Always turn off power at the main power source by switching the
circuit breaker to the OFF position before installing or removing
this thermostat.
All wiring must conform to local and national building and electrical codes and ordinances.
Do not switch system to cool if the outdoor temperature is below
45°F (7°C). This can damage the cooling system.
CAUTION
This is a 24VAC low−voltage thermostat. Do not install on voltages higher than 30VAC.
Do not short (jumper) across terminals on the gas valve or at the
system control to test installation. This will damage the thermostat and void the warranty.
IMPORTANT
Read this manual before programming this thermostat.
Use this thermostat only as described in this manual.
506052−01 11/09
Page 2
icomfortt Thermostat Terms and Acronyms
Subnet Controller (SC): (part of the communicating thermostat) Local
device that controls the system.
Subnet: A part of the communication network that contains devices to
control one functional HVAC system.
RSBus − Residential Serial Bus − the means for transmitting data within
the communicating system.
Controller Area Network Protocol: Rules for networking, for transmission and receipt of information between communicating systems.
Baud Rate: Maximum speed of BUS 40K baud.
Byte: 8 bits of information transmitted on the RSBus.
Integrated Furnace Control (IFC): Communicating control for furnace.
IFC controls ignition, CAI, blower, and monitors all safety features in the
unit.
Air Handler Control (AHC): Communicating control for air handler
units. AHC controls operation of blower, heat strips, and monitors all
safety features in the unit.
HP Control (Defrost Control) (UC): Communicating defrost control.
UC controls low and high speed compressor operation, defrost opera-
tions, fan motor, and reversing valve and monitors all safety features in
the unit.
AC Control: Communicating air conditioning control. AC controls low
and high speed compressor operation, fan motor operation, and all safety monitors in the unit.
Discharge Air Sensor (DAS): Communicating discharge air sensor.
Provides discharge air temperature to Bus, UI, and IFC for proper operation of equipment.
R: 24V power
C: 24V common
i+: + data information connection
i−: − data information connection
Configuration: Function that accrues during setup of system to identify
other communicating devices. Configuration is also used in setup of a
variable capacity furnace to properly set furnace parameters.
Memory Fault Recall: Method of checking for errors
Firmware: Software stored on a memory chip instead of being part of a
program
Software: Programming and applications for computer
The 24VAC icomfort thermostat stores system parameters and settings in a nonvolatile memory (i.e., it retains data when electrical power
fails or is turned off). The thermostat (see figure 1) also:
includes on-board help screens,
supports heat pumps or non−heat pump units, with up to 4 stage
heat / 2 stage compressor operation. (2 stages of heat pump heating and 2 stages of auxiliary backup heat are provided. Also, 2
stages of emergency heat are provided),
supports Indoor Air Quality with time-based notification of consum-
ables including media filters, UVC bulbs, humidifier pads, and
PureAir catalyst service / replacement,
patibility (gas/electric/heat pump/ac), and is dual fuel capable with
two balance points.
Important
Always use correct software version as recommended for replacement
configuration (discovery).
Connections to non communication outdoor units and all accessories is
described in the Quick−Start Installation guide. (Wiring diagrams are also
shown beginning on Page 36.)
Thermostat
connections
R I+ I − C
RSBUS
Minimum wire size is
18 gauge
icomfort Outdoor Units Control
icomfort Furnace Control
icomfort Air Handler Control
External Sensors − outdoor temperature and humidity
Humidify control
Dehumidify control
Figure 1. icomfort thermostat system
Maximum total length
of all connections on
the RSBus is limited
to 1500ft.
506052−01 11/09
Page 4
icomfortt Thermostat Features
Thermostat Type
Electronic communicating, color display touch screen, 7−day programmable.
Supports
Humidification Measurement and Control,
Dew Point Adjustment Control,
Dehumidification Measurement and Control,
Humiditrol® Enhanced Dehumidification Accessory (EDA),
Multi-stage HVAC Systems,
Equipment Maintenance Reminders.
On-board Help Screens.
The icomfort thermostat’s autochangeover mode permits control of
heating, cooling, humidification, and dehumidification without user involvement.
Outdoor Temperature Sensor
Communicating outdoor units contain a built in outdoor temperature sensor.
Installing icomfortt thermostat
Refer to the Quick Start Guide for all the information about installing the
thermostat to a wall and for wiring diagrams for connecting the thermostat to the system using one of a number of possible configurations.
(Wiring diagrams are also shown beginning on Page 36.)
After all the wiring is in place, apply power to the system. 24VAC will begin to power up the thermostat.
After power is applied to the thermostat for the first time, the processor
checks the system for installed communicating devices, the System
discovery" screen (figure 2) is displayed on the thermostat; followed by
the Use this thermostat" screen (figure 3). Press press here to continue.
SYSTEM DISCOVERY IN PROGRESS
Figure 2. System discovery
setupHELP
tests
During the setup process, alerts may pop open to inform the installer
some item of information that affects the setup (figure 4). Tend to any
such alerts prior to continuing setup.
critical alert
Active
Critical Alert Code: 31
AIR HANDLER reports:
Lost Communication with
THERMOSTAT −
Latest occurrence: 8/23/09
1:57 PM
press for more
close
506052−01 11/09
Thermostat 1
Use this Thermostat?
press here
Figure 3. Use this thermostat screen
Figure 4. Alert window
Page 6
System settings (figure 5) appear first. As you use the up/down arrows
to scroll through the settings, the right hand side will show the current
value, for example, Current Value: (35% ) shows the current setting of
the Circulate Fan ON time.
setupHELP
system settings
Time and Date
Daylight Saving
Time
To view/edit a setting,
highlight it, then press edit.
Current Value:
(35%)
Circulate Fan ON
time
edit
Dealer Name
Dealer Address
Dealer Phone
Number
back
next step
Dealer Email
Figure 5. System settings
The following shows the range/condition and defaults for the settings.
system settingrange/conditiondefaultuse
Time and Datesee Page 8
Daylight Saving TimeEnabled/DisabledEnabled
Circulate Fan ON Time15 to 4535%
Dealer Name
Dealer Address
Dealer Phone Number
Dealer Email
Dealer Website
(alpha−numeric
characters)
Lennox
1−800−9−LENNOX
www.lennox.com
use type
writer to
change
Installer setup − Page 2 of 8
If you want to modify a setting, use one of the tools shown in figure 6.
(Make time and date as described on Page 8.) After changes have
been made, use save to store the changed data or cancel to exit the
screen and return to the list of settings.
up/down arrows
scroll through a
numeric range for
some settings
typewriter tool to input
names, address, phone
numbers etc.
Use the arrows to select Time and Date; press edit (see figure 7). Press
next to proceed to the Set current time and date" screen (figure 8).
setupHELP
system settings
Time and Date
Daylight Saving
Time
Circulate Fan ON
time
Dealer Name
Dealer Address
Dealer Phone
Number
Dealer Email
tests
to adjust a setting, highlight
it, then press edit.
Current Value:
(September 15, 2009,
09:23 AM)
edit
back
next step
Press other boxes and adjust with the arrows for all time and date
information. When the date and time is correct, press save to save
settings and return to previous settings screen.
setupHELP
Time and Date
10:19AM
adjust
Oct15 2009
cancel
save
Figure 7. View/edit time and date
When the Time and Date" screen appears, enter the correct date as follows:
Press one of the time and date boxes − the text will change to white
type in a dark box (for example, press the 10" box in figure 8).
Press the up/down arrows to change the data.
506052−01 11/09
Figure 8. Set current time and date
NOTE − After setting the time and date, if you don’t need to add any non−
communicating devices, you may wish to accept the default system parameters and skip forward to tests". To do so, repeatedly press nextstep on each screen until you get to the tests screen. From there, you
can check the systems operation. Thereafter, should you need to
change a communicating device parameter, access those settings by
pressing the equipment tab in the installer section.
Page 8
Add/remove/modify non−communicating devices
From this screen (figure 9), use the yes button to access a list of non−
communicating devices for installing or removing. A list similar to that
shown in figure 10 will appear.
Humidification / Dehumidification Control Modes depend on a humidifier and/or dehumidifier being added to the system. Therefore, you
must press yes on the button near "Add or Remove Non−communicating
equipment?" Also, in order for the user’s display to show these controls,
the system controls must be set. See Page 12 for more information.
Use the up/down arrows (see figure 10) to select a setting. The right hand
side of the screen indicates what is currently selected, for example, Cur-
rent Value: (Not Installed); press edit if you want to modify that setting.
Installer setup − Page 4 of 8
setupHELP
non−communicating
device list
HUMIDIFIER
DEHUMIDIFIER
UV LIGHT
Figure 10. Installing UV Light
A typical Installed status screen (Figure 11) shows if the device is not
installed or type of equipment installed. Use the arrows to change and
use save to save the change. (Cancel goes pack to previous screen.)
With one of the devices highlighted, press about, then use arrow keys to
see a list of data about the selected device. If you select reset ALL, and
then confirm, ALL devices will be reset to their factory settings. (You
would see a screen similar to figure 14.)
With one of the devices in figure 12 highlighted, press edit to go to that
device’s list of settings (see figure 13).
Use the up/down arrows to scroll through the device’s settings and observe the right hand side of the screen (figure 13) to see the current setting, for example, Current Value: (Off). Press edit if you want to modify
that setting, or press back to return to the previous screen.
506052−01 11/09
to adjust a device, highlight
it, then press edit
edit
reset ALL
back
next step
about
setupHELP
HP
Equipment Name
Compressor Short
Cycle Delay
Defrost
Termination Temp
Compressor Shift
Delay On/Off
to adjust a setting, highlight it,
then press edit
Current Value:
(Off)
edit
back
Figure 13. Modify communicating device settings
Settings available for the devices are dependant on the components you
have. Shown below is an example of changing the compressor shift
delay on. After using the arrows to select On, press save to save the
changes and return to the previous screen.
Compressor Shift Delay On/Off
On
Off
Page 10
cancel
save
reset
If you select reset and then confirm, the highlighted device will be reset
to its factory setting. You would see a screen similar to figure 14, but referencing only the selected device.
Resetting ALL devices to their factory default
settings will cause the system to restart the
setup process. If you want to continue, then
press ’confirm’ or press ’cancel’.
confirm
cancel
Installer setup − Page 6 of 8
After a reset, the device which had its settings reset to
default will display in the system devices screen in red
type. You will be required to highlight the red−type device(s) and use edit (see figure 12) to change, or at
least view the changed settings of the red−type devices .
In the edit mode, the feature list will show the selected
device’s changed features in red type. Use the up/
down arrows to select each red−typed feature and
press edit. Make changes to the settings using the
Edit tools if desired, or at least, press save in each fea-
ture screen. Upon saving, the previous screen will
display and the type will again be black. Press back to
return the Modify communicating device settings
screen.
HP
XP19−060−230−06
5809K00015
AIR HANDLER
CBX32MV−60
5809K00020
Equipment
Name
Electric Heating
Airflow
Low Cooling
Airflow
Low Cooling
Airflow
Figure 14. Reset device confirmation note
At this point press next step to advance to the test controls.
An example of installing UV Light is shown in figure 10, Page 9.
To turn on humidification or dehumidification controls, in addition to
the setup described on Page 9, work from either the setup tab or the
equipment tab to get to the adjustment screen (figure 15). Use the arrows
to highlight the SYSTEM selection. Press edit.
A long list of features are listed on the right of the next screen (see figure
16). Use the arrows to locate Humidification Control Mode and/or De-humidification Control Mode. Press edit.
Depending on the type of equipment installed, the lists of options may be
different than those shown in figure 17. In order for either or both of these
controls to display, the selected option must be other than Display
Only".
setuptestsequipmentHELP
system devices
XP19−060−230−06
5809K00015
AIR HANDLER
CBX32MV−60
5809K00020
THERMOSTAT
49W95
A109K00139
SYSTEM
49W95
A109K00139
(to adjust a device, highlight
it, then press edit)
edit
back
Figure 15. Accessing the SYSTEM adjustment screen
about
reset ALL
next step
506052−01 11/09
Page 12
setuptestsequipmentHELP
SYSTEM
Equipment Name
Filter 1 Timer
Selection
.
.
(various)
.
.
Dehumidification
Control Mode
Humidification
Control Mode
(to adjust a setting, highlight
it, then press edit)
BASIC & PRECISIONthese modes allow user control of RH between
15 and 45%. These conditions must be met for either mode to operate:
humidification mode has been enabled, and
the unit is in HEAT mode, and
humidification demand exists (24V present at H), and
BASIC mode also requires heat demand exists (Y for HP heat, or W for
gas heat [W may be energized with G de−energized]).
DEW POINT CONTROLDew point adjustment mode will change the
humidification setpoint based on the outdoor temperature and a user−defined dew point adjustment setting.
DEHUMIDIFICATION modes
In BASIC mode, dehumidification occurs if these conditions are met and
signals are present at specific terminals:
dehumidification has been enabled on installer settings, and
the unit is in COOL mode, and
dehumidification demand exists (RH above setpoint), and
cooling demand exists (Y1 energized).
In PRECISION mode, dehumidification occurs if all BASIC conditions
are true, except cooling demand may or may not be present. Maximum
overcool from cooling set point is 2ºF.
HUMIDITROL or AUX. DEHUMIDIFIER mode requires:
outdoor sensor must be installed and setup
dehumidification has been enabled on installer settings, and
the unit is in COOL mode, (or if in AUTO, at least one thermostat cooling
call made prior to the dehumidification demand), and
a dehumidification demand exists (RH above setpoint), and
outdoor temp. below 95°F; indoor temp. above 65°F, and
for HUMIDITROL, Humiditrol comfort adjust parameters as follows:
The tests feature is not available until after setup has been completed
once. After you press next step in the final setup screen, the Select
tests to run" screen (figure 18) appears.
If you re−select the tests tab from any other screen, a message to press
Start button below to begin system testing" appears; press start.
press start button below to begin system testing
start
setuptestsequipmentHELP
select tests to run
TEST ALL
Blower
HP Heat − 1st
Stage
HP Heat − 2nd
Stage
Defrost Now
Cooling − 1st
Stage
Cooling − 2nd
Stage
select
alertsdiagnostics EXIT
selected tests
skip tests
Figure 18. Select tests to run
When the tests screen opens, TEST ALL will be highlighted (but not yet
selected). If you want to run TEST ALL, press select. Note your selection
on the right side says selected test TEST ALL". Also, note there are now
two buttons along the bottom labeled remove and start. Use remove to
deselect a selected test.
If you prefer, run tests one−at−a−time using the arrows to highlight a desired test and then press select.
Press start to begin testing.
setuptestsequipmentHELP
select tests to run
TEST ALL
Blower
HP Heat − 1st
Stage
HP Heat − 2nd
Stage
Defrost Now
Cooling − 1st
Stage
Cooling − 2nd
Stage
select
alertsdiagnostics EXIT
selected tests
TEST ALL
startremove
Figure 19. Start running tests
506052−01 11/09
Page 14
Tests − Page 1 of 1
After the tests have been started, the screen will describe which test is
running (see figure 20). After concluding that the results are the desired
results for any test, press next (if using TEST ALL) to proceed to the next
test or done (if running a single test).
TEST ALL example
CURRENT TEST: Blower
Check Blower Operation
cancel
next
single test example
CURRENT TEST: Blower
Check Blower Operation
cancel
done
Figure 20. Typical tests results screens
After pressing done, the Testing finished" screen will appear (see figure
21). At this point, use the EXIT tab (if you are finished with all setup), or
use diagnostics tab (to analyze the system), or use equipment tab (if
you wish to make any changes to device details).
This feature allows the installer to edit details of devices in the system
without having to re−run the setup program. The following appears after
the equipment tab has been selected
press start button below to edit details of devices in
Press start; the Equipment details edit" screen (figure 22) will open.
You may view information about or modify communicating devices as
described earlier in the setup pages, beginning on page 10.
setuptestsequipmentHELP
system devices
HP
XP19−060−230−
06
5809K00015
AIR HANDLER
CBX32MV−60
5809K00020
THERMOSTAT
49W95
A109K00139
SYSTEM
Figure 22. Equipment details edit
the system
start
back
to adjust a device, highlight
it, then press edit
about
edit
reset ALL
next step
setuptestsequipmentHELP
SYSTEM
Equipment
Name
Filter 1 Timer
Selection
Filter 2 Timer
Selection
UV Bulb Timer
Selection
Humidifier Pad
Timer Selection
(to adjust a setting, highlight
it, then press edit)
Current Value:
(System)
edit
back
reset
Figure 23. Equipment details edit
Table on Page 25 shows a list of Editable Parameters for the currently
available devices designed to communicate in this system. Other devices and additional parameters may be added at a later date. Check the
unit installation manuals (i.e. furnace, air handler, heat pump, ac unit) for
current information and default parameters.
506052−01 11/09
Page 16
If you need to run diagnostics to analyze the system, press the diagnos-tics tab. The Select device to run diagnostics" screen (figure 24) will
open.
select device to run
diagnostics on
HP
XP19−060−230−
06
5809K00015
AIR HANDLER
CBX32MV−60
5809K00020
run diagnostics on:
select
diagnostics
Figure 24. Select device to run diagnostics
Use the arrow buttons to scroll through the list of items found on the left of
the screen. Then press select. The right side of the screen shows which
item is selected (figure 25). Use start to begin the process. The screen
will show DIAGNOSTICS IN PROGRESS..." briefly, then change to
show the list of values and conditions discovered.
Use the arrow buttons to scroll through the information and take note of
any found to be out of operating range.
Press done when finished with the information and select another device
to diagnose or use EXIT if finished.
As described earlier on Page 6, alerts may pop up on the screen during
setup. To view alerts otherwise, press the alerts tab. Up to 10 alerts are
stored for recall by the technician.
The left side of the main alert screen shows a list of each communicating
device discovered in the system and includes model and serial number
information. The up/down arrows allow you to scroll through the list of
discovered devices. The selected device is shown in bold lettering.
On the right side of the alert screen, press view active alerts to list all
active alerts for either SYSTEM ALERTS (lists alerts from all communicating devices) or a selected device. If there are no alerts, the display will
show There are no new alerts that require service".
Press view cleared alerts to list previously active alerts that were
cleared by the device or installer. Until at least one alert has been cleared
by the device or the installer, the display will show There are no new
alerts that require service".
System Devices
SYSTEM ALERTS
HP
XP19−060−230−06
5809K00015
AIR HANDLER
CBX32MV−60
5809K00020
THERMOSTAT
49W95
A109K00139
alertsdiagnosticsEXIT
use the arrows to
select a device
view active
alerts
view cleared
alerts
The first alert will be displayed in the Device alert" screen (figure 27), in
order of:
1. critical first (red icon),
2. service next (yellow icon).
If the information in the alert box exceeds the box size, press press formore to see the remaining information.
A critical alert (red icon) identifies a system or device issue that can pre-
vent the system from working properly or at all, and if allowed to run,
could cause damage to the system. The issue raised by the alert must
be addressed before clearing the alert.
Press clear (see figure 27) to request
clearing of a critical alert; then confirm
the request (shown to the right). The device will respond to the request indicating
whether or not the alert can be cleared at
that time. If it cannot be cleared, revisit
the alert issue and make repairs accordingly.
The edit date option is not available for a critical alert.
A service alert (yellow icon) reminds users to service filters, humidifier
pad, UV light and PureAir Air Purification system.
Press clear (see figure 27) to request
clearing of a service alert. If you answer
no to the was action taken" screen
(shown to the right), the alert reappears
and is not cleared. Action must be taken,
either to perform the maintenance required, or instead of clearing, you may
edit the time to again be reminded (described later).
If you press yes to ’was action taken?’, the Set new alert date" screen
(figure 28) appears. You may chose from the list of options or set a custom time (see figure 30).
Use Setting custom time" screen (figure 30) to set an exact date and
time for the reminder to appear. Press in one of the boxes to highlight it
and use the up/down arrows to change the value in that box. Repeat for
all boxes. When desired reminder is displayed, press set.
Press done to return to the device alert screen (figure 27, page 18).
506052−01 11/09
Page 20
View cleared alerts
A history of cleared alerts allows the installer to review the cleared alerts.
This information can help diagnose problems. Use the arrows to (figure
34) select either SYSTEM ALERTS or a devicefrom the list (see figure
34) and press view cleared alerts. Then scroll through the alerts using
next alert (see figure 34). The back button returns to the system devices
alerts screen.
Alerts − Page 4 of 4
If no alert or only one alert is present in the history of cleared alerts, only
the back button appears. If no alerts are present in the system or device’s history, a message will state that There are no new alerts that require service".
Access installer program from Home screen − Page 1 of 1
To access the installer program after the unit has been placed in operation and the user home screen is displayed, press the Lennox" logo and
hold for 5 seconds (see figure 35). The system will access the installer
screens.
Figure 36, Qualified Lennox equipment installer warning" screen appears; press yes to proceed (no returns the home screen).
When you press yes, the thermostat’s processor will search for communicating devices in the system. The next display will be a summary of all
alerts detected.
Figure 35. Enter installation setup mode from home screen
506052−01 11/09
After initial installation, if an alert is present when you are making
changes to settings, no action on the alert is mandatory.
Page 22
To begin reconfiguring a system, press the setup tab.
The Start system configuration" screen (figure 37) appears; press start
to proceed.
setup
press start button below only if you wish to setup a
new system, or to re−setup an existing system
testsequipment
tests
HELP
Reconfiguring a system − Page 1 of 2
Press confirm to continue system configuration; the screen will change
to the system discovery screen.
setupHELPtestsequipment
configuring the system may affect some device settings.
confirm to continue, or press cancel
start
back
Figure 37. Start system configuration
If this is the first attempt to configure a system, the screen will change to
the system discovery screen.
The Re−configure confirmation" screen (figure 38) will only appear on
attempts to RE−CONFIGURE the system. It is a reminder that systemconfiguration may affect some existing device settings and prompts to
confirm or cancel the configuration process (returns to figure 37).
While reconfiguring, the thermostat will have retained settings from the
previous configuration. If a device has been replaced and re−configuration has detected its replacement device, it will know the original device
is missing and prompt the installer (figure 40).
If this is the initial configuration, the Compatible device found" screen
does not appear.
Figure 41 lists all communicating devices found and gives you an opportunity to review the reconfigured devices. Use the arrow buttons to scroll
through the list of items found on the left of the screen. Press about to
highlight an option on the right side of the screen and view details about
that device. If necessary, change SYSTEM settings as described on
Page 10.
setupHELP
Missing
(DEVICE ETN)
Model No.(control model no.)
Serial No. (control serial no.)
Settings were not copied
Found Compatible
(DEVICE ETN)
Model No.(control model no.)
Serial No. (control serial no.)
next
Figure 40. Compatible device found
Press next to accept the device and write the thermostat’s settings from
the previous configuration to the found compatible device. The display
changes to Settings were copied". Press next to advance to the next
screen.
506052−01 11/09
setupHELP
system devices
HP
XP19−060−230−
06
5809c00015
AIR HANDLER
CBX32MV−60
5809B00020
THERMOSTAT
49W95
A109B00139
SYSTEM
view/ edit selected device’s
edit
back
Figure 41. System devices screen
Press next step to continue to test the system (see Page 14).
Page 24
settings
about
reset all
next step
Editable Parameters Table (User and Installer)
Parameter Name:DefaultParameter Value SettingIncrement
Installer settings
Time and Date(Time/date elements screen)
Daylight Saving TimeEnabledEnabled, Disabled
Circulate Fan − Percentage of Time ON35%15 to 45%1%
Dealer Contact Information – NameLennox(Typewriter input screen)
Dealer Contact Information – Address(Typewriter input screen)
Dealer Contact Information – Phone1−800−9−LENNOX(Typewriter input screen)
Dealer Contact Information – Email(Typewriter input screen)
Dealer Contact Information – Websitewww.lennox.com(Typewriter input screen)
SYSTEM
Equipment Name(Typewriter input screen)
Filter 1 Timer SelectionCalendar TimeCalendar Time, Run Time
Filter 2 Timer SelectionCalendar TimeCalendar Time, Run Time
Humidifier Pad Timer SelectionCalendar TimeCalendar Time, Run Time
UV Bulb Timer SelectionCalendar TimeCalendar Time, Run Time
PureAir Timer SelectionCalendar TimeCalendar Time, Run Time
Smooth Setback RecoveryDisabledEnabled, Disabled
Electric Heat Control ModeStandardStandard, Even Heat
Gas Heat Control ModeModulatingStaged, Modulating
Heating indoor blower OFF delayDIP SW6018010NoneDIP switch setting in Non−comm.
Heating indoor blower ON delay4515455None45 sec fixed in Non−Comm. IFC
Cooling indoor blower OFF delay00302Outdoor Unit presentNot used on Non Com. IFC
Cooling indoor Blower ON Delay20101Outdoor Unit present2 sec fixed in Non−Comm. IFC
Heat pump indoor blower OFF delay450605Heat Pump presentNot used on Non Com. IFC
Heat pump indoor blower ON delay00305Heat Pump presentNot used on Non Com. IFC
Gas Heat Airflow Setting
Heating Airflow Control Type0 – Fixed CFM011DATS installed0 – Text ID 0x000E (Fixed CFM)
Low Heating Airflow (CFM @ 40% heat)DIP SW32545025Heating Airflow Control Type = 070,000 BTU; 1/2 HP fan
High Heating Airflow (CFM @ 100%
heat)
Low Heating Discharge Air Temperature
(DAT @ 40% heat)
High Heating Discharge Air Temperature (DAT @ 100% heat)
* − Default DAT value is rounded to the closest number on 5 deg F resolution and limited by Minimum and Maximum value.
DIP SW800110025Heating Airflow Control Type = 070,000 BTU; 1/2 HP fan
DIP SW*11 01405 Heating Airflow Control Type = 170,000 BTU; 1/2 HP fan
DIP SW*1201505 Heating Airflow Control Type = 170,000 BTU; 1/2 HP fan
5006752590,000 BTU; 1/2 HP fan
4256252590,000 BTU; 1HP fan
62587525110,000 BTU; 1 HP fan
750102525135,000 BTU; 1HP fan
92512502590,000 BTU; 1/2 HP fan
102514252590,000 BTU; 1HP fan
1350185025110,000 BTU; 1 HP fan
1500205025135,000 BTU; 1HP fan
110140590,000 BTU; 1/2 HP fan
110140590,000 BTU; 1HP fan
1101405110,000 BTU; 1 HP fan
1101405135,000 BTU; 1HP fan
130160590,000 BTU; 1/2 HP fan
120150590,000 BTU; 1HP fan
1201505110,000 BTU; 1 HP fan
1251555135,000 BTU; 1HP fan
1 – Text ID 0x000F (Fixed DAT)
table continued on next page
506052−01 11/09
Page 28
Value
Parameter NameNoteDependency
Parameter NameNoteDependency
Incr.Max.Min.Default
Cooling Airflow Setting
High Cooling Airflow
(CFM @ 100% cool)
Low Cooling Airflow
(CFM @ lowest cool stage)
Airflow Profile − CoolingDIP SW031Outdoor Unit present0–Text ID 0x0105
OU tons (OUNC) *
400CFM
See Note1 belowMin CFMMax CFM252+ stage Outdoor Unit present1/2 HP blower
Min CFMMax CFM25Outdoor Unit present1/2 HP blower
Min CFMMax CFM251 HP blower
Min CFMMax CFM251 HP blower
(A:ON:50%/30s,82%/7.5min
OFF:50%/30s)
1–Text ID 0x0106 (B:ON:82%/7.5min;
OFF: No delays)
2–Text ID 0x0107 (C:ON: No delays;
OFF: 45sec delay)
3–Text ID 0x0108 (D:No delays)
Heat Pump Airflow Setting
High Heat Pump Airflow (CFM @
100%)
Low Heat Pump Airflow (CFM @ lowest
stage)
OU tons (OUNC) *
400CFM
See Note 2 belowMin CFMMax CFM252+ stage Heat Pump present1/2 HP blower
Min CFMMax CFM25Heat Pump present1/2 HP blower
Min CFMMax CFM251 HP blower
Min CFMMax CFM251 HP blower
Other Parameters
Equipment NameFurnaceN/AN/AN/ANoneUp to 35 characters
Continuous Indoor Blower AirflowDIP SW (See
Humidification AirflowSame as aboveMin CFMMax CFM25Humidifier present1/2 HP blower
Dehumidification Airflow Percentage140
Note 1: Minimum Outdoor Unit Cooling Stage as a percentage of High Cooling Airflow (value is rounded up to the closest number on 25 CFM resolution
Note 2: Minimum Outdoor Unit Heating Stage as a percentage of High Heat Pump Airflow (value is rounded up to the closest number on 25 CFM resolution).
Note 3: All communicating Installer Parameters default CFM values based on DIP switch setting (non−communicating value) are calculated using the CFM conversion tables and
rounded up to closest number on 25 CFM resolution.
Note 4: Parameter dependency − Certain parameters are dependent on others and may not be shown on the display.
Note 5: Default Values − Jumper/DIP switches impact the default value of some parameters.
Note 3)
(=70%)
Min CFMMax CFM25None1/2 HP blower
Min CFMMax CFM251 HP blower
Min CFMMax CFM251 HP blower
120
(=60%)
160
(=80%)2(=1%)
OU present AND SC algorithm supportPercent of High Cooling Airflow
Alarm IDMessage NameAction required to Clear/Recover
10Unknown Device Detected − DEVICE2Reconfigure the system. Press and hold Lennox Logo, press setup tab, press start, and press confirm. If still
11Missing DEVICE2Check all connections and cycle system power. If problem persists, then reconfigure the system (procedure
12Incomplete SystemThermostat did not find an Indoor Unit. Check connections and cycle power. Replace board if no response.
14Too Many Devices of the Same TypeThermostat found more than one outdoor unit, or more than 1 indoor unit, or more than 1 thermostat connected
18Low Ambient HP Heat LockoutNotification only − Outdoor Temp is below the Low Balance Point. HP will not be used to service a Heating Call.
19High Ambient Auxiliary Heat LockoutNotification only − Outdoor Temp is above the High Balance Point. Indoor Unit (Furnace or Electric Heat) will not
29Over Temperature ProtectionIndoor Temp went above 99ºF during a heating or cooling call. Heating is not allowed. Check that Thermostat
30Low Temperature ProtectionIndoor Temp went below 40ºF. Cooling is not allowed. Check that cooling equipment is not stuck ON. Check
31Lost Communication with DEVICE2DEVICE2 is not communicating to the thermostat for more than 3 minutes. Check connections if fault persists,
32Asynchronous Reset DEVICE2DEVICE2 is resetting by itself. Check power connections, and check 24VAC voltage at DEVICE. The alarm is
34Must Program Unit Capacity for DEVICE2DEVICE2 is missing the programmed unit capacity. Go to DEVICE2 and program unit capacity manually. See
35Incorrect Operation of DEVICE2DEVICE2 did not follow the command of the thermostat. Check connections and cycle power.
105Communication ProblemEquipment is unable to communicate. Check for miswired and/or loose connections and check for a high volt-
110Low AC Line VoltageLine Voltage Low (Voltage lower than nameplate rating). Check voltage.
113High AC Line VoltageLine Voltage High (Voltage higher than nameplate rating). Check voltage.
114AC Line Frequency/Distortion ProblemNo 60 Hertz Power (Check voltage and frequency).
115Low Secondary (24VAC) Voltage24 Voltage Low (Range is 18 and 30 volts ). Check voltage.
116High Secondary (24VAC) Voltage24 Voltage High (Range is 18 and 30 volts ). Check voltage.
120Unresponsive DEVICE2Usually caused by delay in outdoor unit responding to indoor unit poling recycle power, check wiring.
124Active Subnet Controller MissingEquipment lost communication with the thermostat. Check connections and cycle power on the thermostat.
persists, then check all DEVICE connections to make sure they are icomfort compatible.
mentioned above).
to the system. Check wiring and remove duplicate equipment.
be used to service a Heating Call.
Sensor is accurate. Check that Heating Equipment is not stuck ON (reversing value, etc.). Select system mode
to cooling to try and cool the indoor space.
accuracy of the thermostat temperature. Try to heat the space to above 40ºF.
then cycle power.
only cleared by pressing the clear button on the Installer Alerts Tab. If fault persists after checking connections,
replace board.
unit IOM for instructions.
age source of noise close to the system (welder etc.).
Alarm IDAction required to Clear/RecoverMessage Name
125Control Hardware ProblemHardware problem on the control board. Cycle power on control. Replace if problem prevents service and is
126Control Internal Communication ProblemHardware problem on the control board. Cycle power on control. Replace if problem prevents service and is
130Configuration Jumper MissingConfiguration jumper(s) missing on control board (applicable in non−communication only).
131Corrupted Control ParametersReconfigure the system. Replace board if service (heating cooling) is not viable.
132Failed Flash CRC Check (Check Sum) Software
180Outdoor Temperature Sensor ProblemCompare outdoor sensor resistance to temperature/resistance charts in installation instructions. Replace if
200Rollout Limit Switch OpenCorrect unit cause of rollout trip or replace flame rollout switch and test furnace operation.
201Indoor Blower Motor ProblemIndoor blower communication failure including power outage. Check wiring to motor.
202ID Blower Motor & Unit Size MismatchIncorrect appliance capacity code selected. Check for proper configuring under: Unit Size Codes for Furnace/Air
203Invalid Unit CodeNo appliance capacity code selected. Check for proper configuring under: Unit Size Codes for Furnace/Air
204Gas Valve ProblemCheck operation and wiring of gas valve.
205Gas Valve Relay Contact ClosedCheck wiring to relay; if wiring is correct, replace relay.
207HSI Sensed OpenMeasure resistance of Hot Surface Ignition ignitor. Replace if open or not within specification range found in
223Low Pressure Switch OpenCheck inches of water column closing pressure of low pressure switch on heat call, measure inches of water
224Low Pressure Switch Stuck ClosedCheck operation of low pressure switch for stuck closed on heat call, measure inches of water column of oper-
225High Pressure Switch Failed to CloseCheck inches of water column closing pressure of high pressure switch on heat call, measure inches of water
226High Pressure Switch Stuck ClosedCheck operation of high pressure switch for closing on heat call, measure inches of water column of operating
227Low Pressure Switch Open in Run ModeCheck inches of water column closing pressure of low pressure switch on heat call, measure inches of water
228Inducer/Pressure Switch Calibration FailureUnable to perform pressure switch calibration. Check vent system and pressure switch wiring connections.
240Low Flame Current − Run ModeCheck micro amperes of flame sensor in board diagnostics or field installed mode; clean or replace sensor.
is corrupted.
persistent.
persistent.
Recycle power, if re−occurs replace control.
necessary.
Handler on configuration guide or in installation instructions.
Handler on configuration guide or in installation instructions.
IOM.
column of operating pressure, inspect vent and combustion air inducer for correct operation and restriction.
ating pressure, inspect vent and combustion air inducer for correct operation and restriction.
column of operating pressure, inspect vent and combustion air inducer for correct operation and restriction.
pressure, inspect vent and combustion air inducer for correct operation and restriction.
column of operating pressure, inspect vent and combustion air inducer for correct operation and restriction.
Measure voltage of neutral to ground for good unit ground.
table continued on next page
506052−01 11/09
Page 32
Alarm Codes and Troubleshooting
Alarm IDAction required to Clear/RecoverMessage Name
241Flame Out of Sequence − Still PresentShut off gas, check for gas valve leak.
250Primary Limit Switch OpenCheck firing rate on furnace, blockage in heater, and air flow.
252Discharge Air Temperature HighCheck temperature rise, air flow and input rate.
270Watch Guard − Flame Failure on IgniteCheck for gas flow, ignitor lighting burner, flame sensor current.
271Watch Guard − Low Pressure Switch OpenCheck inches of water column closing pressure of low pressure switch on heat call, measure inches of water
272Watch Guard − Low Pressure Switch Open Run
273Watch Guard − Flame Fail in Run ModeCheck micro amperes of flame sensor in board diagnostics or field installed mode; clean or replace sensor.
274Watch Guard − Primary Limit Switch OpenCheck why limit is tripping, over fired, low air flow.
275Watch Guard − Flame Out of Sequence. No
276Watch Guard − Calibration FailureUnable to perform pressure switch calibration. Check vent system and pressure switch wiring connections.
290Ignition Circuit ProblemMeasure resistance of Hot Surface Ignition ignitor, replace if open or not within specification; otherwise replace
291Heat Airflow Restricted Below Min.Check for dirty filter, unit air flow restriction, blower performance.
292Indoor Blower Motor Start ProblemIndoor blower motor unable to start (seized bearing, stuck wheel, etc.). Replace motor or wheel if assembly
294Inducer Motor Over currentCheck combustion blower bearings, wiring, amps. Replace if does not operate or meets performance.
295Indoor Blower Over TemperatureIndoor blower motor over temperature (motor tripped on internal protector). Check motor bearings, amps; re-
310Discharge Air Sensor ProblemCompare outdoor sensor resistance to temperature/resistance charts in installation instructions. Replace sensor
311Heat Rate Reduced to Match AirflowFurnace blower in cutback mode due to restricted airflow. Check filter and ductwork. To clear, replace filter if
312Reduced Airflow − Indoor Blower CutbackRestricted airflow − Indoor blower is running at a reduced CFM (Cutback Mode − The variable speed motor has
Mode
Flame
column of operating pressure, inspect vent and combustion air inducer for correct operation and restriction.
Check operation of low pressure switch for stuck closed on heat call, measure inches of water column of oper-
ating pressure, inspect vent and combustion air inducer for correct operation and restriction. Check inches of
water column closing pressure of high pressure switch on heat call, measure inches of water column of operating pressure, inspect vent and combustion air inducer for correct operation and restriction.
Measure voltage of neutral to ground for good unit ground.
Shut off gas, check for gas valve leak.
control.
does not operate or meet performance.
place if necessary.
if necessary.
needed or repair/add ductwork.
pre−set speed and torque limiters to protect the motor from damage caused by operating out of its designed
parameters (0 to 0.8" w.g. total external static pressure). Check filter and ductwork. To clear, replace filter if
needed or repair/add ductwork.
Alarm IDAction required to Clear/RecoverMessage Name
313Indoor/Outdoor Unit Capacity MismatchIncorrect indoor/outdoor capacity code selected. Check for proper configuring in installation instructions. Alarm
345Relay O FailureO relay / Stage 1 failed (Pilot relay contacts did not close or the relay coil did not energize),
346HP Jumper not RemovedConfiguration jumper(s) not removed on control board cut O−R. Applicable with non communicating outdoor unit
347Relay Y1 FailureY1 relay / Stage 1 failed (Pilot relay contacts did not close or the relay coil did not energize),
348Relay Y2 FailureY2 relay / Stage 2 failed (Pilot relay contacts did not close or the relay coil did not energize),
349IFC Error Check Jumper O to RConfiguration link R to O needs to restored Applicable in non communicating mode,
350Electric Heat not ConfiguredHeat call with no configured or mis−configured electric heat. Check for proper configuring under Configuring
351Electric Heat Stage 1 ProblemHeat section / Stage 1 failed (Pilot relay contacts did not close or the relay coil in the electric heat section did
352Electric Heat Stage 2 ProblemHeat section / Stage 2 failed (Same as Code 351).
353Electric Heat Stage 3 ProblemHeat section / Stage 3 failed (Same as Code 351).
354Electric Heat Stage 4 ProblemHeat section / Stage 4 failed (Same as Code 351).
355Electric Heat Stage 5 ProblemHeat section / Stage 5 failed (Same as Code 351).
400LSOM Compressor Internal Overload TrippedCompressor protector is open. Check for high head pressure, check compressor supply voltage.
401LSOM Compressor Long Run CycleCompressor ran over 18 hours on one room thermostat demand.
402LSOM Outdoor Unit System Pressure TripOutdoor unit pressure trip. Check dirty coil, fan motor, refrigerant charge.
403LSOM Compressor Short−CyclingCompressor short cycling (Running less than 4 minutes).
404LSOM Compressor Rotor LockedCheck capacitor, wiring, hard−start kit, replace compressor.
405LSOM Compressor Open Circuit
406LSOM Compressor Open Start Circuit
407LSOM Compressor Open Run Circuit
408LSOM Compressor Contactor WeldedReplace contactor.
409LSOM Compressor Voltage LowCheck power to unit.
is just a warning. The system will operate, but might not meet efficiency and capacity parameters and alarm
would clear when commissioning is exited.
with communicating indoor system.
Electric Heat Stages in the air handler installation instructions.
not energize).
Outdoor unit power disconnect is open.
Compressor circuit breaker or fuse(s) is open.
Broken wire or connector is not making contact.
Low or high pressure switch open if present in the system.
Compressor contactor has failed to close.
Check compressor for hot (cool down), check pressures, fan motor etc. Replace compressor if unable to get
circuit to close and compressor to operate.
table continued on next page
506052−01 11/09
Page 34
Alarm Codes and Troubleshooting
Alarm IDAction required to Clear/RecoverMessage Name
410Open Low Pressure SwitchRemove any blockages or restrictions from indoor coils and/or fans. Check refrigerant charge and system operation.
411Low Pressure Switch Strikes LockoutCheck system charge using approach and sub cooling temperatures. Reset by putting outdoor board in test
412Open High Pressure SwitchCheck system operating pressures and compare to unit charging charts.
413High Pressure Switch Strikes LockoutCheck system charge using approach and sub cooling temperatures. Reset by putting outdoor board in test
414High Discharge Line TemperatureCheck system operating pressures and compare to unit charging charts.
415High Discharge Line Temperature Strikes Lock-
416Outdoor Coil Sensor FaultySensor being detected open or shorted or out of temperature range. Board will not perform demand or time/tem-
417Discharge Sensor FaultyThe board detects open sensor or out of temperature sensor range. This fault is detected by allowing the unit to
418W Output Hardware FaultReplace the control board.
419W Output Hardware Fault Lockout
420Defrost Out of ControlDefrost longer than 20 minutes. Check HP operation.
421W External Miswire AlarmCheck and correct the wiring.
530Damper End Switch Failed to CloseRepair/replace damper.
531Damper End Switch Failed to OpenRepair/replace damper.
532Damper Control Module AlarmCheck/replace if needed.
594Discharge Air Temperature Sensor ProblemCheck wiring. Ohm out sensor and check to temperature/resistance chart.
700Comfort Sensor Temperature Sensor ProblemRecalibrate stat to clear, replace thermostat if needed.
701Comfort Sensor Temperature Too HighRecalibrate stat to clear, cool down stat, adjust setpoint, replace thermostat if needed.
702Comfort Sensor Temperature Too LowRecalibrate stat to clear, warm up stat, adjust setpoint, replace thermostat if needed.
703Comfort Sensor Humidity Sensor ProblemRecalibrate stat to clear, adjust setpoint, replace thermostat if needed.
704Comfort Sensor Humidity Too HighRecalibrate stat to clear, replace thermostat if needed.
705Comfort Sensor Humidity Too LowRecalibrate stat to clear replace thermostat if needed.
out
mode or resetting low voltage power.
mode or resetting low voltage power.
Check system charge using approach and sub cooling temperatures. Reset by putting outdoor board in test
mode or resetting low voltage power.
perature defrost operation. (System will still heat or cool).
run for 90 seconds before checking sensor resistance. If the sensor resistances not within range after 90 seconds, the board will count one fault. After 5 faults, the board will lockout.
DAS NOTE − The discharge air sensor
is intended to be mounted downstream
of the heat exchanger and air conditioning coil. It must be placed in free
airflow, where other accessories (such
as humidifiers, UV lights, etc.) will not
interfere with its accuracy. Wiring distance between the IFC or AHC and the
discharge air sensor should not exceed
10ft when wired with 18−gauge thermostat wire.
OAS NOTE − Wiring distance between
the IFC or AHC and the outdoor temperature sensor should not exceed
200ft when wired with 18−gauge thermostat wire.
Wiring Diagrams − Communicating Systems
icomfort
OPTIONAL DIS-
CHARGE AIR SEN-
SOR (SEE DAS
NOTE)
OPTIONAL OUT-
DOOR AIR SENSOR
(SEE OAS NOTE)
icomfort
THERMOSTAT
RSBus
FURNACE (IFC) OR AIR HANDLER (AHC)
icomfort
OUTDOOR AIR
CONDITIONING OR
HEAT PUMP UNIT
icomfort Thermostat
icomfort Indoor Furnace or Air Handler
icomfort Outdoor Condensing Unit or Heat Pump
506052−01 11/09
RSBus
Maximum total length of all connections
on the RSBus is limited to 1500ft.
Wire gauge of RSBus wire is 18.
Page 36
Wiring Diagrams − Communicating Indoor/non−Communicating Outdoor Systems
OPTIONAL DIS-
CHARGE AIR SEN-
SOR (SEE DAS
NOTE Page 36)
icomfort
THERMOSTAT
icomfort AIR HANDLER (AHC)
DOOR AIR SENSOR
OPTIONAL OUT-
(SEE OAS NOTE
Page 36)
icomfort FURNACE (IFC) OR AIR HANDLER (AHC)
OPTIONAL DIS-
CHARGE AIR SEN-
SOR (SEE DAS
NOTE Page 36)
icomfort
THERMOSTAT
OPTIONAL OUT-
DOOR AIR SENSOR
(SEE OAS NOTE
Page 36)
Maximum total
length of all connections on the RSBus
is limited to 1500ft.
Wire gauge of
RSBus wire is 18.
RSBus
icomfort Thermostat
icomfort Air Handler
Standard Outdoor Heat Pump
STANDARD
OUTDOOR HEAT
PUMP UNIT − 1
OR 2 STAGE
RSBus
Maximum total
length of all connections on the RSBus
is limited to 1500ft.
Wire gauge of
RSBus wire is 18.
icomfort Thermostat
icomfort Indoor Furnace or Air Handler
Standard Outdoor Condensing Unit
Optional Accessories for use with any icomfortt system
DISCHARGE AIR SENSOR
(REQUIRED FOR EVEN HEAT)
(SEE DAS NOTE Page 36)
icomfort
THERMOSTAT
icomfort
FURNACE (IFC) OR
AIR HANDLER (AHC)
NOTE: icomfort T’STAT SENSES HUMIDITY & CONTROLS 24V H" OUTPUT (& 120V H" OUTPUT) TO
CYCLE HUMIDIFIER BASED ON DEMAND. NO OTHER CONTROL OR HUMIDISTAT REQUIRED.
OPTIONAL OUTDOOR AIR SENSOR FOR USE WITH
HUMIDIFIER (IF NOT ALREADY IN THE SYSTEM FOR
OTHER FUNCTIONS. BUILT INTO ALL icomfort OUT-
DOOR UNITS). (SEE OAS NOTE Page 36)
NOTE: 24V UV LIGHT
APPLICATIONS
Neither icomfort furnace nor
icomfort air handler transformer
will have adequate VA to power
24V UV light applications. An
additional transformer for UV
light applications is required.
506052−01 11/09
Maximum total
length of all connections on the
RSBus is limited
to 1500ft.
Wire gauge of
RSBus wire is 18.
RSBus
Page 38
icomfort
FURNACE OR
AIR HANDLER
icomfort
FURNACE OR
AIR HANDLER
Optional Accessories for use with any icomfortt system
icomfort
FURNACE OR
HEPA BYPASS FIL-
TER X2680 HEPA
INTERLOCK KIT
LVCS VENTILATION
CONTROL SYSTEM
SEE LVCS VENTILATION
INSTRUCTIONS FOR DAMPER
& SENSOR WIRING
PASS INDOOR BLOWER
MOTOR COMMON WIRE
THROUGH CURRENT LOOP.