Lennox 59M04 Installation Instructions Manual

MISCELLANEOUS
Litho U.S.A.
E2003
504,764M 4/2003
TEMPERATURE
INSTALLATION INSTRUCTIONS FOR WALL−MOUNT SENSOR (59M04) IS USED WITH
BUILDING CONTROLLERS (BC) ON THE L CONNECTION® NETWORK
Shipping and Packing List
Package 1 of 1 contains:
1− Sensor
2− Screws
WARNING
Improper installation, adjustment, alteration, ser vice or maintenance can cause property damage, personal injury or loss of life. Installation and ser vice must be performed by a qualified installer, ser vice agency or the gas supplier
Application
1− Route shielded cable between sensor location and
Building Controller.
Cable type: Lennox P/N 94L63, Belden type 88761 or equivalent. (22AWG stranded or twisted pair, 100% aluminum shield with drain wire, Teflon jacket).
2− Remove sensor cover and center opening in
baseplate over opening in wall. See figure 1.
3− Mark holes for screws. Remove baseplate and drill
holes.
4− Insert wall anchors (field provided) and align baseplate
over opening in wall. Pull wiring through opening in baseplate. Secure baseplate to wall with screws.
INDOOR
SENSOR
This sensor provides a temperature input to the Building Controller. The BC can use the indoor temperature to override NCP scheduled outputs and to set alarms based on over or under temperature conditions.
The BC Building Controller, used with the L Connection Network, controls lights, vent hoods, exhaust fans, sprinklers, security and fire systems, and other building equipment.
The sensor is NOT compatible with IMC or NTC rooftop controllers.
Installation
Locate sensor in conditioned space approximately 5 feet (1−1/2m) above the floor in an area with good air circulation at average temperature. Avoid locating the room thermostat where it might be affected by:
−drafts or dead spots behind doors and in corners
−hot or cold air from ducts
SENSOR
BASEPLATE
WIRING
CONNECTOR
FIGURE 2
5− Connect the shielded cable to sensor terminal block.
−radiant heat from sun or appliances
−concealed pipes and chimneys
04/03
*2P0403*
6− Replace sensor cover and tighten side screws to
secure in place.
Page 1
*P504764M*
504,764M
7− Connect sensor to any available input (T1, T2, T3,
T4) on P187 Building Controller terminal block. Connect the shield drain wire to the input common as shown in figure 2.
Make note of which inputs are used and refer to Unit Controller (UC) Software manual to configure override outputs and alarms.
The temperature will be displayed on the NCP. Refer to the NCP Software manual to enter a description of the temperature input.
WIRE INDOOR SENSOR TO P187 ON BC1
BC
Temperature
Sensors
Building
Controller
1
1
T1
2 3
T2
4 5
T3
6 7
T4
8
P187
Sensor Check
Check the temperature displayed on the NCP. If the temperature is incorrect, disconnect the sensor from the BC and measure the resistance. The resistance should correspond to the temperature as follows:
Important: The sensor must be disconnected from the BC before measuring resistance.
°F Resistance
−40 335,671
−20 164,959 0 85,323 20 46,218 30 34,566 40 26,106 50 19,904 60 15,313 70 11,884 80 9,298 90 7,332 100 5,826 120 3,756 130 3,047
All values are +/− 2%.
The operating range of each input is −40°F to 130°F (−22°C to 54°C).
FIGURE 2
Page 2