THIS APPLIANCE MUST BE INSTALLED BY A QUALIFIED INSTALLER.
READ ENTIRE MANUAL THOROUGHLY BEFORE INSTALLATION.
P/N 775004M, Rev. J, 11/03
IMPORTANT WARNINGS
CAUTION: PLEASE READ THIS ENTIRE MANUAL BEFORE YOU INSTALL AND USE YOUR NEW ROOM
HEATER. FOR YOUR SAFETY, FOLLOW THE INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS EXACTLY, WITHOUT DEVIATION. FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN
PROPERTY DAMAGE, BODILY INJURY, OR EVEN DEATH. IF THIS APPLIANCE IS NOT PROPERLY INSTALLED,
A HOUSE FIRE MAY RESULT. CONTACT YOUR LOCAL BUILDING OR FIRE OFFICIALS ABOUT RESTRICTIONS
AND INSTALLATION INSPECTION REQUIREMENTS IN YOUR AREA.
1. If utilizing an older chimney, it must be inspected
for adequate serviceability. Refer to the heading
Chimney Inspection on page 4.
2. Install only in masonry fireplaces, built to UBC
37 or ULC S628 standards or A factory built fireplace (built to UL 127 or ULC S610 standards).
3. The minimum clearances must be maintained for
all combustible surfaces and materials including;
furniture, carpet, drapes, clothing, wood, papers,
etc. Do not store firewood within this clearance
space. Failure to maintain clearances to all combustibles may result in a house fire.
4. This appliance requires a non-combustible fireplace hearth or hearth extension (see Floor Pro-tection on page 4 for additional information).
5. Minimum ceiling height must be 7 feet (213 cm)
(measured from base of appliance to ceiling).
6. DO NOT CONNECT THIS APPLIANCE TO A
CHIMNEY FLUE CONNECTED TO ANOTHER APPLIANCE.
7. Do not connect this appliance to air ducts or any
air distribution system.
8. Do not install appliance in a sleeping room.
9. PREVENT CREOSOTE FIRE: Inspect and clean
chimney frequently. Under certain conditions of
use, creosote buildup may occur rapidly. Inspect
chimney connector and chimney twice monthly
and clean if necessary. Using green or inadequately seasoned wood can greatly increase
creosote buildup. Use dry wood to minimize
creosote buildup.
10. USE SOLID WOOD FUEL ONLY: This appliance
is approved for burning dry seasoned natural
wood only. CAUTION: BURN UNTREATED
WOOD ONLY. DO NOT BURN GARBAGE OR
FLAMMABLE FLUIDS SUCH AS GASOLINE,
NAPHTHA OR ENGINE OIL.
11. Never use gasoline, gasoline-type lantern fuel,
kerosene, charcoal lighter fluid, or similar liquids to start or "freshen up" a fire in this heater.
Keep all such liquids well away from the heater
while it is in use.
12. DO NOT OVERFIRE: If heater or chimney con-
nector glows, you are overfiring. Overfiring this
appliance could cause a house fire. Overfiring is
a condition where the appliance is operated at
temperatures above its design capabilities.
Overfiring can be caused by improper installation, improper operation, lack of maintenance or
improper fuel usage. Damage caused from over-
PAGE 2
firing is NOT covered under the manufacturer's
limited warranty.
13. NEVER LEAVE AN UNATTENDED FIREPLACE
INSERT BURNING ON HIGH. Operation of the
fireplace insert with the primary air control at its
highest burn rate setting for extended periods
can cause dangerous overfiring conditions. The
primary air control should only be positioned at
the highest setting during start-up procedures
and for short duration. When leaving the fireplace insert unattended ensure that the primary
air control is set to the low or medium low
range.
14. The Start-Up Air Control must only be opened
(pulled out) during the start-up procedures.
CAUTION: OPERATION OF THE APPLIANCE
WITH THE START-UP AIR CONTROL IN THE
OPEN POSITION FOR EXTENDED PERIODS
CAN CAUSE DANGEROUS OVERFIRING CONDITIONS.
15. Use a metal container with a tight fitting lid to
dispose of ashes.
16. IN THE EVENT OF A COMPONENT FAILURE,
USE ONLY COMPONENTS PROVIDED BY THE
MANUFACTURER AS REPLACEMENT PARTS.
17. Burning any kind of fuel uses oxygen from the
dwelling. Be sure that you allow an adequate
source of fresh air into the room where the fireplace insert is operating (see Ventilation Re-quirements on page 5).
18. CAUTION: HOT WHILE IN OPERATION. An appliance hot enough to warm your home can severely burn anyone touching it. Keep children,
clothing and furniture away. Contact may cause
skin burns. Do not let children touch the appliance. Train them to stay a safe distance from
the appliance.
19. Do not operate this appliance without the firebox baffle plate properly installed.
20. Build fires directly upon the brick hearth inside
the fireplace insert. Do not use grates, irons or
any other method to elevate the fire.
21. See the listing label located on the back of fireplace (or see Safety / Listing Label on page 26).
22. SAVE THESE INSTRUCTIONS.
TABLE OF CONTENTS
Important Warnings .................................................2
Testing / Listing, EPA, Using this Manual................ 3
Planning Your Installation ..................................... 4-7
Ownership Records ................................................28
TESTING / LISTING
Model 2800HT has been tested to UL Standards
UL1482, ULC-5627 for installation into residential applications. The listing laboratory is OMNI Test Laboratories Inc, Beaverton, Oregon, Report #030-5-06-2.
EPA CERTIFICATION
This fireplace insert has been tested to rigorous emissions standard, and has been certified by the Environmental Protection Agency.
PACKAGING LIST
This appliance is packaged with an accessory package,
which contains the following:
One - Installation and operation instructions man-
ual.
One - Warranty
One - Marble set (for stove top and ash lip).
One - Insulation pad and strips. Place pad under
top marble and strips under ash lip marble.
USING THIS MANUAL
Please read and carefully follow all of the instructions
found in this manual. Please pay special attention to the
safety instructions provided in this manual. The Homeowner’s Care and Operation Instructions included here
will assure you have many years of dependable and
enjoyable service from your appliance.
CONGRATULATIONS ON THE PURCHASE OF
YOUR NEW WOOD BURNING FIREPLACE INSERT
MANUFACTURED BY LENNOX HEARTH PRODUCTS.
When you purchased your new insert, you joined
the ranks of thousands of concerned individuals
whose answer to their home heating needs reflects
their concern for aesthetics, efficiency and our environment. We extend our continued support to
help you achieve the maximum benefit and enjoyment available from your new insert.
It is our goal at Lennox Hearth Products to provide
you, our valued customer, with an appliance that
will ensure you years of trouble free warmth and
pleasure.
Thank you for selecting a Lennox Hearth Products
stove as the answer to your home heating needs.
Sincerely,
All of us at Lennox Hearth Products
PAGE 3
PLANNING YOUR INSTALLATION
QUESTIONS TO ASK LOCAL BUILDING OFFICIAL
A correct installation is critical and imperative for reducing fire hazards and perilous conditions that can arise
when wood burning appliances are improperly installed.
The installer must follow all of the manufacturer's instructions.
The installation of a wood burning appliance must conform to local codes and applicable state and federal
requirements. Familiarity with these requirements before installation is essential. Important considerations to
discuss with local building officials include:
In USA, NEC, ANSI / NFPA 70-1987.
In Canada, CSA C22.1
2. Local amendments?
3. Is a permit required - cost?
(You may wish to contact your insurance company
4. Rooms where the installation is not allowed?
SMOKE DETECTORS
Since there are always several potential sources of fire
in any home, we recommend installing smoke detectors. If possible, install the smoke detector in a hallway
adjacent to the room (to reduce the possibility of occasional false activation from the heat produced by the
fireplace insert). If your local code requires a smoke
detector be installed within the same room, you must
follow the requirements of your local code. Check with
your local building department for requirements in your
area.
IMPORTANT – THIS APPLIANCE IS NOT
PROVED FOR INSTALLATION INTO A MANUFACTURED (MOBILE) HOME IN CANADA OR IN THE
USA.
State or Regional Codes)
Electrical codes: The blower system has a
flexible electrical cord that must be electrically
grounded per local codes or per electrical codes:
WARNING: ELECTRICAL GROUNDING INSTRUCTIONS: THIS APPLIANCE IS
EQUIPPED WITH A THREE-PRONG
(GROUNDING) PLUG FOR YOUR PROTECTION AGAINST SHOCK HAZARD AND
SHOULD BE PLUGGED DIRECTLY INTO A
PROPERLY GROUNDED THREE-PRONG RECEPTACLE. DO NOT CUT OR REMOVE THE
GROUNDING PRONG FROM THIS PLUG. DO
NOT ROUTE POWER CORD UNDER OR IN
FRONT OF APPLIANCE.
to ask if they require this).
AP-
FLOOR PROTECTION
This appliance requires a heat resistant noncombustible approved fireplace hearth or hearth extension. If the floor protection is to be stone, tile, brick,
etc., it must be mortared or grouted to form a continuous non-combustible surface.
This protected area must extend a minimum of 18" (457
mm) to the front of the fuel door opening and 8" (203
mm) beyond both sides of the fuel door opening.
HEARTH PROTECTION
8" USA
9½" (241 mm) –
CANADA
18" (457 mm)
USA AND CANADA
8" USA
9½" (241 mm) –
CANADA
CHIMNEY INSPECTION
The existing fireplace should be inspected by a local fire
marshal or qualified installer for adequate serviceability
prior to installing this appliance.
Factory built fireplace (not approved in Canada): If
any portion of the chimney system shows signs of
structural or mechanical weaknesses, such as:
cracks, leaky joints, corroded or warped surfaces.
Look for obvious bulges in the lining, which may indicate the need to replace that section (use a bright
flashlight. Any faulty portion must be repaired or replaced prior to installing this appliance. Also, inspect
the attic to see that the chimney has proper clearance
to combustible framing members.
Masonry fireplace: The chimney should have no
cracks, loose mortar, other signs of deterioration, or
blockage. Any necessary repairs should be done by a
qualified mason.
If the existing fireplace flue system is dirty or has some
obstruction in it, clean it. A dirty chimney can cause
your insert to smoke when refueling, and can result in a
chimney fire. An oversized chimney may result in less
than optimum performance. Installations into a large
masonry chimney may require a liner to improve performance.
PAGE 4
PLANNING YOUR INSTALLATION
CLEARANCES
WARNING: IT IS VERY IMPORTANT THAT YOU
OBSERVE THE MINIMUM CLEARANCES. DO NOT
STORE FIREWOOD WITHIN THIS CLEARANCE
SPACE. FAILURE TO MAINTAIN CLEARANCES TO
ALL COMBUSTIBLES MAY RESULT IN A HOUSE
FIRE.
There are listed clearances for your fireplace insert,
which were determined in a Laboratory testing and
must be maintained.
Stove top to mantel: 27" (686 mm)
Stove top to trim: 16" (406 mm)
Stove side to trim: 6" (152 mm)
Stove side to sidewall: 6" (152 mm)
For installation with a combustible mantel or top trim,
Part #16101 deflector must be installed.
DRAFT REQUIREMENTS
The appliance is merely one component of a larger system. The other equally important component is the venting system. This is necessary for achieving the required
flow of combustion air to the fire chamber and for safely
removing unwanted combustion byproducts from the
appliance. If the venting system's design does not promote these ends, the system may not function properly.
Poorly functioning venting systems may create performance problems as well as be a safety hazard (i.e.
an oversized chimney may result in less than optimum
performance. Installations into a large, masonry chimney may require a liner to improve performance). A
draft test should read greater than .04' W.C. (inches
water column) and less than .08" W.C.
American National Standards Institute ANSI/NFPA 211-92,
draft 1-7: A chimney or vent shall be so designed and constructed to develop a flow sufficient to completely remove all
flue and vent gases to the outside atmosphere. The venting
system shall satisfy the draft requirements of the connected
appliance in accordance with the manufacturer’s instructions.
PROVIDE ADEQUATE AIR FOR COMBUSTION
In well insulated and weather tight homes, it may be
difficult to establish a good draft up your chimney. The
poor draft is caused by a shortage of air in the house.
To provide the needed air, crack a window on the windward side of the house.
VENTILATION REQUIREMENTS
THE FRESH AIR REQUIREMENTS OF THIS APPLIANCE MUST BE MET WITHIN THE SPACE WHERE
IT WILL BE INSTALLED.
Ventilation is essential when using a solid fuel burning
heater. The combustion process of this heater uses
oxygen from inside the dwelling and it may be necessary to open a window or install a vent to provide makeup air into a dwelling that is well insulated (modern construction standards have resulted in homes that are
highly energy-efficient and that allow little heat loss and
air transfer). Other appliances in the dwelling also contribute to removing air from the dwelling (i.e. clothes
dryers, exhaust fans, fireplaces, and other fuel burning
appliances). If the available fresh air delivery in the
dwelling is insufficient to support the demands of these
appliances, problems can result (i.e. excessive negative
pressure can develop in the dwelling which will affect
the rate at which this appliance can draft. See Draft Re-quirements on this page).
PAGE 5
PLANNING YOUR INSTALLATION
FACTORY BUILT FIREPLACES
(Not Approved In Canada)
In the USA, this appliance is approved for installation
into a listed factory built solid fuel burning fireplace (built
to UL 127 or ULC S610 standards). The fireplace firebox must accept the insert without modification other
than removing bolted or screwed together pieces such
as smoke shelf / deflectors, ash lips, screen or door
tracks and damper assemblies, that must be reinstalled
to restore the fireplace to its original operating condition
if the insert is removed and not replaced. The removal
of any part must not alter the integrity or outer shell of
the pre-engineered fireplace cabinet in any way.
Venting Requirements for factory built fireplace:
The fireplace damper must be secured in the open position. This appliance requires the use of a 6” (152 mm)
diameter flex or rigid, UL1777 listed 2100° HT liner or
equivalent. The liner must extend from the flue outlet of
the appliance to termination. Do not face seal over fireplace chimney cooling air systems. Offsets can be handled with an offset adapter (it aligns starter pipe with
fireplace flue). For more information on the offset
adapter, see pages 10 and 26.
WARNING: DO NOT SUBSTITUTE THE HEAT
RATED 2100°HT LINER WITH ANY OTHER TYPE
LINE OR A FIRE MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS
OF LIFE.
Factory Built Fireplace Installation
PAGE 6
PLANNING YOUR INSTALLATION
MASONRY FIREPLACES
This appliance is approved for installation into a masonry fireplace built to UBC 37 or ULC S628 standards.
Do not remove brick or mortar form the masonry fireplace to accommodate this appliance. If the fireplace
has been modified to accommodate the fireplace insert,
a metal tag documenting what was modified must be
attached to the fireplace (as required by Clause 5.1.11
it must be secured using screws or nails to the fireplace, in a location readily visible should the fireplace
insert be removed). The lettering shall not be less than
5 mm high.
THIS FIREPLACE HAS BEEN ALTERED TO ACCOMMODATE A FIREPLACE INSERT AND
SHOULD BE INSPECTED BY A QUALIFIED PERSON PRIOR TO RE-USE AS A CONVENTIONAL
FIREPLACE
IMPORTANT: Any opening between the masonry of
the fireplace and the facing masonry must be permanently sealed.
USA Requirements / Masonry Fireplaces - The fire-
place damper must be secured in the open position. In
the USA, a flue extension past the fireplace header is
required as a minimum. A preferred installation is a
positive flue connection (sealing the throat of the chimney). This appliance requires the use of a 6” (152 mm)
diameter flex or rigid single wall pipe, minimum 24 / 25
MSG black or blued steel connector pipe (stainless
steel recommended).
Canada Requirements / Masonry Fireplaces - – This
fireplace insert must be installed into an approved solid
fuel Masonry
built fireplace is not approved). The fireplace damper
must be secured in the open position. The fireplace insert must be installed with a continuous chimney liner of
6” / 152 mm diameter extending from the fireplace insert to the top of the chimney. The chimney liner must
conform to the Class 3 requirements of CAN / ULC –
S635, Standard for Lining Systems for Existing Masonry
or Factory-Built Chimneys and Vents, or CAN / ULC –
S640 Standard for Lining Systems for New Masonry
Chimneys.
fireplace only (installation into a factory
Metal Tag
Offsets
Offsets can be handled with an offset adapter (it aligns
starter pipe with fireplace flue). For more information
on the offset adapter, see pages 10 and 26.
FIREPLACE CHIMNEY MAXIMUM SIZE TO ENSURE
PROPER DRAFT – USA ONLY
Note: Installations in Canada require a full length liner.
The fireplace insert flue size is 6 inches (152 mm) diameter, which is approximately 28 square inches (711
square mm), the minimum. The maximum flue size
should be no more than (3) three times the cross sectional area of the size of the fireplace insert flue collar.
In this case, that would be no larger than a 10 inch (254
mm) diameter stack (area = approx. 85 sq. inches [216
sq. cm]).
Note: Formulas for calculating Area:
Calculating area of a circle:
2
π x r
= Area (π = 3.1416, r = 1/2 diameter)
To calculate area of square or rectangle:
Width x Depth = Area
Notes:
It may be necessary to use a full-length liner to
achieve adequate draft for the appliance. A draft
gauge should read more than .04 W.C.I, but less than
.08 W.C.I. for optimum performance.
This appliance is approved for all heatform style
fireplaces (masonry fireplace with a metal firebox liner).
PAGE 7
INSTALLATION
FIREPLACE INSTALLATION
CHIMNEY
TERMINATION CAP
ENSURE CHIMNEY
IS SOUND
MASONRY FIREPLACE:
USA APPROVED LINER –
6” DIA. FLEX OR
RIGID 24/26 MSG BLACK OR
BLUED STEEL PIPE OR 2100°
HT LINER
CANADA APPROVED LINER –
S635 FLUE LINER
FACTORY BUILT (ZC)
FIREPLACE (USA ONLY) –
APPROVED LINER – 6” DIAMETER 2100° HT LINER
PLACE DAMPER OR
REMOVE FIRE-
SECURE OPEN
• USA only - All masonry fireplace installations require a minimum positive flue connection using a
block-off plate or a positive seal past the bottom of
the chimney flue tile liner. In Canada, a full reline
is required.
• Measure fireplace size to make certain the insert
will fit before considering the installation.
MASONRY FIREPLACE REQUIREMENTS - This appli-
ance may be installed in a masonry fireplace with an opening height of at least 21 inches (533 mm) using Masonry
Fireplace Kit P/N 14M75. Installation into a masonry fireplace with an opening of 24” (610 mm) or higher does not
require this header insulation kit. See page 26 for ordering
information.
Masonry Fireplace Minimum Firebox Dimensions
Minimum size required for fireplace firebox (recessed
area into fireplace):
Height 21” (533 mm)
Width at front of fireplace 24 1/4” (616 mm)
Width at back of fireplace 23 1/4” (591 mm)
Depth into fireplace 15 3/4” (400 mm)
FACTORY BUILT FIREPLACE REQUIREMENTS – Note:
In Canada, installation into a Factory Built Fireplace is not
approved. When installing the 2800HT into a "high dome"
or "low profile" type factory built fireplace (ZC), a ZC Fireplace kit is required (kit consists of components to insulate
and allow for heat dissipation). See page 26 for ordering
information.
Factory Fireplace Minimum Firebox Dimensions
Minimum size required for fireplace firebox (recessed
area into fireplace):
Min. unrestricted front opening: 21” (533 mm)
Min. inside firebox height at flue opening: 22” (559 mm)
Width at front of fireplace 24 1/4” (616 mm)
Width at back of fireplace 23 1/4” (591 mm)
Depth into fireplace 15 3/4” (400 mm)
Side View of Typical Factory-Built Fireplaces
PAGE 8
Do not face seal over
chimney cooling air system.
INSTALLATION
POWER CORD CHANGEOVER
DANGER: Risk of electrical shock. Disconnect
power before servicing appliance. Do not route
power cord under or in front of appliance.
To change the power cord from one side of insert to the
other, perform the following steps:
1. Ensure power cord in NOT
2. Remove the louver blower panels on each side of
fuel door as follows. Each panel is held in place by
two ¼” (7 mm) head screws. Using a ¼” (7 mm)
socket or nut driver, remove the screws
3. Remove panels by pulling them outward slightly then
forward.
4. Locate terminal block on right side of appliance.
Write down the locations where the black, white and
green leads from the power cord are attached to the
terminal block. Disconnect these three wires then reinstall them onto the terminal block on the left side of
appliance in the same corresponding positions (as
you had written down).
5. Reinstall panels.
BAFFLE PLATE
This appliance has a very heavy (60 lbs [27 kg]) 3/8" (9.5
mm) thick steel baffle that is installed directly above the
secondary air tubes in the firebox. To inhibit the baffle
plate from shifting during shipment, a packing block is
installed at the factory (see illustration below). The packing block needs to be removed prior to burning your insert. During installation, the baffle may slide forward, and
must be repositioned (pushed to the back) in order for
the insert to operate properly. When in its proper position, the rear flange of the baffle plate should be flush to
the back wall of the firebox.
plugged in.
MARBLE
Marble is a natural product and therefore each piece will
have its own unique character. Marble can be scratched
so care should be taken to avoid putting heavy or rough
objects (trivet / steamers) on the surface. Do not install
the marble before curing the paint.
The ceramic fiber blanket and cerawool strips provided
with appliance must be placed under the marble to insulate it from the high temperatures on top of the firebox.
Do not place the marble directly on the top metal surface
of the stove or it will crack.
INSTALLATION STEPS
1. Remove all ashes from the fireplace.
2. Remove all materials inside the insert and set them aside.
3. Remove the three-piece surround assembly (face shield)
and attach insulation material provided using a nonflammable adhesive (i.e. RTV Silicone, rated 570° F).
4. Use a large piece of cardboard or other protective material
and place it in front of the fireplace to protect floor or carpet
during installation.
5. Remove the insert from its wood pallet by removing the
screws.
6. Prepare chimney connection system as specified for masonry or zero clearance fireplaces.
7. Set the insert on the protective cardboard laid out in front of
the fireplace centered in front of the fireplace opening.
8. (Masonry Fireplace) Slide insert into the fireplace far enough
to attach the starter pipe or positive flue connection (a minimum of a 6" (152 mm) starter pipe extending past the
header is required). See * note, page 11.
9. (Factory Built Fireplace – USA only) Slide insert into the fireplace far enough to attach connector to flue outlet. See *
note, page 11.
PAGE 9
Loading...
+ 20 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.