Lennox 51M34 5/2, 51M34 Operation Manual

Page 1
OPERATION
E2007 Lennox Industries Inc.
Dallas, Texas, USA
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
51M34 5/2 Day Programmable Thermostat
The Lennox 51M34 5/2 day programmable electronic thermostat has a large, easy-to-read display and provides excellent temperature control. This product includes a programmable filter change reminder, an equipment maintenance reminder, and a system check indicator to notify the user when the equipment requires service.
The 51M34 thermostat is suitable for non−heat pump, single-stage heat/single-stage cool applications with either gas or electric furnace.
MANUAL
51M34 5/2 Day Programmable Thermostat
CONTROLS
505,048M 08/07 Supersedes 05/05
Table of Contents
51M34 5/2 Day Programmable Thermostat 1. . . . . . .
General 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Introduction 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Initial Thermostat Power-up 1. . . . . . . . . . . . . . . . . . . . .
Buttons, Backlight, Timers & Settings 2. . . . . . . . . . . .
DAY/TIME − Set Day and Time 2. . . . . . . . . . . . . . . . . .
HEAT − Heat Mode 3. . . . . . . . . . . . . . . . . . . . . . . . . . . .
COOL − Cool Mode 3. . . . . . . . . . . . . . . . . . . . . . . . . . . .
HOLD − Temperature Hold Mode 4. . . . . . . . . . . . . . . .
PROG − Thermostat Programming 4. . . . . . . . . . . . . . .
FAN − Controlling Fan Operation 5. . . . . . . . . . . . . . . . .
SETTINGS − Filter /Maintenance Reminder 5. . . . . . .
Service Indicator 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Thermostat RESET 6. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Removing/Installing Thermostat 6. . . . . . . . . . . . . . . . .
Default Thermostat Settings 6. . . . . . . . . . . . . . . . . . . .
Technical Specifications 7. . . . . . . . . . . . . . . . . . . . . . . .
Thermostat Output Table 8. . . . . . . . . . . . . . . . . . . . . . .
Litho U.S.A.
General
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities having jurisdiction before installation.
Check equipment for shipping damage. If you find any damage, immediately contact the last carrier.
Introduction
This document describes the operation of Lennox 51M34 thermostat . Refer to the installation manual for instructions regarding installation and wiring of the thermostat.
Initial Thermostat Power-up
When power is initially applied to the thermostat, the dis­play will appear as shown in figure 1.
MO TU WE TH FR SA SU
AM
I8:88
PM
PROG A | B | C | D HOLD
ROOM
SETPOINT
°
°
88
Figure 1. Initial Power−Up Display
All display segments are momentarily activated. This oc­curs as a normal part of thermostat initialization. Within a few seconds, the Home Screen appears (see figure 2) with default settings as shown. After about 1 minute of initializa­tion time, the actual room temperature will be displayed.
88
MAINT
FILTER
SERVICE
FAN ON AUTO
SYSTEM COOL OFF EMG. HEAT
Hi Lo
08/07 505,048M
*2P0807* *P505048M*
Page 2
MO TU WE TH FR SA SU
AM
I2:00
PM
PROG A B C D HOLD
ROOM
°
MAINT
FILTER
SERVICE
FAN
ON
AUTO
SYSTEM
COOL OFF
Heat
Prog
Fan
Settings
Cool
Day/Time
Hold
Enter
(DOOR OPEN)
70
HEAT
Figure 2. Home Screen
At this point, the thermostat will be fully functional; its de­fault temperature setpoint (not shown) is 70°F. At this point, if the equipment has been fully powered and if a heat demand were present, the system would begin operating.
NOTE − Temperature scale default is Fahrenheit units but may be reset to show Celsius, if desired. See page 7.
Buttons, Backlight, Timers & Settings
Buttons are located behind the small door on the right− hand side of the thermostat (see figure 3).
IMPORTANT
Do NOT begin pressing buttons until after you read the following section describing each button.
A pale blue display backlight illuminates for 30 seconds each time any button is pressed.
When PROG or DAY/TIME is pressed, a field begins flash­ing, expecting another input. Start making changes within 15 seconds or the HOME screen will return.
Figure 3. Thermostat Buttons
When an Arrow, HOLD, HEAT, or COOL button is pressed, SETPOINT and the temperature setting appears for 15 seconds. If desired, start making changes within 15 sec­onds or the HOME screen will return. The backlight will turn off 15 seconds after the HOME screen reappears.
DAY/TIME − Setting the Day and Time
Press the DAY/TIME button and set the CURRENT hour, minute, and day of week as follows:
1. AM12" will flash on the screen. Press the UP/DOWN arrows to change the hour. (AM" or PM" must corre­spond to time of day.) Press DAY/TIME OR, if adjust-
ing for daylight savings time, pressing ENTER stores the single change and exits to the HOME screen, by­passing minutes and day of week.
2. Minutes will flash. Use the UP/DOWN arrow button to display the minutes past the hour. Press DAY/TIME.
3. Day MO" (Monday) will flash. Use UP or DOWN arrow buttons to display the current day. Day selections are abbreviated as MO, TU", WE", TH", FR", SA", and SU". Press DAY/TIME.
4. The HOME screen reappears; confirm day and time are correct. This completes day and time setting.
505048M 08/07
Page 2
Page 3
HEAT − Using the Heat Mode
COOL − Using the Cool Mode
Enabling and Disabling Heat Mode
The thermostat must be in the HEAT mode to control the heating equipment. Press the Heat button to enable or dis­able HEAT mode. If the thermostat is in COOL or OFF mode, pressing the Heat button enables the HEAT mode (indicated by HEAT in the SYSTEM box − see figure 4).
Heat
Prog
Fan
Settings
Cool
Day/Time
Hold
Enter
MO
AM
PM
ROOM
66
5:30
HOLD
SETPOINT
°
70
°
FAN
AUTO
SYSTEM
HEAT
Figure 4. Turn Heat ON/OFF
If the thermostat is in heat mode, heat mode is disabled when the HEAT button is pressed. This is indicated by OFF in the SYSTEM box as shown in figure 5.
°
SYSTEM
COOL
OFF
HEAT
ROOM
75
°
SETPOINT
75
Figure 5. Heat/Cool Mode Disabled
Heating Demand
Set the thermostat to heat mode to control the heating equipment. Then, if the room temperature is lower than the temperature setpoint, as shown in figure 6, the thermostat detects a heating demand and will activate the heating equipment to satisfy the demand.
°
SYSTEM
COOL OFF
HEAT
ROOM
72
°
SETPOINT
75
Figure 6. Heating Demand
Heating operation is indicated by a flame icon in the SYS­TEM box. When the actual temperature rises above the temperature setpoint, the flame icon will disappear. This indicates that the heating demand has been satisfied and that the heating equipment has been turned off.
NOTE − Heating equipment is activated for at least 3 min­utes if no buttons are pressed during the demand interval.
Enabling and Disabling Cool Mode
Use the COOL button to enable or disable cool mode as desired. If the thermostat is in HEAT or OFF mode, cool mode is enabled when the COOL button is pressed. This is indicated by COOL in the SYSTEM box (see figure 7).
Heat
Prog
Fan
Settings
Cool
Day/Time
Hold
Enter
MO
AM
PM
I0:30
ROOM
75
°
HOLD
SETPOINT
70
°
FAN
AUTO
SYSTEM COOL
Figure 7. Turn Cool ON/OFF
If the thermostat is in cool mode, pressing the Cool button disables COOL mode (indicated by OFF in the SYSTEM box − see figure 5).
Cooling Demand
Set the thermostat to cool mode to control the cooling equipment. Then, if the room temperature is higher than the temperature setpoint, as shown in figure 8, the thermo­stat detects a cooling demand and will activate the cooling equipment to satisfy the demand.
°
SYSTEM COOL
OFF
HEAT
ROOM
75
SETPOINT
°
70
Figure 8. Cooling Demand
Cooling operation is indicated by flashing snowflake" icons in the SYSTEM box. When the actual temperature drops below the temperature setpoint, the snowflake icons will disappear. This indicates that the cooling demand has been satisfied and that the cooling equipment has been turned off.
NOTE − If no buttons are pressed during a demand for cooling, the equipment must operate for at least 4 minutes. After a demand has been satisfied, cooling equipment op­eration is locked out for 5 minutes. If another cooling de­mand occurs during this 5−minute interval, COOL" and the snowflakes will flash; however, the cooling equipment will not operate until the 5−minute delay has elapsed.
Page 3
51M34 5/2 DAY PROGRAMMABLE THERMOSTAT
Page 4
HOLD − Using Temperature Hold Modes
PROG − Thermostat Programming
When HOLD is displayed at the HOME screen, the ther­mostat is in a temperature hold condition. This means that the temperature program data is ignored and the thermo­stat functions much like a non−programmable thermostat.
Adjusting Temperature Setpoint in Hold Mode
The temperature setpoint represents the desired tempera­ture of the space around the thermostat. The default tem­perature setpoint in Hold mode is 70°F.
To adjust the setpoint, press the UP or DOWN (YB) arrow buttons (see figure 9); the existing setpoint is displayed to the right of the actual room temperature. Each button press adjusts the setpoint up or down by 1 degree.
Heat
Prog
Fan
Settings
Cool
Day/Time
Hold
Enter
MO
AM
PM
I0:36
ROOM
72
SETPOINT
°
68
HOLD
°
FAN
AUTO
SYSTEM COOL
Figure 9. Hold Temperature Mode
After the desired setpoint is reached, the HOME screen will reappear after about 15 seconds.
Permanent Hold Mode
At any time the program is running, from the HOME screen, set a permanent hold (program override) by press­ing the HOLD button (see figure 9). The thermostat now functions much like a non−programmable thermostat. Use the Up/Down arrow buttons to adjust the hold setpoint. To return to the program, press HOLD again.
Temporary (2-Hour) Hold
At any time the program is running, from the HOME screen, set a temporary 2-hour hold by pressing the Up/ Down arrow buttons until the desired setpoint is displayed; HOLD" flashes (see figure 10). This overrides the pro­gram for 2 hours from the last button press, then returns to the program.
Heat
Prog
Fan
Settings
Cool
Day/Time
Hold
Enter
MO
AM
PM
I0:36
PROG B HOLD
ROOM
SETPOINT
°
68
72
°
FAN
AUTO
SYSTEM COOL
Figure 10. Temporary Hold Temperature Mode
While in Temporary Hold, press HOLD once to switch to Permanent Hold (HOLD displays solid; PROG not dis­played); press HOLD again to return to the program (PROG displays; HOLD not displayed).
The 51M34 thermostat can be programmed to perform a set of either heating or cooling events (but not a combination of heat and cool) for 5 consecutive days using a set of 4 unique events per day. The remaining 2 days can then be set for a different set of 4 unique events per day. Both the consecutive days and the events/temperature are set by the homeowner.
To Change Consecutive Days...
To alter the 5 consecutive days, press and hold the PROG button for 5 seconds. The existing 5 consecutive day peri­od is then displayed (default is MOnday thru FRiday). To change to a different 5-consecutive days, use the Up/ Down arrow buttons. Any 5 consecutive−day span may be selected, for example, in figure 11, Saturday through Wednesday is defined as the 5−day programming (Thurs­day and Friday would constitute the 2−day programming). Press the PROG button when finished.
MO TU WE TH FR SA SU
FILTER
Figure 11. Change Consecutive days
To Set Program Events and Temperatures...
Figure 12 gives an example of how the two sets of pro­grams can be set for a normal workweek and weekend.
In the 5−day bar graph, note how programs A and C reflect the desired warmth while the home IS occupied (72°); B allows less heating while the home is NOT occupied; D re­flects a cool sleeping temperature. The 2−day bar graph would support day−long occupancy and, because the first program begins later, a less−demanding time schedule.
5−DAY PROGRAM:
2−DAY PROGRAM:
|A | B | C | D |
72°
68°
64°
6AM NOON 6PM MID 6AM
|A| B | C | D |
72°
68°
64°
6AM NOON 6PM MID 6AM
NIGHT
NIGHT
Figure 12. 5/2 Program Example
NOTE − Pressing ENTER during the following program­ming steps, saves and exits to the HOME screen.
To program events and temperatures, perform the follow­ing steps, once with Cool selected and once with Heat se­lected.
1. Press and release PROG. AM 6:00", period A", and the 5 consecutive days are displayed; AM 6" flashes.
2. Use the Up/Down arrow buttons to select the desired hour; press PROG when the desired hour is reached.
3. Use the Up/Down arrow buttons to select the desired minute; press PROG.
4. Use the Up/Down arrow buttons to select the desired temperature setpoint; press PROG.
5. Repeat steps 2 through 4 for periods B, C, and D.
505048M 08/07
Page 4
Page 5
6. Repeat steps 1 through 5 for the 2−day program.
(1st
)
(Off, 1, 3, 6, 12); f
(2nd
)
(Off, 6, 12). U
thi
NOTE − This thermostat will NOT automatically switch from heating to cooling, or vice versa; operator involve­ment is required. At the change of seasons, or to accomo­date abnormal seasonal temperature swings, you must manually select to the opposite conditioning (Heat or Cool) program.
FAN − Controlling the Fan Operation
Use the FAN button to select either continuous fan mode or auto fan mode.
To change from continuous to auto fan mode (or vice ver­sa), press the FAN button. Note whether a fan icon in the FAN box is present (indicating that the fan is running) or not (fan not running).
If continuous fan mode is enabled (ON displayed in FAN box − see figure 13), the fan will run continuously regard­less of whether the heating or cooling equipment is run­ning.
Heat
Prog
Fan
Settings
Cool
Day/Time
Hold
Enter
MO
AM
PM
PROG B
ROOM
67
I0:I0
°
FAN ON
SYSTEM
HEAT
MAINT
FILTER
OFF
For MAINT, press Settings button 2 times
For FILTER, press Settings button 1 time
Figure 15. Reminder Settings Display
The default setting for the reminders is OFF (disabled). Press Up/Down arrow buttons to select the desired re­minder intervals.
Table 1. Filter and Maintenance Reminders
Buttons to
Use
Settings
press
then Arrows
to scroll
selections
Settings
press
then Arrows
to scroll
selections
Enter Stores settings.
Reminder
FILTER
MAINT
Available Settings and How to Use
Total fan run time expressed in months example, if fan runs 12 hours a day, 1 month reminder displays in 2 calendar months.
Elapsed chronological time in months for example, to remind yourself when to perform routine checks or when to call a technician for perodic preventive maintenance.
se
or
s,
Figure 13. Using Fan ON
If auto fan mode is selected (AUTO displayed in FAN box − see figure 14), the fan will only run when the heating or cooling equipment is running.
Heat
Prog
Fan
Settings
Cool
Day/Time
Hold
Enter
MO
AM
PM
I0:36
PROG B
ROOM
72
FAN
AUTO
SYSTEM COOL
°
Figure 14. Using Fan AUTO
SETTINGS − Filter/Maintenance Reminders
The 51M34 thermostat is designed to remind you when the filter needs changing or when routine maintenance is re­quired, as (and if) defined, by you. These optional remind­ers are not enabled until you activate them. To do so, press the Settings button (shown below the Fan button in figure
14) once or twice for the desired reminder as shown in fig­ure 15 and as described in table 1.
NOTE − The HOME screen will reappear about 15 seconds after the final arrow button press. OR, press ENTER at any time to store any changes and exit to the HOME screen.
After either programmed interval has elapsed, the remind­er will be displayed as shown in figure 16.
MO TU WE TH FR SA SU
AM
PM
I0:i2
PROG A B C D HOLD
ROOM
°
78
MAINT
FILTER
SERVICE
FAN
ON
AUTO
SYSTEM
COOL OFF
HEAT
Figure 16. Reminders
After the filter has been changed, reset the filter reminder by pressing the SETTINGS button for 4 seconds. The screen will blink for a few moments to indicate that the tim­er has been reset.
Page 5
51M34 5/2 DAY PROGRAMMABLE THERMOSTAT
Page 6
Service Indicator
Removing/Installing Thermostat
When abnormal equipment operation is detected, the SERVICE indicator will flash on the screen (see figure 17). This indicates that the equipment requires service from a qualified service technician.
MO TU WE TH FR SA SU
AM
I0:i4
PM
PROG A B C D HOLD
ROOM
°
79
Figure 17. Service Indicator Flashing
FILTER
SERVICE
FAN
ON
AUTO
SYSTEM
COOL OFF
HEAT
Thermostat RESET
Under some abnormal conditions, it may be necessary to reset" the thermostat to its default condition. Such a RE­SET would delete all programming and settings and there­fore should only be used on rare occasions when the the thermostat fails to function as designd and/or as pro­grammed. Such an instance can occur as a result of a pow­er surge or similar electrical disturbance (e.g. after an elec­trical storm or power outage). The RESET button can be used to recover from this situation.
CAUTION
When the RESET button is pressed, ALL settings re­vert back to the defaults, including the default pro­gram (see tables 2 and 3).
The RESET button is an unlabeled, recessed button lo­cated behind the door on the right−hand side of the thermo­stat, below the SETTINGS button (see figure 3). Use a pa­per clip or small pencil to press the RESET button; ALL thermostat settings will be reset to the defaults listed in the Default Thermostat Settings section.
The thermostat hinges on tabs on the top of the subbase; no tool is needed to remove the thermostat from the sub­base. Pivot the bottom of the thermostat outward (releas­ing the snaps), then lift up to remove.
To replace it, first position the top tilted toward the wall bracket and align it until you feel the tabs and slots engage; then, while the top is in place, pivot the bottom toward the wall until the thermostat snaps into place.
Default Thermostat Settings
Default thermostat settings are in table 2 and the default program is shown in table 3.
Table 2. Default Thermostat Settings
Mode Heat (Permanent Hold)
Setpoint 70°F (or 21°C) Fan Auto Filter Reminder OFF Maintenance Reminder OFF Equipment Protection
Timers
Table 3. Default Program Settings
Programs Time
Weekday − A 6:00am 70_F / 21°C 78_F / 26°C Weekday − B 8:00am 62_F / 17°C 85_F / 29°C Weekday − C 6:00pm 70_F / 21°C 78_F / 26°C Weekday − D 10:00pm 62_F / 17°C 82_F / 28°C Weekend − A 6:00am 70_F / 21°C 78_F / 26°C Weekend − B 8:00am 62_F / 17°C 85_F / 29°C Weekend − C 6:00pm 70_F / 21°C 78_F / 26°C Weekend − D 10:00pm 62_F / 17°C 82_F / 28°C
Weekday Monday, Tuesday, Wednesday,
Thursday, Friday
Weekend Saturday, Sunday
Reset Back to Zero
Temperature (Heat)
Temperature (Cool)
505048M 08/07
Page 6
Page 7
Technical Specifications
Thermostat Type
Electronic programmable thermostat for 1-Stage­Heat/1-Stage Cool, gas or electric heat, non−heat pump, non−power robbing applications.
Power Supply Range
18VAC − 30VAC (24VAC nominal), 60Hz
CAUTION
24VAC is present on the terminals of the thermostat bracket. If removing the thermostat from the wall, use caution and avoid touching any of the connec­tor terminals on the wall bracket.
Also, when working with the thermostat dip switches, use a non−conductive tool and take cau­tion to avoid making any contact with the circuit board, its imprinted circuitry and its connector prongs.
Temperature Display
Display Scale: Fahrenheit or Celsius user selectable (via DIP switch; see figure 18) Display range: 35°F (2°C) to 99°F (37°C) Display resolution: 1°F (1°C) Display Accuracy: +/−1°F
If the Fahrenheit/Celsius display must be changed, use a plastic, non−conductive tool to push the dip switch to the right position (see figure 18).
1 2 3 4 5 6
Figure 18. Changing Fahrenheit/Celsius Setting
Temperature Measurement Range
Measurement Scale: Fahrenheit Measurement Range: 35°F to 99°F Measurement Resolution: 0.5°F Measurement Accuracy: +/−1°F Field Offset: via DIP switches to +/−3°F Sampling Method: temperature measurements sampled every 15 seconds. Displayed temperature is the average of the last four measurements.
PLUG IN (Use Care To Avoid Bending Prongs.)
F/C (Fahrenheit/Celsius) switch shown in Celsius position
Temperature Setpoint Range
Setting range: 50°F (10°C) to 90°F (32°C) Setting resolution: 1°F (1°C)
Smart Setback Recovery (via DIP switch #6)
Smart Setback Recovery (SSR) affects the way the ther­mostat responds to program events. If SSR is disabled, the thermostat will react to a program event at the time the event occurs. However, if SSR is enabled, the thermostat will react to a program event before the event occurs such that the desired temperature is reached at the time of the event, not after.
Fan Control
AUTO or ON modes, gas or electric heat compatible via DIP switches (also see Thermostat Output section).
I/O Relays
All thermostat relays are latching type to minimize power consumption.
Table 4. 51M34 Terminal Designations
Terminal Description
R 24VAC Y1 First stage cooling W1 First stage heating G Fan control L Service Indicator C 24VAC common
Equipment Protection Timers
Minimum Compressor OFF time: 5 minutes Minimum Compressor ON time: 4 minutes Minimum Furnace ON time: 3 minutes
Minimum furnace cycle time (elapsed time between any furnace activation and the next furnace activation): 6 min­utes.
Minimum elapsed time between any compressor activa­tion and the next compressor activation: 6 minutes.
NOTE − All protection timers (except the compressor OFF timer) can be over−ridden if a heating or cooling demand is initiated or terminated using the UP, DOWN, HEAT, or COOL buttons.
Equipment Protection Override
Both the minimum compressor OFF timer and the mini­mum equipment cycle timer can be over−ridden by press­ing and holding either the HEAT or COOL button down for 4 seconds.
Over−Temperature Protection
Thermal-mechanical switch opens W1 at 93°F+/−6°F.
Filter Reminder
Settings of Off, 1, 3, 6 or 12 (months of fan run time) are available. When programmed time has elapsed, a FILTER indicator is displayed.
Page 7
51M34 5/2 DAY PROGRAMMABLE THERMOSTAT
Page 8
Maintenance Reminder
Settings of Off, 6 or 12 (months of chronological time) are available. When programmed time has elapsed, a mainte­nance indicator MAINT" is displayed.
Service Reminder
The SERVICE indicator is displayed only under the follow­ing conditions:
S if the thermostat Y1 terminal has been activated with
24VAC for at least 5 minutes, AND the L terminal is shorted to the R terminal;
OR
S if the thermostat Y1 terminal has been activated with
24VAC for at least 5 minutes, AND the L terminal is shorted to the C terminal.
Power Loss/Recovery
Thermostat memory is retained for a minimum of 24 hours during a power loss (includes retention of program infor­mation, HOLD status, programmed temperature setpoint, heat/cool and fan mode settings, filter reminder status, maintenance reminder status, and equipment protection timers). After 24 hours of power loss, programmed settings will be lost and replaced with default settings.
IMPORTANT
Power must be applied for at least six consecutive hours prior to a power loss in order for memory to be retained for the specified time.
LCD Backlight
Activated for 30 seconds when any button is pressed.
NOTE − During an electrical storm or similar disturbance, the backlight may activate for a few seconds. This is nor­mal and will no longer occur after the electrical disturbance has passed.
Thermostat Operating Conditions
35°F to 105°F, 5% to 90% RH
Thermostat Storage Conditions
−40°F to 185°F, 5% to 95% RH
Thermostat Output Table
Table 5 depicts the 51M34 thermostat output states for var­ious input conditions.
Table 5. Thermostat Outputs
Condition W1 Y1 G
Gas Heat, Auto Fan
HEAT Demand X COOL Demand X X No Demand
Gas Heat, Continuous Fan
HEAT Demand X X COOL Demand X X No Demand X
Electric Heat, Auto Fan
HEAT Demand X X COOL Demand X X No Demand
Electric Heat, Continuous Fan
HEAT Demand X X COOL Demand X X No Demand X
NOTE − X = output is activated with 24VAC.
505048M 08/07
Page 8
Loading...