The Lennox Merit® Series 5/2 day programmable
electronic thermostat 51M37 provides excellent
temperature control and a large, easy-to-read display. It
includes a programmable filter change reminder, an
equipment maintenance reminder, and a system check
indicator to notify the user when the equipment requires
service.
The 51M37 is suitable for heat pump, 3-stage heat/2-stage
cool applications using a gas or electric auxiliary heat
source. An optional outdoor temperature sensor provides
auxiliary heat lockout, balance point operation, and
dual−fuel compatibility.
These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
having jurisdiction before installation.
Check equipment for shipping damage. If you find any
damage, immediately contact the last carrier.
Introduction
This document describes the operation of Lennox thermostat
51M37. Refer to the installation manual for instructions regarding installation and wiring of the thermostat.
Initial Thermostat Power-up
When power is initially applied to the thermostat, the display will appear as shown in figure 1.
Initial Power−Up Display
MO TU WE TH FR SA SU
AM
I8:88
PM
PROG A | B | C | D HOLD
ROOM
SETPOINT
°
°
88
All display segments are momentarily activated. This occurs as a normal part of thermostat initialization.
88
Figure 1
MAINT
FILTER
SERVICE
FAN
ON
AUTO
SYSTEM
COOL
OFF
EMG.
HEAT
Hi
Lo
05/05505,050M
Page 1
*2P0505**P505050M*
Within a few seconds, the Home Screen appears (see figure 2) with default settings as shown. After about 1 minute
of initialization time, the actual room temperature will be
displayed.
NOTE − Tables 2 and 3 on page 8 show all system and
programming defaults.
Home Screen
MO TU WE TH FR SA SU
MAINT
FILTER
SERVICE
AM
I2:00
PM
PROGA B C DHOLD
ROOM
°
70
FAN
ON
AUTO
SYSTEM
COOL
OFF
HEAT
Figure 2
At this point, the thermostat will be fully functional; its default temperature setpoint (not shown) is 70°F. At this
point, if the equipment has been fully powered and if a heat
demand were present, the system would begin operating.
NOTE − Temperature scale default is Fahrenheit units but
may be reset to show Celsius, if desired. See page 8.
Buttons, Backlight, Timers & Settings
Buttons are located behind the small door on the right−
hand side of the thermostat (see figure 3).
IMPORTANT
Do NOT begin pressing buttons until after you read
the following section describing each button.
A pale blue display backlight illuminates for 30 seconds
each time any button is pressed.
When PROG or DAY/TIME is pressed, a field begins flashing, expecting another input. Start making changes within
15 seconds or the HOME screen will return.
Thermostat Buttons
Heat
Cool
Prog
Day/Time
Fan
Hold
Settings
Enter
(DOOR
OPEN)
Figure 3
When an Arrow, HOLD, HEAT, or COOL button is pressed,
SETPOINT and the temperature setting appears for 15
seconds. If desired, start making changes within 15 seconds or the HOME screen will return. The backlight will
turn off 15 seconds after the HOME screen reappears.
DAY/TIME − Setting the Day and Time
Press the DAY/TIME button and set the CURRENT hour,
minute, and day of week as follows:
1. AM12" will flash on the screen. Press the Up/Down arrows buttons to change the hour. (AM" or PM" must
correspond to time of day.) Press DAY/TIME OR, if ad-
justing for daylight savings time, pressing ENTER
stores the single change and exits to the HOME
screen, bypassing minutes and day of week.
2. Minutes will flash. Use the Up/Down arrow buttons to
display the minutes past the hour. Press DAY/TIME.
3. Day MO" (Monday) will flash. Use Up/Down arrow
buttons to display the current day. Day selections are
abbreviated as MO, TU", WE", TH", FR", SA",
and SU". Press DAY/TIME.
4. The HOME screen reappears; confirm day and time
are correct. This completes day and time setting.
505050M 5/1/05
Page 2
HEAT − Using the Heat Mode
Normal Heat Mode
In normal heat mode, both the heat pump and the backup
heat source are used to provide heat. If the thermostat detects that the heat pump is not able to provide enough heat
(as may be the case in very cold weather), then the backup
heat source is activated.
Emergency Heat Mode
In emergency heat mode, only the backup heat source
provides heat the heat pump is disabled. The backup
heat source is activated only when there is a heat demand.
Enabling Normal Heat Mode
Use the HEAT button to select normal heat mode, emergency heat mode, or to disable heat modes as desired. If
the thermostat is in OFF or COOL mode, pressing the Heat
button enables Heat mode. This is indicated by HEAT in
the SYSTEM box as shown in figure 4.
Normal Heat Mode Enabled
Heat
Prog
Fan
Settings
Day/Time
°
Cool
Hold
Enter
SYSTEM
COOL
OFF
EMG.
HEAT
MO
AM
5:30
PM
ROOM
°
66
Enabling Emergency Heat Mode
If the thermostat is in heat mode, pressing the Heat button
enables EMG. HEAT mode (see figure 5). If the thermostat
is in normal heat mode when the HEAT button is pressed,
then emergency heat mode is enabled.
Emergency Heat Mode Enabled
ROOM
62
Disabling Heat Mode
If the thermostat is in emergency heat mode when the
HEAT button is pressed, then heat modes are disabled.
This is indicated by OFF in the SYSTEM box as shown in
figure 6.
HOLD
SETPOINT
70
°
FAN
AUTO
SYSTEM
HEAT
°
Figure 4
SETPOINT
75
Figure 5
Heat Mode Disabled
°
°
°
SYSTEM
COOL
OFF
HEAT
SYSTEM
COOL
OFF
HEAT
SYSTEM
COOL
OFF
Hi
HEAT
ROOM
75
Heating Demand
The thermostat must be in either normal or emergency
heat mode in order to properly control the heating equipment. In either heat mode, when the actual temperature is
lower than the temperature setpoint (as shown in figure 7),
the thermostat detects a heating demand and activates the
heating equipment to satisfy the demand. Heating operation is indicated by a flame icon in the SYSTEM box.
ROOM
72
When the actual temperature rises above the temperature
setpoint, the flame icon will disappear. This indicates that
the heating demand has been satisfied and that the heating equipment has been turned off.
Heat pump operation is locked out for 5 minutes after a demand has been satisfied. If another heat pump demand
occurs during this 5−minute interval, the flame icon will
flash; however, the heat pump will not run until the 5−minute delay has elapsed.
NOTE − The heat pump is activated for at least 4 minutes if
no buttons are pressed during the demand interval. The
backup heat source is activated for at least 3 minutes if no
buttons are pressed during the demand interval.
If your system supports 3−stage heating (as does the
51M37 thermostat), you may notice various heating levels
being delivered during a demand.
If a small heat pump heating demand is present, "Lo" is displayed in the SYSTEM box; if a large heat pump heating
demand is present, "Hi" is displayed (see figure 8).
Large Heat Demand
ROOM
SETPOINT
°
75
Figure 6
Heating Demand
SETPOINT
°
75
Figure 7
SETPOINT
°
65
75
Figure 8
Page 3
51M37 SERIES 5/2
COOL − Using the Cool Mode
Enabling and Disabling Cool Mode
Use the COOL button to enable or disable cool mode as
desired. If the thermostat is in HEAT or OFF mode, cool
mode is enabled when the COOL button is pressed. This is
indicated by COOL in the SYSTEM box (see figure 9).
Cooling Demand
Set the thermostat to cool mode to control the cooling
equipment. Then, if the room temperature is higher than
the temperature setpoint, as shown in figure 11, the thermostat detects a cooling demand and will activate the cooling equipment to satisfy the demand.
Cooling Demand
MO TU WE TH FR SA SU
Turn Cool ON/OFF
Heat
Prog
Fan
Settings
Day/Time
°
Cool
Hold
Enter
SYSTEM
COOL
OFF
HEAT
MO
AM
PM
I0:30
ROOM
°
75
If the thermostat is in cool mode, pressing the Cool button
disables COOL mode (indicated by OFF in the SYSTEM
box − see figure 10).
ROOM
75
FAN
HOLD
AUTO
SYSTEM
COOL
SETPOINT
°
70
Figure 9
Cool Mode Disabled
SETPOINT
°
75
Figure 10
AM
i0:00
PM
PROGA B C DHOLD
ROOM
SETPOINT
°
75
Cooling operation is indicated by flashing snowflake"
icons in the SYSTEM box. When the actual temperature
drops below the temperature setpoint, the snowflake icons
will disappear. This indicates that the cooling demand has
been satisfied and that the cooling equipment has been
turned off.
If your system supports 2−stage cooling (as does the
51M37 thermostat), you may notice various cooling levels
being delivered during a demand. Also, if a small cooling
demand is present, "Lo" will be displayed in the SYSTEM
box. However, if a large cooling demand is present, "Hi" will
be displayed in the SYSTEM box (shown in figure 11).
NOTE − If no buttons are pressed during a demand for
cooling, the equipment must operate for at least 4 minutes.
After a demand has been satisfied, cooling equipment operation is locked out for 5 minutes. If another cooling demand occurs during this 5−minute interval, COOL" and the
snowflakes will flash; however, the cooling equipment will
not operate until the 5−minute delay has elapsed.
70
Figure 11
°
FAN
ON
AUTO
SYSTEM
COOL
OFF
Hi
HEAT
505050M 5/1/05
Page 4
HOLD − Using Temperature Hold Modes
PROG − Thermostat Programming
When HOLD is displayed at the HOME screen, the thermostat is in a temperature hold condition. This means that
the temperature program data is ignored and the thermostat functions much like a non−programmable thermostat.
Adjusting Temperature Setpoint in Hold Mode
The temperature setpoint represents the desired temperature of the space around the thermostat. The default temperature setpoint in Hold mode is 70°F.
To adjust the setpoint, press the UP or DOWN (YB) arrow
buttons (see figure 12); the existing setpoint is displayed to
the right of the actual room temperature. Each button
press adjusts the setpoint up or down by 1 degree.
Hold Temperature Mode
MO
AM
PM
I0:36
ROOM
72
°
HOLD
SETPOINT
68
°
FAN
AUTO
SYSTEM
COOL
Heat
Prog
Fan
Settings
Cool
Day/Time
Hold
Enter
Figure 12
After the desired setpoint is reached, the HOME screen
will reappear after about 15 seconds.
Permanent Hold Mode
At any time the program is running, from the HOME
screen, set a permanent hold (program override) by pressing the HOLD button (see figure 12). The thermostat now
functions much like a non−programmable thermostat. Use
the Up/Down arrow buttons to adjust the hold setpoint. To
return to the program, press HOLD again.
Temporary (2-Hour) Hold
At any time the program is running, from the HOME
screen, set a temporary 2-hour hold by pressing the Up/
Down arrow buttons until the desired setpoint is displayed;
HOLD" flashes (see figure 13). This overrides the program for 2 hours from the last button press, then returns to
the program.
Temporary Hold Temperature Mode
MO
AM
PM
I0:36
PROG BHOLD
ROOM
°
72
SETPOINT
68
°
FAN
AUTO
SYSTEM
COOL
Heat
Prog
Fan
Settings
Cool
Day/Time
Hold
Enter
Figure 13
While in Temporary Hold, press HOLD once to switch to
Permanent Hold (HOLD displays solid; PROG not displayed); press HOLD again to return to the program
(PROG displays; HOLD not displayed).
The 51M37 thermostat can be programmed to perform a
set of either heating or cooling events (but not a
combination of heat and cool) for 5 consecutive days using
a set of 4 unique events per day. The remaining 2 days can
then be set for a different set of 4 unique events per day.
Both the consecutive days and the events/temperature are
set by the homeowner.
To Change Consecutive Days...
To alter the 5 consecutive days, press and hold the
PROG button for 5 seconds. The 5 consecutive day period
is then displayed (default is MOnday thru FRiday). To
change to a different 5-consecutive days, use the Up/
Down arrow buttons. Any 5 consecutive−day span may be
selected, for example, in figure 14, Saturday through
Wednesday is defined as the 5−day programming (Thursday and Friday would constitute the 2−day programming).
Press the PROG button when finished.
Change Consecutive days
MO TU WE TH FR SA SU
Figure 14
To Set Program Events and Temperatures...
Figure 15 gives an example of how the two sets of programs can be set for a normal workweek and weekend.
In the 5−day bar graph, note how programs A and C reflect
the desired warmth while the home IS occupied (72°); B
allows less heating while the home is NOT occupied; D reflects a cooler sleeping temperature. The 2−day bar graph
would support day−long occupancy and, because the first
program begins later, a less−demanding time schedule.
5/2 Program Example
5−DAY PROGRAM:
2−DAY PROGRAM:
|A |B| C | D|
72°
68°
64°
6AMNOON 6PMMID6AM
|A| B |C |D|
72°
68°
64°
6AM NOON6PMMID6AM
NIGHT
NIGHT
Figure 15
NOTE − Pressing ENTER during the following programming steps, saves and exits to the HOME screen.
To program events and temperatures, perform the following steps, once with Cool selected and once with Heat selected.
1. Press and release PROG. AM 6:00", period A", and
the 5 consecutive days are displayed; AM 6" flashes.
2. Use the Up/Down arrow buttons to select the desired
hour; press PROG when the desired hour is reached.
3. Use the Up/Down arrow buttons to select the desired
minute; press PROG.
4. Use the Up/Down arrow buttons to select the desired
temperature setpoint; press PROG.
Page 5
FILTER
51M37 SERIES 5/2
5. Repeat steps 2 through 4 for periods B, C, and D.
(1st
)
(Off, 1, 3, 6, 12); f
(2nd
)
(Off, 6, 12). U
thi
6. Repeat steps 1 through 5 for the 2−day program.
NOTE − This thermostat will NOT automatically switch
from heating to cooling, or vice versa; operator involvement is required. At the change of seasons, or to accomodate abnormal seasonal temperature swings, you must
manually select to the opposite conditioning (Heat or Cool)
program.
FAN − Controlling the Fan Operation
Use the FAN button to select either continuous fan mode or
auto fan mode.
To change from continuous to auto fan mode (or vice versa), press the FAN button. Note whether a fan icon in the
FAN box is present (indicating that the fan is running) or not
(fan not running).
If continuous fan mode is enabled (ON displayed in FAN
box − see figure 16), the fan will run continuously regardless of whether the heating or cooling equipment is running.
MO
AM
PM
PROG B
ROOM
67
Using Fan ON
FAN
I0:I0
°
ON
SYSTEM
HEAT
Heat
Prog
Fan
Settings
Cool
Day/Time
Hold
Enter
Reminder Settings Display
MAINT
FILTER
OFF
For MAINT,
press Settings
button 2 times
For FILTER,
press Settings
button 1 time
Figure 18
The default setting for the reminders is OFF (disabled).
Press Up/Down arrow buttons to select the desired reminder intervals.
Table 1
Filter and Maintenance Reminders
Buttons to
Use
Settings
press
then Arrows
to scroll
selections
Settings
press
then Arrows
to scroll
selections
EnterStores settings.
Reminder
FILTER
MAINT
Available Settings and
How to Use
Total fan run time expressed in
months
example, if fan runs 12 hours a
day, 1 month reminder displays
in 2 calendar months.
Elapsed chronological time in
months
for example, to remind yourself
when to perform routine checks
or when to call a technician for
perodic preventive
maintenance.
se
or
s,
Figure 16
If auto fan mode is selected (AUTO displayed in FAN box −
see figure 17), the fan will only run when the heating or
cooling equipment is running.
MO
AM
PM
I0:36
PROG B
ROOM
72
Using Fan Auto
FAN
AUTO
SYSTEM
COOL
°
Heat
Prog
Fan
Settings
Cool
Day/Time
Hold
Enter
Figure 17
SETTINGS − Filter/Maintenance Reminders
The 51M37 thermostat is designed to remind you when the
filter needs changing or when routine maintenance is required, as (and if) defined, by you. These optional reminders are not enabled until you activate them. To do so, press
the Settings button (shown below the Fan button in figure
17) once or twice for the desired reminder as shown in figure 18 and as described in table 1.
NOTE − The HOME screen will reappear about 15 seconds
after the final arrow button press. OR, press ENTER at any
time to store any changes and exit to the HOME screen.
After either programmed interval has elapsed, the reminder will be displayed as shown in figure 19.
Reminders
MO TU WE TH FR SA SU
AM
PM
I0:i2
PROG A B C DHOLD
ROOM
°
78
MAINT
FILTER
SERVICE
FAN
ON
AUTO
SYSTEM
COOL
OFF
HEAT
Figure 19
After the filter has been changed or maintenance performed, reset the reminder by pressing the SETTINGS
button for 4 seconds. The screen will blink for a few moments to indicate that the timer has been reset.
505050M 5/1/05
Page 6
SETTINGS − Balance Point
NOTE − The balance point is only available with the outdoor sensor.
If the optional outdoor sensor (X2658) is connected to the
thermostat, balance point adjustment is available. The balance point feature allows the measured outdoor temperature to govern operation of the heat pump and backup heat
source.
Use the SETTINGS button to access the balance point
setting. If the outdoor sensor is attached to the thermostat,
press the SETTINGS button three times to access the Balance Point Settings screen (see figure 20).
Balance Point Setting
Service Indicator Flashing
MO TU WE TH FR SA SU
AM
I0:i4
PM
PROG A B C DHOLD
ROOM
°
79
Figure 21
FILTER
SERVICE
FAN
ON
AUTO
SYSTEM
COOL
OFF
HEAT
ROOM
SETPOINT
°
6p
The balance point can be set at any temperature between
1°F and 55°F (−17°C to 13°C). A balance point setting of
zero disables the balance point function (in this case, the
thermostat behaves as if no outdoor sensor is attached).
The default balance point setting is 55°F.
To adjust the balance point up or down, press the Up/Down
arrow buttons to the right of the display screen. The balance point setting increases by 1°F each time the Up button is pressed and decreases by 1°F each time the Down
button is pressed.
After the desired balance point is reached, the HOME
screen will reappear after about 15 seconds.
NOTE − The balance point feature allows the outdoor temperature to rise or fall 3°F above or below the balance
point. This prevents excessive cycling of the equipment
when the outdoor temperature is near the balance point.
For example, if the balance point is 40°F and the actual
outdoor temperature is 35°F, the outdoor temperature
must rise to 43°F before equipment adjustment occurs.
Conversely, if the balance point is 40°F and the actual outdoor temperature is 45°F, the outdoor temperature must
drop to 37°F before equipment adjustment occurs.
Service Indicator
When abnormal equipment operation is detected, the
SERVICE indicator will flash on the screen (see figure 21).
This indicates that the equipment requires service from a
qualified service technician.
55
Figure 20
Thermostat RESET
Under some abnormal conditions, it may be necessary to
reset" the thermostat to its default condition. Such a RESET would delete all programming and settings and therefore should only be used on rare occasions when the the
thermostat fails to function as designd and/or as programmed. Such an instance can occur as a result of a power surge or similar electrical disturbance (e.g. after an electrical storm or power outage). The RESET button can be
used to recover from this situation.
CAUTION
When the RESET button is pressed, ALL settings revert back to the defaults, including the default program (see tables 2 and 3).
The RESET button is an unlabeled, recessed button located behind the door, on the right−hand side of the thermostat, below the SETTINGS button (see figure 3). Use a
paper clip or small pencil to press the RESET button; ALL
thermostat settings will be reset to the defaults listed in the
Default Thermostat Settings section.
Removing/Installing Thermostat
The thermostat hinges on tabs on the top of the subbase;
no tool is needed to remove the thermostat from the subbase. Pivot the bottom of the thermostat outward (releasing the snaps), then lift up to remove.
To replace it, first position the top tilted toward the wall
bracket and align it until you feel the tabs and slots engage;
then, while the top is in place, pivot the bottom toward the
wall until the thermostat snaps into place.
Page 7
51M37 SERIES 5/2
Default Thermostat Settings
CAUTION
Default thermostat settings are shown in table 2 and the
default program is shown in table 3.
Weekday − A 6:00am70_F / 21°C78_F / 26°C
Weekday − B 8:00am62_F / 17°C85_F / 29°C
Weekday − C 6:00pm70_F / 21°C78_F / 26°C
Weekday − D 10:00pm 62_F / 17°C82_F / 28°C
Weekend − A 6:00am70_F / 21°C78_F / 26°C
Weekend − B 8:00am62_F / 17°C85_F / 29°C
Weekend − C 6:00pm70_F / 21°C78_F / 26°C
Weekend − D 10:00pm 62_F / 17°C82_F / 28°C
WeekdayMonday, Tuesday, Wednesday,
Thursday, Friday
WeekendSaturday, Sunday
Temperature
(Cool)
24VAC is present on the terminals of the thermostat
bracket. If removing the thermostat from the wall,
use caution and avoid touching any of the connector terminals on the wall bracket.
Also, when working with the thermostat dip
switches, use a non−conductive tool and take caution to avoid making any contact with the circuit
board, its imprinted circuitry and its connector
prongs.
Temperature Display
Display Scale: Fahrenheit or Celsius user selectable (via
DIP switch; see figure 22)
Display range: 35°F (2°C) to 99°F (37°C)
Display resolution: 1°F (1°C)
Display Accuracy: +/−1°F
If the Fahrenheit/Celsius display must be changed, use a
plastic, non−conductive tool to push the dip switch to the
right position (see figure 22).
Changing Fahrenheit/Celsius Setting
1
2
3
4
5
6
PLUG IN (Use Care To Avoid Bending Prongs.)
F/C (Fahrenheit/Celsius) switch
shown in Celsius position
Figure 22
Technical Specifications
Thermostat Type
Electronic programmable thermostat for heat pump,
3-stage heat/2-stage cool.
NOTE − 2 stages of heat pump heat and one stage of auxiliary (gas or electric) backup heat are supported.
Power Supply Range
18VAC − 30VAC (24VAC nominal), 60Hz
505050M 5/1/05
Temperature Measurement Range
Measurement Scale: Fahrenheit
Measurement Range: 35°F to 99°F
Measurement Resolution: 0.5°F
Measurement Accuracy: +/−1°F
Field Offset: via DIP switches to +/−3°F
Sampling Method: temperature measurements sampled
every 15 seconds. Displayed temperature is the average
of the last four measurements.
Smart Setback Recovery (SSR) affects the way the thermostat responds to program events. If SSR is disabled, the
thermostat will react to a program event at the time the
event occurs. However, if SSR is enabled, the thermostat
will react to a program event before the event occurs such
that the desired temperature is reached at the time of the
event, not after.
Fan Control
AUTO or ON modes.
I/O Relays
All thermostat relays are latching type to minimize power
consumption.
Table 4
51M37 Terminal Designations
Term. Description
BReversing valve, heat active
OReversing valve, cool active
R24VAC
Y1First-stage cooling/heating, compressor
energized
E*Emergency heat
GFan control
LService Indicator
C24VAC common
TOutdoor temperature sensor connection 1
TOutdoor temperature sensor connection 2
* For most applications, E will be jumpered to W1. If separate wires are not provided for both E and W1, jumper
the E terminal to the W1 terminal on the thermostat subbase. For applications involving the use of a balance
point (whereby the outdoor temperature is to be used to
restrict either heat pump operation or backup heat
source operation), the optional outdoor sensor (part
number X2658) MUST be installed.
Equipment Protection Timers
Minimum Compressor OFF time: 5 minutes
Minimum Compressor ON time: 4 minutes
Minimum Furnace ON time: 3 minutes
Minimum furnace cycle time (elapsed time between any
furnace activation and the next furnace activation): 6 minutes.
Minimum elapsed time between any compressor activation and the next compressor activation: 6 minutes.
NOTE − All protection timers (except the compressor OFF
timer) can be over−ridden if a heating or cooling demand is
initiated or terminated using the UP, DOWN, HEAT, or
COOL buttons.
Equipment Protection Override
Both the minimum compressor OFF timer and the minimum equipment cycle timer can be over−ridden by pressing and holding either the HEAT or COOL button down for 4
seconds.
Over−Temperature Protection
Thermal-mechanical switch opens W1, Y1, Y2, and E at
93°F+/−6°F.
Filter Reminder
Settings of Off, 1, 3, 6 or 12 (months of fan run time) are
available. When programmed time has elapsed, a FILTER
indicator is displayed.
Maintenance Reminder
Settings of Off, 6 or 12 (months of chronological time) are
available. When programmed time has elapsed, a maintenance indicator MAINT" is displayed.
Service Reminder
The SERVICE indicator is displayed only under the following conditions:
Sif the thermostat Y1 terminal has been activated with
24VAC for at least 5 minutes, AND the L terminal is
shorted to the R terminal;
OR
Sif the thermostat Y1 terminal has been activated with
24VAC for at least 5 minutes, AND the L terminal is
shorted to the C terminal.
Power Loss/Recovery
Thermostat memory is retained for a minimum of 24 hours
during a power loss (includes retention of program information, HOLD status, programmed temperature setpoint,
heat/cool and fan mode settings, filter reminder status,
maintenance reminder status, and equipment protection
timers). After 24 hours of power loss, programmed settings
will be lost and replaced with default settings.
IMPORTANT
Power must be applied for at least six consecutive
hours prior to a power loss in order for memory to
be retained for the specified time.
LCD Backlight
Activated for 30 seconds when any button is pressed.
NOTE − During an electrical storm or similar disturbance,
the backlight may activate for a few seconds. This is normal and will no longer occur after the electrical disturbance
has passed.
Thermostat Operating Conditions
35°F to 105°F, 5% to 90% RH
Thermostat Storage Conditions
−40°F to 185°F, 5% to 95% RH
Page 9
51M37 SERIES 5/2
Thermostat Output Table
Table 5 depicts the 51M37 thermostat output states for various input conditions. The following notes described terms
used in the table.
NOTES:
S X = output is activated with 24VAC.
S BBP: outdoor temperature is below balance point
S ABP: outdoor temperature is above balance point
S In all cases, the state of the B terminal is opposite that
of the O terminal
S Data are tabulated for AUTO fan setting. If the fan set-
ting is ON, the G output is activated in all cases
S Upstage timers:
30 minutes (when upstaging from small to large
demand)
15 minutes (HEAT MODE ONLY − when upstaging
from large to very large demand)
S The temperature ranges expressed in the following
definitions of SMALL/LARGE/VERY LARGE" demands are for guidance only; actual temperatures
may vary:
With a small HEAT demand, temperature is:
below setpoint –0.5F but above setpoint –1.5F
AND 30-minute upstage timer HAS NOT expired.
With a large HEAT demand, temperature is:
less than setpoint –1.5F
OR 30-minute upstage timer HAS expired.
With a very large heat demand, temperature is:
below setpoint –2.5F
OR 15−minute 2nd upstage timer HAS expired.
Emergency heat demand (only if emergency heat is
enabled): temperature is below setpoint –0.5F.
With a small COOL demand, temperature is:
above setpoint +0.5F but below setpoint +1.5F
AND 30-minute upstage timer HAS NOT expired.
With a large COOL demand, temperature is:
above setpoint +1.5F
OR 30-minute upstage timer HAS expired.
Table 5
THERMOSTAT OUTPUTS
Demand Condition
W1 EY1Y2 G O
Cooling Demands
SMALLXX X
LARGEXXX X
No DemandX
Heating Demands
w/Electric Backup (no outdoor sensor)
SMALLXX
LARGEXXX
Very LARGEXXXX
EmergencyXX
No Demand
w/Gas Backup (dual fuel; no outdoor sensor)
SMALLXX
LARGEXXX
Very LARGEX
EmergencyX
No Demand
w/Electric Backup (outdoor sensor attached)
SMALL (Above Balance Point)XX
LARGE (ABP)XXX
Very LARGE (ABP)XXX
SMALL (Below Balance Point)XX
LARGE (BBP)XXX
Very LARGE (BBP)XXXX
EmergencyXX
No Demand
w/Gas Backup (dual fuel; outdoor sensor attached)
SMALL (ABP)XX
LARGE (ABP)XXX
Very LARGE (ABP)X
SMALL (BBP)X
LARGE (BBP)X
Very LARGE (BBP)X
EmergencyX
No Demand
505050M 5/1/05
Page 10
OPERATION
E2005 Lennox Industries Inc.
Dallas, Texas, USA
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
51M35 Merit® Series Thermostat
The Lennox Merit® Series 5/2 day programmable
electronic thermostat 51M35 provides excellent
temperature control and a large, easy-to-read display. This
product includes a programmable filter change reminder,
an equipment maintenance reminder, and a system check
indicator to notify the user when the equipment requires
service.
Thermostat 51M35 is suitable for non-heat pump, twostage heat/two-stage cool applications using a gas or electric furnace.
These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
having jurisdiction before installation.
Check equipment for shipping damage. If you find any
damage, immediately contact the last carrier.
Introduction
This document describes the operation of Lennox thermostat
51M35. Refer to the installation manual for instructions regarding installation and wiring of the thermostat.
Initial Thermostat Power-up
When power is initially applied to the thermostat, the display will appear as shown in figure 1.
Initial Power−Up Display
MO TU WE TH FR SA SU
AM
I8:88
PM
PROG A | B | C | D HOLD
ROOM
SETPOINT
°
°
88
All display segments are momentarily activated. This occurs as a normal part of thermostat initialization.
88
Figure 1
MAINT
FILTER
SERVICE
FAN
ON
AUTO
SYSTEM
COOL
OFF
EMG.
HEAT
Hi
Lo
05/05505,049M
Page 1
*2P0505**P505049M*
Within a few seconds, the Home Screen appears (see figure 2) with default settings as shown. After about 1 minute
of initialization time, the actual room temperature will be
displayed.
NOTE − Tables 2 and 3 on page 6 show all system and
programming defaults.
MO TU WE TH FR SA SU
Home Screen
MAINT
FILTER
SERVICE
AM
I2:00
PM
PROGA B C DHOLD
ROOM
°
70
FAN
ON
AUTO
SYSTEM
COOL
OFF
HEAT
Figure 2
At this point, the thermostat will be fully functional; its default temperature setpoint (not shown) is 70°F. At this
point, if the equipment has been fully powered and if a heat
demand were present, the system would begin operating.
NOTE − Temperature scale default is Fahrenheit units but
may be reset to show Celsius, if desired. See page 7.
Buttons, Backlight, Timers & Settings
Buttons are located behind the small door on the right−
hand side of the thermostat (see figure 3).
IMPORTANT
Do NOT begin pressing buttons until after you read
the following section describing each button.
A pale blue display backlight illuminates for 30 seconds
each time any button is pressed.
When PROG or DAY/TIME is pressed, a field begins flashing, expecting another input. Start making changes within
15 seconds or the HOME screen will return.
Thermostat Buttons
Heat
Cool
Prog
Day/Time
Fan
Hold
Settings
Enter
(DOOR
OPEN)
Figure 3
When an Arrow, HOLD, HEAT, or COOL button is pressed,
SETPOINT and the temperature setting appears for 15
seconds. If desired, start making changes within 15 seconds or the HOME screen will return. The backlight will
turn off 15 seconds after the HOME screen reappears.
DAY/TIME − Setting the Day and Time
Press the DAY/TIME button and set the CURRENT hour,
minute, and day of week as follows:
1. AM12" will flash on the screen. Press the UP/DOWN
arrows to change the hour. (AM" or PM" must correspond to time of day.) Press DAY/TIME OR, if adjust-
ing for daylight savings time, pressing ENTER stores
the single change and exits to the HOME screen, bypassing minutes and day of week.
2. Minutes will flash. Use the UP/DOWN arrow button to
display the minutes past the hour. Press DAY/TIME.
3. Day MO" (Monday) will flash. Use UP or DOWN arrow
buttons to display the current day. Day selections are
abbreviated as MO, TU", WE", TH", FR", SA",
and SU". Press DAY/TIME.
4. The HOME screen reappears; confirm day and time
are correct. This completes day and time setting.
505049M 5/1/05
Page 2
HEAT − Using the Heat Mode
COOL − Using the Cool Mode
Enabling and Disabling Heat Mode
The thermostat must be in the HEAT mode to control the
heating equipment. Press the Heat button to enable or disable HEAT mode. If the thermostat is in COOL or OFF
mode, pressing the Heat button enables the HEAT mode
(indicated by HEAT in the SYSTEM box − see figure 4).
Turn Heat ON/OFF
Heat
Prog
Fan
Settings
Cool
Day/Time
Hold
Enter
MO
AM
PM
ROOM
66
5:30
HOLD
SETPOINT
°
70
°
FAN
AUTO
SYSTEM
HEAT
Figure 4
If the thermostat is in heat mode, pressing the Heat button
disables HEAT mode (indicated by OFF in the SYSTEM
box − see figure 5).
Heat/Cool Mode Disabled
°
SYSTEM
COOL
OFF
HEAT
ROOM
75
°
SETPOINT
75
Figure 5
Heating Demand
Set the thermostat to heat mode to control the heating
equipment. Then, if the room temperature is lower than the
temperature setpoint, as shown in figure 6, the thermostat
detects a heating demand and will activate the heating
equipment to satisfy the demand.
Heating Demand
°
SYSTEM
COOL
OFF
HEAT
ROOM
72
°
SETPOINT
75
Figure 6
Heating operation is indicated by a flame icon in the SYSTEM box. When the actual temperature rises above the
temperature setpoint, the flame icon will disappear. This
indicates that the heating demand has been satisfied and
that the heating equipment has been turned off.
If your system supports 2−stage heating (as does the
51M35 thermostat), you may notice various heating levels
being delivered during a demand.
NOTE − Heating equipment is activated for at least 3 minutes if no buttons are pressed during the demand interval.
Enabling and Disabling Cool Mode
Use the COOL button to enable or disable cool mode as
desired. If the thermostat is in HEAT or OFF mode, cool
mode is enabled when the COOL button is pressed. This is
indicated by COOL in the SYSTEM box (see figure 8).
Turn Cool ON/OFF
Heat
Prog
Fan
Settings
Cool
Day/Time
Hold
Enter
MO
AM
PM
I0:30
ROOM
75
SETPOINT
°
70
HOLD
°
FAN
AUTO
SYSTEM
COOL
Figure 7
If the thermostat is in cool mode, pressing the Cool button
disables COOL mode (indicated by OFF in the SYSTEM
box − see figure 5).
Cooling Demand
Set the thermostat to cool mode to control the cooling
equipment. Then, if the room temperature is higher than
the temperature setpoint, as shown in figure 8, the thermostat detects a cooling demand and will activate the cooling
equipment to satisfy the demand.
Cooling Demand
°
SYSTEM
COOL
OFF
HEAT
ROOM
75
SETPOINT
°
70
Figure 8
Cooling operation is indicated by flashing snowflake"
icons in the SYSTEM box. When the actual temperature
drops below the temperature setpoint, the snowflake icons
will disappear. This indicates that the cooling demand has
been satisfied and that the cooling equipment has been
turned off.
If your system supports 2−stage cooling (as does the
51M35 thermostat), you may notice various cooling levels
being delivered during a demand. Also, if a small cooling
demand is present, "Lo" will be displayed in the SYSTEM
box. However, if a large cooling demand is present, "Hi" will
be displayed in the SYSTEM box (shown in figure 8).
NOTE − If no buttons are pressed during a demand for
cooling, the equipment must operate for at least 4 minutes.
After a demand has been satisfied, cooling equipment operation is locked out for 5 minutes. If another cooling demand occurs during this 5−minute interval, COOL" and the
snowflakes will flash; however, the cooling equipment will
not operate until the 5−minute delay has elapsed.
Page 3
Hi
51M35 SERIES 5/2
HOLD − Using Temperature Hold Modes
PROG − Thermostat Programming
When HOLD is displayed at the HOME screen, the thermostat is in a temperature hold condition. This means that
the temperature program data is ignored and the thermostat functions much like a non−programmable thermostat.
Adjusting Temperature Setpoint in Hold Mode
The temperature setpoint represents the desired temperature of the space around the thermostat. The default temperature setpoint in Hold mode is 70°F.
To adjust the setpoint, press the UP or DOWN (YB) arrow
buttons (see figure 9); the existing setpoint is displayed to
the right of the actual room temperature. Each button
press adjusts the setpoint up or down by 1 degree.
Hold Temperature Mode
MO
AM
PM
I0:36
ROOM
72
°
HOLD
SETPOINT
68
°
FAN
AUTO
SYSTEM
COOL
Heat
Prog
Fan
Settings
Cool
Day/Time
Hold
Enter
Figure 9
After the desired setpoint is reached, the HOME screen
will reappear after about 15 seconds.
Permanent Hold Mode
At any time the program is running, from the HOME
screen, set a permanent hold (program override) by pressing the HOLD button (see figure 9). The thermostat now
functions much like a non−programmable thermostat. Use
the Up/Down arrow buttons to adjust the hold setpoint. To
return to the program, press HOLD again.
Temporary (2-Hour) Hold
At any time the program is running, from the HOME
screen, set a temporary 2-hour hold by pressing the Up/
Down arrow buttons until the desired setpoint is displayed;
HOLD" flashes (see figure 10). This overrides the program for 2 hours from the last button press, then returns to
the program.
Temporary Hold Temperature Mode
MO
AM
PM
I0:36
PROG BHOLD
ROOM
°
72
SETPOINT
68
°
FAN
AUTO
SYSTEM
COOL
Heat
Prog
Fan
Settings
Cool
Day/Time
Hold
Enter
Figure 10
While in Temporary Hold, press HOLD once to switch to
Permanent Hold (HOLD displays solid; PROG not displayed); press HOLD again to return to the program
(PROG displays; HOLD not displayed).
The 51M35 thermostat can be programmed to perform a
set of either heating or cooling events (but not a
combination of heat and cool) for 5 consecutive days using
a set of 4 unique events per day. The remaining 2 days can
then be set for a different set of 4 unique events per day.
Both the consecutive days and the events/temperature are
set by the homeowner.
To Change Consecutive Days...
To alter the 5 consecutive days, press and hold the PROG
button for 5 seconds. The existing 5 consecutive day period is then displayed (default is MOnday thru FRiday). To
change to a different 5-consecutive days, use the Up/
Down arrow buttons. Any 5 consecutive−day span may be
selected, for example, in figure 11, Saturday through
Wednesday is defined as the 5−day programming (Thursday and Friday would constitute the 2−day programming).
Press the PROG button when finished.
Change Consecutive days
MO TU WE TH FR SA SU
FILTER
Figure 11
To Set Program Events and Temperatures...
Figure 12 gives an example of how the two sets of programs can be set for a normal workweek and weekend.
In the 5−day bar graph, note how programs A and C reflect
the desired warmth while the home IS occupied (72°); B
allows less heating while the home is NOT occupied; D reflects a cool sleeping temperature. The 2−day bar graph
would support day−long occupancy and, because the first
program begins later, a less−demanding time schedule.
5/2 Program Example
5−DAY PROGRAM:
2−DAY PROGRAM:
|A |B| C | D|
72°
68°
64°
6AM NOON6PMMID6AM
|A| B |C | D|
72°
68°
64°
6AM NOON6PMMID6AM
NIGHT
NIGHT
Figure 12
NOTE − Pressing ENTER during the following programming steps, saves and exits to the HOME screen.
To program events and temperatures, perform the following steps, once with Cool selected and once with Heat selected.
1. Press and release PROG. AM 6:00", period A", and
the 5 consecutive days are displayed; AM 6" flashes.
2. Use the Up/Down arrow buttons to select the desired
hour; press PROG when the desired hour is reached.
3. Use the Up/Down arrow buttons to select the desired
minute; press PROG.
4. Use the Up/Down arrow buttons to select the desired
temperature setpoint; press PROG.
5. Repeat steps 2 through 4 for periods B, C, and D.
6. Repeat steps 1 through 5 for the 2−day program.
505049M 5/1/05
Page 4
NOTE − This thermostat will NOT automatically switch
(1st
)
(Off, 1, 3, 6, 12); f
(2nd
)
(Off, 6, 12). U
thi
from heating to cooling, or vice versa; operator involvement is required. At the change of seasons, or to accomodate abnormal seasonal temperature swings, you must
manually select to the opposite conditioning (Heat or Cool)
program.
FAN − Controlling the Fan Operation
Reminder Settings Display
OFF
MAINT
FILTER
For MAINT,
press Settings
button 2 times
For FILTER,
press Settings
button 1 time
Use the FAN button to select either continuous fan mode or
auto fan mode.
To change from continuous to auto fan mode (or vice versa), press the FAN button. Note whether a fan icon in the
FAN box is present (indicating that the fan is running) or not
(fan not running).
If continuous fan mode is enabled (ON displayed in FAN
box − see figure 13), the fan will run continuously regardless of whether the heating or cooling equipment is running.
MO
AM
PM
PROG B
ROOM
67
Using Fan ON
FAN
I0:I0
°
ON
SYSTEM
HEAT
Heat
Prog
Fan
Settings
Cool
Day/Time
Hold
Enter
Figure 13
If auto fan mode is selected (AUTO displayed in FAN box −
see figure 14), the fan will only run when the heating or
cooling equipment is running.
MO
AM
PM
I0:36
PROG B
ROOM
72
Using Fan Auto
FAN
AUTO
SYSTEM
COOL
°
Heat
Prog
Fan
Settings
Cool
Day/Time
Hold
Enter
Figure 14
SETTINGS − Filter/Maintenance Reminders
The 51M35 thermostat is designed to remind you when the
filter needs changing or when routine maintenance is required, as (and if) defined, by you. These optional reminders are not enabled until you activate them. To do so, press
the Settings button (shown below the Fan button in figure
14) once or twice for the desired reminder as shown in figure 15 and as described in table 1.
Figure 15
The default setting for the reminders is OFF (disabled).
Press Up/Down arrow buttons to select the desired reminder intervals.
Table 1
Filter and Maintenance Reminders
Buttons to
Use
Settings
press
then Arrows
to scroll
selections
Settings
press
then Arrows
to scroll
selections
EnterStores settings.
Reminder
FILTER
MAINT
NOTE − The HOME screen will reappear about 15 seconds
after the final arrow button press. OR, press ENTER at any
time to store any changes and exit to the HOME screen.
After either programmed interval has elapsed, the reminder will be displayed as shown in figure 16.
MO TU WE TH FR SA SU
AM
PM
I0:i2
PROG A B C DHOLD
ROOM
°
78
Available Settings and
How to Use
Total fan run time expressed in
months
example, if fan runs 12 hours a
day, 1 month reminder displays
in 2 calendar months.
Elapsed chronological time in
months
for example, to remind yourself
when to perform routine checks
or when to call a technician for
perodic preventive
maintenance.
Reminders
MAINT
FILTER
SERVICE
FAN
ON
AUTO
SYSTEM
COOL
OFF
HEAT
se
or
s,
Figure 16
After the filter has been changed or maintenance performed, reset the reminder by pressing the SETTINGS
button for 4 seconds. The screen will blink for a few moments to indicate that the timer has been reset.
Page 5
51M35 SERIES 5/2
Service Indicator
Removing and Installing Thermostat
When abnormal equipment operation is detected, the
SERVICE indicator will flash on the screen (see figure 17).
This indicates that the equipment requires service from a
qualified service technician.
Service Indicator Flashing
MO TU WE TH FR SA SU
AM
I0:i4
PM
PROG A B C DHOLD
ROOM
°
79
Figure 17
FILTER
SERVICE
FAN
ON
AUTO
SYSTEM
COOL
OFF
HEAT
Thermostat RESET
Under some abnormal conditions, it may be necessary to
reset" the thermostat to its default condition. Such a RESET would delete all programming and settings and therefore should only be used on rare occasions when the the
thermostat fails to function as designd and/or as programmed. Such an instance can occur as a result of a power surge or similar electrical disturbance (e.g. after an electrical storm or power outage). The RESET button can be
used to recover from this situation.
CAUTION
When the RESET button is pressed, ALL settings revert back to the defaults, including the default program (see tables 2 and 3).
The RESET button is an unlabeled, recessed button located behind the door on the right−hand side of the thermostat, below the SETTINGS button (see figure 3). Use a paper clip or small pencil to press the RESET button; ALL
thermostat settings will be reset to the defaults listed in the
Default Thermostat Settings section.
The thermostat hinges on tabs on the top of the subbase;
no tool is needed to remove the thermostat from the subbase. Pivot the bottom of the thermostat outward (releasing the snaps), then lift up to remove.
To install it, first position the top tilted toward the wall bracket and align it until you feel the tabs and slots engage; then,
while the top is in place, pivot the bottom toward the wall
until the thermostat snaps into place.
Default Thermostat Settings
Default thermostat settings are in table 2 and the default
program is shown in table 3.
Weekday − A 6:00am70_F / 21°C78_F / 26°C
Weekday − B 8:00am62_F / 17°C85_F / 29°C
Weekday − C 6:00pm70_F / 21°C78_F / 26°C
Weekday − D 10:00pm 62_F / 17°C82_F / 28°C
Weekend − A 6:00am70_F / 21°C78_F / 26°C
Weekend − B 8:00am62_F / 17°C85_F / 29°C
Weekend − C 6:00pm70_F / 21°C78_F / 26°C
Weekend − D 10:00pm 62_F / 17°C82_F / 28°C
WeekdayMonday, Tuesday, Wednesday,
Thursday, Friday
WeekendSaturday, Sunday
Reset Back to Zero
Table 3
Temperature
(Heat)
Temperature
(Cool)
505049M 5/1/05
Page 6
Technical Specifications
Thermostat Type
Electronic programmable thermostat for 2−Stage (gas or
electric) Heat/2-Stage Cool, non−heat pump, non−power
robbing applications.
Power Supply Range
18VAC − 30VAC (24VAC nominal), 60Hz
CAUTION
24VAC is present on the terminals of the thermostat
bracket. If removing the thermostat from the wall,
use caution and avoid touching any of the connector terminals on the wall bracket.
Also, when working with the thermostat dip
switches, use a non−conductive tool and take caution to avoid making any contact with the circuit
board, its imprinted circuitry and its connector
prongs.
Temperature Display
Display Scale: Fahrenheit or Celsius user selectable (via
DIP switch; see figure 18)
Display range: 35°F (2°C) to 99°F (37°C)
Display resolution: 1°F (1°C)
Display Accuracy: +/−1°F
If the Fahrenheit/Celsius display must be changed, use a
plastic, non−conductive tool to push the dip switch to the
right position (see figure 18).
Smart Setback Recovery (SSR) affects the way the thermostat responds to program events. If SSR is disabled, the
thermostat will react to a program event at the time the
event occurs. However, if SSR is enabled, the thermostat
will react to a program event before the event occurs such
that the desired temperature is reached at the time of the
event, not after.
Fan Control
AUTO or ON modes, gas or electric heat compatible via
DIP switches (also see Thermostat Output section).
I/O Relays
All thermostat relays are latching type to minimize power
consumption.
Table 4
51M35 Terminal Designations
TerminalDescription
R24VAC
Y1First-stage cooling
W1First-stage heating
Y2Second-stage cooling
W2Second-stage heating
GFan control
LService Indicator
C24VAC common
Changing Fahrenheit/Celsius Setting
1
2
3
4
5
6
PLUG IN (Use Care To Avoid Bending Prongs.)
F/C (Fahrenheit/Celsius) switch
shown in Celsius position
Figure 18
Temperature Measurement Range
Measurement Scale: Fahrenheit
Measurement Range: 35°F to 99°F
Measurement Resolution: 0.5°F
Measurement Accuracy: +/−1°F
Field Offset: via DIP switches to +/−3°F
Sampling Method: temperature measurements sampled
every 15 seconds. Displayed temperature is the average
of the last four measurements.
Equipment Protection Timers
Minimum Compressor OFF time: 5 minutes
Minimum Compressor ON time: 4 minutes
Minimum Furnace ON time: 3 minutes
Minimum furnace cycle time (elapsed time between any
furnace activation and the next furnace activation): 6 minutes.
Minimum elapsed time between any compressor activation and the next compressor activation: 6 minutes.
NOTE − All protection timers (except the compressor OFF
timer) can be over−ridden if a heating or cooling demand is
initiated or terminated using the UP, DOWN, HEAT, or
COOL buttons.
Equipment Protection Override
Both the minimum compressor OFF timer and the minimum equipment cycle timer can be over−ridden by pressing and holding either the HEAT or COOL button down for 4
seconds.
Over−Temperature Protection
Thermal-mechanical switch opens W1 and W2 at
93°F+/−6°F.
Filter Reminder
Settings of Off, 1, 3, 6 or 12 (months of fan run time) are
available. When programmed time has elapsed, a FILTER
indicator is displayed.