Lennox B050A3B, B075A4B, B075A3B, B100A5B, B125A5B Installation/servicing Instructions And Users Information Manual

...
AFFIX LABEL HERE
INSTALLATION / SERVICING INSTRUCTIONS
AND USER’S INFORMATION MANUAL
HORIZONTAL GAS-FIRED NON-CONDENSING FURNACE
Save these instructions for future reference.
WARNING
Improper installation, adjustment, alteration, service, or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information, consult a qualified installer, service agency, or the gas supplier.
WARNING
Do not store combustible materials, including gasoline and other flammable vapors and liquids, near the furnace, vent pipe, or warm air ducts. The homeowner should be cautioned that the furnace area must not be used as a broom closet or for any other storage purposes. Such uses may result in actions that could cause property damage, personal injury, or death.
WARNING
This furnace is not approved for installation in a mobile home. Do not install this furnace in a mobile home. Installation in a mobile home could result in actions that could cause property damage, personal injury, or death.
TABLE OF CONTENTS
SECTION 1: INSTALLATION AND
SERVICING INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . 1 - 28
Important Safety Information . . . . . . . . . . . . . . . . . . 2
Specification and Installation . . . . . . .. . . . . . . . . . . 3
Start-up and Operation . . . . . . . . . . . . . . . . . . . . . . 17
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Sequence of Operation & Diagnostics . . . . . . . . . . . 23
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
SECTION 2: USER’S INFORMATION MANUAL . . . . . . . . 29 - 36
Important Safety Information . . . . . . . . . . . . . . . . . 30
Operating Your Furnace . . . . . . . . . . . . .. . . . . . . . .30
Maintenance of Your Furnace . . . . .. . . . . . . . . . . . .32
Repair Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
Owner Record . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Manufactured By
Allied Air Enterprises Inc.
A Lennox International Inc. Company
215 Metropolitan Drive
West Columbia, SC 29170
*P506307-01*
(P) 506307-01
IMPORTANT
The installation of the furnace, wiring, warm air ducts, venting, etc. must conform to the requirements of the National Fire Protection Association; the National Fuel Gas Code, ANSI Z223.1/NFPA No. 54 (latest edition) and the National Electrical Code, ANSI/NFPA No. 70 (latest edition) in the United States; CSA B149.1 (latest edition) Natural Gas and Propane Installation Codes and the Canadian Electrical Code Part 1, CSA 22.1 (latest edition) in Canada; and any state or provincial laws, local ordinances (including plumbing or wastewater codes), or local gas utility requirements. Local authorities having jurisdiction should be consulted before installation is made. Such applicable regulations or requirements take precedence over the general instructions in this manual.
506307-01 Page 1 of 36Issue 1207
IMPORTANT SAFETY INFORMATION
The following is a list of safety rules and precautions that must be followed when installing this furnace.
1. Use only with the type of gas approved for this furnace. Refer to the furnace rating plate.
2. Install this furnace only in a location and position as specified in the Location section on page 7 of these instructions.
3. Provide adequate combustion and ventilation air to the furnace space as specified in the Air for Combustion and Ventilation section beginning on page 8 of these instructions.
4. Combustion products must be discharged outdoors. Connect this furnace to an approved vent system only, as specified in Venting beginning on page 10 of these instructions.
5. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections, as specified in Gas Connection Section beginning on page 14 of these instructions.
6. Always install furnace to operate within the furnace’s intended temperature-rise range with a duct system
which has an external static pressure within the allowable range, as specified in Temperature Rise on page 3 of these instructions. See furnace rating plate.
7. When a furnace is installed so that the supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by duct(s) sealed to the furnace casing and terminating outside the space containing the furnace. See Ducting beginning on page 9 of these instructions.
8. A gas-fired furnace for installation in a residential garage must be installed as specified in the Location section on page 7 of these instructions.
9. The furnace is permitted to be used for temporary heating of buildings or structures under construction as specified in the Location section on page 7 of these instructions.
In the State of Massachusetts:
This product must be installed by a licensed Plumber or Gas Fitter. When flexible connectors are used, the maximum length shall not exceed 36". When lever-type gas shutoffs are used, they shall be T­handle type.
Page 2 of 36 506307-01Issue 1207
506307-01 Page 3 of 36Issue 1207
FURNACE BLOWER SPECIFICATIONS AND AIR FLOW DATA
NOTES:
1. Air flow values in cubic feet per minute (CFM), rounded to nearest five (5) CFM.
2. Data taken without filters in place or A/C evaporator in place.
WARNING
When operating the furnace in the heating mode, the static pressure and the temperature rise (supply air temperature minus return air temperature) must be within those limits specified on the rating label. Failure to follow this warning could lead to severe furnace damage.
WARNING
Turn OFF all gas and electrical power to furnace before performing any maintenance or service on unit. (Unless specific test requires gas and electrical supplies.) Failure to take this precaution may result in personal injury due to electrical shock or uncontrolled gas leakage.
Page 4 of 36 506307-01Issue 1207
FURNACE WIRING SPECIFICATIONS
506307-01 Page 5 of 36Issue 1207
WARNING
The furnace cabinet must have an uninterrupted or unbroken electrical ground to minimize personal injury if an electrical fault should occur. The unit must also be electrically grounded in accordance with local codes, or in the absence of local codes, with the latest edition of the (U.S.) Canadian Electrical Code, if an external electrical source is utilized. DO NOT use gas piping as an electrical ground.
National Electrical Code ANSI/NFPA No. 70 or CSA Standard C22.1: Part 1
INTRODUCTION
This furnace is design certified by CSA International as a Category I furnace using air from inside the structure for combustion. The combustion system is fan-assisted which means it is equipped with an integral mechanical means to draw products of combustion through the heat exchanger.
It is shipped as a packaged unit, complete with burners and controls, and requires a line voltage (115V) connection to the junction box, a thermostat hook-up as per the wiring diagram and a gas line connection, ducting and flue piping. This furnace
can be installed in either horizontal right or horizontal left airflow positions. The design of this furnace is NOT CSA Certified for installation in recreation vehicles, in manufactured (mobil) homes, outdoors or as a construction heater.
This furnace has been designed to interface with split system cooling equipment (approved by a nationally recognized testing laboratory) so as to provide “year round air conditioning”. The blower has been sized for both heating and cooling and the furnace controls include a cooling fan relay.
The furnace installation must conform with local building codes or in the absence of local codes, with the latest edition of the (U.S.) National Fuel Gas Code ANSI Z223.1 (NFPA-54) or Canadian Natural Gas and Propane Installation Codes CSA B149.1.
For complete information on installation standards consult the (U.S.) National Fuel Gas Code, obtainable from the National Fire Protection Association, Inc., Batterymarch Park, Quincy, MA 02269 or the American Gas Association, 1515 Wilson Boulevard, Arlington, VA 22209 or the Canadian installation codes obtainable from Canadian Standards Association, 178 Rexdale Boulevard, Etobicoke, Ontario, Canada M9W 1R3.
This furnace is designed from minimum continuous return-air temperature of 60°F dB or intermittent operation down to 55°F dB such as when used with a night setback thermostat. Return-air must not exceed a maximum continuous temperature of 85°F dB.
The furnace may be used for heating of buildings or structures under construction, if the following conditions are met:
The vent system must be permanently installed per these instructions.
A room thermostat must control the furnace. The use of fixed jumpers that will provide continuous heating is not allowed.
The return air duct must be provided and sealed to the furnace.
Return air temperature range between 60°F and 80°F must be maintained.
Air filters must be installed in the system and must be maintained during construction.
Air filters must be replaced upon construction completion.
The input rate and temperature rise must be set per the furnace rating plate.
One hundred percent (100%) outdoor air must be provided for combustion air requirements during construction. Temporary
ducting may supply outdoor air to the furnace. Do not connect combustion air duct directly to the furnace. Size the
temporary duct following these instructions in the section “Air for Combustion & Ventilation” for air in a confinced space
with air from outside.
The furnace heat exchanger, components, duct system, air filters and evaporator coils must be thoroughly cleaned
following final construction clean-up.
All furnace operating conditions (including ignition, input rate, temperature rise and venting) must be verified according to
these installation instructions.
These instructions are written for individual residential installation only. For multi-unit installation, please contact manufacturer for recommendations.
Page 6 of 36 506307-01Issue 1207
LOCATION / PLACEMENT
Site Selection: This furnace may be located in an attic, closet, basement, crawl space, alcove or suspended from the ceiling
of a utility room or basement. Select a location that will meet all requirements for safety, clearances, ventilation and combustion air, ductwork design, gas piping, electrical wiring and venting.
Clearances: The following minimum clearances, or greater, must be provided between the furnace and adjacent
construction.
If the furnace is to be installed in a crawl space, consult
WARNING
Failure to comply with all of the clearances will create a fire hazard.
The furnace should also be located as near to the center of the air distribution system as possible, and should be installed level.
This furnace may be installed on mon-combustible flooring or on wood flooring, however, it must not be installed directly on carpeting, tile or any other combustible material.
Line contact is only permissible bewteen lines formed by the intersection of the furnace top, the front and back sides, and building joists, studs or framing (See Figure 1).
HORIZONTAL LINE CONTACT
local codes. (Use of a concrete pad 1” to 2” thick is recommended.)
If the furnace is to be suspended from the ceiling, it will be necessary to use steel pipe straps around each end of the furnace. These straps should be attached to the furnace with sheet metal screws and to the rafters with bolts. The furnace may also be suspended by using an angle iron frame bolted to the rafters. (See Table on page 3 for size and weight of furnace.) Care must be taken to allow for service access.
If a furnace is to be installed in a residential garage, it must be installed so the burners and the ignition source are located not less than 18” above the floor and the furnace must be located or protected to avoid physical damage by vehicles.
Figure 1
Furnace must not lean back. It must be level or tilt
up to 2° to the front. (See Figure 1.)
A clearance of at lease 30” should be provided at the front of the unit for servicing. For attic installations, the passageway and servicing area adjacent to the furnace should be floored.
506307-01 Page 7 of 36Issue 1207
WARNING
Do not place combustible material on the furnace jacket. Failure to comply with this warning will create a fire hazard.
WARNING
This furnace is not watertight and is not designed for outdoor installation. This furnace shall be installed in such a manner as to protect the electrical components from water. Outdoor installation would lead to a hazrdous electrical condition and to premature furnace failure.
AIR FOR COMBUSTION AND VENTILATION
Contaminated Combustion Air and Fuels:
Allowing exposure to substances containing chlorine or
fluoride could harm the furnace and void warranty. Substances to avoid include, but are not limited to:
Permanent wave solutions
Chlorinated waxes and cleaners
Chlorine based swimming pool chemicals
Water softening chemicals
De-icing salts or chemicals
Carbon tetrachloride
Halogen type refrigerants
Cleaning solvents (such as perchloroethylene)
Printing inks, paint removers, varnishes, etc.
Hydrochloric acid
Cements and glues
Antistatic fabiric softeners for clothes dryers
Masonry acid washing materials
Unrefined Gases
WARNING
Contaminated combustion air may cause premature failure of the heat exchanger that may lead to a hazardous condition and/or bodily harm, or loss of life.
For purposes of this instruction the following definitions
apply:
Confined Space: A space whose volume is less than
50 cubic feet per 1000 Btu/hr of the aggregate input rating of all appliances installed in that space.
Unconfined Space: A space whose volume is not less
than 50 cubic feet per 1000 Btu/hr of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the applicances are installed, through openings not furnished with doors, are considered a part of the unconfined space.
If the installation area meets the definition of “Unconfined Space” and does not have additional air requirements as described, the furnace may be installed without making special provisions for combustion and ventilation air.
CAUTION
Whenever this furnace is installed in an area along with one or more gas appliances, the total Btu/hr input of all appliances must be included when determining the free area requirements for combustion and ventilation air openings.
Adequate Ventilation and Combustion Air:
This section is provided to give guidelines for the introduction of air for ventilation and combustion air. The total quantity of air provided to the installation area must equal the requirements of all gas appliances in the area.
Adequate facilities for providing air for combustion and ventilation must be provided in accordance with the latest edition of the National Fuel Gas Code ANSI Z223.1/NFPA54 or CSA B149.1 Natural Gas and Propane Installation Codes, or applicable provisions of the local building codes.
The furnace shall be installed in a location in which the facilities for ventilation permits satisfactory combustion of gas, proper venting and maintenance of ambient temperature at safe limits under normal conditions of use. The furnace shall be located so as not to interfere with proper circulation of air.
In addition to air needed for combustion, ventilation in the form of process air must be provided as required for: cooling of eqipment or material, controlling dew point, heating, drying, oxidation or dilution, safety exhaust and odor control. Air must be supplied for ventilation, including all air required for comfort and proper working conditions for personnel.
WARNING
Do not block the combustion or ventilation air openings in the furnace. Any blockage will result in improper combustion and may result in a fire hazard or unsafe condition.
If ventilation and/or combustion air must be supplied to the “Confined Space” from outside the building structure, two permanent openings to the outdoors must be created. Each opening must have a free area of not less than one square inch per 4000 Btu per hour of total input of all applicances within the “Confined Space”, (See Figures 2 and 3). Neither openings can be blocked at any time.
Page 8 of 36 506307-01Issue 1207
CONFINED SPACE / OUTDOOR AIR FROM ATTIC
FURNACE
VENTILATION LOUVERS 1 SQ. IN. / 4000 BTUH
OF TOTAL INPUT
F0000309
VENTILATION LOUVERS 1 SQ. IN. / 4000 BTUH OF TOTAL INPUT
F0000310
CONFINED SPACE / OUTDOOR AIR FROM
ATTIC & CRAWL SPACE
For an attic installation it is important to keep insulation 12” or more away from any furnace openings. Some types of insulating materials may be combustible.
The proper sizing of warm air ducts is necessary to insure satisfactory heating operation. Ductwork should be in accordance with the latest editions of (U.S.) Systems) or Canadian equivalent.
Ductwork Recommendation:
The supply ductwork should be attached to the flanged opening provided at the discharge end of the furnace. See page 3 Furnace Specifications for the dimensions of this opening.
Undersized return air vents will adversely affect the airflow capability of the furnace and could cause overheating of the heat exchanger. The following
recommendations should be followed when installing the ductwork:
1. Install locking-type dampers in all branches of the
individual ducts to balance out the system. Dampers should be adjusted to impose the proper static at the outlet of the furnace.
2. Noncombustible flexible duct connectors are
recommended to connect both the supply and return ducts to the furnace.
3. In cases where the return air grille is located close to the
blower inlet, there should be at least one 90° air turn between blower and return grille. Further reduction in sound can be accomplished by installing acoustical air turning vanes and/or lining the inside of the duct with acoustical material.
Figure 2
CAUTION
NFPA-90A (Air Conditioning Systems) and NFPA-90B (Warm Air Heating and Air Conditioning
Figure 3
WARNING
Furnaces installed with combustion air drawn from a heated space which includes exhaust fans, fireplaces, or other devices that may produce a negative pressure should be considered confined space installations.
DUCTING
4. It is recommended that the supply duct be provided with a removable access panel. This opening shall be accessible when the furnace is installed and shall be such a size that the heat exchanger can be viewed for possible openings using light assistance or a probe can be inserted for sampling the air stream. The access panel shall be designed so as to prevent leaks when locked in position. If an air conditioning coil is installed, the access panel to the coil can be used for this purpose.
WARNING
When supply ducts carry air circulated by the furnace to areas outside the spaces containing the furnace, the return air shall also be handled by a duct sealed to the furnace casing and terminating outside the space containing the furance. Incorrect ductwork termination and sealing will create a hazardous condition that could lead to bodily harm.
506307-01 Page 9 of 36Issue 1207
CAUTION
BTU INPUT
FILTER SIZE
50,000
75,000
100,000
125,000
13 X 23
13 X 23
16 1/2 X 26
20 X 23
Air openings, intake and outlet pipes, return air grilles and warm air registers must not be obstructed.
Filters:
Air filters must be used in every installation.
Minimum filter size and suggested filter material are shown in Table 2. If different type filter is used, it must be an equivalent high airflow capacity.
Filter Size Selection
Table 2
If the washable permanent filters are used with this unit they should be cleaned periodically to prevent nuisance tripping of the high limit switch and failure to provide adequate filter media can cause equipment malfunction, uneven room temperature and excessive fuel usage.
When installing the furnace with cooling equipment for year round operation, the following recommendations must be followed for series or parallel air flow:
1. In series flow applications, the coil is mounted after the
furnace in an enclosure in the supply air stream. The furnace blower is used for both heating and cooling airflow.
2. In parallel flow installation, dampers must be provided to
direct air over the furnace heat exchanger when heat is desired and over the cooling when cooling is desired.
IMPORTANT: The dampers should be adequate to prevent cooled air from entering the furance, and if manually operated, must be equipped with means to prevent operation of either the cooling unit or furnace unless the damper is in the full cool or full heat position.
WARNING
The coil MUST be installed on the air discharge side of the furnace. Under no circumstances should the air flow be such that cooled, conditioned air can pass over the furnace heat exchanger. This will cause condensation in the heat exchanger and possible failure of the heat exchanger that could lead to a fire hazard and/or hazardous conditions that may lead to bodily harm. Heat exchanger failure due to improper installation will not be covered by warranty.
VENTING
Venting for the furnace must be to the outside and in accordance with local codes or requirements of the local utility. In the absence of local codes, venting must conform to the applicable sections of the latest edition of the (U.S.) National Fuel Gas Code ANSI Z223.1/NFPA 54. and/or CSA B149.1 Natural Gas and Propane Installation Codes, and the vent manufacturers instructions.
This furnace is CSA International apporved as a Category I forced air appliance and can not be vented into a vent system with any Category II, III or IV appliance. It must be vented vertically, or nearly vertically, unless installed with a listed mechancial venter in accordance with horizontal venting instructions. It must not be connected to any portion of a mechanical draft system operating under positive pressure.
The vent system must be securely fastened to the furnace flue collar with two (2) field supplied, corrosion resitant, sheet metal screws located at least 120 degrees apart and midway up the collar (see Figure 4).
Page 10 of 36 506307-01Issue 1207
VENT SYSTEM CONNECTION
Figure 4
Pre-Installation Vent System Inspection:
Before this furnace is installed, it is highly recommended
that any existing vent system be completely inspected.
For a chimney or “B” vent, this should include the
following:
1. Inspection for any deterioration in the chimney or “B” vent. If deterioration is discovered, the chimney must be repaired or the “B” vent must be replaced.
2. Inspection to ascertain that the vent system is clear and free of obstructions. Any blockage must be cleared before installing this furnace.
3. Cleaning the chimney or “B” vent if previously used for venting a solid fuel burning appliance or fireplace.
4. Confirming that all unused chimney or “B” vent connections are properly sealed.
5. Verification that the chimney is properly lined and sized per the applicable codes.
Masonry Chimney:
This furnace can be common vented into an existing
tile lined masonry chimney provided:
1. The chimney is currently serving at least one drafthood equipped appliance.
2. The vent connectors and chimney are sized in accordance with the applicable sections of the (U.S.) National Fuel Gas Code ANSI Z223.1/NFPA54, and/or CSA B149.1 Natural Gas and Propane Installation Codes.
This furnace must
NOT be vented ALONE into an existing masonry chimney (either title lined or unlined) unless the chimney is also lined with either a type “B” vent system or a listed single wall, metal lining system. Both of these systems must be sized in accordance with the applicable sections of the (U.S.) National Fuel Gas Code ANSI Z223.1/ NFPA 54, and/or CSA B149.1 Natural Gas and Propane Installation Codes.
Before venting this furnace into a chimney, check the chimney for deterioration and repair if necessary. This furnace must not be vented into a chimney serving a separate appliance designed to burn solid fuel. Type II “B” vent connectors must be used on all installations and it must be sized per the applicable sections of the (U.S.) National Fuel Gas Code ANSI Z223.1/NFPA 54, and/or CSA B149.1 Natural Gas and Propane Installation Codes.
Horizontal Venting:
This furnace is design certified by CSA International for horizontal venting through an outside wall by use of one of the following auxiliary draft inducer kits:
AUXILIARY DRAFT INDUCERS
Table 3
See Figure 5 on page 12 for information on where the sidewall vent terminal can and cannot terminate.
For Massachusetts Installations: The installation must comply with Massachusetts 248 CMR 5.08 Modifications to sections of NFPA-54, Chapter 10. (See pages 26 and 27)
General Venting Requirements:
This furnace may be common vented only with other Category I appliances. Common venting is allowed as permitted by national and/or local codes. Refer to the applicable sections of the (U.S.) National Fuel Gas Code ANSI Z223.1/NFPA 54, and/or CSA B149.1 Natural Gas and Propane Installation Codes for proper sizing and set up.
The vent must be terminated with a listed vent cap or roof assembly. This venting must be installed in accordance with the vent manufacturer’s instructions and be in accordance with all local codes and/or national codes.
The following requirements are provided for a proper venting system:
1. Be sure that the chimney flue is clear of any dirt or debris.
2. Be sure that the chimney is not servicing an open fireplace.
Type “B” Vent:
The furnace is also approved for use with a “B” vent that terminates through the roof. Refer to the applicable sections of the (U.S.) National Fuel Gas Code ANSI Z223.1/ NFPA 54, and/or CSA B149.1 Natural Gas and Propane Installation Codes for proper sizing and set-up of this furnace with “B” vent for a dedicated vent system or a common vented system.
506307-01 Page 11 of 36Issue 1207
Sidewall Vent Terminal Clearances (Non-Direct Vented Furnaces)
A** Minimum 12” (30 cm) above grade or 12” (30 cm) above average snow accumulation
V
X
Area Where Terminal Is Not Permitted
Vent Terminal
Air Supply Inlet
1
In accordance with the current
Propane Installation Code
2
In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code
A vent shall not terminate directly above a sidewalk or paved
CSA B149.1, Natural Gas and
driveway that is located between two single family dwellings and serves both dwellings.
Figure 5
Page 12 of 36 506307-01Issue 1207
Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
* For clearances not specified in
ANSI Z223.1/NFPA 54 or CSA
B149.1, the following statement shall be included:
“Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer’s installation instructions.”
3. Never reduce the pipe size below the outlet size of the
furnace without checking the applicable sections of the (U.S.) and/or CSA B149.1 Natural Gas and Propane Installa­tion Codes.
4. All pipe should be supported using the proper clamps
and/or straps. These supports should be at least every four (4’) feet.
5. All horizontal runs of pipe should have at least a 1/4” (in.)
per foot of upward slope from the furnace to the vent terminal.
6. All runs of pipe should be as short as possible with as few
turns as possible.
7. Seams should be tightly joined and checked for leaks.
8. The flue pipe must not extend into the chimney but be
flush with the inside wall.
National Fuel Gas Code ANSI Z223.1/NFPA54,
9. The chimney or vent pipe must extend at least three (3’) feet above the highest point where it passes through a roof of a building and at least two (2’) feet higher than any portion of a building within a horizontal distance of ten (10’) feet. It shall also extend at least five (5’) feet above highest connected equipment flue collar.
Checking For Vent Oversizing:
If this furnace is replacing a furnace that is attached to a venting system serving other appliances, the venting system is likely to be too large to properly vent all of the attached appliances. An improperly sized venting system can lead to condensation, leakage, or spillage.
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death.
The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the common venting system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 or the CSA B149.1, Natural Gas and Propane Installation Codes and these instructions. Determine that there is no blockage or restriction, leakage, corrosion, or other deficiencies which could cause an unsafe condition.
3. As far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other spaces of the building.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they are operating at maximum speed. Do not operate a summer exhaust fan.
6. Follow the lighting instructions. Place the applicance being inspected in operation. Adjust the thermostat so appliance is operating continuously.
7. Test for spillage from draft hood equipped appliances at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle.
8. If improper venting is observed during any of the above tests, the venting system must be corrected in accordance with the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or the CSA B149.1, Natural Gas and Propane Installation Codes.
9. After it has been determined that each appliance connected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers, and any other gas-fired burning appliance to their previous conditions of use.
506307-01 Page 13 of 36Issue 1207
ELECTRICAL CONNECTIONS
When installed, the furnace must be electrically grounded in accordance with local codes or, in the absence of local codes, with the (U.S.) 70 or CSA Standard C22.1; Part 1 Canadian Electrical Code. For proper installation refer to furnace rating label for electrical ratings and for the field wiring of this unit refer to furnace wiring specifications on page 5 or alternately from the wiring diagram on page 25. In all instances, other than wiring for the thermostat, the wiring to be done and any replacement of wire shall conform with the temperature limitation for Type T wire [63°F rise (35°C)].
The electrical connections and the thermostat connections are made through the openings on the side of the control box.
The control system depends on the correct polarity of the power supply. Connect “Hot” (H) wire and “Ground” (G) wire as shown in furnace wiring specification on wiring diagram. Use reference Table on page 3 (Furnace Specifications), for over current protection, max unit amp rating and wire size. Use copper wire only for 115V-supply service to unit. When replacing any original internal wiring, use only 105°C, 16 AWG copper wire.
National Electrical Codes, ANSI/NFPA
GAS CONNECTIONS
Instructions for wiring the thermostat are packed in the thermostat (field supplied) box. Make the thermostat connections as shown in furnace wiring specifications to the wire pigtails on the 24-volt terminal board located in the control box.
When installing optional accessories to this appliance, follow the manufacturer’s installation instructions included with the accessory.
WARNING
The unit cabinet must have an uninterrupted or unbroken electrical ground to minimize personal injury if an electrical fault should occur. This may consist of electrical wire or approved conduit when installed in accordance with existing electrical codes. Do not use gas piping as an electrical ground. Failure to follow this warning can result in an electrical shock, fire, bodily harm, or loss of life.
Gas piping shall be of such size and so installed as to provide a supply of gas sufficient to meet maximum demands without undue loss of pressure between the gas meter and the furnace. It is recommended that the gas line to the furnace shall be a separate line direct from the meter, unless the existing gas line is of ample capacity. Refer to gas pipe capacity table in the (U.S.) Z223.1/NFPA54, and/or CSA B149.1 Natural Gas and Propane Installation Codes.
If local codes allow the use of a flexible gas appliance connector, always use a new listed connector. Do not use a connector which has previously serviced another gas appliance.
Use a joint compound (pipe dope) that is resistant to the action of liquefied petroleum gases or any other chemical constituents of the gases to be conducted through the piping.
For proper furnace operation the maximum gas supply pressure is 14” w.c. and the minimum gas supply pressure is 4.5” w.c. - Natural (11” w.c. - LP) as shown on rating label.
Before any system of gas piping is finally put into service, it should be carefully tested to determine if it is gas tight. Check all piping for leaks using soapy water and a brush. The piping must stand a pressure of six (6) inches of mercury (3 PSIG) for a period of ten (10) minutes or as required by local authority.
National Fuel Gas Code ANSI
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings exactly could result in serious injury, death or property damage.
Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections. A fire or explosion may result causing property damage, personal injury or loss of life.
WARNING
The furnace and its individual shutoff valve must be disconnected from the supply piping system during any pressure testing of that system at test pressures in excess of 1/2 PSIG (3.5kPa or 14” w.c.).
The furnace must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at pressures equal to or less than 1/2 PSIG (3.5kPa or 14” w.c.). Failure to follow the above procedures could lead to a hazardous condition and bodily harm.
Page 14 of 36 506307-01Issue 1207
Figure 6
GAS SUPPLY
FIELD SUPPLIED MAIN
MANUAL SHUT-OFF VALVE
DRIP LEG
F0000316
GAS CONTROL PIPING
CAUTION
Many soaps used for leak testing are corrosive to certain metals. Piping must be rinsed thoroughly with clean water after leak check has been completed.
WARNING
Never use an open flame when testing for gas leaks! Use of an open flame could lead to a fire or explosion.
TYPICAL GAS SERVICE CONNECTION
Figure 7A
TYPICAL GAS SERVICE CONNECTION
FIELD SUPPLIED MAIN
MANUAL SHUT-OFF
VALVE
GAS SUPPLY
DRIP LEG
F0000317
Figure 7B
Field Reversal:
WARNING
Before proceeding with field reversal, insure that all electrical power is turned OFF and that all gas piping is shut OFF and disconnected from the furnace. Failure to do so could result in an extremely hazardous condition and bodily harm.
FIELD REVERSED
BLOWER ACCESS
AIR FLOW
F0000312
Figure 8A
STANDARD
This furnace is manufactured for use with natural gas and must be converted using the proper LP concersion kit for use with LP (Propane) gas. For LP (Propane) gas, a tank requlator is required to reduce supply pressure to 12”­13” w.c. For manifold pressure see Table 5.
A main manual shut off valve must be used in the gas piping. The shut off type and location must follow local codes and should always be in an accessible but protected location. In the absence of local codes the recommended methods for installing the gas piping to the furnace are shown in Figures 6 and 7.
The gas valve contains two threaded ports for a 1/8” NPT tap in order to test incoming gas pressure and outgoing manifold pressure (See Figure 9).
506307-01 Page 15 of 36Issue 1207
BLOWER ACCESS
AIR FLOW
F0000311
Figure 8B
This furnace may be field reversed allowing for a left to right airflow instead of the factory positioned right to left air flow (See Figures 8A and B). Field reversal is accomplished by inverting the furnace so that the “top” panel is down.
THEORY OF OPERATION
Here’s How Your System Works:
Call For Heat
The thermostat calls for heat by energizing the “W” terminal. The control checks to see the limit switch is closed and pressure switch is open. If the limit switch is open, the control responds per the Open Limit section following. If the pressure switch is closed, the control will flash “3” on the LED and wait indefinitely for the pressure switch to open. If the pressure switch is open, the control proceeds to pre­purge.
Pre-Purge
The control energizes the induced draft motor and waits for the pressure switch to close. The control flashes “3” on the LED while the pressure switch is open. If the pressure switch does not close within 60 seconds of the inducer energizing, the control will de-energize the inducer for 300 seconds, and then re-energized the inducer. This cycle shall continue as long as a call for heat exists until the pressure switch is proven.
When the pressure switch is proven closed, the control begins the pre-purge time. If flame is present any time while in pre-purge, the control will flash “5” on the LED and go into soft lockout. The control runs the inducer for a 15 second pre-purge time, then proceeds to the ignition trial period.
Ignition Trial Period
The control energizes the spark and main gas valve. The inducer remains energized. If flame has not been sensed within the 7 second ignition trial, the control de­energizes the gas and spark outputs and proceeds with ignition retires. If flame is not established after three (3) trials for ignition, the control will flash “2” on the LED and goes into lockout.
Blower On Delay
The control waits for 30 seconds from the time the gas valve opened and then energizes the indoor blower heat speed. The gas valve and inducer remain energized. The control proceeds to steady heat mode.
Steady Heat
Control inputs are continuously monitored to ensure limit and pressure switches are closed, flame is established, and the thermostat call for heat remains. When the thermostat call for heat is removed, the control de-energizes the gas valve and begins post-purge and blower off delay time.
When the switch re-closes, the control runs the induced draft motor through post-purge and runs the indoor blower through the selected fan off delay. If the call for heat is still present when the limit switch closes, the control will begin an ignition sequence while the blower off delay continues. NOTE: An open limit switch breaks the power (“R”) to the thermostat. Cycling on the limit is an abnormal condition and a corrective action must be taken. Failure to correct this condition could damage the heat exchangers and void the warranty.
Post Purge
The inducer output remains on for a 15 second post­purge period after the thermostat is satisfied.
Blower Off Delay
The indoor blower motor is de-energized after a 90 second blower off delay. Blower timing begins when the thermostat is satisfied. If the thermostat calls for heat while in the blower off delay, the control immediately restarts the ignition sequence while the blower off delay continues.
WARNING
Should overheating occur, or the gas supply fail to shut OFF, turn OFF the manual gas valve to the appliance BEFORE turning OFF the electrical supply. A failure to adhere to this warning can result in a fire or explosion and bodily harm.
For cooling operation, when the inside temperature exceeds the thermostat setting, the thermostat will turn ON the cooling system.
When the thermostat calls for cooling, power from the transformer energizes the fan control board (for blower operation) and the outdoor condensing unit (for air conditioning).
The fan control board will automatically turn on the blower and condensing unit. The air moving over the indoor coil by the blower is cooled (and dehumidified) and passes through the ducts to the room registers.
When the thermostat is satisfied, the fan control board is de-energized and the condensing unit is shut-off. The blower will continue to operate for an additional 30 seconds for added cooling efficiency.
Open Limit
Any time the limit switch is open, the control de-energizes the gas valve and runs the indoor blower motor on heat speed, and runs the induced draft motor. While the limit switch is open, the control flashes “4” on the LED. Check for a restriction in the duct system (i.e. dirty filters, blocked
ductwork, closed registers . . . . . . ).
Page 16 of 36 506307-01Issue 1207
STARTUP AND OPERATIONAL CHECKOUT
WARNING
Do not use this furnace as a construction heater. Use of this furnace as a construction heater exposes the furnace to abnormal conditions, contaminated combustion air and the lack of air filters. Failure to follow this warning can lead to premature furnace failure and/or vent failure which could result in a fire hazard and/or bodily harm.
The automatic gas valve controls the flow of gas to the main burners. The ignition system control switch built into the automatic valve body has 2 positions: “OFF” and “ON” (Figure 9). To shut off gas manually: Rotate switch from “ON” to “OFF” position. When in “OFF” position, the main burners are extinguished.
This furnace is equipped with an automatic spark ignition control and does not require the manual lighting for furnace operation.
GAS CONTROL DIAGRAM
TYPICAL FLAME APPEARANCE
(Main Burners)
7. Recheck for leaks in the manual shut off valve, gas control valve and gas connections using a soap solution.
WARNING
Never use an open flame when testing for gas leaks! Use of an open flame could lead to a fire or explosion.
CAUTION
Figure 9
WARNING
Do not attempt to manually light the burners. Failure to follow this warning can lead to electrical shock that could result in bodily harm.
After the ductwork connections have been made, gas piping and electrical wiring completed and the furnace has been properly vented, the unit should be started and adjusted for proper operation. Check off the following steps as they are completed.
1. Be sure all electrical power is OFF.
2. Check all wiring using proper wiring diagram on inside
of the control box cover.
3. Turn ON the electrical power.
4. Set the gas control knob in the “ON” position.
5. Set the thermostat above room temperaturae.
6. The ignitior will spark and the main burners will ignite.
Many soaps used for leak testing are corrosive to certain metals. Piping must be rinsed thoroughly with clean water after leak check has been completed.
Manifold Pressure Adjustment:
Turn OFF the gas and electrical before proceeding!
Remove the manifold pressure tap pipe plug from the gas valve (Figure 9 outlet pressure tap) and install a pressure tap and connect it to a manometer. Turn on the gas and electrical supplies, then measure the manifold pressure with
the furnace in operation.
Remove the cap to access the screw for input
adjustment (Figure 9 Pressure Regulator). Turn regulator-
adjusting screw IN to increase pressure, OUT to decrease pressure. Replace the cap. Measure the
manifold pressure.
For natural gas, best results are obtained with a manifold pressure of 3.2” to 3.5” w.c. For units that have been converted to LP (Propane) gases, a manifold pressure of 10” w.c. is necessary. After proper adjustment, turn OFF gas, replace manifold pressure tap pipe plug and turn ON gas.
506307-01 Page 17 of 36Issue 1207
WARNING
WARNING
At higher altitudes and varying heating valves, manifold pressure or orifice changes maybe required. Consult Tables 6 and 7 for appropriate values. Failure to follow this warning could lead to a hazardous furnace operating condition and result in serious bodily injury or loss of life.
Determining Furnace Input - Natural Gas ONLY:
NOTE: Burner access panel of furnace must be in place
when checking gs input.
1. Turn OFF all other gas appliances (except for pilot burners) served by the same gas meter.
2. With furnace operating in full heat cycle, note how many seconds it takes for one full revolution of the smallest dial on the meter. Typically, this will be a 1/2 - or - 1 - cubic foot test dial.
3. Using the number of seconds for one revolution and the size of the meter dial, determine the cubic foot per hour of gas flow by using the formula provided below or Table
4.
Cubic Ft/Hr = Time (in seconds) Required for Number of Timed Revolutions
Number of Dial Revolutions x Cubic Foot/Revolution x 3600
Furnace input should be maintained within ± 2% of the value on the rating plate or appropriate altitude derate. Adjust manifold pressure or change main orifices size if required.
5. Calculate the unit’s input rate.
Example: If the heating value of the natural gas is
1015 Btu/cu. and it takes 60 seconds to burn 2 cu. ft. of gas then:
Input = 1015 Btu/cu. ft. x 1 rev x 2 cu. ft./rev. x 3600
60 sec.
Input = 121,8000 btu/hr.
Burner Orifice Sizing:
The furnace is supplied with standard orifices for the gas shown on the rating plate. Table 5 shows combinations of heating values and specific gravities for various gases, from which proper input can be obtained.
If changing orifices is required, remove the manifold from the furnace (following the instructions found on page 21) and replace orifices as required by Table 5, the altitude derating section of this instruction or as local code dictates.
Gas Rate (Cubic Feet per Hour)
Table 4
4.Calculate the furnace input using the following formula:
BTUH = Cubic Ft/Hr x BTU/Cubic Foot
The local gas supplier should be able to provide the heating value of the gas, in BTU/cubic foot. If a specific value is not available, use 1000 BTU/cubic foot for Natural gas or 2500 BTU/cubic foot for Propane (LP).
Burner Orifice Selection
Table 5
After securing the manifold assembly, replace all other components and/or wiring, being sure that all connections and screws are tightened properly.
Altitude Derating:
The following information is provided as guidelines for altitude derating and is not meant to supersede any state or local codes. Local codes have priority over any others and in some case might limit your options in dealing with an altitude derate situation.
Page 18 of 36 506307-01Issue 1207
NOTE: In Canada for altitudes up to 4500 ft. (1372 m) see
the rating label on this furnace for proper manifold pressure and orifice size. Certification for installations at altitudes over 4500 ft. (1372 m) is the jurisdiction of local authorities.
Check with your local gas company to find out if the gas supply in your area is derated. Gas deration negates the necessity of performing any adjustment on the furnace.
If your gas supply is not derated, and regardless of the type of gas used, installation of this furnace at elevations above 2,000 ft. requires a n input reduction at the rate of four percent (4%) for each 1,000 ft. above sea level.
Unless an orifice change is specified by an applicable code, or the furnace is to be installed above 6,999 feet, the recommended method of altitude derating this furnace is to appropriately lower your manifold pressure. The appropriate manifold pressures based on the elevation and the heating value can be found in Table 6.
High Altitude Manifold Pressure Derate
(with standard 42 orifice Natural / 54 orifice LP sizes)
Table 6
If local codes require an orifices change or if the furnace installation is above 6,999 feet. The appropriate orifice size based on the elevation and the heating value can be found in Table 7. Sizing of the orifice must be based o the previously mentioned 4% derate for each 1,000 feet for installations at/ or above 2,000 feet rule and the orifices must be drilled in such a way as to assure concentricity. Hand drilling of
orifices is unacceptable.
High Altitude Orifice Size Derate
WARNING
Hand drilling of orifices is never acceptable since it could lead to delayed igntion, overfiring, improper combustion, flashback and flame rollout. All these conditions could lead to a fire hazard and bodily harm, or loss of life.
Blower Adjustment Checkout:
Prior to any blower adjustment, electrical service must
be turned OFF.
This furnace is equipped with a 3 speed direct drive motor to deliver a temperature rise within the range specificed on the rating label, between the return and supply plenums, at the external duct static pressure noted on the rating label.
Adjust the blower speed so that the temperature rise is within the rise specified on the rating label. Consult the wiring diagram for speed changes on the direct drive motor.
Limit Control Checkout:
After the furnace has been in operation for at least 15 minutes, restrict the return air supply by blocking the filters or closing the return registers and allow the furnace to shut down on hight limit. The main burners will shut OFF and the main blower and combustion blower should continue to run. Remove the restriction and the burners should come back on in a few minutes.
Flame Rollout Switch:
This unit is equipped with two (2) manual reset flame­rollout switches that protects against improper venting of the flue gases from the heat exchanger due to blockage causing heat (or flames) to “rollout” into the burner box from the heat exchangers, either safety device will activate and shut off power to the automatic gas valve before there is damage to the furnace. The loss of power to the gas vlave will shut off the gas burners. Should this occur, it will be necessary to determine the cause of the rollout, correct the condition that caused it, and reset the flame-rollout switch
Table 7
For installation above 2,000 feet if unit is adjusted for altitude mark the furnace label that has the words “Altitude Adjusted”.
506307-01 Page 19 of 36Issue 1207
WARNING
The furnace should be allowed to cool-off before attempting to reset the switch. Failure to follow these instructions could result in injury due to burns.
The switches are located behind the burner access
panels they are accessed by removing the burner access panels from the furnace, and are reset by pushing in the button in the middle of the switch (between the two wire connections - See Figure 11). Very little force is required to push the reset button, and a “click” should be heard when the switch resets.
FLAME ROLLOUT SWITCH
Figure 11
Pressure Switch Check:
To check the operation of the pressure switch vent safety
control, remove the vent from the combustion blower. Place the furnace into operation. Gradually cover up the blower outlet; the main burners should shut OFF. Remvoe the restriction and the unit should relight. Replace the vent adaptor and reseal the opened joints as required.
The operational checkout is now complete. Be sure to
adjust the thermostat to the desired setting and inform the homeowner how to operate the furnace system before leaving the job site.
WARNING
If the pressure switch activates to shut the furnace down, the vent system must be checked and cleared. Failure to do so may result in serious bodily harm or nuisance furnace shutdown and/or a hazardous condition that may lead to property damage, personal injury or death.
Page 20 of 36 506307-01Issue 1207
BLOWER ACCESS PANEL
BURNER/MANIFOLD ASSEMBLY
BURNER ACCESS PANEL
CONTROL BOX COVER
F0000322
FORWARD MANIFOLD SUPPORT
MAINTENANCE
SERVICING THE FURNACE
WARNING
ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD.
Failure to follow safety warnings exactly could result in dangerous operation, serious injury, death or property damage.
Improper servicing could result in dangerous operation, serious injury, death or property damage.
• Before servicing, disconnect all electrical power to furnace.
• When servicing controls, label all wires prior to disconnecting. Reconnect wires correctly.
• Verify proper operation after servicing.
WARNING
The ability to properly perform maintenance on this equipment requires certain mechanical skills and tools. If you are at all uncertain, contact your dealer for qualified maintenance and service since improper service could lead to furnace shutdown or a hazardous condition which could lead to an unsafe condition and bodily harm.
Combustion Component Check:
The heat exchanger, gas burners and venting system must be checked each year, prior to the heating season, by a qualified dealer/serviceman.
The following procedures should be performed:
1. Remove the burner/manifold assembly from the furnace,
follow the instructions found on this page.
2. Place the burner/manifold assembly on a flat work area
and vacuum the burners. It might be necessary to use a soft bristly brush to remove dirt and then vacuum.
3. Remove the burner opening inlet plate. This will expose
the burner openings of the primary heat exchangers.
4. Vacuum the length of each heat exchanger tube using a
straight attachment into the burner openings and then vacuum the burner box.
5. Replace the burner opening inlet plate, and burner/
manifold assembly. Insure that all gaskets are properly positioned and that no leaks exist.
6. Reattach all wiring and piping as per the wiring diagram
and installation instructions.
7. Turn on utilities and check for leaks using soapy water
and a brush.
506307-01 Page 21 of 36Issue 1207
8. A visual check of the main burner should be made at the beginning of each heating season.
9. Check the input rate and adjust if necessary.
10. Perform a safety check of the limit control and pressure switch.
11. Check the air filter, clean and/or replace as necessary.
12. Replace the appropriate access panels or doors.
WARNING
Never use an open flame when testing for gas leaks! Use of an open flame could lead to a fire or explosion!
CAUTION
Many soaps used for leak testing are corrosive to certain metals. Piping must be rinsed thoroughly with clean water after leak check has been completed.
Manifold (or Burner/Manifold) Removal/Replacement:
1. Make sure that all utilities (gas and electricity) are turned off upstream of the furnace.
2. Disconnect the gas line from the gas valve. Be sure that a wiring diagram is available, or be ready to mark any wires that are disconnected. Unplug the two (2) connectors from the gas valve, three (3) connectors from the rollout switch, flame sensor and sparker ignitor wire.
3. Remove burner access panel and the two (2) screws holding the forward manifold supports.
4. Slide the burner/manifold assembly forward through the burner access opening. Being careful not to jare the sparker or flame sensor.
FURNACE PANEL REMOVAL
Figure 12
5. Slide the burner/manifold assembly forward, out of the furnace until the assembly is clear of the manifold retention pins.
6. To reinstall the burner/manifold assembly, reverse the above steps.
Blower Removal/Replacement:
Removal
1. Turn OFF all electrical power to the furnace.
2. Remove the blower access panel.
3. Unplug wires from the blower assembly, auxiliary limit and door interlock switch to the control box.
4. Remove the two (2) blower retaining screws from the front blower leg (See Figure 13). These are the two (2) screws located in the blower compartment that secure the blower leg to the blower partition panel.
5. Slide the blower forward about two (2) inches. This will disengage the rear blower leg from the blower partition. Rotate the blower down to clear the top of the unit and continue sliding the blower forward until it is out of the unit.
BLOWER REMOVAL AND REPLACEMENT
Figure 13
Replacement
1. Place the blower in the blower opening of the unit and slide the blower back, into the unit, taking care to clear the top of the unit.
2. When the blower is completely into the cabinet, rotate the rear of the blower up so that the face of the rear blower leg engages the back partition clip in the blower partition.
3. Continue sliding the blower into the unit until the front leg lies flat against the blower partition and blower retaining screw holes are aligned. The rear of the blower should be against the clip in the partition and should be under the partition clip.
4. Reattach the two (2) blower securing screws, any disconnected wiring and the blower access panel.
Lubricating Motors:
Direct drive motor and blower assemblies are factory lubricated and normally do not require oiling. If oiling is required lubrication of the blower motor is to be preformed only by a qualified service agency.
Page 22 of 36 506307-01Issue 1207
SEQUENCE OF OPERATION
DIRECT IGNITION SYSTEM CONTROL
506307-01 Page 23 of 36Issue 1207
LED Fla shLED Fla sh
CodeCode
Ind icatesInd icates Chec k/RepairChec k/Repair
OFF
Control not powered or gas valve/control failure.
1. Line voltage input power at L1 and L2 connectors on (IFC) Board.
2. Low voltage (24Vac) power at 24VAC and COM on (IFC) board.
3. Fuse open on (IFC) board.
4. System wiring harness in good condition and securely connected at both ends.
6. Control not functioning, replace.
"Heartbeat" Normal Operation (Standby).
Fast
"Heartbeat"
Call for heat.
2 Flashes Ignition re-try or recycle error.
1. Gas supply off or supply pressure too low to operate appliance.
2. Damaged or broken spark element.
3. Appliance power supply not properly earth grounded.
4. Flame sense rod contaminated, grounded to appliance chas si s, or in incorrect location.
5. Spark elem ent or flame sense wiring not properly connected.
6. Gas valve stuck, replace.
7. Move gas control switch to ON.
3 Flashes
Pressure switch closed when should be open—system waits until pressure switch opens, then proceeds with ignition sequence. Pressure switch or aux. limit was sti ll open 60 seconds after the inducer was energized. System i s in 5-minute delay mode, with inducer on. After 5-minute delay, new ignition sequence is initiated.
1. Pressure switch stuck closed.
2. Pressure switch mi s-wired, jumpered or tubing open.
3. Pressure switch captured or out of calibration, replace.
4. Inducer and inducer wiring not connected.
5. Low line voltage power supply.
6. Obstructions or restrictions in appliance air intake or exhaust flue system that prevent proper combustion air flow.
7. Blower not operating.
4 Flashes
Limit or flame rollout switch open. Combustion air blower is energized. The heat speed circulating air fan will be energized. System waits for limit string to close, then initiates a new ignition sequence. System will remain waiting until flame rollout manual reset is activated.
1. Open high temperatures limit.
2. Open manual reset flame rollout switch in the limit circuit.
3. Limit and rollout switch circuit wiring in good condition and securely connected.
4. Circulating air fan wiring and operation.
5. Dirty air filters.
6. Blower speed too low.
7. Registers closed.
5 Flashes
Flame signal sensed out of proper sequence (with flame signal still present). Combustion blower energized. T he heat speed ci rculation air fan will be energized after the selected heat fan on delay. Sy stem waits for flam e signal to disappear, then goes to Soft Lockout.
1. Flame at main burner.
2. Flame sense ground to chassis
Steady
ON
Control board fault hard lockout.
1. System wiring harness in good condition and securely connected at both ends.
2. All components functioning properly (i.e. inducer, blower, ignitor....).
3. Replace IFC control board.
LED Fla shLED Fla sh
CodeCode
Ind icatesInd icates Chec k/RepairChec k/Repair
OFF
Control not powered or gas valve/control failure.
1. Line voltage input power at L1 and L2 connectors on (IFC) Board.
2. Low voltage (24Vac) power at 24VAC and COM on (IFC) board.
3. Fuse open on (IFC) board.
4. System wiring harness in good condition and securely connected at both ends.
6. Control not functioning, replace.
"Heartbeat" Normal Operation (Standby).
Fast
"Heartbeat"
Call for heat.
2 Flashes Ignition re-try or recycle error.
1. Gas supply off or supply pressure too low to operate appliance.
2. Damaged or broken spark element.
3. Appliance power supply not properly earth grounded.
4. Flame sense rod contaminated, grounded to appliance chas si s, or in incorrect location.
5. Spark elem ent or flame sense wiring not properly connected.
6. Gas valve stuck, replace.
7. Move gas control switch to ON.
3 Flashes
Pressure switch closed when should be open—system waits until pressure switch opens, then proceeds with ignition sequence. Pressure switch or aux. limit was sti ll open 60 seconds after the inducer was energized. System i s in 5-minute delay mode, with inducer on. After 5-minute delay, new ignition sequence is initiated.
1. Pressure switch stuck closed.
2. Pressure switch mi s-wired, jumpered or tubing open.
3. Pressure switch captured or out of calibration, replace.
4. Inducer and inducer wiring not connected.
5. Low line voltage power supply.
6. Obstructions or restrictions in appliance air intake or exhaust flue system that prevent proper combustion air flow.
7. Blower not operating.
4 Flashes
Limit or flame rollout switch open. Combustion air blower is energized. The heat speed circulating air fan will be energized. System waits for limit string to close, then initiates a new ignition sequence. System will remain waiting until flame rollout manual reset is activated.
1. Open high temperatures limit.
2. Open manual reset flame rollout switch in the limit circuit.
3. Limit and rollout switch circuit wiring in good condition and securely connected.
4. Circulating air fan wiring and operation.
5. Dirty air filters.
6. Blower speed too low.
7. Registers closed.
5 Flashes
Flame signal sensed out of proper sequence (with flame signal still present). Combustion blower energized. T he heat speed ci rculation air fan will be energized after the selected heat fan on delay. Sy stem waits for flam e signal to disappear, then goes to Soft Lockout.
1. Flame at main burner.
2. Flame sense ground to chassis
Steady
ON
Control board fault hard lockout.
1. System wiring harness in good condition and securely connected at both ends.
2. All components functioning properly (i.e. inducer, blower, ignitor....).
3. Replace IFC control board.
TROUBLE SHOOTING With LED Indicator Assistance
Soft Lockout
The control shall not initiate a call for heat or call for continuous fan while in lockout. A call for cooling operates as normal. The control will still respond to an open limit and desired flame. Lockout shall automatically reset after 1 hour. Lockout may be manually reset by removing power from the control for more than 1 second or removing the thermostat call for heat for more than 1 and less than 20 seconds.
Hard Lockout
If the control detects a fault on the contorl board, the status LED will be energized steady and the control will lockout as long as the fault remains. A hard lockout will automatically reset if the hardware fault clears.
Page 24 of 36 506307-01Issue 1207
WIRING DIAGRAM
f0000321
506307-01 Page 25 of 36Issue 1207
FOR MASSACHUSETTS ONLY
IMPORTANT
For Side Wall Horizonal Venting
The installation must comply with 248 CMR 5.08 Modifications to sections of NFPA-54, Chapter 10 as listed below.
* “a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure
used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or
an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of
installaiton, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a) 1 through 4:
1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.”
Page 26 of 36 506307-01Issue 1207
** “c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When
the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components;
and
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When
the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies “special venting systems”, the following requirements shall be satisfied by the manufacturer:
1. The identification of each “special venting system” shall include the listing of either the website, phone
number or manufacturer’s address where the venting system installation instructions can be obtained; and
2. The “special venting systems” shall be Product Approved by the Board, and the instructions for provided
with that system shall include a parts list and detailed installation instructions.
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled
equipment and all the venting instructions, parts lists, and/or design instructions for the venting system shall remain with the appliance or equipment at the completion of the installation.”
* Text from Commonwealth of Massachusetts Official Website of the Office of Consumer Affairs & Business Regulation
(OCABR).
** Text from Joseph A Peluso, Jr. (Executive Director Board of State Examiners of Plumbers and Gas Fitters,
Commonwealth of Massachusetts) letter of April 24, 2007 to GAMA.
506307-01 Page 27 of 36Issue 1207
NOTES
Page 28 of 36 506307-01Issue 1207
USER’S INFORMATION MANUAL
Gas-Fired Furnace
Read all instructions in this manual and retain this and all additional instructions for future reference.
Congratulations...
...you have one of the most modern gas furnaces made. Your unit has been carefully selected to keep you warm and comfortable during the winter months. It will deliver superb performance with only minimal help from you.
WARNING
FIRE OR EXPLOSION HAZARD
To keep your operating costs low and to eliminate unnecessary service calls, we have provided a few guidelines. These guidelines will help you understand how your gas furnace operates and how to maintain it so you can get years of safe and dependable service. Read all the instructions in this manual, and keep all manuals for future reference.
AHRI Certified
The Air-Conditioning, Heating and Refrigeration Institute (AHRI) symbol verifies that Annual Fuel Utilization Efficiency (AFUE) ratings for our gas furnaces have been derived from U.S. Government standard tests.
Failure to follow the safety warnings exactly could result in serious injury, death, or property damage.
– Do not store or use gasoline or other
flammable vapors and liquids in the vicinity of this or any other appliance.
– WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Leave the building immediately.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach the gas supplier, call the fire department.
CSA International Design Certified
The CSA International symbols on each nameplate is your assurance that your furnace design meets nationally recognized standards for safety and performance.
506307-01 Page 29 of 36Issue 1207
– Installation and service must be
performed by a qualified installer, service agency, or the gas supplier.
IMPORTANT SAFETY INFORMATION
WARNING
ELECTRICAL SHOCK, FIRE,
OR EXPLOSION HAZARD
Failure to follow the safety warnings exactly could result in dangerous operation, serious injury, death, or property damage.
Improper servicing could result in dangerous operation, serious injury, death, or property damage.
Before servicing, disconnect all electrical power to furnace.
When servicing controls, label all wires prior to disconnecting. Reconnect wires correctly.
Verify proper operation after servicing.
For your safety, read the following before operating your furnace:
5. Should the gas supply fail to shut off or if overheating occurs, shut off the gas valve to the furnace before shutting off the electrical supply.
6. Do not use the furnace if any part has been under water. A flood-damaged furnace is extremely dangerous. Attempts to use the furnace can result in fire or explosion. A qualified service agency should be contacted to inspect the furnace and to replace all gas controls, control system parts, electrical parts that have been wet, or the furnace if deemed necessary.
7. Examine the furnace installation to determine that:
A. All flue gas carrying areas external to the furnace,
such as the chimney and vent connector, are clear and free of obstructions.
B. Vent connector is in place, slopes upward, and
is physically sound without holes or excessive corrosion.
1. The furnace area must be kept clear and free of combustible materials, gasoline, and other flammable vapors and liquids.
2. Insulating materials may be combustible. A furnace installed in an attic or other insulated space must be kept free and clear of insulating materials. Examine the furnace when it is installed and also any time insulation is added.
3. For proper and safe operation, the furnace needs air for combustion and ventilation. Do not block or obstruct air openings on the furnace, air openings to the area in which the furnace is installed, and the spacings around the furnace.
4. This furnace is equipped with an ignition device which automatically lights the burners. See OPERATING YOUR FURNACE on this page for information on lighting and shutting down the furnace.
OPERATING YOUR FURNACE
These furnaces are equipped with an ignition device which automatically lights the burners. Do not try to light the
burners by hand.
Before operating, smell around furnace area for gas. Be
sure to smell near floor because some gas is heavier than air
C. Return air duct connection(s) is physically sound,
sealed to the furnace casing, and terminates outside the space containing the furnace.
D. Physical support of the furnace is sound without
sagging, cracks, gaps, etc. around the base as to provide a seal between the support and the base.
E. There are no obvious signs of deterioration of
the furnace.
F. Burner flames are in good adjustment (see
Burner Flame beginning on page 34).
8. It is important that you conduct a physical inspection of the furnace at least twice a year. It is also recommended that the furnace should be inspected by a qualified service agent at least once per year.
and will settle to the lowest point. See WHAT TO DO IF YOU SMELL GAS on page 29 if the odor of gas is present.
Use only your hand to turn the gas control knob; never use tools. If the knob will not turn by hand, don’t try to repair it. Call a qualified service technician. Force or attempted
repair may result in a fire or explosion.
Page 30 of 36 506307-01Issue 1207
Lighting Instructions
1. STOP! Read the previous safety information.
2. Set the thermostat to the lowest setting.
3. Turn off all electric power to the furnace.
4. Remove the burner compartment access panel.
To Turn Off Gas to Furnace
1. Set the thermostat to the lowest setting.
2. Turn off all electric power to the furnace if service is to be performed.
3. Remove the burner compartment access panel.
4. Move the gas control knob or switch to “OFF” (see Figure
1). Do not force.
5. Replace the burner compartment access panel.
5. This appliance is equipped with an automatic ignition device. Do not try to light the burners by hand.
6. Move the gas control knob or switch to “OFF” (see Figure M-1).
Gas Valves
Alternate Lever
Switch
Honeywell
Single Stage
Figure M-1
7. Wait 5 minutes to clear out any gas, then smell for gas (including at the bottom of the unit near the ground). If you smell gas, stop and follow the directions in WHAT TO DO IF YOU SMELL GAS on page 29. If you don’t smell gas, continue to next step.
Temperature Control
There are many types and styles of thermostats. Yours may look different from the one shown in Figure M-2 on page 32, depending on the type of thermostat and whether cooling was installed with the system. However, almost all thermostats perform the same basic functions described in the following section.
Thermostat Operation
There are four buttons located on the thermostat (see Figure M-2 on page 32). One button controls the heating and cooling (if applicable) functions. Another Button is for “FAN” operation, either continuous or automatic. The remaining two buttons set the temperature range for the heating temperature and the cooling temperature desired.
To put the system into operation, push the button to either “HEAT” or “COOL” position. After choosing the type of operation, set the thermostat to the temperature you would like the system to maintain.
Fan Operation
You may wish to increase your comfort by setting your system for continuous air circulation of the indoor air. The fan switch on the thermostat permits you to do this (see Figure M-2 on page 32).
8. Move the gas control knob or switch to “ON”.
9. Replace the burner compartment access panel.
10. Turn on all electric power to the furnace.
11. Set the thermostat to the desired setting.
12. If the furnace will not operate, follow the instructions found below in To Turn Off Gas to Furnace and call your service technician or gas supplier.
Shutting Down the Furnace
To shut down the furnace, set the thermostat to the “OFF” position.
506307-01 Page 31 of 36Issue 1207
With the switch in the “ON” position the fan will operate continuously. “AUTO” position gives fan operation only when the unit is in either heating or cooling.
Furnace Operation
If your furnace is operating but fails to provide complete comfort, check the following before calling for service:
1. Be sure the thermostat setting is correct.
2. Check to see if the filter is clean.
3. Be sure air can circulate freely throughout your home. Do not block supply registers or return grilles with furniture or rugs.
Thermostat
Figure M-2
And if you also have cooling...
4. Keep surface of the outdoor coil free from dirt, lint, paper, or leaves.
5. Check and clean indoor coil, if necessary. (This check should be made at the start of each cooling season by a qualified service technician.)
If your furnace fails to operate, check the following:
1. Be sure the main switch that supplies power to the furnace is in the “ON” position.
2. Replace any burned-out fuses or reset circuit breakers.
3. Be sure the thermostat is properly set.
If the furnace still does not start, call a qualified service technician.
MAINTENANCE OF YOUR FURNACE
WARNING
Always shut off all power to the unit before attempting any of the following maintenance procedures. Failure to do so may result in personal injury.
There are routine maintenance steps you should take to keep your furnace operating efficiently. This maintenance will assure longer life, lower operating costs, and fewer service calls. In addition to the maintenance procedures listed in this manual, there are also other service and maintenance procedures that require the skills of a service person who has specialized tools and training. Personal injury can result if you are not qualified to do this work. Please call your dealer when service is needed.
Your gas furnace is designed to give many years of efficient, satisfactory service. However, the varied air pollutants commonly found in most areas can affect longevity and safety. Chemicals contained in everyday household items such as laundry detergents, cleaning sprays, hair sprays, deodorizers, and other products which produce airborne residuals may have an adverse affect upon the metals used to construct your appliance.
The cabinet of the furnace can be cleaned with soap and water. Grease spots can be removed with a household cleaning agent.
It is important that you conduct periodic physical inspections of your appliance, paying special attention to the gas burner and the flue outlet from the furnace. These components are located at the front of the unit. A flashlight will be useful for these inspections. Make one inspection prior to the beginning of the heating season and another during the middle.
Should you observe unusual amounts of any of the following conditions, it is important that you call your authorized dealer at once to obtain a qualified service inspection:
Page 32 of 36 506307-01Issue 1207
Rust, flakes, or other deposits
Coatings
Corrosion
Even if no unusual rust or other conditions are observed, it
is recommended that the furnace be inspected and serviced at least once per year by a qualified service technician. Regular inspections and planned maintenance
will assure many years of economical performance from your gas furnace.
Combustion and Ventilation Air
Adequate air supply must be provided to furnaces located in a closet, alcove, or utility room by means of upper and lower
grilles in the door, or by the introduction of outside air, or both,
BTU INPUT
FILTER SIZE
50,000
75,000
100,000
125,000
13 X 23
13 X 23
16 1/2 X 26
20 X 23
in accordance with the
National Fuel Gas Code, ANSI Z223.1/ NFPA 54 (latest edition) or the CSA B149.1, Natural Gas and Propane Installation Codes, and local codes.
WARNING
Adequate combustion and ventilation air must reach the furnace to provide for proper and safe operation. Air openings in front of furnace must be kept free of obstructions. Any obstruction may cause improper operation that can result in a fire hazard or carbon monoxide injury.
Venting and Furnace Support
Venting of this furnace must comply with the unit Installation Instructions. Be sure the installer has followed these requirements. If not, you should request the installer to comply as soon as possible.
For your safety, please note the following:
1. 80% furnaces may be common vented with another
appliance in certain circumstances. Refer to the installation instructions and Category I Venting Tables, National Fuel Gas Code, ANSI Z223.1/NFPA 54 (latest edition) or the CSA B149.1, Natural Gas and Propane Installation Codes, and local codes for proper installation guidelines.
2. This furnace is not designed for use with a vent damper.
Use of such a device will not improve the efficiency of this furnace.
The vent from your furnace may rise vertically and terminate above the roof. When horizontal venting an 80% furnace, an approved sidewall venter must be used. Refer to the Installation Instructions for further information on horizontal venting of an 80% furnace.
Make sure all flue product materials external to the furnace are clear and free of any obstruction, slope upward, and have no holes or leaks. For proper venting terminations, see the Installation Instructions furnished with the furnace.
to prevent operation of the furnace until the condition has been corrected. Contact your dealer if you desire more information about this important safety feature.
NOTE: After any heavy snow, ice or frozen fog event the furnace vent pipes may become restricted. Always check the vent system and remove any snow or ice that may be obstructing the exhaust pipes.
Should any unusual conditions be observed during your inspections, call an authorized service dealer immediately.
Return Air
All return air duct connections must be tight and sealed to furnace cabinet and all return air grilles or registers must be located outside the space containing the furnace.
Cleaning/Replacing the Filter
It is very important to clean or replace the air filter regularly. Dirty filters are the most common cause of inadequate heating or cooling performance and can sharply increase the operational costs of your unit. In some cases, they can double the cost. The air filter should be inspected at
least every 6 weeks and cleaned or replaced as required.
Your furnace may use either a disposable filter or a cleanable filter. The type of filter may be indicated on a label attached to the filter. If a disposable filter is used, replace with the same type and size. To remove excess dirt from a cleanable filter, shake filter and/or use a vacuum cleaner. Wash filter in soap or detergent water and replace after filter is dry. Cleanable filters do not need to be oiled after washing.
Cleanable filters may be replaced with disposable filters. Refer to Table 1 on page 33 when selecting the proper size and quantity of disposable filter. If your air distribution system has a central return air filter­grille, the furnace does not need a filter. Filter-grilles can be maintained the same way as cleanable filters (see above).
Minimum Filter Requirements
Check to see that the furnace cabinet is sound and firmly supported, without sagging. There should be no cracks or gaps between the furnace and the base or floor, which would permit entry of unfiltered air.
It is important that the outside area where the vent terminates is kept clear of any obstructions which might block or impede the venting of the furnace. Screens in vent terminals should be cleaned periodically. Should venting become blocked at anytime, your furnace is equipped with a special safety control
506307-01 Page 33 of 36Issue 1207
Table 1
Lubrication
Heat
Exchanger
Burner
Flame
(Blue Only)
Burner
Gas
Manifold
Lubrication of the bearings in the circulating air blower motor and the combustion blower motor is not recommended.
Burner Flame
While the furnace is in operation, observe the burner flames. Compare these observations to Figure M-3 to determine if proper flame adjustment is present. If your observations indicate improper flame adjustment, call your authorized service dealer for service. Do not attempt to adjust flame! Your service representative will perform this adjustment correctly.
Rollout Switch
This unit is equipped with a manual reset high temperature sensor or rollout switch. In the unlikely event of a sustained burner flame rollout, the rollout switch will shut off the flow of gas by closing the gas valve. The switch is located inside the gas burner area. Flame rollout can be caused by blockage of the power vent system, a blocked heat exchanger, or improper gas pressure or adjustment. If this event occurs, the unit will not operate properly. The gas supply to the unit should be shut off and no attempt should be made to place it in operation. The system should be inspected by a qualified service technician.
Safety Interlock Switch
The blower compartment door on your high efficiency gas furnace is equipped with a safety interlock switch that will automatically shut off your complete system (including blower) once the door is removed. This is for your personal safety. Be sure to check your furnace for proper operation once the door or panel has been replaced. If the system does not operate once the panel has been replaced, try removing and replacing it once again. If the furnace still does not operate, call your dealer for service.
REPAIR PARTS
The following repair parts are available from your local distributor. When ordering parts, include the complete furnace model number and serial number which are printed on the rating plate located on the furnace.
Gas Control Group
Manifold Orifice Manifold Retention Plate Ignition Wire Burner Gas Valve
Heat Exchanger Group
Primary Heat Exchanger Transfer Tube Flue Box Burner Inlet Plate Burner Box
Blower Group
Blower Assembly Capacitor Blower Housing Blower Cutoff Blower Motor Blower Support Blower Wheel
Inducer Group
Inducer Blower and Motor Pressure switch
Electrical Group
Control Box Ignition Control Limit Switch Transformer Fan Timer Control Board Rollout Switch
Typical Flame Appearance
Figure M-3
Page 34 of 36 506307-01Issue 1207
Owner Record
Furnace Model #________________________________ Serial # ____________________ Installation Date ___________
INSTALLED BY:
Dealer ____________________________________________________________________________________________
Address ___________________________________________________________________________________________
Telephone # __________________________________________ License # _____________________________________
Contact Person _______________________________________
Other Equipment Installed:
Equipment Type ______________________________________
Model # _________________________________ Serial # _________________________ Installation Date ____________
Equipment Type ______________________________________
Model # _________________________________ Serial # _________________________ Installation Date ____________
Equipment Type ______________________________________
Model # _________________________________ Serial # __________________________ Installation Date ___________
WHEN FRENCH IS REQUIRED!
ATTENTION: MR. INSTALLER OR HOMEOWNER
TO OBTAIN INSTALLATION INSTRUCTIONS, USER’S INFORMATION MANUAL AND FURNACE
MARKINGS IN FRENCH CONSULT WITH YOUR DEALER OR LOCAL DISTRIBUTOR:
HAVE AVAILABLE THE MODEL NUMBER AND SERIAL NUMBER LOCATED ON THE UNIT RATING
PLATE TO INSURE THE CORRECT FRENCH INSTRUCTION PACKET.
POUR OBTENIR DE LA DOCUMENTATION EN FRANÇAIS!
A L’ATTENTION DE L’INSTALLATEUR OU DU PROPRIÉTAIRE
POUR OBTENIR LES INSTRUCTIONS D’INSTALLATION, LE MANUEL DE L’USAGER ET LES MARQUAGES EN FRANÇAIS, CONSULTEZ VOTRE MARCHAND OU LE DISTRIBUTEUR DE VOTRE RÉGION:
AYEZ EN MAIN LE MODELE ET LE NUMÉRO DE SÉRIE INDIQUÉS SUR LA PLAQUE SIGNALÉTIQUE DE L’APPAREIL POUR OBTENIR LA POCHETTE D’INSTRUCTIONS EN FRANÇAIS APPROPRIÉ APPROPRIÉE.
506307-01 Page 35 of 36Issue 1207
INSTALLATION AND SERVICING
INSTRUCTIONS
AND
USER’S INFORMATION MANUAL
** INSTALLER — AFFIX THIS INSTRUCTION
PACKET ADJACENT TO THE FURNACE.
**HOMEOWNER — RETAIN THESE
INSTRUCTIONS FOR FUTURE REFERENCE.
INSTRUCTIONS D’ENTRETIEN ET
INSTALLATION
ET
MANUAL DE L’USAGER
**INSTALLATEUR — PLACEZ LA POCHETTE
D’INSTRUCTIONS À COTÉ DU GÉNÉRATEUR
D’AIR CHAUD.
**PROPRIÉTAIRE — CONSERVEZ CES
INSTRUCTIONS POUR Y RÉFÉRER PLUS TARD.
Page 36 of 36 506307-01Issue 1207
Loading...