Lennox 15CHAX User Manual

INSTALLATION
2006 Lennox Industries Inc.
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
INSTRUCTIONS
15CHAX SERIES UNITS
PACKAGED ELECTRIC UNIT (2−5 TONS)
505,201M (38152A082) 01/08 Supersedes 05/06
Shipping & Packing List
1 − Assembled packaged electric unit As soon as the unit is received, it should be inspected for
possible damage during transit. If you find any damage, im­mediately contact the last carrier.
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, person­al injury or loss of life. Installation and service must be performed by a licensed professional installer (or equivalent) or service agency.
Litho U.S.A.
Table of Contents
Shipping & Packing List 1. . . . . . . . . . . . . . . . . . . . . . . . .
Unit Dimensions 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parts Arrangement 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Requirements 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Location Selection 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Rigging & Setting Unit 4. . . . . . . . . . . . . . . . . . . . . . . . . .
Clearances 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Existing Common Vent Systems 5. . . . . . . . . . . . . . . . .
Condensate Drain 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Filters 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Supply & Return Connections 6. . . . . . . . . . . . . . . . . . . .
Compressors 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Blower Control Board 9. . . . . . . . . . . . . . . . . . . . . . . . . . .
System Operation Monitor 11. . . . . . . . . . . . . . . . . . . . . .
Unit Start−Up and Operation 13. . . . . . . . . . . . . . . . . . . .
Condenser Fan Clearances 14. . . . . . . . . . . . . . . . . . . . .
Maintenance 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
WARNING
If this unit is to be installed in a mobile or manufac­tured home application, the duct system must be sized to achieve static pressures within the manufacturer’s guidelines. All other installation guidelines must also be followed. Failure to do so may result in equipment damage, personal injury and improper unit performance.
CAUTION
Danger of sharp metallic edges. Can cause injury. Take care when servicing unit to avoid accidental contact with sharp edges.
WARNING
Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch(es). Unit may have multiple power supplies.
01/08
*2P0108*
Page 1
505,201M
*P505201M*
15CHAX Unit Dimensions − inches (mm)
Model
Number
FG
B
E
D
2−1/2 (64)
DOWN−FLOW
SUPPLY AIR
OPENING
FF
AA
2−3/4
(70)
2−1/2 (64)
D
E
DOWNFLOW RETURN AIR
OPENING
EE
TOP VIEW
BB
CCDD
Corner Weights
AA
Number
lbs. lbs. lbs. lbs. in. in.
15CHAX−24 75 94 117 94 16 29
C
15CHAX−30 75 94 117 94 16 29
15CHAX−36 83 97 121 104 16 30
15XHAX−42 110 138 163 129 21 33
15CHAX−48 114 139 164 134 21 33.5
15CHAX−60 119 145 171 140 21 33.5
BB CC DD EE FF
Center Of
Gravity
Model No.
15CHAX−24 15CHAX−30 15CHAX−36
15CHAX−42 15CHAX−48 15CHAX−60
2−1/2 (64)
END VIEW
D
2 (51)
D
2−3/4
JK
E
E
(70)
HORIZONTAL
RETURN
OPENINGS
H
AIR
(2)
FRONT VIEW
HORIZONTAL
SUPPLY AIR
A
OPENING
E
D
2−3/4
(70)
BACK VIEW
ELECTRICAL INLET
L
CONDENSATE DRAIN
END VIEW
A B C D E F
in.
34−1/4 870 65−3/8 1661 36−1/2 927 11−1/4 286 17−1/4 438 20 508
38−1/4 972 75 1905 46 1168 11−1/4 286 19−1/4 489 22 559
mm in. mm in. mm in. mm in. mm in. mm
15CHAX−24 15CHAX−30 15CHAX−36
15CHAX−42 15CHAX−48 15CHAX−60
Model No.
F G H J K L
in.
mm in. mm in. mm in. mm in. mm in. mm
20 508 8−1/2 216 3 76 20−1/4 514 4−1/2 114 19 483
22 559 9−1/4 241 3−1/4 83 22−1/4 572 4 102 16−1/4 413
Page 2
Parts Arrangement
General
These installation instructions are intended as a general guide only, for use by an experienced, licensed contractor (or equivalent).
The 15CHAX units are single−package electric units designed for outdoor installation on a rooftop or a slab. The units are equipped with a transformer and blower control for applications which do not include electric heat. Electric heat sections are available for separate order.
The unit must be sized based on heat loss and heat gain calculations made according to the methods of the Air Conditioning Contractors of America (ACCA).
The units are shipped assembled. All piping, refrigerant charge, and electrical wiring are factory−installed and tested. The units require electric power, condensate drain and duct connections at the point of installation.
Use of this unit as a construction heater or air conditioner is not recommended during any phase of construction. Very low return air temperatures, harmful vapors and operation of the unit with clogged or misplaced filters will damage the unit.
If this unit has been used for heating or cooling of buildings or structures under construction, the following conditions must be met or the warranty will be void:
A room thermostat must control the unit. The use of
fixed jumpers that will provide continuous heating or cooling is not allowed.
A pre−filter must be installed at the entry to the return air
duct.
The return air duct must be provided and sealed to the
unit.
Return air temperature range between 55°F (13°C)
and 80°F (27°C) must be maintained.
Air filters must be replaced and pre−filter must be re-
moved upon construction completion.
The unit components, duct system, air filters and evap-
orator coil must be thoroughly cleaned following final construction clean−up.
The unit operating conditions (including airflow, cool-
ing operation, and heating operation) must be verified according to these installation instructions.
Requirements
These units must be installed in accordance with all applicable national and local safety codes.
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities having jurisdiction before installation.
If components are to be added to a unit to meet local codes, they are to be installed at the dealer’s and/or customer’s expense.
These units are design listed by UL in both the United States and Canada as follows:
For use as a cooling unit. For outdoor installation only.
Page 3
For installation on combustible material.
WARNING
Product contains fiberglass wool.
Disturbing the insulation in this product during installation, maintenance, or repair will expose you to fiberglass wool dust. Breathing this may cause lung cancer. (Fiberglass wool is known to the State of California to cause cancer.)
Fiberglass wool may also cause respiratory, skin, and eye irritation.
To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor.
Lennox Industries Inc.
P.O. Box 799900 Dallas, TX 75379−9900
Location Selection
Use the following guidelines to select a suitable location for these units.
1 − Unit is designed for outdoor installation only. Unit must
be installed so all electrical components are protected
from water. 2 − Condenser coils must have an unlimited supply of air. 3 − For ground level installation, use a level pre−fabricated
pad or use a level concrete slab with a minimum thick-
ness of 4 inches. The length and width should be at
least 6 inches greater than the unit base. Do not tie the
slab to the building foundation. 4 − Maintain level within a tolerance of 1/4 inch maximum
across the entire length or width of the unit.
Rigging & Setting Unit
Exercise care when moving the unit. Do not remove any packaging until the unit is near the place of installation. An optional lifting lug kit (92M51) may be purchased separately for use in rigging the unit for lifting. Spreaders MUST be used across the top of the unit. Recommended spreader length: 2, 2−1/2, 3−ton units −− 44"; 3−1/2, 4, 5−ton units −− 54".
CAUTION
Before lifting a unit, make sure that the weight is dis­tributed equally on the cables so that it will lift even­ly.
Units may also be moved or lifted with a forklift while still in the factory supplied packaging.
NOTE − Length of forks must be a minimum of 42 inches.
Accessory Lift Kit
Lifting Bracket
Accessory
Sheet Metal Screw
Figure 1
Clearances
All units require certain clearances for proper operation and service. Refer to figure 2 for the clearances required for combustible construction, servicing, and proper unit operation.
Service Clearances
REAR
30
(762)
FRONT
*Rear clearance is 18" (457) when required for accessory maintenance. NOTE − Top Clearance − 36 in. (914 mm) NOTE − Entire perimeter of unit base requires support when elevated above mounting surface.
Figure 2
NOTE − Do not permit overhanging structures or shrubs to obstruct condenser air discharge outlet.
In the U.S. units may be installed on combustible floors made from wood or class A, B, or C roof covering material. In Canada, units may be installed on combustible floors.
3 (156)*
48 (1219)
24
(610)
Page 4
Existing Common Vent Systems
The 15CHAX packaged cooling units with auxiliary electric heat may replace an existing furnace which is being re­moved from a venting system commonly run with separate gas appliances. In this case, the existing vent system is likely to be too large to properly vent the remaining at­tached appliances.
Conduct the following test while each appliance is operat­ing and the other appliances (which are not operating) re­main connected to the common venting system. If the vent­ing system has been installed improperly, you must correct the system as indicated in the general venting re­quirements section.
1 − Seal any unused openings in the common venting sys-
tem.
2 − Inspect the venting system for proper size and horizon-
tal pitch. Determine that there is no blockage, restric­tion, leakage, corrosion, or other deficiencies which could cause an unsafe condition.
3 − Close all building doors and windows and all doors be-
tween the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dry­ers and any appliances not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will oper­ate at maximum speed. Do not operate a summer ex­haust fan. Close fireplace dampers.
4 − Follow the lighting instructions. Turn on the appliance
that is being inspected. Adjust the thermostat so that the appliance operates continuously.
5 − After the main burner has operated for 5 minutes, test
for leaks of flue gases at the draft hood relief opening. Use the flame of a match or candle, or smoke from a cigarette, cigar, or pipe.
6 − After determining that each appliance connected to the
common venting system is venting properly, (step 3) return all doors, windows, exhaust fans, fireplace dampers, and any other gas−burning appliances to their previous mode of operation.
7 − If a venting problem is found during any of the preced-
ing tests, the common venting system must be modi­fied to correct the problem.
Resize the common venting system to the minimum vent pipe size determined by using the appropriate tables in Appendix G. (These are in the current stan­dards of the National Fuel Gas Code ANSI-Z223.1/NFPA 54 in the USA, and the appropri-
ate Category 1 Natural Gas and Propane appliances venting sizing tables in the current standards of the CSA B149 Natural Gas and Propane Installation Codes in Canada.)
Condensate Drain
The 15CHAX unit is equipped with a 3/4 inch FPT coupling for condensate line connection. Plumbing must conform to local codes. Use a sealing compound on male pipe threads.
The drain line must be properly trapped and routed to a suitable drain. See figure 3 for proper drain arrangement. The drain line must pitch to an open drain or pump a minimum of 1 inch per 10 feet to prevent clogging of the line. Seal around drain connection with suitable material to prevent air leakage into return air system.
NOTE − Drain line connection may not carry the weight of the unsupported drain line. Support the drain line, if necessary.
Drain piping should not be smaller than drain connection at coil. An open vent in drain line will some times be required due to line length, friction and static pressure. Drains should be constructed in a manner to facilitate future clean­ing.
NOTE − The condensate drain line MUST be trapped to provide proper drainage.
CAUTION
Condensate line connection must be hand−tight­ened. Do not use tools.
Typical Condensate Drain
Unit
Positive Liquid Seal Required
Drain Connection
12.00” Max.
Figure 3
1.00” Min.
3.00” Min.
Page 5
Filters
Filters are not factory−supplied with the unit; however, optional internally installed filter kits are available. Filter kit 92M54 is used with 2, 2−1/2 and 3−ton units. Filter kit 92M55 is used with 3−1/2, 4 and 5−ton units. The filter kits accommodate the use of 1", 2" or 4" filters. If the optional filter kit is not used, a filter must be field−installed.
Filters must always be installed ahead of evaporator coil and must be kept clean or replaced. Dirty filters will reduce the airflow of the unit. Filter sizes are shown in table 1.
Removing Supply and Return
Air Opening Covers
2
1.Remove screw and lift.
2.Slide cover to free back pin.
1
Base
Table 1
Unit Filter Size
Unit Model Filter Size Filter Quantity
−24, −30, −36 20 in. X 25 in. 1
−42, −48, −60 16 in. X 25 in. 2
The Healthy Climate® PureAir® air purification system (PCO20−28) may be used with 15CHAX units installed in horizontal air discharge applications only. Installation hardware kit (Y0629) is required to install the PCO20−28 (X8787) in the packaged unit. The PCO20−28 is designed for universal voltage, and is ready to operate at 208/230V. When used, the PCO should be installed before the unit is set in place and before the duct connections are made.
Supply & Return Duct Connections
The duct system should be designed and sized according to the methods in Manual Q of the Air Conditioning Contractors of America (ACCA).
A closed return duct system shall be used. This shall not preclude use of economizers or outdoor fresh air intake. It is recommended that supply and return duct connections at the unit be made with flexible joints.
The supply and return air duct systems should be designed for the CFM and static requirements of the job. They
should NOT be sized by simply matching the dimensions of the duct connections on the unit.
Ducting installed outdoors MUST be insulated and waterproofed.
Figure 4
The upper return air opening cover must be removed when the PureAir used. In PCO applications, both upper and lower return air openings must be covered by the return air plenum to ensure proper PCO operation. The upper return air opening is not required in horizontal applications when the PCO is not used.
®
air purification system (PCO20−28) is being
Compressors
Units are shipped with the compressor mountings factory−adjusted and ready for operation.
CAUTION
Do not loosen compressor mounting bolts.
Electrical
All wiring should be done in accordance with the current National Electric Code ANSI/NFPA No. 70 in the United States. In Canada, wiring must be done in accordance with the current CSA C22.2 Part 1. Local codes may take precedence.
Use wiring with a temperature limitation of 75C min.; run the 208 or 230 volt, 60 hertz electric power supply through a fused disconnect switch to control box of unit and connect as shown in the wiring diagram located on the inside of the control access panel. Refer to figure 5 for electrical access.
CAUTION
When fastening duct system to side duct flanges on unit, insert screws through duct flanges only. Do not insert screws through casing. Outdoor duct must be insulated and waterproofed.
The 15CHAX unit is shipped ready for horizontal air discharge (side duct connections). If bottom air discharge is desired, the covers must be removed from the supply and return air openings on the bottom of the unit and re−installed to cover the side openings.
Figure 5
Page 6
Unit must be electrically grounded in accordance with local codes or in the absence of local codes with the National Electric Code, ANSI/NFPA No. 70 (latest edition) or CSA C22.2 Part 1 (latest edition).
Power supply to the unit must comply with all applicable codes and NEC or CEC. A fused disconnect switch should be field provided for the unit. The switch must be separate from all other circuits. If any of the wire supplied with the unit must be replaced, replacement wire must be of the type shown on the wiring diagram.
Electrical wiring must be sized to carry minimum circuit ampacity marked on the unit. USE COPPER CONDUCTORS ONLY. Each unit must be wired with a separate branch circuit and be properly fused.
WARNING
Unit is equipped with a single−pole contactor. Line voltage is present at all components when unit is not in operation. Disconnect all remote electric power supplies before opening access panel. Unit may have multiple power supplies. Failure to disconnect all power supplies could result in personal injury or death.
the installation instructions packaged with the electric heat section.
Thermostat
The room thermostat should be located on an inside wall where it will not be subject to drafts, sun exposure or heat from electrical fixtures or appliances. Follow manufacturer’s instructions enclosed with thermostat for general installation procedure. Color coded insulated wires (# 18 AWG) should be used to connect thermostat to unit.
Typical Single−Phase Unit Wiring Connections
CAUTION
When connecting electrical power and control wir­ing to the unit, waterproof type connectors MUST be used so that water or moisture cannot be drawn into the unit during normal operation.
WARNING
Unit must be grounded in accordance with national and local codes. Failure to ground unit properly can result in personal injury or death.
See figure 6 for typical field wiring connections and figure 7 for typical unit wiring diagram.
Optional Electric Heat
Optional electric heat is available and must be purchased separately. Install the electric heat section as outlined in
Figure 6
Page 7
Typical Wiring Diagram
15CHAX Series Packaged Electric Units
Figure 7
Page 8
Blower Control Board (A54)
!
WARNING
Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch(es). Unit may have multiple power supplies.
15CHAX units are equipped with a variable speed motor that is capable of maintaining a specified CFM throughout the external static range. A particular CFM can be obtained by positioning jumpers (COOL, HEAT, and ADJUST) on the blower control board. The HEAT and COOL jumpers are labeled A, B, C and D. Each of the numbers corre­sponds with an air volume (CFM) setting. The ADJUST jumper is labeled Test, −, +, and Norm. The + and − pin set­tings are used to add or subtract a percentage of the CFM selected. The Test jumper is used to operate the motor in the test mode. See figure 8.
Factory settings for the blower speed jumpers are given in the wiring diagram in figure 7. Figure 8 shows the blower control board. Use tables 2, 3 and 4 to determine the cor­rect air volume for operation in heat and cool mode.
The CFM LED located on the blower control board flashes one time per 100 cfm to indicate selected blower speed. For example, if the unit is operating at 1000 CFM, CFM LED will flash 10 times. If the CFM is 1150, CFM LED will flash 11 full times plus one fast or half flash.
At times the light may appear to flicker or glow. This takes place when the control is communicating with the motor be­tween cycles. This is normal operation.
Read through the jumper settings section before adjusting the jumper to obtain the appropriate blower speed.
To change jumper positions, gently pull the jumper off the pins and place it on the desired set of pins. The following section outlines the different jumper selections available and conditions associated with each one. Refer to figure 8.
After the CFM for each application has been determined, the jumper settings must be adjusted to reflect those given in tables 2, 3 and 4. From the tables, determine which row most closely matches the desired CFM. Once a specific row has been chosen (+, NORMAL, or −), CFM volumes from other rows cannot be used. Below are descriptions of the jumper selections.
The variable speed motor slowly ramps up to and down from the selected air flow during both cooling and heating demand. This minimizes noise and eliminates the initial blast of air when the blower is initially energized.
ADJUST
The ADJUST pins allow the motor to run at normal speed, approximately 15 percent higher, or approximately 15 per­cent lower than normal speed. Tables 2, 3 and 4 give three rows (+, NORMAL, and −) with their respective CFM vol­umes. Notice that the normal adjustment setting for cool speed position D in table 2 is 900 CFM. The + adjustment setting for that position is 1035 CFM and for the − adjust­ment setting is 765 CFM. After the adjustment setting has been determined, choose the remaining speed settings from those offered in the table in that row.
The TEST pin is available to bypass the blower control and run the motor at approximately 70 percent to make sure that the motor is operational. This is used mainly in trouble­shooting. The G terminal must be energized for the motor to run.
DIAGNOSTIC
LED
BLOWER CONTROL BOARD (A54)
16−PIN PLUG
(BOARD TO MOTOR)
Figure 8
Page 9
ADJUST
SELECTOR PINS (Setting affects both heating and cooling
modes)
HEATING SPEED SELECTOR PINS
COOLING SPEED
SELECTOR PINS
COOL
JUST"
Jumper
JUST"
Jumper
JUST"
Jumper
The COOL jumper is used to determine the CFM during cooling operation. This jumper selection is activated for cooling when Y1 is energized.
The blower motor runs at 80 percent of the selected air flow for the first 7−1/2 minutes of each cooling demand. This fea­ture allows for greater humidity removal and saves energy.
In the cooling mode, the blower control board delays blower operation for 5 seconds after the compressor starts. The blower continues to operate for 90 seconds after the compressor is de−energized.
HEAT
The HEAT jumper is used to determine CFM during back­up electric heat operation only. These jumper selections are activated only when W is energized.
In the backup heat mode, the blower continues to operate for 2 minutes after the heating demand is satisfied.
NOTE − Due to the nature of electric heat, CFM settings are limited.
CONTINUOUS FAN
When the thermostat is set for Continuous Fan" operation and there is no demand for heating or cooling, the blower control will provide 50 percent of the COOL CFM selected.
NOTE − With the proper thermostat and subbase, continu­ous blower operation is possible by closing the R to G cir­cuit. Cooling blower delay is also functional in this mode.
DEHUMIDIFICATION
The blower control board includes an HUM terminal which provides for connection of a humidistat. The JV1 resistor on the blower control board must be cut to activate the HUM terminal. The humidistat must be wired to open on humidity rise. When the dehumidification circuit is used, the variable speed motor will reduce the selected air flow rate by 25 percent when humidity levels are high. An LED (D1) lights when the blower is operating in the dehumidifi­cation mode.
Table 2
15CHAX−24, 15CHAX−30 Blower Performance
0 through 0.80 in. w.g. (0 through 200 Pa) External Static Pressure Range
AD-
"
Jumper
Setting
NORM 1000 470 800 380 600 285 900 425 1000 470 1000 470 1000 470 1000 470 500 235 400 190 300 140 450 210
A
cfm
+ 1150 545 920 435 690 325 1035 490 1150 545 1150 545 1150 545 1150 545 575 270 460 215 345 165 520 245
850 400 680 320 510 240 765 360 1000 470 1000 470 1000 470 1000 470 425 200 340 160 300 140 385 180
COOL" Speed
B C D A B C D A B C D
L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
Jumper Speed Positions
HEAT" Speed CONTINOUS FAN" Speed
Table 3
15CHAX−36 Blower Performance
0 through 0.80 in. w.g. (0 through 200 Pa) External Static Pressure Range
AD-
"
Jumper
Setting
NORM 1200 565 1000 470 800 380 1100 520 1200 565 1200 565 1000 470 1000 470 600 285 500 235 400 190 550 260
A
cfm
+ 1380 650 1150 545 920 435 1265 575 1380 650 1380 650 1150 545 1150 545 690 325 575 270 460 215 635 300
1020 480 850 400 680 320 935 440 1200 565 1200 565 1000 470 1000 470 510 240 425 200 350 165 470 220
COOL" Speed
B C D A B C D A B C D
L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
Jumper Speed Positions
HEAT" Speed CONTINOUS FAN" Speed
Table 4
15CHAX−42, 15CHAX−48, 15CHAX−60, Blower Performance
0 through 0.80 in. w.g. (0 through 200 Pa) External Static Pressure Range
AD-
"
Jumper
Setting
NORM 1800 850 1600 755 1400 660 1200 565 1400 660 1400 660 1400 660 1400 660 900 425 800 380 700 330 600 285
A
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+ 2070 975 1840 870 1610 760 1380 650 1610 760 1610 760 1610 760 1610 760 1035 490 920 435 805 380 690 325
− 1530 720 1360 640 1190 560 1020 480 1400 660 1400 660 1400 660 1400 660 765 360 680 320 595 280 510 240
COOL" Speed
B C D A B C D A B C D
Jumper Speed Positions
HEAT" Speed CONTINOUS FAN" Speed
Page 10
System Operation Monitor (LSOM)
The system operation monitor (A132) detects the most common fault conditions in the air conditioning system. When an abnormal condition is detected, the module com­municates the specific condition through its ALERT and TRIP lights. The module is capable of detecting both me­chanical and electrical system problems. See figure 9 for the system operation monitor.
System Operation Monitor (A132)
POWER LED
DATA OUTPUT
Y
C
R
ALERT LED
TRIP LED
DATA OUTPUT CONNECTOR
.25" SPADE CONNECTOR (5)
Figure 9
IMPORTANT
This monitor does not provide safety protection. The monitor is a monitoring device only and cannot con­trol or shut down other devices.
LSOM LED Functions Power LED (green) −− Voltage within the range of
19−28VAC is present at the system monitor power connec­tion.
Alert LED (yellow) −− Communicates an abnormal system condition through a unique flash code. The alert LED flashes a number of times consecutively; then pauses; then repeats the process. This consecutive flashing corre­sponds with a particular abnormal condition.
Trip LED (red) −− Indicates a demand signal from the ther­mostat; but detects no current to the compressor.
Flash code number −− Corresponds to a number of LED flashes, followed by a pause, and then repeated.
Trip & Alert LEDs flashing simultaneously −− Indicates that the control circuit voltage is too low for operation.
Reset ALERT flash code by removing 24VAC power from monitor. Last ALERT flash code will display for 1 minute af­ter monitor is powered on.
LSOM codes are given in table 5.
Page 11
Table 5
System Operation Monitor LED Troubleshooting Codes
Status LED Condition Status LED Description Status LED Troubleshooting Information
Green Power" LED ON Module has power 24VAC control power is present at the module terminal.
Green Power" LED
Module not powering up
OFF Red Trip" LED ON System and compressor
check out OK
Thermostat demand signal Y1 is present, but compres­sor not running
Red Trip" & Yellow Alert" LEDs Flashing
Yellow Alert" Flash Code 1*
Simultaneous flashing. Indicates that the control circuit voltage is too low for operation.
Long Run Time − Compressor is running extremely long run cycles
Yellow Alert" Flash Code 2*
System Pressure Trip
Discharge or suction pres­sure out of limits or compressor overloaded
Yellow Alert" Flash Code 3*
Yellow Alert" Flash
Short Cycling − Compres-
sor is running only briefly
Locked Rotor
Code 4*
Yellow Alert" Flash
Open Circuit
Code 5*
Yellow Alert" Flash Code 6*
Yellow Alert" Flash Code 7*
Yellow Alert" Flash Code 8*
Yellow Alert" Flash Code 9*
Open Start Circuit
Current only in run circuit
Open Run Circuit − Current only in start circuit
Welded Contactor − Compressor always runs
Low Voltage − Control circuit <17VAC
*Flash code number corresponds to a number of LED flashes, followed by a pause, and then repeated. Reset ALERT flash code by removing 24VAC power from monitor; last code will display for 1 minute after monitor is powered on.
Determine/verify that both R and C module terminals are connected and voltage is present at both terminals.
1.
2.
3.
Verify Y terminal is connected to 24VAC at contactor coil. Verify voltage at contactor coil falls below 0.5VAC when off. Verify 24VAC is present across Y and C when thermostat
demand signal is present; if not present, R and C wires are reversed.
1.
2.
3.
4.
5.
6.
1.
2.
3.
4.
5.
6.
7.
1.
2.
aged).
3.
4.
5.
1.
2.
3.
4.
1.
2.
3.
4.
1.
2.
3.
4.
5.
6.
7.
1.
2.
3.
1.
2.
1.
2.
1.
2.
Compressor protector is open. Outdoor unit power disconnect is open. Compressor circuit breaker or fuse(s) is open. Broken wire or connector is not making contact. Low pressure switch open if present in the system. Compressor contactor has failed to close.
Low refrigerant charge. Evaporator blower is not running. Evaporator coil is frozen. Faulty metering device. Condenser coil is dirty Liquid line restriction (filter drier blocked if present) Thermostat is malfunctioning
.
.
.
High head pressure. Condenser coil poor air circulation (dirty, blocked, dam-
Condenser fan is not running. Return air duct has substantial leakage. If low pressure switch is present, see Flash Code 1 info.
Thermostat demand signal is intermittent. Time delay relay or control board is defective. If high pressure switch is present, see Flash Code 2 info. If low pressure switch is present, see Flash Code 1 info.
Run capacitor has failed. Low line voltage (contact utility). Excessive liquid refrigerant in the compressor. Compressor bearings are seized.
Outdoor unit power disconnect is open. Unit circuit breaker or fuse(s) is open. Unit contactor has failed to close. High pressure switch is open and requires manual reset. Open circuit in compressor supply wiring or connections. Unusually long compressor protector reset time due to extreme ambient temperature. Compressor windings are damaged.
Run capacitor has failed. Open circuit in compressor start wiring or connections. Compressor start winding is damaged.
Open circuit in compressor start wiring or connections. Compressor start winding is damaged.
Compressor contactor failed to open. Thermostat demand signal not connected to module.
Control circuit transformer is overloaded. Low line voltage (contact utility).
Page 12
Unit Start−Up and Operation
Each 15CHAX packaged cooling unit is factory−charged with R−410A refrigerant. The compressor is hermetically sealed, internally sprung and base−mounted with
immediately stop. The circulating air blower continues operating through a 90−second delay.
Unit compressors have internal protection. If there is an abnormal rise in the compressor temperature, the protector will open and the compressor will stop.
rubber−insulated hold−down bolts.
System Performance
Pre−Start Check List:
1 − Make sure refrigerant lines do not rub against the cabi-
net or each other.
2 − Inspect all electrical wiring, both factory− and field−
installed, for loose connections.
3 − Check voltage at the disconnect switch. Voltage must
be within the range listed on the unit nameplate. If not, consult power company and have voltage condition corrected before starting unit.
4 − Recheck voltage with unit running. If power is not with-
in the range listed on the unit nameplate, stop the unit and consult the power company. Check unit amper­age. Refer to unit nameplate for correct running amps.
5 − Make sure filter is in place before unit start−up.
6 − Before placing the unit into full operation, energize the
unit for three false starts. Energize the compressor just long enough for it to make a few revolutions, wait five to seven minutes before repeating a second and third time.
Cooling Sequence of Operation
When the thermostat calls for cooling, the R" to Y" circuit is closed to energize the compressor contactor. The contactor brings on both the compressor and outdoor fan. The thermostat also closes the R" to G" circuit to energize the circulating air blower. When the cooling demand is satisfied, the thermostat opens the circuits, as well as the compressor contactor. The compressor and outdoor fan
For maximum performance of this cooling system, the operating temperatures and pressure should be checked and subcooling determined at Standard ARI test conditions of 82 F outdoor temperature / 80 F indoor dry bulb / 67 F indoor wet bulb. If subcooling measured deviates from values in table 6, refrigerant charge should be adjusted accordingly for maximum performance.
Table 6
Suction Superheat Values
Unit Model No.
15CHAX−24 15CHAX−30
15CHAX−36 15
15CHAX−42 15CHAX−48 15CHAX−60
Verify system performance using table 7 as a general guide. Table 7 should not be used for charging unit. Minor variations in these pressures may be expected due to dif­ferences in installations. Significant differences could mean that the system is not properly charged or that a prob­lem exists with some component in the system.
Used carefully, this table could serve as a useful service guide. Data is based on 80°F dry bulb / 67°F wet bulb return air. Allow unit operation to stabilize before taking pressure readings.
Suction Superheat
82F OD / 80F IDDB
/ 67F IDWB
12
10
Table 7
Normal Operating Pressures
80°F db / 67°F wb RETURN AIR Air Temperature Entering Outdoor Coil (°F)
UNIT PRESSURE 65 70 75 80 82 85 90 95 100 105 110 115 15CHAX−24 142 143 144 146 146 147 148 149 150 151 152 153 15CHAX−30 134 136 138 140 141 142 144 146 148 149 151 152 15CHAX−36 15CHAX−42 15CHAX−48 140 141 142 144 144 145 146 147 148 149 150 151 15CHAX−60 143 144 145 146 146 147 147 148 149 150 151 152 15CHAX−24 219 242 264 287 296 310 333 355 379 398 430 457 15CHAX−30 232 255 277 300 309 323 345 368 390 408 440 470 15CHAX−36 15CHAX−42 15CHAX−48 243 264 285 307 315 328 349 370 391 408 440 470 15CHAX−60 257 280 303 326 335 349 372 395 418 436 468 497
Suction
Liquid
143 144 146 147 148 149 151 152 155 155 157 157 140 140 140 141 141 141 142 142 143 144 145 147
244 268 292 316 326 340 363 369 410 429 461 493 225 247 269 291 300 314 337 357 383 402 434 457
Page 13
Condenser Fan Clearances
The top of the condenser fan should be 1−1/2 inches from the bottom of the top grille. This dimension should be checked and the fan should be adjusted accordingly any time servicing of the outdoor fan system is required.
Maintenance
At the start of each cooling season, this equipment should be serviced by a licensed professional technician (or equivalent). Periodic inspection and maintenance normally consists of changing or cleaning filters.
Filters
Not supplied. Inspect once a month. Replace disposable or clean permanent type as necessary. DO NOT replace per­manent type with disposable.
Accessories
Description
Filter Kit (2−ton to 3−ton capacity units) 92M54 Filter Kit (3−1/2−ton to 5−ton capacity units) 92M55 PCO20−28 X8787 Installation Hardware Kit for PCO20−28 Y0629
Motors
Indoor, outdoor fan and vent motors are permanently lubricated and require no further lubrication. Motors should be cleaned yearly to prevent the accumulation of dust and dirt on the windings or motor exterior.
Coil
Dirt and debris should not be allowed to accumulate on the coil surfaces or other parts in the air conditioning circuit. Cleaning should be performed as often as necessary. Use a brush, vacuum cleaner attachment, or other suitable means. If water is used to clean the coil, be sure the power to unit is shut off prior to cleaning.
NOTE − Care should be used when cleaning the coil so that the coil fins are not damaged.
Do not permit the hot condenser air discharge to be ob­structed by overhanging structures or shrubs.
LENNOX Cat.
Number
Page 14
Loading...