Lennox 4HP18LT User Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
4HP18LT Series
Split System Heat Pump
Save these instructions for future reference
WARNING
The equipment covered in this manual is to be installed by trained and experienced service and installation technicians. Improper installation, modification, service, or use can cause electrical shock, fire, explosion, or other conditions which may cause personal injury , death, or property damage. Use appropriate safety gear including safety glasses and gloves when installing this equipment.
W ARNING
Risk of electrical shock. Disconnect all remote power supplies before installing or servicing any portion of the system. Failure to disconnect power supplies can result in property damage, personal injury , or death.
INSTALLATION ....................................................2
CONNECTION DIAGRAM....................................4
TABLE OF CONTENTS
W ARNING
Installation and servicing of air conditioning equipment can be hazardous due to internal refrigerant pressure and live electrical components. Only trained and qualified service personnel should install or service this equipment. Installation and service performed by unqualified persons can result in property damage, personal injury , or death.
WARNING
Sharp metal edges can cause injury. When installing the unit, use care to avoid sharp edges.
START-UP..........................................................13
OPERATION ......................................................18
MAINTENANCE .................................................23
Manufactured By
Allied Air Enterprises, Inc.
A Lennox International Inc. Company
West Columbia, SC 29170
*506470-01*
506470-01 Issue 1007
Page 1
INSTALLATION
General
Read this entire instruction manual, as well as the instructions supplied in separate equipment, before starting the installation. Observe and follow all warnings, cautions, instructional labels, and tags. Failure to comply with these instructions could result in an unsafe condition and/or premature component failure.
These instructions are intended as a general guide only for use by qualified personnel and do not supersede any national or local codes in any way . The installation must comply with all provincial, state, and local codes as well as the National Electrical Code (U.S.) or Canadian Electrical Code (Canada). Compliance should be determined prior to installation.
4HP18LT condensing units use R410A which is an ozone­friendly HFC refrigerant. The unit must be installed with a matching indoor coil and line set. A filter drier approved for use with R410A is inst alled in the unit.
IMPORTANT: This product has been designed and manufactured to meet ENERGY STAR criteria for energy efficiency when matched with appropriate coil components. However, proper refrigerant charge and proper air flow are critical to achieve rated capacity and efficiency . Inst allation of this product should follow the manufacturer’s refrigerant charging and air flow instructions. Failure to confirm proper
charge and airflow may reduce energy efficiency and shorten equipment life.
Inspection of Shipment
Upon receipt of equipment, carefully inspect it for possible shipping damage. If damage is found, it should be noted on the carrier’s freight bill. Take special care to examine the unit inside the carton if the carton is damaged. Any concealed damage discovered should be reported to the last carrier immediately, preferably in writing, and should include a request for inspection by the carrier’s agent.
If any damages are discovered and reported to the carrier DO NOT INST ALL THE UNIT, as claim may be denied.
Check the unit rating plate to confirm specifications are as ordered.
Location of Unit
Outdoor units operate under a wide range of weather conditions; therefore, multiple factors must be considered when positioning the unit. The unit must be positioned to give adequate clearances for sufficient airflow and servicing. Refer to Figure 1 for installation clearances.
Installation Clearances
36”
36” *
36”
When servicing or repairing HV AC components, ensure the fasteners are appropriately tightened. T able 1 shows torque values for fasteners.
Torque Table
Fastener Torque
Stem Caps 8 ft. lbs.
Service Port Caps 8 ft. lbs.
Sheet Metal Screws
#8 Machine Screws
#10 Machine Screws
Compressor Bolts
Table 1
16 in. lbs.
16 in. lbs.
28 in. lbs.
90 in. lbs.
36” *
* A service clearance of 30" must be maintained on
one of the sides adjacent to the control box. Clearance to one of the other three sides must be 36". Clearance to one of the remaining two sides may
be 12" and the final side may be 6". A clearance of 24" must be maint ained between units. 48" clearance required on top of unit. Maximum soffit
overhang is 36".
Figure 1
Place a sound-absorbing material, such as Isomode under the unit if it will be installed in a location or position that will transmit sound or vibration to the living area or adjacent buildings..
506470-01 Issue 1007
Page 2
Install the unit high enough above the ground or roof to allow adequate drainage of defrost water and prevent ice buildup.
In heavy snow areas, do not locate the unit where drifting snow will occur. The unit base should be elevated above the depth of average snows.
NOTE: Elevation of the unit may be accomplished by construction a frame using suitable materials. If a support frame is constructed, it must not block drain holes in unit base.
When installed in areas where low ambient temperatures exist, locate unit so winter prevailing winds do not blow directly into outdoor coil.
Locate unit away from overhanging roof lines which would allow water or ice to drop on, or in front of, coil or into unit.
If unit coil cannot be mounted away from prevailing winter winds, a wind barrier should be constructed (See Figure 3). Size the barrier at least the same height and width as the outdoor unit. Mount barrier 24” from the sides of the unit in the direction of the prevailing winds.
Slab Mounting
When installing a unit at grade level, install on slab high enough above grade so that water from higher ground will not collect around the unit (See Figure 2). Slab should have a slope tolerance away from the building of 2° or 2” per 5’. This will prevent ice from building up under the unit during a defrost cycle. Refer to following roof mounting section for barrier construction if unit must face prevailing winter winds.
Slab Mounting
Discharge Air
Building
Structure
Mounting Slab
Ground Level
Figure 3
Electrical Wiring
All field wiring must be done in accordance with the National Electrical Code (NEC) recommendations, Canadian Electrical Code (CEC) and CSA Standards, or local codes, where applicable.
Refer to the furnace or blower coil installation instructions for additional wiring application diagrams and refer to unit rating plate for minimum circuit ampacity and maximum overcurrent protection size.
W ARNING
Unit must be grounded in accordance with national and local codes. Failure to ground unit properly can result in personal injury or death.
Figure 2
Roof Mounting
Install unit at a minimum of 6” above surface of the roof to avoid ice buildup around the unit. Locate the unit above a load bearing wall or area of the roof that can adequately support the unit. Consult local codes for rooftop applications.
506470-01 Issue 1007
WARNING
Line voltage is present at all components when unit is not in operation on units with single pole contactors. Disconnect all remote electric power supplies before opening access panel. Unit may have multiple power supplies. Failure to disconnect all power supplies could result in personal injury or death.
Page 3
Figure 4
1. Install line voltage power supply to unit from a properly sized disconnect switch. Any excess high volt age field wiring should be trimmed or secured away from the low voltage field wiring.
Refrigerant Piping
If the 4HP18L T unit is being inst alled with a new indoor coil and line set, the refrigerant connections should be made as outlined in this section. If an existing line set and/or indoor coil will be used to complete the system, refer to this section as well as the section that follows entitled - Flushing Existing Line Set and Indoor Coil.
If this unit is being matched with an approved line set or indoor coil which was previously charged with R-22 refrigerant, the line set and coil must be flushed prior to installation. If the unit is being used with and existing indoor coil which was equipped with a liquid line which served as a metering device (RFCI), the liquid line must be replaced prior to the installation of the 4HP18L T unit.
Field refrigerant piping consists of liquid and suction lines from the outdoor unit (sweat connections) to the indoor coil (flare or sweat connections).
Select line set diameters from Table 2 to ensure that oil returns to the compressor. Size vertical suction riser to maintain minimum velocity at minimum capacity. Recommended line length is 50’ or less. If more than 50’ line set is required, contact Technical Services. Table 2 shows the diameters for line sets up to 100’ although vertical lift applications and trapping requirements need to be reviewed with Technical Services for line sets over 50’.
2. Ground unit at unit disconnect switch or to an earth ground. To facilitate conduit, a hole is in the bottom of the control box. Connect conduit to the control box using a proper conduit fitting. Units are approved for use only with copper conductors. 24V Class II circuit connections are made in the low voltage junction box. Refer to Figure 4 for high voltage field wiring diagram. A complete unit wiring diagram is located inside the unit control box cover.
3. Install room thermostat on an inside wall that is not subject to drafts, direct sunshine, or other heat sources.
4. Install low voltage wiring from outdoor to indoor unit and from thermostat to indoor unit. (See Wire Diagram on page 27.)
5. Do not bundle any excess 24V control wire inside control box. Run control wire through installed wire tie and tighten wire tie to provide low voltage strain relief and to maintain seperation of field-installed low and high voltage circuits.
Installing Refrigerant Line
During the installation of an air conditioning system, it is important to properly isolate the refrigerant line to prevent unnecessary vibration. Line set contact with the structure (wall, ceiling, or floor) may cause objectionable noise when vibration is translated into sound. As a result, more energy or vibration can be expected. Close attention to line set isolation must be observed.
Following are some points to consider when placing and installing a high-efficiency outdoor unit:
506470-01 Issue 1007
Page 4
Placement
Install unit away
from windows
Two 90° elbows installed in lineset will reduce lineset vibration
Be aware that some localities are adopting sound ordinances based on how noisy the unit is at the neighbor’s home, not at the original installation. Install the unit as far as possible from the property line. When possible, do not install the unit directly outside a bedroom window . Glass has a verry high level of sound transmission. Figure 5 shows how to place the outdoor unit and line set to reduce line set vibration.
Brazing Connection Procedure
1. Cut ends of refrigerant lines square (free from nicks or dents). Debur the ends. The pipe must remain round; do not pinch end of line.
2. Before making line set connections, use dry nitrogen to purge the refrigerant piping. This will help to prevent oxida­tion and the introduction of moisture into the system.
Line Set Isolation
Illustrations on pages 6 and 7 demonstrate procedures which ensure proper refrigerant line set isolation. Figure 6 shows how to install line sets on horizontal runs. Figure 7 shows how to make a transition from horizontal to vertical. Figure 8 shows how to install line sets on vertical runs.
Refrigerant Line Set Diameters (in.)
Liquid Line
Line Set Length and Size
BTUH
12 f t . 25 ft. 50 ft. 75 ft. 100 ft.
24,000
36,000
48,000
60,000
3/8 3/8 3/8 3/8 3/8
3/8 3/8 3/8 3/8
3/8 3/8 3/8 1/2
3/8 3/8 3/8 1/2
1/2
1/2
1/2
3. Use silver alloy brazing rods (5% or 6% silver alloy for copper-to-copper brazing or 45% silver alloy for copper-to­brass or copper-to-steel brazing) which are rated for use with R410A refrigerant.
4. Remove the Schrader core assemblies before brazing to protect them from damage due to extreme heat. Replace the cores when brazing is complete.
5. Remove light maroon washers from service valves and shield light maroon stickers to protect them during brazing. Wrap a wet cloth around the valve body and copper tube stub to protect it from heat damage.
Outside Unit Placement & Installation
S uction Line
Line Set Length and Size
BTUH
12 f t . 25 ft. 50 ft. 75 ft. 100 ft.
24,000
36,000
48,000
60,000 1/8 1/8 1-1/8
3/4 3/4
7/8
7/8
3/4 3/4
7/8
7/8
For installations exceeding 50’, contact
T echnical Services.
Table 2
7/8
7/87/8
1-1/8
1-1/8
7/8
1-1/8
1-1/8
1-1/8
Figure 5
506470-01 Issue 1007
Page 5
6. Braze the line set to the service valve. Quench the joints
with water or a wet cloth to prevent heat damage to the valve core and opening port. The tube end must stay
bottomed in the fitting during final assembly to ensure proper seating, sealing, and rigidity .
7. Install the thermal expansion valve which is sold
separately and which is approved for use with R410A refrigerant in the liquid line at the indoor coil (see Refrigerant
Metering Device on page 9).
Refrigerant Line Sets: Installing Horizont al Runs
CAUTION
When flushing existing line set and/or indoor coil, be sure to empty all existing traps. Residual mineral oil can act as an insulator, preventing proper heat transfer. It can also clog the thermal expansion valve, reducing system performance and capacity . Failure to properly flush system as explained in these instructions will void warranty .
To hang line set from joist or rafter, use either metal strapping material or anchored heavy nylon wire ties.
Strapping Material
(around vapor line only)
8
Floor Joist or
Roof Rafter
Metal Sleeve
Floor Joist or Roof Rafter
Wire Tie
(around vapor line only)
Tape or Wire Tie
8
Strap the vapor line to the joist or rafter at 8 intervals then strap the liquid line
to the vapor line.
Tape or Wire Tie
Figure 6
506470-01 Issue 1007
Page 6
Refrigerant Line Sets: Transition from Vertical to Horizontal
Heavy Nylon
Wall
Stud
Metal Sleeve
Anchored
Wire Tie
Strap Liquid Line to Vapor Line
Liquid Line
Vapor Line Wrapped
in Armaflex
Figure 7
Muffler-Type
Wall
Stud
Metal Sleeve
Automotive
Hanger
Strap Liquid Line to Vapor Line
Liquid Line
Vapor Line Wrapped
in Armaflex
Refrigeraant Line Sets: Installing Vertical Runs (new construction shown)
NOTE: Similar installation practices
should be used if line set is to be installed on exterior of outside wall.
Vapor Line Wrapped
IMPORTANT:
Refrigerant
lines must not
contact structure.
Outside Wall
Wood Block
Between Studs
with Armaflex
Outside Wall
Liquid Line
Caulk
IMPORTANT: Refrigerant lines must not contact wall.
Vapor Line
Liquid Line
Wire Tie
Inside Wall
Strap
Sleeve
Wire Tie
Wood Block
Wire Tie
Strap
PVC Pipe
506470-01 Issue 1007
Fiberglass Insulation
Figure 8
Sleeve
Page 7
Flushing Existing Line Set and Indoor Coil
This procedure should not be performed on systems which contain contaminant s, such as compressor burn out.
Required Euipment
The following equipment is needed to flush the existing line set and indoor coil (See Figure 9). T wo clean R-22 recovery bottles, an oil-less recovery machine with a “pump down” feature, and two sets of gauges (one for use with R-22 and one for use with R410A).
from the existing system. Refer to the gauges after shutdown to confirm that the entire system is completely void of refrigerant. Disconnect the liquid and suction lines from the existing outdoor unit.
If the existing outdoor unit is equipped with manual shutoff valves AND new R-22 refrigerant will be used to flush the system:
Start the existing R-22 refrigerant system in cooling mode and close the liquid line valve. Pump all the existing R-22 refrigerant back into the outdoor unit.
Flushing Procedure
IMPORTANT: The line set and/or indoor coil must be flushed with at least the same amount of refrigerant that previously charged the system. Check the charge in the flushing cylinder before flushing the unit.
1. Remove existing R-22 refrigerant using the appropriate
procedure.
If the existing outdoor unit is not equipped with shutoff valves, or if the unit is not operational AND the existing R-22 refrigerant will be used to flush the system:
Disconnect all power to the existing outdoor unit. Connect the existing unit, a clean recovery cylinder, and the recovery machine according to the instructions provided with the recovery machine. Remove all R-22 refrigerant
Flushing Connections
(It may be necessary to bypass the low pressure switches to ensure complete refrigerant evacuation.)
When the low side system pressures reach 0 psig, close the suction line valve. Disconnect all power to the existing outdoor unit. Refer to the gauges after shutdown to confirm that the valves are not allowing refrigerant to flow back into the low side of the system. Disconnect the liquid and suction lines from the existing outdoor unit.
2. Remove the existing outdoor unit. Set the new R410A unit and follow the brazing connection procedure outlined previously on this page to make line set connections. Do
not install the R410A thermal expansion valve at this time.
3. Make low voltage and line voltage connections to the new outdoor unit. Do not turn on power to the unit or
open the outdoor unit service valves at this time.
Figure 9
506470-01 Issue 1007
Page 8
4. Remover the existing R-22 refrigerant flow control orifice
or thermal expansion valve before continuing with flushing procedures. R-22 flow control devices are not approved for use with R410A refrigerant and may prevent proper flushing. Use a field-provided fitting to reconnect the lines.
5. Remove the pressure tap valve cores from the 4HP18L T
units service valves. Connect an R-22 cylinder with clean refrigerant to the suction service valve. Connect the R-22 gauge set to the liquid line valve and connect a recovery maching with an empty recovery tank to the gauge set.
6. Set the recovery machine for liquid recovery and start
the recovery machine. Open the gauge set valves to allow the recovery machine to pull a vacuum on the existing system line set and indoor coil.
7. Invert the cylinder of clean R-22 and open its valve to
allow liquid refrigerant to flow in to the system through the suction line valve. Allow the refrigerant to pass from the cylinder and through the line set and the indoor coil before it enters the recovery machine.
An R410A system will not operate properly with an R-22 metering device.
Install the refrigerant metering device as shown in Figure 1 1. Do not twist cap tubes when loosening the seal nut from the orifice housing. Use wrench to back up the distributor.
8. Af ter all of the liquid refrigerant has been recovered, switch
the recovery machine to vapor recovery so that all of the R­22 vapor is recovered. Allow the recovery machine to pull a vacuum on the sytem.
NOTE: A single system flush should remove all of the mineral oil from the existing refrigerant lines and indoor coil. A second flushing may be done (using clean refrigerant) if insufficient amounts of mineral oil were removed during the first flush.
After each system flush, allow the recovery machine to pull a vacuum on the system at the end of the procedure.
9. Close the valve on the inverted R-22 cylinder and the
gauge set valves. Pump the remaining refrigerant out of the recovery machine and turn the machine off.
10. Use nitrogen to break the vacuum on the refrigerant
lines and indoor coil before removing the recovery machine, gauges, and R-22 refrigerant drum. Re-install pressure tap valve cores into the 4SHP18L T unit’s service valves.
11. Install the fixed orifice (or thermal expansion valve
approved for use with R410A refrigerant) in the liquid line at the indoor coil.
Refrigerant Metering Device
4HP18LT units are designed for use with TXV systems. Refer to the appropriate following section for information on installing the chosen refrigerant metering device.
Figure 10
Expansion Valve Systems
Expansion valves equipped with Chatleff-type fittings are available from the manufacturer. See Table 3 for proper TXV for each unit.
TXV Data
MODEL PART NUMBER
4HP18LT- 24
4HP18LT - 36
4HP18LT - 48, -60 H4TXV03
T able 3
To install an expansion valve (See Figure 10 above):
1. Separate the distributor assembly and remove the piston orifice and used teflon seal. Insert nozzle end of the expansion valve along with a new teflon seal into the distributor and tighten to 20 - 30 ft. lbs. Use backup wrench on all wrench flats. Overtightening will crush the teflon
seal and may cause a leak.
H4TXV01
H4TXV02
506470-01 Issue 1007
2. Attach liquid line portion of distributor assembly along with new teflon seal to the inlet of the expansion valve. Tighten to 20 - 30 ft. lbs. Use backup wrench on all wrench flats. Overtightening will crush the teflon seal and may
cause a leak.
Page 9
Loading...
+ 19 hidden pages