These instructions must be read and understood completely before attempting installation.
NOTICE TO INSTALLER
This unit is factory-charged with DRY NITROGEN. The unit is intended for installation
in existing HCFC-22 systems. Carefully follow all installation procedures.
WARNING
The equipment covered in this manual is to be installed by trained and experienced
service and installation technicians. Improper installation, modification, service, or use
can cause electrical shock, fire, explosion, or other conditions which may cause personal
injury, death, or property damage. Use appropriate safety gear including safety glasses
and gloves when installing this equipment.
WARNING
Risk of electrical shock. Disconnect all remote power
supplies before installing or servicing any portion of
the system. Failure to disconnect power supplies can
result in property damage, personal injury, or death.
WARNING
Installation and servicing of air conditioning equipment
can be hazardous due to internal refrigerant pressure
and live electrical components. Only trained and
qualified service personnel should install or service
this equipment. Installation and service performed by
unqualified persons can result in property damage,
personal injury, or death.
WARNING
Sharp metal edges can cause injury. When installing
the unit, use care to avoid sharp edges.
The 2SCU13 air conditioner, which will also be referred to
in this instruction as the outdoor unit, uses HCFC-22
refrigerant. This outdoor unit is intended as a replacement
outdoor component for use in residential systems which
include an existing indoor coil which is functioning properly.
It is NOT intended for new installations.
This outdoor unit is:
•shipped from the factory with nitrogen holding charge
that must be purged from the unit;
•designed for use with HCFC-22 refrigerant only;
•designed for use in systems that use either a RFC
device (orifice) included with outdoor unit or thermal
expansion valve (TXV). See the 2SCU13 product
specification sheet for approved fixed orifice sizes and
expansion valve kit match ups.
IMPORTANT: The air conditioning unit must have properly
matched system components including indoor unit and
refrigerant metering device. Mismatched equipment may
have an impact on the operation, performance, reliability,
and warranty of the air conditioning unit.
Upon receipt of equipment, carefully inspect it for possible
shipping damage. If damage is found, it should be noted on
the carrier’s freight bill. Take special care to examine the
unit inside the carton if the carton is damaged. Any
concealed damage discovered should be reported to the
last carrier immediately, preferably in writing, and should
include a request for inspection by the carrier’s agent.
If any damages are discovered and reported to the carrier
DO NOT INSTALL THE UNIT, as claim may be denied.
Check the unit rating plate to confirm specifications are
as ordered.
Location of Unit
Outdoor units operate under a wide range of weather
conditions; therefore, multiple factors must be considered
when positioning the unit. The unit must be positioned to
give adequate clearances for sufficient airflow and servicing.
Refer to Figure 1 for installation clearances.
Installation Clearances
Read this entire instruction manual, as well as the
instructions supplied in separate equipment, before
starting the installation. Observe and follow all
warnings, cautions, instructional labels, and tags.
Failure to comply with these instructions could result
in an unsafe condition and/or premature component
failure.
These instructions are intended as a general guide only for
use by qualified personnel and do not supersede any national
or local codes in any way. The installation must comply with
all provincial, state, and local codes as well as the National
Electrical Code (U.S.) or Canadian Electrical Code (Canada).
Compliance should be determined prior to installation.
When servicing or repairing HVAC components, ensure the
fasteners are appropriately tightened. Table 1 shows torque
values for fasteners.
Inspection of Shipment
Torque Table
* A service clearance of 30" must be maintained on one of the sides adjacent
to the control box. Clearance to one of the other three sides must be 36".
Clearance to one of the remaining two sides may be 12" and the final side
may be 6".
A clearance of 24" must be maintained between units.
48" clearance required on top of unit. Maximum soffit overhang is 36".
Figure 1
Slab Mounting
When installing unit at grade level, install on level slab high
enough so that water from higher ground will not collect
around unit (see Figure 2).
Page 2 of 19506874-01Issue 1140
Table 1
Roof Mounting
Install unit at a minimum of 4" above surface of the roof.
Care must be taken to ensure weight of unit is properly
distributed over roof joists and rafters. Either redwood or
steel supports are recommended.
Page 3
Slab Mounting
Discharge Air
Mounting Slab
Ground Level
Building
Structure
Power
Indoor Unit
Thermostat
Outdoor
Unit
Y1 Outdoor Unit
Heat
Cooling
Indoor Blower
R
W1
Y
G
C
R
W
Y
G
C
C Outdoor Unit
Figure 2
Thermostat Designations
See unit wiring diagram for power supply connections.
If the indoor unit is not equipped with a blower relay, one must be field supplied
and installed.
Do not connect C (common) connection between indoor unit and thermostat
except when required by the indoor thermostat. Refer to thermostat installation
instructions. C (common) connection between indoor unit and outdoor unit
required for proper operation.
Electrical Wiring
All field wiring must be done in accordance with the National
Electrical Code (NEC) recommendations, Canadian
Electrical Code (CEC) and CSA Standards, or local codes,
where applicable.
WARNING
Unit must be grounded in accordance with national and local
codes. Failure to ground unit properly can result in personal
injury or death.
Refer to the furnace or blower coil Installation Instructions
for additional wiring application diagrams and refer to unit
rating plate for minimum circuit ampacity and maximum
overcurrent protection size.
1.Install line voltage power supply to unit from a properly
sized disconnect switch. Any excess high voltage field
wiring should be trimmed or secured away from the low
voltage field wiring.
2.Ground unit at unit disconnect switch or to an earth ground.
To facilitate conduit, a hole is in the bottom of the control
box. Connect conduit to the control box using a proper
conduit fitting. Units are approved for use only with copper
conductors. 24V Class II circuit connections are made to
the low voltage pigtails. A complete unit wiring diagram is
located inside the unit control box cover (see also pages
16 and 17 of this instruction).
Figure 3
5.Do not bundle any excess 24V control wire inside control
box. Run control wire through installed wire tie and tighten
wire tie to provide low voltage strain relief and to maintain
separation of field-installed low and high voltage circuits.
Refrigerant Piping
WARNING
Refrigerant can be harmful if inhaled. Refrigerant must always
be used and recovered responsibly. Incorrect or irresponsible
use of refrigerant can result in personal injury or death.
Field refrigerant piping consists of liquid and suction lines
from the outdoor unit (sweat connections) to the indoor coil
(flare or sweat connections).
Select line set diameters from Table 2 on page 4 to ensure
that oil returns to the compressor. Size vertical suction riser
to maintain minimum velocity at minimum capacity.
Recommended line length is 50' or less. If more than 50'
line set is required, contact Technical Services at (800) 515-
3501.
Table 2 shows the diameters for line sets up to 100' although
vertical lift applications and trapping requirements need to
be reviewed with Technical Services for line sets over 50'.
3.Install room thermostat on an inside wall that is not subject
to drafts, direct sunshine, or other heat sources.
4.Install low voltage wiring from outdoor to indoor unit and
from thermostat to indoor unit (see Figure 3).
506874-01Page 3 of 19Issue 1140
Installing Refrigerant Line
During the installation of an air conditioning system, it is
important to properly isolate the refrigerant line to prevent
unnecessary vibration. Line set contact with the structure
(wall, ceiling, or floor) may cause objectionable noise when
vibration is translated into sound. As a result, more energy
Page 4
Refrigerant Line Set Diameters (in.)
S uc tio n L ine
B T U H
L ine S e t L e ngth a nd S iz e
12 f t.25 ft.5 0 ft.75 ft. 10 0 ft.
18,0003/43/43/43/43/4
24,0003/43/43/43/47/8
30,0003/43/43/47/87/8
36,0007/87/87/87/81-1/8
42,0007/87/87/81-1/81-1/8
48,0007/87/87/81-1/81-1/8
60,000 1-1/81-1/81-1/81-1/81-1/8
L iquid L ine
B T U H
L ine S et L ength a nd S iz e
12 f t.25 ft.5 0 ft.75 f t.100 ft.
18,0003/83/83/83/83/8
24,0003/83/83/83/83/8
30,0003/83/83/83/81/2
36,0003/83/83/83/81/2
42,0003/83/83/81/21/2
48,0003/83/83/81/21/2
60,0003/83/83/81/21/2
Install unit away
from windows
Two 90° elbows installed in lineset
will reduce lineset vibration
Outside Unit Placement
and Installation
Figure 4
Line Set Isolation
Illustrations on the following pages demonstrate procedures
which ensure proper refrigerant line set isolation. Figure 5
shows how to install line sets on horizontal runs. Figure 6
shows how to make a transition from horizontal to vertical.
Figure 7 on page 6 shows how to install line sets on vertical
runs.
For installations exceeding 50', contact
Technical Services at (800) 515-3501.
Table 2
or vibration can be expected. Close attention to line set
isolation must be observed.
Following are some points to consider when placing and
installing a high-efficiency outdoor unit:
Placement
Be aware that some localities are adopting sound ordinances
based on how noisy the unit is at the neighbor’s home, not at
the original installation. Install the unit as far as possible from
the property line. When possible, do not install the unit directly
outside a bedroom window. Glass has a very high level of
sound transmission. Figure 4 shows how to place the outdoor
unit and line set to reduce line set vibration.
Page 4 of 19506874-01Issue 1140
Brazing Connection Procedure
1.Cut ends of refrigerant lines square (free from nicks or
dents). Debur the ends. The pipe must remain round;
do not pinch end of line.
2.Before making line set connections, use dry nitrogen to purge
the refrigerant piping. This will help to prevent oxidation and
the introduction of moisture into the system.
3.Use silver alloy brazing rods (5% or 6% silver alloy for
copper-to-copper brazing or 45% silver alloy for copperto-brass or copper-to-steel brazing) which are rated for
use with HCFC-22 refrigerant.
4.Remove the Schrader core assemblies before brazing
to protect them from damage due to extreme heat.
Replace the cores when brazing is complete.
5.Wrap a wet cloth around the valve body and copper tube
stub to protect them from heat damage during brazing.
6.Braze the line set to the service valve. Quench the joints
with water or a wet cloth to prevent heat damage to the
valve core and opening port. The tube end must stay
bottomed in the fitting during final assembly to ensure
proper seating, sealing, and rigidity.
Page 5
Anchored
Heavy Nylon
Wire Tie
Wall
Stud
Metal Sleeve
Vapor LineWrapped
in Armaflex
–
Liquid Line
Wall
Stud
Automotive
Muffler-Type
Hanger
Strap Liquid
Line to Vapor
Line
Metal Sleeve
Vapor LineWrapped
in Armaflex
–
Liquid Line
Strap Liquid
Line to Vapor
Line
To hang line set from joist or rafter,
use either metal strapping material
or anchored heavy nylon wire ties.
Strapping Material
(around vapor line only)
8’
8’
Tape or Wire Tie
Strap the vapor line to the joist or rafter
at 8 intervals then strap the liquid line
to the vapor line.
’
Floor Joist or
Roof Rafter
Metal Sleeve
Floor Joist or Roof Rafter
Tape or Wire Tie
Wire Tie
(around vapor line only)
Refrigerant Line Sets: Installing Horizontal Runs
Figure 5
Refrigerant Line Sets: Transition from Vertical to Horizontal
506874-01Page 5 of 19Issue 1140
Figure 6
Page 6
Model
Part
Number
Drill
Size
2SCU13- 18
2SCU13- 24
2SCU13- 30
2SCU13- 36
2SCU13- 42
2SCU13- 48
2SCU13- 60
100484-07
100484-12
100484-19
100484-24
100484-26
100484-36
100484-43
.055
.062
.070
.076
.078
.089
.096
Refrigerant Line Sets: Installing Vertical Runs (new construction shown)
Outside Wall
Wood Block
Between Studs
IMPORTANT: Refrigerant
lines must not contact wall.
Vapor Line
Liquid Line
Wire Tie
Inside Wall
Strap
Sleeve
Wire Tie
Wire Tie
Strap
Wood Block
Sleeve
Vapor Line Wrapped
with Armaflex
Liquid Line
Caulk
PVC Pipe
Fiberglass
Insulation
Outside Wall
IMPORTANT:
Refrigerant
lines must not
contact structure.
NOTE: Similar installation practices
should be used if line set is to be installed
on exterior of outside wall.
7.Install the factory-supplied fixed orifice (or thermal
expansion valve which is sold separately and which is
approved for use with HCFC-22 refrigerant) in the liquid
line at the indoor coil.
Refrigerant Metering Device
2SCU13 units are designed for use with either fixed orifice
or TXV systems. Refer to the appropriate following section
for information on installing the chosen refrigerant metering
device.
Fixed Orifice Systems
2SCU13 units are shipped with a fixed orifice refrigerant
metering device. See Table 3 for the proper fixed orifice
size for each unit. In nonstandard applications, the fixed
orifice provided with the indoor unit may not be appropriately
sized to be matched with the 2SCU13 unit. If necessary,
replace the existing indoor unit fixed orifice with the orifice
supplied with the 2SCU13 unit. Place the supplied fixed
orifice sticker on the indoor cabinet after installation.
Page 6 of 19506874-01Issue 1140
Figure 7
Fixed Orifice Data
Figure 8 shows how to install the replacement fixed orifice.
Do not twist distributor tubes when loosening the seal nut from
the orifice housing. Use wrench to back up the distributor.
Table 3
Page 7
Metering Device Installation
Model
Part
Number
2SCU13-18, -24, -30, -36
2SCU13-42, -48
2SCU13-60
A2TXV01
A2TXV02
H2TXV03
Figure 8
Expansion Valve Systems
Expansion valves equipped with Chatleff-type fittings are
available from the manufacturer. See Table 4 for proper TXV
for each unit.
4.Strap the superheat sensing bulb to the suction header.
If installing an expansion valve on an indoor coil that
previously used a fixed orifice, be sure to remove the existing
fixed orifice. Failure to remove a fixed orifice when installing
an expansion valve to the indoor coil will result in improper
operation and damage to the system.
Manifold Gauge Set
When checking the unit charge, use a manifold gauge set that
is equipped with “low loss” hoses. Do not use a manifold gauge
set with anything other than a “low loss” hose.
Liquid and Suction Line Service Valves
The liquid line and suction line service valves and service
ports are used for leak testing, evacuating, charging, and
checking charge.
Each valve is equipped with a service port which has a factoryinstalled Schrader valve (see Figure 9 on page 8). A service
port cap protects the Schrader valve from contamination and
serves as the primary leak seal.
To Access the Schrader Port:
TXV Data
Table 4
To install an expansion valve (see Figure 8):
1.Separate the distributor assembly and remove the piston
orifice and used teflon seal. Insert nozzle end of the
expansion valve along with a new teflon seal into the
distributor and tighten to 20 – 30 ft. lbs. Use backup wrench
on all wrench flats. Overtightening will crush the teflon
seal and may cause a leak.
2.Attach liquid line portion of distributor assembly along
with new teflon seal to the inlet of the expansion valve.
Tighten to 20 – 30 ft. lbs. Use backup wrench on all
wrench flats. Overtightening will crush the teflon seal
and may cause a leak.
3.Connect the external equalizer line to the equalizer port
on the suction line and tighten to 8 ft. lbs.
1.Remove the service port cap with an adjustable wrench.
2.Connect gauge to the service port.
3.When testing is completed, replace service port cap.
Tighten finger tight, then an additional 1/6 turn.
To Open Liquid or Suction Line Service Valve:
1.Remove stem cap with an adjustable wrench.
2.Use a service wrench with a hex-head extension to back
the stem out counterclockwise as far as it will go. Use
a 3/16" hex head extension for liquid line service valves
and a 5/16" extension for suction line service valves.
3.Replace the stem cap. Tighten finger tight, then tighten
an additional 1/6 turn.
To Close Liquid or Suction Line Service Valve:
1.Remove the stem cap with an adjustable wrench.
2.Use a service wrench with a hex-head extension to turn
the stem clockwise to seat the valve. Tighten firmly.
3.Replace the stem cap. Tighten finger tight, then tighten
an additional 1/6 turn.
506874-01Page 7 of 19Issue 1140
Page 8
Service Valve
Valve Closed
Ball Type Service Valve
(Valve Open)
Use adjustable wrench. To open, rotate stem counterclockwise 1/4 turn (90°). To close, rotate stem clockwise 1/4 turn
(90°).
Figure 10
Valve Open
Figure 9
Suction Line (Ball Type) Service Valve
Suction line (ball type) service valves function the same way
as the other valves; the difference is in the construction (see
Figure 10).
The ball valve is equipped with a service port with a factoryinstalled Schrader valve. A service port cap protects the
Schrader valve from contamination and serves as the
primary seal.
Leak Testing
After the line set has been connected to the indoor and
outdoor units, the line set connections and indoor unit must
be checked for leaks.
WARNING
Fire, Explosion, and Personal Safety Hazard.
Failure to follow this warning could result in damage,
personal injury, or death.
Never use oxygen to pressurize or purge refrigeration
lines. Oxygen, when exposed to a spark or open flame,
can cause damage by fire and/or an explosion, that could
result in personal injury or death.
Using an Electronic Leak Detector
1.Connect the high pressure hose of the manifold gauge
set to the suction valve service port. (Normally the high
pressure hose is connected to the liquid line port;
however, connecting it to the suction ports helps to
protect the manifold gauge set from damage caused by
high pressure.)
2.With both manifold valves closed, connect the cylinder
of HCFC-22 refrigerant. Open the valve on the HCFC22 cylinder (vapor only).
Page 8 of 19506874-01Issue 1140
Page 9
3.Open the high pressure side of the manifold to allow
HCFC-22 into the line set and indoor unit. Weigh in a
trace amount of HCFC-22. (A trace amount is a
maximum of 2 oz. of refrigerant or 3 lbs. pressure.)
Close the valve on the HCFC-22 cylinder and the valve
on the high pressure side of the manifold gauge set.
Disconnect the HCFC-22 cylinder.
4.Connect a cylinder of nitrogen with a pressure regulating
valve to the center port of the manifold gauge set. When
using high pressure gas such as nitrogen for this
purpose, be sure to use a regulator that can control
the pressure down to 1 or 2 psig.
5.Adjust nitrogen pressure to 150 psig. Open the valve
on the high side of the manifold gauge set to pressurize
the line set and the indoor coil.
Evacuation
Evacuating the system of noncondensables is critical for
proper operation of the unit. Noncondensables are defined
as any gas that will not condense under temperatures and
pressures present during operation of an air conditioning
system. Noncondensables and water vapor combine with
refrigerant to produce substances that corrode copper piping
and compressor parts.
Use a thermocouple or thermistor electronic vacuum gauge
that is calibrated in microns. Use an instrument that reads
down to 50 microns.
6.Evacuate the system to a minimum of 500 microns or
lower. During the early stages of evacuation, it is
desirable to close the manifold gauge valve at least once
to determine if there is a rapid rise in pressure. A rapid
rise in pressure indicates a relatively large leak. If this
occurs, the leak testing procedure must be repeated.
7.When 500 microns or lower is maintained, close the
manifold gauge valves, turn off the vacuum pump, and
disconnect the manifold gauge center port hose from the
vacuum pump. Attach the manifold gauge center port
hose to a nitrogen cylinder with pressure regulator set to
150 psig and purge the hose. Open the manifold gauge
valves to break the vacuum in the system. Close the
manifold gauge valves.
8.Shut off the nitrogen cylinder and remove the manifold
gauge hose from the cylinder. Open the manifold gauge
valves to release the nitrogen from the system.
9.Reconnect the manifold gauge to the vacuum pump,
turn the pump on, and continue to evacuate the system
until 500 microns is maintained within a 20-minute period
after shutting off the vacuum pump and closing the
manifold gauge valves.
10. When the requirements above have been met,
disconnect the manifold hose from the vacuum pump.
WARNING
Do not use a compressor to evacuate a system. Avoid
deep vacuum operation. Extremely low vacuums can
cause internal arcing and compressor failure. Danger
of equipment damage. Damage caused by deep
vacuum operation will void warranty.
1. Open liquid and suction line service valves on outdoor
unit.
2.Connect the manifold gauge set to the service valve
ports as follows:
•Low pressure gauge to suction line service valve
•High pressure gauge to liquid line service valve
3.Connect micron gauge.
4.Connect the vacuum pump (with vacuum gauge) to the
center port of the manifold gauge set.
5.Open both manifold valves and start vacuum pump.
506874-01Page 9 of 19Issue 1140
Page 10
START-UP
Liquid Line Set
Diameter
Oz. per 5 ft. adjust
from 15 ft. line set*
3/8 in.
3 oz. per 5 ft.
CAUTION
If unit is equipped with a crankcase heater, it should be
energized 24 hours before unit start-up to prevent
compressor damage as a result of slugging.
Optimizing System Charge
The outdoor unit should be charged during warm weather.
However, applications arise in which charging must occur in
the colder months. The method of charging is determined
by the unit’s refrigerant metering device and the outdoorambient temperature.
Measure the liquid line temperature and the outdoor ambient
temperature as outlined below:
1.Rotate fan to check for frozen bearings or binding.
2.Inspect all factory and field-installed wiring for loose
connections.
3.After evacuation is complete, attach HCFC-22 cylinder
to system through gauge set, and weigh in liquid
refrigerant.
4.Replace the stem caps and secure finger tight, then
tighten an additional 1/6 of a turn.
5.Check voltage supply at the disconnect switch. The
voltage must be within the range listed on the unit
nameplate. If not, do not start equipment until the power
company has been consulted and the voltage condition
corrected.
6.Set thermostat for cooling demand, turn on power to
indoor blower and close the outdoor unit disconnect
switch to start the unit.
7.Recheck unit voltage with unit running. Power must be
within range shown on unit nameplate.
1.Connect the manifold gauge set to the service valve
ports as follows:
•Low pressure gauge to suction line service valve
•High pressure gauge to liquid line service valve
2.Close manifold gauge set valves. Connect the center
manifold hose to an upright cylinder of HCFC-22.
3.If room temperature is below 70°F, set the room thermostat
to call for heat. This will create the necessary load for
properly charging the system in the cooling cycle.
4.Use a digital thermometer to record the outdoor ambient
temperature.
5.When the heating demand has been satisfied, switch
the thermostat to cooling mode with a set point of 68°F.
When pressures have stabilized, use a digital
thermometer to record the liquid and suction line
temperatures.
6.The outdoor temperature will determine which charging
method to use. Proceed with the appropriate charging
method.
Refrigerant Charging
This charge is based on a matching indoor coil and outdoor
coil with 15' line set. For varying lengths of line set, refer to
Table 5 for refrigerant charge adjustment.
Refrigerant Charge Adjustment
* If line length is greater than 15 ft., add this amount.
If line length is less than 15 ft., remove this amount.
Table 5
Page 10 of 19506874-01Issue 1140
Charge Using Weigh-In Method (Fixed Orifice/TXV
Systems)
If the system is void of refrigerant, or if the outdoor ambient
temperature is cool, first locate and repair any leaks then
use the weigh-in method to charge the unit.
1.Recover the refrigerant from the unit.
2.Conduct a leak check, then evacuate as previously
outlined.
3.Weigh in the charge according to the total amount shown
on the unit nameplate.
If weighing facilities are not available or if unit is being
charged during warm weather, follow one of the other
procedures outlined below.
Page 11
Charge Using Subcooling Method (TXV Systems) –
Outdoor Temperatures 65°F or Above
If charging a TXV system when the outdoor ambient
temperature is 65°F or above, the subcooling method can
be used to charge the unit.
1.With the manifold gauge hose on the liquid service port
and the unit operating stably, use a digital thermometer
to record the liquid line temperature.
2.At the same time, record the liquid line pressure reading.
3.Use a temperature/pressure chart for HCFC-22 to
determine the saturation temperature for the liquid line
pressure reading.
Subcooling Values for
TXV Systems
4.Subtract the liquid line temperature from the saturation
temperature (according to the chart) to determine
subcooling.
5.Compare the subcooling value with those shown in Table
6. If subcooling is greater than shown, recover some
refrigerant. If subcooling is less than shown, add some
refrigerant.
Charge Using Superheat Method (TXV Systems) –
Outdoor Temperatures 65°F or Above
1.With the manifold gauge hose on the suction service
port and the unit operating stably, use a digital
thermometer to record the suction line temperature.
2.At the same time, record the suction line pressure
reading.
3.Use a temperature/pressure chart for HCFC-22 to
determine the saturation temperature for the suction line
pressure reading.
_____ °Saturation Temperature °F
–
_____ °Liquid Line Temperature °F
=
_____ °Subcooling Value °F
4.Subtract the saturation temperature (according to the
chart) from the suction line temperature to determine
the superheat.
5.Compare the superheat value with those shown in Table
7 on page 12. If superheat is greater than shown, add
some refrigerant. If superheat is less than shown,
recover some refrigerant.
Table 6
Charge Using Approach Method (TXV Systems)
– Outdoor Temperatures 65°F or Above
The following procedure is intended as a general guide and
is for use on expansion valve systems only. For best results,
indoor temperature should 70°F to 80°F. Monitor system
pressures while charging.
_____ °Suction Line Temperature °F
–
_____ °Saturation Temperature °F
=
_____ °Superheat Value °F
1.Record outdoor ambient temperature using a digital
thermometer.
2.Attach high pressure gauge set and operate unit for
several minutes to allow system pressures to stabilize.
3.Compare stabilized pressures with those provided in
Table 9 on page 13. Minor variations in these pressures
may be expected due to differences in installations.
Significant differences could mean that the system
is not properly charged or that a problem exists with
some component in the system. Pressures higher
than those listed indicate that the system is overcharged.
Pressures lower than those listed indicate that the
system is undercharged. Verify adjusted charge using
the approach method.
4.Use the same digital thermometer to check liquid line
temperature.
5.Subtract the outdoor ambient temperature from the liquid
line temperature to determine the approach temperature.
506874-01Page 11 of 19Issue 1140
Page 12
Table 7
6.Compare the approach value with those shown in Table
8. If the values to do not agree with those provided in
Table 8, add refrigerant to lower the approach
temperature or recover refrigerant from the system to
increase the approach temperature.
Approach Values for TXV Systems
Approach value is the liquid line temperature minus the
outdoor ambient temperature (±1°F).
NOTE: For best results, use the same digital thermometer to
check both outdoor ambient and liquid temperatures.
Table 8
_____ °Liquid Line Temperature °F
–
_____ °Outdoor Ambient Temperature °F
=
_____ °Approach Temperature °F
Check Charge Using Normal Operating Pressures
Use Table 9 to perform maintenance checks. Table 9 is not
a procedure for charging the system. Minor variations in
these pressures may be due to differences in installations.
Significant deviations could mean that the system is not
properly charged or that a problem exists with some
component in the system.
Page 12 of 19506874-01Issue 1140
Page 13
Normal Operating Pressures
L – Liquid S – Suction
Values provided above are typical pressures. Indoor unit matchup, indoor air quality, and indoor load will cause pressures to vary.
Table 9
506874-01Page 13 of 19Issue 1140
Page 14
OPERATIONMAINTENANCE
Outdoor unit and indoor blower cycle on demand from the
room thermostat. When the thermostat blower switch is
moved to the ON position, the indoor blower operates
continuously.
WARNING
Before performing maintenance operations on system,
turn the electric power to unit OFF at disconnect
switch(es). Unit may have multiple power supplies.
Electrical shock could cause personal injury or death.
Maintenance and service must be performed by a qualified
installer or service agency.
At the beginning of each cooling season, the system should
be checked as follows:
1.Clean and inspect condenser coil. Coil may be flushed
with a water hose. Be sure the power is off before using
water to clean the coil.
2.Outdoor fan motor is pre-lubricated and sealed. No
further lubrication is needed.
3.Visually inspect connecting lines and coils for evidence
of oil leaks.
4.Check wiring for loose connections.
5.Check for correct voltage at unit (with unit operating).
6.Check amp-draw outdoor fan motor.
Unit Name Plate ________ Actual _________
NOTE: If owner complains of insufficient cooling, the unit
should be gauged and refrigerant charge checked. Refer
to the Refrigerant Charging section on page 10.
Indoor Coil
1.Clean coil, if necessary.
2.Check connecting lines and coils for evidence of oil
leaks.
3.Check condensate pan line and clean, if necessary.
Indoor Unit
1.Clean or change filters.
2.Adjust blower speed for cooling. Measure the pressure
drop over the coil to determine the correct blower CFM.
Page 14 of 19506874-01Issue 1140
3.Belt drive blowers: Check belt for wear and proper
tension.
Page 15
4.Check all wiring for loose connections.
5.Check for correct voltage at unit (with unit operating).
6.Check amp-draw on blower motor.
Unit nameplate _________ Actual
Start-Up and Performance Checklist
Job Name _______________________________Job No. ________________Date ______________
The covered equipment and covered components are warranted by the
manufacturer for a period of one (1) year from the date of the original unitinstallation, when installed and operated in accordance with the manufacturer’s recommendations. If, during this period, a covered component fails
because of a manufacturing defect, the manufacturer will provide a free
replacement part to the owner. The owner must pay shipping charges and
all other costs of warranty service.
EXTENDED COVERAGE
This limited warranty provides extended coverage on the components
outlined below. The extended warranty coverage begins with the date ofthe original unit installation and represents the total warranty period for the
specific component.
Heat Exchangers:
KGA and TGA (Aluminized −− All applications) −− Ten (10) years.
KGA and TGA (Stainless −− All applications) −− Fifteen (15) years.
RGE13, RHP13 and RCE13 −− Ten (10) years.
LF24 and TUA (Aluminized −− All applications) −− Ten (10) years.
LF24 and TUA (Stainless −− All applications) −− Fifteen (15) years.
LD24 (Aluminized −− All applications) −− Two (2) years.
LD24 (Stainless −− All applications) −− Five (5) years.
LG14 (All applications) −− Five (5) years.
Burners:LG14 −− Three (3) years.
Compressors:2SCU13LC, 2SHP13LC, 4SCU13LC, 4SHP13LC −− Five (5) years.
TSA, TPA −− Five (5) years.
KCA, KGA, KHA, TCA, TGA, THA −− Five (5) years.
RGE13, RHP13, RCE13 −− Five (5) years.
NOTE − If the date of original installation cannot be verified, the warranty
period will be deemed to begin six (6) months after the date of manufacture.
COMPONENT AVAILABILITY
In the event that a component covered by this warranty is no longer available, the
manufacturer will, at its option, provide a free suitable substitute component or
allow the owner to purchase an equivalent new unit at a reduced price of 20 percent of the list price in effect on the date of the failure. The owner must pay shipping charges and all other costs of warranty service.
EXCLUDED COMPONENTS
The following components are not protected by this warranty: cabinets,
cabinet pieces, air filters, driers, refrigerant, belts, wiring, fuses and unit
accessories.
REPAIRS
All repairs of covered components must be made with authorized service
parts by a licensed professional service contractor (or equivalent).
CARE OF EQUIPMENT
This new unit must be properly installed, operated and maintained by a licensed professional installer (or equivalent) or service agency in accordance
with the unit installation, operation and maintenance instructions provided
with each unit. Failure to provide maintenance per the manufacturer’s instructions will void this warranty. The owner may be asked to provide written documentation of annual and other periodic preventive maintenance.
WARRANTY PROCEDURE
When warranty parts are required:
1 − Be prepared to furnish the following information:
a − Complete model and serial number.
b − Proof of required periodic maintenance, installation date and location
if warranty claim.
c − An accurate description of the problem.
2 − Call your local installing contractor.
3 − If the installing contractor is unable to provide warranty parts, check the
yellow pages for another contractor in your area. If you are unable to se-
cure assistance from a contractor, contact the appropriate manufacturer
1 − The manufacturer will not pay labor involved in diagnostic calls, or in re-
moving, repairing, servicing, or replacing parts. Such costs may be cov-
ered by a separate warranty provided by the installing contractor.
2 − This warranty is void if the covered equipment is removed from the origi-
nal installation site.
3 − This warranty does not cover damage or defect resulting from:
a − Flood, wind, fire, lightning, mold, or installation and operation in a cor-
rosive atmosphere, or otherwise in contact with corrosive materials
(chlorine, fluorine, salt, recycled waste water, urine, fertilizers, or other damaging substances or chemicals).
b − Accident, neglect, or unreasonable use or operation of the equip-
ment, including operation of electrical equipment at voltages other
than the range specified on the unit nameplate (includes damages
caused by brownouts), or reverse rotation of compressors or motors
due to improper phasing.
c − Modification, change or alteration of the equipment, except as di-
rected in writing by the manufacturer.
d − Operation with system components (indoor unit, outdoor unit and re-
frigerant control devices) which do not match or meet the specifications recommended by the manufacturer.
e − Operation of packaged gas/electric units (equipped with aluminized
heat exchanger) with mixed air temperatures of less than 45°F (7°C).
f − Operation of furnaces with return air temperatures of less than 60°F
(16°C) or operation of a furnace field−installed downstream from a
cooling coil.
g − Use of contaminated or alternate refrigerant.
The installation of replacement parts under terms of this warranty will not ex-
tend the original warranty period.
The manufacturer makes no express warranties other than the warranty
specified above. All implied warranties, including the implied warranty
of merchantability and fitness for a particular purpose, are excluded to
the extent legally permissible. Should such exclusion or limitation of the
warranty be unenforceable, such implied warranties are in any event
limited to to a period of one (1) year. Liability for incidental and consequential damages is excluded. Some states do not allow limitations on
the duration of an implied warranty or the exclusion or limitation of incidental or consequential damages, so the limitations or exclusions may
not apply to you.
The manufacturer will not pay electricity or fuel costs, or increases in
electricity or fuel costs, for any reason whatsoever, including additional
or unusual use of supplemental electric heat. This warranty does not
cover lodging expenses.
The manufacturer shall not be liable for any default or delay in performance under this warranty caused by any contingency beyond its control.
This warranty gives you specific legal rights, and you may also have other
rights which vary from state to state.
NOTE TO CUSTOMER
Please complete information below and retain this warranty for your records and future reference.
Unit Model Number:
Serial Number:Date:
Installing Contractor:Phone:
Litho U.S.A.20112
FORM W−024−L3 −− 3/1/2012
Supersedes 9/1/2011
Page 18 of 19506874-01Issue 1140
Page 19
Page 20
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.