Lennox 2PGE13, 2, PGE15, 4PGE15, 4PGE13 Installation Instructions Manual

...
Page 1
INSTALLAT I STRUCTIO
Gas
(2,4)PG E/SG(13/15)
Heatin ectric Coolin
SAFETY ................................................. 2
START-UP ............................................ 10
OPERATION ........................................ 11
MAINTENANCE ................................... 13
Series
Package Unit
TABLE OF CONTENTS
CONTROL SYSTEM DIAGNOSTICS .. 14
WIRING DIAGRAMS ............................ 15
Manufactured By
A.A.C.
A Lennox International Inc. Company
421 Monroe Street
Bellevue, OH 44811
6AS-HREB
II!il!iilIIIllUI!11II o
I A CAUTION1
The installation of the furnace, wiring, warm air ducts, venting, etc. must conform to the requirements of the National Fire Protection Association; the National Fuel Gas Code, ANSI Z223.1 (latest edition) and the National Electrical Code, ANSl/NFPA No. 70 (latest edition) in the United States; the Canadian Installation Codes CAN/CGA-B149.1 & .2 (latest edition) and the Canadian Electrical Code Part 1, CSA 22.1 (latest edition) in Canada; and any state or provincial laws, local ordinances, or local gas utility requirements. Local
authorities having jurisdiction should be consulted before installation is made. Such applicable regulations or requirements take precedence over the general instructions in this manual.
# 48111B005 Save these instructionsfor future reference Page 1
Page 2
SAFETY INSTALLATION
The following is a list of safety rules and precautions that must be followed when installing this furnace.
1. Use only with the type of gas approved for this furnace. Refer to the furnace rating plate.
2. Install this furnace only in a location and position as specified in the Location section on page 3 of these
instructions.
3. Adequate clearance must be provided around the vent hood as specified in the Clearances section on page 4
of these instructions.
4.
Never test for gas leaks with an open flame. Use a commercially available soap solution made specifi- cally for the detection of leaks to check all connec- tions, as specified in Gas Supply and Piping beginning on page 6 of these instructions.
Always install furnace to operate within the furnace's intended temperature-rise range with a duct system which has an external static pressure within the allowable range, as specified in Temperature Rise on page 11 of these instructions. See furnace rating plate.
These instructions must be hung on or near the furnace in a conspicuous place.
These units are single package air conditioners with gas
heat designed for outdoor installation on a rooftop or a slab.
The units are completely assembled. All piping, refrigerant charge, and electrical wiring are factory installed and
tested. The units require only electric power, gas piping, condensate drain, and duct connections, plus assembly of
the heating vent hood at the point of installation.
If components are to be added to a unit to meet local
codes, they are to be installed at the dealer's and/or customer's expense.
The size of unit for the proposed installation should be based on heat loss/heat gain calculation made according to the
methods of Air Conditioning Contractors of America (ACCA).
These installation instructions are intended as a
general guide only, for use by an experienced, quali-
fied contractor.
These units are listed by UL:
6.
The furnace is not recommended for use for temporary heating of buildings or structures under construction unless certain installationand operating conditions are adhered to, as specified in the Location section on page 3 of these instructions.
For use as a forced air furnace with cooling unit.
For outdoor installation only.
For installation on combustible material.
For use with natural gas or propane gas. (Conversion kit required for propane gas application.)
These units are not suitable for use with conventional venting systems.
IMPORTANT: This product has been designed and manu-
factured to meet ENERGY STAR criteria for energy effi-
ciency. However, proper refrigerant charge and proper air
flow are critical to achieve rated capacity and efficiency.
Installation of this product should follow the manufacturer's refrigerant charging and airflow instructions. Failure to
confirm proper charge and airflow may reduce energy
efficiency and shorten equipment life.
inspection
As soon as the unit is received, it should be inspected for
possible damage during transit. Ifdamage is evident, the extent of the damage should be noted on the carrier's
freight bill. A separate request for inspection by the carrier's agent should be made in writing.
Page 2 # 48111 B005
Page 3
Location Air filters must be replaced upon construction completion.
Use the following guidelines to select a suitable location for the unit.
1. Unit is designed for outdoor installation only. Unit must
be installed so all electrical components are protected from water.
2. Condenser coils must have an unlimited supply of air.
3. For ground level installation, use a level prefabricated
pad or use a level concrete slab. Do not tie the slab to the building foundation.
4. Maintain level within a tolerance of 1/4" maximum
across the entire length or width of the unit.
5. Do not locate the unit where the combustion air supply
will be exposed to any of the following substances:
Permanent wave solutions Chlorinated waxes and cleaners
Chlorine-based swimming pool chemicals Water softening chemicals Deicing salts or chemicals
Carbon tetrachloride Halogen-type refrigerants
Cleaning solvents (such as perchloroethylene) Printing inks, paint removers, varnishes, etc. Cements and glues Antistatic fabric softeners for clothes dryers Masonry acid washing materials Chlorinated laundry products Hydrochloric acid
The input rate and temperature rise must be set per the unit rating plate.
100% outdoor air must be provided for combustion air requirements during construction, installation of this unit in its intended outdoor location will accomplish this.
The heat exchanger, components, duct system, air filter(s), and evaporator coil must be thoroughly cleaned following final construction cleanup.
Following the final cleaning, all furnace operating
conditions (including ignition, input rate, temperature
rise, and venting) must be verified according to these instructions.
Exercise care when moving the unit. Do not remove any packaging until the unit is near the place of installation. An accessory lift kit can be purchased to aid in rigging (see
Figure 1). Spreaders whose length exceed the largest dimension across the unit must be used across the top of the unit. Recommended spreader length: 3 ton and smaller package units- 44", 3.5 ton and larger units - 54".
Units may also be moved or lifted with a forklift while still in the factory-supplied packaging. The lengths of the forks
of the forklift must be a minimum of 42".
Use of unit as a construction heater during any phase of construction is not recommended. Very low return air temperatures, harmful vapors, and operation of the unit with clogged or misplaced filters will damage the unit. However, if the installation and operating conditions specified below are followed, use of this unit for heating of buildings or structures under construction is permissible:
The vent hood must be installed per these installation instructions.
A room thermostat must control the furnace. The use of fixed jumpers that will provide continuous heating is
not allowed.
The return air duct must be provided and sealed to the unit.
Return air temperature must be maintained between 60°F (16°0) and 80°F (27°0).
Air filters must be installed in the system and must be maintained during construction.
# 48111 BOO5 Page 3
Using Accessory Lift Kit
Spreaders
(Field Supplied)
To avoid possible damage to unit panels from lifting clevis, place packing material
between clevis and panels before
lifting unit.
Figure 1
Page 4
Roof Curb Installation
If a roof curb is used, follow the manufacturer's installation instructions and be sure that all required clearances are observed (see following Clearances section).
Roof Curb Assembly
Figure 2
Clearances
All units require certain clearances for proper operation and service. Refer to Table 1 for the minimum clearances
to combustibles as well as minimum clearances neces- sary for servicing and proper unit operation.
Minimum Clearance Requirements
Minimum Clearance to Combustibles
Above and Below the Vent Hood
Minimum Clearance
Above Vent Hood:
Distance from Top
of Vent Hood to Top of Unit
Minimum Clearance Below Vent Hood:
Distance from Bottom of Vent Hood to Base of Unit
Figure 3
In the U.S., units may be installed on combustible floors made from wood or class A, B, or C roof covering material. In Canada, units may be installed on combustible floors.
Front 24" 48" 3"
Rear 0!! 24!!* 3!!_
Condenser
End
Blower , '
End . . ,
Top 0" 36" 36"
0" 24" 3"
0!' 30" 0!!
n n
Table 1
Figure 3 shows the minimum clearances to combustibles required above and below the vent hood. The minimum
clearance in front of the vent hood is 24".
Do not permit overhanging structures or shrubs to obstruct condenser air discharge outlet or vent outlet.
Service Access
Access to all serviceable components is provided by four
removable panels: filter compartment, blower compart- ment, furnace compartment, and top panel.
Combustion Products Discharge
The unit must be positioned such that combustion prod-
ucts discharged at the vent outlet will not result in building
degradation and must be consistent with the National Fuel
Gas Code, Z223.1 or CAN/CGA-B149.1 & .2.
The products of combustion are discharged through a screened opening in the front mullion. The horizontal vent system shall terminate at least 4' below, 4' horizontally from, or 1' above any door, window, or gravity air inlet into the building. The vent system shall terminate at least 3' above any forced air inlet located within 10'.
The unit shall be installed in a manner such that snow accumulation will not restrict the flow of flue products.
Minimum horizontal clearance of 4' from electric meters,
gas meters, regulator, and relief equipment is required.
In addition to the above requirements, consideration must be given to prevent unwanted ice buildup from the vent
condensate. The vent should not be located on the side of a building where the prevailing winter winds could trap the
moisture, causing it to freeze on the walls or on overhangs
Page 4 # 48111 B005
Page 5
(undereaves).Theventlocationshouldnotdischarge overasidewalk,patio,orotherwalkwaywherethecon- densatecouldcausethesurfacetobecomeslippery.
kWARNING
The products of combustion must not be allowed to accumulate within a confined space and recirculate.
Vent Hood
The unit is shipped with the vent hood, screen, and sheet metal screws packed in the plastic bag containing the
Installation Instructions.
To attach the vent hood and screen to the unit:
1. Insert the vent screen into the vent tube so that the screen is flush with the end of the tube, as shown in Figure 4.
Installing Vent Hood
FrontView TopView
_Vent Tube
'_-- OTE:
Screws should pass through
sides of screen
VentTube
Screen is lore-formed
t to hold screen
Vent Hood in place.
L__J
_-- vent hood faces
condenser coil.
Slotted side of
Figure 4
2. Position the vent hood over the vent tube so that the
slotted side of the hood faces the condenser coil. Use the four sheet metal screws (provided) to secure the
vent hood to the vent tube. The screws should pass through the sides of the screen in order to hold the
screen in place.
Existing Venting Systems
When an existing furnace is removed or replaced, the original venting system may no longer be sized to properly
vent the attached appliances. An improperly sized venting system can result in spillage of flue products into the living
space, the formation of condensate, leakage, etc. See the following WARNING box for proper test procedure.
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monox- ide poisoning or death.
The following steps shall be followed for each appli- ance connected to the venting system being placed into operation, while all other appliances connected to the common venting system are not in operation:
1. Seal any unused openings in the common venting system.
2. Visually inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 (latest edition) orthe CSA B149.1, Natural Gas and Propane Installation Codes and these instructions. Determine that there is no blockage or restriction, leakage, corrosion, or other deficiencies which
could cause an unsafe condition.
3. As far as practical, close all building doors and windows between the space in which the appliance(s) connected to the venting system are located and other spaces inthe building.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any
exhaust fans, such as range hoods and bathroom exhausts, so they are operating at maximum
speed. Do not operate a summer exhaust fan.
6. Follow the lighting instructions. Place the unit being inspected in operation. Adjust the thermo- stat so appliance is operating continuously.
7. Test for spillage from draft hood equipped appli- ances at the draft hood relief opening after 5 minutes of main burner operation. Use the flame
of a match or candle.
8.
If improper venting is observed during any of the above tests, the venting system must be corrected
in accordance with the National Fuel Gas Code, ANSI Z223.1/N FPA 54 (latest edition) and/or the
CSA B149.1, Natural Gas and Propane installa- tion Codes.
9.
After it has been determined that each appliance remaining connected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers, and any other gas-fired burning appli- ance to their previous conditions of use.
# 48111B005 Page 5
Page 6
CondensateDrain
1. Remove screw on cover nearest side opening.
ThePGE/SGpackageunitisequippedwitha3/4"FPT couplingforcondensatelineconnection.Plumbingmust conformtolocalcodes.Useasealingcompoundonmale pipethreads.
The condensate drain line must be properly trapped and routed to a suitable drain. See Figure 5 for proper drain arrangement. The drain line must pitch to an open drain or pump to prevent clogging of the line. Seal around the drain connection with suitable material to prevent air leakage into the return air system.
Typical Condensate Drain Connection
Unit /_ Drain Connection
1.00" Min.
,, 3oo:,
2. Lift end of cover slightly and push to slide back screw/ pin free from duct flange.
3. Slide duct cover out the side duct opening.
Removing Bottom Duct Covers
®
(b
1. Remove screw and lift.
2. Slide cover to free back pin.
Figure 6
Base_ J
' Max. '_
Positive Liquid Seal Required _
Figure 5
Ductwork
Ductwork should be designed and sized according to the methods in Manual Q of the Air Conditioning Contractors of America (ACCA).
A closed return duct system shall be used. This shall not preclude use of economizers or outdoor fresh air intake. It is recommended that supply and return duct connections at the unit be made with flexible joints.
The supply and return air duct systems should be de- signed for the CFM and static requirements of the job. They should not be sized by matching the dimensions
of the duct connections on the unit.
Outdoor ductwork must be insulated and waterproofed.
Equipment is shipped for side ductwork connection. The unit can be converted to bottom ductwork connection by removing the duct covers located over the bottom duct openings and placing these covers over the side duct openings (see Figure 6).
To remove the bottom duct cover over supply opening:
Filters
Air filters are to be used with this heating/cooling unit.
Filters are not factory supplied in the unit. However, a filter
frame accessory isavailable from the manufacturer that allows filters to be installed within the unit. if the filter
frame accessory isnot used, a filter must be installed in the duct work by the installer. Filters must always be
installed ahead of the evaporator coil and must be kept
clean or replaced. Dirty filters will reduce the airflow of the
unit. Filters should be sized in accordance with Table 2.
Gas Supply and Piping
Refer to the furnace rating plate to make sure the furnace isequipped to burn the gas supplied (natural or propane).
See LPG/Propane Units, Tanks, and Piping on page 7
for more information on converting to propane gas.
Gas supply piping should be installed in accordance with local codes and the regulations of the utility. In the ab-
sence of local codes, the latest edition of the National Fuel
Gas Code ANSI Z223.1 (in the U.S.), orthe Natural Gas
and Propane installation Codes CAN/CGA B149.1 &
Page 6 # 48111 B005
Page 7
Minimum Required Surface Area
for Disposable Filters
24,000 2.67
30,000 I 3.33
36,000
|
4.00
codes. An 1/8" NPT plugged tapping, accessible for test gauge connection, must be installed immediately up- stream of the gas supply connection to the unit. A sedi- ment trap (drip leg) shall be installed as close as practical to the gas supply inlet of the unit.
The furnace must be isolated from the gas supply piping system by closing the individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressure equal to or less than 1/2 psig (3.5 kPa) or 14" W.C. If the piping system is to be tested at pressures in excess of 1/2 psig (3.5 kPa), the furnace and its appliance main gas valve must be disconnected from the gas supply piping system.
48,000
I
5.33
60,000 _ 6.67
Table 2
B149.2 (in Canada), should be followed. Piping must be of adequate size to prevent undue pressure drop. Consult the local utility or gas supplier for complete details on special requirements for sizing gas piping.
The gas supply line should be routed through the grom- met on the side of the unit. Refer to Figure 7 to locate this access opening.
Gas and Electrical Access
Gas Line
After gas piping is complete, carefully check all piping connections (factory and field) for gas leaks. Use a leak detecting solution or other preferred means. Some soaps
used for leak detection are corrosive to certain metals. Carefully rinse piping thoroughly after leak detection has
been completed.
Thermostat _C)
Entry
Line Voltage
Entry
Figure 7
If local codes allow the use of a flexible gas appliance connector, always use a new listed connector. Do not use a connector which has previously serviced another gas appliance.
Pipe connections must be tight, and a non-hardening pipe compound resistant to liquefied petroleum gases should
be used.
Install a manual shutoff valve in the gas connection to the unit, external to the casing, in accordance with local
# 48111B005 Page 7
LPG/Propane Units, Tanks, and Piping
Units are shipped equipped for natural gas, but can be
converted to LPG/propane in the field by an approved licensed technician.
All LPG/propane gas equipment must conform to the safety standards of the National Fire Protection Association.
Page 8
Forsatisfactoryoperation,LPG/propanegaspressure mustbeaminimumof11"W.C.attheunitunderfullload.
Completeinformationregardingtanksizingforvaporiza- tion,recommendedregulatorsettings,andpipesizingis
availablefrommostregulatormanufacturersandLPG/ propanegassuppliers.
Checkallconnectionsforleakswhenpipingiscompleted, usingasoapysolution.Somesoapsusedforleakdetec-
tionare corrosive to certain metals. Carefully rinse
piping thoroughly after completing leak detection.
Thermostat
The room thermostat should be located on an inside wall where it will not be subject to drafts, sun exposure, or heat
from electrical fixtures or appliances. Follow the
manufacturer's instructions enclosed with thermostat for
general installation procedure. Color-coded insulated wires
(#18 AWG) should be used to connect thermostat to unit. Four wires are required for cooling. The heat anticipator
setting is 0.7 amp.
Compressor
Units are shipped with compressor mountings factory-
adjusted and ready for operation. Caution: Do not
loosen compressor mounting bolts.
Electrical Wiring
All wiring should be done in accordance with the National Electrical Code, ANSI/NFPA No. 70 (latest
edition); Canadian Electrical Code Part 1, CSA C22.1 (latest edition); or local codes where they prevail. Use
wiring with a temperature limitation of 75°C minimum. Run the 208 or 230 volt, 60 hertz electric power supply through
a fused disconnect switch to the connection box of the unit and connect as shown in the wiring diagram located on
the inside of the control access panel.
Power supply to the unit must be N.E.C. Class 1, and must comply with all applicable codes. A fused disconnect switch
should be field provided for the unit. The switch must be separate from all other circuits. If any of the wire supplied
with the unit must be replaced, replacement wire must be of the type shown on the wiring diagram. Electrical wiring must
be sized to carry minimum circuit ampacity marked on the unit. Use copper conductors only. Each unit must be wired
with a separate branch circuit and be properly fused.
Page 8 # 48111 B005
Page 9
Typical Wiring Connections
WITHOUT ECONOMIZER WITH ECONOMIZER
THERMOSTAT OUTDOOR UNIT THERMOSTAT OUTDOOR UNIT
-%
[_ GREEN
SINGLE PHASE
THREE PHASE
BLUE
YELLOW
BLACK
ORANGE
ECONOMIZER
[]
(Not Used)
@
POWER WIRING
208/230-1-80
(80°CMIN. WIRE)
POWER WIRING ............
24V CONTROL WIRING .......
(NEC CLASS 2)
GROUND SCREW
@ @
GROUND SCREW
POWERWIRING
200/230-3-80, 480/575-3-80
(90°C MIN.WIRE)
............ POWER WIRING
....... 24V CONTROL WIRING
(NEC CLASS 2)
Figure 8
# 48111B005 Page 9
Page 10
START-UP
For Your Safety Read Before Lighting
Pre-Start Check List
Gas Valves
Regulator Gas
Adjustment Control
Cap Knob
Complete the following checks before starting the unit:
1. Check the type of gas being supplied. Be sure it isthe same as listed on the unit nameplate.
2. Make sure that the vent hood has been properly installed.
To Light Burners:
1. Turn off electrical power to unit.
2. Turn the thermostat to lowest setting.
3. Turn the gas control knob, or slide the gas control switch, to the "ON" position (see Figure 9).
4. Turn on electrical power to the unit.
5. Set the room thermostat to the desired temperature. (If the thermostat "set" temperature is above room
temperature, the burners will light after the pre-purge time expires.)
To Shut Down Burners:
1. Turn off electrical power to unit.
Inlet Pressure Tap Outlet Pressure Tap
1/8" NPT (Manifold Pressure)
1/8" NPT
Regulator
Adjustment GasControl Switch
Inlet Pressure Tap
1/8" NPT
Outlet Pressure Tap
(Manifold Pressure)
1/8" NPT
Figure 9
propane gas with the burners in operation. If gas pressure is outside these limits, contact the gas
supplier for corrective action.
4. Adjust temperature rise to be within the range speci- fied on the rating plate.
2. Turn the gas control knob, or slide the gas control switch, to the "OFF" position (see Figure 9).
Post-Start Check List
After the entire control circuit has been energized and the heating section is operating, make the following checks:
1. Check for gas leaks, using soapy solution, in the unit piping as well as the supply piping.
2. Check for correct manifold gas pressures (see following Checking and Adjusting Gas input section).
3. Check the supply gas pressure. It must be within the limits shown on the rating plate. Supply pressure
should be checked with all gas appliances in the building at full fire. At no time should the supply
pressure during standby exceed 13" W.C., nor should it be less than 5" W.C. for natural gas or 11"W.C. for
Page 10
Checking and Adjusting Gas input
For purpose of input adjustment, the minimum permis-
sible gas supply pressure is 5" W.C. for natural gas and
11" W.C. for propane.
Gas input must never exceed the input capacity shown on
the rating plate. The furnace is equipped for natural gas
rated inputs with manifold pressure of 3.5" W.C.
The manifold pressure can be measured by shutting off the gas, removing the pipe plug inthe downstream side of the gas valve, and connecting a water manometer or gauge. To adjust the regulator, turn the adjusting screw on the regula- tor clockwise to increase pressure and inputor counter- clockwise to decrease pressure and input.The final
manifold pressure should not vary more than 0.3" W.C.
from the above specified pressure. See Figure 9 to assist
in locating the regulator on the gas valve.
# 48111B005
Page 11
ForNaturalGas:Checkthegasinputratebyobserving thegasmeter,whenavailable,makingsureallothergas appliancesareturnedoff.Thetesthandonthemeter
shouldbetimedforatleastonerevolution.Notethe numberofsecondsforonerevolution.
BTU/HR= Cubic Feet Per Revolution x 3600 x Heating
INPUT # Seconds Per Revolution Value
OPERATION
Cooling System
The cooling system is a complete factory package utilizing an air-cooled condenser. The compressor ishermetically sealed
and base mounted with rubber-insulated hold-down bolts.
The heating value of the gas can be obtained from the local utility company.
For Propane Gas: The only check for the gas input rate is to properly adjust the manifold pressure using a manometer. Typical manifold set point for installationsat altitudes from 0
to 4500 feet above sea level is 10.0" W.C.
Temperature Rise
Check the temperature rise and, if necessary, adjust blower speed to maintain temperature rise within the range shown on the unit rating plate.
High Altitude
Ratings are shown on the rating plate for elevations up to 4500 feet. For elevations above 4500 feet, ratings should
be reduced at a rate of 4% for each 1000 feet above sea level. See the National Fuel Gas Code Z223.1 (latest
edition) or the Canadian Installation Codes CAN/CGA- B149.1 & B149.2 for further details.
Secure Owner's Approval
When the system is functioning properly, secure the owner's approval. Show the owner the location of all
disconnect switches and the thermostat. Instruct the owner on how to start and stop the unit and how to adjust
temperature settings within the limitations of the system.
Unit compressors have internal protection. In the event there is an abnormal rise in the temperature of the compressor, the protector will open and cause the compressor to stop.
Cooling Sequence of Operation
When the thermostat calls for cooling, R is closed to G and Y (see the wiring diagrams found on pages 15and 16). This action completes the low voltage control circuit, energizing the compressor, condenser fan motor, and blower motor.
Blower Delay - Cooling
The circulating air blower is controlled by a timing circuit in the integrated blower/ignition control. Timings are not adjustable. Blower "on" delay is 5 seconds after the compressor starts and blower "off" timing is 90 seconds after the cooling system shuts down.
System Performance
For maximum performance of the cooling system, operat- ing temperatures and pressure should be checked. Superheat should be determined at Standard ARI test conditions of 82°F outdoor and 80°F indoor dry bulb/67°F wet bulb. If superheat measured deviates from values found in Table 3, refrigerant charge should be adjusted accordingly for maximum performance.
Suction Superheat
# 48111B005 Page 11
24 22°
PGE13
SG13 30, 36, 42, 20°
48, 60
24, 30 15°
PGE15 SG15
" 481 60 10°
Table 3
Page 12
HeatingSystem Circulating Air Blower
With the proper thermostat and sub-base, continuous blower operation is possible by closing the R to G circuit. Cooling blower delay is also functional in this mode.
Heating Sequence of Operation
1. When the thermostat calls for heat, the combustion blower is energized by the ignition control.
2. When the speed of the combustion blower reaches proper RPM, the pressure switch closes, initiating the pre-purge timing (30 seconds nominal).
3.
When pre-purge has expired, the ignition control energizes the gas valve, the spark electrode, and the flame sensor. The igniter sparks for 10 seconds, and the
flame sensor senses that flame has been established. If the flame sensor does not sense that flame has been
established in the 10-second interval, then the ignition control will de-energize the gas valve.
4.
The ignition control is designed to repeat this "trial for ignition" a total of three times. If, at the end of the third trial, a flame still has not been established, the ignition control will repeat the trial for ignition sequence 1 hour later. The 1-hour retry is indefinite. The ignition control can be reset by interrupting the unit power or the
thermostat circuit.
Depending on the package unit model, the blower motor will be either a multi-tap PSC motor or a variable speed motor.
PSC Motor
The circulating air blower is controlled by a timing circuit in the
integrated blower/ignition control. Timings are not adjustable.
Cooling - Blower "on" delay is 30 seconds after call for cooling. Blower "off" delay is 90 seconds after the cooling system shuts down.
Heating- Blower "on" delay is 30 seconds nominal after
burner ignition. Blower "off" delay is approximately 120 seconds after the thermostat is satisfied.
Variable Speed Motor
Units equipped with a variable speed circulation air blower
motor will deliver a constant airflow within a wide range of
external static pressures. Other features of this variable speed motor include:
Soft Start/Stop -The variable speed motor will slowly
ramp up to normal operating speed. This minimizes noise and increases comfort by eliminating the initial blasts of air
encountered with standard motors. At the end of a cooling or heating cycle, the motor will slowly ramp down.
Thirty seconds (nominal) after the initial trial for ignition, the circulation air blower will start.
Circulation Airflow Adjustments - The controls include a variable speed motor interface board. The ADJUST tap can be used to raise (+) or lower (-) the airflow by 15%.
6.
When the thermostat is satisfied, the combustion blower and gas valve are de-energized. The circulat- ing air blower motor will continue to run for a short period after the thermostat is satisfied.
Heating and Cooling Airflows -The units are factory set for the correct heating and cooling airflows. However, airflow changes can be made by moving the position of the HEAT and COOL taps (see Table 4).
Adjusting Airflow (Variable Speed Motor Equipped Units Only)
24, 30 68 NORM 800 90C
36 68 100C 110, 36 90 NORM 100C 110,
42, 48; 60 83 NORM 160C 120,
42, 48, 60 110 NORM 160C 120, 42, A8,.,60 i38 160C 120,
m
_OC
ett_
iiilDii_iiiiD!!ii
ADJUST, HEAT, and COOL Taps and Dehumidify
Resistor
on interface
Board
" .....A_S_
Table 4
Page 12 # 48111 B005
Page 13
Continuous Blower-The comfort level of the living space can be enhanced when using this feature by allowing continuous circulation of air between calls for cooling or heating. The continuous circulation of air occurs at half the full cooling airflow rate. To use this feature, place the thermostat fan switch into the ON position.
Cooling Airflow Ramp Up - At the beginning of a call for cooling, the blower will run at 80% of full airflow for 7.5 minutes. This improves the system's moisture removal and saves blower power during cooling start.
Reduced Airflow Operation (Dehumidification) - For situations where humidity control is an issue, the variable speed motor can be connected to operate at a 25% reduction in the normal airflow rate. The variable speed motor interface board provides for connection of a humi-
distat on the HUM terminal. When a humidistat is con- nected, the dehumidifier resistor on the interface must be
cut. The humidistat should be wired to open during high humidity, which will reduce blower airflow.
Safety Controls
The control circuit includes the following safety controls:
MAINTENANCE
Limit Control
This control is located inside the heating compartment and is designed to open at abnormally high air temperatures. It resets automatically. The limit control operates when a high temperature condition, caused by inadequate airflow, occurs. This causes the ignition control to close the gas valve. The circulation air blower continues to operate in this situation.
Pressure Switch
The pressure switch prevents the gas valve and igniter from being energized if there is insufficient combustion air
due to a failed combustion blower or a blocked vent.
Flame Sensor
Ifthe ignitioncontrol does not receive a signal from the flame sensor indicating thatthe burners have established flame, the gas valve closes after the 10-second trial for ignition period.
Rollout Switch
The switch is located above the main burners. In the event of a sustained flame rollout, the rollout switch causes the
ignition control to close the gas valve. To reset, push the button on top of the switch.
Auxiliary Limit (42, 48, and 60 units only)
This control is located in the side of the circulation air blower housing. The switch causes the ignition control to
close the gas valve should the circulation blower fail to operate. This control resets automatically.
It is recommended that this furnace be inspected by a qualified service technician at the beginning of each heating season.
Filters
Filters should be checked at least every 6 weeks. Dispos- able filters should be replaced when dirty, and cleanable filters should be cleaned regularly. It is important to keep the air filters clean, as dirty filters can restrict airflow and the blower and induced draft motors depend upon sufficient air flowing across and through them to keep from overheating.
Lubrication
The blower motor and induced draft motor are pre-lubricated by the manufacturer and do not require further lubricating attention. However, the motors should becleaned periodi- cally to prevent the possibility of overheating due to an accumulation of dust and dirt on the windings or on the
motor exterior.
Burners
Light the burners and allow to operate for a few minutes to establish normal burning conditions. Observe the burner flames. Compare this observation to Figure 10 on page 14 to determine if proper flame adjustment is present. Flame should be predominantly blue in color and strong in appear- ance. Check that all burners are lit, and that the flame does not impinge on the sides of the heat exchanger.
Distorted flame or yellow tipping of the natural gas burner flame, or long yellow tips on propane, may be caused by
# 48111B005 Page 13
Page 14
lintaccumulationordirtinsidetheburnerorburnerports, attheairinletbetweentheburnerandmanifoldpipe,or
obstructionsovertheburnerorifice. Useasoftbrushorvacuumtocleantheaffectedareas.
Typical Flame Appearance
Heat
Exchanger
Burner
Gas Burner
Manifold Flame
(Blue Only)
Figure 10
Outdoor Coil
Dirt and debris should not be allowed to accumulate on the outdoor coil surface or other parts inthe air circuit. Cleaning
should be as often as necessary to keep coil clean. Use a brush, vacuum cleaner attachment, or other suitable means.
If water is used to clean the coil, be sure the power to unit is shut off prior to cleaning. Care should be used when cleaning the coil so that the coil fins are not damaged. Do not permit the hot condenser air discharge to be obstructed by overhanging structures or shrubs.
CONTROL SYSTEM DIAGNOSTICS
Fault Codes
Slow Flash
Fast Flash Two flashes
2 Flash
3 Flash
4 Flash
5 Flash and gas valve
Steady -- Micro-controller
One flash
per second
pei Second
Two flashes
in second with
1-second pause
Three flashes in
1.5 seconds with 1-second pause
Four flashes in
2 seconds with
1-second pause
Five flashes in
2.5 seconds _ith 1-second pause
Normaloperation:
Nocallfor heat
Normaloperation:
Callfor heat
System lockout:
Failedto detect
or sustainflame
Pressure switch
openorC!osed
High limit or
rollout switch
open
Flame sensed
not energized
Internal failure:
failure; self-check
Table 5
Vent Outlet
Visually inspectvent outlet periodically to make sure there is no buildup of soot and dirt. If necessary, clean to maintain adequate opening to discharge flue products.
Page 14 # 48111 B005
Page 15
NOTE: IF ANY OF THE ORIGINAL WIRE iS REPLACED, THE SAME SIZE AND TYPE WIRE MUST BE USED. USE COPPER CONDUCTOR ONLY, MIN. 75°C WIRE.
WARNING- ELECTRIC SHOCK HAZARD. UNIT MUST BE GROUNDED iN ACCORDANCE WITH NATIONAL AND LOCAL CODES.
HEAT ANTICIPATION SETTING: 0.70 AMP
LINE VOLTAGE FIELD INSTALLED
>Z
o_
c_
L2
L
z,
ra
COMPRESSOR
cE
COMPRESSOR
CONTACTOR
K1-2
KI-f
_- COMPRESSOR
- CONTACTOR
1_ BLK
DUAL
CAPACITOR
C12_ BRN
;IGNITION CONTROL : J i-; ,A3 _O m<,
i L1 CMB BLWR < o < z;
SEE CHART
FOR WIRING
M'
I
_B. BL
_ CAPACITOF M(
i- i
o_
CONDENSER
FAN MOTOR
DIAGNOSTICS
The following ignition control board LED codes will indicate normal or abnormal operations:
SLOW FLASH Normal operation, no call for heat. FAST FLASH Normal operation, call for heat. 2 FLASH System lockout. 3 FLASH Pressure switch senses incorrect pressure. 4 FLASH Main limit open or rollout switch open. 5 FLASH Flame sensed and gas valve not energized. STEADY Internal failure (micro-controller failure; self check).
PRESSURE [4___$I8
SWITCH
AUX. LIMIT
SWITCH
(iF USED)
HIGH PRESSURE
SWITCH THERMOSTAT
(iF USED) BLU
:, FUSE ; / l [ /
GRODND G>:,> | /
I ]i w>:,> / ! i
I;I i @LED O> _ -_ ]
Y>:>--q l CONTACTOR
FLAME':l /
LO_._..O.._/Y._-'b._/__........ _Z._.."_ Y_- / y
_1 I _ZH Blower Speed Chart _] I w _I I Unit Factory Shipped Settings
ROLLOUT (_$471 'T' .
SWITCH _ L [ _ C.oohng H.eatmg HEAT (BLU) COOL (BLK)
z:J J mput mput _L_ 24 68 MED LOW
30 68 MED* MED
GV1
r- .....
...... J
GAS
VALVE
MOTOR
SPEED TAPS
36 36 42 42 48 48 48 6O 6O 6O
68 90 83 110 83 110 138 83 110 138
MED
HIGH*
LOW* LOW*
LOW LOW
MED*
LOW LOW MED
HiGH HiGH
LOW LOW MED MED
MED HiGH HiGH HiGH
Connection Diagram
Single Stage Heat, Single Phase
PIN 48129-001
JUMPER REQUIRED
IF THE JUMPER IS NOT USED, CONNECT BLUE WIRE TO THE HEAT TERMINAL.
Page 16
_L1
K1-1
COMPRESSOR
:TI_CONTACTO R
__ _BLK
it DUAL
A1321 ___ CAPACITOR
208/230V-1-60
COMPRESB;ORt_
A1321R
7
CONDENSER
FAN MOTOR
COMPRESSOr
CONTACTOR
K1-2
L2
L
TRANSFORMER
INDOOR
SLOWER
MOTOR
NOTE: IF ANY OF THE ORIGINAL WIRE IS REPLACED. THE SAME SIZE AND TYPE WIRE MUST BE USED. USE COPPER CONDUCTOR ONLY, MIN. 75°C WIRE.
WARNING- ELECTRIC SHOCK HAZARD. UNIT MUST BE GROUNDED IN ACCORDANCE WITH NATIONAL AND LOCAL CODES.
HEAT ANTICIPATION SETTING: 0.70 AMP
LINE VOLTAGE FIELD INSTALLED
DIAGNOSTICS
HIGH PRESSURE
SWITCH THERMOSTAT
(IF USED) YEL ): $1
l_ YEL
i
RED :24VAC
FUSE
The following ignition control board LED codes will
indicate normal or abnormal operations:
ORN
GRN
I_HUM A54 ;
ICM BOARD i
SEE i
I BLOWER SPEED i :=EM
CHART
i
i ADJUST HEAT COOL I
_O NORM o o A Ao "
: (a B ">oB_ I
pY2 0 o c o-, c oo i
(TEST) o D > D,0
L,,
IIIIIIIIIIIIIIII
INDOOR BLOWER |
MOTOR B3J
Blower Speed Chart
Unit Factory Shipped Settings
SLOW FLASH Normal operation, no call for heat. FAST FLASH Normal operation, call for heat. 2 FLASH System lockout. 3 FLASH Pressure switch senses incorrect pressure. 4 FLASH Main limit open or rollout switch open. 5 FLASH Flame sensed and gas valve not energized, STEADY Internal failure (micro-controller failure; self check),
Connection Diagram
Single Stage Heat, Variable Speed, Single Phase
PIN 48107-001
Cooling
Input
24 30 36 36 42 42 48 48 48 60 60 60
Heating
Input
68 68 68 90 83
110
83 110 138
83 110 138
ADJUST
NORM NORM NORM NORM NORM NORM NORM NORM NORM NORM NORM NORM
HEAT
A A
B A C C C C A C C A
COOL
B A A A
C
C
B
B
B A A A
Loading...