Lennox 80UHG2-45, 80UHG2X-60, 80UHG2X-45, 80UHG3-60, 80UHG3X-60 Unit Information

...
Page 1
Corp. 9728−L12
Service Literature
80UHG series units are mid−efficiency gas furnaces used for upflow or horizontal applications only, manufactured with tubular heat exchangers formed of aluminized steel. 80UHG units are available in heating capacities of 45,000 to 120,000 Btuh and cooling applications up to 5 tons. Refer to Engineering Handbook for proper sizing.
Units are factory equipped for use with natural gas. Kits are available for conversion to LPG operation. 80UHG−1 model units use electronic (direct spark) ignition. 80UHG−2 and −3 model units are equipped with the Lennox SureLight silicon nitride ignition system. The 80UHGX unit meets the Califor­nia Nitrogen Oxides (NOx) Standards and California Sea­sonal Efficiency requirements. All units use a redundant gas valve to assure safety shut−off as required by A.G.A. or C.G.A. Units may be installed in upflow or horizontal position.
All specifications in this manual are subject to change. Pro­cedures outlined in this manual are presented as a recom­mendation only and do not supersede or replace local or state codes. In the absence of local or state codes, the guidelines and procedures outlined in this manual (except where noted) are recommended only and do not constitute code.
Revised 01−2002
80UHG
TABLE OF CONTENTS
Introduction 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Specifications 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Blower Data 3−4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
High Altitude 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parts Identification 5−6. . . . . . . . . . . . . . . . . . . . . . . . . . . .
I Unit Components 6−15. . . . . . . . . . . . . . . . . . . . . . . . . . .
II Installation 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
III Start Up 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
IV Heating System Service Checks 16−17. . . . . . . . . . .
V Typical Operating Characteristics 18. . . . . . . . . . . . . .
VI Maintenance 19−20. . . . . . . . . . . . . . . . . . . . . . . . . . . .
VII Wiring and Sequence of Operation 21−28. . . . . . . . .
VIII SureLight Troubleshooting Guide 29−34. . . . . . . . . .
Page 1
© 1999 Lennox Industries Inc.
Litho U.S.A.
Page 2
SPECIFICATIONS
Blower wheel nominal
g
Nominal cooling
)
Up−Flow/Horizontal Filter and Filter Rack Kits
Single (32J02) Te n Pack (66K64)
Blower wheel nominal
g
Nominal cooling
)
Up−Flow/Horizontal Filter and Filter Rack Kits
Single (46J14) Te n Pack (66K65)
Model No. 80UHG2(X)-45 80UHG2(X)-60 80UHG3(X)-60 80UHG2(X)-75 80UHG3(X)-75 80UHG4(X)-75
Input Btuh (kW) 45,000 (13.2) 60,000 (17.6) 75,000 (22.0)
Output Btuh (kW) 36,900 (10.8) 49,200 (14.4) 61,700 (18.1) 61,700 (18.1)
A.F.U.E. 80.1% 80.5% 80.1% 80.0%
California Seasonal Efficiency 75.4% 76.4% 75.9% 76.8% 76.8% 76.3%
Flue size connection diameter  in. (mm) round 3 (76) 4 (102)
Temperature rise range  _F (_C) 30 - 60 (17 - 33) 45 - 75 (25 - 42)
High static cert. by A.G.A./C.G.A.  in wg. (Pa) .50 (125)
Gas Piping Size I.P.S. Natural or LPG/propane 1/2 (13)
Blower wheel nominal
diameter x width
Blower motor output  hp (W) 1/4 (187) 1/3 (224) 1/4 (187) 1/3 (224) 1/2 (373)
Nominal coolin
that can be added
Shipping weight  lbs. (kg) 1 package 130 (59) 135 (61) 140 (64)
Electrical Characteristics 120 volts  60 hertz  1 phase (less than 12 amps) All models
LPG/propane kit LB-69845L (38K84)
Twinning Kit 15L38 − 11lbs. (5 kg)
Up−Flow/Horizontal Filter and Filter Rack Kits Single (32J02) Ten Pack (66K64 No. & sizeoffilters− in. (mm)
Sidewall Power Venting Kit 79J15  25 lbs. (11 kg)
Hanging Bracket Kit LB-69957 (46J66)  15 lbs. (8 kg)
in. 9 x 7 10 x 7 9 x 7 10 x 7 12 x 8
mm 229 x 178 254 x 178 229 x 178 254 x 178 305 x 203
Tons 1, 1-1/2 or 2 2, 2-1/2 or 3 1, 1-1/2 or 2 2, 2-1/2 or 3
kW 3.5, 5.3 or 7.0 7.0, 8.8 or 10.6 3.5, 5.3 or7.0 7.0, 8.8 or 10.6
Optional Accessories (Must Be Ordered Extra)
(1) 16 x 20 x 1 (406 x 508 x 25)
2, 2-1/2, 3,
3-1/2 or 4
7.0, 8.8, 10.6,
12.3 or 14.1
SPECIFICATIONS
Model No. 80UHG3/4(X)-100 80UHG4/5(X)-100 80UHG3/4(X)-120 80UHG4/5(X)-120
Input Btuh (kW) 100,000 (29.3) 120,000 (35.2)
Output Btuh (kW)
A.F.U.E. 80.1% 80.0% 80.0% 80.1%
California Seasonal Efficiency 76.5% 77.0% Not Available 75.5%
Flue size connection diameter  in. (mm) round 4 (102)
Temperature rise range  _F (_C) 45 - 75 (25 - 42) 35 - 65 (19 - 36) 45 - 75 (25 - 42)
High static certified by A.G.A./C.G.A.  in wg. (Pa) .50 (125) .65 (162) .50 (125)
Gas Piping Size I.P.S. Natural or LPG/propane 1/2 (13)
Blower wheel nominal
diameter x width
Blower motor output  hp (W) 1/2 (373) 3/4 (560) 1/2 (373) 3/4 (560)
Nominal coolin
that can be added
Shipping weight  lbs. (kg) 1 package 175 (79)
Electrical Characteristics 120 volts  60 hertz  1 phase (less than 12 amps) All models
LPG/propane kit LB-69845K (81J14)
Twinning Kit 15L38 (5 kg)
Up−Flow/Horizontal Filter and Filter Rack Kits Single (46J14) Ten Pack (66K65 No. & sizeoffilters− in. (mm)
Sidewall Power Venting Kit 79J15  25 lbs. (11 kg)
Hanging Bracket Kit LB-69957 (46J66)  15 lbs. (8 kg)
Annual Fuel Utilization Efficiency based on U.S. DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non-weatherized furnaces.Polyurethane frame type filter is furnished with kit.
in. 12 x 8 12 x 9 12 x 8 12 x 9
mm 305 x 203 305 x 229 305 x 203 305 x 229
Tons 2, 2-1/2, 3, 3-1/2 or 4 3-1/2, 4, 5 or 6 2, 2-1/2, 3, 3-1/2 or 4 3-1/2, 4, 5 or 6
kW 7.0, 8.8, 10.6, 12.3 or 14.1 12.3, 14.1, 17.6 or 21.1 7.0, 8.8, 10.6, 12.3 or 14.1 12.3, 14.1, 17.6or21.1
Optional Accessories (Must Be Ordered Extra)
82,000 (24.0)
(1) 20 x 20 x 1 (508 x 508 x 25)
98,400 (28.8)
Page 2
Page 3
BLOWER DATA
External Static
External Static
External Static
80UHG2−45, 80UHG2−60 AND 80UHG2−75 BLOWER PERFORMANCE
External Static
Pressure
in. w.g. Pa cfm L/s cfm L/s cfm L/s cfm L/s
0 0 1270 600 980 460 770 365 570 270
.05 12 1245 590 975 460 770 365 565 265
.10 25 1220 575 975 460 770 365 565 265
.15 37 1195 565 965 455 765 360 560 265
.20 50 1170 550 960 455 760 360 560 265
.25 62 1140 540 950 450 760 360 555 260
.30 75 1110 525 940 445 760 360 550 260
.40 100 1060 500 910 430 750 355 545 255
.50 125 990 465 880 415 740 350 540 255
.60 150 900 425 810 380 690 325 530 250
.70 175 800 380 740 350 630 295 520 245
NOTE  All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished) in place. Also see Filter Air Resistance table
High Medium-High Medium-Low Low
Air Volume at Various Blower Speeds
80UHG3−60 AND 80UHG3−75 BLOWER PERFORMANCE
External Static
Pressure
in. w.g. Pa cfm L/s cfm L/s cfm L/s cfm L/s
0 0 1425 670 1240 585 1000 470 800 380
.05 12 1415 670 1230 580 995 470 800 380
.10 25 1400 660 1220 575 990 465 795 375
.15 37 1385 655 1200 565 985 465 795 375
.20 50 1370 645 1180 555 980 460 790 375
.25 62 1350 635 1160 545 970 460 780 370
.30 75 1330 630 1140 540 955 450 770 365
.40 100 1280 605 1095 515 925 435 750 355
.50 125 1210 570 1040 490 900 425 720 340
.60 150 1135 535 985 465 860 405 680 320
.70 175 1070 505 920 435 800 380 630 300
NOTE  All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished) in place. Also see Filter Air Resistance table
High Medium-High Medium-Low Low
Air Volume at Various Blower Speeds
80UHG4−75, 80UHG3/4−100 AND 80UHG3/4−120 BLOWER PERFORMANCE
External Static
Pressure
in. w.g. Pa cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
0 0 1830 865 1600 755 1325 625 1070 505 880 415
.05 12 1815 855 1585 750 1320 625 1070 505 880 415
.10 25 1800 850 1570 740 1315 620 1070 505 880 415
.15 37 1875 885 1550 730 1310 620 1065 505 875 415
.20 50 1750 825 1530 720 1300 615 1060 500 875 415
.25 62 1725 815 1515 715 1290 610 1050 495 870 410
.30 75 1700 800 1500 710 1275 600 1040 490 870 410
.40 100 1650 780 1460 690 1245 590 1020 480 860 405
.50 125 1600 755 1420 670 1210 570 1000 470 840 395
.60 150 1550 730 1380 650 1170 550 980 460 820 385
.70 175 1480 700 1330 630 1130 535 960 455 790 375
NOTE  All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished) in place. Also see Filter Air Resistance table
High Medium-High Medium Medium-Low Low
Air Volume at Various Blower Speeds
Page 3
Page 4
BLOWER DATA
External Static
80UHG4/5-100 AND 80UHG4/5-120 BLOWER PERFORMANCE
External Static
Pressure
in. w.g. Pa cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
0 0 2450 1155 2160 1020 1970 930 1700 800 1500 710
.05 12 2440 1150 2155 1015 1965 925 1695 800 1500 710
.10 25 2430 1145 2150 1015 1960 925 1690 800 1495 705
.15 37 2415 1140 2135 1010 1950 920 1685 795 1495 705
.20 50 2400 1135 2120 1000 1940 915 1680 795 1490 705
.25 62 2380 1125 2105 995 1930 910 1675 790 1480 700
.30 75 2360 111 5 2090 985 1915 905 1670 790 1470 695
.40 100 2310 1090 2050 965 1870 880 1650 780 1440 680
.50 125 2260 1065 2000 945 1810 855 1610 760 1410 665
.60 150 2180 1030 1950 920 1750 825 1560 735 1370 645
.70 175 2100 990 1890 890 1700 800 1520 715 1330 630
NOTE  All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished) in place. Also see Filter Air Resistance table
High Medium-High Medium Medium-Low Low
Air Volume at Various Blower Speeds
FILTER AIR RESISTANCE
cfm (L/s) in. w.g. (Pa)
0 (0) 0.00 (0)
200 (95) 0.01 (2)
400 (185) 0.03 (7)
600 (280) 0.04 (10)
800 (375) 0.06 (15)
1000 (470) 0.09 (22)
1200 (560) 0.12 (30)
1400 (655) 0.15 (37)
1600 (750) 0.19 (47)
1800 (845) 0.23 (57)
2000 (935) 0.27 (67)
2200 (1030) 0.33 (82)
2400 (1125) 0.38 (95)
2600 (1220) 0.44 (110)
Refer to table below for manifold pressure settings for Installations at different altitudes and different fuels.
NOTE−In Canada, certification for installations over 4500 ft. (1372m) above sea level is the jurisdictionof the local authorities.
Manifold Absolute Pressure in. w.c. (kPa)
ALTITUDE ft. (m)
FUEL
NAT 3.5 (0.87) 3.4 (0.85) 3.3 (0.82) 3.2 (0.80)
LP 9.5 (2.36) 9.2 (2.29) 8.9 (2.21) 8.6 (2.14)
0−4500
(0−1372)
4500−5500
(1372−1676)
5500−6500
(1676−1981)
HIGH ALTITUDE DERATE
The combustion air inducer prove switches are factory set and are not to be adjusted. At elevations of 4500 ft. (1372m) or greater, change factory installed pressure switch to switch listed in table below.
6500−7500
(1982−2286)
Page 4
UNIT MODEL
80UHG−45 NO CHANGE
80UHG−60 NO CHANGE
80UHG−75 88J8001
80UHG−100 18L2401
80UHG−120 18L2401
PRESSURE SWITCH
PART NUMBER
Page 5
80UHG PARTS IDENTIFICATION
FLUE BOX
VENT ADAPTER
HEAT EXCHANGER
ASSEMBLY
CABINET TOP
COMBUSTION AIR
INDUCER
FRONT ACCESS
PANEL
ROLLOUT SWITCH (2)
PROVE
SWITCH
BURNER
ASSEMBLY
TRANSFORMER
CONTROL
BOARD
DOOR INTERLOCK SWITCH
SECONDARY
LIMITS
BLOWER ASSEMBLY
FIGURE 1
HEATING COMPONENTS (shown in horizontal position)
80UHG
CABINET
CABINET
BOTTOM
PRIMARY LIMIT
COMBUSTION AIR
PROVE SWITCH
MANIFOLD
BURNERS
GAS VALVE
COLLECTOR
FIGURE 2
Left
Bottom
Front
Right
HEAT EXCHANGER
COMBUSTION AIR INDUCER
Back
To p
Page 5
Page 6
80UHG BURNER ASSEMBLY (shown in upflow position)
−2 MODEL SHOWN
SURELIGHT
IGNITOR
BURNER BOX
TOP
UPPER
BURNER
MOUNTING
RAIL
LOWER
BURNER
MOUNTING
RAIL
FLAME
SENSOR
ORIFICE
MANIFOLD
ROLLOUT
SWITCHES
FIGURE 3
I−UNIT COMPONENTS (Figures 1, 2, 3)
80UHG unit components are shown in figure 1. The gas valve, combustion air inducer and burners can be ac­cessed by removing the burner access panel. Electrical components are mounted to the blower housing. 80UHG units are factory equipped with bottom return air pan­els in place. The panels are designed to be field removed as
required for bottom air return. Knockout panels are provided for side return air.
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
BURNER
VEST PANEL
HEAT EXCHANGER
GAS VALVE
BURNER BOX
PRIMARY LIMIT
Left
Front
To p
Back
Right
Bottom
1− Control Transformer (T1)
A transformer located on the blower housing provides power to the low voltage section of the unit. Transformers on all models are rated 30VA with a 120V primary and a 24V secondary.
2−Door Interlock Switch (S51)
A door interlock switch rated 16A at 125VAC is wired in se­ries with line voltage. When the blower door is removed the unit will shut down.
DANGER
CAUTION
Electrostatic discharge can affect electronic components. Take precautions during furnace installation and service to protect the furnace’s electronic controls. Precautions will help to avoid control exposure to electrostatic dis­charge by putting the furnace, the control and the technician at the same electrostatic poten­tial. Neutralize electrostatic charge by touching hand and all tools on an unpainted unit surface, such as the gas valve or blower deck, before per­forming any service procedure.
Shock hazard. Spark related components contain high voltage.
Disconnect power before servicing. Control is not field repairable. If control is inoperable, sim­ply replace entire control.
Can cause injury or death. Unsafe operation will result if repair is attempted.
Page 6
Page 7
3− Furnace Control (A3)
80UHG−2, −3 Models
80UHG−2 and −3 model units are equipped with the Len­nox SureLight ignition system. The system consists of ignition control board (figure 6 with control terminal desig­nations in table 4) and ignitor (figure 7). The board and ig­nitor work in combination to ensure furnace ignition and ignitor durability. The SureLight integrated board controls all major furnace operations. The board also features two LED lights for troubleshooting and two accessory termi­nals rated at (4) four amps. See table 3 for troubleshoot­ing diagnostic codes. Table 1 and 2 show jack plug termi­nal designations. Units equipped with the SureLight board can be used with either electronic or electro−me­chanical thermostats without modification. The SureLight ignitor is made of durable silicon−nitride. Ignitor longevity is also enhanced by voltage ramping by the control board. The board finds the lowest ignitor temperature which will successfully light the burner, thus increasing the life of the ignitor. Each time power is applied to the furnace, the Sur­eLight board performs a selfcheck including energizing the combustion air blower for a period of 1 second.
TABLE 1
SureLight BOARD J156 (J2) TERMINAL
PIN # FUNCTION
1 Combustion Air Inducer Line
2
3
4
SureLight BOARD J58 (J1) TERMINAL
PIN # FUNCTION
1 Primary Limit / Pressure Switch Out
2
3
4
5
6
7
8
9
10
11
12
DESIGNATIONS
Ignitor Line
Combustion Air Inducer Neutral
Ignitor Neutral
TABLE 2
DESIGNATIONS
Secondary Limit
24V
Not Used
Rollout Switch In
24V
Primary Limit In
Ground
Gas Valve In
Pressure Switch In
Rollout Switch Out
Gas Valve Out
a−Electronic Ignition (See Figure 5)
On a call for heat the SureLight control monitors the com­bustion air inducer pressure switch. The control will not be­gin the heating cycle if the prove switch is closed (by− passed). Once the prove switch is determined to be open, the combustion air inducer is energized. When the differ­ential in the prove switch is great enough, the prove switch closes and a 15−second pre−purge begins. If the prove switch is not proven within 2−1/2 minutes, the control goes into Watchguard−Pressure Switch mode for a 5−minute re− set period. After the 15−second pre−purge period, the SureLight igni­tor warms up for 20 seconds during which the gas valve opens at 19 seconds for a 4−second trial for ignition. The ignitor stays energized for the first second of the 4−second trial. 80UHG units equipped with control 10M9301: ignitor remains energized during the 4 second trial until flame is sensed. If ignition is not proved during the 4−second peri­od, the control will try four more times with an inter purge and warm−up time between trials of 35 seconds. After a to­tal of five trials for ignition (including the initial trial), the control goes into Watchguard−Flame Failure mode. After a 60−minute reset period, the control will begin the ignition sequence again. The SureLight control board has an added feature that prolongs the life of the ignitor. After a successful ignition, the SureLight control utilizes less power to energize the ig­nitor on successive calls for heat. The control continues to ramp down the voltage to the ignitor until it finds the lowest amount of power that will provide a successful ignition. This amount of power is used for 255 cycles. On the 256th call for heat, the control will again ramp down until the low­est power is determined and the cycle begins again.
b−Fan Time Control
The fan on time of 45 seconds is not adjustable. Fan off time (time that the blower operates after the heat demand has been satisfied) can be adjusted by flipping the dip switches located on the SureLight integrated control. The unit is shipped with a factory fan off setting of 90 seconds. Fan off time will affect comfort and is adjustable to satisfy individual applications. See figure 4.
FAN-OFF TIME ADJUSTMENT
60sec. 90sec. 120sec. 180sec.
To adjust fan−off timing, flip dip switch to desired setting.
FIGURE 4
Page 7
Page 8
The SureLight board is equipped with two LED lights for troubleshooting. The diagnostic codes are listed below in table 3.
TABLE 3
DIAGNOSTIC CODES
MAKE SURE TO ID LED’S CORRECTLY: REFER TO INSTALLATION INSTRUCTIONS FOR CONTROL BOARD LAYOUT.
LED #1 LED #2 DESCRIPTION
SIMULTANEOUS
SLOW FLASH
SIMULTANEOUS FAST
FLASH
SLOW FLASH ON
OFF SLOW FLASH
ALTERNATING SLOW
FLASH
SLOW FLASH OFF
ON SLOW FLASH
ON ON
OFF
FAST FLASH SLOW FLASH
SLOW FLASH FAST FLASH
ALTERNATING FAST
FLASH
SIMULTANEOUS
SLOW FLASH
SIMULTANEOUS FAST
ALTERNATING SLOW
ALTERNATING FAST
FLASH
FLASH
ON
OFF
ON
FLASH
Also signaled during cooling and continues fan.
Normal operation − signaled when heating demand initiated at thermostat.
Primary or Secondary limit open. Units with board 12L69: Limit must close within 5 trials for ignition or board goes into one hour limit Watchguard. Units with board
56L84: Limit must close within 3 minutes or board goes into one hour limit Watch-
Pressure switch open or has opened 5 times during a single call for heat; OR:
Blocked inlet/exhaust vent; OR: Condensate line blocked; OR: Pressure switch
closed prior to activation of combustion air blower.
Flame sensed without gas valve energized.
Rollout switch open. OR: 9 pin connector improperly attached.
Circuit board failure or control wired incorrectly.
Main power polarity reversed. Switch line and neutral.
Low flame signal. Measures below 0.2 microAmps. Replace flame sense rod.
Improper main ground or line voltage below 75 volts; OR: Broken ignitor; OR:
Power − Normal operation
guard.
Watchguard − burners fail to ignite.
Open ignitor circuit.
NOTE − Slow flash equals 1 Hz (one flash per second). Fast flash equals 3 Hz (three flashes per second). Drop out flame sense current < 0.15 microAmps
SureLight Control Ignition Sequence
(Control 56L8401 ONLY)
15
ON
OFF
DEMAND CA B
IGNITOR GAS VALVE INDOOR BLOWER
*Blower on time will be 45 seconds after ignition. Blower off time will depend on OFF TIME" Setting.
Pre −Purge Ignitor Warmup Trial for
341
35
Ignition
38
Blower On"
Delay
5 SEC80
Post
Purge
FIGURE 5
Page 8
Page 9
SURELIGHT INTEGRATED CONTROL BOARD
XFMR−N
Flame sense
COOL−H
TERMINAL DESIGNATIONS
HEAT−H EAC−H HUM−H XFMR−H LINE−H LINE−N HUM−N EAC−N XFMR−N CIR−N
PARK
(FLAME SENSE)
SURELIGHT IGNITOR
TABLE 4
Blower − Cooling Speed (120VAC) Blower − Heating Speed (120VAC) Electronic Air Cleaner (120VAC) Humidifier (120VAC) Transformer (120VAC) Input (120VAC) Input (Neutral) Humidifier (Neutral) Electronic Air Cleaner (Neutral) Transformer (Neutral) Not Used
SureLight Ignitor
FIGURE 6
4−Flame Sensor 80UHG −2 models
A flame sensor is located on the left side of the burner sup­port. See figure 8. The sensor is mounted on a bracket in the burner support and the tip protrudes into the flame en­velope of the left−most burner. The sensor is fastened to burner supports and can be removed for service without removing any part of the burners. During operation, flame is sensed by current passed through the flame and sens­ing electrode. The SureLight control allows the gas valve to remain open as long as flame signal is sensed.
NOTE − The 80UHG furnace contains electronic com­ponents that are polarity sensitive. Make sure that the furnace is wired correctly and is properly grounded.
BURNER
NORMAL FLAME SIGNAL u 0.2 MICROAMPS LOW FLAME SIGNAL v 0.2 MICROAMPS MINIMUM FLAME SIGNAL v 0.15 MICROAMPS
1/4 in. 7 mm
1/32 in. 0.79
mm
3/16 in.
4.7 mm
FLAME
SIDE VIEW END VIEW
SENSOR
11/16 in. 18 mm
1/32 in. 0.79
FIGURE 8
mm
Page 9
Page 10
5− Furnace Control (A3) 80UHG−1 Model
80UHG units are equipped with an integrated ignition/blower control (EGC-2) which controls ignition, safety circuits, blower operation, fan off timing, and allows for thermostat connection and troubleshooting. The EGC-2 is a printed circuit board which is divided into two sections, 120 and 24VAC. Line voltage comes into the board on the 120VAC side. See figure 10. Terminal designations are listed in tables 6 and 7.
Ignition Control
80UHG units use the EGC−2 direct spark integrated ignition control. The EGC−2 controls and monitors the entire sequence of operation. On a call for heat from the thermostat the control monitors the combustion air in­ducer prove switch. The control will not begin the heat­ing cycle if the prove switch is closed (by-passed). Once the prove switch is determined to be open, the combustion air inducer is energized. When the differential in pressure across the prove switch is great enough, the prove switch closes and a 15 second pre-purge period begins. If the prove switch does not close within 2 1/2 minutes, the con­trol goes into 5 minute watchguard. After the pre-purge pe­riod, the gas valve will open and ignition (spark) will be at­tempted for 10 seconds. After ignition, the control initiates a ten second flame stabilization period. The flame stabi­lization period allows the burners to heat up and the flame to stabilize. Once flame is established, the control will constantly monitor the burner flame using flame rectification. Flame failure response time is 0.8 seconds.
If the initial attempt for ignition fails, the sequence is re­peated up to five times. After the fifth trial, the control goes into Watchguard"*. During watchguard mode, the entire unit will be de-energized for one hour. After one hour the control will repeat the ignition sequence. Watchguard may be manually reset by breaking and remaking thermostat demand.
*NOTE−If flame is established beyond the 10 second flame stabilization period then lost, the control resets for five more ignition trials. The control can be reset five times during one unsatisfied thermostat demand, providing a maximum of 25 trials for ignition.
Safety Circuits
During the entire heating demand the control monitors the safety circuits. If the primary or secondary heating limits open, the control de-energizes the main gas valve and combustion air blower while the indoor blower remains en­ergized. When the limit automatically resets, the ignition se­quence also resets. If either of the limits trip five consecu­tive times during one unsatisfied thermostat demand, the control will go into watchguard for one hour.
The control monitors main valve voltage. If voltage is sensed
when no voltage should be present, the control de-energizes the combustion air inducer which terminates voltage to the valve. The system goes into hard lock-out which is reset only by removing power to the unit.
If flame is sensed when no flame should be present, the con­trol will energize the combustion and indoor blowers. The unit will remain locked in this sequence until the flame is no longer sensed or the main power is turned off to reset the control.
The roll-out circuit is also monitored by the EGC-2 control. If the switch opens, the control will de-energize the gas valve, combustion air inducer, and indoor blower. The unit will remain de-energized until the switch is manual­ly reset.
DANGER
Shock hazard. Avoid personal injury. Make sure to disconnect power before changing fan off" timing.
Blower Operation / Fan Off Timings
Fan off" timing (time that the blower operates after the heat demand has been satisfied) can be adjusted by moving the jumper on the EGC-2 blower control board. Figure 9 shows the various fan off" timings and how jumper should be posi­tioned. To adjust fan off " timing, gently disconnect jumper and reposition across pins corresponding with new timing. Unit is shipped with a factory fan off" setting of 180 seconds. Fan on" time is factory set at 45 seconds following the opening of the main gas valve and is not adjustable.
Fan off" time will affect comfort and efficiency and is ad­justable to satisfy individual applications. The fan off" tim­ing is initiated after a heating demand but not after a cool­ing demand.
NOTEIf fan off" time is set too low, residual heat in heat exchanger may cause primary limit S10 to trip, re­sulting in frequent cycling of blower. If this occurs, adjust blower to longer fan off" time setting.
FAN-OFF TIME ADJUSTMENT
TIMING
JUMPER
180
120 90
60
FIGURE 9
To adjust fan-off timing:
Remove jumper from EGC-2 and select
one of the other pin combinations to
achieve the desired time.
TIMING PINS
(seconds)
Leave jumper off for
240 second fan-off timing.
Page 10
Page 11
Thermostat Connection
Thermostat wires are connected to the terminal strip found on the EGC-2 control board.
Troubleshooting
The EGC-2 control board is equipped with two diagnostic green LEDs to indicate the mode of failure. The LED lights are marked DIAG #1 and DIAG #2. The codes are given in table 5.
A slotted edge connector is also provided for the Lennox Diagnostic Module (part number 11K75). See figure 10. When connected to the EGC-2 control board, the module dis­plays (in words) the diagnostic condition.
80UHG−1 MODEL INTEGRATED CONTROL (EGC−2)
(Shown as installed in horizontal left hand application)
(See tables 6 and 3 for terminal designations)
TABLE 5
EGC-2 DIAGNOSTIC CODES
DIAG #2 DIAG #1 DIagnostic Condition
Simultaneous
Flash
On Flash
Flash Off
Alternate
Flash
Off Flash
Flash On
Continuous
On
Simultaneous
Flash
Alternate Flash
Continuous On
Power ON". Normal Operation. In-
creased flash rate indicates there
is a heating demand.
Primary or Secondary
Limit Switch Open.
Auto-Reset Switch.
Pressure Switch Watchguard,
pressure switch opened during
Circuit board self-check failure or
operation.
Watchguard, burners
failed to ignite.
Flame sensed without
valve energized.
Roll-out Switch Open. Manual-Reset Switch.
ignition/blower control
is wired incorrectly.
DIAGNOSTIC MODULE
DIAGNOSTIC LEDS
BLOWER TIME
ADJUSTMENT
JUMPER
THERMOSTAT
TERMINAL STRIP
(DETACHABLE)
EDGE
CONNECTION
8 9 10 11 12 13 15
7
6
5
4
1
7
2
8
5
14
PLUG P20
24VAC
346
9
DIAGNOSTIC CODE ERASE JUMPER
(Remove power to control and short pins for
10 seconds to erase previous code.)
FIGURE 10
Page 11
123
Page 12
TABLE 6
BLOWER CONTROL A15 TERMINAL DESIGNATIONS
Ter mi na l Designation (See fig. 10)
R Screw Strip 24VAC to Thermostat (Red)
G Screw Strip
W Screw Strip
Y Screw Strip
C Screw Strip Common Ground to Thermostat
1 1/4" Spade 24VAC Hot from Transformer 2 1/4" Spade 24VAC Return to Transformer 3 1/4" Spade 24VAC Ground
4, 5, 6 1/4" Spade 120VAC Return − 120VAC Common
7 1/4" Spade
8 1/4" Spade Combustion Blower (Line Voltage)
9 1/4" Spade Heat Only Accessory (Line Voltage) 10 1/4" Spade 120VAC Hot to Transformer 11 1/4" Spade 120VAC Hot Input
12, 13 1/4" Spade Accessories (Line Voltage)
14 1/4" Spade ACB Cool Speed (Line Voltage) 15 1/4" Spade ACB Heat Speed (Line Voltage)
Type Function
Manual Fan Input from Thermostat
Heat Demand Input from Thermostat
Cool Demand Input from Thermostat
120VAC Return − 120VAC Common
(Green)
(White)
(Yellow)
Input
TABLE 7
EGC-2 CONTROL JACK/PLUG 20 TERMINAL DESIGNATIONS
Pin # Function
1 Rollout Switch Out 2 Spare 3 Gas Valve Common 4 Pressure Switch Return 5 Hi Limit Return / Pressure Switch Out 6 Flame Sensor 7 Gas Valve Out 8 High Limit Out 9 Rollout Switch Return
6−Blower Motors and Capacitors
All 80UHG units use direct drive blower motors. All motors used are 120V permanent split capacitor motors to ensure maximum efficiency. See table 8 for ratings.
80UHG BLOWER RATINGS 120V 1PH
BLOWER MOTOR
80UHG2 80UHG3 80UHG3/4 80UHG4 80UHG4/5 80UHG5/6
TABLE 8
HP 1/4 5MFD 370V 1/3 1/2 1/2 7.5MFD 370V 3/4 40MFD 370V 3/4 40MFD 370V
CAP
5MFD 370V
7.5MFD 370V
SUPPLY AIR BLOWER
AND SECONDARY LIMITS
MOTOR
CAPACITOR
To Remove Blower From Unit: Remove Bolts and
Wiring Jackplugs. Then Slide Out Front of Unit.
SECONDARY
LIMITS (S21)
Left
Front
Bottom
To p
BLOWER
MOTOR
Back
Right
FIGURE 11
7−Combustion Air Inducer (B6)
All 80UHG units use a combustion air inducer to move air through the burners and heat exchanger during heating operation. The blower uses a 120VAC motor. The motor operates during all heating operation and is controlled by furnace control A3. The blower also operates for 15 sec­onds before burner ignition (pre-purge) and for 5 seconds after the gas valve closes (post-purge)
A proving switch connected to the combustion air inducer housing is used to prove combustion air inducer operation. The switch monitors air pressure in the blower housing. Dur­ing normal operation, the pressure in the housing is nega­tive. If pressure becomes less negative (signifying an ob­struction) the prove switch opens. When the prove switch opens, the furnace control (A3) immediately closes the gas valve to prevent burner operation.
8−Flame Rollout Switches (S47)
Flame rollout switch is a high temperature limit located on top of the burner box. Each furnace is equipped with two identical switches. One switch is located over the leftmost burner and the other switch is located over the rightmost burner. The limit is a N.C. SPST manual-reset limit con­nected in series with the ignition control A3. When S47
Page 12
Page 13
senses rollout, the ignition control immediately stops igni­tion and closes the gas valve. If unit is running and flame rollout is detected, the gas valve will close and ignition con­trol will be disabled. Rollout can be caused by a blocked flue or lack of combustion air. The switch is factory set and cannot be adjusted. The setpoint will be printed on the side of the limit. The switch can be manually reset. To manually re­set a tripped switch, push the reset button located on the control.
ROLLOUT SWITCH (S47)
MANUAL
RESET BUTTON
FIGURE 12
9−Primary Limit Control (S10)
LIMIT CONTROL FOR
80UHG SERIES UNITS
THIS TYPE AUTO-RESET LIMIT
IS USED FOR THE PRIMARY LIMIT (S10) AND
RIGHT SECONDARY LIMIT (S21)
(see FIGURE 11)
FIGURE 13
The primary limit (S10) on 80UHG units is located in the middle of the heating vestibule panel. When excess heat is sensed in the heat exchanger, the limit will open. If the limit is tripped, the furnace control energizes the supply air blower and closes the gas valve. The limit automatically resets when unit temperature returns to normal. The switch is factory set and cannot be adjusted. The switch may have a different setpoint for each unit model number. However, the setpoint will be printed on the side of the limit.
10−Secondary Limit Controls (S21)
The secondary limit (S21) on 80UHG units is located in the blower compartment in the back side of the blower housing. When excess heat is sensed in the blower compartment, the limit will open. If the limit is tripped, the furnace control ener­gizes the supply air blower and closes the gas valve. The limit automatically resets when unit temperature returns to normal. The switch is factory set and cannot be adjusted. The set­point will be printed on the limit.
Two limits are supplied in each furnace. 80UHG3, 80UHG4 and 80UHG4/5 model units built prior to Apri 1999, will have one each of style shown in figures 13 and 14. If stick limit (figure 14) suffers frm nuisance trips on the above model units and the furnace is in the horizontal position, re­place with limit kit no. 50L98. All 80UHG2 model units will have one of each style shown in figures 13 and 14.
SECONDARY LIMIT CONTROL (S21)
INSULATING COVER
LIMIT
FOR 80UHG SERIES UNITS
THIS TYPE AUTO-RESET LIMIT IS
SPADE CONNECTORS
USED FOR THE LEFT SECONDARY
LIMIT (S21) (see FIGURE 11)
INSULATING COVER (s)
LIMIT
FIGURE 14
11−Spark Electrode and Flame Sensor
80UHG−1 Models
Figure 17 shows the arrangement of flame sensor, spark electrode and burners. The ignition control uses direct spark to ignite the rightmost burner and the burners cross­light to the left. The flame sensor uses flame rectification to sense combustion. A flame retention ring in the end of each burner is used to maintain correct flame length and shape and to keep the flame from lifting off the burner head. Figure 18 shows the gap between tip of the electrodes and the burner surface, and the gap between the sensor and burner surface.
12−Gas Valve
The 80UHG uses a gas valve manufactured by Honey­well or White Rodgers. The valve is internally redundant to assure safety shut−off. If the gas valve must be replaced, the same type valve must be used. 24VAC terminals and gas control knob are located on top of the valve. All terminals on the gas valve are connected to wires from the electronic ignition control. 24V applied to the terminals energizes the valve. Inlet and outlet pressure taps are located on the valve. A regu­lator adjustment screw (figures 15 and 16) is located on the valve. LPG changeover kits are available from Lennox. Kit s include burner orifices and a gas valve regulator conversion kit.
Page 13
Page 14
WHITE RODGERS 36E SERIES GAS VALVE
MANIFOLD
PRESSURE
ADJUSTMENT
SCREW
HONEYWELL VR8205 SERIES GAS VALVE
MANIFOLD
PRESSURE
ADJUSTMENT
SCREW
MANIFOLD
PRESSURE
OUTLET
GAS VALVE SHOWN IN OFF POSITION
FIGURE 15
TYPICAL BURNER/ELECTRODE ORIENTATION
1/8"(+1/64")
SPARK ELECTRODE
UPPER BURNER MOUNTING RAIL
GROUND
SPARK ELECTRODE TO BURNER GAP
80UHG−1 MODEL SHOWN
BURNER
SPARK
ELEC-
TRODE
SPARK ELECTRODE
FLAME SENSOR TO BURNER GAP
BURNER
MANIFOLD
PRESSURE
OUTLET
80UHG−1 MODEL SHOWN
BURNER
FLAME RETENTION RING
FIGURE 17
5/16 in.
(7 mm)
5/16 in.
(7 mm)
ON
OFF
GAS VALVE SHOWN IN OFF POSITION
FIGURE 16
To p
Right Left
Bottom
MANIFOLD ORIFICE
LOWER BURNER
MOUNTING RAIL
23/32 in. (18 mm)
FLAME SENSOR
13−Combustion Air Blower Prove
Switch (S18)
80UHG series units are equipped with a combustion air prove switch located on the vestibule panel. The switch is connected to the combustion air inducer housing by means of a flexible silicone hose. It monitors air pressure in the combustion air blower housing.
The switch is a single-pole single-throw pressure switch electrically connected to the furnace control. The purpose of the switch is to prevent burner operation if the combus­tion air blower is not operating or if the flue becomes ob­structed.
FLAME SENSOR
FIGURE 18
Page 14
Page 15
COMBUSTION AIR INDUCER
PROVE SWITCH
Normally Open
Closes on Negative Pressure
Sensing Tube
Attaches to Top
Side Of Blower
To p
PROVE
SWITCH
Back
Left
Right
Front
Bottom
FIGURE 19
On start-up, the switch senses that the combustion air blower is operating. It closes a circuit to the furnace control when pressure inside the combustion air blower de­creases to a certain set point. Set points vary depending on unit size. The pressure sensed by the switch is relative to atmospheric pressure. If the flue becomes obstructed during operation, the switch senses a loss of negative pressure (pressure becomes more equal with atmospher­ic pressure) and opens the circuit to the furnace control and gas valve. A bleed port on the switch allows dry relativ­ity air in the vestibule to purge switch tubing, to prevent condensate build up. The switch also has an internal inline orifice, designed to prevent nuisance shut downs due to erratic vent pressure fluctuations. The switch is factory set and is not field adjustable. It is a safety shut-down control in the furnace and must not be by−passed for any reason. If switch is closed or by−passed, the control will not initiate ignition at start up.
II−PLACEMENT AND INSTALLATION
PROVE SWITCH
Make sure unit is installed in accordance with installation instructions and applicable codes.
III−START-UP A−Preliminary and Seasonal Checks
1 − Inspect electrical wiring, both field and factory installed
for loose connections. Tighten as required.
2 − Check voltage at disconnect switch. Voltage must be
within range listed on the nameplate. If not, consult the power company and have voltage condition corrected before starting unit.
B−Heating Start-Up
WARNING
Shock and burn hazard.
80UHG−1 units are equipped with a direct spark igni­tion system. Do not attempt to light manually.
1 − STOP! Read the safety information at the beginning
of this section.
2 − Set thermostat to lowest setting. 3 − Turn off all electrical power to appliance. 4 − This appliance is equipped with an ignition device
which automatically lights the burners. Do not try to
light the burners by hand. 5 − Remove top access panel. 6 − White Rodgers 36E Gas Valve −− Switch lever to
OFF. See figure 15.
Honeywell VR8205 Gas Valve −− Turn knob on gas
valve clockwise to OFF. Do not force. See fig-
ure 16. 7 − Wait five (5) minutes to clear out any gas. If you then
smell gas, STOP! Close manual main shut−off valve to
the furnace. Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instructions.
If you do not smell gas go to next step. 8 − White Rodgers 36E Gas Valve −− Switch gas valve lever
to ON.
Honeywell VR8205 Gas Valve −− Turn knob on gas
valve counterclockwise to ON. Do not force. 9 − Replace access panel.
10− Turn on all electrical power to unit. 11− Set thermostat to desired setting.
NOTE−When unit is initially started, steps 1 through 11 may need to be repeated to purge air from pilot line.
12− If the appliance will not operate, follow the instructions
To Turn Off Gas To Unit".
Turning Off Gas To Unit
1 − Set thermostat to lowest setting. 2 − Turn off all electrical power to unit if service is to be
performed. 3 − Remove access panel.
4 − Switch lever on White Rodgers gas valve to OFF; turn
knob on Honeywell valve clockwise to OFF. Do not
force. 5 − Replace access panel.
C−Safety or Emergency Shutdown
Turn off unit power. Close manual and main gas valves.
D−Extended Period Shutdown
Turn off thermostat or set to UNOCCUPIED" mode. Close all gas valves (both internal and external to unit) to guaran­tee no gas leak into combustion chamber. Turn off power to unit. All access panels, covers and vent caps must be in place and secured.
Page 15
Page 16
IV−HEATING SYSTEM SERVICE CHECKS
A−A.G.A./C.G.A. Certification
All units are A.G.A. and or C.G.A. design certified without modifications. Refer to the 80UHG Operation and Installa­tion Instruction Manual Information.
B−Gas Piping
Gas supply piping should not allow more than 0.5"W.C. drop in pressure between gas meter and unit. Supply gas pipe must not be smaller than unit gas connection.
Compounds used on gas piping threaded joints should be resistant to action of liquefied petroleum gases.
C−Testing Gas Piping
IMPORTANT
In case emergency shutdown is required, turn off the main shut-off valve and disconnect the main power to unit. These controls should be properly labeled by the installer.
When pressure testing gas lines, the gas valve must be disconnected and isolated. Gas valves can be damaged if subjected to more than 0.5psig (14" W.C.). See figure 20. If the pressure is equal to or less than 0.5psig (14"W.C.), use the manual shut−off valve before pressure testing to iso­late furnace from gas supply.
GAS PIPING TEST PROCEDURE
MANUAL MAIN SHUT−OFF VALVE
WILL NOT HOLD TEST PRESSURE
IN EXCESS OF 0.5 PSIG (14"W.C.)
through Lennox under part number 31B2001. See Corp. 8411−L10, for further details.
Do not use matches, candles, flame or any other source of ignition to check for gas leaks.
D−Testing Gas Supply Pressure
When testing supply gas pressure, connect test gauge to inlet pressure tap (field provided). See figure 20. Check gas line pressure with unit firing at maximum rate. Low pressure may result in erratic operation or underfire. High pressure can result in permanent damage to gas valve or overfire. For 80UHG−45,60 and 75 BTUH natural gas units, operating pressure at the unit must be a minimum
4.5"W.C. For the 80UHG−100 and 120 BTUH units, the op­erating pressure must be a minimum of 5.0"W.C. For L.P. gas units, operating pressure at unit gas connection must be a minimum of 11.0" W.C.
On multiple unit installations, each unit should be checked separately, with and without other units operating. Supply pressure must fall within range listed in previous para­graph.
E−Check Manifold Pressure
After line pressure has been checked and adjusted, check manifold pressure. Move pressure gauge to outlet pres­sure tap located on unit gas valve (GV1). Checks of man­ifold pressure are made as verification of proper regulator adjustment. Manifold pressure for the 80UHG can be mea­sured at any time the gas valve is open and is supplying gas to the unit. Normal manifold pressure for natural gas units is
3.5 in. W.C. For LP/propane gas the correct manifold pres­sure is 9.5 in. W.C.
IMPORTANT
GAS VALVE
FIELD PROVIDED
LINE PRESSURE
FIGURE 20
When checking piping connections for gas leaks, use pre­ferred means. Kitchen detergents can cause harmful corro­sion on various metals used in gas piping. Use of a specialty Gas Leak Detector is strongly recommended. It is available
CAP
TAP
Page 16
For safety, connect a shut-off valve between the manometer and the gas tap to permit shut off of gas pressure to the manometer.
Unit (Fuel)
GAS VALVE REGULATION
L.P. 9.5 + 0.5
The gas valve is factory set and should not require adjust­ment. All gas valves are factory regulated. See table 9. See specifications section of this manual for High Altitude manifold pressure settings.
TABLE 9
Operating Pressure (outlet) in. W.C.
3.5 +0 −0.3Natural
Page 17
Manifold Adjustment Procedure:
1 − Connect a test gauge to outlet pressure tap on gas
valve. Start unit and allow 5 minutes for unit to reach steady state.
2 − While waiting for the unit to stabilize, notice the flame.
Flame should be stable and should not lift from burner. Natural gas should burn blue. L.P. gas should burn mostly blue with some orange streaks.
3 − After allowing unit to stabilize for 5 minutes, record
manifold pressure and compare to values given in table 9.
NOTE−Shut unit off and remove manometer as soon as an accurate reading has been obtained. Take care to replace pressure tap plug.
F− Proper Gas Flow (Approximate)
Furnace should operate at least 5 minutes before check­ing gas flow. Determine time in seconds for two revolu­tions of gas through the meter. (Two revolutions assures a more accurate time.) Divide by two and compare to time in table 10 below. Adjust manifold pressure on gas valve to match time needed.
NOTE− To obtain accurate reading, shut off all other gas appliances connected to meter.
TABLE 10
GAS METER CLOCKING CHART
Seconds for One Revolution
80UHG
Unit
−45 80 160 200 400
−60 60 120 150 300
−100 36 72 90 180
−120 30 60 75 150
Natural−1000 btu/cu ft LP−2500 btu/cu ft
Natural LP
1 cu ft
Dial
2 cu ft
Dial
1 cu ft
Dial
2 cu ft
DIAL
To Measure Flame Signal − Ignition Control:
A transducer (Part #78H5401 available from Lennox Repair Parts) is
TRANSDUCER
(PART #78H5401)
required to measure flame signal if meter used will not read a low micro amp signal. Seefig­ure21. The transducer
FIGURE 21
converts microamps to volts on a 1:1 conversion. Flame sig­nal should for the EGC control should be 1.0 − 5.0 with a lock− out signal of .45 nominal microamps, therefore a reading of
1.0 − 5.0 nominal volts should be read on the meter. Flame signal for the SureLight control should read 0.7 microamps with a lockout signal of .15 microamps. A digital readout meter must be used. The transducer plugs into most meters. See figure 22 for proper use of transducer.
1 − Set the volt meter to the DC voltage scale. Insert
transducer into the VDC and common inputs. Ob­serve correct polarities. Failure to do so results in
negative (−) values. 2 − Turn off supply voltage to control. 3 − Disconnect ignition control flame sensor wire from the
flame sensor. 4 − Connect (−) lead of the transducer to flame sensor. 5 − Connect (+) lead of transducer to the ignition control sen-
sor wire. 6 − Turn supply voltage on and close thermostat contacts to
cycle system. 7 − When main burners are in operation for two minutes, take
reading. Remember 1 DC volt = 1 DC microamp.
NOTE−MUST USE DIGITAL METER
IMPORTANT
For safety, shut unit off and remove manometer as soon as an accurate reading has been obtained. Take care to replace pressure tap plug.
G−Flame Signal
A microamp DC meter is needed to check the flame signal on the ignition control.
Flame (microamp) signal is an electrical current which passes from the furnace control through the sensor during unit opera­tion. Current passes from the sensor through the flame to ground to complete a safety circuit.
Page 17
(+) TO
IGNITION
CONTROL
SENSOR
WIRE
SET DIAL TO MEASURE VDC
RED COLLAR
(+)
(−)
(−) TO
FLAME SENSOR
INDICATES
POSITIVE
FIGURE 22
LEAD
Page 18
WARNING
Fire and explosion hazard. These instructions MUST be followed exactly. Can cause a fire or explosion resulting in property
damage, personal injury or loss of life.
V−TYPICAL OPERATING CHARACTERISTICS A−Blower Operation and Adjustment
NOTE− The following is a generalized procedure and does not apply to all thermostat controls.
1 − Blower operation is dependent on thermostat control
system.
2 − Generally, blower operation is set at thermostat sub-
base fan switch. With fan switch in ON position, blower operates continuously on heating speed. With fan switch in AUTO position, blower cycles with demand or runs continuously while heating or cooling circuit cycles.
3 − Depending on the type of indoor thermostat, blower
and entire unit will be off when the system switch is in OFF position.
B−Temperature Rise
Temperature rise for 80UHG units depends on unit input, blower speed, blower horsepower and static pressure as marked on the unit rating plate. The blower speed must be set for unit operation within the range of AIR TEMP. RISE °F" listed on the unit rating plate.
To Measure Temperature Rise:
1 − Place plenum thermometers in the supply and return
air plenums. Locate supply air thermometer in the first horizontal run of the plenum where it will not pick up ra-
diant heat from the heat exchanger. 2 − Set thermostat to highest setting. 3 − After plenum thermometers have reached their high-
est and steadiest readings, subtract the two readings.
The difference should be in the range listed on the unit
rating plate. If the temperature is too low, decrease
blower speed. If temperature is too high, first check
the firing rate. Provided the firing rate is acceptable, in-
crease blower speed to reduce temperature. To
change blower speed taps see the Blower Speed Taps
section in this manual.
C−External Static Pressure
1 − Tap locations shown in figure 23. 2 − Punch a 1/4" diameter hole
in supply and return air ple­nums. Insert manometer hose flush with inside edge of hole or insulation. Seal around the hose with per­magum. Connect the zero end of the manometer to the discharge (supply) side of the system. On ducted sys­tems, connect the other end of manometer to the re­turn duct as above. For systems with non−ducted re­turns, leave the other end of the manometer open to the atmosphere.
3 − With only the blower motor running and the evaporator
coil dry, observe the manometer reading. Adjust blow­er motor speed to deliver the air desired according to the job requirements.
4 − External static pressure drop must not be more than
0.5" W.C.
5 − Seal around the hole when the check is complete.
STATIC PRESSURE
TEST
MANOMETER
80UHG UNIT
FIGURE 23
D−Blower Speed Taps Leadless Motors
80UHG−1 Models
Blower speed tap selection is accomplished by changing the taps at the blower motor harness connector. Disconnect har­ness connector from motor to expose speed selectors. Blower speed selections are listed in table 11. To Change Blower Speed: 1 − Turn off electric power to furnace. 2 − Remove blower access door.
Disconnect blower motor harness from motor.
3 − Select desired speeds for heating and cooling. (Red =
heating, Black = cooling, White = common).
4 − Depress harness connector tab to release wire termi-
nal. Select connector location for new speed (refer to unit wiring diagram). Insert wire terminal until it is se­curely in place. See figure 24.
5 − Replace harness connector to motor.
TABLE 11
Page 18
Page 19
BLOWER SPEED TAP SELEC-
TION
Leaded Motors
DEPRESS TAB TO RELEASE WIRE TERMINAL. SELECT CONNECTOR LOCATION FOR NEW SPEED (REFER TO UNIT WIRING DIAGRAM). IN­SERT WIRE UNTIL IT IS SE­CURELY IN PLACE.
HARNESS
CONNECTOR
MOTOR
FIGURE 24
E−Blower Speed Taps Leaded Motors
80UHG−2 Models
Blower speed tap changes are made on the SureLight control board. See figure 6. Unused taps must be secured on two dummy terminals labeled "PARK on the SureLight board. The heating tap is connected to the "HEAT−H " ter­minal and the cooling tap is connected to the "COOL−H" terminal. The continuous blower tap is the same as the heating tap. To change existing heat tap, turn off power then switch out speed tap on "HEAT−H" with tap connected to "PARK" . See table 12 for blower motor tap colors for each speed.
TABLE 12
VI−MAINTENANCE
At the beginning of each heating season, the system should be checked as follows:
A−Filters
Return air filter is not supplied with unit. See Optional Ac­cessaries section in this manual for filter and rack size. A filter must be used in order to ensure long life and proper operation. The filter is located in the return air duct or return air register. Filters must be cleaned or replaced when dirty to assure proper unit operation.
B− Heat Exchanger and Burners
Due to dimples designed in the heat exchanger, cleaning is not recommended. Removal is for inspection only.
NOTE−Use papers or protective covering in front of fur­nace while cleaning furnace.
To clean burners:
1 − Remove screws holding upper burner mounting rail (fig-
ure 17). Remove rail.
2 − Slide burners off each orifice pull burners from heat ex-
changer.
3 − Clean holes in burner head (retention ring) with a wire
brush. See figure 17.
4 − With a shop vacuum or rags, clean out soot and scale
deposits from burners.
5 − Remove screws securing flue box to vestibule panel.
Remove flue box from unit. Leave combustion air blower attached to flue box.
6 − With a shop vacuum or rags, clean out soot and scale
deposits from heat exchanger tubes and flue box. If tur­bulators are removed (figure 1) make sure they are re­installed before reassembling units.
7 − Inspect heat exchanger for corrosion damage, holes or
cracks.
8 − Replace burners making sure to fully engage on orifice.
Resecure burner mounting rail and flue box. Inspect flue box gasket. Replace gasket if necessary.
9 − Slide heat exchanger into cabinet and re-secure heat
exchanger screws.
10 − Reinstall filler piece making sure that there is a good
seal between the cabinet sides, blower and deck and filler piece. Use silicon caulking to fill in any potential
gaps. 11 − Re-secure flue pipe, gas piping and access panels. 12 − Carefully check all piping connections (factory and
field) for gas leaks. Use a leak detecting solution or oth-
er preferred means. 12 − Turn on gas and electrical supply.
Page 19
Page 20
HEAT EXCHANGER REMOVAL (unit shown in horizontal position)
REMOVE SCREWS (4)
SLIDE ENTIRE ASSEMBLY OUT OF CABINET
FIGURE 25
CAUTION
Potential for gas leaks, fire or explosion. Some soaps used for leak detection are corrosive to certain metals. Carefully clean piping thor­oughly after leak detection has been completed. Can cause damage to piping resulting in gas leaks, fire or explosion.
C−Supply Air Blower
1 − Check and clean blower wheel. 2 − Motors used on the Lennox 80UHG series units are
permanently lubricated and need no further lu­brication.
Left
Back
Bottom
Front
Right
To p
D−Flue and Chimney
Flue must conform to all AGA/GAMA venting require­ments. Flue pipe deteriorates from the inside out and must be disconnected in order to check thoroughly. Check flue pipe, chimney and all connections for tightness and to make sure there is no blockage or leaks.
E−Electrical
1 − Check all wiring for loose connections. 2 − Check for correct voltage. 3 − Check amp−draw on blower motor.
Page 20
Page 21
VII− Wiring and Sequence of Operation
80UHG−1 MODEL WITH EGC CONTROL (SEE FLOW CHARTS ON THE FOLLOWING TWO PAGES):
1 − When disconnect is closed, 120V is routed through door
interlock switch (S51) to feed the line voltage side of the ignition control (A3) and transformer T1 primary. Door in­terlock switch must be closed for A3 and T1 to receive voltage.
2 − T1 supplies 24VAC to terminal 24VAC" on A3. In turn,
terminal R" of A3 supplies 24VAC to terminal R" of the indoor thermostat (not shown).
3 − When there is a call for heat, W1 of the thermostat en-
ergizes W of the ignition control with 24VAC.
4 − CAB of the ignition control energizes the combustion air
inducer (B6). When the combustion air inducer nears full speed, combustion air prove switch (S18) closes. Switch must close within 2 1/2 minutes or control goes into 5 minute Watchguard Pressure Switch delay.
5 − When S18 closes, assuming primary limit (S10) and
secondary limit (S21) are closed, a 15 second pre−purge begins. After the pre−purge period the ignition control starts ignition spark and opens main gas valve.
6 − After 45 seconds, ignition control (A3) energizes the
indoor blower (B3).
7 − When heat demand is satisfied, W1 of the thermostat de-
energizes W of the ignition control and the gas valve is immediately de-energized. The combustion air inducer immediately stops. The indoor blower runs for a desig­nated fan off" period (60−240 seconds) as set by jumper on ignition control.
Page 21
Page 22
80UHG−1 HEATING SEQUENCE OF OPERATION
NORMAL HEATING MODE
CONTROL MAIN POWER ON"
FLAME OFF?
YES
CONTROL SELF−CHECK OKAY?
YES
ROLL−OUT SWITCH CLOSED
YES
LED: SLOW FLASH RATE
THERMOSTAT CALLS FOR HEAT
LED: FAST FLASH RATE
COMB. AIR INDUCER PRESSURE SWITCH OPEN?
YES
COMBUSTION AIR INDUCER ON?
HTG ACC. TERM. ENERGIZED?
YES
PRESSURE SWITCH CLOSED WITHIN 2.5 MIN.?
YES
COMB. AIR INDUCER PREPURGE (15 seconds)
IGNITION TRIAL (10 seconds) −− START IGNITION
SPARK, OPEN MAIN GAS VALVE.
NO
NO
NO
NO
NO
ABNORMAL HEATING MODE
GAS VALVE OFF. COMB. INDUCER ON. INDOOR
BLOWER ON HEAT SPEED. SEQUENCE HOLDS UNTIL
NO FLAME SENSED OR MAIN POWER IS INTERRUPTED
AND RESET. DIAG. CODE: 1− FLASHING; 2−OFF
(FLAME SENSED WITHOUT VALVE ENERGIZED)
GAS VALVE, COMB. INDUCER AND INDOOR BLOWER
(WITH DELAY) OFF. REMOVE POWER TO RESET
CONTROL. DIAG. CODE: BOTH ON (CONTROL
SELF−CHECK FAILURE OR INCORRECT WIRING)
GAS VALVE, COMB. BLOWER AND INDOOR BLOWER
(WITH DELAY) OFF. SEQUENCE HOLDS UNTIL
ROLL−OUT SWITCH IS MANUALLY CLOSED.
2−FLASHING (FLAME ROLL−OUT OPEN)
GAS VALVE, COMB. INDUCER AND INDOOR BLOWER
(WITH DELAY) OFF. SEQUENCE HOLDS UNTIL
PRESSURE SWITCH CLOSES OR THERMOSTAT
RESETS CONTROL. DIAG. CODE: 1−OFF;
2−FLASHING (C.A.B. PRESSURE SWITCH OPEN)
YES
PRESSURE SWITCH WATCHGUARD CONDITION:
GAS VALVE, COMB. INDUCER AND INDOOR BLOWER
(WITH DELAY) OFF. DIAG. CODE: 1−OFF /
2−FLASHING (C.A.B. PRESSURE SWITCH OPEN) IS 5
MINUTE RESET PERIOD COMPLETE?
DIAG. CODE: 1−ON;
HAS FLAME REGISTERED WITHIN 10 SECONDS
AFTER IGNITION TRIAL?
YES
IS FLAME SENSED AFTER 10 SECOND
FLAME RECTIFICATION PERIOD?
YES
INDOOR AIR BLOWER ON.
(Fixed 45−second delay)
PRIMARY/SECONDARY LIMITS MONITORED IN
HEAT CYCLE. ARE SWITCHES CLOSED?
YES
PRESSURE SWITCH CLOSED?
YES
THERMOSTAT OPENS
LED: SLOW FLASH RATE
COMB. AIR INDUCER OFF (5 sec. delay)
HTG ACC. TERM. DE−ENERGIZED.
INDOOR AIR BLOWER OFF (After selected 60, 90,
120, 180, or 240 delay)?
NO
NO
NO
NO
GAS VALVE OFF. COMB. INDUCER ON. INDOOR
BLOWER (WITH 45 DELAY) ON. HAS CONTROL FAILED
FLAME SENSE 5 TIMES DURING ONE HEAT DEMAND?
IF YES, SYSTEM GOES INTO 60 MIN.WATCHGUARD.
DIAG. CODE: 1−ALT. FLASHING / 2−ALT. FLASHING IF
NO, GO TO COMB. AIR BLOWER ON?"
HAS CONTROL RESET IGNITION SEQUENCE 5 TIMES
IF YES, SYSTEM GOES INTO 60 MIN. WATCHGUARD. DIAG. CODE: 1−ALT. FLASHING / 2−ALT. FLASHING IF
NO, GO TO COMB. AIR BLOWER ON?"
GAS VALVE OFF. COMB. INDUCER OFF. INDOOR
BLOWER ON UNTIL LIMIT CLOSES. DIAG.
CODE: 1−FLASHING / 2−ON (LIMIT OPEN)
IS LIMIT NOW CLOSED?
YES
HAS PRIMARY LIMIT OPENED 5 TIMES DURING
ONE UNSATISFIED HEAT DEMAND. IF YES,
SYSTEM GOES INTO 60 MIN.WATCHGUARD.
DIAG. CODE: 1−FLASHING / 2−ON
IF NO, GO TO COMB. AIR BLOWER ON?"
GAS VALVE, COMB. INDUCER AND INDOOR BLOWER
(WITH DELAY) OFF. DIAG. CODE: 1−OFF / 2−FLASHING
(C.A.B. PRESSURE SWITCH OPEN) HAS C.A.B.
PRESSURE SWITCH CLOSED IN 2.5 MINUTES?
YES
NO
Page 22
Page 23
80UHG−1 COOLING SEQUENCE OF OPERATION
REMAINS UNCHANGED THROUGHOUT COOLING CYCLE.
THERMOSTAT CALLS FOR COOLING.
COMPRESSOR CONTACTOR AND SYSTEM FAN
ENERGIZED AT COOLING SPEED AFTER
1 SECOND DELAY. ACC TERMINAL ENERGIZED.
SYSTEM FAN AND ACC TERMINAL OFF AFTER
LED: Slow flash rate.
THERMOSTAT OPENS.
COMPRESSOR OFF.
0 SECONDS.
80UHG−1 MANUAL CONTINUOUS FAN SEQUENCE OF OPERATION
REMAINS UNCHANGED THROUGHOUT SEQUENCE.
CONTINUOUS FAN SELECTION MADE AT THERMOSTAT.
CONTROL ENERGIZES SYSTEM FAN AT HEATING SPEED.
LED: Slow flash rate.
ACC TERMINAL ENERGIZED.
THERMOSTAT CALLS FOR COOLING.
YES NO
SYSTEM FAN SWITCHED TO COOLING
SPEED. ACC TERMINAL REMAINS ENERGIZED.
THERMOSTAT OPENS.
SYSTEM FAN SWITCHES TO HEATING SPEED
AND ENERGIZES ACC TERMINAL. BOTH REMAIN ON
UNTIL CONTINUOUS FAN IS SWITCHED OFF AT THERMOSTAT.
THERMOSTAT CALLS FOR HEAT.
NO
YES
SYSTEM FAN REMAINS ON HEATING SPEED AFTER
SELECTED DELAY. ACC TERM. REMAINS ENERGIZED.
HTG ACC. TERM. ENER-
GIZED WITH COMB. AIR IN-
DUCER
THERMOSTAT OPENS.
SYSTEM FAN SWITCHED OFF AFTER DELAY.
ACC TERMINAL DE−ENERGIZED.
Page 23
Page 24
80UHG−2 MODEL WITH SURELIGHT CONTROL
1 − When there is a call for heat, W1 of the thermostat en-
ergizes W of the furnace control with 24VAC.
2 − S10 primary limit switch and S47 rollout switch are
closed. Call for heat can continue.
3 − SureLight control energizes combustion air blower
B6. Combustion air inducer runs until S18 combus­tion air prove switch closes (switch must close within 2−1/2 minutes or control goes into 5 minute Watch­guard Pressure Switch delay). Once S18 closes, a 15−second pre−purge follows.
4 − SureLight control energizes ignitor. A 20−second
warm−up period begins.
5 − Gas valve opens for a 4−second trial for ignition (igni-
tor will remain energized for the first second).
6 − Flame is sensed, gas valve remains open for the heat
call.
7 − After 45−second delay, SureLight control energizes
indoor blower B3.
8 − When heat demand is satisfied, W1 of the indoor ther-
mostat de−energizes W of the SureLight control which de−energizes the gas valve. Combustion air inducer B6 continues a 5−second post−purge period, and in­door blower B3 completes a selected OFF time delay.
Page 24
Page 25
HEATING SEQUENCE OF OPERATION
NO
NORMAL HEATING MODE
POWER ON
CONTROL SELF−CHECK OKAY?
YES
IS POLARITY REVERSED?
NO
NO
IS VOLTAGE
ABOVE 75 VOLTS?
YES
ROLLOUT SWITCH CLOSED?
YES
BURNER OFF?
(CONTINUOUS FLAME CHECK)
YES
NORMAL OPERATION:
LED #1 −− SLOW FLASH LED #2 −− SLOW FLASH
YES
THERMOSTAT CALLS FOR HEAT:
LED #1 −− FAST FLASH LED #2 −− FAST FLASH
YES
PRIMARY AND SECONDARY LIMIT SWITCH.
CLOSED?
YES
IS COMBUSTION AIR
PRESSURE SWITCH OPEN?
YES
IS COMBUSTION AIR BLOWER
ENERGIZED?
YES
HAS COMBUSTION AIR PRESSURE SWITCH CLOSED IN 2.5 MINUTES?
YES
ABNORMAL HEATING MODE
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.
NO
YES
NO
NO
NO
(RESET CONTROL BY TURNING MAIN POWER OFF.)
THERMOSTAT. CONTROL WILL NOT RESPOND
UNTIL VOLTAGE RISES ABOVE 75 VOLTS.
GAS VALVE OFF. COMBUSTION AIR INDUCER ON.
SEQUENCE HOLDS UNTIL ROLLOUT SWITCH CLOSES.
GAS VALVE OFF. COMBUSTION AIR INDUCER ON.
NO
NO
PRESSURE SWITCH IS IN WATCHGUARD MODE.
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.
IS 5-MINUTE RESET PERIOD COMPLETE?
INDOOR BLOWER DELAY OFF.
LED #1 ON LED #2 ON
POLARITY REVERSED.
LED #1 −− FAST FLASH
LED #2 −− SLOW FLASH
LED SIGNALS WAITING ON CALL FROM
INDOOR BLOWER ON.
LED #1 −− ON. LED #2 −− SLOW FLASH.
INDOOR BLOWER ON HEATING SPEED.
LED #1 −− SLOW FLASH
LED #2 −− OFF
COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER ON
LED #1 SLOW FLASH RATE
LED #2 −− ON
GAS VALVE OFF.
COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF WITH DELAY.
LED #1 OFF
LED #2 SLOW FLASH
(Sequence holds until pressure switch
closes or thermostat resets control.)
INDOOR BLOWER OFF WITH DELAY.
LED #1 −− OFF. LED #2 −− SLOW FLASH.
CONTINUED NEXT PAGE
Page 25
Page 26
HEATING SEQUENCE CONTINUED
NORMAL HEATING MODE ABNORMAL HEATING MODE
15-SECOND COMBUSTION AIR INDUCER PREPURGE
INITIATED BY CLOSED PRESSURE SWITCH.
YES
IGNITOR WARM-UP −− 20 SECONDS.
YES
4-SECOND TRIAL FOR IGNITION.
GAS VALVE OPENS. IGNITOR ENERGIZED FOR 1
SECOND AFTER VALVE OPENS. CONTROL
10M9301: IGNITOR ENERGIZED DURING TRIAL
UNTIL FLAME SENSED.
YES
FLAME STABILIZATION PERIOD.
4 SECONDS
FLAME RECTIFICATION CURRENT
CHECK. CAN FLAME BE PROVEN WITHIN
4 SECONDS AFTER GAS VALVE OPENS?
(u0.15 microamps)
YES
FLAME PRESENT?
YES
FLAME SIGNAL ABOVE 0.2 MICROAMPS?
YES
INDOOR BLOWER ON DELAY BEGINS
(45 seconds.)
YES
PRIMARY AND SECONDARY LIMIT
SWITCHES CLOSED?
YES
IS VOLTAGE ABOVE 75 VOLTS?
NO
IS THERE A PROPER GROUND?
YES
IS IGNITOR INTACT AND CONNECTED?
GAS VALVE OFF. COMBUSTION AIR INDUCER ON.
NO
HAS CONTROL FAILED TO SENSE FLAME FOR
FIVE CONSECUTIVE TRIES DURING A SINGLE
LEDs SIGNAL WATCHGUARD FAILURE CODE.
IS 60-MINUTE RESET PERIOD COMPLETE?
NO
NO
(Does not affect operation of control)
COMBUSTION AIR INDUCER DE−ENERGIZED.
INDOOR BLOWER ON UNTIL SWITCH CLOSES.
NO
LED #1 −− SLOW FLASH. LED #2 −− ON.
YES
YES
INDOOR BLOWER OFF.
HEAT DEMAND?
WATCHGUARD MODE. GAS VALVE OFF.
COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF WITH DELAY
HAS CONTROL RESET IGNITION
SEQUENCE FOUR TIMES?
LOW FLAME SIGNAL
LED #1 −− SLOW FLASH
LED #2 −− FAST FLASH
GAS VALVE DE−ENERGIZED.
IS LIMIT SWITCH CLOSED?
YES
HAS PRIMARY SECONDARY
LIMIT RESET (CLOSED)
WITHIN 3 MINUTES?
NO
NO
LEDS SIGNAL
ALTERNATING
FAST FLASH
NO
YES
LIMIT SWITCH
WATCHGUARD
MODE. GAS VALVE
OFF. COMB. AIR
INDUCER OFF. INDOOR BLOWER OFF WITH DELAY.
LED#1−SLOW
FLASH LED#2− ON.
IS 60−MINUTE
RESET PERIOD
COMPLETE?
NO
YES
NO
YES
NO
ROLLOUT SWITCH CLOSED?
YES
COMBUSTION AIR PRESSURE
SWITCH CLOSED?
YES
THERMOSTAT DEMAND SATISFIED.
YES
LED #1 & #2 SIMULTANEOUS SLOW FLASHES.
YES
COMB. AIR INDUCER CONTINUES 5-SECOND
POST PURGE AFTER T’STAT DEMAND IS SATISFIED.
INDOOR AIR BLOWER COMPLETES SELECTED
OFF" DELAY BEFORE SHUTTING OFF.
NO
SEQUENCE HOLDS UNTIL ROLLOUT SWITCH IS RESET
NO
THERMOSTAT IS CYCLED OFF/ON FOR 1 TO 20 SEC.
GAS VALVE DE−ENERGIZED.
COMBUSTION AIR INDUCER ON.
INDOOR BLOWER OFF WITH DELAY
LED #1 −− OFF. LED #2 −− SLOW FLASH.
HAS CAB SWITCH CLOSED IN 2.5 MINUTES?
5-MINUTE PRESSURE SWITCH
GAS VALVE POWER OFF.
COMBUSTION AIR INDUCER POWER ON.
INDOOR BLOWER ON
LED #1 −− ON. LED #2 −− SLOW FLASH.
AND MAIN POWER IS INTERUPTED OR
NO
WATCHGUARD MODE.
Page 26
YES
Page 27
COOLING SEQUENCE OF OPERATION
NORMAL COOLING MODE ABNORMAL COOLING MODE
POWER ON
IGNITION CONTROL MAIN POWER ON.
CONTROL SELF DIAGNOSTIC CHECK.
IS CONTROL OPERATING NORMALLY?
YES
IS POLARITY REVERSED?
NO
IS VOLTAGE
ABOVE 75 VOLTS?
YES
ROLLOUT SWITCH MONITORED CONTINUOUSLY.
IS ROLLOUT SWITCH CLOSED?
YES
CHECK FOR MAIN BURNER FLAME SENSE.
IS MAIN BURNER FLAME OFF?
YES
LED: SLOW FLASH RATE REMAINS UNCHANGED
THROUGHOUT COOLING CYCLE.
THERMOSTAT CALLS FOR COOLING.
NO
NO
YES
NO
NO
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF WITH NORMAL DELAY.
SIGNAL CIRCUIT BOARD FAILURE AT LED.
INTERRUPT MAIN POWER TO RESET CONTROL.
SIGNAL POLARITY REVERSED AT LED.
LED SIGNALS WAITING ON CALL FROM
THERMOSTAT. CONTROL WILL NOT RESPOND
UNTIL VOLTAGE RISES ABOVE 75 VOLTS.
GAS VALVE OFF. COMBUSTION AIR INDUCER ON.
INDOOR BLOWER ON.
SIGNAL ROLL-OUT SWITCH OPEN AT LED.
SEQUENCE HOLDS UNTIL ROLLOUT SWITCH CLOSES.
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF WITH NORMAL DELAY.
SIGNAL UNWANTED FLAME SENSED AT LED.
SEQUENCE HOLDS UNTIL FLAME IS NOT SENSED.
COMPRESSOR CONTACTOR AND SYSTEM FAN
ENERGIZED WITH 0-SECOND DELAY
(COOLING SPEED). EAC−H TERM. ENERGIZED.
THERMOSTAT OPENS.
COMPRESSOR OFF.
SYSTEM FAN AND ACC. TERM. OFF
WITH 0-SECOND DELAY.
Page 27
Page 28
SURELIGHT CONTROL
CONTINUOUS HEAT SPEED FAN SEQUENCE OF OPERATION
LED: SLOW FLASH RATE REMAINS
UNCHANGED THROUGHOUT SEQUENCE.
MANUAL FAN SELECTION MADE AT THERMOSTAT.
CONTROL (G) ENERGIZES SYSTEM FAN AT HEAT−H
HEAT SPEED. EAC−H TERMINAL IS ENERGIZED.
THERMOSTAT CALLS FOR HEAT (W).
NO
THERMOSTAT CALLS FOR COOLING.
YES
SYSTEM FAN SWITCHED TO COOL−H SPEED.
EAC−H TERM. REMAINS ON.
THERMOSTAT OPENS.
MANUAL FAN SELECTION MADE AT THERMOSTAT.
CONTROL (G) ENERGIZES SYSTEM FAN AT HEAT−H
HEAT SPEED. EAC−H TERM. ENERGIZED.
HUM−N TERM. ENERGIZES
WITH COMB. AIR BLOWER.
YES
SYSTEM FAN REMAINS ON HEAT−H
HEATING SPEED.
THERMOSTAT OPENS.
NO
HUM−N TERM. DE−ENERGIZES
WITH COMB. AIR INDUCER
SYSTEM FAN REMAINS ON HEAT−H
HEATING SPEED.
Page 28
Page 29
VIII−Troubleshooting−SureLight Control
code
code LED#2−Sl
h
ACTION 1
ducer does not energize
ducer does not energize
120V field connection
on operation
SURELIGHT − TROUBLE SHOOTING GUIDE
UPON INITIAL POWER UP, REMOVE ALL THERMOSTAT DEMANDS TO THE UNIT
PROBLEM: 1 UNIT FAILS TO OPERATE IN THE COOLING, HEATING, OR CONTINUOUS FAN MODE
Condition Possible Cause Corrective Action / Comments
1.1
Both diagnostic lights fail to light up.
LED#1−Off LED#2−Off
1.2
Diagnostic lights flash the roll−out
.
.
LED#1−On,
ow Flas
1.3
− On initial power−up the comb. air in­.
.
− Diagnostic lights flash the reverse
polarity code.
Main voltage 120V not supplied to unit.
Miswiring of furnace or improper connections.
Door interlock switch failure.
Transformer Failure.
Failed control board.
Roll−out switch open.
Roll−out switch failure.
Miswiring or improper connections at roll−out switch.
12 pin connector failure
120V main power polarity reversed.
1.1.1
1.1.2
1.1.3
Blown fuse
1.1.4
1.1.5
1.1.6
1.2.1
1.2.2
1.2.3
1.2.4
1.3.1
ACTION 1 − Check 120V main voltage.
Determine cause of main power failure.
ACTION 1 − Check for correct wiring of 120V to power make up box and transformer.
ACTION 2 − Check 24V wiring to control board.
ACTION 1 − Replace fuse. ACTION 2 − If fuse still blows, check for short.
ACTION 1 − Check that door switch is activated
when door is closed. ACTION 2 − Check wire connections to switch, re­place loose connectors. ACTION 3 − Check continuity of switch in closed position. Replace if defective.
ACTION 1 − Check that transformer output is 24V. Replace if defective.
ACTION 1 − If all the above items have been checked, replace board.
ACTION 1 − Manually reset the roll−out switch by pushing the top button. ACTION 2 − Determine the cause of the roll−out switch activation before leaving furnace.
ACTION 1 − Check continuity across roll−out switch. Replace roll−out switch if switch is reset but does not have continuity.
− Check wiring connections to switch.
ACTION 1 − Check 12−pin connector for proper
connection to control board. ACTION 2 − Check continuity of the multi plug pin.
ACTION 1 − Check the 120V has line and neutral correctly input into control. ACTION 2 − Reverse the line and neutral at the 120V field connection.
.
LED#1−Fast Flash, LED#2−Slow Flash.
1.4
− On initial power up the combustion
air inducer does not energize.
− Diagnostic lights flash normal power
on operation.
.
LED#1−Slow Flash LED#2−Slow Flash
1.4.1
Open combustion air inducer motor circuit.
1.4.2
Failed combustion air inducer motor.
Page 29
ACTION 1 − Check for 120V to combustion air inducer. If no power, check wire and connec­tions.
ACTION 1 − If power is present at blower, replace blower.
Page 30
PROBLEM 1: UNIT FAILS TO OPERATE IN THE COOLING, HEATING, OR CONTINUOUS FAN MODE
g
LED#2 Alternating Fast Flash
gg
Diagnostic lights flash the pressure
Condition Possible Cause Corrective Action / Comments
1.5
Diagnostic lights flash the improper
main ground.
LED#1−Alternating Fast Flash LED#2−Alternating Fast Flash
1.5.1
Improper ground to the unit.
1.5.2
4−Pin connector is improperly at-
tached to the circuit board.
1.5.3
Line voltage is below 75V.
1.5.4
Open ignitor circuit.
1.5.5
Broken or failed ignitor.
ACTION 1 − Check that the unit is properly ground. ACTION 2 − Install a proper main ground to the unit
ACTION 1 − Check 4−pin connector for proper installation. Correctly insert connector into con­trol.
ACTION 1 − Check that the line voltage is above 75V. Determine cause of voltage drop and sup­ply correct voltage to the control.
ACTION 1 − Check for correct wiring and loose connections in the ignitor circuit. Check mult− plug connections for correct installation.
ACTION 1 − Unplug ignitor and read resistance across ignitor. If resistance does not read be­tween 10.9 and 19.7 ohms, replace the ignitor.
PROBLEM 2: UNIT FAILS TO FIRE IN THE HEATING MODE, COMBUSTION AIR BLOWER DOES
NOT ENERGIZE
Condition Possible Cause Corrective Action / Comments
2.1
Unit operates with a cooling or con-
tinuous fan demand.
Combustion air inducer will not start
with a Heating demand.
− Diagnostic lights flash the limit failure
mode.
LED#1−Slow Flash, LED#2−On
2.1.1
Primary or secondary (if equipped )
limit open.
2.1.2
Miswiring of furnace or improper con-
nections at limit switch(es).
ACTION 1 − Check continuity across switch(es). Switches reset automatically upon cool down. ACTION 2 − Check for restrictions on blower inlet air (including filter) and outlet air. Determine cause for limit activation before placing unit back in operation.
ACTION 1 − Check for correct wiring and loose connections. Correct wiring and/or replace any loose connections.
2.2
− Unit operates with a cooling and con-
tinuous fan demand.
− Combustion air inducer will not start
with a Heating demand.
Diagnostic lights flash the pressure
switch failure code.
LED#1−Off, LED#2−Slow Flash
2.2.1
Miswiring of furnace or improper con-
nections to combustion air inducer.
2.2.2
Pressure switch stuck closed.
Page 30
ACTION 1 − Check for correct wiring and loose connections. Correct wiring and/or replace any loose connections.
ACTION 1 − Check that the pressure switch is open without the combustion air inducer operat­ing. Replace if defective.
Page 31
PROBLEM 2: UNIT FAILS TO FIRE IN THE HEATING MODE, COMBUSTION AIR INDUCER DOES
g
LED#1 Off
NOT ENERGIZE (CONT.).
Condition Possible Cause Corrective Action/Comments
2.3
− Unit operates with a cooling and con-
tinuous fan demand.
Combustion air inducer will not start
with a Heating demand.
Miswiring of furnace or improper con-
nections to combustion air inducer.
2.3.1
ACTION 1 − Check for correct wiring and loose
connections. Correct wiring and/or replace any loose connections.
Diagnostic lights flash the pressure
switch failure code 2.5 minutes after heating demand.
ACTION 1 − If there is 120V to combustion air in­ducer and it does not operate, replace combus­tion air inducer.
LED#1−Off,
2.3.2
Combustion air inducer failure.
LED#2−Slow Flash
PROBLEM 3: UNIT FAILS TO FIRE IN THE HEATING MODE, COMBUSTION AIR BLOWER
ENERGIZES, IGNITOR IS NOT ENERGIZED.
Condition Possible Cause Corrective Action/Comments
3.1
Unit operates with a cooling and
continuous fan demand.
Combustion air inducer energizes
with a heating demand.
− Diagnostic lights flash the pressure
switch failure code 2.5 minutes after heating demand.
LED#1−Off LED#2−Slow Flash
Pressure switch does not close due
to incorrect routing of the pressure
Pressure switch does not close due
to obstructions in the pressure lines.
Pressure switch lines damaged
Condensate in pressure switch line.
Pressure switchdoes not close due to
a low differential pressure across the
Wrong pressure switch installed in
the unit, or pressure switch is out of
Miswiring of furnace or improper con-
nections at pressure switch.
Pressure switch failure.
3.1.1
switch lines.
3.1.2
3.1.3
3.1.4
3.1.5
pressure switch.
3.1.6
calibration.
3.1.7
3.1.8
ACTION 1 − Check that the pressure switch lines
are correctly routed. Correctly route pressure switch lines.
ACTION 1 − Remove any obstructions from the the pressure lines and/or taps.
ACTION 1 − Check pressure switch lines for leaks. Replace any broken lines.
ACTION 1 − Check pressure switch lines for con­densate. Remove condensate from lines. Check that the condensate lines are located correctly.
ACTION 1 − Check the differential pressure across the pressure switch. This pressure should exceed the set point listed on the switch. ACTION 2 − Check for restricted inlet vent. Re­move all blockage. ACTION 3 − Check for proper vent sizing and run length. See installation instructions.
ACTION 1 − Check that the proper pressure switch is installed in the unit. Replace pressure switch if necessary.
ACTION 1 − Check for correct wiring and loose connections. Correct wiring and/or replace any loose connections.
ACTION 1 − If all the above modes of failure have been checked, the pressure switch may have failed. Replace pressure switch and determine if unit will operate.
Page 31
Page 32
PROBLEM 4: UNIT FAILS TO FIRE IN THE HEATING MODE, COMBUSTION AIR BLOWER
ignite code.
ENERGIZES, IGNITOR IS ENERGIZED.
Condition Possible Cause Corrective Action/Comments
4.1
− Unit operates with a cooling and
continuous fan demand.
− Combustion air inducer energizes
with Heating demand.
Ignitor is energized but unit fails to
light.
LED#1−Alternating Slow Flash LED#2−Alternating Slow Flash
4.1.1
Check that gas is being supplied to
the unit.
4.1.2
Miswiring of gas valve or loose con-
nections at multi−pin control amp
plugs or valve.
4.1.3
Defective gas valve or ignition con-
trol.
ACTION 1 − Check line pressure at the gas valve. Pressure should not exceed 13" WC for both natural and propane. Line pressure should read a minimum 4.5" WC for natural and 8.0"WC for propane.
ACTION 1 − Check for correct wiring and loose connections. Correct wiring and/or replace any loose connections.
ACTION 1 − Check that 24V is supplied to the gas valve approximately 35 seconds after heat demand is initiated. ACTION 2 − Replace the valve if 24V is supplied but valve does not open. ACTION 3 − Replace the control board if 24V is not supplied to valve.
PROBLEM 5: BURNERS LIGHT WITH A HEATING DEMAND BUT UNIT SHUTS DOWN
PREMATURELY
Condition Possible Cause Corrective Action/Comments
5.1
− Burners fire with a heating de-
mand.
− Burners light but unit shuts off prior
to satisfying T−stat demand.
− Diagnostic lights flash the pressure
switch code.
5.1.1
Low pressure differential at the pres-
sure switch.
ACTION 1 − Check for restricted exhaust vent. Remove all blockage. ACTION 2: Check for proper vent sizing. See installation instructions.
LED#1−Off LED#2−Slow Flash
5.2
− Combustion air inducer energizes
with a heating demand.
− Burners light but fail to stay lit.
− After 5 tries the control diagnostics
flash the watchguard burners failed to ignite code.
LED#1−Alternating Slow Flash LED#2−Alternating Slow Flash
5.2.1
Sensor or sensor wire is improperly
installed.
5.2.2
Sensor or sensor wire is broken.
5.2.3
Sensor or sensor wire is grounded to
the unit.
5.2.4
Control does not sense flame.
ACTION 1 − Check that sensor is properly lo­cated and that the sense wire is properly at­tached to both the sensor and the control.
ACTION 1 − Check for a broken sensor. ACTION 2 − Test continuity across the sense
wire. If wire or sensor are damaged replace the component.
ACTION 1 − Check for resistance between the sensor rod and the unit ground. ACTION 2 − Check for resistance between the sensor wire and the unit ground.
ACTION 3 − Correct any shorts found in circuit.
ACTION 1 − Check the microamp signal from
the burner flame. If the microamp signal is be­low 0.20 microamps, check the sensor rod for proper location or contamination. ACTION 2 − Replace, clean, or relocate flame sensor rod. If rod is to be cleaned, use steel wool or replace sensor. DO NOT CLEAN ROD WITH SAND PAPER. SAND PAPER WILL CONTRIBUTE TO THE CONTAMINATION PROBLEM. NOTE: Do not attempt to bend sensor rod. ACTION 3 − Check that there is proper ground to burner box. Repair as necessary.
Page 32
Page 33
PROBLEM 5: BURNERS LIGHT WITH HEATING DEMAND BUT UNIT SHUTS DOWN
LED#1 On
Burners light roughly and the unit
Condition Possible Cause Corrective Action/Comments
5.3
− Combustion air inducer energizes
with a heating demand.
− Burners light.
− Roll−out switch trips during the
heating demand.
− Diagnostic lights flash roll−out fail-
ure.
LED#1−On LED#2−Slow Flash
5.4
Combustion air inducer energizes
with a heating demand.
− Burners light roughly and the unit
fails to stay lit.
− Diagnostic lights flash watchguard
flame failure.
PREMATURELY (CONT.)
5.3.1
Unit is firing above 100% of the
nameplate input.
5.3.2
Gas orifices leak at the manifold con-
nection.
5.3.3
Insufficient flow through the heat ex-
changer caused by a sooted or re-
stricted heat exchanger.
5.3.4
Burners are not properly located in
the burner box.
5.4.1
Poor Venting
5.4.2
Improper burner cross−overs
ACTION 1 − Check that the manifold pressure matches value listed on nameplate. See installa­tion instructions for proper procedure. ACTION 2 − Verify that the installed orifice size match the size listed on the nameplate or instal­lation instructions. ACTION 3 − Check the input rate to verify rate matches value listed on nameplate.
ACTION 1 − Tighten orifice until leak is sealed. NOTE: Be careful not to strip orifice threads. ACTION 2 − Check for gas leakage at the
threaded orifice connection. Use approved method for leak detection (see unit instructions).
ACTION 1 − Check for sooting deposits or other restrictions in the heat exchanger assembly. Clean assembly as outlined in instruction manu­al. ACTION 2 − Check for proper combustion. See NO TAG Heating System Service Checks sec­tion NO TAG.
ACTION 1 − Check that the burners are firing into the center of the heat exchanger openings. Cor­rect the location of the burners if necessary.
ACTION 1 −Check vent pipe and remove any ob­structions ACTION 2 − Check for correct exhaust vent installation. See instructions
ACTION 1 − Remove burner and inspect the cross−overs for burrs, or any restriction or if crossover is warped. Remove restriction or re­place burners.
LED#1−Alternating Slow Flash LED#2−Alternating Slow Flash
5.5
− Combustion air inducer energizes
with a heating demand.
− Burners light.
− Diagnostic lights flash watch guard
flame failure.
− NOTE" Unit might go into 60 min-
ute Watchguard mode depending on intermittent nature of sensor signal.
LED#1−Alternating Slow Flash LED#2−Alternating Slow Flash
5.4.3
Burrs in gas orifices
5.5.1
Loose sensor wire connection
causes intermittent loss of flame sig-
nal.
5.5.2
Poor ground to burner box
ACTION 1 − Remove gas orifices and inspect. Remove any burrs that are present or replace orifice.
ACTION 1 − Check that the sensor is properly lo­cated. ACTION 2 − Check that the sense wire is proper­ly attached to both the sensor and the control. Pay extra attention to the pin connectors.
ACTION 1 − Check for proper ground and repair as necessary.
Page 33
Page 34
PROBLEM 6: CONTROL SIGNALS LOW FLAME SENSE DURING HEATING MODE
sense code
Condition Possible Cause Corrective Action/Comments
6.0
− Unit operates correctly but the
diagnostic lights flash low flame
6.1.1
Sensor rod is improperly located on
the burner.
ACTION 1 − Check the sensor rod for proper location on the burner. Properly locate the sen­sor rod or replace if rod cannot be located cor­rectly.
.
ACTION 1 − Check sensor rod for contamination or coated surface. Clean the sensor rod with steel wool or replace sensor. DO NOT USE SAND PAPER TO CLEAN ROD. SAND PAPER WILL CONTRIBUTE TO THE CONTAMI­NATION PROBLEM.
LED#1−Slow Flash LED#2−Fast Flash
6.1.2
Sensor rod is contaminated.
PROBLEM 7: INDOOR BLOWER FAILS TO OPERATE IN COOLING, HEATING, OR CONTINUOUS
FAN MODE
Condition Possible Cause Corrective Action/Comments
7.0
− Indoor blower fails to operate in
continuous fan, cooling, or heating mode.
Miswiring of furnace or improper con-
nections at control or indoor blower
120V is not being supplied to the in-
door air blower or blower motor fail-
Defective control board
7.1.1
motor.
7.1.2
ure.
7.1.3
7.1.4
ACTION 1− Correct wiring and/or replace any
loose connections. Check for correct wiring and loose connections.
ACTION 1 − Check for 120V at the various calls for indoor blower by energizing "Y", "G", and "W" individually on the low voltage terminal strip. Note that when "W’ is energized, the blower is delayed 45 seconds. If there is 120V to each mo­tor tap but the blower does not operate, replace the motor.
ACTION 1 − If there is not 120V when "Y", "G", or "W" is energized, replace the control.
ACTION 1 − Replace capacitor
Defective run capacitor
PROBLEM 8: RF STATIC DURING TIME FOR IGNITION
Condition Possible Cause Corrective Action/Comments
8.0
− AM radio interference.
8.1.2
Ignitor operation
ACTION 1 − Call Technical Support, Dallas.
Page 34
Loading...