oui No/ Non
% Minimum FA:
%minimum Air Neuf:
Power exhaust checked/
Ventilateur extraction
Enthalpy sensor(s) checked/
Control enthalpie installé
IOM / ROOFTOP BALTIC Series - 0704-E Page 5
COMMISSIONING REPORT
(8) REFRIGERATI
ON SECTION /
SECTION REFRIGERATION
Outdoor Fan Motor Current / Intensité Moteurs Batterie externe: Check Rotation
Motor 1 / Moteur 1 L1 ……..A L2 ……..A L3 ……A Yes/Oui No/ Non
Motor 2 / Moteur 2 L1 ……..A L2 ……..A L3 ……A Yes/Oui No/ Non
Motor 3 / Moteur 3 L1 ……..A L2 ……..A L3 ……A Yes/Oui No/ Non Comp1: …….. V
Motor 4 / Moteur 4 L1 ……..A L2 ……..A L3 ……A Yes/Oui No/ Non Comp2: …….. V
Motor 5 / Moteur 5 L1 ……..A L2 ……..A L3 ……A Yes/Oui No/ Non Comp3: …….. V
Motor 6 / Moteur 6 L1 ……..A L2 ……..A L3 ……A Yes/Oui No/ Non Comp4: …….. V
Compressor Amps COOLING / Intensité
Compresseur MODE FROID
Comp 1 …..… A …..… A …..… A ……… °C ……… °C ……… Bar ……… Bar
Comp 2 …..… A …..… A …..… A ……… °C ……… °C ……… Bar ……… Bar
Comp 3 …..… A …..… A …..… A ……… °C ……… °C ……… Bar ……… Bar
Comp 4 …..… A …..… A …..… A ……… °C ……… °C ……… Bar ……… Bar
Comp 1 …..… A …..… A …..… A ……… °C ……… °C ……… Bar ……… Bar
Comp 2 …..… A …..… A …..… A ……… °C ……… °C ……… Bar ……… Bar
Comp 3 …..… A …..… A …..… A ……… °C ……… °C ……… Bar ……… Bar
Comp 4 …..… A …..… A …..… A ……… °C ……… °C ……… Bar ……… Bar
HP cut out / Coupure HP ……Bar LP cut out / Coupure sécurité BP ………..…... Bar
(9) HOT WATER COIL SECTION / SECTION BATTERIE EAU CHAUDE
Check Three Way Valve Movement / Vérification Mouvement Vanne trois voies: Yes/Oui No/ Non
(10) GAS HEATING SECTION / RAMPE GAZ
Gas Burner N°1 / Brûleur gaz N°1 Gas Burner N°2 / Brûleur gaz N°2
Size / Taille:
……………………….
Pipe size/ tuyauterie:
Line press./ press. ligne :
………………………
Check manifold pressure/ Pression injection:
High fire/Grande allure…….…Low fire/Petite allure………..
Pressure cut out airflow press switch / Pression coupure
pressostat débit d’air : ……………………mbar /Pa
Motor amps
I moteur:
……….A
Flue temp /
temp fumées
……… °C
Valve type / Type vanne:
…………………….
Gas type / Type gas : G…….
Drop test / test pression
Yes/Oui No/ Non
CO2 %:
………%
CO ppm:
………%
Size / Taille:
……………………….
Pipe size/ tuyauterie
line press./ press. ligne :
………………………
High fire/Grande allure…….…... Low fire/Petite allure………..
Motor Amps
Check manifold pressure/ Pression injection:
Pressure cut out airflow press switch / Pression coupure
pressostat débit d’air : ……………………mbar /Pa
I Moteur:
……….A
Flue temp /
temp fumées
………. °C
Valve type / Type vanne:
Gas type / Type gas : G…….
Drop test / test pression
Yes/Oui No/ Non
CO2 %:
………%
(11) REMOTE CONTROL BMS CHECK / VERIFICATIONS BMS CONTROL A DISTANCE
Type / Type:
…………………………..
Sensor type / Type Capteur
………………………………..
KP07 KP/17 checked/ vérifiées:
Yes/Oui No/ Non
Interconnect wiring checked:
Yes/Oui No/ Non
Compressor
Voltage/ Tension
Compresseur.
HP / HP
HP / HP
…………………….
CO ppm:
………%
Page 6 - IOM / ROOFTOP BALTIC Series - 0704 - E
COMMISSIONING REPORT
dessous avant de transférer les consignes de zones vers le contrôleur
It is recommended that you fill the two tables below before transferring the zone settings to the Climatic controller.
Il est recommandé de remplir les deux tableaux ciClimatic50.
Refer to control section page 55 / Se référer à la section régulation page 55
On receipt of a new equipment please check the following
points. It is the customer's responsibility to ensure that the
products are in good working order:
- The exterior has not been damaged in any way.
- The lifting and handling equipment are suitable for the
equipment and comply with the specifications of the handling
instructions enclosed here-in.
- Accessories ordered for on site installation have been
delivered and are in good working order.
- The equipment supplied corresponds to the order and
matches the delivery note.
If the product is damaged, exact details must be confirmed
in writing by registered post to the shipping company within
48 hours of delivery (working days). A copy of the letter must
be addressed to Lennox and the supplier or distributor for
information purposes. Failure to comply will invalidate any
claim against the shipping company.
RATING PLATE
The rating plate provides a complete reference for the model
and ensures that the unit corresponds to the model ordered.
It states the electrical power consumption of the unit on startup, its rated power and its supply voltage. The supply voltage
must not deviate beyond +10/-15 %. The start-up power is
the maximum value likely to be achieved for the specified
operational voltage. The customer must have a suitable
electrical supply. It is therefore important to check whether
the supply voltage stated on the unit's rating plate is
compatible with that of the mains electrical supply. The rating
plate also states the year of manufacture as well as the type
of refrigerant used and the required charge for each
compressor circuit.
STORAGE
When units are delivered on site they are not always required
immediately and are sometimes put into storage. In the event
of medium to long-term storage, we recommend the following
procedures :
- Ensure that there is no water in the hydraulic systems.
- Keep the heat exchanger covers in position (AQUILUX cover).
- Keep protective plastic film in position.
- Ensure the electrical panels are closed.
- Keep all items and options supplied in a dry and clean
place for future assembly before using the equipment.
MAINTENANCE KEY
On delivery we recommend that you keep the key which is
attached to an eyebolt in a safe and accessible place. This
allows you to open the panels for maintenance and
installation work.
The locks are ¼ turn + then tighter (figure 1).
Fig. 1
CONDENSATE DRAINS
The condensate drains are not assembled when delivered
and are stored
in the electrical panel with their clamping collars.
To assemble them, insert them on the condensate tray outlets
and use a screwdriver to tighten the collars (Figure 2).
Without hoodkg 394414541 528 547 529 589 591 604 604619796852
With hoodkg417437569 556 575 556 622 624 677 67765283 7893
Weight of gas units
Standard heat without hoodkg445465602 589 608 590 663 665 678 678693904960
Standard heat with hoodkg468488630 617 636 618 696 698 711 7117269451001
SS
S
SS
High heat without hoodkg454474621 608 627 609 685 687 700 7007159631019
High heat with hoodkg4 7 7497649 636 655 637 661 720 733 73374810041060
SS
DD
SS
DD
SS
DD
SS
DD
SS
S
D
S
D
S
D
S
SS
DD
SS
DD
SS
DD
SS
DD
SS
DD
SS
S
D
S
SS
DD
D
SS
DD
DD
S
D
SS
DD
D
SS
DD
SS
DD
S
D
SS
DD
DD
S
D
SS
DD
SS
DD
S
D
SS
DD
DD
D
DD
DD
D
DD
DD
D
DD
DD
D
DD
Page 10 - IOM / ROOFTOP BALTIC Series - 0704 - E
TRANSPORT - HANDLING
RETRACTABLE LIFTING LUG
LIFTING B BOX
18501410
(mini)(mini)
LIFTING D BOX
LIFTING C BOX
19301700
(mini)(mini)
LIFTING E BOX
2250
(mini)
1700
(mini)
2890
(mini)(mini)
IOM / ROOFTOP BALTIC Series - 0704-E Page 11
2080
TRANSPORT - HANDLING
LIFTING THE ROOFCURBS
Adjustable Roofcurb
A
Exhaust Horizontal Roofcurb
A
B
B
Dimensions (mm)
B boxC boxD boxE box
A1890173517352085
B1100129515451995
Weights (kg)
B boxC boxD boxE box
No aux.heating879 41041 52
With aux.heating8690100138.2
Exhaust Vertical Roofcurb
A
B
Dimensions (mm)
B boxC boxD boxE box
A2050190019002250
B1160136016102060
Page 12 - IOM / ROOFTOP BALTIC Series - 0704 - E
Weights (kg)
B boxC boxD boxE box
Vertical No aux.heating19 22202 4 0370
Vertical With aux.heating194194240365
Horizontal142168185301
TRANSPORT - HANDLING
Multidirectional (mm)
A
Energy Recovery
A
B
B
Dimensions (mm)
B boxC boxD boxE box
A2050190019002250
B1160136016102060
Weights (kg)
B boxC boxD boxE box
No aux.heating818 81001 47
With aux.heating909310 3146.7
Dimensions (mm)
B boxC boxD boxE box
A1290129012901290
B820117015471895
Weights (kg)
B boxC boxD boxE box
143172229317
IOM / ROOFTOP BALTIC Series - 0704-E Page 13
TRANSPORT - HANDLING
FORKLIFT PROTECTIONS
NEVER LIFT THE UNIT WITHOUT FORLIFT PROTECTIONS
REMOVE FORKLIFT PROTECTIONS
BEFORE INSTALLATION
PRELIMINARY CHECKS
Before installing the equipment, the following points MUST
be checked :
-Have the forklift protections been removed ?
-Is there sufficient space for the equipment?
-Is the surface on which the equipment is to be installed
sufficiently solid to withstand its weight? A detailed study of
the frame must be made beforehand.
-Do the supply and return ductwork openings excessively
weaken the structure?
-Are there any obstructing items which could hinder the
operation of the equipment?
-Does the electrical power available correspond to the
equipment's electrical specifications?
-Is drainage provided for the condensate?
-Is there sufficient access for maintenance?
-Installation of the equipment could require different lifting
methods which may vary with each installation (helicopter or
crane). Have these been evaluated ?
-Ensure that the unit is installed in accordance with the
installation instructions and local applicable codes.
-Check to ensure that the refrigerant lines do not rub against
the cabinet or against other refrigerant lines.
In general, make sure no obstacles (walls, trees or roof
ledges) are obstructing the duct connections or hindering
assembly and maintenance access.
INSTALLATION REQUIREMENTS
The surface on which the equipment is to be installed
must be clean and free of any obstacles which could
hinder the flow of air to the condensers:
-Avoid uneven surfaces
-Avoid installing two units side by side or close to each
other as this may restrict the airflow to the condensers.
Before installing a packaged Rooftop unit it is important to
understand :
-The direction of prevailing winds.
-The direction and position of air flows.
-The external dimensions of the unit and the dimensions
of the supply and return air connections.
-The arrangement of the doors and the space required to
open them to access the various components.
CONNECTIONS
-Ensure that all the pipe-work crossing walls or roofs are
secured, sealed and insulated.
-To avoid condensation problems, make sure that all pipes
are insulated according to the temperatures of fluids and
type of rooms.
NOTE: The AQUILUX protection sheets fitted to the finned
surfaces must be removed prior to start up.
Page 14 - IOM / ROOFTOP BALTIC Series - 0704 - E
TRANSPORT - HANDLING
MINIMUM CLEARANCE AROUND THE UNIT
Figure 4 shows the required clearances and service access around the unit.
NOTE : Ensure the fresh air inlet does not face prevailing wind direction.
D
A
ABC D
B Box1000 (1)1500 (2)15001000
C Box1200 (1)1500 (2)15001000
D Box1400 (1)1500 (2)15001000
E Box1800 (1)1500 (2)15001100
C
B
(1) Add 1 meter if the units are equipped with gas burner
(2) Double this distance if the units are equipped with extraction
IOM / ROOFTOP BALTIC Series - 0704-E Page 15
INSTALLATION ON A ROOF MOUNTING FRAMES
NON ADJUSTABLE NON ASSEMBLiED ROOFCURB INSTALLATION ..
INSTALLATION ON A ROOF MOUNTING FRAME .......................................
CURBING AND FLASHING .............................................................................
P29
P41
P41
As levels are adjustable, observe the following
recommendations when installing the equipment.
Above all, ensure that all the adjustable returns are facing
outward 1 ( figure 3). They are usually turned inside-out for
transport.
1
Fig. 3
Place the roof mounting frame on the trimmer beam by first
lining up the inlet and the outlet opening. ("2"- figure 4)
After levelling the frame, secure the adjustable returns on
the trimmer (figure 5).
2
Fig. 4
Fig. 5
It is important to centre the unit on the roof frame.
Page 16 - IOM / ROOFTOP BALTIC Series - 0704 - E
adjustable ROOFCURB DRAWINGS
020025
15834747690.5
AA
1896
1186
103.51085103.5103.51795103.5
319.2547319.5
Roof opening 1795 x 1085
2D
D
12890
5
D
A-A
8
D
848
2D
247.5
A
BCK / BHK without auxiliary heating54339 5
BGK / BDK or BCK / BHK with auxiliary heating 2 476 91
B
AB
Down Supply Air
1D
DownReturn Air
2D
Down main power entry
4D
Down hot water
5D
Entry
Main Power Entry
8
IOM / ROOFTOP BALTIC Series - 0704-E Page 17
adjustable ROOFCURB DRAWINGS
A
030035
13831743
103.51282103.5
747318
158347
2D
227.5100
A-A
97.5
A
A
847.5
Roof opening 1642 x 1282
D
401
103.51642103.5
2D
8
90.5
BCK / BHK without auxiliary heating49 66 334 003 49
BGK / BDK or BCK / BHK with auxiliary heating 6 363 517 902 41
BCD
ABCD
5
D
Down Supply Air
1D
DownReturn Air
2D
Down main power entry
4D
Down hot water
5D
Entry
Main Power Entry
8
Page 18 - IOM / ROOFTOP BALTIC Series - 0704 - E
adjustable ROOFCURB DRAWINGS
045050040
1633
103.51532103.5
1072280.5
157347847.5
2D
227100
97
5D
D
ABC
1743
401
103.51642103.5
Roof opening 1642 x 1532
2D
8
DD
ABCD
BCK / BHK without auxiliary heating63 73 521050230
BGK / BDK or BCK / BHK with auxiliary heating 4 967 505 003 82
Down Supply Air
1D
DownReturn Air
2D
Down main power entry
4D
Down hot water
5D
Entry
Main Power Entry
8
IOM / ROOFTOP BALTIC Series - 0704-E Page 19
adjustable ROOFCURB DRAWINGS
2082
2D
BCK
BhK
(*) without auxiliary electric heater
without hot water coil.
292.51497292.5
5
D
347199
060070
2092
401
103.51992103.5103.51982103.5
2D
97
D
D
380287380431.5
410466
1197
Down Supply Air
1D
DownReturn Air
2D
8
Page 20 - IOM / ROOFTOP BALTIC Series - 0704 - E
Down main power entry
4D
Down hot water
5D
Entry
Main Power Entry
8
adjustable ROOFCURB DRAWINGS
2082
2D
BGK
BDK
(*) This roofcurb is also necessary for all cooling
only or heatpump rooftop with auxiliary electric
heater or hot water coil.
292.51497292.5
5
D
347199
060070
2092
401
103.51992103.5103.51982103.5
2D
97
D
D
380287380431.5
410466
1197
Down Supply Air
1D
DownReturn Air
2D
8
Down main power entry
4D
Down hot water
5D
Entry
Main Power Entry
8
IOM / ROOFTOP BALTIC Series - 0704-E Page 21
MULTIDIRECTIONAL HORIZONTAL ROOFCURB
2F'
2F
BCK
BHK
(*) without auxiliary electric heater
without hot water coil.
2F'
020025
1F1F
1F'
2F
1F'
Front supply air
1F
Front supply air
1F'
Front return air
2F
Front return air
2F'
1F
2F'
2F
2F'
1F'
1F
WARNING : ONL Y ONE OF THE 4 FOLLOWINGS POSSIBILITIES :
2F - 1F / 2F - 1F'
2F' - 1F / 2F' - 1F'
Page 22 - IOM / ROOFTOP BALTIC Series - 0704 - E
MULTIDIRECTIONAL HORIZONTAL ROOFCURB
2F'
1F'
2F
1F
BGK
BDK
(*) This roofcurb is also necessary for all cooling
only or heatpump rooftop with auxiliary electric
heater or hot water coil.
2F'
020025
1F
1F'
2F
1F
Front supply air
1F
Front supply air
1F'
Front return air
2F
2F'
2F
1F'
1F
WARNING : ONL Y ONE OF THE 4 FOLLOWINGS POSSIBILITIES :
2F - 1F / 2F - 1F'
2F' - 1F / 2F' - 1F'
2F'
Front return air
2F'
IOM / ROOFTOP BALTIC Series - 0704-E Page 23
MUL TIDIRECTIONAL HORIZONTAL ROOFCURB
2F'
2F
1F
BCK
BHK
(*) without auxiliary electric heater
without hot water coil.
1F'1F1F'
035030
2F
1F'
1F
Front supply air
1F
Front supply air
1F'
Front return air
2F
2F'
2F
2F'
1F'
WARNING : ONL Y ONE OF THE 4 FOLLOWINGS POSSIBILITIES :
2F - 1F / 2F - 1F'
2F' - 1F / 2F' - 1F'
1F
Front return air
2F'
Page 24 - IOM / ROOFTOP BALTIC Series - 0704 - E
MULTIDIRECTIONAL HORIZONTAL ROOFCURB
BGK
BDK
(*) This roofcurb is also necessary for all cooling
only or heatpump rooftop with auxiliary electric
heater or hot water coil.
2F'2F1F2F'
030035
1F
1F'
2F
1F'
Front supply air
1F
Front supply air
1F'
1F2F'
2F
2F'
1F'
WARNING : ONL Y ONE OF THE 4 FOLLOWINGS POSSIBILITIES :
2F - 1F / 2F - 1F'
2F' - 1F / 2F' - 1F'
1F
Front return air
2F
Front return air
2F'
IOM / ROOFTOP BALTIC Series - 0704-E Page 25
MULTIDIRECTIONAL HORIZONTAL ROOFCURB
2F'
1F'
2F
2F
1F
BGK
BDK
(*) This roofcurb is also necessary for all cooling only or heatpump
rooftop with auxiliary electric heater or hot water coil.
2F'
1F'
045050040
1F
1F'
2F
2F'
Front supply air
1F
Front supply air
1F'
Front return air
2F
Front return air
2F'
1F
2F'1F
WARNING : ONL Y ONE OF THE 4 FOLLOWINGS POSSIBILITIES :
2F - 1F / 2F - 1F'
2F' - 1F / 2F' - 1F'
Page 26 - IOM / ROOFTOP BALTIC Series - 0704 - E
MULTIDIRECTIONAL HORIZONTAL ROOFCURB
BCK
BHK
2080
2F
340140034013070090090
1F'
750
1F
2F
20902080
2F'
BGK
BDK
71040
060070
1F'
4651400215
2F
500
100
1F
1F
1F'
2F
2F'
Front supply air
Front supply air
Front return air
1F'
2F'
1F
WARNING : ONL Y ONE OF THE 4 FOLLOWINGS POSSIBILITIES :
2F - 1F / 2F - 1F'
2F' - 1F / 2F' - 1F'
Front return air
2F'
IOM / ROOFTOP BALTIC Series - 0704-E Page 27
INST ALLATION ON A ROOF MOUNTING FRAME
NON ADJUSTABLE NON ASSEMBLIED ROOFCURB INSTALLATION
FRAME PAR TS IDENTIFICA TION
Figure 6 shows the different parts for identification
INSTALLATION
The roof mounting frame provides support when the units are installed in down-flow configurations.
The non adjustable, non assembled roof mounting frame can be installed directly on decks having adequate structural
strength or on roof supports under deck. See page 29 for frame dimensions, location of supply and return air opening
NOTE: frame assembly must be installed flat, levelled within 5mm per linear meter in any direction.
UNIT FLOOR
INSULA TION
AIR DUCT
Fig. 6
UNIT FLOOR
UNIT SUPPORT RAIL
ROOFCURB
Page 28 - IOM / ROOFTOP BALTIC Series - 0704 - E
Non-adjustable ROOFCURB
BCK = Cooling only unit
BHK = Heat pump unit
BGK = Cooling only unit with gas fired heating
BDK = Heat pump unit with gas fired heating
A
JI
2D
All units
B
D
Roof opening I x J
2D
D
D
G
H
E
Down Supply Air
1D
Return Air
2D
TypeTailleABCDEFGHIJ
All020
All030
All040
All060
118318936914002462465155017831083
025
138017407904003512406755016401280
035
0451630174010504003522296755016401530
050
20802090140040042525572015619901980
070
CF
Main Power Entry 030-035-040-045-050
8
Main Power Entry 020-025
8'
(*) Non adjustable, non assembled roofcurb.
IOM / ROOFTOP BALTIC Series - 0704-E Page 29