The 15CHAX packaged heat pump units are available in
sizes ranging from 2 through 5 tons (7.0 through 17.6 kW).
15CHAX units are designed for R−410A refrigerant and outdoor residential use only. Units can be installed at ground
level or rooftop applications. Optional field installed supplemental electric heat is available in 5, 7.5, 10, 15 and 20 kW.
The 15CHAX units utilize a scroll compressor. It operates
much like a standard compressor, but the scroll compressor
is unique in the way that it compresses refrigerant. The
compressor has overload protection.
Information contained in this manual is intended for use by
qualified service technicians only. All specifications are subject to change. Procedures outlined in this manual are presented as a recommendation only and do not supersede or
replace local or state codes.
IMPORTANT
Operating pressures of a R−410A unit are higher
than pressures in R−22 units. Always use service
equipment rated for R−410A.
2 to 5 Ton (7.0 to 17.6 kW)
WARNING
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, personal injury or loss of life. Installation and service must
be performed by a qualified installer or service
agency.
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
CAUTION
Electrostatic discharge can affect electronic
components. Take precautions during unit installation and service to protect the unit’s electronic
controls. Precautions will help to avoid control
exposure to electrostatic discharge by putting
the unit, the control and the technician at the
same electrostatic potential. Neutralize electrostatic charge by touching hand and all tools on an
unpainted unit surface before performing any
service procedure.
WARNING
Refrigerant can be harmful if it is inhaled. Refrigerant
must be used and recovered responsibly.
Failure to follow this warning may result in personal
injury or death.
Diameter − in. & No. of blades22 − 322 − 322 − 326 − 326 − 326 − 3
Blower wheel size dia. x width − in.10 x 610 x 610 x 810 x 1010 x 1010 x 10
Motor horsepower1/51/51/51/41/41/4
Motor horsepower1/21/21/23/43/43/4
Net weight of basic unit370370390500510510
Shipping weight of basic unit (1 Pkg.)415415435555565565
Electrical characteristics (60 hz)208/230V−1ph−60hz
15CHAXA
−24
15CHAXA
−30
15CHAXA
−36
15CHAXA
−42
15CHAXA
−48
15CHAXA
22752820335040305040
OPTIONAL ACCESSORIES − MUST BE ORDERED EXTRA
Compressor Crankcase Heater93M04SSSSSS
Compressor Hard Start Kit
NOTE − Circuit 1 Minimum Circuit Ampacity includes the Blower Motor Full Load Amps.
NOTE− Extremesofoperatingrangeareplusandminus10%oflinevoltage.
1 HACR type breaker or fuse.
2
RefertoNational or CanadianElectricalCodemanualtodeterminewire,fuseanddisconnectsizerequirements.
Rated Load Amps13.414.114.117.921.826.4
Locked Rotor Amps587377112117134
Full Load Amps1.11.11.11.71.71.7
Locked Rotor Amps2.22.22.2444
Rated Load Amps1.51.51.52.72.72.7
Locked Rotor Amps334555
Unit only, no electric heat303030405060
5 kW353535353535
ower
Motor
15 kW
7.5 kW454545505050
10 kW606060606060
Circuit 1− − −− − −60606060
Circuit 2− − −− − −30303030
20 kW
Circuit 1− − −− − −− − −606060
Circuit 2− − −− − −− − −606060
Unit only, no electric heat212222293439
5 kW31.331.331.333.033.033.0
ower
Motor
15 kW
7.5 kW44.344.344.346.146.146.1
10 kW57.357.357.359.159.159.1
Circuit 1− − −− − −57.359.159.159.1
Circuit 2− − −− − −26.026.026.026.0
20 kW
Circuit 1− − −− − −− − −59.159.159.1
Circuit 2− − −− − −− − −52.152.152.1
Btuh
Output
Page 3
Page 4
15CHAX PARTS ARRANGEMENT
TRANSFORMER
(T1)
BLOWER CONTROL
(A54)
FIGURE 1
15CHAX CONTROL BOX
CONTACTOR
SYSTEM OPERATION MONITOR
(A132)
(K1)
DUAL / FAN CAPACITOR
(C12)
FIGURE 2
Page 4
Page 5
I−APPLICATION
15CHAX 2 through 5 ton (7.0 through 17.6kW) model units
are single phase air conditioning units designed for outdoor
installation on a slab or roof top.The units are available in two
cabinet sizes. Electric heat can be factory or field installed if
required. Refer to the Engineering Handbook for more specific application data.
II−UNIT COMPONENTS
15CHAX components are shown in figure 1. Control box components are shown in figure 2.
A−Control Box Components
1−Compressor Contactor K1
K1 is a 24VAC to line voltage s ingle pole double break contactor, which energizes the compressor in response to thermostat
demand.
2−Control Transformer T1
All 15CHAX series units use line voltage to 24VAC transformer
mounted in the control box. The transformer supplies power to
control circuits in the unit. Transformers use two primary voltage taps as shown in figure 3.
208 / 240 VOLT TRANSFORMER
PRIMARY
L2
240 VOLTS
208 VOLTS
L1
FIGURE 3
SECONDARY
24 VOLTS
3−Dual Capacitor C12
The compressor and condenser fan in the 15CHAX series
units use permanent split capacitor motors. The capacitor is located in the control box. A dual rated capacitor is used for both
the condenser fan motor and the compressor (see unit wiring
diagram per respective unit). The fan side and the compressor
side of the capacitor have different MFD ratings. See side of
capacitor for ratings.
4− Blower Control A15
!
WARNING
Electric shock hazard. Can cause injury or
death. Before attempting to perform any
service or maintenance, turn the electrical
power to unit OFF at disconnect switch(es).
Unit may have multiple power supplies.
15CHAX units are equipped with a variable speed motor
that is capable of maintaining a specified CFM throughout
the external static range. A particular CFM can be obtained
by positioning jumpers (COOL, HEAT, and ADJUST) on
the blower control board. The HEAT and COOL jumpers
are labeled A, B, C and D. Each of the numbers corresponds with an air volume (CFM) setting. The ADJUST
jumper is labeled Test, −, +, and Norm. The + and − pin settings are used to add or subtract a percentage of the CFM
selected. The Test jumper is used to operate the motor in
the test mode. See figure 4.
Factory settings for the blower speed jumpers are given in
the wiring diagram. Figure 4 shows the blower control
board. Use tables 1, 2 and 3 to determine the correct air volume for operation in heat and cool mode.
The CFM LED located on the blower control board flashes
one time per 100 cfm to indicate selected blower speed.
For example, if the unit is operating at 1000 CFM, CFM LED
will flash 10 times. If the CFM is 1150, CFM LED will flash 11
full times plus one fast or half flash.
At times the light may appear to flicker or glow. This takes
place when the control is communicating with the motor between cycles. This is normal operation.
Read through the jumper settings section before adjusting
the jumper to obtain the appropriate blower speed.
To change jumper positions, gently pull the jumper off the pins
and place it on the desired set of pins. The following section
outlines the different jumper selections available and conditions associated with each one. Refer to figure 4.
After the CFM for each application has been determined,
the jumper settings must be adjusted to reflect those given
in tables 1, 2 and 3. From the tables, determine which row
most closely matches the desired CFM. Once a specific row
has been chosen (+, NORMAL, or −), CFM volumes from
other rows cannot be used. Below are descriptions of the
jumper selections.
The variable speed motor slowly ramps up to and down
from the selected air flow during both cooling and heating
demand. This minimizes noise and eliminates the initial
blast of air when the blower is initially energized.
ADJUST
The ADJUST pins allow the motor to run at normal speed,
approximately 15 percent higher, or approximately 15 percent lower than normal speed. Tables 1, 2 and 3 give three
rows (+, NORMAL, and −) with their respective CFM volumes. Notice that the normal adjustment setting for cool
speed position D in table 1 is 900 CFM. The + adjustment
setting for that position is 1035 CFM and for the − adjustment setting is 765 CFM. After the adjustment setting has
been determined, choose the remaining speed settings
from those offered in the table in that row.
The TEST pin is available to bypass the blower control and
run the motor at approximately 70 percent to make sure that
the motor is operational. This is used mainly in troubleshooting. The G terminal must be energized for the motor to
run.
Page 5
Page 6
BLOWER CONTROL BOARD (A54)
16−PIN PLUG
(BOARD TO MOTOR)
ADJUST
SELECTOR PINS
(Setting affects both
heating and cooling
modes)
DIAGNOSTIC
LED
FIGURE 4
COOL
The COOL jumper is used to determine the CFM during
cooling operation. This jumper selection is activated for
cooling when Y1 is energized.
The blower motor runs at 80 percent of the selected air flow
for the first 7−1/2 minutes of each cooling demand. This feature allows for greater humidity removal and saves energy.
In the cooling mode, the blower control board delays blower
operation for 5 seconds after the compressor starts. The
blower continues to operate for 90 seconds after the
compressor is de−energized.
HEAT
The HEAT jumper is used to determine CFM during backup
electric heat operation only. These jumper selections are
activated only when W is energized.
In the backup heat mode, the blower continues to operate
for 2 minutes after the heating demand is satisfied.
NOTE − Due to the nature of electric heat, CFM settings are
limited.
HEATING SPEED
SELECTOR PINS
COOLING SPEED
SELECTOR PINS
CONTINUOUS FAN
When the thermostat is set for Continuous Fan" operation
and there is no demand for heating or cooling, the blower
control will provide 50 percent of the COOL CFM selected.
NOTE − With the proper thermostat and subbase, continuous blower operation is possible by closing the R to G circuit. Cooling blower delay is also functional in this mode.
DEHUMIDIFICATION
The blower control board includes an HUM terminal which
provides for connection of a humidistat. The JV1 resistor on
the blower control board must be cut to activate the HUM
terminal. The humidistat must be wired to open on humidity
rise. When the dehumidification circuit is used, the variable
speed motor will reduce the selected air flow rate by 25 percent when humidity levels are high. An LED (D1) lights
when the blower is operating in the dehumidification mode.
Page 6
Page 7
TABLE 1
ADJUST
Jumper
ADJUST
Jumper
JUS
ADJUST
Jumper
15CHAX−24, 15CHAX−30 Blower Performance
0 through 0.80 in. w.g. (0 through 200 Pa) External Static Pressure Range
This monitor does not provide safety protection. The
monitor is a monitoring device only and cannot control or shut down other devices.
The Lennox system operation monitor (LSOM) detects
the most common fault conditions in the air conditioning
system. When an abnormal condition is detected, the
module communicates the specific condition through its
ALERT and TRIP lights. The module is capable of detecting both mechanical and electrical system problems. See
figure 5 for the system operation monitor.
Lennox System Operation Monitor (A132)
POWER LED
DATA OUTPUT
Y
C
R
ALERT LED
TRIP LED
DATA OUTPUT
CONNECTOR
.25" SPADE
CONNECTOR (5)
LSOM LED Functions
Power LED (green) −− Voltage within the range of
19−28VAC is present at the system monitor power connection.
Alert LED (yellow) −− Communicates an abnormal system condition through a unique flash code. The alert LED
flashes a number of times consecutively; then pauses;
then repeats the process. This consecutive flashing corresponds with a particular abnormal condition.
Trip LED (red) −− Indicates a demand signal from the thermostat; but detects no current to the compressor.
Flash code number −− Corresponds to a number of LED
flashes, followed by a pause, and then repeated.
Trip & Alert LEDs flashing simultaneously −− Indicates
that the control circuit voltage is too low for operation.
Reset ALERT flash code by removing 24VAC power from
monitor. Last ALERT flash code will display for 1 minute
after monitor is powered on.
LSOM codes are given in table 4.
Page 7
Page 8
TABLE 4
System Operation Monitor LED Troubleshooting Codes
Status LED ConditionStatus LED DescriptionStatus LED Troubleshooting Information
Green Power" LED ONModule has power24VAC control power is present at the module terminal.
Green Power" LED OFF Module not powering up
Red Trip" LED ONSystem and compressor
check out OK
Thermostat demand signal
Y1 is present, but compressor not running
Red Trip" & Yellow
Alert" LEDs Flashing
Yellow Alert" Flash
Code 1*
Simultaneous flashing.Indicates that the control circuit voltage is too low for operation.
Long Run Time −
Compressor is running
extremely long run cycles
Yellow Alert" Flash
Code 2*
System Pressure Trip −
Discharge or suction pressure out of limits or
compressor overloaded
Yellow Alert" Flash
Code 3*
Yellow Alert" Flash
Short Cycling − Compres-
sor is running only briefly
Locked Rotor
Code 4*
Yellow Alert" Flash
Open Circuit
Code 5*
Yellow Alert" Flash
Code 6*
Yellow Alert" Flash
Code 7*
Yellow Alert" Flash
Code 8*
Yellow Alert" Flash
Code 9*
Open Start Circuit − Cur-
rent only in run circuit
Open Run Circuit − Current
only in start circuit
Welded Contactor − Com-
pressor always runs
Low Voltage − Control circuit <17VAC
*Flash code number corresponds to a number of LED flashes, followed by a pause, and then repeated. Reset ALERT flash code by
removing 24VAC power from monitor; last code will display for 1 minute after monitor is powered on.
Determine/verify that both R and C module terminals are connected and
voltage is present at both terminals.
1.
2.
3.
Verify Y terminal is connected to 24VAC at contactor coil.
Verify voltage at contactor coil falls below 0.5VAC when off.
Verify 24VAC is present across Y and C when thermostat
demand signal is present; if not present, R and C wires are reversed.
1.
2.
3.
4.
5.
6.
1.
2.
3.
4.
5.
6.
7.
1.
2.
3.
4.
5.
1.
2.
3.
4.
1.
2.
3.
4.
1.
2.
3.
4.
5.
6.
7.
1.
2.
3.
1.
2.
1.
2.
1.
2.
Compressor protector is open.
Outdoor unit power disconnect is open.
Compressor circuit breaker or fuse(s) is open.
Broken wire or connector is not making contact.
Low pressure switch open if present in the system.
Compressor contactor has failed to close.
Low refrigerant charge.
Evaporator blower is not running.
Evaporator coil is frozen.
Faulty metering device.
Condenser coil is dirty
Liquid line restriction (filter drier blocked if present)
Thermostat is malfunctioning
.
.
.
High head pressure.
Condenser coil poor air circulation (dirty, blocked, damaged).
Condenser fan is not running.
Return air duct has substantial leakage.
If low pressure switch is present, see Flash Code 1 info.
Thermostat demand signal is intermittent.
Time delay relay or control board is defective.
If high pressure switch is present, see Flash Code 2 info.
If low pressure switch is present, see Flash Code 1 info.
Run capacitor has failed.
Low line voltage (contact utility).
Excessive liquid refrigerant in the compressor.
Compressor bearings are seized.
Outdoor unit power disconnect is open.
Unit circuit breaker or fuse(s) is open.
Unit contactor has failed to close.
High pressure switch is open and requires manual reset.
Open circuit in compressor supply wiring or connections.
Unusually long compressor protector reset time due to
extreme ambient temperature.
Compressor windings are damaged.
Run capacitor has failed.
Open circuit in compressor start wiring or connections.
Compressor start winding is damaged.
Open circuit in compressor start wiring or connections.
Compressor start winding is damaged.
Compressor contactor failed to open.
Thermostat demand signal not connected to module.
Control circuit transformer is overloaded.
Low line voltage (contact utility).
Page 8
Page 9
B−Blower Compartment
Access panels can easily be removed for service.
1−Blower Wheel
Blower wheel size varies between models. See SPECIFICATIONS.
2−Variable Speed Motor (B3)
15CHAX units use a three-phase, electronically controlled
D.C. brushless motor (controller converts single phase a.c. to
three phase D.C.), with a permanent-magnet-type rotor (figure 6). Because this motor has a permanent magnet rotor it
does not need brushes like conventional D.C. motors.
Internal components are shown in figure 7. The stator windings are split into three poles which are electrically connected
to the controller. This arrangement allows mo t o r win d i n gs to
turn on and off in sequence by the controller.
A solid-state controller is permanently attached to the
motor. The controller is primarily an A.C. to D.C. converter. Converted D.C. power is used to drive the motor. The
controller contains a microprocessor which monitors
varying conditions inside the motor (such as motor workload).
BLOWER MOTOR B3
J48
SHAFT
tion"). This allows for precise control of motor speed and allows
the motor to compensate for varying load conditions as sensed
by the controller. In this case, the controller monitors the static
workload on the motor and varies motor rpm in order to maintain constant airflow (cfm).
The motor controller is driven by the blower control
board (figure 4). The board receives its demand (PWM
signal or fixed 24 VAC or VDC signal) from optional controls
such as the Harmony zone control system, Lennox SignatureStatt or a conventional thermostat.
Motor rpm is continually adjusted internally to maintain
constant static pressure against the blower wheel. The controller monitors the static work load on the motor and motor ampdraw to determine the amount of rpm adjustment. Blower rpm
may be adjusted any amount in order to maintain a constant
cfm as shown in Blower Ratings Tables (1, 2 and 3). The cfm
remains relatively stable over a broad range of static pressure.
Since the blower constantly adjusts rpm to maintain a specified
cfm, motor rpm is not rated. Hence, the terms cool speed" ,
heat speed " or speed tap" if used in this manual, on the unit
wiring diagram and on blower B3, refer to blower cfm regardless of motor rpm.
When Harmony is used, speed taps are overridden and a
PWM signal generated by the Harmony controller continuously
varies motor speed based upon zone demands.
Initial Power Up
MOTOR
CONTROLLER
J49
FIGURE 6
BLOWER MOTOR COMPONENTS
STATOR
(WINDINGS)
BEARING
OUTPUT
SHAFT
ROTOR
FIGURE 7
The controller uses sensing devices to sense what position
the rotor is in at any given time. By sensing the position of the
rotor and then switching the motor windings on and off in sequence, the rotor shaft turns the blower.
All blower motors use single phase power. An external
run capacitor is not used. The motor uses permanently
lubricated ball-type bearings.
Internal Operation
Each time the controller switches a stator winding (figure 7) on
and off, it is called a pulse." The length of time each pulse
stays on is called the pulse width." By varying the pulse width ,
the controller varies motor speed (called pulse-width modula-
When line voltage is applied to B3, there will be a large inrush
of power lasting less than 1/4 second. This inrush charges a
bank of DC filter capacitors inside the controller. If the disconnect switch is bounced when the disconnect is closed, the disconnect contacts may become welded. Try not to bounce the
disconnect switch when applying power to the unit.
Motor Start-Up
When B3 begins start-up, the motor gently vibrates back and
forth for a moment. This is normal. During this time the electronic controller is determining the exact position of the rotor.
Once the motor begins turning, the controller slowly eases the
motor up to speed (this is called soft-start"). The motor may
take as long as 10-15 seconds to reach full speed. If the motor
does not reach 200rpm within 13 seconds, the motor shuts
down. Then the motor will immediately attempt a restart. The
shutdown feature provides protection in case of a frozen bearing or blocked blower wheel. The motor may attempt to start
eight times. If the motor does not start after the eighth try, the
controller locks out. Reset controller by momentarily turning off
power to unit.
The DC filter capacitors inside the controller are connected
electrically to the speed tap wires. The capacitors take
approximately 5 minutes to discharge when the disconnect
is opened. For this reason it is necessary to wait at least 5
minutes after turning off power to the unit before attempting to change speed taps.
Page 9
Page 10
DANGER
Disconnect power from unit and
wait at least five minutes to allow
capacitors to discharge before attempting to adjust motor speed tap
settings. Failure to wait may cause
personal injury or death.
External Operation (Speed Tap Priority)
Figure 8 shows the two quick-connect jacks (J48 and J49)
which connect the motor to the 15CHAX. Jack J48 is the
power plug and jack J49 connects the unit controls to the
motor.
Line voltage must be applied to J48 pin 5 in order for the motor to operate. When using 120VAC pins 1 and 2 must be
jumpered. When control voltage is applied to J49 pin 3 and
15, the motor is energized on the continuous fan mode.
When voltage is applied to J49 pin 2 in addition to pin 3 and
15 (first stage heating), the blower is energized on the low
speed heating tap. When voltage is applied to J49 pin 13 in
addition to pin 3 and 15 (second stage heating), the blower
is energized on the high speed heating tap. The motor assigns priority to J49 pin 2 so that if a call for cooling and a call for
heating are concurrent, heating call overrides and the blower
operates on high speed heating tap.
Precautions
If the 15CHAX or its electronically controlled blower motor is
improperly or inadequately grounded, it may cause television
interference (commonly known as RFI or radio frequency interference).
This interference is caused by internal switching frequencies of the motor controller. TV interference may
show up as small sp e c k s or lin es which randomly appear on
the TV screen accompanied by pops or clicks in the sound. Before attempting any service, make sure the indoor unit is causing the interference. To check, disconnect power to indoor unit
then check TV for continued signs of interference.
TV interference may be stopped by making sure the motor is solidly grounded to the cabinet (metal to metal) and
by making sure the cabinet is solidly grounded. If TV interfe rence persi sts, make sure the television (and all affected
RF appliances) are moved away from the 15CHAX. Also make
sure affected appliances are connected to a separate electrical
circuit.
BLOWER B3 HARNESS CONNECTORS
POWER
CONNECTOR J48
J48
PIN 1 - Jumper PIN 1 to PIN2 for 120VAC line input only.
PIN 2 - Jumper PIN 1 to PIN2 for 120VAC line input only.
PIN 3 - Ground
PIN 4 - AC Line
PIN 5 - AC Line
Using the transformer in the unit, test motor operation by jumping 24 volts
into the terminals illustrated below for the desired speed.
LOW (continuous blower) SPEED
12345678 910111213
J46
C
R
1. Disconnect power to unit.
2. Disconnect plug J46 from P46 located on the
blower control board.
3. Disconnect C and R from ignition control
board.
4. Disconnect Y" from ignition control and connect a separate wire between R" on the
transformer and Y" on the ignition control.
5. Connect voltage source as shown above.
6. Turn on power to unit. Blower should operate
at LOW speed.
COOLING SPEED
12345678 910111213
J46
C
R
7− Disconnect power to unit.
8− Connect voltage source as shown above.
9− Disconnect Y" on ignition control and con-
nect a separate wire between R" on transformer and Y" on ignition control.
10− Turn on power to unit. Blower should oper-
ate at COOLING speed.
VARIABLE SPEED CHECKOUT
14 15
16
To Y" on ignition control. !
14 15
16
To Y" on ignition control.
J46
C
J46
C
HEATING SPEED
12345678 91011121314 15
R
11− Disconnect power to unit.
12− Connect voltage source as shown above.
13− Disconnect W" from ignition control and
connect a separate wire between R" on
transformer and W" on the ignition control.
14− Turn on power to unit. Blower should operate
at HEATING speed.
16
To W" on on ignition control.
HIGH HEATING SPEED
1 2 3 4 5 6 7 8 9 10111213
R
15− Disconnect power to unit.
16− Connect voltage source as shown above.
17− Disconnect W2" from ignition control and
connect a separate wire between R" on
transformer and W2" on ignition control.
18− Turn on power to unit. Blower should operate
at HIGH HEATING speed.
14 15
To W2" on ignition control.
16
J49 CONTROL CONNECTORVOLTAGEWHEN VOLTAGE IS PRESENT
PIN 1C1CommonLow voltage transformer is powered
PIN 2W / W124VACW1 (1st stage heating) call from thermostat
PIN 3C2CommonLow voltage transformer is powered
PIN 4Delaysee note
PIN 5Coolsee note
1
1
Low voltage transformer is powered
Low voltage transformer is powered
PIN 6Y124VACY (cooling) call from thermostat
PIN 7Adjustsee note
1
Low voltage transformer is powered
PIN 8OutMotor sends pulse signals between pin 8 and pin 16 to signal CFM
PIN 9O24VACFrom thermostat (in heat pump application)
PIN 10DS / PWM0 / 24 VACLow voltage is transformer is powered and humidistat operation:
24VAC = normal humidity, 0VAC = high humidity (reduced CFM)
PIN 11Heatsee note
1
Low voltage transformer powered
PIN 12R24VACLow voltage transformer is powered
PIN 13EM / W224VACW2 (2nd stage heating) call from thermostat
PIN 14Y / Y2Not used on single stage cooling
PIN 15G24VACG is present from thermostat
PIN 16OutMotor sends pulse signals between pin 8 and 16 to signal CFM
1
signal from selection taps − A tap = 0 volts, B and C taps = half wave, D tap = 24VAC
Page 11
Page 12
C−Cooling Components
SCROLL COMPRESSOR
DISCHARGE
CROSS−SECTION OF SCROLLS
DISCHARGE
PRESSURE
DISCHARGE
STATIONARY
SCROLL
SUCTION
ORBITING
SCROLL
SUCTION
FIGURE 9
The scroll compressor design is simple, efficient and requires few moving parts. A cutaway diagram of the scroll
compressor is shown in figure 9. The scrolls are located in
the top of the compressor can and the motor is located in
the bottom of the compressor can. The oil level is immediately below the motor.
The scroll is a simple compression concept centered
around the unique spiral shape of the scroll and its inherent
properties. Two identical scrolls are mated together forming concentric spiral shapes (figure 10). One scroll remains
stationary, while the other is allowed to "orbit" (figure 11).
Note that the orbiting scroll does not rotate or turn but merely orbits the stationary scroll.
NOTE − The head of a scroll compressor may be hot since it
is in constant contact with discharge gas.
TIPS SEALED BY
DISCHARGE PRESSURE
FIGURE 10
The counterclockwise orbiting scroll draws gas into the outer
crescent shaped gas pocket created by the two scrolls (figure (figure 11 − 1). The centrifugal action of the orbiting scroll
seals off the flanks of the scrolls (figure 11 − 2). As the orbiting
motion continues, the gas is forced toward the center of the
scroll and the gas pocket becomes compressed (figure 11 −
3). When the compressed gas reaches the center, it is discharged vertically into a chamber and discharge port in the
top of the compressor (figure 9). The discharge pressure
forcing down on the top scroll helps seal off the upper and
lower edges (tips) of the scrolls (figure 10). During a single
orbit, several pockets of gas are compressed simultaneously
providing smooth continuous compression.
The scroll compressor is tolerant to the effects of liquid return. If liquid enters the scrolls, the orbiting scroll is allowed
to separate from the stationary scroll. Continued slugging of
liquid will cause damage to the scroll and replacement will
be necessary. The liquid is worked toward the center of the
scroll and is discharged. If the compressor is replaced, conventional Lennox cleanup practices must be used.
1
SUCTION
POCKET
SUCTION
3
SUCTION
ORBITING
SCROLL
STATIONARY
SCROLL
HIGH PRESSURE GAS
SUCTION
2
FLANKS SEALED
BY CENTRIFUGAL FORCE
MOVEMENT OF ORBIT
FIGURE 11
INTERMEDIATE PRESSURE
GAS
CRECENT SHAPED
GAS POCKET
SUCTION
4
DISCHARGE
POCKET
Page 12
Page 13
1−Condenser Fan
All 15CHAX units use single phase condenser fans. Specifications for the condenser fans are at the front of this manual. See
figure 12 for fan and motor replacement.
1 1/2"
fan guard
hub and shaft
should be flush
FIGURE
12
2−High Pressure Switch S4
S4 is a N.C. auto−reset high pressure switch located on the
liquid line. The switch shuts off the compressor when liquid
pressure rises above the factory setting. The switch on
15CHAX units is set to open at 590 + 10 psi and close at
418 + 10 psi.
3−Low Pressure Switch (S79)
2−Heating Element HE1 through HE4
Heating elements are composed of helix−wound bare nichrome wire exposed directly to the air stream. The elements are
supported by insulators mounted to the wire frame. Each element is energized independently by a corresponding relay located on the heat vest panel. Once energized, heat transfer is
instantaneous.
PHK VESTIBULE PARTS ARRANGEMENT
(PHK−10)
TB 2
SEQUENCER
RELAY
PRIMARY
LIMITS
The low pressure switch is an auto−reset N.C. switch that
opens on pressure drop. The switch is wired in series with
the high pressure switch S4 and compressor contactor
K1 and is located on the suction line . When suction pressure drops to 10 psig (68.95kPa) the switch opens and the
compressor is de−energized. When suction pressure
rises to 30 psig (206.85 kPa) the pressure switch will
close.
III−Electric Heat
A−Matchups and Ratings
Matchups and ratings are listed with ELECTRICAL DATA"
See table of contents.
B−Electric Heat Components
See figure 13 for electric heat parts arrangement.
1− Limit Switches 1, 2, 3 and 4
Limit switches 1, 2, 3and 4 are N.C. auto−reset high temperature limits located on the electric heat vest panel. Each heating
element is wired in series with a high temperature limit. When
the limit opens the corresponding heating element is de−energized. All other heating elements remain energized. The limits
will automatically close when temperatures return to normal.
Limit rating will be on front side.
FIGURE 13
3−Terminal Strip TB2 PHK−05, −07, −10
For electric heat sections without circuit breakers or fuses, line
voltage connections are made to terminal strip TB2.
4− Sequencer Relays 1 and 2
Relays 1 and 2 are N.O. sequencer relays with a resistive element for a coil and bi−metal disk which actuates the contacts.
The relays are located on the electric heat vest panel and are
energized by a 24V heating demand (W1 and W2) via jack/
plug P2 which is used to connect electric heat to the blower
control circuit. When energized, the internal resistance heats
the bi−metal disk causing the contacts to close. When the relay
is de−energized the disk cools and the contacts open. The relays energize different stages of heat, as well as the blower.
The blower is always first on and last off.
5−Circuit Breaker CB1 and CB2 (option)
PHK−15, −20,
Line voltage connections are made to circuit breakers CB1 and
CB2 in electric heat sections with circuit breakers. Table 5
shows amp rating for each circuit breaker used. Two−pole circuit breakers are used.
For maximum performance of this cooling system, the
operating temperatures and pressure should be checked
and subcooling determined at Standard ARI test conditions
of 82_ F outdoor temperature / 80_ F indoor dry bulb / 67_ F
indoor wet bulb. If subcooling measured deviates from
values in table 6, refrigerant charge should be adjusted
accordingly for maximum performance.
TABLE 6
Subcooling Values
Unit Model No.
82_F OD / 80_F IDDB
/ 67_F IDWB
Verify system performance using table 7 as a general guide.
Table 7 should not be used for charging unit. Minor variations
in these pressures may be expected due to differences in
installations. Significant differences could mean that the system is not properly charged or that a problem exists with
some component in the system.
Used carefully, this table could serve as a useful service
guide. Data is based on 80°F dry bulb / 67°F wet bulb return
air. Allow unit operation to stabilize before taking pressure
readings.
15CHAX−24
15CHAX−30
15CHAX−3615_
15CHAX−42
15CHAX−48
15CHAX−60
12_
10_
Table 7
Normal Operating Pressures
80°F db / 67°F wb RETURN AIRAir Temperature Entering Outdoor Coil (°F)
At the start of each cooling season, this equipment should
be serviced by a qualified technician. Periodic inspection
and maintenance normally consists of changing or cleaning
filters.
Filters
Not supplied. Inspect once a month. Replace disposable or
clean permanent type as necessary. DO NOT replace permanent type with disposable.
Motors
Indoor, outdoor fan and vent motors are permanently
lubricated and require no further lubrication. Motors
should be cleaned yearly to prevent the accumulation of
dust and dirt on the windings or motor exterior.
Coil
Dirt and debris should not be allowed to accumulate on the
coil surfaces or other parts in the air conditioning circuit.
Cleaning should be performed as often as necessary. Use a
brush, vacuum cleaner attachment, or other suitable
means. If water is used to clean the coil, be sure the power
to unit is shut off prior to cleaning.
NOTE − Care should be used when cleaning the coil so that
the coil fins are not damaged.
Do not permit the hot condenser air discharge to be obstructed by overhanging structures or shrubs.
Page 14
Page 15
VI−Wiring Diagram and Sequence of Operation
A−Unit Diagram
Page 15
Page 16
B−PHK Electric Heat
HE3HE3
HE4HE4
ELECTRIC HEAT - 2ND STAGEELECTRIC HEAT - 2ND STAGE
LIMIT SWITCH 3LIMIT SWITCH 3
BLKBLK
BLKBLK
BLKBLK
44
11
SEQUENCER 2SEQUENCER 2
55
33
BLUBLU
Wiring Diagram - Electric HeatWiring Diagram - Electric Heat
BLKBLK
BLKBLK
LIMIT SWITCH 4LIMIT SWITCH 4
YELYEL
HE1HE1
HE2HE2
ELECTRIC HEAT - 1ST STAGEELECTRIC HEAT - 1ST STAGE