Lennox ASC 020S, ASC 045D, ASC 025S, ASC 055D, ASC 070D Installation, Operating And Maintenance Manual

...
INSTALLATION, OPERATING
AND MAINTENANCE
AIR COOLED CONDENSING UNIT
ASC/ASH
20 - 230 kW
www.lennoxemea.com
MIL152E-1217 01/2019
TABLE OF CONTENTS
ASC/ASH
INSTALLATION OPERATION MAINTENANCE MANUAL
POINTS TO BEAR IN MIND
DATA PAGE FOR COMMISSIONING OF THE UNIT
1 -
GENERAL CHARACTERISTICS
1.1 4
Physical data
1.2 5
Electrical data
1.3 6
Fan performance
1.4 6
Operating limits
Piping drawings
1.5 7
Unit dimensions
1.6 11
2 -
INSTALLATION
2.1 12
Preliminary preparations
2.2 12
Unit acceptance
2.3 13
Unit location
2.4 13
Installation clearances
2.5 14
Inside location
2.6 15
Refrigerant connections
2.7 19
Electrical connections
2.8 21
Dry contact board control
2.9 22
Options installation
3 -
COMMISSIONING AND OPERATION
3.1 23
Preliminary checks before fi rst installation
Preliminary checks at fi rst installation
3.2 24
4 -
MAINTENANCE
4.1 25
Preventive maintenance
4.2 25
Corrective maintenance
4.3 26
Fault diagnosis
WARNING: Read this manual before carrying out installation, repair or maintenance work.
All the technical and technological information contained in this manual, including any drawings and technical descriptions provided by us, remain the property of Lennox and must not be utilised (except in the operation of this product), reproduced, issued to or made available to third parties without the prior written agreement of Lennox.
• 1 •
Installation, Operation and Maintenance manual • ASC/ASH-MIL152E-1217-01/2019
• 2 • Installation, Operation and Maintenance manual • ASC/ASH-MIL152E-1217-01/2019
POINTS TO BEAR IN MIND
DANGER AND WARNING SIGNS
Abrasive surfaces Low temperatures High temperatures Risk of injury from
moving objects
Electrical voltage Risk of injury from
rotating objects
ELECTRICAL CONNECTIONS
Make sure to switch off the power before installing, repairing or carrying out maintenance on the unit, in order to prevent serious electrical injury.
Keep local and national legislation in mind when installing the unit.
Standard Guidelines to Lennox equipment
All technical data contained in these operating instructions, including the diagrams and technical description remains the property of Lennox and may not be used (except for the purpose of familiarizing the user with the equipment), reproduced, photocopied, transferred or transmitted to third parties without prior written authorization from Lennox.
The data published in the operating instructions is based on the latest information available. We reserve the right to make modifi cations without notice.
We reserve the right to modify our products without notice without obligation to modify previously supplied goods.
These operating instructions contain useful and important information for the smooth operation and maintenance of your equipment.
The instructions also include guidelines on how to avoid accidents and serious damage before commissioning the equipment and during its operation and how to ensure smooth and fault-free operation. Read the operating instructions carefully before starting the equipment, familiarize yourself with the equipment and handling of the installation and carefully follow the instructions. It is very important to be properly trained in handling the equipment. These operating instructions must be kept in a safe place near the equipment.
Like most equipment, the unit requires regular maintenance. This section concerns maintenance and management personnel. If you have any queries or would like to receive further information on any aspect relating to your equipment, do not hesitate to contact us.
The manufacturing of these units is made under the requirements of the ISO 9001 and ISO 14001.
• 3 • Installation, Operation and Maintenance manual • ASC/ASH-MIL152E-1217-01/2019
DATA PAGE FOR UNIT COMMISSIONING
UNIT: ___________________________________________ SERIAL NUMBER : ___________________________________ CONTROL PANEL IDENTIFICATION CODE : _________________________________________________________________ INST ALLA TION ADDRESS: _______________________________________________________________________________ INSTALLER : _____________________________________ INSTALLER TEL : ____________________________________ INST ALLER ADDRESS : __________________________________________________________________________________
______________________________________________________________________________________________________ COMMISSIONING DATE : ________________________________________________________________________________ CHECKS : _____________________________________________________________________________________________
______________________________________________________________________________________________________ SUPPLY VOLTAGE : _______________________________ RATED VOLTAGE OF THE UNIT : _______________________
YES NO
Unit on shock absorbers Drainage with trap Main power supply connection Control panel connection Compressor oil level indicator
DATA INPUT:
COOLING CYCLE
Air intake temperature to the outdoor coil:
Air output temperature to the outdoor coil:
Circuit 1
High pressure:
Circuit 2 Circuit 1
Low pressure:
Circuit 2
ELECTRIC POWER CONSUMPTION (Amps)
Compressor 1: . . . . . . . . . . . . . . . . . . .
Compressor 2 : . . . . . . . . . . . . . . . . . .
Compressor 3 : . . . . . . . . . . . . . . . . . .
Outdoor fan section 1 . . . . . . . . . . . . .
Outdoor fan section 2 . . . . . . . . . . . . .
C 2ºC 1ºC 2ºC
Air intake temperature to the outdoor coil:
Air output temperature to the outdoor coil:
High pressure:
Low pressure:
Compressor 1: . . . . . . . . . . . . . . . . .
Compressor 2 : . . . . . . . . . . . . . . . .
Compressor 3 : . . . . . . . . . . . . . . . .
Outdoor fan section 1 . . . . . . . . . . .
Outdoor fan section 2 . . . . . . . . . . .
HEATING CYCLE
C 2ºC 1ºC
C Circuit 1 Circuit 2 Circuit 1 Circuit 2
Options installed : ____________________________________________________________________________ ___________________________________________________________________________________________ ___________________________________________________________________________________________ Comments : _________________________________________________________________________________ ___________________________________________________________________________________________ ___________________________________________________________________________________________
• 4 • Installation, Operation and Maintenance manual • ASC/ASH-MIL152E-1217-01/2019
1. GENERAL CHARACTERISTICS
1.1.- PHYSICAL DATA
A S C 020 S N M 3 M
Air cooled
condensing unit
S: Outdoor unit Split
C: Cooling only
H: Heat pump
S: One Circuit
D: Two Circuits
Approximate cooling
Type of refrigerant
M: R-410A
- - -
capacity in kW
Units valid for combine with air treatment units
ASC/ADC: Cooling only unit R-410A. ASH/ADH: Heat pump unit R-410A.
MODELS
Type of compressor Scroll Number of compressors
Cooling only unit ASC/ADC
Net weight
Air fl ow m Refrigerant charge NITROGEN (*)
MODELS
Type of compressor Scroll Number of compressors
Net weight
Air fl ow m Refrigerant charge NITROGEN (*)
Heat pump unit ASH/ADH
Optional Soft starter Optional FP1
Cooling only unit ASC/ADC
Heat pump unit ASH/ADH
Optional Soft starter Optional FP1
ASC/ASH 020S 025S
255 443 452 520
kg
3
/h
258 452 463 537
3666
6800 9750 11500 11300
ASC/ASH 040S 045D
12222
255 443 452 481 520
kg
3
/h
258 452 463 499 537
36666
11000 9750+9750 11500+11500 11300+11300 11000+11000
1
N/A
055D 070D 085D
N/A
M: 400V/3/50
Number
of revision
030S 035S
n/a: not available
n/a: not available
MODELS
Type of compressor Scroll Number of compressors
Cooling only unit ASC/ADC
Net weight
Air fl ow m Refrigerant charge NITROGEN (*)
Heat pump unit ASH/ADH
Optional Soft starter Optional FP1
ASC/ASH 100D 120D
22344
632 797 906 1659 1679
kg
748 828 932 1684 1704
9 9 9 n/a n/a
40 40 40 80 80
3
/h
22700+18100 22700+18100 22700+22700 28600+28600 36000+36000
140D 200D 230D
(*) The units are supplied with nitrogen gas; this must be removed and the unit charged with refrigerant R-410A, depending on unit model.
(See page
21 to calculate refrigerant charge for model ASC/ADC and ASH/ADH units to work with Air treatment units).
R-410A factory refrigerant precharge kit is available as an option.
• 5 •
Installation, Operation and Maintenance manual • ASC/ASH-MIL152E-1217-01/2019
1. GENERAL CHARACTERISTICS
1.2.- ELECTRICAL DATA
ELECTRICAL CONSUMPTION FOR STANDARD UNITS
MODELS ASC/ASH
Voltage Ph/V/Hz
Maximum absorbed power (kW)
Compressor Fan Total power
Maximum current (A)
Compressor Fan Total current Start up current (A)
MODELS ASC/ASH
Voltage Ph/V/Hz
Maximum absorbed power (kW)
Compressor Fan Total power
Maximum current (A)
Compressor Fan Total current Start up current (A)
020S 025S 030S 035S 040S 045D 055D
3N~400V
50Hz
3~400V 50Hz
8,25 10,1 11,8 15,6 16,9 20,2 23,6
0,3 0,69 0,69 0,84 0,84 1,38 1,38
8,55 10,79 12,49 16,44 17,74 21,58 24,98
15 21 22 25,6 31 42 44
1,6 3 3,4 3,4 3,4 6 6,8 16,6 24 25,4 29 34,4 48 50,8 87,5 97,4 104 138 17,2 121 129
070D 085D 100D 120D 140D 200D 230D
3~400V 50Hz
31,1 33,8 42,6 45,6 55,9 78,8 88,2 1,68 1,68 3,05 3,05 4 4,2 8
32,78 35,48 45,65 48,65 59,9 83 96,2
51,2 62 77,6 84 102 142 159
6,8 6,8 6,4 6,4 8 9,6 16
58 68,8 84 90,4 110 151,6 175
167 206 221 228 292 302,9 358
ADDITIONAL ELECTRICAL CONSUMPTION FOR THE OPTIONS
FP1 OPTION ASC/ASH
Voltage Ph/V/Hz
Maximum absorbed power kW
Maximum current A
Start up current A
100D FP1
(Low Speed/
High speed)
2,00 / 6,20 2,00 / 6,20 1,00 / 5,2 5,8 / 14,2 2 / 10,4
3,2 / 9,8 3,2 / 9,8 1,6 / 8,2 9,6 / 22,8 3,2 / 16,4
3,2 / 9,8 3,2 / 9,8 1,6 / 8,2 9,6 / 22,8 3,2 / 16,4
120D FP1
(Low Speed/
High speed)
140D FP1
(Low Speed/
High speed)
3/400V/50Hz
200D FP1
(Low Speed/
High speed)
230D FP1
(Low Speed/
High speed)
• 6 •
Installation, Operation and Maintenance manual • ASC/ASH-MIL152E-1217-01/2019
1. GENERAL CHARACTERISTICS
1.3.- FAN PERFORMANCES
1.3.1.- CONDENSING UNIT WITH AVAILABLE HIGH PRESSURE FAN (OPTION)
Air fl ow data / FP1 option / Low speed.
MODELS
Fan type Fan number
Airfl ow rate m3/h
50
Absorbed power kW Airfl ow rate m3/h
75
Absorbed power kW
(Pa)
Airfl ow rate m3/h
100
Absorbed power kW Airfl ow rate m
Available static pressure
125
Absorbed power kW
Air fl ow data. FP1 option. High speed.
MODELS
Fan type Fan number
Airfl ow rate m3/h
50
Absorbed power kW Airfl ow rate m
100
sure Pa,
Available static pres-
Absorbed power kW Airfl ow rate m
125
Absorbed power kW
100D - 120D - 140D 200D 230D
Axial “short case” - direct coupling
900 r.p.m. (Low speed) 3~400V
24
19000 + 19000 28000 + 28000
510
18000 + 18000 24000 + 24000
5,1 10.2
17000 + 17000 22000 + 22000 N/A
5,2 10,4 N/A
3
/h
15000 + 15000 20000 + 20000 N/A
5,3 10,6 N/A
100D - 120D - 140D 200D - 230D
Axial “short case”-direct coupling
1450 r.p.m. (High speed) 3~400V
24
22000 + 22000 34000 + 34000
9,2 18,4
3
/h
20000 + 20000 28000 + 28000
9,3 18,6
3
/h
18000 + 18000 24000 + 24000
9,4 18,8
n/a: Not available
1.4.- OPERATING LIMITS (For installation with air treatment units. Example)
COOLING ONL Y UNITS
Cooling cycle operation
HEAT PUMP UNITS
Cooling cycle operation
Heating cycle operation
(*)
With low temperature 0ºC kit (option)
Indoor temperature
Outdoor temperature
Indoor temperature
Outdoor temperature
Indoor temperature
Outdoor temperature
Maximum temperatures Minimum temperatures
32ºC DB
23ºC WB
(20S-25S-30S-45D-55D)
(35S-40S-70D-85D-100D-120D-140D)
45ºC
------------­47ºC
Maximum temperatures Minimum temperatures
32ºC DB
23ºC WB
20S-25S-30S-45D-55D)
-------------
(35S-40S-70D-85D-100D-120D-140D)
(See tables for heating capacities)
47ºC
27ºC DB
Depending on model
DB:
Dry bulb temperature.
21ºC DB
15ºC WB
+10ºC STANDARD UNIT
(*) / (**)
21ºC DB
15ºC WB
0ºC
15ºC DB
-10ºC DB
-11ºC WB
• 7 •
(**)
With option kit low temperature -15ºC or kit -15ºC and low noise level.
Installation, Operation and Maintenance manual • ASC/ASH-MIL152E-1217-01/2019
WB:
Wet bulb temperature
1. GENERAL CHARACTERISTICS
1.5.- PIPING DRAWINGS
COOLING ONLY UNITS
AIR TREATMENT UNIT. EXAMPLE CONDENSING UNIT
ASC 020S/025S/030S/035S/040S
DS
Fan
Coil
Expansion valve
(ELEMENTO OPCIONAL)
OPTION ELEMENT
AIR TREATMENT UNIT. EXAMPLE
Fan
Filter drier
Service valve option
C1
SVL1
Service valve option
Service valve
option
C1
Scroll compressor
LPT1
LP1
CH1
HP1
Suction accumulator (long distance connection option).
CONDENSING UNIT
ASC 045D/055D/070D/085D
LPT1
Scroll compressor
LP1
CH1
Suction accumulator (long distance connec­tion option).
HP1
Fan motor
HPT1
PT1
Coil
Fan motor
PT1
HPT1
Coil
DS
055D/070D/085D
Coil
Expansion
valve
Filter drier
SVL1
Service valve option
Service valve
option
LP2
LPT2
Scroll compressor
CH3
Suction accumulator ( long distance connec-
C2
SVL3
Expansion valve
OPTION ELEMENT
(ELEMENTO OPCIONAL)
Filter drier
Pressure gauge (5/16” to be fi tted by the installer) High pressure switch, circuit 1 Discharge sensor High pressure switch, circuit 2
DS HP2 SVL1 CH1
Liquid solenoid valve. (long distance option) To be connected by the installer to air treatment unit.
SVL3 CH3
Low pressure switch, circuit 1 High pressure transducer, circuit 1
LPT1 HPT1
Low pressure transducer, circuit 2 High pressure transducer, circuit 2
LPT2 HPT2
tion option).
Service valve option
HP1
Crankcase heater (Low ambient option) Crankcase heater (Low ambient option)
Outdoor temperature sensor
OS
Fan motor
HP2
PT2
HPT2
OS
Coil
• 8 •
Installation, Operation and Maintenance manual • ASC/ASH-MIL152E-1217-01/2019
1. GENERAL CHARACTERISTICS
1.5.- PIPING DRAWINGS
COOLING ONLY UNITS
AIR TREATMENT UNIT. EXAMPLE
Coil
Fan
Expansion valve
Coil
Filter drier
CONDENSING UNIT
ASC 100D/120D/140D
LPT1
Service valve
option
C1
Suction accumulator (Low ambient
-15ºC and low noise level option).
Service valve option
LPT2
Service valve
option
C2
Scroll compressor
1
CH
Scroll compressor
2
CH
Scroll compressor
3
CH
Suction accumulator (Low ambient -15ºC and low noise level option).
HPT1
HPT2
Fan motor
Coil
Fan motor
Coil
Expansion valve
Filter drier
Service valve option
OPTION ELEMENT
Pressure gauge. (5/16” to be fi tted by the installer) High pressure switch, circuit 1.
Discharge sensor High pressure switch, circuit 2.
DS HP2
SVL1 CH...
Liquid solenoid valve. (long distance option) To be connected by the installer to air treatment unit.
SVL3 HPT1
Low pressure switch, circuit 1 High pressure transducer, circuit 2
LPT1 HPT2
HP1
Crankcase heater (Low ambient option)
High pressure transducer, circuit 1
Low pressure transducer, circuit 2 Outdoor temperature sensor
LPT2 OS
• 9 •
Installation, Operation and Maintenance manual • ASC/ASH-MIL152E-1217-01/2019