Lennox 506586-01, XP17 User Manual

INSTALLATION
E2011 Lennox Industries Inc.
Dallas, Texas, USA
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities having jurisdiction before installation.
NOTICE TO INSTALLER
It is critical for proper unit operation to place outdoor unit on an elevated surface as described in Unit Placement section on page 7.
It is critical for proper defrost operation to set the defrost termination pins (E46) on the heat pump control prior to starting system. See Defrost System section on page 32 for further details.
BRAZING LINE SET TO SERVICE VALVES
It is imperative to follow the brazing technique illustrated starting on page 13 to avoid damaging the service valve’s internal seals.
UNIT PLACEMENT
DEFROST OPERATION
NOTICE
A thermostat is not included and must be ordered separately.
D The Lennox icomfort Touch® thermostat must be used
in communicating application
D In non−icomfortt applications, the Lennox
ComfortSense® 7000 thermostat may be used, as well as other non−communicating thermostats.
In all cases, setup is critical to ensure proper system operation.
Field wiring examples for non−icomforttapplications begin on page 25.
See the icomfort Touch® thermostat Quick Start Guide for communicating and partial communicating field wiring connections.
INSTRUCTIONS
Dave Lennox Signature Collection XP17 System
HEAT PUMPS
506586−01 06/11 Supersedes 05/11
TABLE OF CONTENTS
General 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit Dimensions 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Model Number Identification 2. . . . . . . . . . . . . . . . . . . .
Typical Unit Parts Arrangement 3. . . . . . . . . . . . . . . . .
Shipping and Packing List 4. . . . . . . . . . . . . . . . . . . . . .
Using Manifold Gauge Set 4. . . . . . . . . . . . . . . . . . . . . .
Operating Service Valves 4. . . . . . . . . . . . . . . . . . . . . . .
Recovering Refrigerant from Existing System 6. . . . .
Unit Placement 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Removing and Installing Panels 9. . . . . . . . . . . . . . . . .
New or Replacement Line Set 11. . . . . . . . . . . . . . . . . . .
Flushing the System 16. . . . . . . . . . . . . . . . . . . . . . . . . . .
Brazing Connections 13. . . . . . . . . . . . . . . . . . . . . . . . . . .
Flushing Line Set and Indoor Coil 16. . . . . . . . . . . . . . . .
Installing Indoor Expansion Valve 17. . . . . . . . . . . . . . . .
Leak Test Line Set and Indoor Coil 18. . . . . . . . . . . . . . .
Evacuating Line Set and Indoor Coil 18. . . . . . . . . . . . .
Electrical 20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Heat Pump Control (A175) Jumpers and Terminals 23
Field Control Wiring 25. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Servicing Unit Delivered Void of Charge 27. . . . . . . . . .
Unit Start−Up 27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Refrigerant 27. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Air Handler / Coil Matchups and Targeted Subcooling
Values 30. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operating and Temperature Pressures 31. . . . . . . . . . .
System Operations 32. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Defrost System 32. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Status, Fault and Lockout LED Codes 40. . . . .
Field Configuration and Testing 45. . . . . . . . . . . . . . . . . .
Maintenance (Dealer and Homeowner) 51. . . . . . . . . . .
SunSource® Home Energy System 53. . . . . . . . . . . . . .
Start Up and Performance Checklist 54. . . . . . . . . . . . .
General
This outdoor unit is designed for use with HFC−410A refrigerant only. This unit must be installed with an approved indoor air handler or coil. See the Lennox XP17 Engineering Handbook for approved indoor component matchups.
®
Litho U.S.A.
06/11 506586−01
Page 1
*2P0611* *P506586-01*
Unit Dimensions −− Inches (mm)
39−1/2 (1003)
DISCHARGE AIR
ELECTRICAL INLETS
37 (940) [−024 THRU −042] 47
(1194) [−048 AND −060]
VAPOR LINE INLET
LIQUID LINE INLET
4−7/16
18−1/2
(470)
(113)
8 (203)
1 (25)
SIDE VIEW ACCESS VIEW
UNIT SUPPORT FEET
35−1/2
(902)
16−7/8
(429)
8−3/4 (222)
3−1/8
(79)
Model Number Identification
Refrigerant Type
X = R−410A
Unit Type
P = Heat Pump Outdoor Unit
Series
30−3/4
(781)
BASE WITH ELONGATED LEGS
P 17 036
X 2
230
Nominal Cooling Capacity
024 = 2 tons 030 = 2.5 tons 036 = 3 tons 042 = 3.5 tons 048 = 4 tons 060 = 5 tons
26−7/8
(683)
3−3/4 (95)
4−5/8 (117)
Minor Revision Number
Voltage
230 = 208/230V−1ph−60hz
506586−01 10/10
Page 2
Typical Unit Parts Arrangement
WIRE TIE
OUTDOOR AMBIENT
TEMPERATURE SENSOR (RT13)
SLEEVE
SECOND GROUND LUG FOR SOURCESOURCEt
CONTACTOR−1POLE (K1−1)
HIGH VOLTAGE FIELD
DISCHARGE
LINE
CONNECTIONS
CONTROL (A175)
GROUND LUG
HEAT PUMP
COMPRESSOR
FAN MOTOR CONTROL (A177)
CONTROL BOX
CAPACITOR (C12)
RT21  MODELS
−024, − 030, −036 AND −042 (12 TUBES UP)
REVERSING
VALV E
REVERSING
VALV E
SOLENOID (L1)
VAPOR VALVE
AND GAUGE
PORT
TRUE SUCTION
LINE PORT
LIQUID VALVE AND
GAUGE PORT
LIQUID LINE
BI−FLOW FILTER
DRIER
MUFFLER
LOW PRESSURE SWITCH (S87)
TRUE SUCTION LINE
CHECK EXPANSION VALV E
HR1 CRANKCASE HEATER
CRANKCASE HEATER THERMOSTAT (S40)
HIGH PRESSURE SWITCH (S4)
MODELS −048
AND −060
24 TUBES UP
Figure 1. Typical Parts Arrangement
Page 3
XP17 SERIES
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause personal injury, loss of life, or damage to property.
Installation and service must be performed by a licensed professional installer (or equivalent) or a service agency.
1  Bushing (for low voltage wiring)
2  Isolation grommets for liquid and suction lines
Using Manifold Gauge Set
When checking the system charge, only use a manifold gauge set that features low−loss anti−blow back fittings.
IMPORTANT
CAUTION
Physical contact with metal edges and corners while applying excessive force or rapid motion can result in personal injury. Be aware of, and use caution when working near these areas during installation or while servicing this equipment.
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFCs, HCFCs AND HFCs) as of July 1,
1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for noncompliance.
WARNING
Electric Shock Hazard. Can cause injury or death. Unit must be grounded in accordance with national and local codes.
Line voltage is present at all components when unit is not in operation on units with single-pole contactors. Disconnect all remote electric power supplies before opening access panel. Unit may have multiple power supplies.
To prevent stripping of the various caps used, the appropriately sized wrench should be used and fitted snugly over the cap before tightening.
Manifold gauge set used with HFC−410A refrigerant systems must be capable of handling higher system operating pressures. The gauges should be rated for use with pressures of 0 − 800 psig on the high side and a low side of 30" vacuum to 250 psig with dampened speed to 500 psi. Gauge hoses must be rated for use at or up to 800 psig of pressure with a 4000 psig burst rating.
Table 1. Torque Requirements
Parts Recommended Torque
Service valve cap 8 ft.− lb. 11 NM
Sheet metal screws 16 in.− lb. 2 NM
Machine screws #10 28 in.− lb. 3 NM
Compressor bolts 90 in.− lb. 10 NM
Gauge port seal cap 8 ft.− lb. 11 NM
Operating Service Valves
The liquid and vapor line service valves are used for removing refrigerant, flushing, leak testing, evacuating, verifying charge and charging.
Each valve is equipped with a service port which has a factory−installed valve stem. Figure 2 provides information on how to access and operating both angle and ball service valves.
IMPORTANT
This model is designed for use in check expansion valve systems only. An indoor expansion valve approved for use with HFC−410A refrigerant must be ordered separately, and installed prior to operating the system.
Shipping and Packing List
Check unit for shipping damage. Consult last carrier immediately if damage is found.
1  Assembled outdoor unit.
1  Bag assembly which includes the following:
506586−01 10/10
IMPORTANT
Only use Allen wrenches of sufficient hardness (50Rc − Rockwell Harness Scale minimum). Fully insert the wrench into the valve stem recess.
Service valve stems are factory−torqued (from 9 ft−lbs for small valves, to 25 ft−lbs for large valves) to prevent refrigerant loss during shipping and handling. Using an Allen wrench rated at less than 50Rc risks rounding or breaking off the wrench, or stripping the valve stem recess.
See the Lennox Service and Application Notes #C−08−1 for further details and information.
Page 4
SERVICE VALVES
ANGLE AND BALL
Operating Angle Type Service Valve:
1. Remove stem cap with an appropriately sized wrench.
2. Use a service wrench with a hex−head extension (3/16" for liquid line valve sizes and 5/16" for vapor line valve sizes) to back the stem out counterclockwise as far as it will go.
SERVICE PORT CAP
SERVICE PORT CORE
(VALVE STEM SHOWN CLOSED) INSERT HEX WRENCH HERE
TO INDOOR
UNIT
(VALVE STEM SHOWN OPEN) INSERT HEX WRENCH HERE
STEM CAP
TO OUTDOOR UNIT
ANGLE−TYPE SERVICE VALVE
(BACK−SEATED OPENED)
When service valve is OPEN, the service port is open to linE set, indoor and outdoor unit.
Operating Ball Type Service Valve:
1. Remove stem cap with an appropriately sized wrench.
2. Use an appropriately sized wrenched to open. To open valve, rotate stem counterclockwise 90°. To close, rotate stem clockwise 90°.
TO INDOOR UNIT
TO OPEN ROTATE STEM COUNTERCLOCKWISE 90°.
TO CLOSE ROTATE STEM CLOCKWISE 90°.
SERVICE PORT
SERVICE PORT
SERVICE PORT
CORE
CAP
TO OUTDOOR
UNIT
BALL (SHOWN CLOSED)
VALV E STEM
STEM CAP
ANGLE−TYPE SERVICE VALVE
(FRONT−SEATED CLOSED)
WHEN SERVICE VALVE IS CLOSED, THE SERVICE PORT IS OPEN TO
THE LINE SET AND INDOOR UNIT.
To Access Service Port:
A service port cap protects the service port core from contamination and serves as the primary leak seal.
1. Remove service port cap with an appropriately sized wrench.
2. Connect gauge set to service port.
3. When testing is completed, replace service port cap and tighten as follows:
11
1/6 TURN
12
1
2
3
4
5
7
6
1/12 TURN
S With torque wrench: Finger tighten and
torque cap per table 1.
S Without torque wrench: Finger tighten and
use an appropriately sized wrench to turn an additional 1/6 turn clockwise.
Reinstall Stem Cap:
Stem cap protects the valve stem from damage and serves as the primary seal. Replace the stem cap and tighten as follows:
10
9
8
S With Torque Wrench: Finger tighten and then
torque cap per table 1.
S Without Torque Wrench: Finger tighten and use
an appropriately sized wrench to turn an addi­tional 1/12 turn clockwise.
10
9
12
11
8
1
2
4
5
7
6
3
NOTE  A label with specific torque requirements may be affixed to the stem cap. If the label is present, use the specified torque.
Figure 2. Angle and Ball Service Valves
Page 5
XP17 SERIES
Recovering Refrigerant from Existing System
DISCONNECT POWER
Disconnect all power to the existing outdoor unit at the disconnect
1
switch or main fuse box/breaker panel.
SERVICE DISCONNECT
SWITCH
CONNECT MANIFOLD GAUGE SET
Connect a gauge set, clean recovery cylinder and a recovery
2
machine to the service ports of the existing unit. Use the instruction provided with the recovery machine to make the connections.
MANIFOLD GAUGES
RECOVERY MACHINE
LOW
HIGH
RECOVERING REFRIGERANT
Remove existing HCFC−22 refrigerant using one of the following methods
3
below:
IMPORTANT  Some system configurations may contain higher than normal refrigerant charge due to either large internal coil volumes, and/or long line sets.
CLEAN RECOVERY CYLINDER
OUTDOOR UNIT
METHOD 1:
Us this method if the existing outdoor unit is not equipped with shut−off valves, or if the unit is not operational and you plan to use the existing HCFC−22 to flush the system.
Remove all HCFC−22 refrigerant from the existing system. Check gauges after shutdown to confirm that the entire system is completely void of refrigerant.
METHOD 2:
Use this method if the existing outdoor unit is equipped with manual shut−off valves, and you plan to use new HCFC−22 refrigerant to flush the system.
The following devices could prevent full system charge recovery into the outdoor unit:
S Outdoor unit’s high or low−pressure switches (if applicable) when tripped can cycle the compressor OFF.
S Compressor can stop pumping due to tripped internal pressure relief valve.
S Compressor has internal vacuum protection that is designed to unload the scrolls (compressor stops pumping) when the pressure ratio meets
a certain value or when the suction pressure is as high as 20 psig. (Compressor suction pressures should never be allowed to go into a vacuum. Prolonged operation at low suction pressures will result in overheating of the scrolls and permanent damage to the scroll tips, drive bearings and internal seals.)
Once the compressor can not pump down to a lower pressure due to one of the above system conditions, shut off the vapor valve. Turn OFF the main power to unit and use a recovery machine to recover any refrigerant left in the indoor coil and line set.
Perform the following task:
A Start the existing HCFC−22 system in the cooling mode and close the liquid line valve.
B Use the compressor to pump as much of the existing HCFC−22 refrigerant into the outdoor unit until the outdoor system is full (high pressure
switch will trip and shut the compressor off). Turn the outdoor unit main power OFF and use a recovery machine to remove the remaining refriger­ant from the system.
NOTE  It may be necessary to bypass the low pressure switch (if equipped) to ensure complete refrigerant evacuation.
C When the low side system pressures reach 0 psig, close the vapor line valve.
D Check gauges after shutdown to confirm that the valves are not allowing refrigerant to flow back into the low side of the system.
Figure 3. Refrigerant Recovery Procedure
Page 6
506586−01 10/10
CLEARANCE ON ALL SIDES  INCHES (MILLIMETERS)
MINIMUM CLEARANCE
ABOVE UNIT
12 (305)
6 (152)
36 (914)
ACCESS PANEL
CONTROL PANEL
ACCESS
LOCATION
30 (762)
LINE SET CONNECTIONS
MINIMUM CLEARANCE BETWEEN
TWO UNITS
24 (610)
Figure 4. Installation Clearances
NOTES:
S CLEARANCE TO ONE OF THE
OTHER THREE SIDES MUST BE 36 INCHES (914MM).
S CLEARANCE TO ONE OF THE
REMAINING TWO SIDES MAY BE 12 INCHES (305MM) AND THE FINAL SIDE MAY BE 6 INCHES (152MM).
ACCESS PANEL
LINE SET
CONNECTIONS
48 (1219)
REAR VIEW OF UNIT
Unit Placement
CAUTION
In order to avoid injury, take proper precaution when lift­ing heavy objects.
See Unit Dimensions on page 3 for sizing mounting slab, platforms or supports. Refer to figure 4 for mandatory installation clearance requirements.
POSITIONING CONSIDERATIONS
Consider the following when positioning the unit:
S Some localities are adopting sound ordinances based
on the unit’s sound level registered from the adjacent property, not from the installation property. Install the unit as far as possible from the property line.
S When possible, do not install the unit directly outside
a window. Glass has a very high level of sound transmission. For proper placement of unit in relation to a window see the provided illustration in figure 5, detail A.
PLACING UNIT ON SLAB
When installing unit at grade level, the top of the slab should be high enough above grade so that water from higher ground will not collect around the unit. The slab should have a slope tolerance as described in figure 5, detail B.
NOTE  If necessary for stability, anchor unit to slab as described in figure 5, detail D.
ELEVATING THE UNIT
Units are outfitted with elongated support feet as illustrated in figure 5, detail C.
If additional elevation is necessary, raise the unit by extending the height of the unit support feet. This may be achieved by using a 2 inch (50.8mm) Schedule 40 female threaded adapter.
The specified coupling will fit snuggly into the recessed portion of the feet. Use additional 2−inch (50.8mm) Schedule 40 male threaded adaptors which can be threaded into the female threaded adaptors to make additional adjustments to the level of the unit.
NOTE  Keep the height of extenders short enough to ensure a sturdy installation. If it is necessary to extend further, consider a different type of field−fabricated framework that is sturdy enough for greater heights.
Page 7
XP17 SERIES
DETAIL A
Install unit away from windows.
 Outside Unit Placement
DETAIL B
Install unit level or, if on a slope, maintain slope tolerance of two (2) degrees (or two inches per five feet [50 mm per 1.5 m]) away from building structure.
 Slab Mounting at Ground Level
BUILDING
STRUCTURE
MOUNTING SLAB
TWO 90° ELBOWS INSTALLED IN LINE SET WILL
REDUCE LINE SET VIBRATION.
DETAIL C
Elevated Slab Mounting
using Feet Extenders
LEG DETAIL
2" (50.8MM) SCH 40
FEMALE THREADED
ADAPTER
BASE
GROUND LEVEL
STABILIZING UNIT ON UNEVEN SURFACES
DETAIL D
#10 1/2" LONG SELF−DRILLING
SHEET METAL SCREWS
STABILIZING BRACKET (18 GAUGE
METAL  2" WIDTH; HEIGHT AS
#10 1−1/4" LONG HEX HD SCREW
Concrete slab  use two plastic anchors (hole drill 1/4")
Wood or plastic slab  no plastic anchor (hole drill 1/8")
DETAIL E
Stabilizing bracket (18 gauge metal  2" (50.8mm) width; height as required); bend to form right angle as exampled below.
 Slab Side Mounting
REQUIRED)
AND FLAT WASHER
 Deck Top Mounting
MINIMUM ONE
PER SIDE
COIL
BASE PAN
CORNER POST
2" (50.8MM) SCH 40
MALE THREADED
ADAPTER
Use additional 2" SCH 40 male threaded adapters which can be threaded into the female threaded adapters to make additional adjustments to the level of the unit.
IMPORTANT  To help stabilize an outdoor unit, some installations may require strapping the unit to the pad using brackets and anchors commonly available in the marketplace.
One bracket per side (minimum). For extra stability, two brackets per side, two inches (51mm) from each corner.
SAME FASTENERS AS SLAB SIDE MOUNTING.
FOR EXTRA
STABILITY
Figure 5. Placement, Slab Mounting and Stabilizing Unit
Page 8
506586−01 10/10
STABILIZING UNIT ON UNEVEN SURFACES
IMPORTANT
Unit Stabilizer Bracket Use (field−provided):
Always use stabilizers when unit is raised above the factory height. (Elevated units could become unstable in gusty wind conditions).
Stabilizers may be used on factory height units when mounted on unstable an uneven surface.
1. Remove two side louvered panels to expose the unit base.
2. Install the brackets as illustrated in figure 5, detail D using conventional practices.
3. Replace the panels after installation is complete.
ROOF MOUNTING
Install the unit a minimum of six inches (152 mm) above the roof surface to avoid ice build−up around the unit. Locate the unit above a load bearing wall or area of the roof that can adequately support the unit. Consult local codes for rooftop applications.
If unit coil cannot be mounted away from prevailing winter winds, a wind barrier should be constructed. Size barrier at least the same height and width as outdoor unit. Mount barrier 24 inches (610 mm) from the sides of the unit in the direction of prevailing winds.
PREVAILING WINTER
WINDS
WIND BARRIER
INLET AIR
INLET AIR
24"
(610)
NOTICE
Roof Damage! This system contains both refrigerant and oil. Some
rubber roofing material may absorbed oil and cause the rubber to swell when it comes into contact with oil. The rubber will then bubble and could cause leaks. Protect the roof surface to avoid exposure to refrigerant and oil during service and installation. Failure to follow this notice could result in damage to roof surface.
Removing and Installing Panels
IMPORTANT
Do not allow panels to hang on unit by top tab. Tab is for alignment and not designed to support weight of panel.
IMPORTANT
To help stabilize an outdoor unit, some installations may require strapping the unit to the pad using brackets and anchors commonly available in the marketplace.
WARNING
To prevent personal injury, or damage to panels, unit or structure, be sure to observe the following:
While installing or servicing this unit, carefully stow all removed panels out of the way, so that the panels will not cause injury to personnel, nor cause damage to objects or structures nearby, nor will the panels be subjected to damage (e.g., being bent or scratched).
While handling or stowing the panels, consider any weather conditions, especially windy conditions, that may cause panels to be blown around and battered.
INLET AIR
Figure 6. Rooftop Application and Wind Barrier 
Inches (millimeters)
Page 9
XP17 SERIES
REMOVING AND INSTALLING PANELS
Panel shown slightly rotated to allow top tab to exit (or enter) top slot for removing (or installing) panel.
LOUVERED PANEL REMOVAL
Remove the louvered panels as follows:
LOUVERED PANEL INSTALLATION
Position the panel almost parallel with the unit as illustrated in detail D with the screw side as close to the unit as possible. Then, in a continuous motion:
Detail C
WARNING
1. Remove two screws, allowing the panel to swing open slightly.
2. Hold the panel firmly throughout this procedure Rotate bottom corner of panel away
from hinged corner post until lower three tabs clear the slots as illustrated in detail B.
3. Move panel down until lip of upper tab clears the top slot in corner post as illustrated
in detail A.
1. Slightly rotate and guide the lip of top tab inward as illustrated in detail A and C; then
upward into the top slot of the hinge corner post.
2. Rotate panel to vertical to fully engage all tabs.
3. Holding the panel’s hinged side firmly in place, close the right−hand side of the panel, aligning the screw holes.
4. When panel is correctly positioned and aligned, insert the screws and tighten.
Detail A
LIP
SCREW
HOLES
REMOVE 4 SCREWS TO REMOVE PANEL FOR ACCESSING COMPRESSOR AND CONTROLS.
Position panel with holes aligned; install screws and tighten.
Detail D
ANGLE MAY BE TOO EXTREME
PREFERRED ANGLE FOR INSTALLATION
Maintain minimum panel angle (as close to parallel with the unit as possible) while installing panel.
HOLD DOOR FIRMLY ALONG
THE HINGED SIDE TO MAINTAIN
FULLY−ENGAGED TABS
Figure 7. Removing and Installing Panels
Detail B
ROTATE IN THIS DIRECTION; THEN
DOWN TO REMOVE PANEL
506586−01 10/10
Page 10
New or Replacement Line Set
REFRIGERANT LINE SET
This section provides information on installation or replacement of existing line set. If new or replacement line set is not being installed then proceed to Brazing Connections on page 13.
IMPORTANT
Lennox highly recommends changing line set when converting the existing system from HCFC−22 to HFC−410A. If that is not possible and the line set is the proper size as reference in Table 2, use the procedure outlined under Flushing the System on page 13.
If refrigerant lines are routed through a wall, then seal and isolate the opening so vibration is not transmitted to the building. Pay close attention to line set isolation during installation of any HVAC system. When properly isolated from building structures (walls, ceilings. floors), the refrigerant lines will not create unnecessary vibration and subsequent sounds. See figure 8 for recommended installation practices. Also, consider the following when placing and installing a high−efficiency outdoor unit.
IMPORTANT
Refrigerant lines must not contact structure.
Liquid lines that meter the refrigerant, such as RFC1 liquid lines, must not be used in this application. Existing line set of proper size as listed in table 2 may be reused. If system was previously charged with HCFC−22 refrigerant, then existing line set must be flushed (see Flushing the System on page 16).
Table 2. Refrigerant Line Set  Inches (mm)
Model
−024 and
−030
−036, −042 and −048
−060 3/8" (10)
NOTE  Some applications may required a field provided 7/8" to 1−1/8" adapter
Liquid
Line
3/8" (10) 3/4" (19)
3/8" (10) 7/8" (22)
Vapor
Line
1−1/8"
(29)
L15 line set sizes are depen-
dent on unit match up. See XP17 Engineering Handbook to determine correct line set sizes.
L15
Line Sets
Feet (Meters)
Field Fabricated
NOTE  When installing refrigerant lines longer than 50 feet, see the Lennox Refrigerant Piping Design and Fabrication Guidelines, or contact Lennox Technical Support Product Applications for assistance. :
To obtain the correct information from Lennox, be sure to communicate the following information:
S Model (XP17) and size of unit (e.g. −036).
S Line set diameters for the unit being installed as listed
in table 2 and total length of installation.
S Number of elbows vertical rise or drop in the piping.
The compressor is charged with sufficient Polyol ester oil for line set lengths up to 50 feet. Recommend adding oil to system based on the amount of refrigerant charge in the system. No need to add oil in system with 20 pounds of refrigerant or less. For systems over 20 pounds − add one ounce of every five pounds of refrigerant.
Recommended topping−off POE oils are Mobil EAL ARCTIC 22 CC or ICI EMKARATEt RL32CF.
WARNING
Polyol Ester (POE) oils used with HFC−410A refrigerant absorb moisture very quickly. It is very important that the refrigerant system be kept closed as much as possible. DO NOT remove line set caps or service valve stub caps until you are ready to make connections.
Field refrigerant piping consists of liquid and vapor lines from the outdoor unit to the indoor unit coil (braze connections). Use Lennox L15 (sweat, non−flare) series line set, or field−fabricated refrigerant line sizes as listed in table 2.
IMPORTANT
Mineral oils are not compatible with HFC−410A. If oil
must be added, it must be a Polyol ester oil.
Page 11
XP17 SERIES
Line Set Isolation  The following illustrations are examples of proper refrigerant line set isolation:
REFRIGERANT LINE SET  TRANSITION
FROM VERTICAL TO HORIZONTAL
ANCHORED HEAVY NYLON WIRE TIE OR AUTOMOTIVE
MUFFLER-TYPE HANGER
WALL
STUD
NON−CORROSIVE
METAL SLEEVE
AUTOMOTIVE
MUFFLER-TYPE HANGER
STRAP LIQUID LINE TO VAPOR LINE
LIQUID LINE
VAPOR LINE − WRAPPED IN ARMAFLEX
REFRIGERANT LINE SET  INSTALLING
HORIZONTAL RUNS
To hang line set from joist or rafter, use either metal strapping material or anchored heavy nylon wire ties.
WIRE TIE (AROUND VAPOR LINE ONLY)
8 FEET (2.43 METERS)
STRAPPING
MATERIAL (AROUND
VAPOR LINE ONLY)
TAPE OR WIRE TIE
FLOOR JOIST OR
ROOF RAFTER
8 FEET (2.43 METERS)
NON−CORROSIVE METAL SLEEVE
STRAP THE VAPOR LINE TO THE JOIST OR RAFTER AT 8 FEET (2.43 METERS) INTERVALS THEN STRAP THE LIQUID LINE TO THE VAPOR LINE.
TAPE OR WIRE TIE
REFRIGERANT LINE SET  INSTALLING
VERTICAL RUNS (NEW CONSTRUCTION SHOWN)
NOTE  Insulate liquid line when it is routed through areas where the surrounding ambient temperature could become higher than the temperature of the liquid line or when pressure drop is equal to or greater than 20 psig.
OUTSIDE WALL
WOOD BLOCK
BETWEEN STUDS
VAPOR LINE WRAPPED
WITH ARMAFLEX
OUTSIDE
WALL
PVC
PIPE
FIBERGLASS
INSULATION
VAPOR LINE
SLEEVE
CAULK
LIQUID LINE
NOTE  Similar installation practices should be used if line set is to be installed on exterior of outside wall.
LIQUID LINE
WIRE TIE
INSIDE WALL
STRAP
NON−CORROSIVE METAL SLEEVE
WIRE TIE
WOOD BLOCK
WIRE TIE
STRAP
FLOOR JOIST OR
ROOF RAFTER
506586−01 10/10
Figure 8. Line Set Installation
Page 12
Brazing Connections
Use the procedures outline in figures 9 and 10 for brazing line set connections to service valves.
WARNING
Danger of fire. Bleeding the refrigerant charge from only the high side may result in pressurization of the low side shell and suction tubing. Application of a brazing torch to a pressurized system may result in ignition of the refrigerant and oil mixture − Check the high and low pressures before applying heat.
IMPORTANT
Connect gauge set low pressure side to vapor line service valve and repeat procedure starting at paragraph 4 for brazing the liquid line to service port valve.
IMPORTANT
Allow braze joint to cool before removing the wet rag from the service valve. Temperatures above 250ºF can damage valve seals.
WARNING
When using a high pressure gas such as dry nitrogen to pressurize a refrigeration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kPa).
CAUTION
Brazing alloys and flux contain materials which are hazardous to your health.
Avoid breathing vapors or fumes from brazing operations. Perform operations only in well−ventilated areas.
Wear gloves and protective goggles or face shield to protect against burns.
Wash hands with soap and water after handling brazing alloys and flux.
IMPORTANT
Use silver alloy brazing rods with 5% minimum silver alloy for copper−to−copper brazing. Use 45% minimum alloy for copper−to−brass and copper−to−steel brazing.
WARNING
Fire, Explosion and Personal Safety Hazard.
Failure to follow this warning could result in damage, personal injury or death.
Never use oxygen to pressurize or purge refrigeration lines. Oxygen, when exposed to a spark or open flame, can cause fire and/or an ex­plosion, that could result in property damage, personal injury or death.
Page 13
XP17 SERIES
PIPING PANEL REMOVAL AND PREPARING LINE SET
1
Remove piping panel for easier access to service valves. Cut ends of the refrigerant lines square (free from nicks or dents) and debur the ends. The pipe must remain round. Do not crimp end of the line.
CUT AND DEBUR
LINE SET SIZE MATCHES
SERVICE VALVE CONNECTION
SERVICE VALVE
COPPER TUBE
REDUCER
STUB
CONNECTION
LINE SET SIZE IS SMALLER
THAN CONNECTION
CAP AND CORE REMOVAL
Remove service cap and core from both the suction / vapor and
2
liquid line service ports.
SERVICE PORT CAP
SERVICE PORT CORE
LIQUID LINE SERVICE VALVE
REFRIGERANT LINE
DO NOT CRIMP SERVICE VALVE
CONNECTOR WHEN PIPE IS
SMALLER THAN CONNECTION
ATTACH THE MANIFOLD GAUGE SET FOR BRAZING LIQUID AND SUCTION / VAPOR LINE SERVICE VALVES
3
A Connect gauge set low pressure side to liquid line
service valve (service port).
B Connect gauge set center port to bottle of nitrogen with
regulator.
C With valve core removed from the suction / vapor line
service port, nitrogen flow will have an exit point.
ATTACH
GAUGES
SUCTION / VAPOR SERVICE PORT MUST BE
OPEN AND SERVICE PORT CORE REMOVED
TO ALLOW EXIT POINT FOR NITROGEN FLOW
SUCTION / VAPOR
LINE
INDOOR
UNIT
C
SUCTION /
VAPOR LINE
SERVICE
VALV E
SUCTION / VAPOR LINE
SERVICE VALVE
HIGHLOW
B
OUTDOOR
UNIT
SERVICE PORT CORE
SERVICE PORT CAP
506586−01 10/10
LIQUID LINE
LIQUID LINE SERVICE
VALV E
A
Figure 9. Brazing Procedures
Page 14
NITROGEN
WRAP SERVICE VALVES
To help protect service valve seals during brazing, wrap water saturated cloths around service valve bodies and copper tube stubs. Use
4
additional water saturated cloths underneath the valve body to protect the base paint.
FLOW NITROGEN
Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration
5
gauge set into the valve stem port connection on the liquid service valve and out of the suction / vapor valve stem port. See steps 3A, 3B and 3C on previous page and below for manifold gauge setup.
BRAZE LINE SET
Water saturated cloths must remain water saturated throughout
6
the brazing and cool−down process.
A Braze liquid line to liquid line service valve.
B Braze suction / vapor line to suction / vapor service
valve.
1. FIRE, PERSONAL INJURY, OR PROPERTY DAMAGE will result if you do not wrap a water saturated cloth around both liquid and suction line service valve bodies and copper tube stub while brazing in the line set! The braze, when complete, must be quenched with water to absorb any residual heat.
2. Do not open service valves until refrigerant lines and indoor coil have been leak−tested and evacuated. Refer to procedures provided in this supplement.
WHEN BRAZING LINE SET TO
SERVICE VALVES, POINT FLAME AWAY
FROM SERVICE VALVE.
WARNING
6B
SUCTION / VAPOR LINE
WATER SATURATED CLOTHS
IMPORTANT  Allow braze joint to cool. Apply
additional water saturated cloths to help cool brazed joints. Do not remove water saturated cloths until piping has cooled. Temperatures above 250ºF will damage valve seals.
SUCTION / VAPOR SERVICE PORT
MUST BE OPEN AND SERVICE PORT
CORE REMOVED TO ALLOW EXIT
POINT FOR NITROGEN FLOW
6A
LIQUID LINE
WATER SATURATED
PREPARATION FOR NEXT STEP
After all connections have been brazed, disconnect manifold gauge set from service ports. Apply additional water saturated cloths to both services
7
valves to cool piping. Once piping is cool, remove all water saturated cloths. Refer to the unit installation instructions for the next step in preparing the unit.
CLOTHS
Figure 10. Brazing Procedures (Continued)
Page 15
XP17 SERIES
Flushing Line Set and Indoor Coil
TYPICAL EXISTING FIXED ORIFICE
1A
DISTRIBUTOR
ASSEMBLY
A On fully cased coils, remove the coil access and plumbing panels. B Remove any shipping clamps holding the liquid line and distributor as-
sembly.
C Using two wrenches, disconnect liquid line from liquid line orifice hous-
ing. Take care not to twist or damage distributor tubes during this pro­cess.
D Remove and discard fixed orifice, valve stem assembly if present and
Teflon® washer as illustrated above.
E Use a field−provided fitting to temporary reconnect the liquid line to the
indoor unit’s liquid line orifice housing.
COIL SHOWN)
DISTRIBUTOR TUBES
LIQUID LINE ORIFICE HOUSING
REMOVE AND DISCARD
WHITE TEFLON
(IF PRESENT)
TEFLON® RING
FIXED ORIFICE
®
SEAL
LIQUID LINE ASSEMBLY
(INCLUDES STRAINER)
REMOVAL PROCEDURE (UNCASED
OR
BRASS NUT
1B
TWO PIECE PATCH PLATE
(UNCASED COIL ONLY)
CONNECT GAUGES AND EQUIPMENT FOR FLUSHING PROCEDURE
2
INVERTED HCFC−22 CYLINDER CONTAINS CLEAN HCFC−22 TO BE USED FOR FLUSHING.
A
1
VAPOR LINE
SERVICE VALVE
EXISTING
INDOOR
UNIT
LIQUID LINE SERVICE
VALV E
VAPOR
LIQUID
D
RECOVERY
CYLINDER
A Inverted HCFC−22 cylinder with clean refrigerant to the vapor service
valve.
B HCFC−22 gauge set (low side) to the liquid line valve. C HCFC−22 gauge set center port to inlet on the recovery machine with an
empty recovery tank to the gauge set.
D Connect recovery tank to recovery machines per machine instructions.
OUTDOOR
B
NEW
UNIT
OPENED
C
RECOVERY MACHINE
GAUGE
MANIFOLD
LOW HIGH
CLOSED
TANK RETURN
INLET
DISCHARGE
TYPICAL EXISTING EXPANSION VALVE REMOVAL PROCEDURE (UNCASED COIL SHOWN)
ORIFICE
HOUSING
EQUALIZER LINE
STUB END
TEFLON RING
VAPOR
CHECK
EXPANSION
VALV E
®
LIQUID LINE
ASSEMBLY WITH
BRASS NUT
LINE
TEFLON
RING
®
SENSING
LINE
LIQUID
LINE
LIQUID LINE
DISTRIBUTOR
TUBES
DISTRIBUTOR
ASSEMBLY
MALE EQUALIZER
LINE FITTING
SENSING BULB
A On fully cased coils, remove the coil access and plumbing panels. B Remove any shipping clamps holding the liquid line and distributor
assembly.
C Disconnect the equalizer line from the check expansion valve
equalizer line fitting on the vapor line.
D Remove the vapor line sensing bulb. E Disconnect the liquid line from the check expansion valve at the liquid
line assembly.
F Disconnect the check expansion valve from the liquid line orifice
housing. Take care not to twist or damage distributor tubes during this process.
G Remove and discard check expansion valve and the two Teflon® rings. H Use a field−provided fitting to temporary reconnect the liquid line to the
indoor unit’s liquid line orifice housing.
FLUSHING LINE SET
The line set and indoor unit coil must be flushed with at least the
3
same amount of clean refrigerant that previously charged the system. Check the charge in the flushing cylinder before proceeding.
A Set the recovery machine for liquid recovery and start the
recovery machine. Open the gauge set valves to allow the recovery machine to pull a vacuum on the existing system line
B
set and indoor unit coil.
B Invert the cylinder of clean HCFC−22 and open its valve to allow
liquid refrigerant to flow into the system through the vapor line valve. Allow the refrigerant to pass from the cylinder and through the line set and the indoor unit coil before it enters the recovery machine.
C After all of the liquid refrigerant has been recovered, switch the
recovery machine to vapor recovery so that all of the HCFC−22 vapor is recovered. Allow the recovery machine to pull down to 0 the system.
D Close the valve on the inverted HCFC−22 drum and the gauge
set valves. Pump the remaining refrigerant out of the recovery machine and turn the machine off.
506586−01 10/10
Figure 11. Flushing Line Set and Indoor Coil
Page 16
Installing Indoor Expansion Valve
This outdoor unit is designed for use in systems that use check expansion valve metering device. See the Lennox XP17 Engineering Handbook for approved check expansion valve kit match−ups and application information. The check
expansion valve unit can be installed internal or external to the indoor coil. In applications where an uncased coil is being installed in a field−provided plenum, install the check expansion valve in a manner that will provide access for field servicing of the check expansion valve. Refer to below illustration for reference during installation of check expansion valve unit.
INDOOR EXPANSION VALVE INSTALLATION
TWO PIECE
PATCH PLATE
(UNCASED
COIL ONLY)
DISTRIBUTOR
TUBES
DISTRIBUTOR
ASSEMBLY
MALE EQUALIZER LINE
FITTING (SEE
EQUALIZER LINE INSTALLATION FOR FURTHER DETAILS)
(Uncased Coil Shown)
LIQUID LINE
ORIFICE
HOUSING
STUB
END
TEFLON RING
EQUALIZER LINE
VAPOR
CHECK
EXPANSION
VALV E
®
ASSEMBLY WITH
LINE
TEFLON
RING
SENSING
LIQUID LINE
BRASS NUT
LIQUID LINE
Sensing bulb insulation is required if mounted external to the coil casing. sensing bulb installation for bulb positioning.
EQUALIZER LINE INSTALLATION
A Remove and discard either the flare seal cap or flare nut
with copper flare seal bonnet from the equalizer line port on the vapor line as illustrated in the figure to the right.
B Remove and discard either the flare seal cap or flare nut
with copper flare seal bonnet from the equalizer line port on the vapor line as illustrated in the figure to the right.
®
LINE
A Remove the field−provided fitting that temporary
reconnected the liquid line to the indoor unit’s distributor assembly.
B Install one of the provided Teflon® rings around the
stubbed end of the check expansion valve and lightly lubricate the connector threads and expose surface of the Teflon® ring with refrigerant oil.
C Attach the stubbed end of the check expansion valve to
the liquid line orifice housing. Finger tighten and use an appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in the figure above, or 20 ft−lb.
D Place the remaining Teflon® washer around the other
end of the check expansion valve. Lightly lubricate connector threads and expose surface of the Teflon ring with refrigerant oil.
E Attach the liquid line assembly to the check expansion
valve. Finger tighten and use an appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in the figure above or 20 ft−lb.
SENSING BULB INSTALLATION
A Attach the vapor line sensing bulb in the proper
orientation as illustrated to the right using the clamp and screws provided.
NOTE  Confirm proper thermal contact between vapor line and check expansion bulb before insulating the sensing bulb once installed.
B Connect the equalizer line from the check expansion
valve to the equalizer vapor port on the vapor line. Finger tighten the flare nut plus 1/8 turn (7 ft−lbs) as illustrated below.
VAPOR LINE
BULB
12
ON LINES SMALLER THAN 7/8", MOUNT SENSING BULB AT EITHER THE 3 OR 9 O’CLOCK POSITION.
BULB
®
1/2 Turn
11
10
9
8
7
1/8 Turn
11
10
9
8
7
12
1
2
3
4
5
6
12
1
2
3
4
5
6
FLARE SEAL CAP
OR
FLARE NUT
COPPER FLARE SEAL BONNET
MALE BRASS EQUALIZER LINE FITTING
VAPOR LINE
VAPOR LINE
BULB
NOTE  NEVER MOUNT ON BOTTOM OF LINE.
Figure 12. Installing Indoor Expansion Valve
Page 17
ON 7/8" AND LARGER LINES, MOUNT SENSING BULB AT EITHER THE 4 OR 8 O’CLOCK
12
POSITION. NEVER MOUNT ON BOTTOM OF LINE.
BULB
XP17 SERIES
IMPORTANT
Leak Test Line Set and Indoor Coil
The Environmental Protection Agency (EPA) prohibits the intentional venting of HFC refrigerants during maintenance, service, repair and disposal of appliance. Approved methods of recovery, recycling or reclaiming must be followed.
IMPORTANT
If this unit is being matched with an approved line set or indoor unit coil which was previously charged with mineral oil, or if it is being matched with a coil which was manufactured before January of 1999, the coil and line set must be flushed prior to installation. Take care to empty all existing traps. Polyol ester (POE) oils are used in Lennox units charged with HFC−410A refrigerant. Residual mineral oil can act as an insulator, preventing proper heat transfer. It can also clog the expansion device, and reduce the system performance and capacity. Failure to properly flush the system per the instructions below will void the warranty.
CONNECT GAUGE SET
A Connect an HFC−410A manifold gauge set high pressure
1
hose to the vapor valve service port.
NOTE  Normally, the high pressure hose is connected to the liquid line port. However, connecting it to the vapor port better protects the manifold gauge set from high pressure damage.
B With both manifold valves closed, connect the cylinder of
HFC−410A refrigerant to the center port of the manifold gauge set.
NOTE  Later in the procedure, the HFC−410A container will be replaced by the nitrogen container.
IMPORTANT
Leak detector must be capable of sensing HFC refrigerant.
WARNING
When using a high pressure gas such as dry nitrogen to pressurize a refrigeration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kPa).
WARNING
Refrigerant can be harmful if it is inhaled. Refrigerant must be used and recovered responsibly.
Failure to follow this warning may result in personal injury or death.
HIGHLOW
MANIFOLD GAUGE SET
OUTDOOR UNIT
B
A
TEST FOR LEAKS
After the line set has been connected to the indoor and outdoor units, check the line set connections and indoor unit for leaks. Use the
2
following procedure to test for leaks:
A With both manifold valves closed, connect the cylinder of HFC−410A refrigerant to the center port of the manifold gauge set. Open the valve
B Open the high pressure side of the manifold to allow HFC−410A into the line set and indoor unit. Weigh in a trace amount of HFC−410A. [A
C Connect a cylinder of dry nitrogen with a pressure regulating valve to the center port of the manifold gauge set.
D Adjust dry nitrogen pressure to 150 psig (1034 kPa). Open the valve on the high side of the manifold gauge set in order to pressurize the line set
E After a few minutes, open one of the service valve ports and verify that the refrigerant added to the system earlier is measurable with a leak
F After leak testing disconnect gauges from service ports.
506586−01 10/10
TO VAPOR
SERVICE VALVE
NITROGEN
HFC−410A
on the HFC−410A cylinder (vapor only).
trace amount is a maximum of two ounces (57 g) refrigerant or three pounds (31 kPa) pressure]. Close the valve on the HFC−410A cylinder and the valve on the high pressure side of the manifold gauge set. Disconnect the HFC−410A cylinder.
and the indoor unit.
detector.
Figure 13. Leak Test
Page 18
Evacuating Line Set and Indoor Coil
CONNECT GAUGE SET
NOTE  Remove cores from service valves (if not already done).
1
A Connect low side of manifold gauge set
with 1/4 SAE in−line tee to vapor line service valve
B Connect high side of manifold gauge
set to liquid line service valve
C Connect micron gauge available
connector on the 1/4 SAE in−line tee.
D Connect the vacuum pump (with
vacuum gauge) to the center port of the manifold gauge set. The center port line will be used later for both the HFC−410A and nitrogen containers.
NITROGEN
HFC−410A
VACUUM PUMP
OUTDOOR
UNIT
A
B
A34000 1/4 SAE TEE WITH SWIVEL COUPLER
500
C
MICRON
GAUGE
MANIFOLD
GAUGE SET
TO VAPOR
SERVICE VALVE
TO LIQUID LINE SERVICE VALVE
LOW
D
EVACUATE THE SYSTEM
A Open both manifold valves and start the vacuum pump.
2
B Evacuate the line set and indoor unit to an absolute pressure of 23,000 microns (29.01 inches of mercury).
NOTE  During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once. A rapid rise in pressure indicates a relatively large leak. If this occurs, repeat the leak testing procedure.
NOTE  The term absolute pressure means the total actual pressure within a given volume or system, above the absolute zero of pressure. Absolute pressure in a vacuum is equal to atmospheric pressure minus vacuum pressure.
C When the absolute pressure reaches 23,000 microns (29.01 inches of mercury), perform the following:
S Close manifold gauge valves S Close valve on vacuum pump S Turn off vacuum pump S Disconnect manifold gauge center port hose from vacuum pump S Attach manifold center port hose to a dry nitrogen cylinder with pressure regulator set to 150 psig (1034 kPa) and purge the hose. S Open manifold gauge valves to break the vacuum in the line set and indoor unit. S Close manifold gauge valves.
D Shut off the dry nitrogen cylinder and remove the manifold gauge hose from the cylinder. Open the manifold gauge valves to release the
dry nitrogen from the line set and indoor unit.
E Reconnect the manifold gauge to the vacuum pump, turn the pump on, and continue to evacuate the line set and indoor unit until the
absolute pressure does not rise above 500 microns (29.9 inches of mercury) within a 20−minute period after shutting off the vacuum pump and closing the manifold gauge valves.
F When the absolute pressure requirement above has been met, disconnect the manifold hose from the vacuum pump and connect it to an
upright cylinder of HFC−410A refrigerant. Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and indoor unit.
G Perform the following:
S Close manifold gauge valves. S Shut off HFC−410A cylinder. S Reinstall service valve cores by removing manifold hose from service valve. Quickly install cores with core
tool while maintaining a positive system pressure.
S Replace stem caps and secure finger tight, then tighten an additional one−sixth (1/6) of a turn as illustrated.
RECOMMEND
MINIMUM 3/8" HOSE
10
9
11
8
7
1/6 TURN
12
1
5
6
HIGH
2
3
4
Figure 14. Evacuating System
Page 19
XP17 SERIES
IMPORTANT
Use a thermocouple or thermistor electronic vacuum gauge that is calibrated in microns. Use an instrument capable of accurately measuring down to 50 microns.
WARNING
Danger of Equipment Damage. Avoid deep vacuum operation. Do not use compressors to evacuate a system. Extremely low vacuums can cause internal arcing and compressor failure. Damage caused by deep vacuum operation will void warranty.
Evacuating the system of non−condensables is critical for proper operation of the unit. Non−condensables are defined as any gas that will not condense under
temperatures and pressures present during operation of an air conditioning system. Non−condensables and water suction combine with refrigerant to produce substances that corrode copper piping and compressor parts.
Electrical
In the U.S.A., wiring must conform with current local codes and the current National Electric Code (NEC). In Canada, wiring must conform with current local codes and the current Canadian Electrical Code (CEC).
Refer to the furnace or air handler installation instructions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size.
24VAC TRANSFORMER
Use the transformer provided with the furnace or air handler for low-voltage control power (24VAC − 40 VA minimum)
SIZE CIRCUIT AND INSTALL DISCONNECT SWITCH
1
Refer to the unit nameplate for minimum circuit ampacity, and maximum fuse or circuit breaker (HACR per NEC). Install power wiring and properly sized disconnect switch.
SERVICE
DISCONNECT
SWITCH
NOTE  Units are approved for use only with copper conductors. Ground unit at disconnect switch or to an earth ground.
WARNING
Electric Shock Hazard. Can cause injury or death. Unit must be grounded in accordance with national and local codes.
Line voltage is present at all components when unit is not in operation on units with single-pole contactors. Disconnect all remote electric power supplies before opening access panel. Unit may have multiple power supplies.
INSTALL THERMOSTAT
Install room thermostat (ordered separately) on an inside wall
2
approximately in the center of the conditioned area and 5 feet (1.5m) from the floor. It should not be installed on an outside wall or where it can be affected by sunlight or drafts.
THERMOSTAT
5 FEET
(1.5M)
NOTE  24VAC, Class II circuit connections are made in the control box.
CAUTION
ELECTROSTATIC DISCHARGE
(ESD)
Precautions and Procedures
506586−01 10/10
Electrostatic discharge can affect electronic components. Take precautions during unit installation and service to protect the unit’s electronic controls. Precautions will help to avoid control exposure to electrostatic discharge by putting the unit, the control and the technician at the same electrostatic potential. Neutralize electrostatic charge by touching hand and all tools on an unpainted unit surface before performing any service procedure
Page 20
A. ROUTE CONTROL WIRES  NON−COMMUNICATING
Install low voltage control wiring from outdoor to indoor unit and from
3
thermostat to indoor unit.
A Run 24VAC control wires through hole with grommet.
B Make 24VAC control wire connections to heat pump control (A175) .
NOTE  Do not bundle any excess 24VAC control wires inside control box.
NOTE  Wire tie provides low voltage wire strain relief and to maintain
separation of field installed low and high voltage circuits.
NOTE  For proper voltages, select control wires gauge per table below.
WIRE RUN LENGTH AWG# INSULATION TYPE
LESS THAN 100’ (30 METERS) 18 TEMPERATURE RATING
MORE THAN 100’ (30 METERS) 16 35ºC MINIMUM.
CONTROL (A175)
B. ROUTE CONTROL WIRES  COMMUNICATING
Maximum length of wiring (18 gauge) for all connections on the RSBus is limited to 1500 feet (457 meters). Color−coded, temperature rating 95ºF (35ºC) minimum, solid core. (Class II Rated Wiring)
B
HEAT PUMP
HOLE
CONTROL BOX
A
ROUTE HIGH VOLTAGE AND GROUND WIRES
Any excess high voltage field wiring should be trimmed and secured away from any low voltage field wiring. To facilitate a conduit, a
4
cutout is located in the bottom of the control box. Connect conduit to the control box using a proper conduit fitting.
HIGH VOLTAGE
CONDUIT HOLE
WATERTIGHT
CONDUIT
FITTING
WATERTIGHT
FLEXIBLE CONDUIT
TO SERVICE
DISCONNECT BOX
PIPING PANEL
GROUND LUG
CONTACTOR
CONTROL BOX
ELECTRICAL INLET
(HIGH VOLTAGE)
WIRING ENTRY POINTS
ELECTRICAL INLET (CONTROL WIRING  LOW VOLTAGE). USE BUSHING PROVIDED IN BAG ASSEMBLY HERE.
ACCESS VIEW
Page 21
XP17 SERIES
506586−01 10/10
Figure 15. Typical XP17 Wiring
Page 22
Heat Pump Control (A175) Jumpers and Terminals
HEAT PUMP CONTROL  ONE STAGE
Table 3 on page 24 provides additional information concerning jumpers, links, and connections for the heat pump control.
DS11 and DS14
LED ALERT CODES
*30
SECOND DELAY
30
0
SECOND DELAY
0
DS13 and DS15
LED ALERT CODES
E47
100
DEGREE
TARGET
100
90
70
50
90 DEGREE TARGET
100
90
70
E37
COMPRESSOR SHIFT DELAY
E33
FIELD TEST
50
70 DEGREE
TARGET
100
90
70
50
*50
DEGREE
TARGET
100
90
70
50
DEFROST TERMINATION TEMPERATURE
DS12
RECEIVING DATA INDICATOR (COMMUNICATION MODE ONLY)
W1
CUT FOR HUMIDITROL APPLICATION (TWO−STAGE UNITS ONLY)
Figure 16. Heat Pump Control (A175) Jumpers, Connections and LED Locations
Page 23
XP17 SERIES
Table 3. Heat Pump Control (A175) Jumper and Terminal Descriptions
Board ID Label Description
E12 PSC Fan 240 VAC output connection for outdoor fan.
E16 PSC Fan 240 VAC input connection for outdoor fan.
W 24VAC output for defrost auxiliary heat output.
L Thermostat service light connection.
Y2 24VAC thermostat input/output for second stage operation of the unit.
Y1 24VAC thermostat input for first stage operation of the unit.
E18
E19 and E20 O OUT 24 VAC output connection for reversing valve.
E21 and E22 LO−PS Connection for low−pressure switch (2.4 milliamps @ 18VAC)
E31 and E32 Y1 OUT 24 VAC common output, switched for enabling compressor contactor.
E24 and E25 HS−PS S87 connection for high−pressure switch (E25) and 24VAC (E24) to A177 R" input.
E26 FAN 1 First Stage and second stage basic and precision dehumidification ECM fan motor 24VDC output connection 1.
E27 FAN 2 Second stage basic and precision dehumidification ECM fan motor 24VDC output connection 2.
E28 FAN C ECM common connection for ECM fan.
E30
E33 Field Test
E37
E47
W1 Short DS To R Cut for Humiditrol (EDA) application. Use only in two−stage units.
* Factory default setting
O 24VAC thermostat input for reversing valve operation
DS Humiditrol Input
C 24VAC system common
i− Input/Output − RSBus data low. Used in communicating mode only with compatible indoor thermostat.
i+ Input/Output − RSBus data high. Used in communicating mode only with compatible indoor thermostat.
R 24VAC system power input
Six position square pin header. P4 provides connections for the temperature sensors.
DIS (YELLOW)
AMB (BLACK) (RT13)
COIL (BROWN) (RT21)
Comp Shift Delay
50*
70
90
100
Not used.
AMB 1  Outdoor ambient temperature sensor supply.
AMB 2  Outdoor ambient temperature return.
Range is −40ºF to +140ºF
COIL 1  Outdoor coil temperature sensor supply.
COIL 2  Outdoor coil temperature sensor return
Range is −40ºF to 140ºF. Sensor is clipped on a 5/16" copper return bend.
This jumper allows service personnel to defeat the timed off control, initiate or terminate a defrost and field programming of unit nominal capacity feature.
Two position square pin header. When jumper is installed, a 30−second compressor shift delay which de−energizes the compressor contactor output, second−stage solenoid output (if on) and the ECM fan outputs. After the timer expires, the compressor contactor and ECM fan outputs are energized. If no jumper is installed, it changes the reversing valve with de−energizing the outputs immediately.
Seven position square pin header. E47 provides selection of the defrost terminate temperature based on the posi­tion of the selection jumper. The defrost termination temperature is measured by the defrost coil sensor. The jumper termination pin is factory set at 50°F (10°C). If the temperature jumper is not installed, the default termination tem­perature is 90°F (32°C). In addition, it provides selection points for enabling the field test mode.
506586−01 10/10
Page 24
Field Control Wiring
OneStage
Heat Pump Control
2
W
L
Y2
Y1
O
DS
C
i
i+
R
Air Hander Control
DS
O
5
6
L
H
DH
R
C
Y1
Y2
G
W3
3
W2
W1
ComfortSense[ 7000 Thermostats
Catalog # Y0349 or Y2081
R
Onboard link
G
W2
W1
O
L
H
D
B
Y2
Y1
Low voltage thermostat wiring
Flat metal jumper
1
C
4
T
T
1. Thermostat T terminals are used for outdoor sensor input. Use for thermostat’s outdoor temperature display (optional).
®
2. R to L connection is required for this model when using the ComfortSense
required and ordered separately.
3. Air handler control ships from factory with metal jumpers installed across W1, W2 and W3. For one−stage electric heat, do not remove factory
installed metal jumpers.
4. Air handler control ships from factory with metal jumpers installed across W1, W2 and W3. For two−stage electric heat, remove factory installed metal jumper between W1 to W2. Then connect thermostat wire between the air handler control’s W2 and the thermostat’s W2 terminal.
5. Cut on−board link (clippable wire) from R−O HEAT PUMP for heat pump applications.
®
6. Cut on−board link (clippable wire) DS−R for Humiditrol setting. See air handler installation instruction or engineering handbook for lowest fan speed information.
or Harmony IIIt applications. This will slow the indoor blower motor to the lowest speed
7000 − catalog number Y0349 only. Resistor Kit (catalog number 47W97)
Figure 17. ComfortSense® 7000 Series Thermostat  Air Hander/One−Stage Heat Pump
Page 25
XP17 SERIES
OneStage
Heat Pump Control
W
L
Y2
Y1
O
DS
Furnace Control
DS
O
4
L
H
DH
R
ComfortSense[ 7000 Thermostats
Catalog # Y0349 or Y2081
R
3
G
W2
W1
O
L
H
Onboard link
Low voltage thermostat wiring
2
C
i
C
Y1
Y2
G
i+
R
W2
D
B
Y2
Y1
C
1
T
W1
1. Thermostat T terminals are used for outdoor sensor input. Use for thermostat’s outdoor temperature display (optional).
®
2. R to L connection is required for this model when using the ComfortSense
47W97) required and ordered separately.
3. Cut on−board link W951 (clippable wire) from R−O HEAT PUMP for heat pump applications.
®
4. Cut onboard link (clippable wire) DSR for Humiditrol
setting. See furnace installation instruction or engineering handbook for lowest fan speed information.
NOTE − For defrost temper with furnace, the optional 67M41 temper kit would be wired between W of from the heat pump control (A175) to the W1 of the furnace control. The kit allows for the furnace to cycle on and off during a defrost. It protects the compressor from high refrigeration pressures during defrost.
or Harmony IIIt applications. This will slow the indoor blower motor to the lowest speed
7000 − catalog number Y0349 only. Resistor Kit (catalog number
T
506586−01 10/10
Figure 18. ComfortSense® 7000 Series Thermostat  Furnace/One−Stage Heat Pump
Page 26
Servicing Units Delivered Void of Charge
If the outdoor unit is void of refrigerant, clean the system using the procedure described below.
1. Leak check system using procedure outlined on page
18.
2. Evacuate the system using procedure outlined on page 19.
3. Use nitrogen to break the vacuum and install a new filter drier in the system.
4. Evacuate the system again using procedure outlined on page 19.
5. Weigh in refrigerant using procedure outlined in figure
21.
6. Monitor the system to determine the amount of moisture remaining in the oil. It may be necessary to replace the filter drier several times to achieve the required dryness level. If system dryness is not
verified, the compressor will fail in the future.
3. After evacuation is complete, open both the liquid and vapor line service valves to release the refrigerant charge contained in outdoor unit into the system.
4. Replace the stem caps and tighten to the value listed in table 1.
5. Check voltage supply at the disconnect switch. The voltage must be within the range listed on the unit’s nameplate. If not, do not start the equipment until you have consulted with the power company and the voltage condition has been corrected.
6. Set the thermostat for a cooling demand. Turn on power to the indoor indoor unit and close the outdoor unit disconnect switch to start the unit.
7. Recheck voltage while the unit is running. Power must be within range shown on the nameplate.
8. Check system for sufficient refrigerant by using the procedures listed under System Refrigerant.
Unit Start−Up
IMPORTANT
If unit is equipped with a crankcase heater, it should be energized 24 hours before unit start−up to prevent compressor damage as a result of slugging.
1. Rotate fan to check for binding.
2. Inspect all factory− and field−installed wiring for loose connections.
GAUGE SET
CONNECTIONS FOR TESTING AND CHARGING
TRUE SUCTION PORT
B
CONNECTION
REFRIGERANT TANK
CHARGE IN
LIQUID PHASE
System Refrigerant
This section outlines procedures for:
1. Connecting gauge set for testing and charging (see figure 19.
2. Checking and adjusting indoor airflow as described in figure 20.
3. Add or remove refrigerant using the weigh in method provided in figure 21, and verifying charge using subcooling method described in figure 22.
MANIFOLD GAUGE SET
LOW
HIGH
OUTDOOR UNIT
A
DIGITAL SCALE
INSIDE OUTDOOR UNIT
TEMPERATURE
D
SENSOR
AClose manifold gauge set valves and connect the center hose to a cylinder of HFC−410A. Set for liquid phase charging.
BConnect the manifold gauge set’s low pressure side to the true suction port.
CConnect the manifold gauge set’s high pressure side to the liquid line service port.
DPosition temperature sensor on liquid line near liquid line service port.
LINE SERVICE
TO LIQUID
VALV E
C
TEMPERATURE SENSOR
(LIQUID LINE)
Figure 19. Gauge Set Connections
Page 27
XP17 SERIES
ADDING OR REMOVING REFRIGERANT
This system uses HFC−410A refrigerant which operates at much higher pressures than HCFC−22. The pre−installed liquid line filter drier is approved for use with HFC−410A only. Do not replace it with components designed for use with HCFC−22.
COOLING MODE INDOOR AIRFLOW CHECK
Check airflow using the Delta−T (
DT) process using the
illustration in figure 20.
HEATING MODE INDOOR AIRFLOW CHECK
Blower airflow (CFM) may be calculated by energizing electric heat and measuring:
S Temperature rise between the return air and supply air
temperatures at the indoor coil blower unit,
S Measuring voltage supplied to the unit, S Measuring amperage being drawn by the heat unit(s).
Then, apply the measurements taken in following formula to determine CFM:
CFM =
Amps x Volts x 3.41
1.08 x Temperature rise (F)
AIRFLOW
DRY
BULB
T
C
53º
All temperatures are expressed in ºF
DROP
19º
INDOOR COIL
TEMPERATURE OF AIR ENTERING INDOOR COIL ºF
A
WET−BULB ºF
DT
80 24 24 24 23 23 22 22 22 20 19 18 17 16 15 78 23 23 23 22 22 21 21 20 19 18 17 16 15 14 76 22 22 22 21 21 20 19 19 18 17 16 15 14 13 74 21 21 21 20 19 19 18 17 16 16 15 14 13 12
DRY−BULB
72 20 20 19 18 17 17 16 15 15 14 13 12 11 10 70 19 19 18 18 17 17 16 15 15 14 13 12 11 10
57 58 59 60 61 62 63 64 65 66 67 68 69 70
B
AIR FLOWAIR FLOW
B
64º
INDOOR COIL
WET BULB
A
72º
DRY BULB
Use the following procedure to adjust for optimal air flow across the indoor coil:
1. DETERMINE THE DESIRED DT  MEASURE ENTERING AIR TEMPERATURE USING DRY BULB (A) AND WET BULB (B). DT IS THE INTERSECTING VALUE OF A AND B IN THE TABLE (SEE TRIANGLE).
2. Find temperature drop across coil  Measure the coil’s dry bulb entering and leaving air temperatures (A and C). Temperature Drop Formula:
(T
) = A minus C.
Drop
3. Determine if fan needs adjustment  If the difference between the measured T
is needed. See example below:
ASSUME DT = 15 AND A TEMP. = 72º, THESE C TEMPERATURES WOULD NECESSITATE STATED ACTIONS:
T
53º 19 15 = 4 INCREASE THE AIRFLOW 58º 14 15 = −1 (WITHIN +3º RANGE) NO CHANGE 62º 10 15 = −5 DECREASE THE AIRFLOW
4. ADJUST THE FAN SPEED  See indoor unit instructions to increase/decrease fan speed.
DT = ºF ACTION
DROP
Changing air flow affects all temperatures; recheck temperatures to confirm that the temperature drop and DT are within +3º.
and the desired DT (T
Drop
DT) is within +3º, no adjustment
Drop
Figure 20. Checking Indoor Airflow over Evaporator Coil using Delta−T Chart Formula
Page 28
506586−01 10/10
Use WEIGH IN method for adding initial refrigerant charge, and then use SUBCOOLING method for for verifying refrigerant charge.
WEIGH IN
CHARGING METHOD
CALCULATING SYSTEM CHARGE FOR OUTDOOR UNIT VOID OF CHARGE
If the system is void of refrigerant, first, locate and repair any leaks and then weigh in the refrigerant charge into the unit. To calculate the total refriger­ant charge:
Amount specified on
nameplate
Adjust amount. for variation in line set
length listed on line set length table below.
+
Additional charge specified per indoor
unit match−ups starting on page 30.
+
Total Charge
=
Refrigerant Charge per Line Set Length
LIQUID LINE SET DIAMETER
3/8" (9.5 MM)
*If line length is greater than 15 ft. (4.6 m), add this amount. If line length is less than 15 ft. (4.6 m), subtract this amount.
NOTE  Insulate liquid line when it is routed through areas where the surrounding ambient temperature could become higher than the temperature of the liquid line or when pressure drop is equal to or greater than 20 psig.
NOTE  The above nameplate is for illustration purposes only. Go to actual nameplate on outdoor unit for charge information.
OUNCES PER 5 FEET (G PER 1.5 M) ADJUST FROM 15 FEET (4.6 M)
3 OUNCE PER 5’ (85 G PER 1.5 M)
LINE SET*
Figure 21. Using HFC−410A Weigh In Method
SUBCOOLING
1. Check the airflow as illustrated in figure 20 to be sure the indoor airflow is as required. (Make any air flow adjustments before continuing with the following procedure.)
2. Measure outdoor ambient temperature; determine whether to use cooling mode or heating mode to check charge.
3. Connect gauge set.
4. Check liquid and vapor line pressures. Compare pressures with either heat or cooling mode normal operating pressures in table 10, Normal Operating Pressures, High Stage.
NOTE  The reference table is a general guide. Expect minor pressure variations. Significant differences may mean improper charge or other system problem.
5. Set thermostat for heat/cool demand, depending on mode being used:
USING COOLING MODE  When the outdoor ambient temperature is 60°F (15°C) and above. Target
subcooling values (second stage − high capacity) in table 10 are based on 70 to 80°F (21−27°C) indoor return air temperature; if necessary, operate heating to reach that temperature range; then set thermostat to cooling mode setpoint to 68ºF (20ºC) which should call for second−stage (high stage) cooling. When pressures have stabilized, continue with Step 6.
USING HEATING MODE  When the outdoor ambient temperature is below 60°F (15°C). Target subcooling
values (second−stage − high capacity) in table 10 are based on 65−75°F (18−24°C) indoor return air temperature; if necessary, operate cooling to reach that temperature range; then set thermostat to heating mode setpoint to 77ºF (25ºC) which should call for second−stage (high stage) heating. When pressures have stabilized, continue with Step 6.
6. Read the liquid line temperature; record in the LIQº space.
7. Read the liquid line pressure; then find its corresponding temperature in the temperature/ pressure chart listed in table 11 and record it in the SATº space.
8. Subtract LIQº temperature from SATº temperature to determine subcooling; record it in SCº space.
9. Compare SCº results with tables 4 through 9, being sure to note any additional charge for line set and/or match− up.
10. If subcooling value is greater than shown in tables 4 through 9 for the applicable unit, remove refrigerant; if less than shown, add refrigerant.
11. If refrigerant is added or removed, repeat steps 5 through 6 to verify charge.
12. Disconnect gauge set and re−install both the liquid and suction service valve caps.
SATº LIQº – SCº =
USE
COOLING
MODE
60ºF
(15ºC)
USE
HEATING
MODE
CHARGING METHOD
Figure 22. Using HFC−410A Subcooling Method  High Stage (High Capacity)
Page 29
XP17 SERIES
Air Handler / Coil Match ups and Targeted Subcooling Values
g
g
g
g
g
g
Listed below are the targeted subcooling and charging values for approved indoor unit air handler / coil match ups. This information is also listed on the unit charging sticker located on the access panel.
* Indicates amount of charge required in additional to charge shown on unit nameplate. Remember to consider line set length differences.
Table 4. XP17−024
Target
INDOOR MATCHUPS
CBX27UH−024 16 3 1 6 CBX27UH−030 16 5 1 9 CBX32M−030 16 3 1 6 CBX32M−036 16 5 1 9 CBX32MV−024/030 16 3 1 6 CBX32MV−036 16 5 1 9 CBX40UHV−024, −030, −036 16 5 1 9 CH23−51 16 3 1 6 CH33−31 16 3 0 11 CH33−42 16 3 0 11 CR33−48 28 3 0 0 CX34−31 16 3 1 6 CX34−38 16 5 1 9
Subcooling
Heat Cool
5ºF)(+1ºF)
(+
*Add
charge
lb oz
Table 5. XP17−030
Target
INDOOR MATCHUPS
CBX27UH−030, −036 15 5 1 3 CBX32M−030 19 5 1 7 CBX32M−036 15 5 1 3 CBX32MV−024/030 19 5 1 7 CBX32MV−036 15 5 1 3 CBX40UHV−024, −030, −036 15 5 1 3 CH23−51 19 5 1 7 CH33−31 19 5 1 7 CH33−42 19 5 1 7 CR33−48 30 4 0 0 CX34−31 19 5 1 7 CX34−38 15 5 1 3 CX34−43 6 4 0 11 CX34−44/48B 15 5 1 3 CX34−49 8 8 1 14 CX34−50/60C 6 4 0 11
Subcooling
Heat Cool
5ºF)(+1ºF)
(+
*Add
charge
lb oz
Table 6. XP17−036
Target
INDOOR MATCHUPS
CBX27UH−036 19 7 1 1 CBX27UH−042 12 5 2 4 CBX32M−036, −042 19 7 1 1 CBX32M−048 12 5 2 4 CBX32MV−036 19 7 1 1 CBX32MV−048 12 5 2 4 CBX40UHV−036 19 7 1 1 CBX40UHV−042, −048 12 5 2 4 CH23−51 19 7 0 10 CH33−42, −43 18 6 1 4 CH33−44/48B 18 6 1 4 CH33−48C 18 6 1 4 CR33−48 32 4 0 0 CX34−38 19 7 1 1 CX34−43 18 6 1 4 CX34−44/48B 19 7 1 1 CX34−49 9 9 2 8 CX34−50/60C 18 6 1 4
Subcooling
Heat Cool
5ºF)(+1ºF)
(+
*Add
charge
lb oz
INDOOR MATCHUPS
CBX27UH−042, −048 12 4 1 0 CBX32M−048 12 4 1 0 CBX32MV−048 12 4 1 0 CBX40UHV−042, −048 12 4 1 0 CH23−51 17 7 0 0 CH33−43 14 4 0 0 CH33−44/48B, −48C, −49C 14 4 0 0 CH33−50/60C 14 4 0 0 CR33−48 36 4 0 0 CR33−50/60 11 6 0 8 CX34−38 19 6 0 6 CX34−43 14 4 0 0 CX34−44/48B 19 6 0 6 CX34−49 8 7 1 0 CX34−50/60C 14 4 0 0
INDOOR MATCHUPS
CBX27UH−048 23 3 0 2 CBX27UH−060 15 8 2 8 CBX32M−048 23 3 0 2 CBX32M−060 20 5 1 0 CBX32MV−048 23 3 0 2 CBX32MV−060 20 5 1 0 CBX32MV−068 15 5 1 7 CBX40UHV−048 23 3 0 2 CBX40UHV−060 20 5 1 0 CH23−68 15 8 2 8 CH33−49C 20 5 1 0 CH33−50/60C 20 5 1 0 CH33−60D 25 4 0 0 CH33−62D 15 5 1 7 CR33−50/60, −60D 21 4 0 0 CX34−49 15 6 1 0 CX34−60D 25 4 0 0 CX34−62C, −62D 11 4 1 5
INDOOR MATCHUPS
CBX27UH−048 14 3 0 0 CBX27UH−060 15 8 1 8 CBX32M−048 14 3 0 0 CBX32M−060 16 3 0 12 CBX32MV−048 14 3 0 0 CBX32MV−060 16 3 0 12 CBX32MV−068 13 5 0 15 CBX40UHV−048 14 3 0 0 CBX40UHV−060 16 3 0 12 CH23−68 18 8 1 8 CH33−49C 16 3 0 12 CH33−50/60C 16 3 0 12 CH33−62D 13 5 0 15 CR33−50/60, −60D 21 4 0 0 CX34−49 16 3 0 12 CX34−60D 13 5 0 15 CX34−62C, −62D 13 5 0 15
Table 7. XP17−042
(+
Table 8. XP17−048
(+
Table 9. XP17−060
(+
Target
Subcooling
Heat Cool
5ºF)(+1ºF)
Target
Subcooling
Heat Cool
5ºF)(+1ºF)
Target
Subcooling
Heat Cool
5ºF)(+1ºF)
*Add
charge
lb oz
*Add
charge
lb oz
*Add
charge
lb oz
506586−01 10/10
Page 30
Operating and Temperature Pressures
Minor variations in these pressures may be expected due to differences in installations. Significant differences could mean that the system is not properly charged or that a problem exists with some component in the system. The normal operating pressures listed here are also located on the unit charging sticker located on the unit access panel.
Table 10. Normal Operating Pressure − Liquid +10 and Vapor +5 PSIG*
Use this table to perform maintenance checks; it is not a procedure for charging the
IMPORTANT
Model XP17−024 XP17−030 XP17−036 XP17−042 XP17−048 XP17−060
5F (5C)** Liquid Vapor Liquid Vapor Liquid Vapor Liquid Vapor Liquid Vapor Liquid Vapor
20 (−6.6) 291 65 303 63 280 60 288 59 324 63 330 58
30 (−1.1) 309 79 328 77 290 74 306 68 345 76 354 72
40 (4.4) 319 94 338 92 310 88 320 85 366 91 368 83
50 (10.0) 340 11 0 366 11 0 326 105 339 107 398 109 391 107
60 (15.5) 361 129 387 128 344 124 361 125 428 127 413 126
65 (18.3) 233 143 234 137 227 137 234 138 240 136 238 133
70 21.1) 250 144 251 139 243 139 250 139 256 138 256 135
75 (23.9) 269 145 270 141 262 140 269 141 275 139 278 136
80 (26.7) 289 147 291 142 284 141 292 143 297 140 299 137
85 (29.4) 310 148 312 143 306 142 315 144 319 141 322 138
90 (32.2) 332 149 335 145 329 143 337 146 342 142 344 139
95 (35.0) 356 150 358 146 354 144 362 147 366 144 369 140
100 (37.8) 379 151 383 147 377 144 386 148 392 144 395 141
105 (40.6) 405 152 408 148 406 147 415 147 418 146 422 142
110 (43.3) 431 153 433 149 434 148 442 148 446 148 450 143
115 (46.1) 456 155 462 150 463 150 472 150 475 150 481 145
*These are most−popular−match−up pressures. Indoor match up, indoor air quality, and indoor load cause pressures to vary. **Temperature of the air entering the outdoor coil.
system. Minor variations in these pressures may be due to differences in installations. Significant deviations could mean that the system is not properly charged or that a problem exists with some component in the system.
Heating Operation
Cooling Operation
Table 11. HFC−410A Temperature (°F) − Pressure (Psig)
°F Psig °F Psig °F Psig °F Psig °F Psig °F Psig °F Psig °F Psig
32 100.8 48 137.1 63 178.5 79 231.6 94 290.8 110 365.0
33 102.9 49 139.6 64 181.6 80 235.3 95 295.1 111 370.0 126 451.8 142 552.3
34 105.0 50 142.2 65 184.3 81 239.0 96 299.4 112 375.1 127 457.6 143 559.1
35 107.1 51 144.8 66 187.7 82 242.7 97 303.8 113 380.2 128 463.5 144 565.9
36 109.2 52 147.4 67 190.9 83 246.5 98 308.2 114 385.4 129 469.5 145 572.8
37 111.4 53 150.1 68 194.1 84 250.3 99 312.7 115 390.7 130 475.6 146 579.8
38 113.6 54 152.8 69 197.3 85 254.1 100 317.2 11 6 396.0 131 481.6 147 586.8
39 115.8 55 155.5 70 200.6 86 258.0 101 321.8 11 7 401.3 132 487.8 148 593.8
40 118.0 56 158.2 71 203.9 87 262.0 102 326.4 11 8 406.7 133 494.0 149 601.0
41 120.3 57 161.0 72 207.2 88 266.0 103 331.0 11 9 412.2 134 500.2 150 608.1
42 122.6 58 163.9 73 210.6 89 270.0 104 335.7 120 417.7 135 506.5 151 615.4
43 125.0 59 166.7 74 214.0 90 274.1 105 340.5 121 423.2 136 512.9 152 622.7
44 127.3 60 169.6 75 217.4 91 278.2 106 345.3 122 428.8 137 519.3 153 630.1
45 129.7 61 172.6 76 220.9 92 282.3 107 350.1 123 434.5 138 525.8 154 637.5
46 132.2 62 175.4 77 224.4 93 286.5 108 355.0 124 440.2 139 532.4 155 645.0
47 134.6 78 228.0 109 360.0 140 539.0
125 445.9
141 545.6
Page 31
XP17 SERIES
System Operations
IMPORTANT
Some scroll compressor have internal vacuum protector that will unload scrolls when suction pressure goes below 20 psig. A hissing sound will be heard when the compressor is running unloaded. Protector will reset when low pressure in system is raised above 40 psig. DO NOT REPLACE COMPRESSOR.
The heat pump control (A175) provides the following functions:
S Demand defrost algorithm
S Field−selectable defrost termination temperatures
S Internal switching of outputs S Compressor anti−short−cycle delay. S Five strikes lockout safety function S High (S4) and low (S87) pressure switches
S Ambient (RT13), and coil temperatures (RT21)
temperature monitoring and protection.
COMPRESSOR ANTI−SHORT CYCLE DELAY
The heat pump control protects the compressor from:
S Short cycling (five minutes) when there is initial power
up
S Interruption in power to the unit S Pressure or sensor trips S Delay after Y1 demand is removed.
In non−communicating systems the delay is set for 300 seconds (five minutes) and can not be changed. To override timer when active or inactive, place a jumper on the field test pins between 1 and 2 seconds.
In communicating system, the icomfort Touch® thermostat has a separate built−in 5−minute non−adjustable short cycle protection.
Resetting Anti−Short Cycle Delay
The FIELD TEST pins (E33) on the heat pump control can be jumpered between 1 to 2 seconds to bypass delay.
HIGH (S4) AND LOW (S87) PRESSURE SWITCHES
The unit’s pressure switches (LO PS − S87 and HI PS − S4) are factory−wired into the heat pump control on the LO−PS and HI−PS terminals, respectively.
Low Pressure Switch (LO−PS)  See figure 28 for low pressure switch sequence of operation.
High Pressure Switch (HI−PS)  See figure 29 for high pressure switch sequence of operation.
Pressure Switch Event Settings
The following pressures are the auto reset event value triggers for low and high pressure thresholds:
S High Pressure (auto reset) − trip at 590 psig; reset at
418.
S Low Pressure (auto reset) − trip at 25 psig; reset at 40.
COMPRESSOR PROTECTION  FIVE−STRIKE LOCKOUT SAFETY FUNCTION
The five−strike lockout safety function is designed to protect the unit’s compressor from damage. The five−strike feature is used for high pressure (S4) and low (S87) pressure switch trips and W input fault or miswire.
Resetting Five−Strike Lockout
Once the condition has been rectified, power to the heat pump control’s R terminal must be cycled OFF, or a jumper placed on the FIELD TEST pins between 1− to 2−seconds to reset the heat pump control.
Defrost System
The heat pump control (A175) measures differential temperatures to detect when the system is performing poorly because of ice build−up on the outdoor coil. The controller self−calibrates (see figure 26) when the defrost system starts and after each system defrost cycle. The heat pump control monitors ambient temperature, outdoor coil temperature, and total run−time to determine when a defrost cycle is required. The coil temperature sensor is designed with a spring clip to allow mounting to the outside coil tubing. The location of the coil sensor is important for proper defrost operation (see figure 1 for location of coil sensor).
NOTE − The heat pump control accurately measures the performance of the system as frost accumulates on the outdoor coil. This typically will translate into longer running time between defrost cycles as more frost accumulates on the outdoor coil before the heat pump control initiates defrost cycles.
DEFROST OPERATING MODES
The heat pump control board has three operational modes which are:
S Defrost calibration and operation (see figure 26) S Defrost test (see figure 27)
DEFROST TERMINATION TEMPERATURES (E47)
The heat pump control selections are: 50, 70, 90, and 100°F (10, 21, 32 and 38°C). The jumper termination pin is factory set at 50°F (10°C).
If the temperature jumper is not installed, the default termination temperature is 90°F (32°C). See figure 26 for on how this settings affects defrost calibration and defrost modes.
NOTE − Colder climates could require a high discharge termination temperature setting to maintain a clear coil.
50
50
IF JUMPER IS NOT INSTALLED (90ºF)
FACTORY DEFAULT (50ºF)
100
DEGREE TARGET
70 DEGREE TARGET
100
100
90
70
90
70
90 DEGREE TARGET
50
DEGREE
TARGET
50
100
90
70
50
100
90
70
Figure 23. Defrost Termination Temperature
Settings
506586−01 10/10
Page 32
UNIT SENSORS
Sensors connect to the heat pump control through a field-replaceable harness assembly that plugs into the control. Through the sensors, the heat pump control detects outdoor ambient and coil temperature fault conditions. As the detected temperature changes, the resistance across the sensor changes. table 13 shows how the resistance varies as the temperature changes for both type of sensors. Sensor resistance values can be checked by ohming across pins shown in table 12.
NOTE  When checking the ohms across a sensor, be aware that a sensor showing a resistance value that is not within the range shown in table 12, may be performing as designed. However, if a shorted or open circuit is detected, then the sensor may be faulty and the sensor harness will need to be replaced.
Ambient Temperature Sensor (RT13)
See table 12 for sensor range. If the ambient sensor is detected as being open, shorted or out of the temperature range of the sensor, the heat pump control will not perform demand defrost operation. The heat pump control will revert to time/temperature defrost operation and will display the appropriate alert code. Heating and cooling operation will be allowed in this fault condition.
Coil Temperature Sensor (RT21)
See table 12 for sensor range. If the defrost coil sensor is open, shorted or out of the temperature range of the sensor, the heat pump control will not perform demand or time/temperature defrost operation and will display the appropriate fault code. Heating and cooling operation will be allowed in this fault condition.
High Discharge Line Temperature Sensor
This model does not use a high discharge line temperature sensor. The cable assembly attached to the heat pump control’s E30 connection has a 10K resister installed between pins 1 and 2 as illustrated in figure 24. No alerts or alarms would be generated if resistor is damage.
COIL TEMPERATURE
SENSOR
AMBIENT AIR
TEMPERATURE SENSOR
10K RESISTOR
Figure 24. 10k Resistor Location
Table 12. Sensor Temperature / Resistance Range
Sensor
Outdoor (Ambient)
Coil
NOTE  Sensor resistance decreases as sensed temperature increases (see table 13).
Temperature Range °F (°C)
−40 (−40) to 140 (60)
Resistance values range (ohms)
280,000 to 3750
Pins/Wire Color
3 and 4 (Black)
5 and 6 (Brown)
W Input Fault or Miswire
In case of a W input fault or possible miswire, the system will function as listed in the sequence of operation in figure
30.
Shift Delay (E37)
The heat pump control has a field−selectable function to reduce occasional sounds that may occur while the unit is cycling in and out of the defrost mode. When a jumper is installed on the DELAY pins (E37), the compressor will be cycled off for 30 seconds going in and out of the defrost mode. Units are shipped with jumper installed on DELAY pins.
*30
SECOND DELAY
0
SECOND DELAY
30
0
FACTORY DEFAULT OR WHEN JUMPER IS MISSING
Figure 25. Shift Delay Settings
Page 33
XP17 SERIES
Heat pump control monitors mode of operation through outdoor ambient temperature (RT13), outdoor coil temperature (RT21) and compressor run−time to determine when a defrost cycle is required.
NOTE  No system alert codes can be active for defrost calibration to be achieved.
100
DEGREE
TARGET
90
DEGREE
TARGET
70
DEGREE
TARGET
*50
DEGREE
TARGET
100
100
100
100
90
90
90
E47
*Heat Pump Control (A175)
70
50
Defrost Termination (E47) Pins (Factory Default is 50ºF)
70
50
90
70
50
70
50
Defrost Calibration
Coil sensor (RT21) detects temperature below 35°F {2°C} during either initial power−up, after loss of power or after cooling mode, a sacrificial defrost will be used to ensure there is a clear coil before attempting calibration.
Coil sensor
below 35°F {2°C}
NO
YES
Accumulate compressor run−time while outdoor coil temperature sensor input (RT21) is below 35°F (2°C)
30−35 minutes
compressor
NO
run−time
YES
No attempt to calibrate.
Continue to accumulate run time.
Demand Mode
After the initial calibration, the heat pump control disables the defrost mode for 30−34 minutes in order to avoid unnecessary defrosts. Beyond this timing period, both the ambient (RT13) and coil (RT21) sensors are continuously moni­tored. If the coil temperature is below 35°F (2°C) and the calibration delta is reached or accumu­lated compressor run−time is more than six (6) hours, a defrost is to be initiated.
Initiate a defrost and monitor coil temperature sensor input (RT21) and accumulate defrost time.
Coil temperature sensor input (RT21) reached specified de­frost termination temperature as set on heat pump control E47 pins*.
Calibration Attempted
(Unit Running in Heat Mode)
Defrost Mode
How did defrost
terminate?
Defrosted for 14 minutes with­out the coil temperature sensor input (RT21) reaching defrost termination temperature as set on heat pump control E47 pins*.
506586−01 10/10
YES
Calibration
NO
Figure 26. Defrost Calibration Sequence of Operations
Page 34
MULTI−FUNCTION TEST PINS (E33)
Placing the jumper on the field test pins (E33) using a specific sequence allows the technician to:
S Clear short cycle lockout S Clear five−strike fault lockout S Cycle the unit in and out of defrost mode S Manually place the unit in defrost mode to clear the coil
When Y1 is energized and 24V power is being applied to the heat pump control (A175), a test cycle can be initiated by placing a jumper on the heat pump control’s TEST pins for 2 to 5 seconds. If the jumper remains on the TEST pins (E33) for longer than five seconds, the heat pump control will ignore the jumpered TEST pins and revert to normal operation.
The heat pump control will initiate one test event each time a jumper is placed on the TEST pins. For each TEST the jumper must be removed for at least one second and then reapplied.
Y1 Active
Place a jumper on TEST pins for
longer than one second but less than two seconds.
Clears any short cycle lockout and five strike fault lockout function, if applicable. No other functions will be executed and unit will continue in the mode it was operating.
If in COOLING Mode
No further test mode operation will be executed until the jumper is removed from the TEST pins and reapplied.
Place a jumper on TEST pins for
more than two seconds.
Clears any short cycle lockout and five strike fault lockout function, if applicable.
ACTIVE
O Line Status
If in DEFROST Mode
The unit will terminate defrost and enter HEAT MODE uncalibrated with defrost timer set for a maximum 34 minute test.
INACTIVE
If in HEATING Mode
If no ambient or coil sensor fault ex­ist, unit will go into DEFROST MODE. If ambient or coil faults exist (open or shorted), unit will remain in HEAT MODE.
NOTE  Heat pump control cannot be force into defrost mode when the ambient temperature input from the RT13 sensor is above 65ºF (18ºC).
NOTE  If ambient or coil fault is detected, the board will not execute the TEST mode.
Figure 27. Test Pin (E33) Functions
If jumper on TEST pins remains in place for more than five seconds.
The unit will return to HEAT MODE uncalibrated with defrost timer set for 34 minutes.
Page 35
If jumper on TEST pins is removed before a maximum of five seconds.
The unit will remain in DEFROST MODE until termination on time or
temperature.
XP17 SERIES
Y1 DEMAND
LOW
PRESSURE
SWITCH (S87)
CLOSED
COMPRESSOR
CONTACTOR
ENERGIZED
INITIAL TRIP
SWITCH IS
IGNORED FOR
90 SECONDS
OPEN
OPEN
COMPRESSOR
CONTACTOR
DE−ENERGIZED
COMPRESSOR
ANTI−SHORT
CYCLE TIMER
BEGINS
INCREMENT
5−STRIKE
COUNTER
1
LED ALERT CODE / OR
MODERATE
ALERT 410
DISPLAYED
LOW
PRESSURE
SWITCH (S87)
1
If 5−strike counter has four or less strikes when Y1 demand is
CLOSED
SWITCH IS CLOSED OR OUTDOOR
AMBIENT TEMPERATURE IS 15ºF
terminated or satisfied, the strike counter will reset to zero. In a icomfort Touch® thermostat enabled setup, the thermostat will terminate demand
when the compressor contactor is de−energized. If demand is satisfied when alarm is not active, the 5−strike counter will reset.
2
Lockouts can be reset by either cycling power off to the heat pump con-
trol’s (A175) R terminal, or placing a jumper on the field test pins (E33) between 1 to 2 seconds.
5−STRIKE
COUNTER
REACHES 5
WITHIN A SINGLE
Y1 DEMAND
LOW
PRESSURE
SWITCH (S87)
LOCKOUT
OR BELOW
SERVICE
REQUIRED
506586−01 10/10
2
OPEN
ANTI−SHORT
CYCLE TIMER
ENDS
COMPRESSOR
CONTACTOR
ENERGIZED
LOW
PRESSURE
SWITCH (S87)
WAITING FOR
PRESSURE SWITCH TO
CLOSE
LED ALERT
CODE / OR
CRITICAL
ALERT 411
SERVICE
REQUIRED
DISPLAYED
LED ALERT
CODE / OR
CLOSED
MODERATE
ALERT 410
DISPLAYED
CLOSED
Figure 28. Low Pressure (S87) Switch Operation
Page 36
2
NORMAL
OPERATION
Y1 DEMAND
OPEN
HIGH
PRESSURE
SWITCH (S4)
OPEN
COMPRESSOR
CONTACTOR
DE−ENERGIZED
COMPRESSOR
ANTI−SHORT
CYCLE TIMER
BEGINS
INCREMENT
5−STRIKE
COUNTER
1
CLOSED
COMPRESSOR
CONTACTOR
ENERGIZED
HIGH
PRESSURE
SWITCH (S4)
1
If 5−strike counter has four or less strikes when Y1 demand is terminated
CLOSED
or satisfied, the strike counter will reset to zero. In a icomfort Touch thermostat enabled setup, the thermostat will terminate demand when the compressor contactor is de−energized. If demand is satisfied when alarm is not active, the 5−strike counter will reset.
2
Lockouts can be reset by either cycling power off to the heat pump con-
trol’s (A175) R terminal, or placing a jumper on the field test pins (E33) be­tween 1 to 2 seconds.
5−STRIKE
COUNTER
REACHES 5
WITHIN A SINGLE
Y1 DEMAND
®
SERVICE
REQUIRED
2
OPEN
LED ALERT
CODE / OR
MODERATE
ALERT 412
DISPLAYED
ANTI−SHORT
CYCLE TIMER
ENDS
COMPRESSOR
CONTACTOR
ENERGIZED
HIGH
PRESSURE
SWITCH (S4)
WAITING FOR
PRESSURE
SWITCH TO
CLOSE
CLOSED
CLOSED
HIGH
PRESSURE
SWITCH (S4)
LOCKOUT
LED ALERT CODE / OR
CRITICAL
ALERT 413
CLEARED
LED ALERT
CODE / OR
MODERATE
ALERT 412
DISPLAYED
SERVICE
REQUIRED
2
NORMAL
OPERATION
Figure 29. High Pressure Switch (S4) Sequence of Operation
Page 37
XP17 SERIES
Y1 DEMAND
COMPRESSOR
CONTACTOR
ENERGIZED
YES
COMPRESSOR
CONTACTOR
DE−ENERGIZED
W OUTPUT
ACTIVE)
NO
INITIAL TRIP
SWITCH IS
IGNORED FOR
90 SECONDS
NORMAL
OPERATION
W OUTPUT
ACTIVE)
NO
COMPRESSOR
ANTI−SHORT
CYCLE TIMER
BEGINS
INCREMENT
5−STRIKE
COUNTER
1
LED ALERT
CODE / OR
MODERATE
ALERT 418
DISPLAYED
YES
COMPRESSOR
ANTI−SHORT
CYCLE TIMER
BEGINS
5−STRIKE
COUNTER
REACHES 5
WITHIN A SINGLE
Y1 DEMAND
W OUTPUT
HARDWARE
FAULT
LOCKOUT
LED ALERT CODE / OR
MODERATE
ALERT 418
DISPLAYED
ANTI−SHORT
CYCLE TIMER
ENDS
W OUTPUT
ACTIVE)
YES
WAITING FOR
W OUTPUT TO
DEACTIVATE
NO
LED ALERT CODE / OR
MODERATE
ALERT 418
CLEARED
506586−01 10/10
ANTI−SHORT
CYCLE TIMER
ENDS
LED ALERT
CODE / OR
MODERATE
ALERT 418
CLEARED
LED ALERT CODE / OR
CRITICAL
ALERT 419
SERVICE
REQUIRED
2
DISPLAYED
1
If 5−strike counter has four or less strikes when Y1 demand is terminated or satisfied, the strike counter will
reset to zero. In a icomfort Touch® thermostat enabled setup, the thermostat will terminate demand when the compressor contactor is de−energized. If demand is satisfied when alarm is not active, the 5−strike counter will reset.
2
Lockouts can be reset by either cycling power off to the heat pump control’s (A175) R terminal, or placing
a jumper on the field test pins (E33) between 1 to 2 seconds.
Figure 30. W Input Fault or Miswire
Page 38
Table 13. Ambient (RT13) and Coil (RT21) Sensors Temperature / Resistance Range
Degrees
Fahrenheit
136.3 2680 56.8 16657 21.6 44154 −11.3 123152
133.1 2859 56.0 16973 21.0 44851 −11.9 125787
130.1 3040 55.3 17293 20.5 45560 −12.6 128508
127.3 3223 54.6 17616 20.0 46281 −13.2 131320
124.7 3407 53.9 17942 19.4 47014 −13.9 134227
122.1 3592 53.2 18273 18.9 47759 −14.5 137234
119.7 3779 52.5 18607 18.4 48517 −15.2 140347
117.5 3968 51.9 18945 17.8 49289 −15.9 143571
115.3 4159 51.2 19287 17.3 50074 −16.5 146913
113.2 4351 50.5 19633 16.8 50873 −17.2 150378
111.2 4544 49.9 19982 16.3 51686 −17.9 153974
109.3 4740 49.2 20336 15.7 52514 −18.6 157708
107.4 4937 48.5 20695 15.2 53356 −19.3 161588
105.6 5136 47.9 21057 14.7 54215 −20.1 165624
103.9 5336 47.3 21424 14.1 55089 −20.8 169824
102.3 5539 46.6 21795 13.6 55979 −21.5 174200
100.6 5743 46.0 22171 13.1 56887 −22.3 178762
99.1 5949 45.4 22551 12.5 57811 −23.0 183522
97.6 6157 44.7 22936 12.0 58754 −23.8 188493
96.1 6367 44.1 23326 11.5 59715 −24.6 193691
94.7 6578 43.5 23720 11.0 60694 −25.4 199130
93.3 6792 42.9 24120 10.4 61693 −26.2 204829
92.0 7007 42.3 24525 9.9 62712 −27.0 210805
90.6 7225 41.7 24934 9.3 63752 −27.8 217080
89.4 7444 41.1 25349 8.8 64812 −28.7 223677
88.1 7666 40.5 25769 8.3 65895 −29.5 230621
86.9 7890 39.9 26195 7.7 67000 −30.4 237941
85.7 8115 39.3 26626 7.2 68128 −31.3 245667
84.5 8343 38.7 27063 6.7 69281 −32.2 253834
83.4 8573 38.1 27505 6.1 70458 −33.2 262482
82.3 8806 37.5 27954 5.6 71661 −34.1 271655
81.2 9040 37.0 28408 5.0 72890 −35.1 281400
80.1 9277 36.4 28868 4.5 74147 −36.1 291774
79.0 9516 35.8 29335 3.9 75431 −37.1 302840
78.0 9757 35.2 29808 3.4 76745 −38.2 314669
77.0 10001 34.7 30288 2.8 78090 −39.2 327343
76.0 10247 34.1 30774 2.3 79465
75.0 10496 33.5 31267 1.7 80873
74.1 10747 33.0 31766 1.2 82314
73.1 11000 32.4 32273 0.6 83790
72.2 11256 31.9 32787 0.0 85302
71.3 11515 31.3 33309 −0.5 86852
70.4 11776 30.7 33837 −1.1 88440
69.5 12040 30.2 34374 −1.7 90068
68.6 12306 29.6 34918 −2.2 91738
67.7 12575 29.1 35471 −2.8 93452
66.9 12847 28.6 36031 −3.4 95211
66.0 13122 28.0 36600 −4.0 97016
65.2 13400 27.5 37177 −4.6 98870
64.4 13681 26.9 37764 −5.2 100775
63.6 13964 26.4 38359 −5.7 102733
62.8 14251 25.8 38963 −6.3 104746
62.0 14540 25.3 39577 −6.9 106817
61.2 14833 24.8 40200 −7.5 108948
60.5 15129 24.2 40833 −8.2 111141
59.7 15428 23.7 41476 −8.8 113400
59.0 15730 23.2 42130 −9.4 115727
58.2 16036 22.6 42794 −10.0 118126
57.5 16345 22.1 43468 −10.6 120600
Resistance
Degrees
Fahrenheit
Resistance
Degrees
Fahrenheit
Resistance
Degrees
Fahrenheit
Resistance
Page 39
XP17 SERIES
System Status, Fault and Lockout LED Codes
LED codes are displayed using various LEDs located on the heat pump control (A175). See figure 16 for locations of heat pump control LEDs.
DS11 AND DS14  SYSTEM STATUS, FAULT AND LOCKOUT LED CODES
DS11 (Green) and DS14 (Red) LEDs indicate non−communicating mode diagnostics conditions that are listed in table 14.
These LEDs display the most common fault conditions in the system. When an abnormal condition is detected, this function communicates the specific condition through system LED alert codes The function is capable of detecting both mechanical and electrical system problems.
DS15 AND DS13  COMPRESSOR FAULT AND LOCKOUT LED CODES
DS15 (Yellow) and DS13 (Red) LEDs indicate non−communicating mode diagnostics conditions that are listed in table 15.
These LEDs display the most common fault conditions in the system. When an abnormal condition is detected, this function communicates the specific condition through system LED alert codes The function is capable of detecting both mechanical and electrical system problems.
IMPORTANT
DS15 and DS13 compressor LED fault and lockout codes do not provide safety protection. The is a monitoring function only and cannot control or shut down other devices.
RESETTING FAULT AND LOCKOUT LED CODES
All LED fault and lockout codes can be reset manually or automatically:
1. Manual Reset
Manual reset can be achieve by one of the following methods:
S Disconnecting R wire from the heat pump control’s
R terminal.
S Turning the indoor unit off an on again
After power up, existing code will display for 60 seconds and then clear.
2. Automatic Reset
After a fault or lockout is detected, the heat pump control continues to monitor the unit’s system and compressor operations. When/if conditions return to normal, the alert code is turned off automatically.
Table 14. System Status, Fault and Lockout LED Codes and Related icomfort Touch® Thermostat Alert Codes
System fault and lockout LED (DS11 / DS14) alarm codes takes precedence over system status LED codes (cooling, heating stages or defrost/dehumidification). Only the latest active LED fault or lockout alarm code if present will be displayed. If no fault or lockout codes are active, then system status LEDs are routinely displayed. See notes 1 and 2 in table below for duration of fast / slow flashes and pause.
Heat Pump Control
LEDs
DS11
Green
Off Off
Simultaneous slow flash
Alternating slow flash
Simultaneous fast
Alternating fast flash
DS14 Red
flashes
icomfort
®
Touch
Thermostat
Display
Not
applicable
Not
applicable
Not
applicable
Moderate /
Critical Alert
Code 180
Moderate /
Critical Alert
Code 417
Condition Possible Cause(s) Solution
SYSTEM STATUS
1. No power (24V) to heat pump control terminal’s
Power problem
Normal operation Unit operating normally or in standby mode.
5−minute
anti−short cycle
delay
Ambient sensor
problem
Coil sensor
problem
R and C or heat pump control failure.
2. Heat pump control failure.
Initial power up, safety trip, end of room thermostat de­mand.
If sensor detects an open, shorted or out−of−temperature range. heat pump control will revert to time/temperature defrost operation. System will still heat or cool.
If the outdoor coil temperature sensor is detected as being open or shorted, the heat pump control will not perform defrost operations.
1
Check control transformer power (24V).
2
If power is available to control and LED(s) do not light, replace the heat pump control.
None required (Jumper FIELD TEST (E33) pins to override)
On On
506586−01 10/10
Not
applicable
Heat pump
control failure
Indicates that heat pump control has an internal component failure. Cycle 24 volt power to heat pump control. If code does not clear, replace the heat pump control.
Page 40
System fault and lockout LED (DS11 / DS14) alarm codes takes precedence over system status LED codes (cooling, heating stages or defrost/dehumidification). Only the latest active LED fault or lockout alarm code if present will be displayed. If no fault or lockout codes are active, then system status LEDs are routinely displayed. See notes 1 and 2 in table below for duration of fast / slow flashes and pause.
icomfort
icomfort
Heat Pump Control
LEDs
DS11
DS11
Green
Green
Off
DS14 Red
DS14 Red
1 fast flash then pause
icomfort
®
®
®
Touch
Touch
Touch
Thermostat
Thermostat
Thermostat
Display
Display
Display
Not
applicable
Single stage compressor
heating
SolutionPossible Cause(s)Condition
SolutionPossible Cause(s)Condition
SolutionPossible Cause(s)Condition
On
1 fast flash
then pause
2 fast
flashes
then pause
then pause
None
None
None
None
2 fast
flashes
Off
On
Not
applicable
Not
applicable
Not
applicable
Moderate
Alert Code
105
Moderate
Alert Code
120
Critical Alert
Code 124
Critical Alert
Code 125
Defrost
Single−stage compressor
cooling
Dehumidification
mode
Device
communication
failure
Unresponsive
device
Active subnet
controller missing
Hardware Failure
These are codes that show status of operation whether the system is operating in either in first or second stage heating or cooling operation, defrost or in the dehumidification modes.
ALERT STATUS
icomfort Touch® thermostat is unable to communicate with any other device on the RSBus. Alarm only occurs if a specific device did communicate initially after power up and communication was later lost. Possible causes are lost connection, bus short or open, or other device stop responding.
Message could be sent by any device on RSBus if expected response message is not received from other device. If sent by indoor or heat pump control, device did not get expected response (incorrect or no response at all) from active Subnet controller. If sent by the icomfort Touch® thermostat, and did not get the expected response (incorrect or no response at all) from device. Normally this indicate device malfunction.
Device lost connection to icomfort Touch® thermostat. Thermostat is sending heartbeat message in one minute intervals. Device sets this alarm if no Heartbeat is received for three minutes. Normally this indicate lost connection to thermostat, or thermostat is not working. Alert will clear after valid subnet controller message is received.
Entire or partial system failure. Alert will clear 300 seconds after fault has recovered.
None
None
None
Off
Slow flash
Off On
Slow flash Off
On Off
Moderate /
Critical Alert
Code 126
Critical Alert
Code 131
Critical Alert
Code 132
Moderate
Alert Code
410
Critical Alert
Code 411
Moderate
Alert Code
412
Critical Alert
Code 413
Internal control communication
failure
Corrupted control
parameters
Failed flash CRC
check.
Low pressure
fault
Low pressure
switch lockout
High pressure
fault
High pressure switch lockout
Internal communication on heat pump control. Alert will clear 300 seconds after fault has recovered.
System stored configuration data is corrupted. System will not run.
No operations, heat pump control enters boot loader mode. Alarm will clears after reset. Refer to communicating thermostat for memory corrupt handling.
1
1
Restricted air flow over in­door or outdoor coil.
2
Improper refrigerant charge in system.
3
Improper metering device installed or incorrect op­eration of metering device.
4
Incorrect or improper sen­sor location or connection to system.
Remove any blockages or restrictions from coils and/or fans. Check indoor and outdoor fan motor for proper current draws.
2
Check system charge using approach and sub­cooling temperatures.
3
Check system operating pressures and compare to unit charging charts.
4
Make sure all pressure switches and sensors have secure connections to system to prevent refriger­ant leaks or errors in pressure and temperature measurements.
Page 41
XP17 SERIES
System fault and lockout LED (DS11 / DS14) alarm codes takes precedence over system status LED codes (cooling, heating stages or defrost/dehumidification). Only the latest active LED fault or lockout alarm code if present will be displayed. If no fault or lockout codes are active, then system status LEDs are routinely displayed. See notes 1 and 2 in table below for duration of fast / slow flashes and pause.
icomfort
icomfort
Heat Pump Control
LEDs
DS11
DS11
Green
Green
DS14 Red
DS14 Red
Slow flash On
Fast flash On
icomfort
®
®
®
Touch
Touch
Touch
Thermostat
Thermostat
Thermostat
Display
Display
Display
Moderate
Alert Code
414
Critical Alert
Code 415
Discharge line
temperature fault
Discharge line
temperature
lockout
SolutionPossible Cause(s)Condition
SolutionPossible Cause(s)Condition
SolutionPossible Cause(s)Condition
This code indicates high discharge temperatures. If the discharge line temperature exceeds a temperature of 279ºF (137ºC) during compressor operation, the control will de−energize the compressor contactor output (and the defrost output if active). The compressor will remain off until the discharge temperature has dropped below 225ºF (107ºC).
Off Fast flash
Moderate /
Critical Alert
Code 417
Discharge sensor
fault
The heat pump control (A175) detects open or short sensor or out of temperature sensor range. This fault is detected by allowing the unit to run for 90 seconds before checking sensor resistance. If the sensor resistance is not within range after 90 seconds, the control will raise the alarm.
3 fast
flashes
Off
then pause
3 fast
flashes
On
then pause
3 fast
Off
flashes
then pause
Simultaneous fast
flashes then pause
Fast simultaneous flashing of DS11,
Moderate /
Critical Alert
Code 418
Moderate /
Critical Alert
Code 419
Critical Alert
Code 421
None
W output
hardware fault
W output
hardware fault
lockout
W external
miswire fault
Second−stage
heat lock−in
When auxiliary heat output is detected as active. Fault in the heat pump control. Replace heat pump control. See figure 30 for further details.
If heat pump control recognizes five output hardware fault events during a single cooling demand, the heat pump control will initiate a lockout. See figure 30 for fur­ther details.
When auxiliary heat output is detected as active after compressor has been de−en­ergized. See figure 30 for further details.
If the unit is in non−communicating mode and it goes to second stage due to ambi­ent temperature being below second stage lock−in setting (E48).
OEM mode Factory test mode.
DS13, DS14 and DS15
1. Pause duration is two (2) seconds.
2. Fast flash duration is 1/2 second. Slow flash duration is one (1) second.
506586−01 10/10
Page 42
Table 15. Compressor Fault and Lockout LED Codes and Related icomfort Touch® Thermostat Alert Codes
NOTE  See notes 1 and 2 in table below for duration of fast / slow flashes and pause.
Heat Pump Control
LEDs
DS15 Yellow
DS13
Red
Off On
1 flash then pause
2 flashes then pause
Off
Off
icomfort
®
Touch
Thermostat
Display
Moderate/
Critical3 Alert
Code 400
Critical Alert
Code 401
Critical Alert
Code 402
Condition
Compressor
internal
overload trip
Long run time.
System
pressure trip
Possible Cause(s)
Thermostat demand signal Y1 is present, but compressor not running
Compressor is running extremely long run cycles.
Indicates the compressor protector is open or missing supply power to the compressor.
Solution
1
Compressor protector is open.
S Check for high head pressure S Check compressor supply voltage
2
Outdoor unit power disconnect is open.
3
Compressor circuit breaker or fuse(s) is open.
4
Broken wire or connector is not making contact.
5
Low or high pressure switch open if present in the system.
6
Compressor contactor has failed to close.
1
Low refrigerant charge.
2
Evaporator blower is not running.
S Check blower relay coil and contacts S Check blower motor capacitor S Check blower motor for failure or blockage S Check evaporator blower wiring and connec-
tors
S Check indoor blower control S Check thermostat wiring for open circuit
3
Evaporator coil is frozen.
S Check for low suction pressure S Check for excessively low thermostat setting S Check evaporator airflow (coil blockages or re-
turn air filter)
S Check ductwork or registers for blockage.
4
Faulty metering device.
S Check TXV bulb installation (size, location and
contact)
S Check if TXV/fixed orifice is stuck closed or de-
fective
5
Condenser coil is dirty
6
Liquid line restriction (filter drier blocked if present)
7
Thermostat is malfunctioning
.
.
S Check thermostat sub−base or wiring for short
circuit
S Check thermostat installation (location and lev-
el)
1
High head pressure.
S Check high pressure switch if present in sys-
tem
S Check if system is overcharged with refrigerant S Check for non−condensable in system
2
Condenser coil poor air circulation (dirty, blocked, damaged).
3
Condenser fan is not running.
S Check fan capacitor S Check fan wiring and connectors S Check fan motor for failure or blockage
4
Return air duct has substantial leakage.
Clearing Status
Clears the error after current is sensed in the run and start winding for two seconds, ser­vice removed or power reset.
Clears the error after 30 consec­utive normal run cycles, or after power reset.
.
Clears after four consecutive normal com­pressor run cycles, or after power reset.
3 flashes then pause
Off
Moderate
Alert Code
403
Short cycling
Compressor is running less than three minutes.
Page 43
1
Thermostat demand signal is intermittent.
2
Time delay relay or heat pump control is defective.
3
If high pressure switch is present, see flash code 2 information.
Clears after four consecutive normal com­pressor run cycles, or after power reset.
XP17 SERIES
Heat Pump Control
LEDs
DS15 Yellow
4 flashes then pause
5 flashes then pause
6 flashes then pause
7 flashes then pause
DS13
Red
Off
Off
Off
Off
icomfort
icomfort
®
®
Touch
Touch
Thermostat
Thermostat
Display
Display
Critical Alert
Code 404
Critical Alert
Code 405
Critical Alert
Code 406
Critical Alert
Code 407
Condition
Condition
Locked rotor
Open circuit
Open start
circuit
Open run
circuit
Possible
Possible Cause(s)
Cause(s)
Compressor has a locked out due to run capacitor short, bearings are seized, excessive liquid refrigerant.
Compressor has an open circuit due to power dis­connection, fuse is open or other similar conditions.
Current not sensed by Start transformer.
Current not sensed by run transformer.
Solution
Solution
1
Run capacitor has failed.
2
Low line voltage (contact utility if voltage at discon­nect is low).
S Check wiring connections
3
Excessive liquid refrigerant in the compressor.
4
Compressor bearings are seized.
1
Outdoor unit power disconnect is open.
2
Unit circuit breaker or fuse(s) is open.
3
Unit contactor has failed to close.
S Check compressor contactor wiring and
connectors
S Check for compressor contactor failure
(burned, pitted or open)
S Check wiring and connectors between supply
and compressor
S Check for low pilot voltage at compressor
contactor coil
4
High pressure switch is open and requires manual reset.
5
Open circuit in compressor supply wiring or connections.
6
Unusually long compressor protector reset time due to extreme ambient temperature.
7
Compressor windings are damaged.
S Check compressor motor winding resistance
1
Run capacitor has failed.
2
Open circuit in compressor start wiring or connections.
S Check wiring and connectors between supply
and the compressor S terminal
3
Compressor start winding is damaged.
S Check compressor motor winding resistance
1
Open circuit in compressor start wiring or connections.
S Check wiring and connectors between supply
and the compressor R terminal
2
Compressor start winding is damaged.
S Check compressor motor winding resistance
Clearing Status
Clearing Status
Clears after power reset or four normal compressor cycles.
Clears after one normal com­pressor run cycle or power reset.
Clears when amperage is de­tected in RUN and START sensors, or after power reset.
Clears when amperage is de­tected in RUN and START sensors, or after power reset.
1
8 flashes then pause
9 flashes then pause
Off
Off
Critical Alert
Code 408
Moderate/
Critical Alert
Code 409
Fast simultaneous flashing of DS11,
Welded
contactor
Secondary low
3
voltage
Compressor always runs
24VAC is below 18VAC.
OEM Mode Factory test mode.
Compressor contactor failed to open.
2
Thermostat demand signal not connected to mod­ule.
1
Control circuit transformer is overloaded.
2
Low line voltage (contact utility if voltage at discon­nect is low).
S Check wiring connections
DS13, DS14 and DS15
1. Pause duration is two (2) seconds.
2. Fast flash duration is 1/2 second. Slow flash duration is one (1) second.
3. Initially a moderate status is displayed and is escalated to critical if alarm exists for more than 10 minutes.
Page 44
506586−01 10/10
Clears after one normal com­pressor run cycle or after power reset.
Clears after volt­age is higher than 20VAC for two seconds, or after power re­set.
Field Configuration and Testing
This section provides procedures for configuring, adjusting and testing various components of this unit.
S Fan Motor (B4) Testi Procedure
S Fan Motor Control (A177) Configuration and Testing
S Top Grille and Fan Motor Mounting Adjustment (Fan
Clearance)
S Heat Pump Control (A175) Unit Nominal Capacity
Code configuration
FAN MOTOR (B4) TEST PROCEDURE
The following procedure can be used to test the fan motor operation. A fully charged 9V battery will be required for this procedure. See figure 31 for complete test procedure.
FAN MOTOR CONTROL (A177) OPERATION, AND TROUBLESHOOTING
This section provides information concerning operation and testing of the fan control.
Fan Motor Control Sequence of Operation
During start up, the following sequence is followed:
1. Display error conditions (see table 17), if present.
2. If no errors are detected, the LED code indicating stage operation (see table 18) will display the applicable code and then a long pause.
3. The fan motor speed / RPM (revolutions per minute) indicator is displayed next (see table 16).
4. There is a short pause.
The above sequence will continue to repeat if a thermostat demand is present. See figure 32 for LED sequence and table 18 for description of flash and pause durations.
This is a test that will verify that the motor does operate.
1. Verify main (240 volt) power if OFF to unit.
2. Remove both wires (brown and black) from the J2 terminal on the fan motor control (A177).
3. Room thermostat should be in OFF position (unit in idle mode − no heating or cooling demands)
4. Turn main power (240 volt) ON to unit.
5. Connect 9 Volt battery to fan motor plugs as noted in picture below.
6. Fan motor should run at a reduced fan speed.
7. If fan motor does not run, then replace fan motor assembly.
FAN MOTOR CONTROL
BLACK LEAD
BROWN LEAD
REMOVE BOTH LEADS
FROM J2 TERMINALS
BLACK LEAD
BROWN LEAD
J2
BLACK LEAD
COM
PARK
FAN PWM OUT
CONNECT B4 FAN
MOTOR BLACK COMMON
WIRE TO 9V BATTERY
NEGATIVE TERMINAL
NEGATIVE TERMINAL
FULLY CHARGED
Figure 31. Fan Motor (B4) Test
9V BATTERY
BROWN LEAD
V
CONNECT B4 FAN MOTOR WIRE TO 9V BATTERY POSITIVE TERMINAL
POSITIVE TERMINAL
Page 45
XP17 SERIES
Table 16. Fan Motor Control RPM, LED Code and DC Voltage Output
Model LED Code*
4 3 2 1 RPM (J2) DC Volt
XP17−024 5 OFF ON ON ON 400 12.7
XP17−030 6 OFF ON ON OFF 450 14.3
XP17−036, −042 8 OFF OFF ON ON 600 19.2
XP17−048, −060 9 OFF OFF OFF ON 675 21.6
* LED Code indicates fan motor control LED flash sequence. For example, LED Code 9 indicates 9 slow flashes and pause.
CFM Profile Pin Select ECM1/Y1
Table 17. Fan Motor Control Error/Fault LED Codes
Unit Status Motor Control LED Possible Cause
Mismatched RPM
CRC Failure Constant ON.
Fast flash with no
pause
Internal feedback, PWM does not match target
Microcontroller CRC failure
Table 18. 19. Fan Motor Control Stage LED Indicator
Codes
Unit Status Unit Status
One Stage Operation
Low Stage  ECM1/Y1 ONLY
Fan Motor Control LED
One slow flash, then short pause.
Table 20. Fan Motor Control Flash and Pause
Durations
Flash or Pause State Duration
Flash Flash Three flashes per second
Slow Flash One flash per second
Short Pause Two seconds of OFF time
Long Pause Five seconds of OFF time
Testing
Use the following subsections to verify and test the fan motor control (A177).
Verifying Jumper Settings (J2)
The unit is shipped from the factory with the default fan motor speed setting (in RPMs) required for each specific model. Use the table 16 verify that jumpers are set correctly for the specific unit.
Verifying LED Status Codes
During start up, the fan motor control (A177) LED will display any error conditions. If error conditions exist then no other codes will display. If no error conditions are present, then the stage status and and RPM indicator are displayed. Fan motor speeds
are not adjustable for a single stage outdoor unit (see table 16).
Verifying Correct DC Output Voltage (J2)
The following three methods can be used to determine whether the fan motor (B4) is operating at the correct RPMs based on unit size.
1. Use the information provided in table 16 to verify that all four jumper terminals are set correctly for the specific size unit.
2. Verify LED RPM indicator is displaying the correct flash sequence for the applicable size unit (see table
18).
3. Test DC voltage output on the fan motor control’s J2 terminals (see figure 34) while under full load and verify the voltage read to the voltage listed in table 16 for the applicable size unit.
4. If no voltage is detected at the J2 terminals, verify there is a Y1 demand at the thermostat and applicable voltages detected all fan motor control (A177) voltage inputs, see table 21.
If there is a demand, proceed to the next section for further testing.
Verifying Correct Input Voltage (ECM/Y1, ECM/Y2,
ECM C and EXT ECM/R)
Using a voltmeter, check voltages on the following fan motor control inputs using table 21. Voltage will only be present during a thermostat demand. See figure 35 for test example.
If correct voltages are detected at applicable inputs during a demand, and no voltage is present at the J2 terminals, then fan motor control should be replaced.
Table 21. Fan Motor Control Voltage Inputs
Input
ECM/Y1 and ECM C
EXT ECM/R and ECM C
Call for Cooling
YES
NO NONE
YES 24VAC
NO NONE
Voltage Present
Between 24VDC and 32 VDC
506586−01 10/10
Page 46
DEMAND
BEGINS
MOTOR SPEED
ECM1/Y1
ONLY OR
ECM2/Y2
ONLY
DEFAULT FAN
MOTOR SPEED
USED
DEFAULT FAN
USED
FAN MOTOR
RPM SET PER
JUMPER
SETTINGS
LED CONTINUOUS FAST
FLASH
LED CONSTANT ON
STAGE LED INDICATOR: ONE SLOW FLASH AND ONE SHORT PAUSE FOR SINGLE STAGE OR EDA OPERATION
REPLACE FAN MOTOR
CONTROL BOARD
REPLACE FAN MOTOR
CONTROL BOARD
YES
MISMATCHED
RPM
CRC FAILURE
SINGLE STAGE
OR EDA
OPERATION
NO
LED RPM INDICATOR:
DEMAND
ENDED
EXAMPLE: (2TON UNIT) – 5 SLOW
FLASHES AND ONE
LONG PAUSE
Figure 32. Fan Motor Control One Stage LED Sequence of Operation
TOP GRILLE OR FAN MOTOR MOUNT ADJUSTMENT FOR FAN CLEARANCE
Sometimes during shipping, either the fan motor mounting or top grille may become out of alignment. This may cause the fan motor blade to not clear the orifice ring. If this situation occurs, simply adjust either or both the fan motor mount or top grille positions to allow proper clearance. The top grille four fastener insertion points to the plastic top and motor mount locations are larger than the fasteners used to secure the grille and fan motor mounts. Use the procedures provided in figure 33 to adjust for fan clearance.
PUSH
FORWARD
GRILLE MOUNTING
POINTS
PUSH
FORWARD
GRILLE MOUNTING POINTS
Figure 33. Fan Blade Clearance Adjustment
The four mounting point holes that secure the top grille to the plastic top are larger than the fasteners used to secure the grille. this is also true for the four fasteners securing the fan motor to the top grille. To provide more clearance, preform either or both of the following procedures.
TOP GRILLE ADJUSTMENT
loosen the four grille mounting fasteners and push the grille forward. tighten mounting hardware. if there is still insufficient clearance proceed to Fan Motor Position Adjustment.
FAN MOTOR POSITION ADJUSTMENT
Loosen the four fan motor grille mounting fasteners and push the fan motor forward. tighten mounting hardware.
ORIFICE RING
FAN MOTOR MOUNTING POINTS
FASTENER INSERTION POINT
Page 47
XP17 SERIES
FAN MOTOR CONTROL (A177) 
PULSE−WIDTH MODULATION (PWM)
CFM Profile Pin Select
HEAT PUMP
CONTROL (A175)
CONTROL BOX
VERIFY DC VOLTAGE OUTPUT USING FAN PWM OUT AND COM TERMINALS. SEE TABLE 16 FOR OPTIMAL DC VOLTAGE BASED ON CFM PROFILE USED.
J2
COM
COM
PARK
J2
JUMPER
OFF
JUMPER
ON
LED
GREEN
FAN PWM OUT
FAN PWM OUT
RED
RED
YELLOW
YELLOW
HIGH PRESSURE SWITCH (S4)
YELLOW
YELLOW
BLUE
BLACK
YELLOW
YELLOW
FAN MOTOR
CONTROL
HEAT PUMP CONTROL (A175)
Figure 34. Fan Motor Control, Wiring, Jumper Settings, Testing and LED Location
GREEN
RED
RED
B4 FAN
BLACK
BROWN
SEE TABLE 16 FOR CFM PROFILE SELECTION OPTIONS.
MOTOR
506586−01 10/10
Page 48
FAN MOTOR CONTROL (A177) 
PULSE−WIDTH MODULATION (PWM)
CONTROL BOX
INPUT VOLTAGES DURING DEMAND
ECM/Y1 ONLY − 24VDC
HEAT PUMP
CONTROL (A175)
BLUE WIRE
24
BLACK WIRE
VDC
VAC
ONE YELLOW WIRE FROM PS (E24) TERMINAL ON HEAT PUMP
CONTROL (A175) AND SECOND YELLOW WIRES ON PIGGYBACK
GREEN
TERMINALS GOES TO S4 HIGH PRESSURE SWITCH.
RED
RED
YELLOW
S4 HIGH PRESSURE SWITCH
YELLOW
YELLOW
YELLOW WIRE
EXT PWR/R (24VAC INPUT
DURING DEMAND ONLY)
YELLOW
BLUE
BLACK
YELLOW
YELLOW
FAN MOTOR
CONTROL
GREEN
RED RED
B4 FAN
BLACK
BROWN
SEE TABLE 16 FOR CFM PROFILE SELECTION OPTIONS.
MOTOR
HEAT PUMP CONTROL
Figure 35. Testing for External Power to Fan Motor Control
Page 49
XP17 SERIES
HEAT PUMP CONTROL (A175) UNIT NOMINAL CAPACITY CODE CONFIGURATION
In a communicating system, if the room thermostat is indicating either a error code 313, indoor and outdoor unit
capacity mismatch error code, or error code 34, must program unit capacity for outdoor unit. Use the procedure
provided in figure 36 to set the unit nominal capacity code.
Set room thermostat
Go to control terminal
Remove R wire
from control (24 volt
AC power)
icomfort
enabled
Remove control
wires from i+ and
i− terminals
®
START
to OFF
strip
Non − icomfort
enabled
Remove control
wire from Y1
terminal
DS14 (Red)
DS11 (Green)
Field Test
(E33)
DS12
Communicating
®
Status Indicator
TERMINAL STRIP
Sensor harness must be attached to air conditioner control.
FINISH
Connect R wire to
control (24 volt AC
power)
Reconnect any control
wiring previously
removed.
Remove R wire from
air conditioner control
(24 volt AC power)
Place jumper on
FIELD TEST
(E33 pins)
Connect R wire to control
(24 volt AC power)
Status LED lights DS11 and DS14 will blink and then on continuously. Once both LEDs are on continuously then remove jumper immediately from E33.
If jumper is not removed immediately from E33, then DS11 and DS14 LEDs will resume blinking again.
YES
successfully
Remove R wire
from control (24 volt
AC power)
Jumper
removed
NO
Place jumper on FIELD
TEST (E33 pins) within 2 to 4
seconds after removal
The control´s DS11 and DS14 LEDs will start blinking the Unit Nominal Code at three (3) second intervals starting at 1−ton through to 6−ton. If a code is not selected, the control will cycle one more time through the codes before defaulting back to the idle mode (simultaneous slow flash).
Long blink ON red LED (DS14) to indicate tonnage and solid ON green LED (DS11) to indicate ½ tonnage.
When the required Unit Capacity Code is displaying on the LEDs, remove FIELD TEST jumper from pins (E33). LEDs will continue to display the selected unit capacity code for two (2) minutes before defaulting back to the idle mode {simultaneous slow flash}, or until the 24 volt
power is cycled to the air conditioner control.
Model
−012
−018
−024
−030
−036
−042
−048
−054
−060
−066
−072
Size
1−ton
1.5−ton
2−ton
2.5−ton
3−ton
3.5−ton
4−ton
4.5−ton
5−ton
5.5−ton
6.0−ton
DS11 Green LED
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
DS14 Red LED
1 long flash
1 long flash
2 long flashes
2 long flashes
3 long flashes
3 long flashes
4 long flashes
4 long flashes
5 long flashes
5 long flashes
6 long flashes
506586−01 10/10
Figure 36. Heat Pump Control (A175) Unit Nominal Capacity Code Configuration
Page 50
Maintenance
WARNING
This product and/or the indoor unit it is matched with may contain fiberglass wool.
Disturbing the insulation during installation, maintenance, or repair will expose you to fiberglass wool dust. Breathing this may cause lung cancer. (Fiberglass wool is known to the State of California to cause cancer.)
Fiberglass wool may also cause respiratory, skin, and eye irritation.
To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor.
Lennox Industries Inc. P.O. Box 799900 Dallas, TX 75379−9900
DEALER
Outdoor Unit
Maintenance and service must be performed by a qualified installer or service agency. At the beginning of each cooling season, the system should be checked as follows:
1. Clean and inspect outdoor coil (may be flushed with a water hose). Ensure power is off before cleaning.
2. Outdoor unit fan motor is pre−lubricated and sealed. No further lubrication is needed.
3. Visually inspect all connecting lines, joints and coils for evidence of oil leaks.
4. Check all wiring for loose connections.
5. Check for correct voltage at unit (unit operating).
6. Check amp draw on outdoor fan motor.
Motor Nameplate:_________ Actual:__________.
S Outdoor Coil  The outdoor coil may be flushed with
a water hose.
S Outdoor Coil (sea coast)  Moist air in ocean
locations can carry salt, which is corrosive to most metal. Units that are located near the ocean require frequent inspections and maintenance. These inspections will determine the necessary need to wash the unit including the outdoor coil. Consult your installing contractor for proper intervals/procedures for your geographic area or service contract.
Indoor Unit
1. Clean or change filters.
2. Lennox blower motors are prelubricated and permanently sealed. No more lubrication is needed.
3. Adjust blower speed for cooling. Measure the pressure drop over the coil to determine the correct blower CFM. Refer to the unit information service manual for pressure drop tables and procedure.
4. Belt Drive Blowers − Check belt for wear and proper tension.
5. Check all wiring for loose connections.
6. Check for correct voltage at unit. (blower operating)
7. Check amp draw on blower motor.
Motor Nameplate:_________ Actual:__________.
Indoor Coil
1. Clean coil if necessary.
2. Check connecting lines, joints and coil for evidence of oil leaks.
3. Check condensate line and clean if necessary.
Locations with Possibility of Heavy Snow or
Freezing Rain Accumulation
Heavy snow and/or freezing rain can interfere with the performance of the outdoor fan assembly. Lennox recommends use of the optional snow guard (X8782) in these areas.
7. Inspect drain holes in coil compartment base and clean if necessary.
NOTE - If insufficient heating or cooling occurs, the unit should be gauged and refrigerant charge should be checked.
Outdoor Coil
It may be necessary to flush the outdoor coil more frequently if it is exposed to substances which are corrosive or which block airflow across the coil (e.g., pet urine, cottonwood seeds, fertilizers, fluids that may contain high levels of corrosive chemicals such as salts)
Figure 37. Snow Guard Top Cover  X8782
Page 51
XP17 SERIES
HOMEOWNER
Cleaning of the outdoor unit’s coil should be performed by a trained service technician. Contact your dealer and set up a schedule (preferably twice a year, but at least once a year) to inspect and service your outdoor unit. The following maintenance may be performed by the homeowner.
IMPORTANT
Sprinklers and soaker hoses should not be installed where they could cause prolonged exposure to the outdoor unit by treated water. Prolonged exposure of the unit to treated water (i.e., sprinkler systems, soakers, waste water, etc.) will corrode the surface of steel and aluminum parts and diminish performance and longevity of the unit.
Outdoor Coil
The outdoor unit must be properly maintained to ensure its proper operation.
S Please contact your dealer to schedule proper
inspection and maintenance for your equipment.
S Make sure no obstructions restrict airflow to the
outdoor unit.
S Grass clippings, leaves, or shrubs crowding the unit
can cause the unit to work harder and use more energy.
S Keep shrubbery trimmed away from the unit and
periodically check for debris which collects around the unit.
Routine Maintenance
In order to ensure peak performance, your system must be properly maintained. Clogged filters and blocked airflow prevent your unit from operating at its most efficient level.
1. Air Filter  Ask your Lennox dealer to show you
where your indoor unit’s filter is located. It will be either at the indoor unit (installed internal or external to the cabinet) or behind a return air grille in the wall or ceiling. Check the filter monthly and clean or replace it as needed.
2. Disposable Filter  Disposable filters should be
replaced with a filter of the same type and size.
NOTE If you are unsure about the filter required for your system, call your Lennox dealer for assistance.
3. Reusable Filter  Many indoor units are equipped
with reusable foam filters. Clean foam filters with a mild soap and water solution; rinse thoroughly; allow filter to dry completely before returning it to the unit or grille.
NOTE The filter and all access panels must be in place any time the unit is in operation.
4. Lennox Branded Air Filters  are designed to
remove airborne particles from the air passing through the filter.
5. Indoor Unit  The indoor unit’s evaporator coil is
equipped with a drain pan to collect condensate
formed as your system removes humidity from the inside air. Have your dealer show you the location of the drain line and how to check for obstructions. (This would also apply to an auxiliary drain, if installed.)
Thermostat Operation
See the ComfortSense® 7000 thermostat homeowner manual for instructions on how to operate your thermostat.
Heat Pump Operation
Your new Lennox heat pump has several characteristics that you should be aware of:
S Heat pumps satisfy heating demand by delivering
large amounts of warm air into the living space. This is quite different from gas- or oil-fired furnaces or an electric furnace which deliver lower volumes of considerably hotter air to heat the space.
S Do not be alarmed if you notice frost on the outdoor coil
in the winter months. Frost develops on the outdoor coil during the heating cycle when temperatures are below 45F (7C). The heat pump control activates a defrost cycle lasting 5 to 15 minutes at preset intervals to clear the outdoor coil of the frost.
S During the defrost cycle, you may notice steam rising
from the outdoor unit. This is a normal occurrence. The thermostat may engage auxiliary heat during the defrost cycle to satisfy a heating demand; however, the unit will return to normal operation at the conclusion of the defrost cycle.
Extended Power Outage
The heat pump is equipped with a compressor crankcase heater which protects the compressor from refrigerant slugging during cold weather operation.
If power to your unit has been interrupted for several hours or more, set the room thermostat selector to the EMERGENCY HEAT setting to obtain temporary heat without the risk of serious damage to the heat pump.
In EMERGENCY HEAT mode, all heating demand is satisfied by auxiliary heat; heat pump operation is locked out. After a six-hour compressor crankcase warm-up period, the thermostat can be switched to the HEAT setting and normal heat pump operation may resume.
Preservice Check
If your system fails to operate, check the following before calling for service:
S Verify room thermostat settings are correct. S Verify that all electrical disconnect switches are ON. S Check for any blown fuses or tripped circuit breakers. S Verify unit access panels are in place. S Verify air filter is clean. S If service is needed, locate and write down the unit
model number and have it handy before calling.
Accessories
For update−to−date information, see any of the following publications:
S Lennox XP17 Engineering Handbook S Lennox Product Catalog S Lennox Price Book
506586−01 10/10
Page 52
SunSource® Home Energy System
This Dave Lennox Signature® Collection heat pump is factory−equipped with components that make it SunSource with solar modules and other optional equipment so that they can become part of a SunSource System.
Units can be upgraded for use with solar equipment at the time of installation or in the future.
Solar energy is first used to meet cooling/heating demands. When the outdoor unit is not operating, the system powers lighting, appliances and other electronic devices in the home. Any surplus power is sent back to the utility company for a possible credit (check with your local utility company for availability).
®
solar−ready. These units can be matched
®
Home Energy
The SolarSynct package consists of the following components:
S Lennox
Signature
®
Solar Subpanel installed in a Dave Lennox
®
Collection air conditioner or heat pump
unit.
S Solar modules (1 to 15 may be used to vary the
amount of electricity generated).
S Envoy Communications Gateway monitors solar
power performance.
All components must be ordered separately. See the Lennox XP17 Engineering Handbook for SunSource Home Energy System component ordering.
Wiring runs from the roof−mounted solar modules to the outdoor unit. From there, power travels to the home electrical service panel using the existing outdoor unit power wiring.
®
Page 53
XP17 SERIES
XP17 Start−Up and Performance Checklist
Customer Address
Indoor Unit Model Serial
Outdoor Unit Model Serial
Solar Module Mfg and Model Serial
Notes:
START−UP CHECKS
Refrigerant Type:
Rated Load Amps Actual Amps Rated Volts Actual Volts
Condenser Fan Full Load Amps Actual Amps:
COOLING MODE
Vapor Pressure: Liquid Pressure:
Supply Air Temperature: Ambient Temperature: Return Air Temperature:
HEATING MODE
Vapor Pressure: Liquid Pressure:
Supply Air Temperature: Ambient Temperature: Return Air Temperature:
System Refrigerant Charge (Refer to manufacturer’s information on unit or installation instructions for required subcooling and approach temperatures.)
Subcooling:
Saturated Condensing Temperature (A)
minus Liquid Line Temperature (B)
Approach:
Liquid Line Temperature (A)
minus Outdoor Air Temperature (B)
Indoor Coil Temp. Drop (18 to 22°F)
Return Air Temperature (A)
minus Supply Air Temperature (B)
A B = SUBCOOLING
A B = APPROACH
A B = COIL TEMP DROP
506586−01 10/10
Page 54
Loading...