Lennox 51M37 User Manual

OPERATION
E2005 Lennox Industries Inc.
Dallas, Texas, USA
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
51M37 Merit® Series Thermostat
The Lennox Merit® Series 5/2 day programmable electronic thermostat 51M37 provides excellent temperature control and a large, easy-to-read display. It includes a programmable filter change reminder, an equipment maintenance reminder, and a system check indicator to notify the user when the equipment requires service.
The 51M37 is suitable for heat pump, 3-stage heat/2-stage cool applications using a gas or electric auxiliary heat source. An optional outdoor temperature sensor provides auxiliary heat lockout, balance point operation, and dual−fuel compatibility.
MANUAL
®
51M37 Merit
5/2 Day Programmable Thermostat
CONTROLS
505,050M 05/05 Supersedes 03/05
Table of Contents
51M37 Series Thermostat 1. . . . . . . . . . . . . . . . . . . . . .
General 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Introduction 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Initial Thermostat Power-up 1. . . . . . . . . . . . . . . . . . . . .
Buttons, Backlight, Timers & Settings 2. . . . . . . . . . . .
DAY/TIME − Set Day and Time 2. . . . . . . . . . . . . . . . . .
HEAT − Heat Mode 3. . . . . . . . . . . . . . . . . . . . . . . . . . . .
COOL − Cool Mode 4. . . . . . . . . . . . . . . . . . . . . . . . . . . .
HOLD − Temperature Hold Mode 5. . . . . . . . . . . . . . . .
PROG − Thermostat Programming 5. . . . . . . . . . . . . . .
FAN − Controlling Fan Operation 6. . . . . . . . . . . . . . . . .
SETTINGS − Filter and Maintenance Reminders 6. . .
SETTINGS − Balance Point 7. . . . . . . . . . . . . . . . . . . . .
Service Indicator 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Thermostat RESET 7. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Removing/Installing Thermostat 7. . . . . . . . . . . . . . . . .
Default Thermostat Settings 7. . . . . . . . . . . . . . . . . . . .
Technical Specifications 8. . . . . . . . . . . . . . . . . . . . . . . .
Thermostat Output Table 10. . . . . . . . . . . . . . . . . . . . . . .
Series
Litho U.S.A.
General
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities having jurisdiction before installation.
Check equipment for shipping damage. If you find any damage, immediately contact the last carrier.
Introduction
This document describes the operation of Lennox thermostat 51M37. Refer to the installation manual for instructions re­garding installation and wiring of the thermostat.
Initial Thermostat Power-up
When power is initially applied to the thermostat, the dis­play will appear as shown in figure 1.
Initial Power−Up Display
MO TU WE TH FR SA SU
AM
I8:88
PM
PROG A | B | C | D HOLD
ROOM
SETPOINT
°
°
88
All display segments are momentarily activated. This oc­curs as a normal part of thermostat initialization.
88
Figure 1
MAINT
FILTER
SERVICE
FAN ON AUTO
SYSTEM COOL OFF EMG. HEAT
Hi Lo
05/05 505,050M
Page 1
*2P0505* *P505050M*
Within a few seconds, the Home Screen appears (see fig­ure 2) with default settings as shown. After about 1 minute of initialization time, the actual room temperature will be displayed.
NOTE − Tables 2 and 3 on page 8 show all system and programming defaults.
Home Screen
MO TU WE TH FR SA SU
MAINT
FILTER
SERVICE
AM
I2:00
PM
PROG A B C D HOLD
ROOM
°
70
FAN
ON
AUTO
SYSTEM
COOL OFF
HEAT
Figure 2
At this point, the thermostat will be fully functional; its de­fault temperature setpoint (not shown) is 70°F. At this point, if the equipment has been fully powered and if a heat demand were present, the system would begin operating.
NOTE − Temperature scale default is Fahrenheit units but may be reset to show Celsius, if desired. See page 8.
Buttons, Backlight, Timers & Settings
Buttons are located behind the small door on the right− hand side of the thermostat (see figure 3).
IMPORTANT
Do NOT begin pressing buttons until after you read the following section describing each button.
A pale blue display backlight illuminates for 30 seconds each time any button is pressed.
When PROG or DAY/TIME is pressed, a field begins flash­ing, expecting another input. Start making changes within 15 seconds or the HOME screen will return.
Thermostat Buttons
Heat
Cool
Prog
Day/Time
Fan
Hold
Settings
Enter
(DOOR OPEN)
Figure 3
When an Arrow, HOLD, HEAT, or COOL button is pressed, SETPOINT and the temperature setting appears for 15 seconds. If desired, start making changes within 15 sec­onds or the HOME screen will return. The backlight will turn off 15 seconds after the HOME screen reappears.
DAY/TIME − Setting the Day and Time
Press the DAY/TIME button and set the CURRENT hour, minute, and day of week as follows:
1. AM12" will flash on the screen. Press the Up/Down ar­rows buttons to change the hour. (AM" or PM" must correspond to time of day.) Press DAY/TIME OR, if ad-
justing for daylight savings time, pressing ENTER stores the single change and exits to the HOME screen, bypassing minutes and day of week.
2. Minutes will flash. Use the Up/Down arrow buttons to display the minutes past the hour. Press DAY/TIME.
3. Day MO" (Monday) will flash. Use Up/Down arrow buttons to display the current day. Day selections are abbreviated as MO, TU", WE", TH", FR", SA", and SU". Press DAY/TIME.
4. The HOME screen reappears; confirm day and time are correct. This completes day and time setting.
505050M 5/1/05
Page 2
HEAT − Using the Heat Mode
Normal Heat Mode
In normal heat mode, both the heat pump and the backup heat source are used to provide heat. If the thermostat de­tects that the heat pump is not able to provide enough heat (as may be the case in very cold weather), then the backup heat source is activated.
Emergency Heat Mode
In emergency heat mode, only the backup heat source provides heat the heat pump is disabled. The backup heat source is activated only when there is a heat demand.
Enabling Normal Heat Mode
Use the HEAT button to select normal heat mode, emer­gency heat mode, or to disable heat modes as desired. If the thermostat is in OFF or COOL mode, pressing the Heat button enables Heat mode. This is indicated by HEAT in the SYSTEM box as shown in figure 4.
Normal Heat Mode Enabled
Heat
Prog
Fan
Settings
Day/Time
°
Cool
Hold
Enter
SYSTEM
COOL OFF
EMG. HEAT
MO
AM
5:30
PM
ROOM
°
66
Enabling Emergency Heat Mode
If the thermostat is in heat mode, pressing the Heat button enables EMG. HEAT mode (see figure 5). If the thermostat is in normal heat mode when the HEAT button is pressed, then emergency heat mode is enabled.
Emergency Heat Mode Enabled
ROOM
62
Disabling Heat Mode
If the thermostat is in emergency heat mode when the HEAT button is pressed, then heat modes are disabled. This is indicated by OFF in the SYSTEM box as shown in figure 6.
HOLD
SETPOINT
70
°
FAN
AUTO
SYSTEM
HEAT
°
Figure 4
SETPOINT
75
Figure 5
Heat Mode Disabled
°
°
°
SYSTEM
COOL
OFF
HEAT
SYSTEM
COOL OFF
HEAT
SYSTEM
COOL OFF
Hi
HEAT
ROOM
75
Heating Demand
The thermostat must be in either normal or emergency heat mode in order to properly control the heating equip­ment. In either heat mode, when the actual temperature is lower than the temperature setpoint (as shown in figure 7), the thermostat detects a heating demand and activates the heating equipment to satisfy the demand. Heating opera­tion is indicated by a flame icon in the SYSTEM box.
ROOM
72
When the actual temperature rises above the temperature setpoint, the flame icon will disappear. This indicates that the heating demand has been satisfied and that the heat­ing equipment has been turned off.
Heat pump operation is locked out for 5 minutes after a de­mand has been satisfied. If another heat pump demand occurs during this 5−minute interval, the flame icon will flash; however, the heat pump will not run until the 5−min­ute delay has elapsed.
NOTE − The heat pump is activated for at least 4 minutes if no buttons are pressed during the demand interval. The backup heat source is activated for at least 3 minutes if no buttons are pressed during the demand interval.
If your system supports 3−stage heating (as does the 51M37 thermostat), you may notice various heating levels being delivered during a demand.
If a small heat pump heating demand is present, "Lo" is dis­played in the SYSTEM box; if a large heat pump heating demand is present, "Hi" is displayed (see figure 8).
Large Heat Demand
ROOM
SETPOINT
°
75
Figure 6
Heating Demand
SETPOINT
°
75
Figure 7
SETPOINT
°
65
75
Figure 8
Page 3
51M37 SERIES 5/2
COOL − Using the Cool Mode
Enabling and Disabling Cool Mode
Use the COOL button to enable or disable cool mode as desired. If the thermostat is in HEAT or OFF mode, cool mode is enabled when the COOL button is pressed. This is indicated by COOL in the SYSTEM box (see figure 9).
Cooling Demand
Set the thermostat to cool mode to control the cooling equipment. Then, if the room temperature is higher than the temperature setpoint, as shown in figure 11, the ther­mostat detects a cooling demand and will activate the cool­ing equipment to satisfy the demand.
Cooling Demand
MO TU WE TH FR SA SU
Turn Cool ON/OFF
Heat
Prog
Fan
Settings
Day/Time
°
Cool
Hold
Enter
SYSTEM
COOL
OFF
HEAT
MO
AM
PM
I0:30
ROOM
°
75
If the thermostat is in cool mode, pressing the Cool button disables COOL mode (indicated by OFF in the SYSTEM box − see figure 10).
ROOM
75
FAN
HOLD
AUTO
SYSTEM COOL
SETPOINT
°
70
Figure 9
Cool Mode Disabled
SETPOINT
°
75
Figure 10
AM
i0:00
PM
PROG A B C D HOLD
ROOM
SETPOINT
°
75
Cooling operation is indicated by flashing snowflake" icons in the SYSTEM box. When the actual temperature drops below the temperature setpoint, the snowflake icons will disappear. This indicates that the cooling demand has been satisfied and that the cooling equipment has been turned off.
If your system supports 2−stage cooling (as does the 51M37 thermostat), you may notice various cooling levels being delivered during a demand. Also, if a small cooling demand is present, "Lo" will be displayed in the SYSTEM box. However, if a large cooling demand is present, "Hi" will be displayed in the SYSTEM box (shown in figure 11).
NOTE − If no buttons are pressed during a demand for cooling, the equipment must operate for at least 4 minutes. After a demand has been satisfied, cooling equipment op­eration is locked out for 5 minutes. If another cooling de­mand occurs during this 5−minute interval, COOL" and the snowflakes will flash; however, the cooling equipment will not operate until the 5−minute delay has elapsed.
70
Figure 11
°
FAN
ON
AUTO
SYSTEM COOL
OFF
Hi
HEAT
505050M 5/1/05
Page 4
HOLD − Using Temperature Hold Modes
PROG − Thermostat Programming
When HOLD is displayed at the HOME screen, the ther­mostat is in a temperature hold condition. This means that the temperature program data is ignored and the thermo­stat functions much like a non−programmable thermostat.
Adjusting Temperature Setpoint in Hold Mode
The temperature setpoint represents the desired tempera­ture of the space around the thermostat. The default tem­perature setpoint in Hold mode is 70°F.
To adjust the setpoint, press the UP or DOWN (YB) arrow buttons (see figure 12); the existing setpoint is displayed to the right of the actual room temperature. Each button press adjusts the setpoint up or down by 1 degree.
Hold Temperature Mode
MO
AM
PM
I0:36
ROOM
72
°
HOLD
SETPOINT
68
°
FAN
AUTO
SYSTEM COOL
Heat
Prog
Fan
Settings
Cool
Day/Time
Hold
Enter
Figure 12
After the desired setpoint is reached, the HOME screen will reappear after about 15 seconds.
Permanent Hold Mode
At any time the program is running, from the HOME screen, set a permanent hold (program override) by press­ing the HOLD button (see figure 12). The thermostat now functions much like a non−programmable thermostat. Use the Up/Down arrow buttons to adjust the hold setpoint. To return to the program, press HOLD again.
Temporary (2-Hour) Hold
At any time the program is running, from the HOME screen, set a temporary 2-hour hold by pressing the Up/ Down arrow buttons until the desired setpoint is displayed; HOLD" flashes (see figure 13). This overrides the pro­gram for 2 hours from the last button press, then returns to the program.
Temporary Hold Temperature Mode
MO
AM
PM
I0:36
PROG B HOLD
ROOM
°
72
SETPOINT
68
°
FAN
AUTO
SYSTEM COOL
Heat
Prog
Fan
Settings
Cool
Day/Time
Hold
Enter
Figure 13
While in Temporary Hold, press HOLD once to switch to Permanent Hold (HOLD displays solid; PROG not dis­played); press HOLD again to return to the program (PROG displays; HOLD not displayed).
The 51M37 thermostat can be programmed to perform a set of either heating or cooling events (but not a combination of heat and cool) for 5 consecutive days using a set of 4 unique events per day. The remaining 2 days can then be set for a different set of 4 unique events per day. Both the consecutive days and the events/temperature are set by the homeowner.
To Change Consecutive Days...
To alter the 5 consecutive days, press and hold the PROG button for 5 seconds. The 5 consecutive day period is then displayed (default is MOnday thru FRiday). To change to a different 5-consecutive days, use the Up/ Down arrow buttons. Any 5 consecutive−day span may be selected, for example, in figure 14, Saturday through Wednesday is defined as the 5−day programming (Thurs­day and Friday would constitute the 2−day programming). Press the PROG button when finished.
Change Consecutive days
MO TU WE TH FR SA SU
Figure 14
To Set Program Events and Temperatures...
Figure 15 gives an example of how the two sets of pro­grams can be set for a normal workweek and weekend.
In the 5−day bar graph, note how programs A and C reflect the desired warmth while the home IS occupied (72°); B allows less heating while the home is NOT occupied; D re­flects a cooler sleeping temperature. The 2−day bar graph would support day−long occupancy and, because the first program begins later, a less−demanding time schedule.
5/2 Program Example
5−DAY PROGRAM:
2−DAY PROGRAM:
|A | B | C | D |
72°
68°
64°
6AM NOON 6PM MID 6AM
|A| B | C | D |
72°
68°
64°
6AM NOON 6PM MID 6AM
NIGHT
NIGHT
Figure 15
NOTE − Pressing ENTER during the following program­ming steps, saves and exits to the HOME screen.
To program events and temperatures, perform the follow­ing steps, once with Cool selected and once with Heat se­lected.
1. Press and release PROG. AM 6:00", period A", and the 5 consecutive days are displayed; AM 6" flashes.
2. Use the Up/Down arrow buttons to select the desired hour; press PROG when the desired hour is reached.
3. Use the Up/Down arrow buttons to select the desired minute; press PROG.
4. Use the Up/Down arrow buttons to select the desired temperature setpoint; press PROG.
Page 5
FILTER
51M37 SERIES 5/2
5. Repeat steps 2 through 4 for periods B, C, and D.
(1st
)
(Off, 1, 3, 6, 12); f
(2nd
)
(Off, 6, 12). U
thi
6. Repeat steps 1 through 5 for the 2−day program.
NOTE − This thermostat will NOT automatically switch from heating to cooling, or vice versa; operator involve­ment is required. At the change of seasons, or to accomo­date abnormal seasonal temperature swings, you must manually select to the opposite conditioning (Heat or Cool) program.
FAN − Controlling the Fan Operation
Use the FAN button to select either continuous fan mode or auto fan mode.
To change from continuous to auto fan mode (or vice ver­sa), press the FAN button. Note whether a fan icon in the FAN box is present (indicating that the fan is running) or not (fan not running).
If continuous fan mode is enabled (ON displayed in FAN box − see figure 16), the fan will run continuously regard­less of whether the heating or cooling equipment is run­ning.
MO
AM
PM
PROG B
ROOM
67
Using Fan ON
FAN
I0:I0
°
ON
SYSTEM
HEAT
Heat
Prog
Fan
Settings
Cool
Day/Time
Hold
Enter
Reminder Settings Display
MAINT
FILTER
OFF
For MAINT, press Settings button 2 times
For FILTER, press Settings button 1 time
Figure 18
The default setting for the reminders is OFF (disabled). Press Up/Down arrow buttons to select the desired re­minder intervals.
Table 1
Filter and Maintenance Reminders
Buttons to
Use
Settings
press
then Arrows
to scroll
selections
Settings
press
then Arrows
to scroll
selections
Enter Stores settings.
Reminder
FILTER
MAINT
Available Settings and How to Use
Total fan run time expressed in months example, if fan runs 12 hours a day, 1 month reminder displays in 2 calendar months.
Elapsed chronological time in months for example, to remind yourself when to perform routine checks or when to call a technician for perodic preventive maintenance.
se
or
s,
Figure 16
If auto fan mode is selected (AUTO displayed in FAN box − see figure 17), the fan will only run when the heating or cooling equipment is running.
MO
AM
PM
I0:36
PROG B
ROOM
72
Using Fan Auto
FAN
AUTO
SYSTEM COOL
°
Heat
Prog
Fan
Settings
Cool
Day/Time
Hold
Enter
Figure 17
SETTINGS − Filter/Maintenance Reminders
The 51M37 thermostat is designed to remind you when the filter needs changing or when routine maintenance is re­quired, as (and if) defined, by you. These optional remind­ers are not enabled until you activate them. To do so, press the Settings button (shown below the Fan button in figure
17) once or twice for the desired reminder as shown in fig­ure 18 and as described in table 1.
NOTE − The HOME screen will reappear about 15 seconds after the final arrow button press. OR, press ENTER at any time to store any changes and exit to the HOME screen.
After either programmed interval has elapsed, the remind­er will be displayed as shown in figure 19.
Reminders
MO TU WE TH FR SA SU
AM
PM
I0:i2
PROG A B C D HOLD
ROOM
°
78
MAINT
FILTER
SERVICE
FAN
ON
AUTO
SYSTEM
COOL OFF
HEAT
Figure 19
After the filter has been changed or maintenance per­formed, reset the reminder by pressing the SETTINGS button for 4 seconds. The screen will blink for a few mo­ments to indicate that the timer has been reset.
505050M 5/1/05
Page 6
SETTINGS − Balance Point
NOTE − The balance point is only available with the out­door sensor.
If the optional outdoor sensor (X2658) is connected to the thermostat, balance point adjustment is available. The bal­ance point feature allows the measured outdoor tempera­ture to govern operation of the heat pump and backup heat source.
Use the SETTINGS button to access the balance point setting. If the outdoor sensor is attached to the thermostat, press the SETTINGS button three times to access the Bal­ance Point Settings screen (see figure 20).
Balance Point Setting
Service Indicator Flashing
MO TU WE TH FR SA SU
AM
I0:i4
PM
PROG A B C D HOLD
ROOM
°
79
Figure 21
FILTER
SERVICE
FAN
ON
AUTO
SYSTEM
COOL OFF
HEAT
ROOM
SETPOINT
°
6p
The balance point can be set at any temperature between 1°F and 55°F (−17°C to 13°C). A balance point setting of zero disables the balance point function (in this case, the thermostat behaves as if no outdoor sensor is attached). The default balance point setting is 55°F.
To adjust the balance point up or down, press the Up/Down arrow buttons to the right of the display screen. The bal­ance point setting increases by 1°F each time the Up but­ton is pressed and decreases by 1°F each time the Down button is pressed.
After the desired balance point is reached, the HOME screen will reappear after about 15 seconds.
NOTE − The balance point feature allows the outdoor tem­perature to rise or fall 3°F above or below the balance point. This prevents excessive cycling of the equipment when the outdoor temperature is near the balance point. For example, if the balance point is 40°F and the actual outdoor temperature is 35°F, the outdoor temperature must rise to 43°F before equipment adjustment occurs. Conversely, if the balance point is 40°F and the actual out­door temperature is 45°F, the outdoor temperature must drop to 37°F before equipment adjustment occurs.
Service Indicator
When abnormal equipment operation is detected, the SERVICE indicator will flash on the screen (see figure 21). This indicates that the equipment requires service from a qualified service technician.
55
Figure 20
Thermostat RESET
Under some abnormal conditions, it may be necessary to reset" the thermostat to its default condition. Such a RE­SET would delete all programming and settings and there­fore should only be used on rare occasions when the the thermostat fails to function as designd and/or as pro­grammed. Such an instance can occur as a result of a pow­er surge or similar electrical disturbance (e.g. after an elec­trical storm or power outage). The RESET button can be used to recover from this situation.
CAUTION
When the RESET button is pressed, ALL settings re­vert back to the defaults, including the default pro­gram (see tables 2 and 3).
The RESET button is an unlabeled, recessed button lo­cated behind the door, on the right−hand side of the ther­mostat, below the SETTINGS button (see figure 3). Use a paper clip or small pencil to press the RESET button; ALL thermostat settings will be reset to the defaults listed in the Default Thermostat Settings section.
Removing/Installing Thermostat
The thermostat hinges on tabs on the top of the subbase; no tool is needed to remove the thermostat from the sub­base. Pivot the bottom of the thermostat outward (releas­ing the snaps), then lift up to remove.
To replace it, first position the top tilted toward the wall bracket and align it until you feel the tabs and slots engage; then, while the top is in place, pivot the bottom toward the wall until the thermostat snaps into place.
Page 7
51M37 SERIES 5/2
Default Thermostat Settings
CAUTION
Default thermostat settings are shown in table 2 and the default program is shown in table 3.
Table 2
Default Thermostat Settings
Mode Heat (Permanent Hold
Mode) Setpoint 70°F (or 21°C) Fan Auto Filter Reminder OFF Maintenance Reminder OFF Equipment Protection
Reset Back to Zero Timers
Table 3
Default Program Settings
Temperature
Programs Time
(Heat)
Weekday − A 6:00am 70_F / 21°C 78_F / 26°C Weekday − B 8:00am 62_F / 17°C 85_F / 29°C Weekday − C 6:00pm 70_F / 21°C 78_F / 26°C Weekday − D 10:00pm 62_F / 17°C 82_F / 28°C Weekend − A 6:00am 70_F / 21°C 78_F / 26°C Weekend − B 8:00am 62_F / 17°C 85_F / 29°C Weekend − C 6:00pm 70_F / 21°C 78_F / 26°C Weekend − D 10:00pm 62_F / 17°C 82_F / 28°C
Weekday Monday, Tuesday, Wednesday,
Thursday, Friday
Weekend Saturday, Sunday
Temperature (Cool)
24VAC is present on the terminals of the thermostat bracket. If removing the thermostat from the wall, use caution and avoid touching any of the connec­tor terminals on the wall bracket.
Also, when working with the thermostat dip switches, use a non−conductive tool and take cau­tion to avoid making any contact with the circuit board, its imprinted circuitry and its connector prongs.
Temperature Display
Display Scale: Fahrenheit or Celsius user selectable (via DIP switch; see figure 22) Display range: 35°F (2°C) to 99°F (37°C) Display resolution: 1°F (1°C) Display Accuracy: +/−1°F
If the Fahrenheit/Celsius display must be changed, use a plastic, non−conductive tool to push the dip switch to the right position (see figure 22).
Changing Fahrenheit/Celsius Setting
1 2 3 4 5 6
PLUG IN (Use Care To Avoid Bending Prongs.)
F/C (Fahrenheit/Celsius) switch shown in Celsius position
Figure 22
Technical Specifications
Thermostat Type
Electronic programmable thermostat for heat pump, 3-stage heat/2-stage cool.
NOTE − 2 stages of heat pump heat and one stage of auxil­iary (gas or electric) backup heat are supported.
Power Supply Range
18VAC − 30VAC (24VAC nominal), 60Hz
505050M 5/1/05
Temperature Measurement Range
Measurement Scale: Fahrenheit Measurement Range: 35°F to 99°F Measurement Resolution: 0.5°F Measurement Accuracy: +/−1°F Field Offset: via DIP switches to +/−3°F Sampling Method: temperature measurements sampled every 15 seconds. Displayed temperature is the average of the last four measurements.
Temperature Setpoint Range
Setting range: 50°F (10°C) to 90°F (32°C) Setting resolution: 1°F (1°C)
Page 8
Smart Setback Recovery (via DIP switch #6)
Smart Setback Recovery (SSR) affects the way the ther­mostat responds to program events. If SSR is disabled, the thermostat will react to a program event at the time the event occurs. However, if SSR is enabled, the thermostat will react to a program event before the event occurs such that the desired temperature is reached at the time of the event, not after.
Fan Control
AUTO or ON modes.
I/O Relays
All thermostat relays are latching type to minimize power consumption.
Table 4
51M37 Terminal Designations
Term. Description
B Reversing valve, heat active O Reversing valve, cool active R 24VAC Y1 First-stage cooling/heating, compressor
energized W1* Auxiliary heating, furnace energized Y2 Second-stage cooling/heating, compressor
energized E* Emergency heat G Fan control L Service Indicator C 24VAC common T Outdoor temperature sensor connection 1 T Outdoor temperature sensor connection 2
* For most applications, E will be jumpered to W1. If sep­arate wires are not provided for both E and W1, jumper the E terminal to the W1 terminal on the thermostat sub­base. For applications involving the use of a balance point (whereby the outdoor temperature is to be used to restrict either heat pump operation or backup heat source operation), the optional outdoor sensor (part number X2658) MUST be installed.
Equipment Protection Timers
Minimum Compressor OFF time: 5 minutes Minimum Compressor ON time: 4 minutes Minimum Furnace ON time: 3 minutes
Minimum furnace cycle time (elapsed time between any furnace activation and the next furnace activation): 6 min­utes.
Minimum elapsed time between any compressor activa­tion and the next compressor activation: 6 minutes.
NOTE − All protection timers (except the compressor OFF timer) can be over−ridden if a heating or cooling demand is initiated or terminated using the UP, DOWN, HEAT, or COOL buttons.
Equipment Protection Override
Both the minimum compressor OFF timer and the mini­mum equipment cycle timer can be over−ridden by press­ing and holding either the HEAT or COOL button down for 4 seconds.
Over−Temperature Protection
Thermal-mechanical switch opens W1, Y1, Y2, and E at 93°F+/−6°F.
Filter Reminder
Settings of Off, 1, 3, 6 or 12 (months of fan run time) are available. When programmed time has elapsed, a FILTER indicator is displayed.
Maintenance Reminder
Settings of Off, 6 or 12 (months of chronological time) are available. When programmed time has elapsed, a mainte­nance indicator MAINT" is displayed.
Service Reminder
The SERVICE indicator is displayed only under the follow­ing conditions:
S if the thermostat Y1 terminal has been activated with
24VAC for at least 5 minutes, AND the L terminal is shorted to the R terminal;
OR
S if the thermostat Y1 terminal has been activated with
24VAC for at least 5 minutes, AND the L terminal is shorted to the C terminal.
Power Loss/Recovery
Thermostat memory is retained for a minimum of 24 hours during a power loss (includes retention of program infor­mation, HOLD status, programmed temperature setpoint, heat/cool and fan mode settings, filter reminder status, maintenance reminder status, and equipment protection timers). After 24 hours of power loss, programmed settings will be lost and replaced with default settings.
IMPORTANT
Power must be applied for at least six consecutive hours prior to a power loss in order for memory to be retained for the specified time.
LCD Backlight
Activated for 30 seconds when any button is pressed.
NOTE − During an electrical storm or similar disturbance, the backlight may activate for a few seconds. This is nor­mal and will no longer occur after the electrical disturbance has passed.
Thermostat Operating Conditions
35°F to 105°F, 5% to 90% RH
Thermostat Storage Conditions
−40°F to 185°F, 5% to 95% RH
Page 9
51M37 SERIES 5/2
Thermostat Output Table
Table 5 depicts the 51M37 thermostat output states for var­ious input conditions. The following notes described terms used in the table.
NOTES:
S X = output is activated with 24VAC.
S BBP: outdoor temperature is below balance point
S ABP: outdoor temperature is above balance point
S In all cases, the state of the B terminal is opposite that
of the O terminal
S Data are tabulated for AUTO fan setting. If the fan set-
ting is ON, the G output is activated in all cases
S Upstage timers:
30 minutes (when upstaging from small to large demand)
15 minutes (HEAT MODE ONLY − when upstaging from large to very large demand)
S The temperature ranges expressed in the following
definitions of SMALL/LARGE/VERY LARGE" de­mands are for guidance only; actual temperatures may vary:
With a small HEAT demand, temperature is: below setpoint –0.5F but above setpoint –1.5F AND 30-minute upstage timer HAS NOT expired.
With a large HEAT demand, temperature is: less than setpoint –1.5F OR 30-minute upstage timer HAS expired.
With a very large heat demand, temperature is: below setpoint –2.5F OR 15−minute 2nd upstage timer HAS expired.
Emergency heat demand (only if emergency heat is enabled): temperature is below setpoint –0.5F.
With a small COOL demand, temperature is: above setpoint +0.5F but below setpoint +1.5F AND 30-minute upstage timer HAS NOT expired.
With a large COOL demand, temperature is: above setpoint +1.5F OR 30-minute upstage timer HAS expired.
Table 5
THERMOSTAT OUTPUTS
Demand Condition
W1 E Y1 Y2 G O
Cooling Demands
SMALL X X X
LARGE X X X X
No Demand X
Heating Demands
w/Electric Backup (no outdoor sensor)
SMALL X X
LARGE X X X
Very LARGE X X X X
Emergency X X
No Demand
w/Gas Backup (dual fuel; no outdoor sensor)
SMALL X X
LARGE X X X
Very LARGE X
Emergency X
No Demand
w/Electric Backup (outdoor sensor attached)
SMALL (Above Balance Point) X X
LARGE (ABP) X X X
Very LARGE (ABP) X X X
SMALL (Below Balance Point) X X
LARGE (BBP) X X X
Very LARGE (BBP) X X X X
Emergency X X
No Demand
w/Gas Backup (dual fuel; outdoor sensor attached)
SMALL (ABP) X X
LARGE (ABP) X X X
Very LARGE (ABP) X
SMALL (BBP) X
LARGE (BBP) X
Very LARGE (BBP) X
Emergency X
No Demand
505050M 5/1/05
Page 10
OPERATION
E2005 Lennox Industries Inc.
Dallas, Texas, USA
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
51M35 Merit® Series Thermostat
The Lennox Merit® Series 5/2 day programmable electronic thermostat 51M35 provides excellent temperature control and a large, easy-to-read display. This product includes a programmable filter change reminder, an equipment maintenance reminder, and a system check indicator to notify the user when the equipment requires service.
Thermostat 51M35 is suitable for non-heat pump, two­stage heat/two-stage cool applications using a gas or elec­tric furnace.
MANUAL
®
51M35 Merit
5/2 Day Programmable Thermostat
CONTROLS
505,049M 05/05 Supersedes 03/05
Table of Contents
51M35 Series Thermostat 1. . . . . . . . . . . . . . . . . . . . . .
General 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Introduction 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Initial Thermostat Power-up 1. . . . . . . . . . . . . . . . . . . . .
Buttons, Backlight, Timers & Settings 2. . . . . . . . . . . .
DAY/TIME − Set Day and Time 2. . . . . . . . . . . . . . . . . .
HEAT − Heat Mode 3. . . . . . . . . . . . . . . . . . . . . . . . . . . .
COOL − Cool Mode 3. . . . . . . . . . . . . . . . . . . . . . . . . . . .
HOLD − Temperature Hold Mode 4. . . . . . . . . . . . . . . .
PROG − Thermostat Programming 4. . . . . . . . . . . . . . .
FAN − Controlling Fan Operation 5. . . . . . . . . . . . . . . . .
SETTINGS − Filter /Maintenance Reminder 5. . . . . . .
Service Indicator 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Thermostat RESET 6. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Removing/Installing Thermostat 6. . . . . . . . . . . . . . . . .
Default Thermostat Settings 6. . . . . . . . . . . . . . . . . . . .
Technical Specifications 7. . . . . . . . . . . . . . . . . . . . . . . .
Thermostat Output Table 8. . . . . . . . . . . . . . . . . . . . . . .
Series
Litho U.S.A.
General
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities having jurisdiction before installation.
Check equipment for shipping damage. If you find any damage, immediately contact the last carrier.
Introduction
This document describes the operation of Lennox thermostat 51M35. Refer to the installation manual for instructions re­garding installation and wiring of the thermostat.
Initial Thermostat Power-up
When power is initially applied to the thermostat, the dis­play will appear as shown in figure 1.
Initial Power−Up Display
MO TU WE TH FR SA SU
AM
I8:88
PM
PROG A | B | C | D HOLD
ROOM
SETPOINT
°
°
88
All display segments are momentarily activated. This oc­curs as a normal part of thermostat initialization.
88
Figure 1
MAINT
FILTER
SERVICE
FAN ON AUTO
SYSTEM COOL OFF EMG. HEAT
Hi Lo
05/05 505,049M
Page 1
*2P0505* *P505049M*
Within a few seconds, the Home Screen appears (see fig­ure 2) with default settings as shown. After about 1 minute of initialization time, the actual room temperature will be displayed.
NOTE − Tables 2 and 3 on page 6 show all system and programming defaults.
MO TU WE TH FR SA SU
Home Screen
MAINT
FILTER
SERVICE
AM
I2:00
PM
PROG A B C D HOLD
ROOM
°
70
FAN
ON
AUTO
SYSTEM
COOL OFF
HEAT
Figure 2
At this point, the thermostat will be fully functional; its de­fault temperature setpoint (not shown) is 70°F. At this point, if the equipment has been fully powered and if a heat demand were present, the system would begin operating.
NOTE − Temperature scale default is Fahrenheit units but may be reset to show Celsius, if desired. See page 7.
Buttons, Backlight, Timers & Settings
Buttons are located behind the small door on the right− hand side of the thermostat (see figure 3).
IMPORTANT
Do NOT begin pressing buttons until after you read the following section describing each button.
A pale blue display backlight illuminates for 30 seconds each time any button is pressed.
When PROG or DAY/TIME is pressed, a field begins flash­ing, expecting another input. Start making changes within 15 seconds or the HOME screen will return.
Thermostat Buttons
Heat
Cool
Prog
Day/Time
Fan
Hold
Settings
Enter
(DOOR OPEN)
Figure 3
When an Arrow, HOLD, HEAT, or COOL button is pressed, SETPOINT and the temperature setting appears for 15 seconds. If desired, start making changes within 15 sec­onds or the HOME screen will return. The backlight will turn off 15 seconds after the HOME screen reappears.
DAY/TIME − Setting the Day and Time
Press the DAY/TIME button and set the CURRENT hour, minute, and day of week as follows:
1. AM12" will flash on the screen. Press the UP/DOWN arrows to change the hour. (AM" or PM" must corre­spond to time of day.) Press DAY/TIME OR, if adjust-
ing for daylight savings time, pressing ENTER stores the single change and exits to the HOME screen, by­passing minutes and day of week.
2. Minutes will flash. Use the UP/DOWN arrow button to display the minutes past the hour. Press DAY/TIME.
3. Day MO" (Monday) will flash. Use UP or DOWN arrow buttons to display the current day. Day selections are abbreviated as MO, TU", WE", TH", FR", SA", and SU". Press DAY/TIME.
4. The HOME screen reappears; confirm day and time are correct. This completes day and time setting.
505049M 5/1/05
Page 2
HEAT − Using the Heat Mode
COOL − Using the Cool Mode
Enabling and Disabling Heat Mode
The thermostat must be in the HEAT mode to control the heating equipment. Press the Heat button to enable or dis­able HEAT mode. If the thermostat is in COOL or OFF mode, pressing the Heat button enables the HEAT mode (indicated by HEAT in the SYSTEM box − see figure 4).
Turn Heat ON/OFF
Heat
Prog
Fan
Settings
Cool
Day/Time
Hold
Enter
MO
AM
PM
ROOM
66
5:30
HOLD
SETPOINT
°
70
°
FAN
AUTO
SYSTEM
HEAT
Figure 4
If the thermostat is in heat mode, pressing the Heat button disables HEAT mode (indicated by OFF in the SYSTEM box − see figure 5).
Heat/Cool Mode Disabled
°
SYSTEM
COOL
OFF
HEAT
ROOM
75
°
SETPOINT
75
Figure 5
Heating Demand
Set the thermostat to heat mode to control the heating equipment. Then, if the room temperature is lower than the temperature setpoint, as shown in figure 6, the thermostat detects a heating demand and will activate the heating equipment to satisfy the demand.
Heating Demand
°
SYSTEM
COOL OFF
HEAT
ROOM
72
°
SETPOINT
75
Figure 6
Heating operation is indicated by a flame icon in the SYS­TEM box. When the actual temperature rises above the temperature setpoint, the flame icon will disappear. This indicates that the heating demand has been satisfied and that the heating equipment has been turned off.
If your system supports 2−stage heating (as does the 51M35 thermostat), you may notice various heating levels being delivered during a demand.
NOTE − Heating equipment is activated for at least 3 min­utes if no buttons are pressed during the demand interval.
Enabling and Disabling Cool Mode
Use the COOL button to enable or disable cool mode as desired. If the thermostat is in HEAT or OFF mode, cool mode is enabled when the COOL button is pressed. This is indicated by COOL in the SYSTEM box (see figure 8).
Turn Cool ON/OFF
Heat
Prog
Fan
Settings
Cool
Day/Time
Hold
Enter
MO
AM
PM
I0:30
ROOM
75
SETPOINT
°
70
HOLD
°
FAN
AUTO
SYSTEM COOL
Figure 7
If the thermostat is in cool mode, pressing the Cool button disables COOL mode (indicated by OFF in the SYSTEM box − see figure 5).
Cooling Demand
Set the thermostat to cool mode to control the cooling equipment. Then, if the room temperature is higher than the temperature setpoint, as shown in figure 8, the thermo­stat detects a cooling demand and will activate the cooling equipment to satisfy the demand.
Cooling Demand
°
SYSTEM COOL
OFF
HEAT
ROOM
75
SETPOINT
°
70
Figure 8
Cooling operation is indicated by flashing snowflake" icons in the SYSTEM box. When the actual temperature drops below the temperature setpoint, the snowflake icons will disappear. This indicates that the cooling demand has been satisfied and that the cooling equipment has been turned off.
If your system supports 2−stage cooling (as does the 51M35 thermostat), you may notice various cooling levels being delivered during a demand. Also, if a small cooling demand is present, "Lo" will be displayed in the SYSTEM box. However, if a large cooling demand is present, "Hi" will be displayed in the SYSTEM box (shown in figure 8).
NOTE − If no buttons are pressed during a demand for cooling, the equipment must operate for at least 4 minutes. After a demand has been satisfied, cooling equipment op­eration is locked out for 5 minutes. If another cooling de­mand occurs during this 5−minute interval, COOL" and the snowflakes will flash; however, the cooling equipment will not operate until the 5−minute delay has elapsed.
Page 3
Hi
51M35 SERIES 5/2
HOLD − Using Temperature Hold Modes
PROG − Thermostat Programming
When HOLD is displayed at the HOME screen, the ther­mostat is in a temperature hold condition. This means that the temperature program data is ignored and the thermo­stat functions much like a non−programmable thermostat.
Adjusting Temperature Setpoint in Hold Mode
The temperature setpoint represents the desired tempera­ture of the space around the thermostat. The default tem­perature setpoint in Hold mode is 70°F.
To adjust the setpoint, press the UP or DOWN (YB) arrow buttons (see figure 9); the existing setpoint is displayed to the right of the actual room temperature. Each button press adjusts the setpoint up or down by 1 degree.
Hold Temperature Mode
MO
AM
PM
I0:36
ROOM
72
°
HOLD
SETPOINT
68
°
FAN
AUTO
SYSTEM COOL
Heat
Prog
Fan
Settings
Cool
Day/Time
Hold
Enter
Figure 9
After the desired setpoint is reached, the HOME screen will reappear after about 15 seconds.
Permanent Hold Mode
At any time the program is running, from the HOME screen, set a permanent hold (program override) by press­ing the HOLD button (see figure 9). The thermostat now functions much like a non−programmable thermostat. Use the Up/Down arrow buttons to adjust the hold setpoint. To return to the program, press HOLD again.
Temporary (2-Hour) Hold
At any time the program is running, from the HOME screen, set a temporary 2-hour hold by pressing the Up/ Down arrow buttons until the desired setpoint is displayed; HOLD" flashes (see figure 10). This overrides the pro­gram for 2 hours from the last button press, then returns to the program.
Temporary Hold Temperature Mode
MO
AM
PM
I0:36
PROG B HOLD
ROOM
°
72
SETPOINT
68
°
FAN
AUTO
SYSTEM COOL
Heat
Prog
Fan
Settings
Cool
Day/Time
Hold
Enter
Figure 10
While in Temporary Hold, press HOLD once to switch to Permanent Hold (HOLD displays solid; PROG not dis­played); press HOLD again to return to the program (PROG displays; HOLD not displayed).
The 51M35 thermostat can be programmed to perform a set of either heating or cooling events (but not a combination of heat and cool) for 5 consecutive days using a set of 4 unique events per day. The remaining 2 days can then be set for a different set of 4 unique events per day. Both the consecutive days and the events/temperature are set by the homeowner.
To Change Consecutive Days...
To alter the 5 consecutive days, press and hold the PROG button for 5 seconds. The existing 5 consecutive day peri­od is then displayed (default is MOnday thru FRiday). To change to a different 5-consecutive days, use the Up/ Down arrow buttons. Any 5 consecutive−day span may be selected, for example, in figure 11, Saturday through Wednesday is defined as the 5−day programming (Thurs­day and Friday would constitute the 2−day programming). Press the PROG button when finished.
Change Consecutive days
MO TU WE TH FR SA SU
FILTER
Figure 11
To Set Program Events and Temperatures...
Figure 12 gives an example of how the two sets of pro­grams can be set for a normal workweek and weekend.
In the 5−day bar graph, note how programs A and C reflect the desired warmth while the home IS occupied (72°); B allows less heating while the home is NOT occupied; D re­flects a cool sleeping temperature. The 2−day bar graph would support day−long occupancy and, because the first program begins later, a less−demanding time schedule.
5/2 Program Example
5−DAY PROGRAM:
2−DAY PROGRAM:
|A | B | C | D |
72°
68°
64°
6AM NOON 6PM MID 6AM
|A| B | C | D |
72°
68°
64°
6AM NOON 6PM MID 6AM
NIGHT
NIGHT
Figure 12
NOTE − Pressing ENTER during the following program­ming steps, saves and exits to the HOME screen.
To program events and temperatures, perform the follow­ing steps, once with Cool selected and once with Heat se­lected.
1. Press and release PROG. AM 6:00", period A", and the 5 consecutive days are displayed; AM 6" flashes.
2. Use the Up/Down arrow buttons to select the desired hour; press PROG when the desired hour is reached.
3. Use the Up/Down arrow buttons to select the desired minute; press PROG.
4. Use the Up/Down arrow buttons to select the desired temperature setpoint; press PROG.
5. Repeat steps 2 through 4 for periods B, C, and D.
6. Repeat steps 1 through 5 for the 2−day program.
505049M 5/1/05
Page 4
NOTE − This thermostat will NOT automatically switch
(1st
)
(Off, 1, 3, 6, 12); f
(2nd
)
(Off, 6, 12). U
thi
from heating to cooling, or vice versa; operator involve­ment is required. At the change of seasons, or to accomo­date abnormal seasonal temperature swings, you must manually select to the opposite conditioning (Heat or Cool) program.
FAN − Controlling the Fan Operation
Reminder Settings Display
OFF
MAINT
FILTER
For MAINT, press Settings button 2 times
For FILTER, press Settings button 1 time
Use the FAN button to select either continuous fan mode or auto fan mode.
To change from continuous to auto fan mode (or vice ver­sa), press the FAN button. Note whether a fan icon in the FAN box is present (indicating that the fan is running) or not (fan not running).
If continuous fan mode is enabled (ON displayed in FAN box − see figure 13), the fan will run continuously regard­less of whether the heating or cooling equipment is run­ning.
MO
AM
PM
PROG B
ROOM
67
Using Fan ON
FAN
I0:I0
°
ON
SYSTEM
HEAT
Heat
Prog
Fan
Settings
Cool
Day/Time
Hold
Enter
Figure 13
If auto fan mode is selected (AUTO displayed in FAN box − see figure 14), the fan will only run when the heating or cooling equipment is running.
MO
AM
PM
I0:36
PROG B
ROOM
72
Using Fan Auto
FAN
AUTO
SYSTEM COOL
°
Heat
Prog
Fan
Settings
Cool
Day/Time
Hold
Enter
Figure 14
SETTINGS − Filter/Maintenance Reminders
The 51M35 thermostat is designed to remind you when the filter needs changing or when routine maintenance is re­quired, as (and if) defined, by you. These optional remind­ers are not enabled until you activate them. To do so, press the Settings button (shown below the Fan button in figure
14) once or twice for the desired reminder as shown in fig­ure 15 and as described in table 1.
Figure 15
The default setting for the reminders is OFF (disabled). Press Up/Down arrow buttons to select the desired re­minder intervals.
Table 1
Filter and Maintenance Reminders
Buttons to
Use
Settings
press
then Arrows
to scroll
selections
Settings
press
then Arrows
to scroll
selections
Enter Stores settings.
Reminder
FILTER
MAINT
NOTE − The HOME screen will reappear about 15 seconds after the final arrow button press. OR, press ENTER at any time to store any changes and exit to the HOME screen.
After either programmed interval has elapsed, the remind­er will be displayed as shown in figure 16.
MO TU WE TH FR SA SU
AM
PM
I0:i2
PROG A B C D HOLD
ROOM
°
78
Available Settings and How to Use
Total fan run time expressed in months example, if fan runs 12 hours a day, 1 month reminder displays in 2 calendar months.
Elapsed chronological time in months for example, to remind yourself when to perform routine checks or when to call a technician for perodic preventive maintenance.
Reminders
MAINT
FILTER
SERVICE
FAN
ON
AUTO
SYSTEM
COOL OFF
HEAT
se
or
s,
Figure 16
After the filter has been changed or maintenance per­formed, reset the reminder by pressing the SETTINGS button for 4 seconds. The screen will blink for a few mo­ments to indicate that the timer has been reset.
Page 5
51M35 SERIES 5/2
Service Indicator
Removing and Installing Thermostat
When abnormal equipment operation is detected, the SERVICE indicator will flash on the screen (see figure 17). This indicates that the equipment requires service from a qualified service technician.
Service Indicator Flashing
MO TU WE TH FR SA SU
AM
I0:i4
PM
PROG A B C D HOLD
ROOM
°
79
Figure 17
FILTER
SERVICE
FAN
ON
AUTO
SYSTEM
COOL OFF
HEAT
Thermostat RESET
Under some abnormal conditions, it may be necessary to reset" the thermostat to its default condition. Such a RE­SET would delete all programming and settings and there­fore should only be used on rare occasions when the the thermostat fails to function as designd and/or as pro­grammed. Such an instance can occur as a result of a pow­er surge or similar electrical disturbance (e.g. after an elec­trical storm or power outage). The RESET button can be used to recover from this situation.
CAUTION
When the RESET button is pressed, ALL settings re­vert back to the defaults, including the default pro­gram (see tables 2 and 3).
The RESET button is an unlabeled, recessed button lo­cated behind the door on the right−hand side of the thermo­stat, below the SETTINGS button (see figure 3). Use a pa­per clip or small pencil to press the RESET button; ALL thermostat settings will be reset to the defaults listed in the Default Thermostat Settings section.
The thermostat hinges on tabs on the top of the subbase; no tool is needed to remove the thermostat from the sub­base. Pivot the bottom of the thermostat outward (releas­ing the snaps), then lift up to remove.
To install it, first position the top tilted toward the wall brack­et and align it until you feel the tabs and slots engage; then, while the top is in place, pivot the bottom toward the wall until the thermostat snaps into place.
Default Thermostat Settings
Default thermostat settings are in table 2 and the default program is shown in table 3.
Table 2
Default Thermostat Settings
Mode Heat (Permanent Hold
Mode) Setpoint 70°F (or 21°C) Fan Auto Filter Reminder OFF Maintenance Reminder OFF Equipment Protection
Timers
Default Program Settings
Programs Time
Weekday − A 6:00am 70_F / 21°C 78_F / 26°C Weekday − B 8:00am 62_F / 17°C 85_F / 29°C Weekday − C 6:00pm 70_F / 21°C 78_F / 26°C Weekday − D 10:00pm 62_F / 17°C 82_F / 28°C Weekend − A 6:00am 70_F / 21°C 78_F / 26°C Weekend − B 8:00am 62_F / 17°C 85_F / 29°C Weekend − C 6:00pm 70_F / 21°C 78_F / 26°C Weekend − D 10:00pm 62_F / 17°C 82_F / 28°C
Weekday Monday, Tuesday, Wednesday,
Thursday, Friday
Weekend Saturday, Sunday
Reset Back to Zero
Table 3
Temperature (Heat)
Temperature (Cool)
505049M 5/1/05
Page 6
Technical Specifications
Thermostat Type
Electronic programmable thermostat for 2−Stage (gas or electric) Heat/2-Stage Cool, non−heat pump, non−power robbing applications.
Power Supply Range
18VAC − 30VAC (24VAC nominal), 60Hz
CAUTION
24VAC is present on the terminals of the thermostat bracket. If removing the thermostat from the wall, use caution and avoid touching any of the connec­tor terminals on the wall bracket.
Also, when working with the thermostat dip switches, use a non−conductive tool and take cau­tion to avoid making any contact with the circuit board, its imprinted circuitry and its connector prongs.
Temperature Display
Display Scale: Fahrenheit or Celsius user selectable (via DIP switch; see figure 18) Display range: 35°F (2°C) to 99°F (37°C) Display resolution: 1°F (1°C) Display Accuracy: +/−1°F
If the Fahrenheit/Celsius display must be changed, use a plastic, non−conductive tool to push the dip switch to the right position (see figure 18).
Temperature Setpoint Range
Setting range: 50°F (10°C) to 90°F (32°C) Setting resolution: 1°F (1°C)
Smart Setback Recovery (via DIP switch #6)
Smart Setback Recovery (SSR) affects the way the ther­mostat responds to program events. If SSR is disabled, the thermostat will react to a program event at the time the event occurs. However, if SSR is enabled, the thermostat will react to a program event before the event occurs such that the desired temperature is reached at the time of the event, not after.
Fan Control
AUTO or ON modes, gas or electric heat compatible via DIP switches (also see Thermostat Output section).
I/O Relays
All thermostat relays are latching type to minimize power consumption.
Table 4
51M35 Terminal Designations
Terminal Description
R 24VAC Y1 First-stage cooling W1 First-stage heating Y2 Second-stage cooling W2 Second-stage heating G Fan control L Service Indicator C 24VAC common
Changing Fahrenheit/Celsius Setting
1 2 3 4 5 6
PLUG IN (Use Care To Avoid Bending Prongs.)
F/C (Fahrenheit/Celsius) switch shown in Celsius position
Figure 18
Temperature Measurement Range
Measurement Scale: Fahrenheit Measurement Range: 35°F to 99°F Measurement Resolution: 0.5°F Measurement Accuracy: +/−1°F Field Offset: via DIP switches to +/−3°F Sampling Method: temperature measurements sampled every 15 seconds. Displayed temperature is the average of the last four measurements.
Equipment Protection Timers
Minimum Compressor OFF time: 5 minutes Minimum Compressor ON time: 4 minutes Minimum Furnace ON time: 3 minutes
Minimum furnace cycle time (elapsed time between any furnace activation and the next furnace activation): 6 min­utes.
Minimum elapsed time between any compressor activa­tion and the next compressor activation: 6 minutes.
NOTE − All protection timers (except the compressor OFF timer) can be over−ridden if a heating or cooling demand is initiated or terminated using the UP, DOWN, HEAT, or COOL buttons.
Equipment Protection Override
Both the minimum compressor OFF timer and the mini­mum equipment cycle timer can be over−ridden by press­ing and holding either the HEAT or COOL button down for 4 seconds.
Over−Temperature Protection
Thermal-mechanical switch opens W1 and W2 at 93°F+/−6°F.
Filter Reminder
Settings of Off, 1, 3, 6 or 12 (months of fan run time) are available. When programmed time has elapsed, a FILTER indicator is displayed.
Page 7
51M35 SERIES 5/2
Loading...
+ 37 hidden pages