Lennox 505, 021 User Manual

INSTALLATION/
E2006 Lennox Industries Inc.
Dallas, Texas, USA
SERVICE INSTRUCTIONS
®
Humiditrol Accessory (EDA) Units
ACCESSORIES
505,021M 02/06 Supersedes 01/06
Humiditrol
The Dave Lennox Signaturet Collection Humiditrol® En­hanced Dehumidification Accessory (EDA) is designed for installation with a Lennox R−410A split−system outdoor unit and an air handler or a furnace with a variable speed blow­er. This accessory is designed for indoor installations in ei­ther upflow or horizontal air discharge applications. This
unit is for use only on R−410A systems with thermal expansion valves.
Prior to installation, study the decision tree on page 16 to confirm that all application requirements for EDA installation are met.
NOTE − For downflow application, refer to Installation In­struction Supplement, Installing EDA Unit in Downflow Configuration 505,134M.
Shipping & Packing List
S 1 − Assembled EDA indoor unit S 1 − Bag assembly (includes check/flow restrictor for
use on EDA coil, EDA notification label).
S 1 − Outdoor fan relay and wiring harness (used only
with outdoor units equipped with variable speed fan motors)
Check the components for shipping damage. If any dam­age is found, immediately contact the last carrier.
Other Required Components
Separately-ordered components are restricted to those listed in the Engineering Handbook and the price book:
S SignatureStat
included],
− Single-stage (81M26)
− Multi−stage (81M27)
− Multi−stage heat-pump (81M28)
S Twisted Pair Wire (84X49) for outdoor sensor to ther-
mostat − Required for use with SignatureStatt.
®
EDA Series Unit
thermostat [Outdoor Sensor (46M98)
Table of Contents
EDA Series Unit 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Shipping & Packing List 1. . . . . . . . . . . . . . . . . . . . . . . .
Other Required Components 1. . . . . . . . . . . . . . . . . . . .
General Information 1. . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit Dimensions 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation Dimensions and Arrangement 3. . . . . . . . .
Component Functions 4. . . . . . . . . . . . . . . . . . . . . . . . . .
General Installation Information 5. . . . . . . . . . . . . . . . .
Electrical Wiring 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
EDA Installation Flow Chart & Procedures 5. . . . . . . .
Leak Testing, Evacuation, Charging 8. . . . . . . . . . . . . .
Insulating and Sealing the Unit 9. . . . . . . . . . . . . . . . . .
Other System Components 9. . . . . . . . . . . . . . . . . . . . .
How the EDA Unit Works 10. . . . . . . . . . . . . . . . . . . . . . .
Cooling Mode with Dehumidification ON 10. . . . . . . . . .
Cooling Mode (Dehumidification OFF) 11. . . . . . . . . . . .
Heating Mode (Heat Pump Applications) 11. . . . . . . . . .
Air Resistance Table 13. . . . . . . . . . . . . . . . . . . . . . . . . . .
Repair Parts List 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wiring Diagrams 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Decision Tree 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General Information
NOTE − These instructions are intended as a general guide and do not supersede local codes in any way. Consult au­thorities having jurisdiction before installation.
The Humiditrol® EDA unit will operate to dehumidify, as re­quired, when ambient temperatures are below 95ºF. When temperatures reach 95ºF, the cooling and dehumidification requirements will both be satisfied by the increased sys­tem runtime. In applications that include a Humiditrol EDA unit, a call to activate the dehumidification mode at or above 95ºF is unnecessary and would not be issued or al­lowed by the SignatureStatt room thermostat.
Prior to system checkout, consider the outdoor ambient temperature. REMEMBER, the EDA unit does NOT function in temperatures at or above 95ºF. Plan testing to be conducted when temperatures are between 65ºF and 95ºF to ensure proper EDA set up and checkout operation.
S 75VA 24VAC indoor unit transformer (12P61) − Re-
quired when EDA unit is installed with a two-stage heat pump system.
S Humiditrol
plications information in Lennox Engineering Hand­book)
®
EDA Insulation and Piping Kit (refer to ap-
02/06 505,021M
The approved application for the EDA Series unit is restricted to those listed in the Engineering Hand­book and price book.
*2P0206* *P505021M*
Enhanced Dehumidification
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
IMPORTANT
Litho U.S.A.
®
WARNING
11/16
20−3/4
11/16
This cased product contains fiberglass wool. Dis­turbing the insulation during installation, mainte­nance, or repair will expose you to fiberglass wool dust. Breathing this may cause lung cancer. (Fiber­glass wool is known to the State of California to cause cancer.)
Fiberglass wool may also cause respiratory, skin, and eye irritation.
To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor.
Lennox Industries Inc. P.O. Box 799900 Dallas, TX 75379−9900
Unit Dimensions
WARNING
Risk of explosion or fire. Can cause injury or death. Recover all refrigerant to relieve pressure before opening the system.
IMPORTANT
The Clean Air Act of 1990 bans the intentional vent­ing of refrigerant (CFC’s, HFC’s, and HCFC’s) as of July 1, 1992. Approved methods of recovery, recycl­ing or reclaiming must be followed. Fines and/or in­carceration may be levied for noncompliance.
EDA Model Dimensions − Inches (mm)
Dimension EDA−024B EDA−036C EDA−060D
A 17−1/2 (445) 21 (533) 24−1/2 (622)
B 12−1/4 (311) 12−1/4 (311) 14 (356)
C 16−1/8 (422) 19−5/8 (498) 23−1/8 (587)
D 16−1/8 (422) 19-5/8 (498) 23−1/8 (587)
E 1−3/8 (35) 3−1/8 (79) 4−7/8 (124)
F 3−1/8 (79) 4−7/8 (124) 6−5/8 (168)
G 3 (76) 3−1/4 (83) 4−3/4 (121)
Check/Flow Restrictor to Vapor Line Tee
Liquid Line to Indoor TXV
Liquid Line From Outdoor Unit
E
1
(25)
To Charge Compensator side connection
A
9−1/2 (241)
2−1/2
(64)
F
G
Electrical Inlet
B
(17)
1−3/4
(44)
11/16 (17)
D
11/16 (17)
OUTLET
AIR
OPENING
(527)
22−1/4
(565)
(17)
EDA 01/06
11/16 (17)
INLET AIR OPENING INLET AIR OPENING
C
11/16 (17)
1−7/16 (37)
20−1/8
(511)
Page 2
11/16 (17)
Installation Dimensions and Arrangement
EDA UNIT
(TRANSITION See Note 2)
INDOOR COIL
EDA−024B: 12−1/2 EDA−036C: 12−1/2
EDA−060D: 14
Varies by indoor
coil model; see
LENNOX
Engineering
Handbook.
12" (min.)
TRANSITION (See Note 1)
FURNACE
TYPICAL
UP−FLOW
POSITION
(Furnace Shown)
TYPICAL HORIZONTAL
POSITION (Furnace Shown)
AIR FLOW
UP-FLOW FURNACE
NOTES:
1. Transition is required for all air handlers; dimension width and depth is dependent upon the air handler and the EDA model used.
2. Transition is required between indoor coil and EDA if 5 ton EDA unit is used with small profile furnace.
Figure 1
Varies by air
handler model; see
Handbook for
40
AIR FLOW
LENNOX
Engineering
dimensions.
UP-FLOW AIR HANDLER
Page 3
EDA INSTALLATION/ SERVICE INSTRUCTIONS
Component Functions
Check/Flow Restrictor Operation
Charge CompensatorThe charge compensator
(shown in figure 5) serves to maintain the proper amount of refrigerant circulating in larger systems. [Some systems do not require a charge compensator, but do require a simi-
FROM
VAPOR
LINE
TEE
CHECK/FLOW RESTRICTOR FLOATS IN CHATLEFF CONNECTOR
GREATER
PRESSURE
lar kit to connect into the system (see Engineering Hand­book)]
The charge compensator stores excess refrigerant when the EDA coil is active and returns it to the system during
FROM
VAPOR
LINE
TEE
GREATER
PRESSURE
O−RING SEALS CHECK/FLOW RESTRICTOR
normal cooling or heating operations. When the EDA coil is active, less charge is required to obtain the proper amount of subcooling because of the additional coil surface and the cooler air which passes over the EDA coil.
Check/Flow RestrictorThe check function of the check/flow restrictor (shown in figure 2) prevents refriger­ant from flowing into the inactive components during times when the EDA coil is inactive. The flow restrictor controls the rate of return of charge to the system from the charge compensator and the EDA coil when the system changes from "EDA coil active" to "EDA coil inactive."
Valve AssemblyThe first valve of the diverting valve as­sembly (figure 3, E) directs the flow of refrigerant to either bypass the EDA coil (EDA coil is inactive) or pass through the EDA coil (EDA coil is active).The second valve (figure 3 F) directs the flow of refrigerant back to the liquid line when the first valve (E) allows flow through the EDA coil. When the EDA coil is inactive, the second valve (F) provides a vent path to the suction line, draining the EDA coil and charge compensator of liquid refrigerant.
Figure 2
EDA Unit Parts Arrangement
AB CD A B CD A B C D
EDA−024B
EDA−036C EDA−060D
EDA
UNIT
EDA
UNIT
EFEF
3−WAY DIVERTING VALVE ASSEMBLY
A − Liquid Line From Outdoor Unit B − Liquid Line to Indoor TXV C − Check/Flow Restrictor to Vapor
Line Tee
EDA COIL
3−WAY DIVERTING VALVE ASSEMBLY
D − To Charge Compensator side connection (1/4" line must be brazed closed on systems that do not require the installation of a charge compensator)
E − EDA inactive mode − bypasses the EDA EDA active mode − allows refrigerant flow through EDA F − EDA inactive mode − vent path to suction line; EDA active mode − directs refrigerant flow back to
liquid line
EDA COIL
3−WAY DIVERTING VALVE ASSEMBLY
Figure 3
EF
EDA COIL
EDA 01/06
Page 4
General Installation Information
Releasing Air Charge
NOTE − EDA units use dry air as a holding charge.
WARNING
Improper installation, adjustment, alteration, ser­vice or maintenance can cause personal injury, loss of life, or damage to property.
Installation and service must be performed by a qualified installer or service agency.
The EDA unit may be used in upflow or horizontal dis­charge installations. Slots around the inlet end of the EDA cabinet are provided to secure the EDA unit to the duct flanges of indoor coil/air handler cabinets. Use field-pro­vided #8 x 1" long SDST screw (usually 6 required).
CAUTION
Physical contact with metal edges and corners while applying excessive force or rapid motion can result in personal injury. Be aware of, and use caution when working nearby these areas during installation or while servicing this equipment.
Refrigeration
All EDA coils are shipped with a combination check/flow restrictor. The restrictor is provided in the bag assem- bly and must be installed. Refer to the appropriate high and/or low side installation instructions for information on the appropriate line sets. Refer to Lennox Refrigerant Pip­ing guide (Corp. 9351−L9) for proper size, type, and ap­plication of field−fabricated lines.
CAUTION
The EDA coil is shipped from the factory pressur­ized with dry air. Pierce a hole in the coil’s rubber plug vapor line seal to relieve the pressure before re­moving the seals.
Ensure that the coil is void of pressure. Remove the rubber plug from the lines.
NOTE − If there is no pressure when the plugs are pierced, check the unit for leaks before continuing with the installa­tion.
Refrigerant Line Connections
NOTE − When connecting lines, be careful to avoid damag­ing the 3−way diverting valve access panel. Place a wet rag against the piping plate and around the EDA unit line con­nections. A wet rag heat shield must be in place during brazing to guard against damage to the paint.
Electrical Wiring
Electrical wiring diagrams are provided in figures 12 and 13 (see pages 14 and 15). Some modifications to certain units may be necessary. Review the diagrams before installa­tion to ensure all necessary components are on hand at time of installation.
EDA Installation and Checkout Flow Chart
Follow the procedures in the flow chart in figure 4 while re­ferring to the illustration in figure 5 to install the EDA: and associated components.
Page 5
EDA INSTALLATION/ SERVICE INSTRUCTIONS
Loading...
+ 11 hidden pages