Lennox 2800HT User Manual

EPA CERTIFIED
WOOD BURNING
FIREPLACE INSERT
RETAIN THESE
INSTRUCTIONS
FOR FUTURE
REFERENCE
INSTALLATION AND OPERATION
MANUAL
MODEL 2800HT
THIS APPLIANCE MUST BE INSTALLED BY A QUALIFIED INSTALLER.
READ ENTIRE MANUAL THOROUGHLY BEFORE INSTALLATION.
P/N 775004M, Rev. J, 11/03
IMPORTANT WARNINGS
CAUTION: PLEASE READ THIS ENTIRE MANUAL BEFORE YOU INSTALL AND USE YOUR NEW ROOM HEATER. FOR YOUR SAFETY, FOLLOW THE INSTALLATION, OPERATION AND MAINTENANCE INSTRUC­TIONS EXACTLY, WITHOUT DEVIATION. FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN PROPERTY DAMAGE, BODILY INJURY, OR EVEN DEATH. IF THIS APPLIANCE IS NOT PROPERLY INSTALLED, A HOUSE FIRE MAY RESULT. CONTACT YOUR LOCAL BUILDING OR FIRE OFFICIALS ABOUT RESTRICTIONS AND INSTALLATION INSPECTION REQUIREMENTS IN YOUR AREA.
1. If utilizing an older chimney, it must be inspected for adequate serviceability. Refer to the heading Chimney Inspection on page 4.
2. Install only in masonry fireplaces, built to UBC 37 or ULC S628 standards or A factory built fire­place (built to UL 127 or ULC S610 standards).
3. The minimum clearances must be maintained for all combustible surfaces and materials including; furniture, carpet, drapes, clothing, wood, papers, etc. Do not store firewood within this clearance space. Failure to maintain clearances to all com­bustibles may result in a house fire.
4. This appliance requires a non-combustible fire­place hearth or hearth extension (see Floor Pro- tection on page 4 for additional information).
5. Minimum ceiling height must be 7 feet (213 cm) (measured from base of appliance to ceiling).
6. DO NOT CONNECT THIS APPLIANCE TO A CHIMNEY FLUE CONNECTED TO ANOTHER AP­PLIANCE.
7. Do not connect this appliance to air ducts or any air distribution system.
8. Do not install appliance in a sleeping room.
9. PREVENT CREOSOTE FIRE: Inspect and clean chimney frequently. Under certain conditions of use, creosote buildup may occur rapidly. Inspect chimney connector and chimney twice monthly and clean if necessary. Using green or inade­quately seasoned wood can greatly increase creosote buildup. Use dry wood to minimize creosote buildup.
10. USE SOLID WOOD FUEL ONLY: This appliance
is approved for burning dry seasoned natural wood only. CAUTION: BURN UNTREATED WOOD ONLY. DO NOT BURN GARBAGE OR FLAMMABLE FLUIDS SUCH AS GASOLINE, NAPHTHA OR ENGINE OIL.
11. Never use gasoline, gasoline-type lantern fuel,
kerosene, charcoal lighter fluid, or similar liq­uids to start or "freshen up" a fire in this heater. Keep all such liquids well away from the heater while it is in use.
12. DO NOT OVERFIRE: If heater or chimney con-
nector glows, you are overfiring. Overfiring this appliance could cause a house fire. Overfiring is a condition where the appliance is operated at temperatures above its design capabilities. Overfiring can be caused by improper installa­tion, improper operation, lack of maintenance or improper fuel usage. Damage caused from over-
PAGE 2
firing is NOT covered under the manufacturer's limited warranty.
13. NEVER LEAVE AN UNATTENDED FIREPLACE INSERT BURNING ON HIGH. Operation of the fireplace insert with the primary air control at its highest burn rate setting for extended periods can cause dangerous overfiring conditions. The primary air control should only be positioned at the highest setting during start-up procedures and for short duration. When leaving the fire­place insert unattended ensure that the primary air control is set to the low or medium low range.
14. The Start-Up Air Control must only be opened (pulled out) during the start-up procedures. CAUTION: OPERATION OF THE APPLIANCE WITH THE START-UP AIR CONTROL IN THE OPEN POSITION FOR EXTENDED PERIODS CAN CAUSE DANGEROUS OVERFIRING CON­DITIONS.
15. Use a metal container with a tight fitting lid to dispose of ashes.
16. IN THE EVENT OF A COMPONENT FAILURE, USE ONLY COMPONENTS PROVIDED BY THE MANUFACTURER AS REPLACEMENT PARTS.
17. Burning any kind of fuel uses oxygen from the dwelling. Be sure that you allow an adequate source of fresh air into the room where the fire­place insert is operating (see Ventilation Re- quirements on page 5).
18. CAUTION: HOT WHILE IN OPERATION. An ap­pliance hot enough to warm your home can se­verely burn anyone touching it. Keep children, clothing and furniture away. Contact may cause skin burns. Do not let children touch the appli­ance. Train them to stay a safe distance from the appliance.
19. Do not operate this appliance without the fire­box baffle plate properly installed.
20. Build fires directly upon the brick hearth inside the fireplace insert. Do not use grates, irons or any other method to elevate the fire.
21. See the listing label located on the back of fire­place (or see Safety / Listing Label on page 26).
22. SAVE THESE INSTRUCTIONS.
TABLE OF CONTENTS
Important Warnings .................................................2
Testing / Listing, EPA, Using this Manual................ 3
Planning Your Installation ..................................... 4-7
Installation .......................................................... 8-12
Product Features and Controls ..............................12
Care and Operation ......................................... 13-15
Recommended Fuel ...............................................16
Maintenance ..................................................... 16-18
Troubleshooting ................................................ 19-20
Specifications..........................................................21
Replacement Parts List..................................... 22-24
Optional Accessories ..............................................25
Safety / Listing Label...............................................26
EPA Label ...............................................................27
Ownership Records ................................................28
TESTING / LISTING
Model 2800HT has been tested to UL Standards UL1482, ULC-5627 for installation into residential appli­cations. The listing laboratory is OMNI Test Laborato­ries Inc, Beaverton, Oregon, Report #030-5-06-2.
EPA CERTIFICATION
This fireplace insert has been tested to rigorous emis­sions standard, and has been certified by the Environ­mental Protection Agency.
PACKAGING LIST
This appliance is packaged with an accessory package, which contains the following:
One - Installation and operation instructions man-
ual. One - Warranty One - Marble set (for stove top and ash lip). One - Insulation pad and strips. Place pad under
top marble and strips under ash lip marble.
USING THIS MANUAL
Please read and carefully follow all of the instructions found in this manual. Please pay special attention to the safety instructions provided in this manual. The Home­owner’s Care and Operation Instructions included here will assure you have many years of dependable and enjoyable service from your appliance.
CONGRATULATIONS ON THE PURCHASE OF YOUR NEW WOOD BURNING FIREPLACE INSERT MANUFACTURED BY LENNOX HEARTH PROD­UCTS.
When you purchased your new insert, you joined the ranks of thousands of concerned individuals whose answer to their home heating needs reflects their concern for aesthetics, efficiency and our en­vironment. We extend our continued support to help you achieve the maximum benefit and enjoy­ment available from your new insert.
It is our goal at Lennox Hearth Products to provide you, our valued customer, with an appliance that will ensure you years of trouble free warmth and pleasure.
Thank you for selecting a Lennox Hearth Products stove as the answer to your home heating needs.
Sincerely, All of us at Lennox Hearth Products
PAGE 3
PLANNING YOUR INSTALLATION
QUESTIONS TO ASK LOCAL BUILDING OFFICIAL
A correct installation is critical and imperative for reduc­ing fire hazards and perilous conditions that can arise when wood burning appliances are improperly installed. The installer must follow all of the manufacturer's in­structions.
The installation of a wood burning appliance must con­form to local codes and applicable state and federal requirements. Familiarity with these requirements be­fore installation is essential. Important considerations to discuss with local building officials include:
1. Applicable codes (i.e. Uniform Mechanical Code,
In USA, NEC, ANSI / NFPA 70-1987. In Canada, CSA C22.1
2. Local amendments?
3. Is a permit required - cost? (You may wish to contact your insurance company
4. Rooms where the installation is not allowed?
SMOKE DETECTORS Since there are always several potential sources of fire in any home, we recommend installing smoke detec­tors. If possible, install the smoke detector in a hallway adjacent to the room (to reduce the possibility of occa­sional false activation from the heat produced by the fireplace insert). If your local code requires a smoke detector be installed within the same room, you must follow the requirements of your local code. Check with your local building department for requirements in your area.
IMPORTANT – THIS APPLIANCE IS NOT PROVED FOR INSTALLATION INTO A MANUFAC­TURED (MOBILE) HOME IN CANADA OR IN THE USA.
State or Regional Codes)
Electrical codes: The blower system has a flexible electrical cord that must be electrically grounded per local codes or per electrical codes:
WARNING: ELECTRICAL GROUNDING IN­STRUCTIONS: THIS APPLIANCE IS EQUIPPED WITH A THREE-PRONG (GROUNDING) PLUG FOR YOUR PROTEC­TION AGAINST SHOCK HAZARD AND SHOULD BE PLUGGED DIRECTLY INTO A PROPERLY GROUNDED THREE-PRONG RE­CEPTACLE. DO NOT CUT OR REMOVE THE GROUNDING PRONG FROM THIS PLUG. DO NOT ROUTE POWER CORD UNDER OR IN FRONT OF APPLIANCE.
to ask if they require this).
AP-
FLOOR PROTECTION
This appliance requires a heat resistant non­combustible approved fireplace hearth or hearth exten­sion. If the floor protection is to be stone, tile, brick, etc., it must be mortared or grouted to form a continu­ous non-combustible surface.
This protected area must extend a minimum of 18" (457 mm) to the front of the fuel door opening and 8" (203 mm) beyond both sides of the fuel door opening.
HEARTH PROTECTION
8" USA
9½" (241 mm) –
CANADA
18" (457 mm)
USA AND CANADA
8" USA
9½" (241 mm) –
CANADA
CHIMNEY INSPECTION
The existing fireplace should be inspected by a local fire marshal or qualified installer for adequate serviceability prior to installing this appliance.
Factory built fireplace (not approved in Canada): If any portion of the chimney system shows signs of structural or mechanical weaknesses, such as: cracks, leaky joints, corroded or warped surfaces. Look for obvious bulges in the lining, which may indi­cate the need to replace that section (use a bright flashlight. Any faulty portion must be repaired or re­placed prior to installing this appliance. Also, inspect the attic to see that the chimney has proper clearance to combustible framing members.
Masonry fireplace: The chimney should have no cracks, loose mortar, other signs of deterioration, or blockage. Any necessary repairs should be done by a qualified mason.
If the existing fireplace flue system is dirty or has some obstruction in it, clean it. A dirty chimney can cause your insert to smoke when refueling, and can result in a chimney fire. An oversized chimney may result in less than optimum performance. Installations into a large masonry chimney may require a liner to improve per­formance.
PAGE 4
PLANNING YOUR INSTALLATION
CLEARANCES
WARNING: IT IS VERY IMPORTANT THAT YOU OBSERVE THE MINIMUM CLEARANCES. DO NOT STORE FIREWOOD WITHIN THIS CLEARANCE SPACE. FAILURE TO MAINTAIN CLEARANCES TO ALL COMBUSTIBLES MAY RESULT IN A HOUSE FIRE.
There are listed clearances for your fireplace insert, which were determined in a Laboratory testing and must be maintained.
Stove top to mantel: 27" (686 mm) Stove top to trim: 16" (406 mm) Stove side to trim: 6" (152 mm) Stove side to sidewall: 6" (152 mm)
For installation with a combustible mantel or top trim, Part #16101 deflector must be installed.
DRAFT REQUIREMENTS The appliance is merely one component of a larger sys­tem. The other equally important component is the vent­ing system. This is necessary for achieving the required flow of combustion air to the fire chamber and for safely removing unwanted combustion byproducts from the appliance. If the venting system's design does not pro­mote these ends, the system may not function properly. Poorly functioning venting systems may create per­formance problems as well as be a safety hazard (i.e. an oversized chimney may result in less than optimum performance. Installations into a large, masonry chim­ney may require a liner to improve performance). A draft test should read greater than .04' W.C. (inches water column) and less than .08" W.C.
American National Standards Institute ANSI/NFPA 211-92, draft 1-7: A chimney or vent shall be so designed and con­structed to develop a flow sufficient to completely remove all flue and vent gases to the outside atmosphere. The venting system shall satisfy the draft requirements of the connected appliance in accordance with the manufacturer’s instructions.
PROVIDE ADEQUATE AIR FOR COMBUSTION In well insulated and weather tight homes, it may be difficult to establish a good draft up your chimney. The poor draft is caused by a shortage of air in the house. To provide the needed air, crack a window on the wind­ward side of the house.
VENTILATION REQUIREMENTS
THE FRESH AIR REQUIREMENTS OF THIS APPLI­ANCE MUST BE MET WITHIN THE SPACE WHERE IT WILL BE INSTALLED.
Ventilation is essential when using a solid fuel burning heater. The combustion process of this heater uses oxygen from inside the dwelling and it may be neces­sary to open a window or install a vent to provide make­up air into a dwelling that is well insulated (modern con­struction standards have resulted in homes that are highly energy-efficient and that allow little heat loss and air transfer). Other appliances in the dwelling also con­tribute to removing air from the dwelling (i.e. clothes dryers, exhaust fans, fireplaces, and other fuel burning appliances). If the available fresh air delivery in the dwelling is insufficient to support the demands of these appliances, problems can result (i.e. excessive negative pressure can develop in the dwelling which will affect the rate at which this appliance can draft. See Draft Re- quirements on this page).
PAGE 5
PLANNING YOUR INSTALLATION
FACTORY BUILT FIREPLACES (Not Approved In Canada)
In the USA, this appliance is approved for installation into a listed factory built solid fuel burning fireplace (built to UL 127 or ULC S610 standards). The fireplace fire­box must accept the insert without modification other than removing bolted or screwed together pieces such as smoke shelf / deflectors, ash lips, screen or door tracks and damper assemblies, that must be reinstalled to restore the fireplace to its original operating condition if the insert is removed and not replaced. The removal of any part must not alter the integrity or outer shell of the pre-engineered fireplace cabinet in any way.
Venting Requirements for factory built fireplace:
The fireplace damper must be secured in the open po­sition. This appliance requires the use of a 6” (152 mm) diameter flex or rigid, UL1777 listed 2100° HT liner or equivalent. The liner must extend from the flue outlet of the appliance to termination. Do not face seal over fire­place chimney cooling air systems. Offsets can be han­dled with an offset adapter (it aligns starter pipe with fireplace flue). For more information on the offset adapter, see pages 10 and 26.
WARNING: DO NOT SUBSTITUTE THE HEAT RATED 2100°HT LINER WITH ANY OTHER TYPE LINE OR A FIRE MAY RESULT CAUSING PROP­ERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
Factory Built Fireplace Installation
PAGE 6
PLANNING YOUR INSTALLATION
MASONRY FIREPLACES
This appliance is approved for installation into a ma­sonry fireplace built to UBC 37 or ULC S628 standards. Do not remove brick or mortar form the masonry fire­place to accommodate this appliance. If the fireplace has been modified to accommodate the fireplace insert, a metal tag documenting what was modified must be attached to the fireplace (as required by Clause 5.1.11 it must be secured using screws or nails to the fire­place, in a location readily visible should the fireplace insert be removed). The lettering shall not be less than
5 mm high.
THIS FIREPLACE HAS BEEN ALTERED TO AC­COMMODATE A FIREPLACE INSERT AND SHOULD BE INSPECTED BY A QUALIFIED PER­SON PRIOR TO RE-USE AS A CONVENTIONAL FIREPLACE
IMPORTANT: Any opening between the masonry of the fireplace and the facing masonry must be per­manently sealed.
USA Requirements / Masonry Fireplaces - The fire-
place damper must be secured in the open position. In the USA, a flue extension past the fireplace header is required as a minimum. A preferred installation is a positive flue connection (sealing the throat of the chim­ney). This appliance requires the use of a 6” (152 mm) diameter flex or rigid single wall pipe, minimum 24 / 25 MSG black or blued steel connector pipe (stainless steel recommended).
Canada Requirements / Masonry Fireplaces - – This fireplace insert must be installed into an approved solid fuel Masonry built fireplace is not approved). The fireplace damper must be secured in the open position. The fireplace in­sert must be installed with a continuous chimney liner of 6” / 152 mm diameter extending from the fireplace in­sert to the top of the chimney. The chimney liner must conform to the Class 3 requirements of CAN / ULC – S635, Standard for Lining Systems for Existing Masonry or Factory-Built Chimneys and Vents, or CAN / ULC – S640 Standard for Lining Systems for New Masonry Chimneys.
fireplace only (installation into a factory
Metal Tag
Offsets
Offsets can be handled with an offset adapter (it aligns starter pipe with fireplace flue). For more information on the offset adapter, see pages 10 and 26.
FIREPLACE CHIMNEY MAXIMUM SIZE TO ENSURE PROPER DRAFT – USA ONLY
Note: Installations in Canada require a full length liner. The fireplace insert flue size is 6 inches (152 mm) di­ameter, which is approximately 28 square inches (711 square mm), the minimum. The maximum flue size should be no more than (3) three times the cross sec­tional area of the size of the fireplace insert flue collar. In this case, that would be no larger than a 10 inch (254 mm) diameter stack (area = approx. 85 sq. inches [216 sq. cm]).
Note: Formulas for calculating Area:
Calculating area of a circle:
2
π x r
= Area (π = 3.1416, r = 1/2 diameter)
To calculate area of square or rectangle: Width x Depth = Area
Notes: It may be necessary to use a full-length liner to
achieve adequate draft for the appliance. A draft gauge should read more than .04 W.C.I, but less than .08 W.C.I. for optimum performance.
This appliance is approved for all heatform style
fireplaces (masonry fireplace with a metal fire­box liner).
PAGE 7
INSTALLATION
FIREPLACE INSTALLATION
CHIMNEY
TERMINATION CAP
ENSURE CHIMNEY
IS SOUND
MASONRY FIREPLACE:
USA APPROVED LINER – 6” DIA. FLEX OR RIGID 24/26 MSG BLACK OR BLUED STEEL PIPE OR 2100° HT LINER
CANADA APPROVED LINER – S635 FLUE LINER
FACTORY BUILT (ZC) FIREPLACE (USA ONLY) –
APPROVED LINER – 6” DI­AMETER 2100° HT LINER
PLACE DAMPER OR
REMOVE FIRE-
SECURE OPEN
USA only - All masonry fireplace installations re­quire a minimum positive flue connection using a block-off plate or a positive seal past the bottom of the chimney flue tile liner. In Canada, a full reline is required.
Measure fireplace size to make certain the insert will fit before considering the installation.
MASONRY FIREPLACE REQUIREMENTS - This appli-
ance may be installed in a masonry fireplace with an open­ing height of at least 21 inches (533 mm) using Masonry Fireplace Kit P/N 14M75. Installation into a masonry fire­place with an opening of 24” (610 mm) or higher does not require this header insulation kit. See page 26 for ordering information.
Masonry Fireplace Minimum Firebox Dimensions Minimum size required for fireplace firebox (recessed area into fireplace):
Height 21” (533 mm) Width at front of fireplace 24 1/4” (616 mm) Width at back of fireplace 23 1/4” (591 mm) Depth into fireplace 15 3/4” (400 mm)
FACTORY BUILT FIREPLACE REQUIREMENTSNote: In Canada, installation into a Factory Built Fireplace is not approved. When installing the 2800HT into a "high dome" or "low profile" type factory built fireplace (ZC), a ZC Fire­place kit is required (kit consists of components to insulate and allow for heat dissipation). See page 26 for ordering information.
Factory Fireplace Minimum Firebox Dimensions Minimum size required for fireplace firebox (recessed area into fireplace):
Min. unrestricted front opening: 21” (533 mm) Min. inside firebox height at flue opening: 22” (559 mm) Width at front of fireplace 24 1/4” (616 mm) Width at back of fireplace 23 1/4” (591 mm) Depth into fireplace 15 3/4” (400 mm)
Side View of Typical Factory-Built Fireplaces
PAGE 8
Do not face seal over
chimney cooling air system.
INSTALLATION
POWER CORD CHANGEOVER
DANGER: Risk of electrical shock. Disconnect power before servicing appliance. Do not route power cord under or in front of appliance.
To change the power cord from one side of insert to the other, perform the following steps:
1. Ensure power cord in NOT
2. Remove the louver blower panels on each side of fuel door as follows. Each panel is held in place by two ¼” (7 mm) head screws. Using a ¼” (7 mm) socket or nut driver, remove the screws
3. Remove panels by pulling them outward slightly then forward.
4. Locate terminal block on right side of appliance. Write down the locations where the black, white and green leads from the power cord are attached to the terminal block. Disconnect these three wires then re­install them onto the terminal block on the left side of appliance in the same corresponding positions (as you had written down).
5. Reinstall panels.
BAFFLE PLATE
This appliance has a very heavy (60 lbs [27 kg]) 3/8" (9.5 mm) thick steel baffle that is installed directly above the secondary air tubes in the firebox. To inhibit the baffle plate from shifting during shipment, a packing block is installed at the factory (see illustration below). The pack­ing block needs to be removed prior to burning your in­sert. During installation, the baffle may slide forward, and must be repositioned (pushed to the back) in order for the insert to operate properly. When in its proper posi­tion, the rear flange of the baffle plate should be flush to the back wall of the firebox.
plugged in.
MARBLE Marble is a natural product and therefore each piece will have its own unique character. Marble can be scratched so care should be taken to avoid putting heavy or rough objects (trivet / steamers) on the surface. Do not install the marble before curing the paint.
The ceramic fiber blanket and cerawool strips provided with appliance must be placed under the marble to insu­late it from the high temperatures on top of the firebox. Do not place the marble directly on the top metal surface of the stove or it will crack.
INSTALLATION STEPS
1. Remove all ashes from the fireplace.
2. Remove all materials inside the insert and set them aside.
3. Remove the three-piece surround assembly (face shield) and attach insulation material provided using a nonflamma­ble adhesive (i.e. RTV Silicone, rated 570° F).
4. Use a large piece of cardboard or other protective material and place it in front of the fireplace to protect floor or carpet during installation.
5. Remove the insert from its wood pallet by removing the screws.
6. Prepare chimney connection system as specified for ma­sonry or zero clearance fireplaces.
7. Set the insert on the protective cardboard laid out in front of the fireplace centered in front of the fireplace opening.
8. (Masonry Fireplace) Slide insert into the fireplace far enough to attach the starter pipe or positive flue connection (a mini­mum of a 6" (152 mm) starter pipe extending past the header is required). See * note, page 11.
9. (Factory Built Fireplace – USA only) Slide insert into the fire­place far enough to attach connector to flue outlet. See * note, page 11.
PAGE 9
Loading...
+ 20 hidden pages