Lennox BCE3MC, BCS3MC Installation Instructions Manual

Page 1
INSTALLATION INSTRUCTIONS
BCE3M*C & BCS3M*C SERIES AIR HANDLER
These instructions must be read and understood completely before attempting installation.
This is a safety alert symbol and should never be ignored. When you see this symbol on labels or in manuals, be alert to the potential for personal injury or death.
Table of Contents
Unit Dimensions ..........................................................2
Shipping and Packing List ...........................................3
General ........................................................................3
Requirements ..............................................................3
Installation Clearances ................................................4
Installation ...................................................................4
Condensate Drain........................................................8
Duct System and Filters ............................................10
Sealing the Unit .........................................................13
Electrical Connections ...............................................13
Air Flow — Cooling Blower Speed ............................17
Check-Out Procedures ..............................................19
Operation ...................................................................19
Maintenance ..............................................................20
Cabinet Insulation ......................................................20
Use of Air Handler During Construction.....................21
THIS MANUAL MUST BE LEFT WITH THE
HOMEOWNER FOR FUTURE REFERENCE
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a licensed professional installer (or equivalent), service agency or the gas supplier.
215 Metropolitan Drive
West Columbia, SC 29170
507621-01 Issue 1720 Page 1 of 23
WARNING
This product contains a chemical known to the State of California to cause cancer, birth defects or other reproductive harm.
CAUTION
The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFCs, HCFCs and HFCs) as of July 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for noncompliance.
*P507621-01*
(P) 507621-01
Page 2
FRONT VIEW SIDE VIEW
1 (25)
Unit Dimensions
SUPPLY AIR
OPENING
E
1 (25)
LINE VOLTAGE
INLETS
(Top and Left Side)
3-5/8
(92)
5 (102)
F
TOP VIEW
CIRCUIT
BREAKER
COVER
AIR FLOW
G
D
SUCTION
LINE
LIQUID
LINE
1 (25)
LOW VOLTAGE
INLETS
(Top and Right Side)
3/4 (19)
LINE VOLTAGE INLETS
A
CONDENSATE DRAIN
PIPING PLATE (4)
(2-1/4 x 3-3/4)
FILTER ACCESS
(Top and Right Side)
LOW VOLTAGE INLETS
(Either Side)
CB
1/2
(13)
JH
Dimension
1-1/8
(29)
OPENING OPENING
1-1/8
(29)
018 024 030 036 042 048/060
in. mm in. mm in. mm in. mm in. mm in. mm
A 38 965 40-1/2 1029 43 1092 52-1/2 1334 48 1219 52-1/2 1334
B 15 381 18-1/2 470 18-1/2 470 21-7/8 556 21-7/8 556 21-7/8 556
C 22 559 22 559 22 559 22 559 26-1/4 667 26-1/4 667
D 13 330 16-1/2 419 16-1/2 419 19-7/8 505 19-7/8 505 19-7/8 505
E 14-1/2 368 14-1/2 368 14-1/2 368 14-1/2 368 18-3/4 476 18-3/4 476
F 8 203 8 203 8 203 8 203 9-1/4 235 9-1/4 235
G 5-5/8 143 5-5/8 143 5-5/8 143 5-5/8 143 4-1/2 114 4-1/2 114
H 12-3/4 324 16-1/4 413 16-1/4 413 19-5/8 498 19-5/8 498 19-5/8 498
J 20-3/8 518 20-3/8 518 20-3/8 518 20-3/8 518 24-5/8 625 24-5/8 625
Note: Unit is shipped congured for horizontal left-hand air discharge. Unit may be converted to horizontal right-hand air
discharge by repositioning horizontal drain pan.
Dimensions remain the same in all congurations.
1-1/8
(29)
507621-01Issue 1720Page 2 of 23
Page 3
NOTE: These instructions are intended as a general guide and
do not supersede national, state or local codes in any way.
Shipping and Packing List
Package 1 of 1 contains the following:
1 - Assembled air handler unit factory-equipped for upow
or horizontal air discharge application (includes upow
and horizontal drain pans and pre-installed air lter).
Check equipment for shipping damage. If found, immediately report damage to the last carrier. Check the
unit rating plate to conrm that delivered unit matches
order.
General
These air handlers are designed for indoor installation only. As shipped, the unit is ready for installation in either
upow or horizontal left-hand air discharge applications. Horizontal drain pan may be repositioned in the eld to
allow installation in the horizontal right-hand air discharge
position. Downow applications can be accomplished by purchasing the available downow kit (see table 1).
All units come with a metering device installed.
CAUTION
Physical contact with metal edges and corners while applying excessive force or rapid motion can result in personal injury. Be aware of, and use caution when working near these areas during installation or while servicing this equipment.
These instructions are intended as a general guide and do not supersede local or national codes in any way. Consult authorities having jurisdiction before installation.
Compliance with all local, state, or national codes pertaining to this type of equipment should be determined prior to installation. Read this instruction manual, as well as the instructions supplied in separate equipment, before starting the installation.
In addition to conforming to manufacturer’s installation instructions and local municipal building codes, installation of Allied Air air handler units (with or without optional electric heat), MUST conform with National Fire Protection Association (NFPA) standards: “Standard for Installation of Air Conditioning and Ventilation Systems” (NFPA No. 90A) and “Standard for Installation of Residence Type Warm Air Heating and Air Conditioning Systems” (NFPA No. 90B).
Model Downow Kit
-018 96W37
-024, -030 96W38
-036 97W95
-042, -048, -060 97W96
Table 1. Downow Kits
Requirements
IMPORTANT
These units are designed to match, and must be used with, outdoor units as rated. The indoor sections are manufactured with a metering device installed to provide optimum refrigerant control and system performance with a variety of different capacities of outdoor units.
WARNING
Excessive Weight Hazard - Use two or more people when moving and installing the unit. Failure to do so can result in back or other type of injury.
All models are designed for indoor installation only. The
installation of the air handler, eld wiring, duct system, etc.
must conform to the requirements of the National Electrical Code, ANSI/NFPA No. 70 (latest edition) in the United States, and any state laws, and local ordinances (including plumbing or waste water codes). Local authorities having jurisdiction should be consulted before installation is made. Such applicable regulations or requirements take precedence over the general instructions in this manual.
Install the conditioned air plenum, ducts and air lters
(provided) in accordance with NFPA 90B Standard for the Installation of Warm Air Heating and Air-Conditioning Systems (latest edition).
The air handler is shipped from the factory completely
assembled. The unit is provided with anges for the
connection of the duct system.
Do not remove the cabinet knockouts until it has been determined which knockouts will need to be removed for the installation.
Select the air discharge position which best suits the site conditions. Consider required clearances, space, routing requirements for refrigerant line, condensate disposal,
lters, duct system, wiring, and accessibility for service. Refer to the rating plate on the air handler for specic
information.
507621-01 Issue 1720 Page 3 of 23
Page 4
WARNING
Installation Clearances
Danger of explosion. Keep ammable
materials and vapors, such as gasoline, away from air handler. Place air handler so that heating elements are at least 18 inches (46
cm) above the oor for a garage installation.
Failure to follow these instructions can result
in death, explosion, or re.
IMPORTANT
Excessive condensation may occur if the unit is installed in a warm, humid place. When the unit is installed in an unconditioned space, apply sealant around the electrical wires, refrigerant piping, and condensate lines at the point where they enter the cabinet.
Apply sealant on the inside of the cabinet at the point where the electrical wires exit through the conduit opening. This will also keep warm and moist unconditioned air out of the air handler cabinet where it will form condensate on the cooler control box and electrical controls.
IMPORTANT
Non-Ducted Return Closet Installation
The air handler can be installed in a closet with a false bottom to form a return air plenum. It may also be installed with a return air plenum under the air handler.
Louvers or return air grilles are eld-supplied. Local codes
may limit application of systems without a ducted return to single-story buildings.
When a BCE3M*C or BCS3M*C unit is installed in a closet with a louvered return opening, the minimum open area for the louvers will be:
320 square inches for -018 and -024 models;
360 square inches for -030 and -036 models;
450 square inches for -042 thru -060 models.
If the free area is not known, assume a 25% free area for wood or a 75% free area for metal louvers or grilles. Using the louver dimensions and the 25% or 75% assumption, determine if the open area meets the minimum open area listed above.
If a return air plenum is used, the return air grille should be immediately in front of the opening in the plenum to allow
for the free ow of return air. When not installed in front of
the opening, there must be adequate clearance around the
air handler to allow for the free ow of return air.
This unit is approved for installation clearance to combustible material as stated on the unit rating plate. Accessibility and service clearances must take precedence over combustible material clearances.
The air handler must be installed so that free access
is allowed to the coil/lter compartment and blower/
control compartment.
IMPORTANT
Horizontal applications of the air handler must be installed sloped (approximately 5/8 inch) toward the drain pan openings to ensure proper condensate drainage.
Installation
General Information
WARNING
Improper installation, adjustment, alteration, service, or maintenance can cause property damage, personal injury, or loss of life. Installation and service must be
performed by a qualied installer or service agency.
These units are factory-assembled and congured for installation in upow or horizontal left-hand air discharge
applications. Horizontal drain pan may be repositioned in
the eld to allow installation in the horizontal right-hand air
discharge position.
Each unit consists of a blower assembly, refrigerant coil, and controls in an insulated galvanized steel factory-
nished enclosure. Knockouts are provided for electrical
wiring entrance.
For ease in installation, it is best to make any necessary
coil conguration changes before setting air handler in
place.
507621-01Issue 1720Page 4 of 23
Page 5
For all performance testing, units must be tested in the
upow orientation with the horizontal drain pan removed.
Refrigerant Metering Device
These units are equipped with a factory-installed metering device (TXV or piston). Ensure the indoor coil metering device is properly sized for the outdoor unit being used.
Upow Application
1. The air handler must be supported on the bottom only
and set on solid oor or eld-supplied support frame. Securely attach the air handler to the oor or support
frame.
2. If installing a unit in an upow application, remove the horizontal drain pan.
IMPORTANT - The horizontal drain pan is not required
in upow air discharge installations; its removal provides the best efciency and air ow.
3. Place the unit in the desired location and slope unit. Connect return and supply air plenums as required using sheet metal screws.
4. Install units that have no return air plenum on a stand
that is at least 14” from the oor. This will allow proper
air return.
NOTE: When the unit is installed in horizontal applications, a secondary drain pan is recommended. Refer to local codes.
NOTE: This unit may be installed in left-hand or right-hand air discharge horizontal applications. Adequate support must be provided to ensure cabinet integrity. Ensure that there is adequate room to remove service and access panels if installing in the horizontal position.
Left-Hand Air Discharge
1. Determine which plugs are required for drain line connections.
2. With access door removed, remove drain line plugs to install drain lines.
3. Set unit so that it is sloped toward the drain pan end of
the unit (see gure 11).
4. The left-hand air discharge horizontal conguration is shown in gure 2.
AIR FLOW
Drains
HORIZONTAL DRAIN PAN
IMPORTANT - REMOVE PAN
FOR BEST EFFICIENCY
AND AIR FLOW.
HORIZONTAL DRAIN
UP-FLOW
DRAIN PAN
UP-FLOW DRAIN
CONNECTIONS (BOTH
SIDES; USE ONE SIDE
OR OTHER)
CONNECTIONS (BOTH SIDES; NOT USED)
Figure 1. Upow Conguration
Horizontal Applications
IMPORTANT
When removing the coil, there is possible danger of equipment damage and personal injury. Be careful when removing the coil assembly from a unit installed in right- or left-hand applications. The coil may tip into the drain pan once it is clear of the cabinet. Support the coil when removing it.
PLUGS
LEFT‐HAND DRAINS
Figure 2. Left-Hand Discharge Conguration
5. If the unit is suspended, the entire length of the cabinet must be supported. If you use a chain or strap, use a piece of angle iron or sheet metal attached to the unit (either above or below) to support the length of the cabinet. Use securing screws no longer than 1/2 inch
to avoid damaging the coil or lter. See gure 3. Use
sheet metal screws to connect the return and supply air plenums as required.
ANGLE IRON OR SHEET METAL
MAXIMUM 1/2” LONG SCREW
AIR FLOW
FRONT VIEW
ELECTRICAL INLET CLEARANCE
4 IN. (102 MM)
END VIEW
Figure 3. Suspending Horizontal Unit
507621-01 Issue 1720 Page 5 of 23
Page 6
Right-Hand Air Discharge
For horizontal right-hand air discharge, the following eld modications are required.
1. Remove and set aside blower and coil access panels.
2. Remove brackets securing pan to unit. See gure 4.
Figure 4
3. Remove coil assembly, bottom drain pan and horizontal drain pan as one unit from the air handler.
See gure 5.
4. Remove the blow-off prevention brackets, top cap and drip pan between slabs. Move the horizontal drain pan
to the opposite side of the coil. See gure 6.
NOTE: The 1.5- and 2-ton units do not have or require blow-off prevention brackets or drip pan.
Figure 5
Figure 6
507621-01Issue 1720Page 6 of 23
Page 7
5. Reinstall the top cap. Rotate the blow-off prevention brackets 180º and reinstall using the same screws. Use the correct mounting holes; the brackets must
cover the hairpins. See gure 7.
7. Reinstall the brackets that hold the coil and horizontal
drain pan in place. See gure 9.
Figure 7
6. Slide coil assembly, bottom drain pan and horizontal drain pan as one unit back into the air handler. See
gure 8.
Figure 9
8. Reinstall the blower and coil access panels.
Figure 8
507621-01 Issue 1720 Page 7 of 23
Page 8
Condensate Drain
The air handler is provided with ¾” NPT condensate drain connections.
IMPORTANT
On units of this type, where the blower “draws” rather than “blows” air through the coil, traps must be installed in the condensate drain lines (primary and auxiliary, if used). Traps prevent the blower from drawing air through the drain lines into the air supply.
ABOVE
FINISHED
SPACE?
YES
NOTE - WHEN AN AIR HANDLER IS LOCATED ABOVE A FINISHED SPACE, THE SECONDARY DRAIN PA N MUST HAVE A LARGER FOOTPRINT THAN THE AIR HANDLER.
ALWAYS RUN A SECONDARY (OVERFLOW) DRAIN LINE. IF NOT POSSIBLE, INSTA LL LOW VOLTAGE OVERFLOW SWITCH KIT. WIRE KIT TO SHUT DOWN COMPRESSOR PER INSTRUCTIONS.
USE TWO-PA RT 3/4” FEMALE SLIP INLET AND MALE ADAPTER
NO
WHEN OBSTRUCTIONS PREVENT DIRECT THREADING OF OVERFLOW SWITCH.
SECONDARY (OVERFLOW) DRAIN LINE
PART #
X3169
AIR HANDLER DRAIN PA N
MAIN DRAIN
WHEN A COIL IS LOCATED ABOVE A FINISHED SPACE, A 3/4” (19.1MM) SECONDARY DRAIN LINE MUST BE:
CONNECTED TO SECONDARY DRAIN PAN
SECONDARY
DRAIN PAN
TRAP MUST BE DEEP ENOUGH TO OFFSET MAXIMUM STATIC DIFFERENCES — GENERALLY, TWO INCHES (51MM).
1
P-TRAP 49P66 REQUIRES A LARGER INSTALLATION SPACE THAN THE J-TRAP 91P90.
2
PIPE NIPPLE PROVIDED IN BAG ASSEMBLY - SCH 80, 3/4” I. D. X 5” - 34K7401 (1): CUT THE PIPE
IN HALF AND USE IT TO ROUTE THE MAIN DRAIN.
OR
CONNECTED TO THE SECONDARY
(OVERFLOW) DRAIN OUTLET OF THE AIR HANDLER DRAIN PAN.
VENT MUST EXTEND
ABOVE HEIGHT OF
COIL DRAIN PAN BY
TWO INCHES (51MM)
CLEAN OUT
PRESS IN
(DO NOT GLUE)
1” X 3/4” X 3/4”
REDUCING
TEE WITH
PLUG
1 #
P-TRAP J-TRAP # 91P90
40 P- OR J-TRAP 3/4”
FOR NEGATIVE PRESSURE COILS (BLOWER AFTER COIL), A TRAP IS REQUIRED ON THE MAIN DRAIN LINE CONNECTED TO COIL. SEE LOCAL CODES FOR TRAP REQUIREMENTS ON SECONDARY DRAINS.
49P66,
OR ANY PVC SCH
VENT
2”
(51MM)
TRAP DEPTH
DRAIN LINE SHOULD SLOPE A MINIMUM OF ONE INCH PER 10 FEET (25MM PER 3 METERS)
TO APPROVED
DRAIN
Figure 10. Typical Main and Overow Drain
IMPORTANT
A eld-fabricated secondary drain pan, with a drain
pipe to the outside of the building, is required in all
installations over a nished living space or in any area that may be damaged by overow from the main drain
pan. In some localities, local codes may require a secondary drain pan for any horizontal installation.
507621-01Issue 1720Page 8 of 23
Page 9
Sloping the Unit
Make sure the unit is sloped (similar to the slope shown in
gure 11) (horizontal or upow) so that the drain pan will
empty completely without water standing in the pan.
NOTE: When installing drain line connection ttings to the drain pan, hand tighten the tting and use a thread sealant. Over-tightening the ttings can split
connections on the drain pan.
THIS CORNER SHOULD BE 5/8” (+/- 1/8”) HIGHER THAN DRAIN CORNER
THIS CORNER SHOULD BE 5/8” (+/- 1/8”) HIGHER THAN DRAIN CORNER
LEVEL PLANE
DRAIN CORNER
LEVEL PLANE
Figure 11. Sloping the Drain
Install Condensate Drain
The air handler is equipped with ¾” NPT condensate drain connections.
IMPORTANT
On some pans, the primary and secondary drain holes
have knockouts. Conrm primary and secondary drains
are open.
1. These units are equipped with a drain pan, which includes green (main drain) and red (secondary drain) plugs. Unscrew the plugs to remove them before
inserting condensate drain ttings. See gure 12.
4. If the secondary drain line is to be used, remove the plug or the knockout and route the drain line so that water draining from the outlet will be easily noticed by the homeowner. Refer to local codes for drain trap requirements on the secondary drain line.
5. Check again to ensure drain ports and drain pan are free of all debris.
6. Plug and check any unused drain pan openings for tightness. Torque plugs to 30 in. lb. to prevent water leaks or seepage from the drain pan.
7. Install a 2” trap in the main (primary) drain lines as
close to the unit as practical (see gure 10). Make sure
the top of the trap is below the connection to the drain pan to allow complete drainage of the pan.
NOTE: Horizontal runs must have an anti-siphon air vent (standpipe) installed ahead of the horizontal run.
See gure 10. An extremely long horizontal run may
require an oversized drain line to eliminate air traps.
NOTE: Do not operate air handler without a trap in the main (primary) drain. The condensate drain is on the negative pressure side of the blower; therefore, air being pulled through the condensate line will not allow positive drainage without a proper trap.
8. Route the drain line to the outside or to an appropriate drain. Drain lines must be installed so they do not block service access to the front of the air handler. A 24”
clearance is required for lter, coil, or blower removal
and service access.
NOTE: Check local codes before connecting the drain
line to an existing drainage system.
UNSCREW PLUGS
AND CONNECT
PROPERLY SIZED
FIELD-PROVIDED
FITTINGS AND
DRAIN LINES.
DRAIN PAN
GREEN MAIN
DRAIN PLUG
Figure 12
2. After removal of drain pan plugs, check the drain port to see if holes have been drilled. If not drilled, use a 19/32” bit to drill out the primary drain hole; use a 3/8” drill bit for the secondary drain hole. Remove all drill shavings.
3. Install properly-sized, eld-provided connection ttings and connect primary drain line to the main drain pan connection.
507621-01 Issue 1720 Page 9 of 23
RED SECONDARY
DRAIN PLUG
9. Insulate the drain lines where sweating could cause water damage.
Test Condensate Drain
Test the drain pan and drain line after installation:
1. Pour several quarts of water into drain pan. Use
enough water to ll both the drain trap and the line.
2. Check the installed drain pan. Drain pan must be
draining completely. Drain line ttings must not be
leaking. Water must be draining from the end of the primary drain line.
3. Correct any leaks found.
Page 10
Duct System and Filters
Duct System
The air handler is provided with anges for the connection
of the plenum and ducts. The air handler is equipped with
anges that can form a lter rack for the installation of the air lter, or the lter may be installed as part of the return
air duct system.
Installing Duct System
Install the conditioned air plenum, ducts and air lters
(not provided) in accordance with NFPA 90B Standard for the Installation of Warm Air Heating and Air-Conditioning Systems (latest edition).
Connect supply air duct to the ange on top of the air
handler. If an isolation connector is used, it must be
nonammable.
Supply and return duct system must be adequately sized to meet the system’s air requirements and static pressure capabilities. The duct system should be insulated with a minimum of 1” thick insulation with a vapor barrier in conditioned areas or 2” minimum in unconditioned areas.
Supply plenum should be the same size as the anged
opening provided around the blower outlet and should extend at least 3 ft. from the air handler before turning or branching off plenum into duct runs. The plenum forms an extension of the blower housing and minimizes air expansion losses from the blower.
Filters
A lter is provided. Table 2 lists the lter size for each unit.
Model Filter Size
-018 12” x 20” x 1 11.50” x 19.50” x .75”
-024 and -030 15” x 20” x 1 14.50” x 19.50” x .75”
-036 18” x 20” x 1 17.50” x 19.50” x .75”
-042, -048 and -060 18” x 24” x 1 17.50” x 23.50” x .75”
Table 2. Filters
Actual Minimum
Filter Size
Field-Fabricated Return Air Duct Flange for Horizontal Applications
A return air duct system is recommended, but not factory-
provided. If the unit is installed in a conned space or
closet, run a full-size return connection to a location outside the closet.
CABINET DOOR FLANGE
1−1/2
(38)
DUCT FLANGE
3/4
(19)
1−1/2(38)
3/4
(19)
“A”
BRAKE DOWN 90 DEGREES
1/2
(13)
3/4
(19)
1/4 (6) DIA.
2−HOLES
BOTTOM OF CABINET
DUCT ADAPTER
3/4
(19)
1−1/2
(38)
IMPORTANT
If a high -efciency lter is being installed as part of this system to ensure better indoor air quality, the lter must be properly sized. High -efciency lters have a higher static pressure drop than standard- efciency glass/foam lters. If the pressure drop is too great,
system capacity and performance may be reduced. The pressure drop may also cause the limit to trip more frequently during the winter and the indoor coil to freeze in the summer, resulting in an increase in the number of service calls.
Before using any lter with this system, check the specications provided by the lter manufacturer
against the data given in the appropriate Allied Air
Product Specications bulletin.
UNIT SIZE
−018 14−7/8 (378)
−024 & −030 18−3/8 (467)
−036 to −060
“A”
21−3/4 (552)
Figure 13. Cabinet and Duct Flange
507621-01Issue 1720Page 10 of 23
Page 11
Brazing Refrigerant Lines
CAUTION
Refrigerant lines must be connected by a qualied
technician in accordance with established procedures.
IMPORTANT
Refrigerant lines must be clean, dehydrated, refrigerant-grade copper lines. Air handler coils should
be installed only with specied line sizes for approved
system combinations.
Handle the refrigerant lines gently during the installation process. Sharp bends or possible kinking in the lines will cause a restriction.
Do not remove the caps from the lines or system connection points until connections are ready to be completed.
WARNING
Polyolester (POE) oils used with HFC-410A refrigerant absorb moisture very quickly. It is very important that the refrigerant system be kept closed as much as possible. DO NOT remove line set caps or service valve stub caps until you are ready to make connections.
WARNING
Danger of re. Bleeding the refrigerant
charge from only the high side may result in the low side shell and suction tubing being pressurized. Application of a brazing torch while pressurized may result in ignition of the refrigerant and oil mixture - check the high and low pressures before unbrazing.
Brazing alloys and ux contain materials which are
hazardous to your health.
Avoid breathing vapors or fumes from brazing operations. Perform operations only in well ventilated areas.
Wear gloves and protective goggles or face shield to protect against burns.
Wash hands with soap and water after handling brazing
alloys and ux.
NOTE: Recommended line length is 50’ or less. If more than 50’ line set is required, contact Technical Services.
1. Route the suction and liquid lines from the ttings on
the indoor coil to the ttings on the outdoor unit. Run
the lines in a direct path, avoiding unnecessary turns and bends.
2. Make sure that the suction line is insulated over the entire exposed length and that neither suction nor
liquid lines are in direct contact with oors, walls, duct system, oor joists, or other piping.
3. Connect the suction and liquid lines to the evaporator coil. Take care to protect the cabinet and internal
components as detailed in gure 14.
4. To avoid damaging the rubber grommets in the cabinet while brazing, slide the rubber grommets over the refrigerant lines until they are away from the heat source.
NOTE: Place wet rags against piping plate and around suction line connections.
5. Braze using an alloy of silver or copper and phosphorus with a melting point above 1,100°F (593°C).
NOTE: Do not use soft solder.
WARNING
When using a high pressure gas, such as dry nitrogen, to pressurize a refrigeration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kPa).
IMPORTANT
To prevent the build-up of high levels of nitrogen when purging, be sure it is done in a well ventilated area. Purge low pressure nitrogen (1 to 2 psig) through the refrigerant piping during brazing. This will help to prevent oxidation and the introduction of moisture into a system.
507621-01 Issue 1720 Page 11 of 23
6. Allow refrigerant pipes to cool to room temperature.
NOTE: Make sure to route copper refrigerant tubing away from sharp edges and make sure that it does not touch other metal surfaces. This prevents damage caused by vibration or metal-on-metal contact.
7. Reinstall the rubber grommets into the refrigerant piping panel.
NOTE: Make sure expansion valve capillary tube is
not touching metal edges or copper tubing.
8. Make sure outdoor unit has been placed according to the Installation Instructions and is connected to the refrigerant lines.
Page 12
PLEASE READ IMPORTANT ISSUES CONCERNING BRAZING
p
OPERATIONS ON PREVIOUS PAGES BEFORE PROCEEDING.
NOTE - REFER TO OUTDOOR UNIT INSTALLATION INSTRUCTIONS FOR REFRIGERANT PIPING SIZE REQUIREMENTS.
NOTE - Use silver alloy brazing rods with five or six percent minimum silver alloy for copper-to-copper brazing, 45
ercent alloy for copper-to-brass and copper-to-steel
brazing.
PIPING PLATE
REMOVE ACCESS PANEL
A
REMOVE RUBBER PLUG FROM BOTH LIQUID
B
AND SUCTION LINES
NOTE - BCE3M*V SERIES UNITS USE NITROGEN OR DRY AIR AS A HOLDING CHARGE. IF THERE IS NO PRESSURE WHEN THE RUBBER PLUGS ARE REMOVED, CHECK THE COIL FOR LEAKS BEFORE INSTALLING.
EITHER REMOVE OR PUSH PIPE WRAPPING BACK
C
THROUGH HOLE IN PIPING PLATE BEFORE LINE SET CONNECTION AND BRAZING.
LOW
HIGH
CONNECT PIPES
D
NOTE - REFRIGERANT LINE SETS SHOULD BE ROUTED TO ALLOW FILTER ACCESSIBILITY.
PLACE A WET RAG AGAINST PIPING
F
PLATE AND AROUND THE SUCTION LINE CONNECTION. A
BRAZE CONNECTION. ALLOW PIPE TO
G
COOL BEFORE REMOVING WET RAG FROM CTXV SENSING BULB AND PIPING PANEL AREA.
REPEAT PREVIOUS PROCEDURE FOR
H
LIQUID LINE.
CONNECT GAUGES AND
E
START NITROGEN FLOW
FLOW REGULATED NITROGEN (AT 1 TO 2 PSIG) THROUGH THE REFRIGERATION GAUGE SET INTO THE VALV E STEM PORT CONNECTION ON THE OUTDOOR UNIT LIQUID LINE SERVICE VALVE AND OUT OF THE VALV E STEM PORT CONNECTION ON THE SUCTION SERVICE VALVE.
REFER TO INSTRUCTIONS PROVIDED WITH OUTDOOR UNIT FOR LEAK TESTING, EVACUATING AND CHARGING PROCEDURES
NITROGEN
Figure 14. Brazing
507621-01Issue 1720Page 12 of 23
Page 13
Sealing the Unit
WARNING
Seal the unit so that warm air is not allowed into the cabinet. Warm air introduces moisture, which results in water blow­off problems. This is especially important when the unit is installed in an unconditioned area.
If installed in an unconditioned space, sealant should be applied around the electrical wires, refrigerant tubing, and condensate lines where they enter the cabinet.
WARNING
There must be an airtight seal between the bottom of
the air handler and the return air plenum. Use berglass
sealing strips, caulking, or equivalent sealing method between the plenum and the air handler cabinet to ensure a tight seal. Return air must not be drawn from a room where this air handler or any gas-fueled appliance (ie., water heater), or carbon monoxide-
producing device (ie., wood replace) is installed.
IMPORTANT
Run 24V Class II wiring only through specied low
voltage opening. Run line voltage wiring only through
specied high voltage opening. Do not combine
voltage in one opening.
WARNING
ELECTRIC SHOCK HAZARD
Can cause injury or death.
Foil-faced insulation has conductive characteristics similar to metal. Be sure there are no electrical connections within a 1/2” of the insulation. If the foil­faced insulation comes in contact with electrical voltage, the foil could provide a path for current to pass through to the outer metal cabinet. While the current produced may not be enough to trip existing electrical safety devices (e .g. fuses or circuit breakers), the current can be enough to cause an electric shock hazard that could cause personal injury or death.
When sealing the cabinet, be sure to seal closed any space around the holes where the drain lines exit the cabinet using duct tape and/or Permagum. Warm air must not be allowed to enter through any gaps or holes in the cabinet.
IMPORTANT
Make sure the liquid line and suction line entry points
are sealed with either Armaex material or with
Permagum. Permagum may also be used to seal around the main and auxiliary drains and around open areas of electrical inlets.
Electrical Connections
WARNING
Electric shock hazard! - Disconnect all
power supplies before servicing.
Replace all parts and panels before operating.
Failure to do so can result in death or electrical shock.
WARNING
ELECTRIC SHOCK HAZARD
Can cause injury or death. Unit must be grounded in accordance with national and local codes.
Line voltage is present at all components when unit is not in operation on units with single-pole contactors. Disconnect all remote electric power supplies before opening access panel. Unit may have multiple power supplies.
Wiring must conform to the current National Electric Code ANSI/NFPA No. 70, or Canadian Electric Code Part I, CSA Standard C22.1, and local building codes. Refer to following wiring diagrams. See unit nameplate for minimum circuit ampacity and maximum over­current protection size.
Electrical wiring, disconnect means and over­current protection are to be supplied by the installer. Refer to the air handler rating plate for maximum over-current protection, minimum circuit ampacity, as well as operating voltage. Select the proper supply circuit conductors in accordance with tables 310-16 and 310-17 in the National Electric Code, ANSI/NFPA No. 70 or tables 1 through 4 in the Canadian Electric Code, Part I, CSA Standard C22.1.
507621-01 Issue 1720 Page 13 of 23
Page 14
The power supply must be sized and protected
according to the specications supplied on the product.
This air handler is factory-congured for 240 volt, single phase, 60 cycles. For 208-volt applications, see “208 Volt Conversion” later in this section.
Separate openings have been provided for 24V low voltage and line voltage. Refer to the dimension
illustration for specic location.
This unit is provided with holes for conduit. Use provided caps to seal holes not used.
Typical unit wiring (as well as wiring of optional eld-
installed electric heat) is given in gure 18. Refer to
the instructions provided with the electric heat section for proper installation.
For optional eld-installed electric heat applications, refer to the instructions provided with the accessory for proper installation.
WARNING
Figure 16
USE COPPER CONDUCTORS ONLY!
1. Disconnect all power supplies.
2. Remove the air handler access panel.
3. Route the eld supply wires to the air handler electrical connection box.
4. Use UL-listed wire nuts to connect the eld supply conductors to the unit black and yellow leads, and the ground wire to ground terminal marked GND.
5. Replace the air handler access panel.
208 Volt Conversion
1. Disconnect all power supplies.
2. Remove the air handler access panel.
3. Using the wiring diagram located on the unit access panel as a reference, move the 2 connected black transformer leads from the 240 volt terminal on the transformer to the 208 volt terminal on the transformer.
WARNING
Electrically ground air handler. Connect ground wire to ground terminal marked “GND”.
Failure to do so can result in death or electrical shock.
208 / 240 VOLT TRANSFORMER
PRIMARY SECONDARY
Figure 15
NOTE: To avoid the possibility of moisture damage to the
control in some right-hand discharge congurations, the
control panel can be relocated to the end panel as shown
in gure 16.
240 Volts
208 Volts
Figure 17
507621-01Issue 1720Page 14 of 23
Page 15
220
208/240
VOLTAGE
BY OTHERS
PART NO. 067203400
CIRCUIT BREAKER 2
L1B
L2B
L1A
L2A
14 YEL
14 BLK
TO BLOWER
GROUND LUG
2
1
1
GND.
CIRCUIT BREAKER 1
GND
WIRING DIAGRAM - ELECTRIC HEAT
SEQUENCER 2
12 BLK
12 BLK
12 BLK
12 BLK
14 RED
14 GRN
14 RED
3
3
1
18 BLU
18 BLU
SEQUENCER 1
5
3
1
12 YEL 12 YEL
18 BLU
4
4
2
6
4
2
12 YEL
12 YEL
18 WHT
5
18 BLK
12 BLK
12 BLK
***SEQ4
12
3
18 BLU
12 BLK
12 BLK
18 WHT
6
65432
4
***SEQ3 1
3
LS3
LS1
LS2
LS4
2
4
6-PIN
PLUG
2nd STAGE
12 YEL
12 YEL
18 BLK
1st STAGE
1st STAGE
HE2
HEATERS USED 5 KW = HE1
7.5 & 10 KW = HE1 & HE2
HE3
HE4
HE1
15 KW = HE1,HE2 & HE3
20 KW = HE1,HE2,HE3 & HE4
TB = TERMINAL BLOCK
CB = CIRCUIT BREAKER SEQ = SEQUENCER GND = GROUND LUG LS = LIMIT SWITCH HE = HEAT ER ELEMENT
POWER (FACTORY WIRED) POWER (FIELD WIRED) CONTROL (FACTORY WIRED) CONTROL (FIELD WIRED)
18 BLK
CONTROL CIRCUIT WIRING TO
BE 24 VOLT, N.E.C. CLASS 2
PLUG PIN
LOCATION
2
2
3
3
6514
4156
(OPT.)
(OPT.)
THREE POLE SEQUENCER
TIMING - SEC
ON
OFF
1-20
40-110
20-60
1-30
20-60
1-30
TWO POLE SEQUENCER
TIMING - SEC ON
OFF
30-90
1-30
30-90
1-30
14 BLK L1
14 YEL L2
TRANSFORMER
COM
208V
240V
120V
OR
220V
# FACTORY SPEED SET TO MEDIUM (BLUE) FOR -018, -024, -030, -036,
-042, AND -060. FACTORY SPEED SET TO LOW (RED) FOR -048
24
18 BLU
14 BLK
18 RED
18 BLU
24V
C
3
1
TIME DELAY
18 BLU
14 RED
18 GRN
BLOWER REALY
3
6
4
1
5
2
18 WHT
18 BLU
18 GRN
5
18 RED
2
#
14 BLUE (MED)
14 RED(LO) 14 BLK(HI)
14 YEL(COM)
WARNING
USE COPPER CONDUCTORS
18 BLK
4
3
2
1
ONLY
BLUE
RED BLK
YEL
+
W2
W1
**
BLK
WHT
C
BLU
GRN
RED
GND
BRN/WHT
BRN
TO
THERMOSTAT
CAP
G
R
MTR
TD = TIME DELAY (OPT.)
TR = TRANSFORMER BR = BLOWER RELAY
MTR = BLOWER MOTOR
CAP = MOTOR CAPACITOR GND = GROUND CONNECTION
*** SEQUENCER USED: WIRED AS SHOWN
BY OTHERS
RELAY USED: WIRED PER RELAY POLE TO BREAK CIRCUIT NO DEVICE PRIOR TO 10-15-2014
WIRING DIAGRAM: NO HEAT
WIRE NUTS
BY OTHERS
14 BLK
1
6-PIN
PLUG
14 YEL(240V)
14 WHT(120V)
2
TO
GROUND LUG
14 GRN
L1
L2 OR
NEUT.
15 AMP
SUPPLY
VOLTAGE
507621-01 Issue 1720 Page 15 of 23
Figure 18. Typical Wiring Diagram
Page 16
SEE
NOTE
AIR HANDLERTHERMOSTAT
R
G
BU
Y
AIR
CONDITIONER
UNIT
COOLINGONLY APPLICATION
SEE
NOTE
THERMOSTAT
AIR HANDLERTHERMOSTAT
R
G
BU
W
HEATONLY APPLICATION
AIR HANDLER
R
HEAT PUMP
UNIT
AIR HANDLERTHERMOSTAT
G
R
SEE
NOTE
G
W
BK
BU
Y
AIR CONDITIONER
UNIT
COOLING APPLICATION WITH
ELECTRIC HEAT
CONNECT COMMON
WIRE ONLY IF
REQUIRED
(REFER TO THE
APPROPRIATE
THERMOSTAT
INSTALLATION
INSTRUCTIONS)
HEAT PUMP APPLICAT ION WITH
ELECTRIC HEAT
BU
BK
W
NOTE - Connect common wire only if required (Refer to the appropriate thermostat installation instructions).
Figure 19. Low Voltage Connections
507621-01Issue 1720Page 16 of 23
Page 17
Air Flow — Cooling Blower Speed
p
The cooling blower speed is factory congured to provide correct air ow for an outdoor unit that matches the cooling
capacity rating of the air handler.
If the outdoor unit is smaller than the maximum cooling capacity rating for the air handler, the cooling blower speed may need to be changed. Refer to blower performance chart (table 3).
WARNING
ELECTRIC SHOCK HAZARD!
Disconnect all power supplies before servicing.
Replace all parts and panels before operating.
Failure to do so can result in death or electrical shock.
Change Blower Speed
1. Disconnect all power supplies.
2. Remove the air handler access panel.
3. Locate pin number 2 on the blower relay. Two black wires are connected to this terminal pin. One connects to pin number 5 on the blower relay, one connects to an in-line splice connecting to a blue wire.
4. Select the required blower motor speed connect red­LO or black-HI and plug it into the 4-pin blower relay harness connector.
NOTE: Reuse the factory-installed wire nut on the unused wires.
5. Replace all panels.
6. Reconnect power.
BLOWER RELAY
NOTE - Refer to wiring diagram located on the unit access panel, this figure, and blower
erformance (table 2).
All air data measured external to unit with 1 inch non-pleated air filter in place.
All factory settings are medium speed except the -48 which is set to low speed from the factory.
All data given while air handler is operating with a dry DX coil.
3 6
4
GND
BRN / WHT
BRN
Figure 20
MTR
5
BLOWER RELAY HARNESS
BLUE (MED)
PLASTIC CAPS
RED (L0)
2
BLACK (HI)
BLUE
4
RED
3
BLK
2
YEL+
1
4-PIN
BLOWER CONNECTOR
YELLOW (COM)
507621-01 Issue 1720 Page 17 of 23
Page 18
Air Handler
Model
-018
-024
-030
-036
-042
-048
-060
Blower Speed .10” WC .20” WC .30” WC .40” WC .50” WC
Low (Red) 510 495 475 420 325
Med (Blue) 670 650 630 595 505
High (Black) 905 865 820 770 705
Low (Red) 630 625 615 610 580
Med (Blue) 885 875 850 820 780
High (Black) 1130 1100 1070 1010 950
Low (Red) 900 865 830 780 740
Med (Blue) 1075 1060 1030 985 940
High (Black) 1240 1210 1170 1135 1085
Low (Red) 1075 1040 1000 950 900
Med (Blue) 1300 1250 1205 1145 1085
High (Black) 1510 1450 1390 1320 1245
Low (Red) 1325 1315 1300 1275 1225
Med (Blue) 1490 1465 1440 1395 1315
High (Black) 1820 1770 1690 1600 1500
Low (Red) 1775 1710 1645 1565 1470
Med (Blue) 1995 1895 1800 1685 1560
High (Black) 2070 1970 1850 1719 1595
Low (Red) 1675 1630 1580 1520 1450
Med (Blue) 1965 1925 1875 1800 1695
High (Black) 2140 2085 2000 1895 1795
Blower Performance (CFM vs. ESP inches H2O)
Cooling speeds should not be reduced below factory setting.
Units with electric heat approved at 0.5” maximum and medium blower speed minimum.
Downow units should be set to high speed minimum.
Different speeds can be set for heating mode.
Table 3. Blower Performance
507621-01Issue 1720Page 18 of 23
Page 19
Check-Out Procedures
NOTE: Refer to outdoor unit installation instructions for
system start-up instructions and refrigerant charging instructions.
Pre-Start-Up Checks
Is the air handler properly and securely installed?
If horizontally congured, is the unit sloped up to 5/8 inch toward drain lines?
Will the unit be accessible for servicing?
Has an auxiliary pan been provided under the unit
with separate drain for units installed above a nished ceiling or in any installation where condensate overow
could cause damage?
Have ALL unused drain pan ports been properly plugged?
Has the condensate line been properly sized, run, trapped, pitched, and tested?
Is the duct system correctly sized, run, sealed, and insulated?
Have all cabinet openings and wiring been sealed?
Is the indoor coil metering device properly sized for the outdoor unit being used?
Have all unused parts and packaging been disposed of properly?
Is the lter clean, in place, and of adequate size?
Is the wiring neat, correct, and in accordance with the wiring diagram?
Is the unit properly grounded and protected (fused)?
Is the thermostat correctly wired and in a good location?
Are all access panels in place and secure?
Check Blower Operation
Set thermostat to FAN ON.
The indoor blower should come on.
Check Cooling Operation
Set thermostat to force a call for cooling (approximately 5ºF lower than the indoor ambient temperature).
The outdoor and indoor units should come on immediately.
Check the air ow from a register to conrm that the system is moving cooled air.
Set the thermostat 5ºF higher than the indoor temperature. The indoor blower and outdoor unit should cycle off. Air handler should cycle off 45 seconds after the outdoor unit shuts off.
Check Electric Heater (if used)
Set thermostat to call for auxiliary heat (approximately 5°F above ambient temperature). The indoor blower and auxiliary heat should come on together. Allow a minimum of 3 minutes for all sequencers to cycle on.
Set the thermostat so that it does not call for heat. Allow up to 5 minutes for all sequencers to cycle off.
Operation
Time Delay Relay
Blower time delay operation:
1. When cooling demand is initiated, there is a 1 second motor-on delay.
2. After the motor-on delay expires, motor ramps up to 100% and runs at 100% until cooling demand is
satised.
3. Once demand is met, motor runs at 100% for 45 seconds.
4. Motor ramps down to stop.
34
100%
1
1
SECOND
DELAY
2
CFM
COOLING
DEMAND
Figure 21
Cooling (Cooling Only or Heat Pump)
When the thermostat calls for cooling, 24 volts is put on the blower time-delay relay coil and then the indoor blower relay energizes. The normally open contacts close, causing the indoor blower motor to operate. The circuit between R and Y is completed, closing the circuit to the contactor in the outdoor unit, starting the compressor and outdoor fan motor.
On heat pumps, circuit R and O energizes the reversing valve, switching the valve to the cooling position. (The reversing valve remains energized as long as the thermostat selector switch is in the COOL position.)
At the completion of the cooling demand, the indoor blower and outdoor unit should cycle off. Air handler should cycle off 45 seconds after the outdoor unit shuts off.
Heating (Electric Heat Only)
When the thermostat calls for heat, the circuit between R and W is completed, and the heat sequencer is energized. A time delay follows before the heating elements and the indoor blower motor come on. Units with a second heat sequencer can be connected with the rst sequencer to W on the thermostat sub-base, or they may also be connected to a second stage on the sub-base.
100%
CFM
45
SECS
OFF
507621-01 Issue 1720 Page 19 of 23
Page 20
Heating (Heat Pump)
When the thermostat calls for heating, 24 volts is applied to the blower time-delay relay coil. The normally open contacts close, causing the indoor blower motor to operate. The circuit between R and Y is completed, closing the circuit to the contactor in the outdoor unit, starting the compressor and outdoor fan motor.
If the room temperature continues to decrease, the circuit between R and W1 is completed by the second-stage heat room thermostat. Circuit R-W1 energizes a heat sequencer. The completed circuit will energize supplemental electric heat (if applicable). Units with a second heat sequencer can be connected with the rst sequencer to W1 on the thermostat. They may also be connected to a second heating stage W2 on the thermostat sub-base.
Emergency Heat (Heating Heat Pump)
If the selector switch on the thermostat is set to the emergency heat position, the heat pump will be locked out of the heating circuit, and all heating will be electric heat (if applicable). A jumper should be placed between W2 and E on the thermostat sub-base so that the electric heat control
will transfer to the rst-stage heat on the thermostat. This
will allow the indoor blower to cycle on and off with the electric heat when the fan switch is in the AUTO position.
Maintenance
IMPORTANT
Do not operate system without a lter. A lter is
required to protect the coil, blower, and internal parts
from excessive dirt and dust. The lter is placed in the
return duct by the installer.
Cabinet Insulation
IMPORTANT
DAMAGED INSULATION MUST BE REPAIRED OR REPLACED before the unit is put back into
operation. Insulation loses its insulating value when wet, damaged, separated or torn.
Matte- or foil-faced insulation is installed in indoor equipment to provide a barrier between outside air conditions (surrounding ambient temperature and humidity) and the varying conditions inside the unit. If the insulation barrier is damaged (wet, ripped, torn or separated from the cabinet walls), the surrounding ambient air will affect the inside surface temperature of the cabinet. The temperature/ humidity difference between the inside and outside of the cabinet can cause condensation on the inside or outside of the cabinet, which leads to sheet metal corrosion and subsequently, component failure.
Repairing Damaged Insulation
Areas of condensation on the cabinet surface are an indication that the insulation is in need of repair.
If the insulation in need of repair is otherwise in good condition, the insulation should be cut in an X pattern, peeled open, glued with an appropriate all-purpose glue and placed back against the cabinet surface, being careful to not overly compress the insulation so the insulation can retain its original thickness. If such repair is not possible, replace the insulation. If using foil-faced insulation, any cut, tear, or separations in the insulation surface must be taped with a similar foil-faced tape.
Inspect air lters at least once a month and replace or
clean as required. Dirty lters are the most common
cause of inadequate heating or cooling performance.
Replace disposable lters. Cleanable lters can be cleaned by soaking in mild detergent and rinsing with cold water.
Install new/clean lters with the arrows on the side
pointing in the direction of air ow. Do not replace a cleanable (high velocity) lter with a disposable (low velocity) lter unless return air system is properly
sized for it.
If water is seen dripping from the secondary drain line,
contact a qualied service technician. This is a sign
of a problem that must be investigated and corrected.
GLUE - Make sure there is full coverage of glue on the metal or insulation so there are no areas where air pockets may form, which can lead to sweating.
1. Cut insulation in X pattern
2. Apply glue
3. Press glued tabs against cabinet
Figure 22. Repairing Insulation
507621-01Issue 1720Page 20 of 23
Page 21
Use of Air Handler During Construction
Allied Air does not recommend the use of its air handler unit during any phase of construction. Very low return air temperatures, harmful vapors and operation of the unit
with clogged or misplaced lters will damage the unit.
Air handler units may be used for heating (heat pumps) or cooling of buildings under construction, if the following conditions are met:
A room thermostat must control the air handler. The
use of xed jumpers is not allowed.
Air lter must be installed in the system and must be maintained during construction.
Air lter must be replaced upon construction completion.
The air handler evaporator coil, supply fan assembly and duct system must be thoroughly cleaned following
nal construction clean-up.
All air handler operating conditions must be veried according to these installation instructions.
507621-01 Issue 1720 Page 21 of 23
Page 22
Installing Contractor’s Name_______________________
Installing Contractor’s Phone_______________________ Job Address____________________________________
8
Temperature
1
Duct
System
5
Duct Static
Installing Date_______________________________
Air Handler Model #___________________________
Thermostat
SUPPLY
AIR
9
Disconnect
Switch
2
Line Voltage
3
Integrated Control
Blower Motor Amps
6
Electric Heat Amps
7
RETURN
AIR
DUCT SYSTEM
1
SUPPLY AIR DUCT
Sealed
Insulated (if necessary)
Registers Open and Unobstructed
RETURN AIR DUCT
Sealed
Filter Installed and Clean
Registers Open and Unobstructed
2
INTEGRATED CONTROL
Jumpers Configured Correctly (if applicable)
Appropriate Links in Place (if applicable)
3
VOLTAGE CHECK
Supply Voltage ___________
Low Voltage _____________
Electrial Connections Tight
4
DRAIN LINE
Leak Free
Filter
TOTAL EXTERNAL STATIC (dry coil)
5
Supply External Static ______ ______
Return External Static ______ ______
Total External Static = ______ ______
6
ELECTRIC HEAT AMPS____________
7
INDOOR BLOWER AMPS___________
INDOOR BLOWER CFM____________
TEMPERATURE DROP (Cooling Mode)
8
Return Duct Temperature ___________
Supply Duct Temperature − ___________
8
TEMPERATURE RISE (Heating Mode)
Return Duct Temperature __________
Supply Duct Temperature − __________
9
THERMOSTAT
Adjusted and Programmed
Operation Explained to Owner
4
Drain Line
dry coil wet coil
Temperature Drop = ___________
Temperature Rise = __________
Explained Operation of System to Homeowner
Technician’s Name:_______________________Date Start−Up & Performance Check Completed__________
Figure 23. Start-Up and Performance Checklist (Up-ow Conguration)
507621-01Issue 1720Page 22 of 23
Page 23
Installing Contractor’s Name_______________________ Installing Contractor’s Phone_______________________
Job Address____________________________________
Thermostat
9
1
Duct System
2
Integrated
Control
Filter
Installing Date_______________________________ Air Handler Model #___________________________
Disconnect
Switch
Line Voltage
3
1
Duct System
RETURN
AIR
4
Drain Line
DUCT SYSTEM
1
SUPPLY AIR DUCT
Sealed
Insulated (if necessary)
Registers Open and Unobstructed
RETURN AIR DUCT
Sealed
Filter Installed and Clean
Registers Open and Unobstructed
2
INTEGRATED CONTROL
Jumpers Configured Correctly (if applicable)
Appropriate Links in Place (if applicable)
3
VOLTAGE CHECK
Supply Voltage ___________
Low Voltage _____________
Electrial Connections Tight
4
DRAIN LINE
Leak Free
5
Duct Static
8
Temperature
SUPPLY
AIR
Electric Heat Amps
6
Blower motor Amps
7
TOTAL EXTERNAL STATIC (dry coil)
5
dry coil wet coil
Supply External Static ______ ______
Return External Static ______ ______
Total External Static = ______ ______
6
ELECTRIC HEAT AMPS____________
7
INDOOR BLOWER AMPS___________
INDOOR BLOWER CFM____________
TEMPERATURE DROP (Cooling Mode)
8
Return Duct Temperature ___________
Supply Duct Temperature − ___________
Temperature Drop = ___________
8
TEMPERATURE RISE (Heating Mode)
Return Duct Temperature __________
Supply Duct Temperature − __________
Temperature Rise = __________
9
THERMOSTAT
Adjusted and Programmed
Operation Explained to Owner
Explained Operation of System to Homeowner
Technician’s Name:_______________________Date Start−Up & Performance Check Completed__________
Figure 24. Start-Up and Performance Checklist (Horizontal Conguration)
507621-01 Issue 1720 Page 23 of 23
Loading...