Lennox 15CHAX, 15CHAXA−24, 15CHAXA−30, 15CHAXA−36, 15CHAXA−42 Unit Information

...
Page 1
15CHAX
Service Literature
Corp. 0634−L6
15CHAX SERIES UNITS
Information contained in this manual is intended for use by qualified service technicians only. All specifications are sub­ject to change. Procedures outlined in this manual are pre­sented as a recommendation only and do not supersede or replace local or state codes.
IMPORTANT
Operating pressures of a R−410A unit are higher than pressures in R−22 units. Always use service equipment rated for R−410A.
2 to 5 Ton (7.0 to 17.6 kW)
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, person­al injury or loss of life. Installation and service must be performed by a qualified installer or service agency.
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
CAUTION
Electrostatic discharge can affect electronic components. Take precautions during unit instal­lation and service to protect the unit’s electronic controls. Precautions will help to avoid control exposure to electrostatic discharge by putting the unit, the control and the technician at the same electrostatic potential. Neutralize electro­static charge by touching hand and all tools on an unpainted unit surface before performing any service procedure.
WARNING
Refrigerant can be harmful if it is inhaled. Refrigerant must be used and recovered responsibly.
Failure to follow this warning may result in personal injury or death.
TABLE of CONTENTS
Specifications / Accessories Page 2. . . . . . . . . .
Electric Heat Capacities Page 3. . . . . . . . . . . . .
Electrical / Electric Heat Data Page 3. . . . . . . .
Parts Arrangement Page 4. . . . . . . . . . . . . . . . .
I Application Page 5. . . . . . . . . . . . . . . . . . . . . . .
II Unit Components Page 5. . . . . . . . . . . . . . . . .
III Electric Heat Page 13. . . . . . . . . . . . . . . . . . . .
IV Charging Page 14. . . . . . . . . . . . . . . . . . . . . . . .
V Maintenance Page 14. . . . . . . . . . . . . . . . . . . . .
VII Wiring Diagrams Page 15. . . . . . . . . . . . . . . .
Page 1
© 2006 Lennox Industries Inc.
Litho U.S.A.
Page 2
SPECIFICATIONS
g
p
208/240V−1ph
g
g
Power Kits
General Data
Model No.
Nominal Tonnage 2 2.5 3 3.5 4 5
Cooling Performance
Total cooling capacity − Btuh 23,000 28,200 35,000 41,500 47,500 59,000
Total unit watts 1850
2
SEER (Btuh/Watt) 14.50 14.00 15.00 14.50 14.00 14.00
EER (Btuh/Watt) 12.40 12.40 12.40 12.40 11.80 11.70
Sound Rating Number (dB) 77 77 77 79 79 79
Refrigerant Type R−410A R−410A R−410A R−410A R−410A R−410A
Refrigerant Charge 7 lbs. 8 oz. 6 lbs. 10 oz. 7 lbs. 13 oz. 11 lbs. 5 oz. 11 lbs. 13 oz. 11 lbs. 12 oz.
Outdoor Coil
Net face area − sq. ft. (m2) 15.1 15.1 15.1 22 22 22
Tube dia. − in. (mm) & No. of rows 5/16 − 2 5/16 − 2 5/16 − 2 5/16 − 2 5/16 − 2 5/16 − 2
Fins per inch (m) 22 22 22 22 22 22
Indoor Coil
Tube dia. − in. (mm) & No. of rows 3/8 − 2 3/8 − 2 3/8 − 4 3/8 − 2 3/8 − 3 3/8 − 4
Net face area − sq. ft. (m2) 4.67 4.67 4.67 6 6 6
Fins per inch (m) 14 14 14 14 14 14
Condensate drain size (fpt) − in. 3/4 3/4 3/4 3/4 3/4 3/4 Outdoor
Coil Fan
Indoor Blower
Diameter − in. & No. of blades 22 − 3 22 − 3 22 − 3 26 − 3 26 − 3 26 − 3
Blower wheel size dia. x width − in. 10 x 6 10 x 6 10 x 8 10 x 10 10 x 10 10 x 10
Motor horsepower 1/5 1/5 1/5 1/4 1/4 1/4
Motor horsepower 1/2 1/2 1/2 3/4 3/4 3/4
Net weight of basic unit 370 370 390 500 510 510 Shipping weight of basic unit (1 Pkg.) 415 415 435 555 565 565 Electrical characteristics (60 hz) 208/230V−1ph−60hz
15CHAXA
−24
15CHAXA
−30
15CHAXA
−36
15CHAXA
−42
15CHAXA
−48
15CHAXA
2275 2820 3350 4030 5040
OPTIONAL ACCESSORIES − MUST BE ORDERED EXTRA
Compressor Crankcase Heater 93M04 S S S S S S Compressor Hard Start Kit
Compressor Time−Off Control 47J27 S S S S S S Electric
Heat Size
5 kW − PHK05BP
7.5 kW − PHK07BP 10 kW − PHK10BP 15 kW − PHK15CP 20 kW − PHK20CP
3
Internal Filter Kit
(No.) and size of filters − in.
92M54 − (1) 20 x 25 S S S
92M55 − (2) 16 x 25 Lifting Brackets 92M51 S S S S S S Low Ambient Kit 34M72 S S S S S S PCO Accessory Kit 92M53 S S S S S S Roof Curbs 8 inch height
14 inch height
SignatureStatt Home Comfort Control 81M27 S S S S S S Single Point
Power Kits
For 5 kW Electric Heat
ASPWR813−01
For 7.5 kW Electric Heat
ASPWR814−01
For 10 kW Electric Heat
ASPWR815−01
For 15−20 kW Electric Heat
ASPWR816−01
NOTE−Extremesofoperatingrangeareplusandminus10%ofline voltage.
1
Annual Fuel Utilization Efficiency based on U.S. DOE test procedures and FTC labeling regulations.
2
Rated in accordance with ARI Standard 210/240; 95_F outdoor air temperature, 80_F db/67_F wb entering evaporator air.
3
Filters are not furnished and must be field provided. 1, 2 or 4 inch thick filters can be used.
4
HACR type circuit breaker or fuse.
5
RefertoNational or CanadianElectricalCodemanualtodeterminewire,fuseanddisconnectsizerequirements.
10J42 S S S S S 81J69 S
10W47 S S S S S S 10W48 S 10W49 S 10W50 10W51
S S S S S S S S S S
S S S S
S S S
S S S
92M99 93M01 93M00 93M02
S S S
S
S S
S S S
S S S
13W88 S S S S S S
13W89 S
13W90 S
S S S S S
S S S S S
13W91 S S S S
−60
Page 2
Page 3
ELECTRIC HEAT CAPACITIES
I
p
Protecti
Bl
Motor
A
Bl
Motor
nput
Volta ge
No of Steps
208 1 3.8 12,800 1 5.6 19,200 1 7.5 17,900 1 11.2 38,200 1 15.0 51,200
220 1 4.2 14,300 1 6.3 21,500 1 8.4 20,100 1 12.6 43,000 1 16.8 57,300
230 1 4.6 15,700 1 6.9 23,500 1 9.2 21,900 1 13.8 47,000 1 18.4 62,700
240 1 5.0 17,100 1 7.5 25,600 1 10.0 23,900 1 15.0 51,200 1 20.0 68,200
5 kW 7.5 kW 10 kW 15 kW 20 kW
kW
input
Btuh
Output
No of StepskWinput
Btuh
Output
No of StepskWinput
Btuh
Output
No of StepskWinput
Btuh
Output
No of
StepskWinput
ELECTRICAL/ELECTRIC HEAT DATA
Model No. 15CHAXA−24 15CHAXA−30 15CHAXA−36 15CHAXA−42 15CHAXA−48 15CHAXA−60
Linevoltagedata − 60hz 1 phase 208/230V 208/230V 208/230V 208/230V 208/230V 208/230V
Compressor
Outdoor Fan Motor
Indoor Blower Motor
1
Maximum
Overcurrent
on
Electric
Heat &
Circuit
2
Minimum
Circuit
mpacity
Electric
Heat &
Circuit
NOTE − Circuit 1 Minimum Circuit Ampacity includes the Blower Motor Full Load Amps. NOTE− Extremesofoperatingrangeareplusandminus10%oflinevoltage. 1 HACR type breaker or fuse.
2
RefertoNational or CanadianElectricalCodemanualtodeterminewire,fuseanddisconnectsizerequirements.
Rated Load Amps 13.4 14.1 14.1 17.9 21.8 26.4
Locked Rotor Amps 58 73 77 112 117 134
Full Load Amps 1.1 1.1 1.1 1.7 1.7 1.7
Locked Rotor Amps 2.2 2.2 2.2 4 4 4
Rated Load Amps 1.5 1.5 1.5 2.7 2.7 2.7
Locked Rotor Amps 3 3 4 5 5 5
Unit only, no electric heat 30 30 30 40 50 60
5 kW 35 35 35 35 35 35
ower
Motor
15 kW
7.5 kW 45 45 45 50 50 50
10 kW 60 60 60 60 60 60
Circuit 1 − − − − − − 60 60 60 60
Circuit 2 − − − − − − 30 30 30 30
20 kW
Circuit 1 − − − − − − − − − 60 60 60
Circuit 2 − − − − − − − − − 60 60 60
Unit only, no electric heat 21 22 22 29 34 39
5 kW 31.3 31.3 31.3 33.0 33.0 33.0
ower
Motor
15 kW
7.5 kW 44.3 44.3 44.3 46.1 46.1 46.1
10 kW 57.3 57.3 57.3 59.1 59.1 59.1
Circuit 1 − − − − − − 57.3 59.1 59.1 59.1
Circuit 2 − − − − − − 26.0 26.0 26.0 26.0
20 kW
Circuit 1 − − − − − − − − − 59.1 59.1 59.1
Circuit 2 − − − − − − − − − 52.1 52.1 52.1
Btuh
Output
Page 3
Page 4
15CHAX PARTS ARRANGEMENT
TRANSFORMER
(T1)
BLOWER CONTROL
(A54)
FIGURE 1
15CHAX CONTROL BOX
CONTACTOR
SYSTEM OPERATION MONITOR
(A132)
(K1)
DUAL / FAN CAPACITOR
(C12)
FIGURE 2
Page 4
Page 5
I−APPLICATION
15CHAX 2 through 5 ton (7.0 through 17.6kW) model units are single phase air conditioning units designed for outdoor installation on a slab or roof top.The units are available in two cabinet sizes. Electric heat can be factory or field installed if required. Refer to the Engineering Handbook for more spe­cific application data.
II−UNIT COMPONENTS
15CHAX components are shown in figure 1. Control box com­ponents are shown in figure 2.
A−Control Box Components
1−Compressor Contactor K1
K1 is a 24VAC to line voltage s ingle pole double break contac­tor, which energizes the compressor in response to thermostat demand.
2−Control Transformer T1
All 15CHAX series units use line voltage to 24VAC transformer mounted in the control box. The transformer supplies power to control circuits in the unit. Transformers use two primary volt­age taps as shown in figure 3.
208 / 240 VOLT TRANSFORMER
PRIMARY
L2
240 VOLTS
208 VOLTS
L1
FIGURE 3
SECONDARY
24 VOLTS
3−Dual Capacitor C12
The compressor and condenser fan in the 15CHAX series units use permanent split capacitor motors. The capacitor is lo­cated in the control box. A dual rated capacitor is used for both the condenser fan motor and the compressor (see unit wiring diagram per respective unit). The fan side and the compressor side of the capacitor have different MFD ratings. See side of capacitor for ratings.
4− Blower Control A15
!
WARNING
Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch(es). Unit may have multiple power supplies.
15CHAX units are equipped with a variable speed motor that is capable of maintaining a specified CFM throughout the external static range. A particular CFM can be obtained by positioning jumpers (COOL, HEAT, and ADJUST) on the blower control board. The HEAT and COOL jumpers are labeled A, B, C and D. Each of the numbers corre­sponds with an air volume (CFM) setting. The ADJUST jumper is labeled Test, −, +, and Norm. The + and − pin set­tings are used to add or subtract a percentage of the CFM selected. The Test jumper is used to operate the motor in the test mode. See figure 4.
Factory settings for the blower speed jumpers are given in the wiring diagram. Figure 4 shows the blower control board. Use tables 1, 2 and 3 to determine the correct air vol­ume for operation in heat and cool mode.
The CFM LED located on the blower control board flashes one time per 100 cfm to indicate selected blower speed. For example, if the unit is operating at 1000 CFM, CFM LED will flash 10 times. If the CFM is 1150, CFM LED will flash 11 full times plus one fast or half flash.
At times the light may appear to flicker or glow. This takes place when the control is communicating with the motor be­tween cycles. This is normal operation.
Read through the jumper settings section before adjusting the jumper to obtain the appropriate blower speed.
To change jumper positions, gently pull the jumper off the pins and place it on the desired set of pins. The following section outlines the different jumper selections available and condi­tions associated with each one. Refer to figure 4.
After the CFM for each application has been determined, the jumper settings must be adjusted to reflect those given in tables 1, 2 and 3. From the tables, determine which row most closely matches the desired CFM. Once a specific row has been chosen (+, NORMAL, or −), CFM volumes from other rows cannot be used. Below are descriptions of the jumper selections.
The variable speed motor slowly ramps up to and down from the selected air flow during both cooling and heating demand. This minimizes noise and eliminates the initial blast of air when the blower is initially energized.
ADJUST
The ADJUST pins allow the motor to run at normal speed, approximately 15 percent higher, or approximately 15 per­cent lower than normal speed. Tables 1, 2 and 3 give three rows (+, NORMAL, and −) with their respective CFM vol­umes. Notice that the normal adjustment setting for cool speed position D in table 1 is 900 CFM. The + adjustment setting for that position is 1035 CFM and for the − adjust­ment setting is 765 CFM. After the adjustment setting has been determined, choose the remaining speed settings from those offered in the table in that row.
The TEST pin is available to bypass the blower control and run the motor at approximately 70 percent to make sure that the motor is operational. This is used mainly in trouble­shooting. The G terminal must be energized for the motor to run.
Page 5
Page 6
BLOWER CONTROL BOARD (A54)
16−PIN PLUG
(BOARD TO MOTOR)
ADJUST
SELECTOR PINS (Setting affects both heating and cooling
modes)
DIAGNOSTIC
LED
FIGURE 4
COOL
The COOL jumper is used to determine the CFM during cooling operation. This jumper selection is activated for cooling when Y1 is energized.
The blower motor runs at 80 percent of the selected air flow for the first 7−1/2 minutes of each cooling demand. This fea­ture allows for greater humidity removal and saves energy. In the cooling mode, the blower control board delays blower operation for 5 seconds after the compressor starts. The blower continues to operate for 90 seconds after the compressor is de−energized.
HEAT
The HEAT jumper is used to determine CFM during backup electric heat operation only. These jumper selections are activated only when W is energized. In the backup heat mode, the blower continues to operate for 2 minutes after the heating demand is satisfied.
NOTE − Due to the nature of electric heat, CFM settings are limited.
HEATING SPEED SELECTOR PINS
COOLING SPEED
SELECTOR PINS
CONTINUOUS FAN
When the thermostat is set for Continuous Fan" operation and there is no demand for heating or cooling, the blower control will provide 50 percent of the COOL CFM selected.
NOTE − With the proper thermostat and subbase, continu­ous blower operation is possible by closing the R to G cir­cuit. Cooling blower delay is also functional in this mode.
DEHUMIDIFICATION
The blower control board includes an HUM terminal which provides for connection of a humidistat. The JV1 resistor on the blower control board must be cut to activate the HUM terminal. The humidistat must be wired to open on humidity rise. When the dehumidification circuit is used, the variable speed motor will reduce the selected air flow rate by 25 per­cent when humidity levels are high. An LED (D1) lights when the blower is operating in the dehumidification mode.
Page 6
Page 7
TABLE 1
ADJUST
Jumper
ADJUST
Jumper
JUS
ADJUST
Jumper
15CHAX−24, 15CHAX−30 Blower Performance
0 through 0.80 in. w.g. (0 through 200 Pa) External Static Pressure Range
Jumper Speed Positions
"
Jumper
Setting
NORM 1000 470 800 380 600 285 900 425 1000 470 1000 470 1000 470 1000 470 500 235 400 190 300 140 450 210
A
cfm
1150 545 920 435 690 325 1035 490 1150 545 1150 545 1150 545 1150 545 575 270 460 215 345 165 520 245
+
850 400 680 320 510 240 765 360 1000 470 1000 470 1000 470 1000 470 425 200 340 160 300 140 385 180
COOL" Speed
B C D A B C D A B C D
L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
HEAT" Speed CONTINUOUS FAN" Speed
TABLE 2
15CHAX−36 Blower Performance
0 through 0.80 in. w.g. (0 through 200 Pa) External Static Pressure Range
Jumper Speed Positions
"
Jumper
Setting
NORM 1200 565 1000 470 800 380 1100 520 1200 565 1200 565 1000 470 1000 470 600 285 500 235 400 190 550 260
A
cfm
1380 650 1150 545 920 435 1265 575 1380 650 1380 650 1150 545 1150 545 690 325 575 270 460 215 635 300
+
− 1020 480 850 400 680 320 935 440 1200 565 1200 565 1000 470 1000 470 510 240 425 200 350 165 470 220
COOL" Speed
B C D A B C D A B C D
L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
HEAT" Speed CONTINUOUS FAN" Speed
TABLE 3
15CHAX−42, 15CHAX−48, 15CHAX−60, Blower Performance
0 through 0.80 in. w.g. (0 through 200 Pa) External Static Pressure Range
Jumper Speed Positions
AD
T"
Jumper
Setting
NORM 1800 850 1600 755 1400 660 1200 565 1400 660 1400 660 1400 660 1400 660 900 425 800 380 700 330 600 285
A
cfm
2070 975 1840 870 1610 760 1380 650 1610 760 1610 760 1610 760 1610 760 1035 490 920 435 805 380 690 325
+
− 1530 720 1360 640 1190 560 1020 480 1400 660 1400 660 1400 660 1400 660 765 360 680 320 595 280 510 240
COOL" Speed
B C D A B C D A B C D
L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
HEAT" Speed CONTINUOUS FAN" Speed
5−Lennox System Operation Monitor (A132)
IMPORTANT
This monitor does not provide safety protection. The monitor is a monitoring device only and cannot con­trol or shut down other devices.
The Lennox system operation monitor (LSOM) detects the most common fault conditions in the air conditioning system. When an abnormal condition is detected, the module communicates the specific condition through its ALERT and TRIP lights. The module is capable of detect­ing both mechanical and electrical system problems. See figure 5 for the system operation monitor.
Lennox System Operation Monitor (A132)
POWER LED
DATA OUTPUT
Y
C
R
ALERT LED
TRIP LED
DATA OUTPUT CONNECTOR
.25" SPADE CONNECTOR (5)
LSOM LED Functions
Power LED (green) −− Voltage within the range of
19−28VAC is present at the system monitor power connec­tion.
Alert LED (yellow) −− Communicates an abnormal sys­tem condition through a unique flash code. The alert LED flashes a number of times consecutively; then pauses; then repeats the process. This consecutive flashing cor­responds with a particular abnormal condition.
Trip LED (red) −− Indicates a demand signal from the ther­mostat; but detects no current to the compressor.
Flash code number −− Corresponds to a number of LED flashes, followed by a pause, and then repeated.
Trip & Alert LEDs flashing simultaneously −− Indicates that the control circuit voltage is too low for operation.
Reset ALERT flash code by removing 24VAC power from monitor. Last ALERT flash code will display for 1 minute after monitor is powered on.
LSOM codes are given in table 4.
Page 7
Page 8
TABLE 4
System Operation Monitor LED Troubleshooting Codes
Status LED Condition Status LED Description Status LED Troubleshooting Information
Green Power" LED ON Module has power 24VAC control power is present at the module terminal.
Green Power" LED OFF Module not powering up
Red Trip" LED ON System and compressor
check out OK
Thermostat demand signal Y1 is present, but compres­sor not running
Red Trip" & Yellow Alert" LEDs Flashing
Yellow Alert" Flash Code 1*
Simultaneous flashing. Indicates that the control circuit voltage is too low for operation.
Long Run Time − Compressor is running extremely long run cycles
Yellow Alert" Flash Code 2*
System Pressure Trip
Discharge or suction pres­sure out of limits or compressor overloaded
Yellow Alert" Flash Code 3*
Yellow Alert" Flash
Short Cycling − Compres-
sor is running only briefly
Locked Rotor
Code 4*
Yellow Alert" Flash
Open Circuit
Code 5*
Yellow Alert" Flash Code 6*
Yellow Alert" Flash Code 7*
Yellow Alert" Flash Code 8*
Yellow Alert" Flash Code 9*
Open Start Circuit − Cur-
rent only in run circuit
Open Run Circuit − Current only in start circuit
Welded Contactor Com- pressor always runs
Low Voltage − Control cir­cuit <17VAC
*Flash code number corresponds to a number of LED flashes, followed by a pause, and then repeated. Reset ALERT flash code by removing 24VAC power from monitor; last code will display for 1 minute after monitor is powered on.
Determine/verify that both R and C module terminals are connected and voltage is present at both terminals.
1.
2.
3.
Verify Y terminal is connected to 24VAC at contactor coil. Verify voltage at contactor coil falls below 0.5VAC when off. Verify 24VAC is present across Y and C when thermostat
demand signal is present; if not present, R and C wires are reversed.
1.
2.
3.
4.
5.
6.
1.
2.
3.
4.
5.
6.
7.
1.
2.
3.
4.
5.
1.
2.
3.
4.
1.
2.
3.
4.
1.
2.
3.
4.
5.
6.
7.
1.
2.
3.
1.
2.
1.
2.
1.
2.
Compressor protector is open. Outdoor unit power disconnect is open. Compressor circuit breaker or fuse(s) is open. Broken wire or connector is not making contact. Low pressure switch open if present in the system. Compressor contactor has failed to close.
Low refrigerant charge. Evaporator blower is not running. Evaporator coil is frozen. Faulty metering device. Condenser coil is dirty Liquid line restriction (filter drier blocked if present) Thermostat is malfunctioning
.
.
.
High head pressure. Condenser coil poor air circulation (dirty, blocked, damaged). Condenser fan is not running. Return air duct has substantial leakage. If low pressure switch is present, see Flash Code 1 info.
Thermostat demand signal is intermittent. Time delay relay or control board is defective. If high pressure switch is present, see Flash Code 2 info. If low pressure switch is present, see Flash Code 1 info.
Run capacitor has failed. Low line voltage (contact utility). Excessive liquid refrigerant in the compressor. Compressor bearings are seized.
Outdoor unit power disconnect is open. Unit circuit breaker or fuse(s) is open. Unit contactor has failed to close. High pressure switch is open and requires manual reset. Open circuit in compressor supply wiring or connections. Unusually long compressor protector reset time due to extreme ambient temperature. Compressor windings are damaged.
Run capacitor has failed. Open circuit in compressor start wiring or connections. Compressor start winding is damaged.
Open circuit in compressor start wiring or connections. Compressor start winding is damaged.
Compressor contactor failed to open. Thermostat demand signal not connected to module.
Control circuit transformer is overloaded. Low line voltage (contact utility).
Page 8
Page 9
B−Blower Compartment
Access panels can easily be removed for service.
1−Blower Wheel
Blower wheel size varies between models. See SPECIFI­CATIONS.
2−Variable Speed Motor (B3)
15CHAX units use a three-phase, electronically controlled D.C. brushless motor (controller converts single phase a.c. to three phase D.C.), with a permanent-magnet-type rotor (fig­ure 6). Because this motor has a permanent magnet rotor it does not need brushes like conventional D.C. motors. Internal components are shown in figure 7. The stator wind­ings are split into three poles which are electrically connected to the controller. This arrangement allows mo t o r win d i n gs to turn on and off in sequence by the controller.
A solid-state controller is permanently attached to the motor. The controller is primarily an A.C. to D.C. convert­er. Converted D.C. power is used to drive the motor. The controller contains a microprocessor which monitors varying conditions inside the motor (such as motor work­load).
BLOWER MOTOR B3
J48
SHAFT
tion"). This allows for precise control of motor speed and allows the motor to compensate for varying load conditions as sensed by the controller. In this case, the controller monitors the static workload on the motor and varies motor rpm in order to main­tain constant airflow (cfm).
The motor controller is driven by the blower control board (figure 4). The board receives its demand (PWM signal or fixed 24 VAC or VDC signal) from optional controls such as the Harmony zone control system, Lennox Signatu­reStatt or a conventional thermostat.
Motor rpm is continually adjusted internally to maintain constant static pressure against the blower wheel. The control­ler monitors the static work load on the motor and motor amp­draw to determine the amount of rpm adjustment. Blower rpm may be adjusted any amount in order to maintain a constant cfm as shown in Blower Ratings Tables (1, 2 and 3). The cfm remains relatively stable over a broad range of static pressure. Since the blower constantly adjusts rpm to maintain a specified cfm, motor rpm is not rated. Hence, the terms cool speed" , heat speed " or speed tap" if used in this manual, on the unit wiring diagram and on blower B3, refer to blower cfm regard­less of motor rpm.
When Harmony is used, speed taps are overridden and a PWM signal generated by the Harmony controller continuously varies motor speed based upon zone demands.
Initial Power Up
MOTOR
CONTROLLER
J49
FIGURE 6
BLOWER MOTOR COMPONENTS
STATOR
(WINDINGS)
BEARING
OUTPUT
SHAFT
ROTOR
FIGURE 7
The controller uses sensing devices to sense what position the rotor is in at any given time. By sensing the position of the rotor and then switching the motor windings on and off in se­quence, the rotor shaft turns the blower.
All blower motors use single phase power. An external run capacitor is not used. The motor uses permanently lubricated ball-type bearings.
Internal Operation
Each time the controller switches a stator winding (figure 7) on and off, it is called a pulse." The length of time each pulse stays on is called the pulse width." By varying the pulse width , the controller varies motor speed (called pulse-width modula-
When line voltage is applied to B3, there will be a large inrush of power lasting less than 1/4 second. This inrush charges a bank of DC filter capacitors inside the controller. If the discon­nect switch is bounced when the disconnect is closed, the dis­connect contacts may become welded. Try not to bounce the disconnect switch when applying power to the unit.
Motor Start-Up
When B3 begins start-up, the motor gently vibrates back and forth for a moment. This is normal. During this time the elec­tronic controller is determining the exact position of the rotor. Once the motor begins turning, the controller slowly eases the motor up to speed (this is called soft-start"). The motor may take as long as 10-15 seconds to reach full speed. If the motor does not reach 200rpm within 13 seconds, the motor shuts down. Then the motor will immediately attempt a restart. The shutdown feature provides protection in case of a frozen bear­ing or blocked blower wheel. The motor may attempt to start eight times. If the motor does not start after the eighth try, the controller locks out. Reset controller by momentarily turning off power to unit.
The DC filter capacitors inside the controller are connected electrically to the speed tap wires. The capacitors take approximately 5 minutes to discharge when the disconnect is opened. For this reason it is necessary to wait at least 5 minutes after turning off power to the unit before attempt­ing to change speed taps.
Page 9
Page 10
DANGER
Disconnect power from unit and wait at least five minutes to allow capacitors to discharge before at­tempting to adjust motor speed tap settings. Failure to wait may cause personal injury or death.
External Operation (Speed Tap Priority)
Figure 8 shows the two quick-connect jacks (J48 and J49) which connect the motor to the 15CHAX. Jack J48 is the power plug and jack J49 connects the unit controls to the motor.
Line voltage must be applied to J48 pin 5 in order for the mo­tor to operate. When using 120VAC pins 1 and 2 must be jumpered. When control voltage is applied to J49 pin 3 and 15, the motor is energized on the continuous fan mode.
When voltage is applied to J49 pin 2 in addition to pin 3 and 15 (first stage heating), the blower is energized on the low speed heating tap. When voltage is applied to J49 pin 13 in addition to pin 3 and 15 (second stage heating), the blower is energized on the high speed heating tap. The motor as­signs priority to J49 pin 2 so that if a call for cooling and a call for heating are concurrent, heating call overrides and the blower operates on high speed heating tap.
Precautions
If the 15CHAX or its electronically controlled blower motor is improperly or inadequately grounded, it may cause television interference (commonly known as RFI or radio frequency inter­ference).
This interference is caused by internal switching fre­quencies of the motor controller. TV interference may show up as small sp e c k s or lin es which randomly appear on the TV screen accompanied by pops or clicks in the sound. Be­fore attempting any service, make sure the indoor unit is caus­ing the interference. To check, disconnect power to indoor unit then check TV for continued signs of interference.
TV interference may be stopped by making sure the mo­tor is solidly grounded to the cabinet (metal to metal) and by making sure the cabinet is solidly grounded. If TV inter­fe rence persi sts, make sure the television (and all affected RF appliances) are moved away from the 15CHAX. Also make sure affected appliances are connected to a separate electrical circuit.
BLOWER B3 HARNESS CONNECTORS
POWER
CONNECTOR J48
J48 PIN 1 - Jumper PIN 1 to PIN2 for 120VAC line input only. PIN 2 - Jumper PIN 1 to PIN2 for 120VAC line input only. PIN 3 - Ground PIN 4 - AC Line PIN 5 - AC Line
CONTROL
CONNECTOR J49
J49 PIN 1 - C1 PIN 2 - W / W1
11
PIN 3 - C2 PIN 4 − Delay PIN 5 - Cool PIN 6 - Y1 PIN 7 - Adjust PIN 8 - 0ut PIN 9 - 0 PIN 10 - DS(PWM) PIN 11 - Heat PIN 12 - R PIN 13 - EM / W2 PIN 14 - Y / Y2 PIN 15 - G PIN 16 - Out +
FIGURE 8
Page 10
Page 11
Using the transformer in the unit, test motor operation by jumping 24 volts into the terminals illustrated below for the desired speed.
LOW (continuous blower) SPEED
12345678 910111213
J46
C
R
1. Disconnect power to unit.
2. Disconnect plug J46 from P46 located on the blower control board.
3. Disconnect C and R from ignition control board.
4. Disconnect Y" from ignition control and con­nect a separate wire between R" on the transformer and Y" on the ignition control.
5. Connect voltage source as shown above.
6. Turn on power to unit. Blower should operate at LOW speed.
COOLING SPEED
12345678 910111213
J46
C
R
7− Disconnect power to unit. 8− Connect voltage source as shown above. 9− Disconnect Y" on ignition control and con-
nect a separate wire between R" on trans­former and Y" on ignition control.
10− Turn on power to unit. Blower should oper-
ate at COOLING speed.
VARIABLE SPEED CHECKOUT
14 15
16
To Y" on ignition control. !
14 15
16
To Y" on ignition control.
J46
C
J46
C
HEATING SPEED
12345678 91011121314 15
R
11− Disconnect power to unit. 12− Connect voltage source as shown above. 13− Disconnect W" from ignition control and
connect a separate wire between R" on transformer and W" on the ignition control.
14− Turn on power to unit. Blower should operate
at HEATING speed.
16
To W" on on ignition control.
HIGH HEATING SPEED
1 2 3 4 5 6 7 8 9 10111213
R
15− Disconnect power to unit. 16− Connect voltage source as shown above. 17− Disconnect W2" from ignition control and
connect a separate wire between R" on transformer and W2" on ignition control.
18− Turn on power to unit. Blower should operate
at HIGH HEATING speed.
14 15
To W2" on ignition control.
16
J49 CONTROL CONNECTOR VOLTAGE WHEN VOLTAGE IS PRESENT
PIN 1 C1 Common Low voltage transformer is powered
PIN 2 W / W1 24VAC W1 (1st stage heating) call from thermostat
PIN 3 C2 Common Low voltage transformer is powered
PIN 4 Delay see note
PIN 5 Cool see note
1
1
Low voltage transformer is powered
Low voltage transformer is powered
PIN 6 Y1 24VAC Y (cooling) call from thermostat
PIN 7 Adjust see note
1
Low voltage transformer is powered
PIN 8 Out Motor sends pulse signals between pin 8 and pin 16 to signal CFM
PIN 9 O 24VAC From thermostat (in heat pump application)
PIN 10 DS / PWM 0 / 24 VAC Low voltage is transformer is powered and humidistat operation:
24VAC = normal humidity, 0VAC = high humidity (reduced CFM)
PIN 11 Heat see note
1
Low voltage transformer powered
PIN 12 R 24VAC Low voltage transformer is powered
PIN 13 EM / W2 24VAC W2 (2nd stage heating) call from thermostat
PIN 14 Y / Y2 Not used on single stage cooling
PIN 15 G 24VAC G is present from thermostat
PIN 16 Out Motor sends pulse signals between pin 8 and 16 to signal CFM
1
signal from selection taps − A tap = 0 volts, B and C taps = half wave, D tap = 24VAC
Page 11
Page 12
C−Cooling Components
SCROLL COMPRESSOR
DISCHARGE
CROSS−SECTION OF SCROLLS
DISCHARGE
PRESSURE
DISCHARGE
STATIONARY
SCROLL
SUCTION
ORBITING
SCROLL
SUCTION
FIGURE 9
The scroll compressor design is simple, efficient and re­quires few moving parts. A cutaway diagram of the scroll compressor is shown in figure 9. The scrolls are located in the top of the compressor can and the motor is located in the bottom of the compressor can. The oil level is immedi­ately below the motor.
The scroll is a simple compression concept centered around the unique spiral shape of the scroll and its inherent properties. Two identical scrolls are mated together form­ing concentric spiral shapes (figure 10). One scroll remains stationary, while the other is allowed to "orbit" (figure 11). Note that the orbiting scroll does not rotate or turn but mere­ly orbits the stationary scroll.
NOTE − The head of a scroll compressor may be hot since it is in constant contact with discharge gas.
TIPS SEALED BY
DISCHARGE PRESSURE
FIGURE 10
The counterclockwise orbiting scroll draws gas into the outer crescent shaped gas pocket created by the two scrolls (fig­ure (figure 11 − 1). The centrifugal action of the orbiting scroll seals off the flanks of the scrolls (figure 11 − 2). As the orbiting motion continues, the gas is forced toward the center of the scroll and the gas pocket becomes compressed (figure 11 −
3). When the compressed gas reaches the center, it is dis­charged vertically into a chamber and discharge port in the top of the compressor (figure 9). The discharge pressure forcing down on the top scroll helps seal off the upper and lower edges (tips) of the scrolls (figure 10). During a single orbit, several pockets of gas are compressed simultaneously providing smooth continuous compression.
The scroll compressor is tolerant to the effects of liquid re­turn. If liquid enters the scrolls, the orbiting scroll is allowed to separate from the stationary scroll. Continued slugging of liquid will cause damage to the scroll and replacement will be necessary. The liquid is worked toward the center of the scroll and is discharged. If the compressor is replaced, con­ventional Lennox cleanup practices must be used.
1
SUCTION
POCKET
SUCTION
3
SUCTION
ORBITING
SCROLL
STATIONARY
SCROLL
HIGH PRESSURE GAS
SUCTION
2
FLANKS SEALED
BY CENTRIFUGAL FORCE
MOVEMENT OF ORBIT
FIGURE 11
INTERMEDIATE PRESSURE
GAS
CRECENT SHAPED
GAS POCKET
SUCTION
4
DISCHARGE
POCKET
Page 12
Page 13
1−Condenser Fan
All 15CHAX units use single phase condenser fans. Specifica­tions for the condenser fans are at the front of this manual. See figure 12 for fan and motor replacement.
1 1/2"
fan guard
hub and shaft should be flush
FIGURE
12
2−High Pressure Switch S4
S4 is a N.C. auto−reset high pressure switch located on the liquid line. The switch shuts off the compressor when liquid pressure rises above the factory setting. The switch on 15CHAX units is set to open at 590 + 10 psi and close at 418 + 10 psi.
3−Low Pressure Switch (S79)
2−Heating Element HE1 through HE4
Heating elements are composed of helix−wound bare nich­rome wire exposed directly to the air stream. The elements are supported by insulators mounted to the wire frame. Each ele­ment is energized independently by a corresponding relay lo­cated on the heat vest panel. Once energized, heat transfer is instantaneous.
PHK VESTIBULE PARTS ARRANGEMENT
(PHK−10)
TB 2
SEQUENCER
RELAY
PRIMARY
LIMITS
The low pressure switch is an auto−reset N.C. switch that opens on pressure drop. The switch is wired in series with the high pressure switch S4 and compressor contactor K1 and is located on the suction line . When suction pres­sure drops to 10 psig (68.95kPa) the switch opens and the compressor is de−energized. When suction pressure rises to 30 psig (206.85 kPa) the pressure switch will close.
III−Electric Heat A−Matchups and Ratings
Matchups and ratings are listed with ELECTRICAL DATA" See table of contents.
B−Electric Heat Components
See figure 13 for electric heat parts arrangement.
1− Limit Switches 1, 2, 3 and 4
Limit switches 1, 2, 3and 4 are N.C. auto−reset high tempera­ture limits located on the electric heat vest panel. Each heating element is wired in series with a high temperature limit. When the limit opens the corresponding heating element is de−ener­gized. All other heating elements remain energized. The limits will automatically close when temperatures return to normal. Limit rating will be on front side.
FIGURE 13
3−Terminal Strip TB2 PHK−05, −07, −10
For electric heat sections without circuit breakers or fuses, line voltage connections are made to terminal strip TB2.
4− Sequencer Relays 1 and 2
Relays 1 and 2 are N.O. sequencer relays with a resistive ele­ment for a coil and bi−metal disk which actuates the contacts. The relays are located on the electric heat vest panel and are energized by a 24V heating demand (W1 and W2) via jack/ plug P2 which is used to connect electric heat to the blower control circuit. When energized, the internal resistance heats the bi−metal disk causing the contacts to close. When the relay is de−energized the disk cools and the contacts open. The re­lays energize different stages of heat, as well as the blower. The blower is always first on and last off.
5−Circuit Breaker CB1 and CB2 (option)
PHK−15, −20,
Line voltage connections are made to circuit breakers CB1 and CB2 in electric heat sections with circuit breakers. Table 5 shows amp rating for each circuit breaker used. Two−pole cir­cuit breakers are used.
TABLE 5
Circuit Breakers
UNIT CB1 AMPS CB2 AMPS PHK15CP 60 AMPS 30 AMPS PHK20CP 60 AMPS 60 AMPS
Page 13
Page 14
IV−Charging
System Performance
TABLE 6
Subcooling Values
Unit Model No.
82_F OD / 80_F IDDB
/ 67_F IDWB
Verify system performance using table 7 as a general guide. Table 7 should not be used for charging unit. Minor variations in these pressures may be expected due to differences in installations. Significant differences could mean that the sys­tem is not properly charged or that a problem exists with some component in the system.
Used carefully, this table could serve as a useful service guide. Data is based on 80°F dry bulb / 67°F wet bulb return air. Allow unit operation to stabilize before taking pressure readings.
15CHAX−24 15CHAX−30
15CHAX−36 15_
15CHAX−42 15CHAX−48 15CHAX−60
12_
10_
Table 7
Normal Operating Pressures
80°F db / 67°F wb RETURN AIR Air Temperature Entering Outdoor Coil (°F)
UNIT PRESSURE 65 70 75 80 82 85 90 95 100 105 110 11 5 15CHAX−24 142 143 144 146 146 147 148 149 150 151 152 153 15CHAX−30 134 136 138 140 141 142 144 146 148 149 151 152 15CHAX−36 15CHAX−42 15CHAX−48 140 141 142 144 144 145 146 147 148 149 150 151 15CHAX−60 143 144 145 146 146 147 147 148 149 150 151 152 15CHAX−24 219 242 264 287 296 310 333 355 379 398 430 457 15CHAX−30 232 255 277 300 309 323 345 368 390 408 440 470 15CHAX−36 15CHAX−42 15CHAX−48 243 264 285 307 315 328 349 370 391 408 440 470 15CHAX−60 257 280 303 326 335 349 372 395 418 436 468 497
Suction
Liquid
143 144 146 147 148 149 151 152 155 155 157 157 140 140 140 141 141 141 142 142 143 144 145 147
244 268 292 316 326 340 363 369 410 429 461 493 225 247 269 291 300 314 337 357 383 402 434 457
V−Maintenance
At the start of each cooling season, this equipment should be serviced by a qualified technician. Periodic inspection and maintenance normally consists of changing or cleaning filters.
Filters
Not supplied. Inspect once a month. Replace disposable or clean permanent type as necessary. DO NOT replace per­manent type with disposable.
Motors
Indoor, outdoor fan and vent motors are permanently lubricated and require no further lubrication. Motors should be cleaned yearly to prevent the accumulation of dust and dirt on the windings or motor exterior.
Coil
Dirt and debris should not be allowed to accumulate on the coil surfaces or other parts in the air conditioning circuit. Cleaning should be performed as often as necessary. Use a brush, vacuum cleaner attachment, or other suitable means. If water is used to clean the coil, be sure the power to unit is shut off prior to cleaning.
NOTE − Care should be used when cleaning the coil so that the coil fins are not damaged.
Do not permit the hot condenser air discharge to be ob­structed by overhanging structures or shrubs.
Page 14
Page 15
VI−Wiring Diagram and Sequence of Operation
A−Unit Diagram
Page 15
Page 16
B−PHK Electric Heat
HE3HE3
HE4HE4
ELECTRIC HEAT - 2ND STAGEELECTRIC HEAT - 2ND STAGE
LIMIT SWITCH 3LIMIT SWITCH 3
BLKBLK
BLKBLK
BLKBLK
44
11
SEQUENCER 2SEQUENCER 2
55
33
BLUBLU
Wiring Diagram - Electric HeatWiring Diagram - Electric Heat
BLKBLK
BLKBLK
LIMIT SWITCH 4LIMIT SWITCH 4
YELYEL
HE1HE1
HE2HE2
ELECTRIC HEAT - 1ST STAGEELECTRIC HEAT - 1ST STAGE
LIMIT SWITCH 3LIMIT SWITCH 3
BLKBLK
WHTWHT
44
YELYEL
SEQUENCER 1SEQUENCER 1
55
BLUBLU
BLKBLK
LIMIT SWITCH 4LIMIT SWITCH 4
BLKBLK
11
YELYEL
YELYEL
33
BLKBLK
BLKBLK
WHTWHT
BLUBLU
REDRED
POWER (FACTORY WIRED)POWER (FACTORY WIRED)
6-PIN6-PIN
POWER FIELD WIRED)POWER FIELD WIRED)
66
55
PLUGPLUG
44
33
CONTROL (FACTORY WIRED)CONTROL (FACTORY WIRED)
%%uHEATER ELEMENTS USED:%%uHEATER ELEMENTS USED:
5KW-HE15KW-HE1
7.57.5 & 10KW - HE1& 10KW - HE1 & HE2& HE2
15KW - HE1, HE2,15KW - HE1, HE2, & HE3& HE3
5566
44
33
20KW - HE1, HE2, HE3,20KW - HE1, HE2, HE3, & HE4& HE4
WHTWHT
WHTWHT
BLUBLU
REDRED
6-PIN6-PIN
PLUGPLUG
66
33
22
55
11
44
W2W2
W1W1
TO THERMOSTATTO THERMOSTAT
PACKAGE UNITPACKAGE UNIT
WIRINGWIRING
CIRCUIT BREAKER 2 (OPT)CIRCUIT BREAKER 2 (OPT)
( IF USED )( IF USED )
SINGLE POINTSINGLE POINT
POWER ACCESSORYPOWER ACCESSORY
RELAYRELAY
GNDGND
CIRCUIT BREAKER 1 (OPT)CIRCUIT BREAKER 1 (OPT)
L2L2
L1L1
208/240208/240
VOLTAGEVOLTAGE
BY OTHERSBY OTHERS
L1L1
L2L2
L2L2
L1L1
GNDGND
YELYEL
BLKBLK
CIRCUITCIRCUIT
BREAKERBREAKER
COMPRESSORCOMPRESSOR
1122
BLOWERBLOWER
MOTORMOTOR
BLOWERBLOWER
22
11
YELYEL
BLKBLK
BLKBLK
BLKBLK
24V24V
208V208V
L1L1 L2L2
TO CONTACTORTO CONTACTOR
Page 16
Loading...