Lennox 51M32 User Manual

®
OPERATION
2003 Lennox Industries Inc.
Dallas, Texas, USA
MeritR Series Thermostat
The Lennox Merit® Series Thermostat 51M32 is a nonpro­grammable electronic thermostat that is easy-to-use and has a large, easy-to-read display and excellent tempera­ture control. The thermostat also includes a programmable filter change reminder and a system check indicator. The system check indicator will notify the user of the need for equipment service.
Thermostat 51M32 is suitable for non-heat pump, single− stage heat/single cool applications that are matched with a gas or electric furnace.
General
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities having jurisdiction before installation.
Check equipment for shipping damage. If you find any damage, immediately contact the last carrier.
Introduction
This document describes the operation of Lennox thermostat 51M32. Refer to the installation manual for instructions re­garding installation and wiring of the thermostat.
Initial Thermostat Power-up
When power is initially applied to the thermostat, the dis­play will appear as shown in figure 1.
MANUAL
Merit® Series Thermostat
CONTROLS (51M32)
504,865M 09/04
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
Table of Contents
Merit® Series Thermostat 1. . . . . . . . . . . . . . . . . . . . . .
General 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Introduction 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Initial Thermostat Power-up 1. . . . . . . . . . . . . . . . . . . . . .
Heating Control 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cooling Control 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Adjusting Temperature Setpoint 3. . . . . . . . . . . . . . . . . .
Fan Control 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Filter Reminder 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Service Indicator 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Thermostat Reset 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Default Thermostat Settings 5. . . . . . . . . . . . . . . . . . . . .
Technical Specifications 5. . . . . . . . . . . . . . . . . . . . . . . . .
Thermostat Output Table 6. . . . . . . . . . . . . . . . . . . . . . . .
Display − Initial Power−Up
ROOM
Litho U.S.A.
FILTER
SERVICE
88
FAN ON
AUTO
SETPOINT
All display segments are momentarily activated. This oc­curs as a normal part of thermostat initialization. Within a few seconds, the display will appear as shown in figure 2 (figure shows temperature in Fahrenheit units).
88
Figure 1
SYSTEM COOL OFF
EMG. HEAT
Page 1
Display − Home Screen
Heat Mode Enabled
ROOM
70
FAN
AUTO
SYSTEM
HEAT
Figure 2
Figure 2 illustrates the HOME screen. Note that an indoor room temperature of 70°F is initially displayed. After about 1 minute of warm−up time, the actual room temperature will be displayed. HEAT mode is the system default (as indi­cated in the SYSTEM box at lower right).
A pale blue display backlight will turn on each time a key is pressed. The backlight will turn off 8 seconds after the last key is pressed.
Heating Control
The HEAT button is located behind the small door on the right−hand side of the thermostat. See figure 3.
ROOM
69
FAN
AUTO
SETPOINT
If the thermostat is in heat mode, heat mode is disabled when the HEAT button is pressed. This is indicated by OFF in the SYSTEM box as shown in figure 5.
ROOM
64
Figure 4
Heat Mode Disabled
SYSTEM
HEAT
69
FAN
Additional Thermostat Buttons
Figure 3
Enabling and Disabling Heat Mode
Use the HEAT button to enable or disable heat mode as de­sired. If the thermostat is in off mode, heat mode is enabled when the HEAT button is pressed. This is indicated by HEAT in the SYSTEM box as shown in figure 4.
AUTO
SETPOINT
Heating Demand
The thermostat must be in heat mode in order to properly control the heating equipment. When in heat mode, if the actual temperature is lower than the temperature setpoint, a heating demand is detected by the thermostat. The thermo­stat will then activate the heating equipment to satisfy the de­mand. Heating operation is indicated by a flame icon in the SYSTEM box as shown in figure 6.
64
Figure 5
SYSTEM
OFF
Page 2
Heating Demand
Cooling Demand
ROOM
72
FAN
AUTO
88
Figure 6
When the actual temperature rises above the temperature setpoint, the flame icon will disappear. This indicates that the heating demand has been satisfied and that the heating equipment has been turned off.
NOTE − The heating equipment is activated for at least 3 minutes if no buttons are pressed during the demand inter­val.
Cooling Control
The COOL button is located behind the small door on the right-hand side of the thermostat. See figure 3.
Enabling and Disabling Cool Mode
Use the COOL button to enable or disable cool mode as necessary. If the thermostat is in off mode, cool mode is en­abled when the COOL button is pressed. This is indicated by COOL in the SYSTEM box.
If the thermostat is in cool mode, cool mode is disabled when the COOL button is pressed. This is indicated by OFF in the SYSTEM box.
Cooling Demand
The thermostat must be in cool mode in order to properly control the cooling equipment. When in cool mode, if the room temperature is higher than the temperature setpoint, a cooling demand is detected by the thermostat.
The thermostat will then activate the cooling equipment to satisfy the demand. Cooling operation is indicated by a snowflake icon in the SYSTEM box as shown in figure 7. When the actual temperature drops below the temperature setpoint, the snowflake icon will disappear. This indicates that the cooling demand has been satisfied and that the cooling equipment has been turned off.
SYSTEM
HEAT
ROOM
79
FAN
AUTO
SYSTEM COOL
Figure 7
NOTE − The cooling equipment is activated for at least 4 minutes if no buttons are pressed during the demand inter­val. Cooling equipment operation is locked out for 5 min­utes after a demand has been satisfied. If another cooling demand occurs during this 5−minute interval, the snowflake icon will flash; however, the cooling equipment will not run until the 5−minute delay has elapsed.
Adjusting Temperature Setpoint
The temperature setpoint represents the desired tempera­ture of the space around the thermostat. The default tem­perature setpoint is 70°F. To adjust the setpoint, press the UP or DOWN arrow keys to the right of the display screen.
The existing setpoint will be displayed just below the actual room temperature as shown in figure 8. Use the UP or DOWN arrow keys to adjust the setpoint up or down. The setpoint will increase by 1°F each time the UP key is pressed. The setpoint will decrease by 1°F each time the DOWN key is pressed.
Setpoint Display and Adjustment
ROOM
69
FAN
AUTO
SETPOINT
After the desired setpoint is reached, the HOME screen will reappear after about 8 seconds.
64
Figure 8
SYSTEM
HEAT
Page 3
Fan Control
Filter Reminder
The FAN button is located behind the small door on the right-hand side of the thermostat. See figure 3. The FAN button can be used to select either continuous fan mode or auto fan mode.
If continuous fan mode is enabled, the fan will run continu­ously regardless of whether the heating or cooling equip­ment is running. Also, ON will be displayed in the FAN box as shown in figure 9.
Fan ON with Icon
ROOM
73
FAN ON
SYSTEM
HEAT
Figure 9
If auto fan mode is selected, the fan will only run when the heating or cooling equipment is running. In this case, AUTO will be displayed in the FAN box as shown in figure 10.
Fan AUTO with Icon
ROOM
73
FAN
The 51M32 thermostat includes a filter reminder feature. The filter reminder can be set for 1, 3, 6, or 12−month inter­vals. The SETTINGS button, located behind the door on the right−hand side of the thermostat is used to set the filter reminder interval. See figure 3. Press the SETTINGS but­ton from the HOME screen to display the Filter Reminder Settings screen as shown in figure 11.
Filter Reminder Settings
Filter
0
Figure 11
The default setting for the filter reminder is 0, which dis­ables the function. Use the UP arrow while in the Filter Re­minder Settings screen to select the desired interval be­tween reminders. It may be necessary to press the UP arrow several times to access the desired setting. The HOME screen will reappear about 10 seconds after the ar­row key has been pressed for the final time.
After the programmed interval has elapsed, the FILTER re­minder will be displayed as shown in figure 12. After the fil­ter has been changed, reset the filter reminder by pressing the SETTINGS button for 4 seconds. The screen will blink for a few moments to indicate that the timer has been reset.
Display of Filter Reminder
AUTO
SYSTEM
HEAT
Figure 10
To change from continuous to auto fan mode and vice versa, press the FAN button. Also note the presence of a fan icon in the FAN box. This icon indicates that the fan is running.
Page 4
ROOM
FILTER
72
FAN
AUTO
SYSTEM
HEAT
Figure 12
Service Indicator
Technical Specifications
When abnormal equipment operation is detected, the SERVICE indicator will flash on the upper-right corner of the screen. This indicates that the equipment requires ser­vice from a qualified service technician. The SERVICE indi­cator is shown in figure 13.
Service Indicator Flashing
ROOM
SERVICE
73
FAN
AUTO
SYSTEM
HEAT
Figure 13
Thermostat RESET
Under some abnormal conditions, it may be desirable to reset" the thermostat to its default condition. This can be useful on rare occasions when the the thermostat is behav­ing abnormally (e.g. after an electrical storm or power out­age). The RESET button can be used to recover from this situation.
The RESET button is an unlabeled, recessed button lo­cated behind the door on the right−hand side of the thermo­stat, just below the SETTINGS button. The RESET button is visible in figure 3. Use a paper clip or small pencil to press the RESET button. After the RESET button is pressed, the thermostat settings will return to the defaults listed in the Default Settings section.
Default Thermostat Settings
Default thermostat settings are in table 1.
Table 1
Default Thermostat Settings
Mode Heat
Setpoint 70°F (or 21°C)
Fan Auto
Filter Reminder OFF (reminder setting = 0)
Equipment Protection Timers
reset back to zero
Thermostat Type
Electronic nonprogrammable thermostat for 1H/1C, gas or electric heat, non−heat pump, non−power robbing applica­tions.
Power Supply Range
18VAC − 30VAC (24VAC nominal), 60Hz
Temperature Display
Display Scale: Fahrenheit or Celsius user selectable (via DIP switches) Display range: 35°F (2°C) to 99°F (37°C) Display resolution: 1°F (1°C) Display Accuracy: +/−1°F
Temperature Measurement Range
Measurement Scale: Fahrenheit Measurement Range: 35°F to 99°F Measurement Resolution: 0.5°F Measurement Accuracy: +/−1°F Field Offset: via DIP switches to +/−3°F Sampling Method: temperature measurements sampled every 15 seconds. Displayed temperature is the average of the last four measurements.
Temperature Setpoint Range
Setting range: 50°F (10°C) to 90°F (32°C) Setting resolution: 1°F (1°C)
Fan Control
AUTO or ON modes, gas or electric heat compatible via DIP switches (also see Thermostat Output section).
I/O Relays
All thermostat relays are latching type to minimize power consumption.
1. HEAT/COOL relay output
2. FAN relay output
3. SERVICE relay input
Equipment Protection Timers
Minimum Compressor OFF time: 5 minutes Minimum Compressor ON time: 4 minutes Minimum Furnace ON time: 3 minutes
Minimum furnace cycle time (elapsed time between any furnace activation and the next furnace activation): 6 min­utes.
Minimum elapsed time between any compressor activation and the next compressor activation: 6 minutes.
NOTE − All protection timers (except the compressor OFF timer) can be over−ridden if a heating or cooling demand is initiated or terminated using the UP, DOWN, HEAT, or COOL buttons.
Page 5
Equipment Protection Override
Both the minimum compressor OFF timer and the mini­mum equipment cycle timer can be over−ridden by press­ing and holding either the HEAT or COOL button down for 4 seconds.
Over−Temperature Protection
Thermal mechanical switch opens W1 at 93°F+/−6°F.
Power Loss/Recovery
Thermostat memory is retained for a minimum of 24 hours during a power loss (includes retention of programmed temperature setpoint, heat/cool and fan mode settings, fil­ter reminder status, and equipment protection timers). Af­ter 24 hours of power loss, programmed settings will be lost and replaced with default settings.
Filter Reminder
Settings of 0 (Off), 1, 3, 6 or 12 months are available. When programmed time has elapsed, a FILTER indicator is dis­played.
Service Reminder
The SERVICE indicator is displayed only under the follow­ing conditions:
if the thermostat Y1 terminal has been activated
with 24VAC for at least 5 minutes, AND the L terminal is shorted to the R terminal;
OR
if the thermostat Y1 terminal has been activated
with 24VAC for at least 5 minutes, AND the L terminal is shorted to the C terminal.
Power must be applied for at least six consecutive hours prior to a power loss in order for memory to be retained for the specified time.
LCD Backlight
Activated for 8 seconds when any key is pressed.
NOTE − During an electrical storm or similar disturbance, the backlight may activate for a few seconds. This is normal and will no longer occur after the electrical disturbance has passed.
Thermostat Operating Conditions
35°F to 105°F, 5% to 90% RH
Thermostat Storage Conditions
−40°F to 185°F, 5% to 95% RH
IMPORTANT
Thermostat Output Table
The following table depicts the 51M32 thermostat output states for various input conditions. See table 2.
Table 2
Thermostat Outputs
Condition W1 Y1 G
Gas Heat, Auto Fan
heat demand X
cool demand X X
no demand
Gas Heat, Continuous Fan
heat demand X X
cool demand X X
no demand X
Electric Heat, Auto Fan
heat demand X X
cool demand X X
no demand
Electric Heat, Continuous Fan
heat demand X X
cool demand X X
no demand X
NOTE −
X = output is activated with 24VAC.
Page 6
®
OPERATION
2003 Lennox Industries Inc.
Dallas, Texas, USA
MeritR Series Thermostat
The Lennox Merit® Series Thermostat 51M33 is a nonpro­grammable electronic thermostat that is easy-to-use and has a large, easy-to-read display and excellent tempera­ture control. The thermostat also includes a programmable filter change reminder and a system check indicator. The system check indicator will notify the user of the need for equipment service.
Thermostat 51M33 is suitable for heat pump, single−stage heat/single cool applications that are matched with a gas or electric furnace.
General
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities having jurisdiction before installation.
Check equipment for shipping damage. If you find any damage, immediately contact the last carrier.
Introduction
This document describes the operation of Lennox thermostat 51M33. Refer to the installation manual for instructions re­garding installation and wiring of the thermostat.
Initial Thermostat Power-up
When power is initially applied to the thermostat, the dis­play will appear as shown in figure 1.
MANUAL
Merit® Series Thermostat
CONTROLS (51M33)
504,931M 09/04
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
Table of Contents
Merit® Series Thermostat 1. . . . . . . . . . . . . . . . . . . . . .
General 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Introduction 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Initial Thermostat Power-up 1. . . . . . . . . . . . . . . . . . . . . .
Heating Control 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cooling Control 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Adjusting Temperature Setpoint 3. . . . . . . . . . . . . . . . . .
Fan Control 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Filter Reminder 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Balance Point 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Service Indicator 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Thermostat Reset 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Default Thermostat Settings 6. . . . . . . . . . . . . . . . . . . . .
Technical Specifications 6. . . . . . . . . . . . . . . . . . . . . . . . .
Thermostat Output Table 7. . . . . . . . . . . . . . . . . . . . . . . .
Display − Initial Power−Up
ROOM
Litho U.S.A.
FILTER
SERVICE
88
FAN ON
AUTO
SETPOINT
All display segments are momentarily activated. This oc­curs as a normal part of thermostat initialization. Within a few seconds, the display will appear as shown in figure 2 (figure shows temperature in Fahrenheit units).
88
Figure 1
SYSTEM COOL OFF
EMG. HEAT
Page 1
Display − Home Screen
ROOM
70
FAN
AUTO
Enabling and Disabling Heat Mode
Use the HEAT button to select normal heat mode, emer­gency heat mode, or to disable heat modes as desired. If the thermostat is in off mode, normal heat mode is enabled when the HEAT button is pressed. This is indicated by HEAT in the SYSTEM box as shown in figure 4.
SYSTEM
HEAT
Figure 2
Figure 2 illustrates the HOME screen. Note that an indoor room temperature of 70°F is initially displayed. After about 1 minute of warm−up time, the actual room temperature will be displayed. HEAT mode is the system default (as indi­cated in the SYSTEM box at lower right).
A pale blue display backlight will turn on each time a key is pressed. The backlight will turn off 8 seconds after the last key is pressed.
Heating Control
The HEAT button is located behind the small door on the right−hand side of the thermostat. See figure 3.
Additional Thermostat Buttons
Normal Heat Mode Enabled
ROOM
69
FAN
AUTO
SETPOINT
If the thermostat is in normal heat mode when the HEAT button is pressed, then emergency heat mode is enabled. This is indicated by EMG. HEAT in the SYSTEM box as shown in figure 5.
If the thermostat is in emergency heat mode when the HEAT button is pressed, then heat modes are disabled. This is indicated by OFF in the SYSTEM box as shown in figure 6.
64
Figure 4
SYSTEM
HEAT
Figure 3
Normal Heat Mode
In normal heat mode, both the heat pump and the backup heat source are used to provide heat. If the thermostat de­tects that the heat pump is not able to provide enough heat (as may be the case in very cold weather), then the backup heat source is activated.
Emergency Heat Mode
In emergency heat mode, only the backup heat source is used to provide heat. The heat pump is disabled. The back­up heat source will be activated only when there is a heat demand.
Page 2
Emergency Heat Mode Enabled
ROOM
69
FAN
AUTO
SETPOINT
64
Figure 5
SYSTEM
EMG. HEAT
Heat Mode Disabled
ROOM
69
FAN
AUTO
SETPOINT
Heating Demand
The thermostat must be in either normal or emergency heat mode in order to properly control the heating equip­ment. When in either heat mode, if the actual temperature is lower than the temperature setpoint, a heating demand is de­tected by the thermostat. The thermostat will then activate the heating equipment to satisfy the demand. Heating operation is indicated by a flame icon in the SYSTEM box as shown in figure 7.
ROOM
64
Figure 6
Heating Demand
SYSTEM
OFF
72
FAN
Enabling and Disabling Cool Mode
Use the COOL button to enable or disable cool mode as necessary. If the thermostat is in off mode, cool mode is en­abled when the COOL button is pressed. This is indicated by COOL in the SYSTEM box.
If the thermostat is in cool mode, cool mode is disabled when the COOL button is pressed. This is indicated by OFF in the SYSTEM box.
Cooling Demand
The thermostat must be in cool mode in order to properly control the cooling equipment. When in cool mode, if the room temperature is higher than the temperature setpoint, a cooling demand is detected by the thermostat.
The thermostat will then activate the cooling equipment to satisfy the demand. Cooling operation is indicated by a snowflake icon in the SYSTEM box as shown in figure 8. When the actual temperature drops below the temperature setpoint, the snowflake icon will disappear. This indicates that the cooling demand has been satisfied and that the cooling equipment has been turned off.
Cooling Demand
ROOM
79
FAN
AUTO
AUTO
88
Figure 7
When the actual temperature rises above the temperature setpoint, the flame icon will disappear. This indicates that the heating demand has been satisfied and that the heating equipment has been turned off.
NOTE − The heat pump is activated for at least 4 minutes if no buttons are pressed during the demand interval. The backup heat source is activated for at least 3 minutes if no buttons are pressed during the demand interval.
Heat pump operation is locked out for 5 minutes after a de­mand has been satisfied. If another heat pump demand oc­curs during this 5−minute interval, the flame icon will flash; however, the heat pump will not run until the 5−minute delay has elapsed.
SYSTEM
HEAT
Cooling Control
The COOL button is located behind the small door on the right-hand side of the thermostat. See figure 3.
SYSTEM COOL
Figure 8
NOTE − The cooling equipment is activated for at least 4 minutes if no buttons are pressed during the demand inter­val. Cooling equipment operation is locked out for 5 min­utes after a demand has been satisfied. If another cooling demand occurs during this 5−minute interval, the snowflake icon will flash; however, the cooling equipment will not run until the 5−minute delay has elapsed.
Adjusting Temperature Setpoint
The temperature setpoint represents the desired tempera­ture of the space around the thermostat. The default tem­perature setpoint is 70°F. To adjust the setpoint, press the UP or DOWN arrow keys to the right of the display screen.
The existing setpoint will be displayed just below the actual room temperature as shown in figure 9. Use the UP or DOWN arrow keys to adjust the setpoint up or down. The setpoint will increase by 1°F each time the UP key is pressed. The setpoint will decrease by 1°F each time the DOWN key is pressed.
Page 3
Setpoint Display and Adjustment
Fan AUTO with Icon
ROOM
69
FAN
AUTO
SETPOINT
After the desired setpoint is reached, the HOME screen will reappear after about 8 seconds.
Fan Control
The FAN button is located behind the small door on the right-hand side of the thermostat. See figure 3. The FAN button can be used to select either continuous fan mode or auto fan mode.
If continuous fan mode is enabled, the fan will run continu­ously regardless of whether the heating or cooling equip­ment is running. Also, ON will be displayed in the FAN box as shown in figure 10.
64
Figure 9
SYSTEM
HEAT
ROOM
73
FAN
AUTO
SYSTEM
HEAT
Figure 11
To change from continuous to auto fan mode and vice versa, press the FAN button. Also note the presence of a fan icon in the FAN box. This icon indicates that the fan is running.
Filter Reminder
The 51M33 thermostat includes a filter reminder feature. The filter reminder can be set for 1, 3, 6, or 12−month inter­vals. The SETTINGS button, located behind the door on the right−hand side of the thermostat is used to set the filter reminder interval. See figure 3. Press the SETTINGS but­ton from the HOME screen to display the Filter Reminder Settings screen as shown in figure 12.
Filter Reminder Settings
Filter
0
Fan ON with Icon
ROOM
73
FAN ON
SYSTEM
HEAT
Figure 10
If auto fan mode is selected, the fan will only run when the heating or cooling equipment is running. In this case, AUTO will be displayed in the FAN box as shown in figure 11.
Figure 12
The default setting for the filter reminder is 0, which dis­ables the function. Use the UP arrow while in the Filter Re­minder Settings screen to select the desired interval be­tween reminders. It may be necessary to press the UP arrow several times to access the desired setting. The HOME screen will reappear about 10 seconds after the ar­row key has been pressed for the final time.
After the programmed interval has elapsed, the FILTER re­minder will be displayed as shown in figure 13. After the fil­ter has been changed, reset the filter reminder by pressing the SETTINGS button for 4 seconds. The screen will blink for a few moments to indicate that the timer has been reset.
Page 4
Display of Filter Reminder
ROOM
72
Figure 13
FILTER
FAN
AUTO
SYSTEM
HEAT
DOWN arrow keys to the right of the display screen. The balance point setting will increase by 1°F each time the UP key is pressed. The balance point setting will decrease by 1°F each time the DOWN key is pressed.
After the desired balance point is reached, the HOME screen will reappear after about eight seconds.
NOTE − The balance point feature allows the temperature to rise or fall 3°F above or below the setpoint. This prevents excessive cycling of the equipment when the outdoor tem­perature is near the balance point. For example, if the bal­ance point is 40°F and the actual outdoor temperature is 35°F, the outdoor temperature must rise to 43°F before equipment adjustment occurs. Conversely, if the balance point is 40°F and the actual outdoor temperature is 45°F, the outdoor temperature must drop to 37°F before equip­ment adjustment occurs.
Balance Point
NOTE − The balance point is only available with the out­door sensor.
If the optional outdoor sensor (X2658) is connected to the thermostat, balance point adjustment is available. The bal­ance point feature allows the measured outdoor tempera­ture to govern operation of the heat pump and backup heat source.
Use the SETTINGS button to access the balance point set­ting. If the outdoor sensor is attached to the thermostat, press the SETTINGS button twice to access the Balance Point Settings screen (see figure 14).
Balance Point Setting
6P
SETPOINT
The balance point can be set at any temperature between 1°F and 55°F (−17°C to 13°C). A balance point setting of zero disables the balance point function (in this case, the thermostat behaves as if no outdoor sensor is attached). The default balance point setting is 55°F. To adjust the balance point up or down, press the UP or
55
Figure 14
Service Indicator
When abnormal equipment operation is detected, the SERVICE indicator will flash on the upper-right corner of the screen. This indicates that the equipment requires ser­vice from a qualified service technician. The SERVICE indi­cator is shown in figure 15.
Service Indicator Flashing
ROOM
SERVICE
73
FAN
AUTO
SYSTEM
HEAT
Figure 15
Thermostat RESET
Under some abnormal conditions, it may be desirable to re­set the thermostat to its default condition. The RESET but­ton can be used to return the unit to normal operation after an occurrence such as an electrical storm or power outage.
The RESET button is an unlabeled, recessed button lo­cated behind the door on the right−hand side of the thermo­stat, just below the SETTINGS button. The RESET button is visible in figure 3. Use a paper clip or small pencil to press the RESET button. After the RESET button is pressed, the thermostat settings will return to the defaults listed in the Default Settings section.
Page 5
Default Thermostat Settings
Default Thermostat settings are in table 1.
Table 1
Default Thermostat Settings
Mode Heat
Setpoint 70°F (or 21°C)
Fan Auto
Filter Reminder OFF (reminder setting = 0)
Equipment Protection Timers
reset back to zero
Technical Specifications
Thermostat Type
Electronic nonprogrammable thermostat for 1H/1C, heat pump with electric or gas backup heat source, non−power robbing applications.
Power Supply Range
18VAC − 30VAC (24VAC nominal), 60Hz
Temperature Display
Display Scale: Fahrenheit or Celsius user selectable (via DIP switches) Display range: 35°F (2°C) to 99°F (37°C) Display resolution: 1°F (1°C) Display Accuracy: +/−1°F
Temperature Measurement Range
Measurement Scale: Fahrenheit Measurement Range: 35°F to 99°F Measurement Resolution: 0.5°F Measurement Accuracy: +/−1°F Field Offset: via DIP switches to +/−3°F Sampling Method: temperature measurements sampled every 15 seconds. Displayed temperature is the average of the last four measurements.
Temperature Setpoint Range
Setting range: 50°F (10°C) to 90°F (32°C) Setting resolution: 1°F (1°C)
Fan Control
AUTO or ON modes.
Backup Heat Source Selection
Electric or gas furnace, selectable via DIP switch #5 (Aux or Dual, respectively). See also Thermostat Output section.
I/O Relays
All thermostat relays are latching type to minimize power consumption. See table 2.
Table 2
51M33 Terminal Designations
Connections Description
O Reversing valve, cool active
B Reversing valve, heat active
R 24VAC
G Fan control
Y1 First stage cooling/heating, compres-
sor generated
W1 Auxiliary heating, furnace generated
L Service Indicator
C 24VAC common
E Emergency heat
T Outdoor temperature sensor
connection 1
T Outdoor temperature sensor
connection 2
Equipment Protection Timers
Minimum Compressor OFF time: 5 minutes Minimum Compressor ON time: 4 minutes Minimum Furnace ON time: 3 minutes
Minimum backup furnace cycle time (elapsed time be­tween any furnace activation and the next furnace activa­tion): 6 minutes.
Minimum elapsed time between any compressor activation and the next compressor activation: 6 minutes.
NOTE − All protection timers (except the compressor OFF timer) can be over−ridden if a heating or cooling demand is initiated or terminated using the UP, DOWN, HEAT, or COOL buttons.
Equipment Protection Override
Both the minimum compressor OFF timer and the mini­mum equipment cycle timer can be over−ridden by press­ing and holding either the HEAT or COOL button down for 4 seconds.
Over−Temperature Protection
Thermal mechanical switch opens W1 at 93°F+/−6°F.
Filter Reminder
Settings of 0 (Off), 1, 3, 6 or 12 months are available. When programmed time has elapsed, a FILTER indicator is dis­played.
Balance Point
0°F (OFF) to 55°F, user selectable.
Page 6
Service Reminder
The SERVICE indicator is displayed only under the follow­ing conditions:
if the thermostat Y1 terminal has been activated
with 24VAC for at least 5 minutes, AND the L terminal is shorted to the R terminal;
OR
if the thermostat Y1 terminal has been activated
with 24VAC for at least 5 minutes, AND the L terminal is shorted to the C terminal.
Power Loss/Recovery
Thermostat memory is retained for a minimum of 24 hours during a power loss (includes retention of programmed temperature setpoint, heat/cool and fan mode settings, fil­ter reminder status, and equipment protection timers). Af­ter 24 hours of power loss, programmed settings will be lost and replaced with default settings.
IMPORTANT
Power must be applied for at least six consecutive hours prior to a power loss in order for memory to be retained for the specified time.
LCD Backlight
Activated for 8 seconds when any key is pressed.
NOTE − During an electrical storm or similar disturbance, the backlight may activate for a few seconds. This is normal and will no longer occur after the electrical disturbance has passed.
Thermostat Operating Conditions
35°F to 105°F, 5% to 90% RH
Thermostat Storage Conditions
−40°F to 185°F, 5% to 95% RH
Thermostat Output Table
Table 3 (see page 8) provides details of the 51M33 ther­mostat output states for various input conditions.
Page 7
Table 3
Thermostat Output States
Condition W1 Y1 G O E
Electric Heat Backup − No Outdoor Sensor
small heat demand X X large heat demand X X X emergency heat demand X X cool demand X X X no demand dc
Gas Heat Backup (Dual Fuel) − No Outdoor Sensor
small heat demand X X large heat demand X emergency heat demand X cool demand X X X no demand dc
Electric Heat Backup − Outdoor Sensor Attached
small heat demand (BBP) X X large heat demand (BBP) X X X small heat demand (ABP) X X large heat demand (ABP) X X emergency heat demand X X cool demand X X X no demand dc
Gas Heat Backup (Dual Fuel) − Outdoor Sensor Attached
small heat demand (BBP) X large heat demand (BBP) X small heat demand (ABP) X X large heat demand (ABP) X emergency heat demand X cool demand X X X no demand dc
NOTE −
X = output is activated with 24VAC dc: does not care (output can be in either state, i.e., either active or inactive) BBP: outdoor temperature is below balance point ABP: outdoor temperature is above balance point small heat demand: temperature is between (setpoint − 1.5°F) and (setpoint − 0.5°F), and 30-minute upstage
timer has not expired (see Normal Heat Mode graph)
large heat demand: temperature is below (setpoint − 1.5°F), or 30-minute upstage timer has expired (see Nor-
mal Heat Mode graph)
the state of the B terminal is opposite the state of the O terminal. data above are tabulated for AUTO fan setting. If fan setting is ON, the fan is activated in all cases.
Page 8
Loading...