IOM / ROOFTOP BALTIC Series - 0803 - E Page 69
control interfaces ds50 menu tree
Main Screen Code Description Code Description Code Description Code UNIT Min Factory Max
4-Ventilation 3410 1-Air Flow 3411 Pa 0 25 1000
2-No Filter 3412 Pa 0 50 1000
3-Dirty Fil 3413 Pa 0 250 1000
5-Fresh Air 3510 1-Out.Limit 3511 °C -20 0 40
2-Maximum 3512 % 0 100 100
3-Start Ext 3513 % 0 30 100
4-Mini.Co2 3514
ppm 0 1000 2000
5-Maxi.Co2 3515 ppm 0 1500 2000
6-Compressor 3600 1-Out.Limit 3610 1-Cool. 50 3611
°C -10 or 10 20 40
2-Cool.100 3612
°C -10 or 10 12 40
3-Heat.100 3613
°C -50 -20 40
2-Defrost 3620 1-Type 3621 List 0 0 1
2-Outside 3622 °C 8 10 20
3-Coil 3623 °C -10 -2 10
4-Time Limit 3624 m30 45 90
5-Time Fc 3625 ~1 3 5
3-Safety 3630 1-W/Cd Mini 3631 °C 4 5 20
2-W/Cd Maxi 3632 °C 20 45 46
description
*[Safety Limit] Airflow Detection Threshold of pressure
difference in Pa indicating Low Airflow Rate. If the pressure
difference across the filter is lower than this threshold the
safety is activated.
*[Safety Limit] Missing Filters. Threshold of pressure
difference in Pa indicating absence of filters. If the pressure
difference across the filter is lower than this threshold the
safety is activated.
*[Safety Limit] Dirty Filters. Threshold of pressure difference
in Pa indicating Filters are Dirty. If the pressure difference
across the filter is Higher than this threshold the safety is
activated.
*[Fresh air Damper] mimimum outdoor temperature limit in
°C. If the outdoor temperature is lower than this limit the
control in free cooling is not allowed. The fresh air damper is
then set to the minimum setting.
*[fresh air Damper] Maximum allowable opening of the fresh
air damper in %
*[Extraction] Threshold of activation of the power exhaust fan
according to the position of the economiser damper in %.
*[CO2] Fresh air damper minimum opening threshold in ppm
*[CO2] Fresh air damper maximum opening limit in ppm
*[ Limit of Regulation ] * 1° If Option Regulation all seasons -
Reduction speed of the fans condenser - Threshold of outside
temperature (in °c). - If the outside temperature is lower than
this threshold the fans condenser function in low speed * 2° If
not - Unloading 50% of the Compressors in Cooling -
Threshold of outside temperature (in °c). - If the outside
temperature is lower than this threshold 50% of the
compressors are used by the Regulation
*[ Limit of Regulation ] * 1° If Option Regulation all seasons -
Stopping of the fans condenser - Threshold of outside
temperature (in °c). - If the outside temperature is lower than
this threshold the fans condenser are stopped * 2° If not -
Unloading 100% of the Compressors in Cold - Threshold of
outside temperature (in °c). - If the outside temperature is
lower than this threshold the compressors are not used by the
Regulation
*[ Limit of Regulation ] Unloading 100% of the Compressors
in Heating - Threshold of outside temperature (in °c). - If the
outside temperature is lower than this threshold the
compressors are not used by the Regulation
*[ Function Defrost ] Choice of defrost: 1 = "cycling" or 0 =
"dynamic"
*[ Function Defrost ] Authorization of defrost - Threshold of
outside temperature (in °c)
*[ Function Defrost ] Authorization of defrost - Threshold of
coil temperature (in °c)
*[ Function Defrost ] Time limit for icing (in minute) -For the
dynamic defrost the unit will run this minimum amount of
time. If cycling defrost this is the time delay to start the
defrost once the temperature conditions are met.
*[ Function Defrost ] Number of condenser fan start-ups to
end defrost. If the number of start-ups can not be acheived
within 4min the defrost will end.
*[Safety limit] Low Temperature Limit for water heat
exchanger output (in °c) - Threshold of activation of the
safety limit.
*[safety limit] High Temperature Limit for water heat
exchanger output (in °c) - Threshold of activation of the
safety limit.