Lennox 47W36, 47W37 Installation Instructions Manual

COMMERCIAL UNITS KITS AND ACCESSORIES
E2018 Lennox Industries Inc.
Dallas, Texas, USA
504,603M 1/2018 Supersedes 11/2016
INSTALLATION INSTRUCTIONS FOR INDOOR REMOTE TEMPERATURE SENSORS
— 10K OHM (47W37) AND 20K OHM (47W36)
Electrical Wiring Practices
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal inju ry or loss of life.
Installation and service must be performed by a licensed professional HVAC installer (or equivalent) or service agency.
When the remote indoor sensor is installed with a commercial touch screen thermostat, use these instructions to install the sensor. Also see the touch screen instructions for more on wiring the sensor to the thermostat.
PRE-INSTALLATION
Cover Removal
A snap-fit locking mechanism is used to attach the cover of the remote indoor sensor to its sub-base. To remove the cover from the sub-base:
1. Insert a thin, flat blade screwdriver into each of the two slots at the bottom of the module to release the two locking tabs (see figure 1).
LOCKING TAB SLOTS (2)
Erratic System Operation Hazard.
Failure to follow proper wiring practices can introduce disruptive electrical interference (noise).
All wiring must comply with local electrical codes and ordinances, or as specified on installation wiring diagrams.
Typical Commercial Touch Screen Thermostats
The following items are recommended for indoor remote sensor installations:
1. Keep wiring at least one foot away from large inductive loads such as motors, line starters, lighting ballasts, and large power distribution panels.
2. Shielded cable is required in installations where these guidelines cannot be met.
3. Ground shield only to grounded controller case.
4. When connecting to all other thermostats, remote indoor sensor wiring can be sized from 16 to 22 AWG (1.31 to .34 mm2) depending on the application.
5. The maximum length of wire from a thermostat or remote indoor sensor to another remote indoor sensor is 1000 feet (305 meters).
6. Twisted pair wire is recommended for wire runs longer than 100 feet (30.5 meters).
ComfortSense 7500 Commercial Thermostat (13H15)
and ComfortSense 8500 (14X55 and 14X56)
1. Must keep wiring at least one foot away from large inductive loads such as motors, line starters, lighting ballasts, and large power distribution panels.
2. Do not use shielded cabling.
3. Use only standard two-wire thermostat wire.
4. Indoor (room) sensor wiring can be sized from 16 to 22
AWG depending on the application.
5. The maximum length of wire from the thermostat to all
remote sensors should not exceed 300 feet (100 meters).
CAUTION
IMPORTANT
Figure 1. Cover Removal
2. Tilt the cover out and away from the sub-base to release the two locking tabs.
INSTALLATION
Install the remote indoor sensor on an inside wall approximately 54 inches (1372 mm) from the floor (or in the specified location) to allow exposure to the average room temperature. Do not mount the remote indoor sensor
Page 1
on an outside wall, on a wall containing water pipes or near air ducts. Avoid locations that are exposed to discharge air from registers or radiation from lights, appliances, or the sun.
The remote indoor sensor may be installed on a wall, on a standard utility conduit box using no. 6 (3.5 mm) screws or on a 60 mm wall outlet box (see figure 2). When installing directly on a wall, use the type of screws appropriate for the wall material. See figure 3 for remote indoor sensor dimensions.
STANDARD UTILITY CONDUIT BOX
SUBBASE
NO. 6 SCREW
FRONT COVER
60 MM WALL OUTLET BOX
SUBBASE
FRONT COVER
3.5 MM SCREW
Figure 2. Installing Remote Indoor Sensor on
Standard Utility Conduit Box or 60 mm Wall Outlet
Box
3” (76mm)
4-9/16” (116mm)
CAUTION
Improper Electrical Contact Hazard.
Screw type terminal blocks are designed to accept no more than one 16 AWG (1.31 sq. mm
Connect multiple wires that are 16-18 AWG (1.31 to .82 mm2) with a wire nut. Include a pigtail with this wire group and attach the pigtail to the individual terminal block.
Wire the terminal blocks as follows:
1. For single wires, strip 3/16" (5mm); for multiple wires going into one terminal, strip 1/2 in. (13 mm) insulation from the conductor.
2. If two or more wires are being inserted into one terminal, twist the wires together before inserting.
E-BUS CONNECTOR TERMINALS
1. STRIP 1/2 IN. (13 MM) FROM WIRES TO BE ATTACHED AT ONE TERMINAL.
2. TWIST WIRES TOGETHER WITH PLIERS (A MINIMUM OF THREE TURNS)
3. CUT TWISTED END OF WIRES TO 3/16 IN. (5 MM) BEFORE INSERTING INTO TERMINAL AND TIGHTENING SCREW. THEN PULL ON EACH WIRE IN ALL TERMINALS TO CHECK FOR GOOD MECHANICAL CONNECTION.
Figure 4. Multi-wire Installation
NOTE: When two or more wires are being inserted into one terminal, be sure to twist them together. Deviation from this rule can result in improper electrical contact (see figure 4).
3. Insert the wire in the required terminal location and tighten the screw to complete the termination.
4. Verify remote indoor sensor wiring per figure 5. Check that thermistor is in place.
ZONE SENSOR (RT2)
2
) conductor.
THERMOSTAT (A2)
7/8” (22mm)
Figure 3. Room Sensor Dimensions
WIRING
Attach the wires from the device sensor terminals to the appropriate remote indoor sensor terminals on the thermostat (see figure 5).
THERM ISTOR
S1
S2
Figure 5. Room Sensor Wiring
Page 2
Loading...
+ 1 hidden pages