Lennox 2SHP13, 2SHP13-18, 2SHP13-24, 2SHP13-30, 2SHP13-36 Installation And Maintenance Instructions Manual

...
Page 1
INSTALLATION AND MAINTENANCE
INSTRUCTIONS
2SHP13 Series
Split System Heat Pump
WARNING
The equipment covered in this manual is to be installed by trained and experienced service and installation technicians. Improper installation, modification, service, or use can cause electrical shock, fire, explosion, or other conditions which may cause personal injury, death, or property damage. Use appropriate safety gear including safety glasses and gloves when installing this equipment.
WARNING
Risk of electrical shock. Disconnect all remote power supplies before installing or servicing any portion of the system. Failure to disconnect power supplies can result in property damage, personal injury, or death.
WARNING
Installation and servicing of air conditioning equipment can be hazardous due to internal refrigerant pressure and live electrical com­ponents. Only trained and qualified service personnel should install or service this equip­ment. Installation and service performed by unqualified persons can result in property damage, personal injury, or death.
WARNING
Sharp metal edges can cause injury. When installing the unit, use care to avoid sharp edges.
TABLE OF CONTENTS
INSTALLATION ...................................... 2
START-UP............................................. 11
OPERATION ........................................ 15
MAINTENANCE ................................... 17
HOMEOWNER INFORMATION ........... 18
CONNECTION DIAGRAMS ................. 21
WARRANTY......................................... 23
Manufactured By
A.A.C.
A Lennox International Inc. Company
421 Monroe Street
Bellevue, OH 44811
*48306B006*
Save these instructions for future reference
# 48306B006 Page 1
Page 2
INSTALLATION
Location of Unit
General
Read this entire instruction manual, as well as the instructions supplied in separate equipment, before starting the installation. Observe and follow all warn­ings, cautions, instructional labels, and tags. Failure to comply with these instructions could result in an unsafe condition and/or premature component failure.
These instructions are intended as a general guide only for use by qualified personnel and do not supersede any national or local codes in any way. The installation must comply with all provincial, state, and local codes as well as the National Electrical Code (U.S.) or Canadian Electrical Code (Canada). Compliance should be determined prior to installation.
When servicing or repairing HVAC components, ensure the fasteners are appropriately tightened. Table 1 shows torque values for fasteners.
Torque Table
renetsaF euqroT
spaCmetS.sbl.tf8
spaCtroPecivreS .sbl.tf8
swercSlateMteehS.sbl.ni61
swercSenihcaM8# .sbl.ni61
swercSenihcaM01#.sbl.ni82
Outdoor units operate under a wide range of weather conditions; therefore, multiple factors must be considered when positioning the unit. The unit must be positioned to give adequate clearances for sufficient airflow and servic­ing. Refer to Figure 1 for installation clearances.
Installation Clearances
36"
36 *"
36 *"
* A service clearance of 30" must be maintained on
one of the sides adjacent to the control box. Clearance to one of the other three sides must be 36". Clearance to one of the remaining two sides may be 12" and the final side may be 6".
A clearance of 24" must be maintained between units.
48" clearance required on top of unit. Maximum soffit overhang is 36".
36"
stloBrosserpmoC .sbl.ni09
Table 1
Inspection of Shipment
Upon receipt of equipment, carefully inspect it for possible shipping damage. If damage is found, it should be noted on the carrier’s freight bill. Take special care to examine the unit inside the carton if the carton is damaged. Any concealed damage discovered should be reported to the last carrier immediately, preferably in writing, and should include a request for inspection by the carrier’s agent.
If any damages are discovered and reported to the carrier DO NOT INSTALL THE UNIT, as claim may be denied.
Check the unit rating plate to confirm specifications are as ordered.
Figure 1
Place a sound-absorbing material, such as Isomode, under the unit if it will be installed in a location or position that will transmit sound or vibration to the living area or adjacent buildings.
Install the unit high enough above the ground or roof to allow adequate drainage of defrost water and prevent ice buildup.
In heavy snow areas, do not locate the unit where drifting snow will occur. The unit base should be elevated above the depth of average snows.
NOTE: Elevation of the unit may be accomplished by constructing a frame using suitable materials. If a support frame is constructed, it must not block drain holes in unit base.
When installed in areas where low ambient tempera­tures exist, locate unit so winter prevailing winds do not blow directly into outdoor coil.
Page 2 # 48306B006
Page 3
Locate unit away from overhanging roof lines which would allow water or ice to drop on, or in font of, coil or into unit.
Slab Mounting
Wind Barrier Construction
Prevailing Winter Winds
When installing a unit at grade level, install on slab high enough above grade so that water from higher ground will not collect around the unit (see Figure 2). Slab should have a slope tolerance away from the building of 2° or 2" per 5'. This will prevent ice from building up under the unit during a defrost cycle. Refer to following roof mounting section for barrier construction if unit must face prevailing winter winds.
Slab Mounting
Discharge Air
Building
Structure
Mounting Slab
Ground Level
2° or 2" per 5' slope tolerance away from building structure.
Figure 2
Roof Mounting
Install unit at a minimum of 6" above surface of the roof to avoid ice buildup around the unit. Locate the unit above a load bearing wall or area of the roof that can adequately support the unit. Consult local codes for rooftop applications.
If unit coil cannot be mounted away from prevailing winter winds, a wind barrier should be constructed (see Figure 3). Size the barrier at least the same height and width as the outdoor unit. Mount barrier 24" from the sides of the unit in the direction of the prevailing winds.
Electrical Wiring
Wind Barrier
Inlet Air
Inlet Air
24"
Inlet Air
Figure 3
WARNING
Unit must be grounded in accordance with national and local codes. Failure to ground unit properly can result in personal injury or death.
WARNING
Line voltage is present at all components when unit is not in operation on units with single pole contactors. Disconnect all remote electric power supplies before opening access panel. Unit may have multiple power supplies. Failure to disconnect all power supplies could result in personal injury or death.
Refer to the furnace or blower coil Installation Instructions for additional wiring application diagrams and refer to unit rating plate for minimum circuit ampacity and maximum overcurrent protection size.
1. Install line voltage power supply to unit from a properly sized disconnect switch. Any excess high voltage field wiring should be trimmed or secured away from the low voltage field wiring.
All field wiring must be done in accordance with the National Electrical Code (NEC) recommendations, Canadian Electrical Code (CEC) and CSA Standards, or local codes, where applicable.
# 48306B006 Page 3
2. Ground unit at unit disconnect switch or to an earth ground. To facilitate conduit, a hole is in the bottom of the control box. Connect conduit to the control box using a proper conduit fitting. Units are approved for use only with copper conductors. 24V Class II circuit connections are made in the low voltage junction box. A complete unit wiring diagram is located inside the unit control box cover (see also pages 20 and 21 of this instruction).
Page 4
3. Install room thermostat on an inside wall that is not subject to drafts, direct sunshine, or other heat sources.
4. Install low voltage wiring from outdoor to indoor unit and from thermostat to indoor unit (see Figure 4).
Refrigerant Piping
Field refrigerant piping consists of liquid and suction lines from the outdoor unit (sweat connections) to the indoor coil (flare or sweat connections).
5. Do not bundle any excess 24V control wire inside control box. Run control wire through installed wire tie and tighten wire tie to provide low voltage strain relief and to maintain separation of field-installed low and high voltage circuits.
Thermostat Designations
(Some connections may not apply.
Refer to specific thermostat and indoor unit.)
Without Auxiliary Heat
Select line set diameters from Table 2 to ensure that oil returns to the compressor. Size vertical suction riser to maintain minimum velocity at minimum capacity. Recom­mended line length is 50' or less. If more than 50' line set is required, contact Technical Services at (419) 483-4840. Table 2 shows the diameters for line sets up to 100' although vertical lift applications and trapping requirements need to be reviewed with Technical Services for line sets over 50'.
Refrigerant Line Set Diameters (in.)
eniLdiuqiL
eziSdnahtgneLteSeniL
HUTB
.tf21 .tf52 .tf05 .tf57 .tf001
000,818/38/38/38/38/3
000,42 8/3 8/3 8/3 8/3 8/3
000,038/38/38/38/32/1
000,63 8/3 8/3 8/3 8/3 2/1
000,248/38/38/32/12/1
With Auxiliary Heat
Do not connect C (common) connection between indoor unit and thermostat except when required by the indoor thermostat. Refer to thermostat installation instructions. C (common) connection between indoor unit and outdoor unit required for proper operation.
000,84 8/3 8/3 8/3 2/1 2/1
000,068/38/38/32/12/1
eniLnoitcuS
eziSdnahtgneLteSeniL
HUTB
.tf21 .tf52 .tf05 .tf57 .tf001
000,814/34/34/34/34/3
000,42 4/3 4/3 4/3 4/3 8/7
000,034/34/34/38/78/7
000,63 8/7 8/7 8/7 8/7 8/1-1
000,248/78/78/78/1-18/1-1
000,84 8/7 8/7 8/7 8/1-1 8/1-1
000,068/1-18/1-18/1-18/1-18/1-1
For installations exceeding 50', contact
Technical Services at (419) 483-4840.
Table 2
Figure 4
Page 4 # 48306B006
Page 5
Installing Refrigerant Line
Brazing Connection Procedure
During the installation of an air conditioning system, it is important to properly isolate the refrigerant line to prevent unnecessary vibration. Line set contact with the structure (wall, ceiling, or floor) may cause objectionable noise when vibration is translated into sound. As a result, more energy or vibration can be expected. Close attention to line set isolation must be observed.
Following are some points to consider when placing and installing a high-efficiency outdoor unit:
Placement
Be aware that some localities are adopting sound ordi­nances based on how noisy the unit is at the neighbor’s home, not at the original installation. Install the unit as far as possible from the property line. When possible, do not install the unit directly outside a bedroom window. Glass has a very high level of sound transmission. Figure 5 shows how to place the outdoor unit and line set to reduce line set vibration.
Outside Unit Placement
and Installation
Install unit away
from windows
1. Cut ends of refrigerant lines square (free from nicks or dents). Debur the ends. The pipe must remain round; do not pinch end of line.
2. Before making line set connections, use dry nitrogen to purge the refrigerant piping. This will help to prevent oxidation and the introduction of moisture into the system.
3. Use silver alloy brazing rods (5% or 6% silver alloy for copper-to-copper brazing or 45% silver alloy for copper-to-brass or copper-to-steel brazing) which are rated for use with HCFC-22 refrigerant.
4. Remove the Schrader core assemblies before brazing
to protect them from damage due to extreme heat. Replace the cores when brazing is complete.
5. Wrap a wet cloth around the valve body and copper tube stub to protect them from heat damage during brazing. Wrap another wet cloth underneath the valve body to protect the base paint.
6. Braze the line set to the service valve. Quench the joints with water or a wet cloth to prevent heat damage to the valve core and opening port. The tube end must stay
bottomed in the fitting during final assembly to ensure proper seating, sealing, and rigidity.
7. Install the factory-supplied fixed orifice (or thermal expansion valve which is sold separately and which is approved for use with HCFC-22 refrigerant) in the liquid line at the indoor coil.
Two 90° elbows installed in lineset will reduce lineset vibration
Figure 5
Line Set Isolation
Illustrations on the pages 6 and 7 demonstrate procedures which ensure proper refrigerant line set isolation. Figure 6 shows how to install line sets on horizontal runs. Figure 7 shows how to make a transition from horizontal to vertical. Figure 8 shows how to install line sets on vertical runs.
Refrigerant Metering Device
2SHP13 units are designed for use with either fixed orifice or TXV systems. Refer to the appropriate following section for information on installing the chosen refrigerant meter­ing device.
Fixed Orifice Systems
2SHP13 units are shipped with a fixed orifice refrigerant metering device. Replace the existing indoor unit fixed orifice with the orifice supplied with this unit. Place the supplied fixed orifice sticker on the indoor cabinet after installation. See Table 3 on page 7 for the proper fixed orifice size for each unit. In nonstandard applications, the provided fixed orifice may not be appropriately sized.
Install the fixed orifice as shown in Figure 9 on page 7. Do not twist cap tubes when loosening the seal nut from the orifice housing. Use wrench to back up the distributor.
# 48306B006 Page 5
Page 6
Refrigerant Line Sets: Installing Horizontal Runs
To hang line set from joist or rafter, use either metal strapping material or anchored heavy nylon wire ties.
Strapping Material
(around vapor line only)
8
Floor Joist or
Roof Rafter
Metal Sleeve
Floor Joist or Roof Rafter
Wire Tie
(around vapor line only)
Tape or Wire Tie
8
Strap the vapor line to the joist or rafter at 8 intervals then strap the liquid line
to the vapor line.
Wall Stud
Tape or Wire Tie
Figure 6
Refrigerant Line Sets: Transition from Vertical to Horizontal
Anchored
Heavy Nylon
Wire Tie
Strap Liquid Line to Vapor Line
Wall
Stud
Automotive
Muffler-Type
Hanger
Strap Liquid Line to Vapor Line
Metal Sleeve
Liquid Line
Vapor Line Wrapped
in Armaflex
Metal Sleeve
Vapor Line Wrapped
in Armaflex
Liquid Line
Figure 7
Page 6 # 48306B006
Page 7
Refrigerant Line Sets: Installing Vertical Runs (new construction shown)
NOTE: Similar installation practices should be used if line set is to be installed on exterior of outside wall.
IMPORTANT:
Refrigerant
lines must not
contact structure.
Wood Block
Between Studs
Vapor Line Wrapped
with Armaflex
Outside Wall
Outside Wall
Liquid Line
Caulk
IMPORTANT: Refrigerant lines must not contact wall.
Vapor Line
Liquid Line
Wire Tie
Inside Wall
Strap
Sleeve
Wire Tie
Wood Block
Wire Tie
Strap
PVC Pipe
Fixed Orifice Data
ledoM
81-31PHS280-484001750.
42-31PHS2 11-484001 160.
03-31PHS212-484001270.
63-31PHS2 32-484001 470.
24-31PHS233-484001680.
84-31PHS2 53-484001 880.
06-31PHS273-484001090.
traP
rebmuN
Table 3
Fiberglass Insulation
llirD
eziS
Sleeve
Figure 8
Metering Device Installation
If installing an expansion valve on an indoor coil that previously used a fixed orifice, remove orifice before installing valve.
# 48306B006 Page 7
Figure 9
Page 8
Expansion Valve Systems
Expansion valves equipped with Chatleff-type fittings are available from the manufacturer. See Table 4 for proper TXV for each unit.
TXV Data
ledoM
63-,03-,42-,81-31PHS210VXT2H
84-,24-31PHS2 20VXT2H
06-31PHS230VXT2H
traP
rebmuN
Service Valve
Valve Closed
Service Port
To outdoor coil
Service
Port Cap
Schrader valve open
to line set when valve is
closed (front seated)
Insert hex
wrench here
Stem Cap
Insert hex wrench here
To indoor coil
(valve front seated)
Stem Cap
Table 4
To install an expansion valve (see Figure 9 on page 7):
1. Separate the distributor assembly and remove the piston orifice and used teflon seal. Insert nozzle end of the expansion valve along with a new teflon seal into the distributor and tighten to 20 – 30 ft. lbs. Use backup wrench on all wrench flats. Overtightening
will crush the teflon seal and may cause a leak.
2. Attach liquid line portion of distributor assembly along with new teflon seal to the inlet of the expansion valve. Tighten to 20 – 30 ft. lbs. Use backup wrench on all wrench flats. Overtightening will crush the
teflon seal and may cause a leak.
3. Connect the external equalizer line to the equalizer port on the suction line and tighten to 8 ft. lbs.
4. Strap the superheat sensing bulb to the suction header.
If installing an expansion valve on an indoor coil that previously used a fixed orifice, be sure to remove the existing fixed orifice. Failure to remove a fixed orifice when installing an expansion valve to the indoor coil will result in improper operation and damage to the system.
Manifold Gauge Set
When checking the unit charge, use a manifold gauge set that is equipped with “low loss” hoses. Do not use a manifold gauge set with anything other than a “low loss” hose.
Liquid and Suction Line Service Valves
The liquid line and suction line service valves (see Figure
10) and service ports are used for leak testing, evacuat-
ing, charging, and checking charge.
Service Port
To outdoor coil
Service Port Cap
Schrader
Valve
To indoor coil
Valve Open
Figure 10
Each valve is equipped with a service port which has a factory-installed Schrader valve. A service port cap protects the Schrader valve from contamination and serves as the primary leak seal.
To Access the Schrader Port:
1. Remove the service port cap with an adjustable wrench.
2. Connect gauge to the service port.
3. When testing is completed, replace service port cap. Tighten finger tight, then an additional 1/6 turn.
To Open Liquid or Suction Line Service Valve:
1. Remove stem cap with an adjustable wrench.
2. Use a service wrench with a hex-head extension to back the stem out counterclockwise as far as it will go. Use a 3/16" hex head extension for liquid line service valves and a 5/16" extension for suction line service valves.
3. Replace the stem cap. Tighten finger tight, then tighten an additional 1/6 turn.
Page 8 # 48306B006
Page 9
To Close Liquid or Suction Line Service Valve:
Leak Testing
1. Remove the stem cap with an adjustable wrench.
2. Use a service wrench with a hex-head extension to turn the stem clockwise to seat the valve. Tighten firmly.
3. Replace the stem cap. Tighten finger tight, then tighten an additional 1/6 turn.
Suction Line (Ball Type) Service Valve
Suction line (ball type) service valves function the same way as the other valves; the difference is in the construc­tion (see Figure 11).
The ball valve is equipped with a service port with a factory-installed Schrader valve. A service port cap protects the Schrader valve from contamination and serves as the primary seal.
Ball Type Service Valve
(Valve Open)
After the line set has been connected to the indoor and outdoor units, the line set connections and indoor unit must be checked for leaks.
WARNING
Refrigerant can be harmful if inhaled. Refrigerant must always be used and recovered responsibly. Incorrect or irresponsible use of refrigerant can result in personal injury or death.
WARNING
Never use oxygen to pressurize refrigeration or air conditioning systems. Oxygen will ex­plode on contact with oil and could cause personal injury or death.
Using an Electronic Leak Detector
Use adjustable wrench. To open, rotate stem counterclockwise 1/4 turn (90°). To close, rotate stem clockwise 1/4 turn (90°).
Figure 11
1. Connect the high pressure hose of the manifold gauge set to the suction valve service port. (Normally the high pressure hose is connected to the liquid line port; however, connecting it to the suction ports helps to protect the manifold gauge set from damage caused by high pressure.)
2. With both manifold valves closed, connect the cylin­der of HCFC-22 refrigerant. Open the valve on the HCFC-22 cylinder (vapor only).
3. Open the high pressure side of the manifold to allow HCFC-22 into the line set and indoor unit. Weigh in a trace amount of HCFC-22. (A trace amount is a maximum of 2 oz. of refrigerant or 3 lbs. pressure.) Close the valve on the HCFC-22 cylinder and the valve on the high pressure side of the manifold gauge set. Disconnect the HCFC-22 cylinder.
4. Connect a cylinder of nitrogen with a pressure regulat­ing valve to the center port of the manifold gauge set.
When using high pressure gas such as nitrogen for this purpose, be sure to use a regulator that can control the pressure down to 1 or 2 psig.
# 48306B006 Page 9
5. Adjust nitrogen pressure to 150 psig. Open the valve on the high side of the manifold gauge set to pressur­ize the line set and the indoor coil.
Evacuation
Evacuating the system of noncondensables is critical for proper operation of the unit. Noncondensables are defined
Page 10
as any gas that will not condense under temperatures and pressures present during operation of an air conditioning system. Noncondensables and water vapor combine with refrigerant to produce substances that corrode copper piping and compressor parts.
WARNING
Do not use a compressor to evacuate a sys­tem. Avoid deep vacuum operation. Extremely low vacuums can cause internal arcing and compressor failure. Danger of equipment damage. Damage caused by deep vacuum operation will void warranty.
Use a thermocouple or thermistor electronic vacuum gauge that is calibrated in microns. Use an instrument that reads down to 50 microns.
1. Connect the manifold gauge set to the service valve ports as follows:
within a 20-minute period after shutting off the vacuum pump and closing the manifold gauge valves.
9. When the requirements above have been met, disconnect the manifold hose from the vacuum pump. Open the service valves to break the vacuum in the line set and indoor unit.
Low pressure gauge to suction line service valve
High pressure gauge to liquid line service valve
2. Connect micron gauge.
3. Connect the vacuum pump (with vacuum gauge) to the center port of the manifold gauge set.
4. Open both manifold valves and start vacuum pump.
5. Evacuate the line set and indoor unit to a minimum of 500 microns or lower. During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once to determine if there is a rapid rise in pressure. A rapid rise in pressure indicates a relatively large leak. If this occurs, the leak testing procedure must be repeated.
6. When 500 microns or lower is maintained, close the manifold gauge valves, turn off the vacuum pump, and disconnect the manifold gauge center port hose from the vacuum pump. Attach the manifold gauge center port hose to a nitrogen cylinder with pressure regulator set to 150 psig and purge the hose. Open the manifold gauge valves to break the vacuum in the line set and indoor unit. Close the manifold gauge valves.
7. Shut off the nitrogen cylinder and remove the manifold gauge hose from the cylinder. Open the manifold gauge valves to release the nitrogen from the line set and indoor unit.
8. Reconnect the manifold gauge to the vacuum pump, turn the pump on, and continue to evacuate the line set and indoor unit until 500 microns is maintained
Page 10 # 48306B006
Page 11
START-UP
If the system is void of refrigerant, clean the system using the procedure described below.
CAUTION
If unit is equipped with a crankcase heater, it should be energized 24 hours before unit start-up to prevent compressor damage as a result of slugging.
1. Rotate fan to check for frozen bearings or binding.
2. Inspect all factory and field-installed wiring for loose
connections.
3. After evacuation is complete, open liquid line and
suction line service valves to release refrigerant charge (contained in outdoor unit) into system.
4. Replace the stem caps and secure finger tight, then
tighten an additional 1/6 of a turn.
5. Check voltage supply at the disconnect switch. The
voltage must be within the range listed on the unit nameplate. If not, do not start equipment until the power company has been consulted and the voltage condition corrected.
6. Set thermostat for cooling demand, turn on power to
indoor blower, and close the outdoor unit disconnect switch to start the unit.
1. Use dry nitrogen to pressurize the system and check for leaks. Repair leaks, if possible.
2. Evacuate the system to remove as much of the moisture as possible.
3. Use dry nitrogen to break the vacuum.
4. Evacuate the system again.
5. Weigh the appropriate amount of HCFC-22 refrigerant (listed on unit nameplate) into the system.
6. Monitor the system to determine the amount of moisture remaining in the oil. Use a test kit to verify that the moisture content is within the kit’s dry color range. It may be necessary to replace the filter drier several times to achieve the required dryness level. If
system dryness is not verified, the compressor will fail in the future.
The outdoor unit should be charged during warm weather. However, applications arise in which charging must occur in the colder months. The method of charging is deter­mined by the unit’s refrigerant metering device and the outdoor ambient temperature.
Measure the liquid line temperature and the outdoor ambient temperature as outlined below:
7. Recheck unit voltage with unit running. Power must be within range shown on unit nameplate.
Refrigerant Charging
Units are factory charged with the amount of HCFC-22 refrigerant indicated on the unit rating plate. This charge is based on a matching indoor coil and outdoor coil with 15' line set. For varying lengths of line set, refer to Table 5 for refrigerant charge adjustment.
Refrigerant Charge Adjustment
teSeniLdiuqiL
retemaiD
.ni8/3.tf5rep.zo3
* If line length is greater than 15 ft., add this amount.
If line length is less than 15 ft., remove this amount.
tsujda.tf5rep.zO
*tesenil.tf51morf
Table 5
1. Connect the manifold gauge set to the service valve ports as follows (see Figure 12 on page 12):
Low pressure gauge to suction line service valve
High pressure gauge to liquid line service valve
2. Close manifold gauge set valves. Connect the center manifold hose to an upright cylinder of HCFC-22.
3. If room temperature is below 70°F, set the room thermo­stat to call for heat. This will create the necessary load for properly charging the system in the cooling cycle.
4. Use a digital thermometer to record the outdoor ambient temperature.
5. When the heating demand has been satisfied, switch the thermostat to cooling mode with a set point of 68°F. When pressures have stabilized, use a digital thermometer to record the liquid and suction line temperatures.
6. The outdoor temperature will determine which charg­ing method to use. Proceed with the appropriate charging method.
# 48306B006 Page 11
Page 12
Cooling Cycle
DEFROST THERMOSTAT
EXPANSION/CHECK VALVE
LOW
PRESSURE
GAUGE MANIFOLD
PRESSURE
TO
HCFC-22
DRUM
HIGH
LIQUID
SERVICE
BIFLOW FILTER / DRIER
MUFFLER
LINE
PORT
DISTRIBUTOR
OUTDOOR COIL
COMPRESSOR
SUCTION SERVICE
PORT
REVERSING VALVE
SUCTION LINE VALV E
EXPANSION/CHECK VALVE
NOTE - ARROWS INDICATE
DIRECTION OF REFRIGERANT FLOW
INDOOR UNIT
INDOOR
COIL
Use gauge ports on suction line valve and liquid line valve for evacuating refrigerant lines and indoor coil. Use suction gauge port to measure suction pressure during charging.
Figure 12
OUTDOOR UNIT
Charge Using Weigh-In Method (Fixed Orifice/TXV Systems)
If the system is void of refrigerant, or if the outdoor ambient temperature is cool, first locate and repair any leaks then use the weigh-in method to charge the unit.
1. Recover the refrigerant from the unit.
2. Conduct a leak check, then evacuate as previously outlined.
3. Weigh in the charge according to the total amount shown on the unit nameplate.
If weighing facilities are not available or if unit is being charged during warm weather, follow one of the other procedures outlined below.
Charge Using Subcooling Method (Fixed Orifice/TXV Systems) – Outdoor Temperatures 65°F or Above
If charging a fixed orifice or TXV system when the outdoor ambient temperature is 65°F or above, the subcooling method can be used to charge the unit.
check both the outdoor ambient and the liquid line temperatures.
2. At the same time, record the liquid line pressure reading.
3. Use a temperature/pressure chart for HCFC-22 to determine the saturation temperature for the liquid line pressure reading.
4. Subtract the liquid line temperature from the satura­tion temperature (according to the chart) to determine subcooling.
_____ ° Saturation Temperature °F
_____ ° Liquid Line Temperature °F
=
_____ ° Subcooling Value °F
5. Compare the subcooling value with those shown in Table 6. If subcooling is greater than shown, recover some refrigerant. If subcooling is less than shown, add some refrigerant.
Charge Using Superheat Method (Fixed Orifice Sys­tems) – Outdoor Temperatures 65°F or Above
1. With the manifold gauge hose still on the liquid service port and the unit operating stably, use a digital thermometer to record the liquid line temperature. For
1. With the manifold gauge hose on the suction service port and the unit operating stably, use a digital ther­mometer to record the suction line temperature.
best results, use the same digital thermometer to
2. At the same time, record the suction line pressure reading.
Page 12 # 48306B006
Page 13
Subcooling Values for
Fixed Orifice or TXV Systems
roodtuO
.pmeT
F°
5631514131315141
57 01 31 21 01 01 31 21
588111188 1111
59 7 9 01 7 7 9 01
501 6896689
511 3 5 6 3 3 5 6
81- 42- 03- 63- 24- 84- 06-
)F°1±(gniloocbuSdiuqiL
Table 6
Superheat Values for
Fixed Orifice Systems
(80°DB/67°WB Return Air)
.pmeTtneibmAroodtuO
F°
0683
56 53
0703
57 62
0822
58 81
0921
59 8
taehrepuS
3. Use a temperature/pressure chart for HCFC-22 to determine the saturation temperature for the suction line pressure reading.
4. Subtract the saturation temperature (according to the chart) from the suction line temperature to determine the superheat.
_____ ° Suction Line Temperature °F
_____ ° Saturation Temperature °F
=
_____ ° Superheat Value °F
5. Compare the superheat value with those shown in Table 7. If superheat is greater than shown, add some refrigerant. If superheat is less than shown, recover some refrigerant.
Charge Using Approach Method (TXV Systems) – Outdoor Temperatures 65°F or Above
The following procedure is intended as a general guide and is for use on expansion valve systems only. For best results, indoor temperature should 70°F to 80°F. Monitor system pressures while charging.
0015
501 0
Table 7
Pressures higher than those listed indicate that the system is overcharged. Pressures lower than those listed indicate that the system is undercharged. Verify adjusted charge using the approach method.
4. Use the same digital thermometer used to check outdoor ambient temperature in Step 1 to check liquid line temperature. Verify the unit charge using the approach method.
5. Subtract the outdoor ambient temperature from the liquid line temperature to determine the approach temperature.
_____ ° Liquid Line Temperature °F
_____ ° Outdoor Ambient Temperature °F
=
_____ ° Approach Temperature °F
1. Record outdoor ambient temperature using a digital thermometer.
2. Attach high pressure gauge set and operate unit for several minutes to allow system pressures to stabilize.
3. Compare stabilized pressures with those provided in Table 8 on page 14. Minor variations in these pres­sures may be expected due to differences in installa­tions. Significant differences could mean that the
system is not properly charged or that a problem exists with some component in the system.
# 48306B006 Page 13
6. Compare the approach value with those shown in Table 9 on page 14. If the values to do not agree with those provided in Table 9, add refrigerant to lower the approach temperature or recover refrigerant from the system to increase the approach temperature.
Check Charge Using Normal Operating Pressures
Use Table 8 on page 14 to perform maintenance checks. Table 8 is not a procedure for charging the system. Minor variations in these pressures may be due to differences in installations. Significant deviations could mean that the
Page 14
Normal Operating Pressures
gnilooC
lioCroodtuO
riAgniretnE
F°.pmeT
5614118841086418745187931767418764176
57 361 28 671 28 171 97 081 88 361 47 371 97 071 47
5819148602381020801299191183020899118
59 222 58 042 48 332 18 642 901 022 48 632 18 032 48
5016527877268172187729116525837238
511 692 98 223 78 313 38 813 031 492 78 513 48 603 78
81- 42- 03- 63- 24- 84- 06-
L S L S L S L S L S L S L S
662
gnitaeH
lioCroodtuO
riAgniretnE
F°.pmeT
0529146581068918569185402952129541206
04 081 35 671 05 881 74 581 74 591 94 591 04 202 05
0327134561945715367173481939819319104
02 461 43 261 13 361 62 071 03 871 23 971 13 181 33
81- 42- 03- 63- 24- 84- 06-
L S L S L S L S L S L S L S
L – Liquid S – Suction
Values provided above are typical pressures. Indoor unit matchup, indoor air quality, and indoor load will cause pressures to vary.
58
system is not properly charged or that a problem exists with some component in the system.
Table 8
Approach Values for TXV Systems
ledoM 81- 42- 03- 63- 24- 84- 06-
.pmeT
789 11787
F°
Approach value is the liquid line temperature minus the outdoor ambient temperature (±1°F).
NOTE: For best results, use the same digital thermometer to check both outdoor ambient and liquid temperatures.
Table 9
Page 14 # 48306B006
Page 15
OPERATION
Outdoor unit and indoor blower cycle on demand from the room thermostat. When the thermostat blower switch is moved to the ON position, the indoor blower operates continuously.
Emergency heat is usually used during an outdoor shut­down, but it should also be used following a power outage if power has been off for over an hour and the outdoor temperature is below 50°F. System should be left in the emergency heat mode at least 6 hours to allow the crank­case heater sufficient time to prevent compressor slugging.
Filter Drier
The unit is equipped with a bi-flow filter, If replacement is necessary, replace with one of similar design.
Crankcase Heater
If unit is equipped with a crankcase heater, it should be energized 24 hours before unit start-up to prevent compressor damage as a result of slugging.
Emergency Heat Function (Room Thermostat)
An emergency heat function is designed into some room thermostats. This feature is applicable when isolation of outdoor unit is required or when auxiliary electric heat is stage by outdoor thermostats. When the room thermostat is placed in the emergency heat position, the outdoor unit control circuit is isolated from power and the field-supplied relays bypass the outdoor thermostats. An amber indicating light simultaneously comes on to remind the homeowner that the unit is operating in the emergency heat mode.
Defrost System
The defrost system includes two components: the defrost thermostat and the defrost control.
Defrost Thermostat
The defrost thermostat is located on the liquid line be­tween the check/expansion valve and the distributor. When the defrost thermostat senses 42°F or cooler, the thermostat contacts close and send a signal to the defrost control board to start the defrost timing. It also terminates defrost when the liquid line warms up to 70°F.
Defrost Control
The defrost control board includes the combined functions of time/temperature defrost control, defrost relay, diagnos­tic LEDs and terminal strip for field wiring connections (see Figure 13).
Defrost Interval
Timing Pins
Test Pins
Compressor Delay Pins
Reversing Valve
S87
Low Pressure Switch
Defrost Thermostat
High Pressure Switch
Defrost Control Board
P1
30
P5
O-OUT
LO-PS
DF
Y1-OUT
HI-PS
(optional)
60 90
TEST
U1
K3 Relay
C2
K1 Relay
U2
C5
TST PS DF C R O Y1
FAN
K2 Relay
L
24V
P6
P2
DS1
DS2
W1
C
L
R
O
Y1
Diagnostic LEDs
24V TerminalStrip Connections
# 48306B006 Page 15
Figure 13
Page 16
The control provides automatic switching from normal heating operation to defrost mode and back. During the compressor cycle (call for defrost), the control accumu­lates compressor run time at 30, 60, 90 minute field­adjustable intervals. If the defrost thermostat is closed when the selected compressor run time interval ends, the defrost relay is energized and the defrost begins.
Defrost Control Timing Pins
Each timing pin selection provides a different accumulated compressor run time period during one thermostat run cycle. This time period must occur before a defrost cycle is initiated. The defrost interval can be adjusted to 30 (T1), 60 (T2), or 90 (T3) minutes. The defrost timing jumper is factory installed to provide a 60-minute defrost interval. If the timing selector jumper is not in place, the control defaults to a 90-minute defrost interval. The maximum defrost period is 14 minutes and cannot be adjusted.
A test option is provided for troubleshooting. The test mode may be started any time the unit is in the heating mode and the defrost thermostat is closed or jumpered. If the jumper is in the TEST position at power up, the control will ignore the test pins. When the jumper is placed across the TEST pins for 2 seconds, the control will enter the defrost mode. If the jumper is removed before an additional 5-second period has elapsed (7 seconds total), the unit will remain in defrost mode until the defrost thermostat opens or 14 minutes have passed. If the jumper is not removed until after the additional 5-second period has elapsed, the defrost will terminate and the test option will not function again until the jumper is removed and reapplied.
During a single demand cycle, the defrost control will lock out the unit after the fifth time that the circuit is interrupted by any pressure switch wired to the control board. In addition, the diagnostic LEDs will indicate a locked-out pressure switch after the fifth occurrence of an open pres­sure switch (see Table 10). The unit will remain locked out until power to the board is interrupted, then re-established, or until the jumper is applied to the TEST pins for 0.5 seconds.
NOTE: The defrost control board ignores input from the low pressure switch terminals as follows:
During the TEST mode
During the defrost cycle
During the 90-second start-up period
For the first 90 seconds each time the reversing valve switches heat/cool modes
If the TEST pins are jumpered and the 5-minute delay is being bypassed, the LO PS terminal signal is not ignored during the 90-second start-up period.
Diagnostic LEDs
The defrost board uses two LEDs for diagnostics. The LEDs flash a specific sequence according to the condition as shown in Table 10.
Compressor Delay
The defrost board has a field-selectable function to reduce occasional sounds that may occur while the unit is cycling in and out of the defrost mode. The compressor will be cycled off for 30 seconds going in and out of the defrost mode when the compressor delay jumper is removed.
NOTE: The 30-second “off” cycle is not functional when jumpering the TEST pins.
Time Delay
The timed-off delay is 5 minutes long. The delay helps to protect the compressor from short cycling in case the power to the unit is interrupted or a pressure switch opens. The delay is bypassed by placing the timer select jumper across the TEST pins for 0.5 seconds.
Pressure Switch Circuit
The defrost control includes a low pressure (loss of charge pressure) switch. A high pressure switch (optional) can be connected to the board’s HI PS terminals (see Figure 13 on page 15).
Page 16 # 48306B006
Page 17
Defrost Control Board
Diagnostic LEDs
edoM
rewoPoN
draoBot
DELneerG
)2SD(
ffOffO
MAINTENANCE
WARNING
Before performing maintenance operations on
DELdeR
)1SD(
system, turn the electric power to unit OFF at disconnect switch(es). Unit may have multiple power supplies. Electrical shock could cause personal injury or death.
draoBotrewoP
tuokcoL
erusserPwoL
tluaFhctiwS
erusserPwoL
erusserPhgiH
tluaFhctiwS
erusserPhgiH
/noitarepOlamroN
elcyCtrohS-itnA
tuokcoLhctiwS
tuokcoLhctiwS
Table 10
ffO hsalFwolS
ffOnO
hsalFwolS ffO
nOffO
hsalFwolSsuoenatlumiS
hsalFwolSgnitanretlA
Before the start of each heating and cooling season, the following service checks should be performed by a qualified service technician.
Inspect and clean outdoor and indoor coils. The outdoor coil may be flushed with a water hose.
NOTE: It may be necessary to flush the outdoor coil more frequently if it is exposed to substances which are corrosive or which block airflow across the coil (such as pet urine, cottonwood seeds, etc...).
Visually inspect the refrigerant lines and coils for leaks.
Check wiring for loose connections.
Check voltage at the indoor and outdoor units (with units operating).
Check amperage draw at the outdoor fan motor, compressor, and indoor blower motor. Values should be compared with those given on unit nameplate.
Check, clean (or replace) indoor unit filters.
# 48306B006 Page 17
Check the refrigerant charge and gauge the system pressures.
Check the condensate drain line for free and unob­structed flow. Clean drain line, if necessary.
Adjust blower speed for cooling. Measure the pressure drop over the coil to determine the correct blower CFM.
Belt drive blowers: Check drive belt for wear and proper tensions.
If insufficient cooling is reported, the unit should be gauged and refrigerant charge checked (see Refrigerant Charging on page 11).
Page 18
HOMEOWNER INFORMATION
In order to ensure peak performance, your system must be properly maintained. Clogged filters and blocked airflow prevent your unit from operating at its most efficient level.
WARNING
Turn all electric power to unit OFF at discon­nect switch(es) before performing any mainte­nance operations on system. Unit may have multiple power supplies. Electrical shock could cause personal injury or death.
Ask your dealer to show you where the indoor unit’s filter is located. It will be either at the indoor unit (installed internal or external to the cabinet) or behind a return air grille in the wall or ceiling. Check the filter monthly and clean or replace it as needed.
which block airflow across the coil (such as pet urine, cottonwood seeds, etc...).
Heat Pump Operation
Heat pump units have several characteristics you should be aware of:
Heat pumps satisfy heating demand by delivering large amounts of warm air into the living space. This is quite different from gas-fired, oil-fired, or electric furnaces which deliver lower volumes of considerably hotter air to heat the space.
Do not be alarmed if you notice frost on the outdoor coil in the winter months. Frost develops on the outdoor coil during the heating cycle when tempera­tures are below 45°F. An electronic control activates a defrost cycle lasting 5 to 15 minutes at preset inter­vals to clear the outdoor coil of the frost. A shift in sound type does occur during the defrost mode.
Disposable filters should be replaced with a filter of the same type and size. If you unsure of the filter you need for your system, contact your dealer.
Many indoor units are equipped with reusable foam filters. These filters can be cleaned with a mild soap and water solution. Rinse the filter thoroughly and let dry completely before returning to unit or grille.
The filter and all access panels must be in place any time the unit is in operation.
Some systems are equipped with an electronic air cleaner, designed to remove the majority of airborne particles from the air passing through the cleaner. If your system includes an electronic air cleaner, ask your dealer for maintenance instructions.
Inspect and clean indoor coil. The indoor evaporator coil is equipped with a drain pan to collect condensate formed as the system removes humidity from the inside air. Have your dealer show you the location of the drain line and how to check for obstructions. This also applies to an auxiliary drain, if one is installed.
Inspect and clean outdoor coil: Make sure no obstruc­tions restrict airflow to the outdoor unit. Leaves, trash, or shrubs crowding the unit can cause it to work harder and use more energy. Keep shrubbery trimmed away from the unit and periodically check for debris which collects around the unit.
The outdoor coil may require frequent cleaning, depending on environmental conditions. Clean the outdoor coil with a nonpressurized water hose to remove surface contaminants and debris. It may be necessary to flush the outdoor coil more frequently if it is exposed to substances which are corrosive or
During the defrost cycle, you may notice steam rising from the unit. This is a normal occurrence. The thermostat may engage auxiliary heat during the defrost cycle to satisfy a heating demand. The unit will return to normal operation at the conclusion of the defrost cycle.
In case of extended power outage...
If the outdoor temperature is below 50°F and power to the outdoor unit has been interrupted for 6 hours or longer, observe the following when restoring power to the heat pump system.
Set the room thermostat selector to the “Emergency Heat” setting to obtain temporary heat for a minimum of 6 hours. This will allow system refrigerant pres­sures and temperatures enough time to return to a stabilized condition.
In the Emergency Heat mode, all heating demand is satisfied by auxiliary heat; heat pump operation is locked out. After a 6-hour “warmup” period, the thermostat can then be switched to the “Heat” setting and normal heat operation may resume.
Thermostat Operation
Though your thermostat may vary somewhat from the description below, its operation will be similar.
Temperature Setting Levers
Most heat pump thermostats have two temperature selector levers: one for heating and one for cooling. Set the levers or dials to the desired temperature setpoints for both heating and cooling. Avoid frequent temperature
Page 18 # 48306B006
Page 19
adjustment; turning the unit off and back on before pressures equalize puts stress on unit compressor.
Fan Switch
Preservice Check
If your system fails to operate, check the following before calling for service:
In AUTO or INT (intermittent) mode, the blower operates only when the thermostat calls for heating or cooling. This mode is generally preferred when humidity control is a priority. The ON or CONT mode provides continuous indoor blower operation, regardless of whether the compressor or auxiliary heat are operating. This mode is required when constant air circulation or filtering is desired.
System Switch
Set the system switch for heating, cooling, or auto opera­tion. The auto mode allows the heat pump to automatically switch from heating mode to cooling mode to maintain predetermined comfort settings. Many heat pump thermo­stats are also equipped with an emergency heat mode which locks out heat pump operation and provides temporary heat supplied by the auxiliary heat.
Indicating Light
Most heat pump thermostats have an amber light which indicates when the heat pump is operating in the emer­gency heat mode.
Temperature Indicator
Check to see that all electrical disconnect switches
are ON.
Make sure the thermostat temperature selector is
properly set.
Make sure the thermostat system switch is properly set.
Replace any blown fuses, or reset circuit breakers.
Make sure unit access panels are in place.
Make sure air filter is clean.
Locate unit model number and have it handy before
calling.
The temperature indicator displays the actual room temperature.
Programmable Thermostats
Your system may be controlled by a programmable thermo­stat. These thermostats provide the added feature of programmable time-of-day setpoints for both heating and cooling. Refer to the user’s information manual provided with your particular thermostat for operation details.
# 48306B006 Page 19
Page 20
Start-Up and Performance Checklist
Job Name _______________________________ Job No. ________________ Date ______________
Job Location _____________________________ City ___________________ State ______________
Installer _________________________________ City ___________________ State ______________
Unit Model No.______________ Serial No. ___________________
Service Technician ________________________________________ Nameplate Voltage ______________
Rated Load Ampacity ________ Compressor Amperage ____________ Outdoor Fan ______________
Maximum Fuse or Circuit Breaker ________________________
Electrical Connections Tight? Indoor Filter Clean? Supply Voltage (Unit Off) ________________
Indoor Blower RPM _____________ S.P. Drop Over Indoor (Dry) ____________
Outdoor Coil Entering Air Temperature _____________ Voltage with Compressor Operating _____________
Outdoor Fan Checked?
Cooling
Liquid Line Pressure __________ Suction Line Pressure ___________ Refrigerant Charge Checked?
Heating
Liquid Line Pressure __________ Suction Line Pressure ___________ Refrigerant Charge Checked?
Refrigerant Lines: Leak Checked? Properly Insulated?
Service Valves: Fully Opened? Caps Tight?
Thermostat: Calibrated? Properly Set? Level?
Sequence of Operation
Heating Correct? Cooling Correct?
Page 20 # 48306B006
Page 21
OUTDOOR
FAN
RED
R
SC
COMPRESSOR
CRANKCASE HEATER
GROUND
L1
1
208-230/60/1
L2
HR1
EQUIPMENT
GROUND
PURPLE
BLACK
ORANGE
YELLOW
BLACK
COMPRESSOR
CONTACTOR
LUG
S40
DEFROST
THERMOSTAT
S40
K1-1
BLACK
YELLOW
H
RED
C
C12
DUAL
CAPACITOR
C
F
RED
REVERSING
VALV E
S
C
RED
BLACK
ORANGE
FAN
CMC1
F
PURPLE
H
BLACK
R
BLACK
B4
B1
L1
S6
K1
DEFROST
CONTROL
FAN
O-OUT
2
LO-PS
DF
COMMON
Y1 OUT
HI-PS
2
BLUE
208-230/60/1
CMC1
FAN
O-OUT
LO-PS
DF
COMMON
Y1 OUT
HI-PS
BLUE
S87 LOW PRESSURE SWITCH
W1
C
L
R
O
Y1
L2
L1
GROUND
W1
C
2
L R O
Y1
2
LO-PS
1
S4 HIGH PRESSURE SWITCH
THERMOSTAT
W1OY1
R
C
THERMOSTAT
W1
Y1
R
O
C
HI-PS
LINE VOLTAGE FACTORY INSTALLED LINE VOLTAGE FIELD INSTALLED
24 VOLT FACTORY INSTALLED CLASS II VOLTAGE FIELD INSTALLED
NOTE: DO NOT CONNECT C (COMMON) CONNECTION BETWEEN THE INDOOR
UNIT AND THERMOSTAT EXCEPT WHEN REQUIRED BY THE INDOOR THERMOSTAT. REFER TO THERMOSTAT INSTALLATION INSTRUCTIONS. C (COMMON) CONNECTION BETWEEN INDOOR UNIT AND OUTDOOR UNIT REQUIRED FOR PROPER OPERATION.
WARNING-­ELECTRIC SHOCK HAZARD, CAN CAUSE INJURY OR DEATH. UNIT MUST
BE GROUNDED IN ACCORDANCE WITH NATIONAL AND LOCAL CODES.
FOR USE WITH COPPER CONDUCTORS ONLY. REFER TO UNIT
1
RATING PLATE FOR MINIMUM CIRCUIT AMPACITY AND MAXIMUM OVERCURRENT PROTECTION SIZE.
2
CONNECTION MUST BE JUMPERED WHEN OPTIONAL SWITCH IS NOT USED.
Single Phase Wiring Diagram P/N 46330-002
# 48306B006 Page 21
Figure 14
DESCRIPTION
KEY COMPONENT
B1 COMPRESSOR
B4
MOTOR - OUTDOOR FAN
C12 CAPACITOR - DUAL
CMC1 CONTROL-DEFROST
HR1 HEATER - COMPRESSOR K1-1 CONTACTOR - COMPRESSOR
L1 VALVE - REVERSING S4 SWITCH - HIGH PRESSURE
S6 SWITCH - DEFROST S40 THERMOSTAT - CRANKCASE S87 SWITCH - LOW PRESSURE
Page 22
OUTDOOR FAN
RED
RELAY
25
7
OUTDOOR
FAN
OUTDOOR FAN
CAPACITOR
PURPLE
BLACK
ORANGE
BLACK
COMPRESSOR
CRANKCASE HEATER
BLACK
BLACK
COMPRESSOR
CONTACTOR
BLACK
T2
T3
L3L2L1
BLACK
T1
GROUND
LUG
S40
REVERSING
VALV E
208-230/60/3
L1
L2
1
L3
K1-1
BLACK
BLACK
BLACK
ORANGE
EQUIPMENT
GROUND
HR1
S40
C1
RED
2
BLACK
PURPLE
LINE VOLTAGE FACTORY INSTALLED
LINE VOLTAGE FIELD INSTALLED
24 VOLT FACTORY INSTALLED
CLASS II VOLTAGE FIELD INSTALLED
NOTE: DO NOT CONNECT C (COMMON) CONNECTION BETWEEN THE INDOOR
UNIT AND THERMOSTAT EXCEPT WHEN REQUIRED BY THE INDOOR THERMOSTAT. REFER TO THERMOSTAT INSTALLATION INSTRUCTIONS. C (COMMON) CONNECTION BETWEEN INDOOR UNIT AND OUTDOOR UNIT REQUIRED FOR PROPER OPERATION.
FOR USE WITH COPPER CONDUCTORS ONLY. REFER TO UNIT
1
RATING PLATE FOR MINIMUM CIRCUIT AMPACITY AND MAXIMUM OVERCURRENT PROTECTION SIZE.
CONNECTION MUST BE JUMPERED WHEN OPTIONAL SWITCH IS
2
NOT USED.
WARNING-­ELECTRIC SHOCK HAZARD, CAN CAUSE INJURY OR DEATH. UNIT MUST
BE GROUNDED IN ACCORDANCE WITH NATIONAL AND LOCAL CODES.
BLACK
DEFROST CONTROL
FAN
O-OUT
LO-PS
DF COMMON Y1 OUT
HI-PS
BLUE
W1
C
2
L
R O
Y1
2
208-230/60/3
L1
L2
THERMOST
1
L3
GROUND
THERMOSTAT
C L
R
O
Y1
S4 HIGH PRESSURE SWITCH
B4
CMC1
FAN
B1
7
K10-1
5
S6
K1
L1
O-OUT
LO-PS
COMMON
Y1 OUT
HI-PS
BLUE
W1
2
DF
2
LO-PS
S87 LOW PRESSURE SWITCH
DESCRIPTION
KEY COMPONENT
B1 COMPRESSOR B4
MOTOR - OUTDOOR FAN
C1 CAPACITOR - OUTDOOR FAN
CMC1 CONTROL-DEFROST
HR1 HEATER - COMPRESSOR
K1-1 CONTACTOR - COMPRESSOR
K10-1 RELAY - OUTDOOR FAN
L1 VALVE - REVERSING S4 SWITCH - HIGH PRESSURE
S6 SWITCH - DEFROST S40 THERMOSTAT - CRANKCASE S87 SWITCH - LOW PRESSURE
CRW1O
W1
R
C
HI-PS
Y1
Y1
O
Three Phase Wiring Diagram P/N 48437-001
Figure 15
Page 22 # 48306B006
Page 23
Limited Warranty
August 1, 1997
This warranty gives you specific legal rights and you may have other rights
which vary from state/province to state/province.
Warrantor: Armstrong Air Conditioning Inc., 421 Monroe St., Bellevue, OH 44811
Armstrong Air Conditioning Inc. products are available under the following names: Air Ease, Armstrong Air, American Aire, Concord
Subject to the limitations stated in this warranty, we warrant to the first buyer for use the residential heating, cooling or heat pump unit, when installed, operated and maintained as required by this warranty, to be free of defects in workmanship or material for a period of 5 years in residential installations (1 year in non-residential installations) from the time of installation. We will replace any defective component without cost or expense to you except for the costs of delivery and labor for removal and replacement of the defective component.
The 2SHP13LB Series heat pumps carry a 5-year compressor warranty. The 2SHP13LE Series heat pumps carry a 10-year compressor warranty.
Warranty Begins
The warranty period begins when the installation is complete and the product is ready to operate. You must be able to verify this date whenever a warranty claim is made. Original bill of sale, installer’s invoice or other similar document will suffice. If the beginning date cannot be verified, we will consider warranty coverage to begin 6 months after the date the product was shipped from our factory.
Limitations on Implied Warranties
Implied warranties of merchantability or, to the extent applicable, fitness for a particular purpose are limited to 5 years, the same duration as the basic limited written warranty provided herein. Some states/provinces do not allow limitations on how long an implied warranty of merchantability or fitness lasts, so the above limitations or exclusions may not apply to you.
Only Warranty
This written Limited Warranty is the only warranty made by the warrantor; this warranty is in lieu of and excludes all other warranties, express or implied. The warrantor does not authorize any person to provide any other warranty or to assume for it any further obligation in connection with the warranted product.
What is NOT Covered
1. Cabinets or cabinet pieces.
2. Normal maintenance items such as filters, fan belts, fuses or other consumable items.
3. Damage caused by misuse, failure to maintain properly, accidents or acts of God.
4. External wiring, piping, venting or attachment of accessory products not integral to our product, including without limitation, humidifier, air cleaner, vent damper, thermostat or other mechanical devices not manufactured by the warrantor.
5. Products that have been operated in a corrosive atmosphere where a concentration of acids, halogenated hydrocarbons or other corrosive elements causes deterioration to metal surfaces or integral components. NOTE: Operation in a corrosive atmosphere is considered abuse and voids this warranty.
6. Products that have NOT been installed in accordance with our published installation instructions, applicable local, state/ provincial or national codes, ACCA published standards.
7. Products that have NOT been installed by competent, qualified installers.
8. Products that have been moved from their original place of installation.
Warranty on Replacement Components
Any replacement component furnished by us will assume the remaining (unused) portion of the Limited Warranty.
Consequential Damages
The warrantor shall not be responsible for any consequential damages caused by any defect in the product. Some state/provinces do not allow the exclusion or limitations of incidental or consequential damages, so the above limitation or exclusion may not apply to you.
This product must be installed, used and cared for in accordance with the instruction manual. You are responsible for required periodic maintenance or service, such as changing or cleaning of air filters and lubrication or cleaning of components. Failure to properly install, operate or maintain your unit voids this warranty.
# 48306B006 Page 23
Loading...