Lennox 14HPX, 14HPX−018, 14HPX−024, 14HPX−030, 14HPX−036 Unit Information

...
Page 1
© 2007 Lennox Industries Inc.
Corp. 0719−L5
14HPX
Service Literature
1.5 to 5 ton
Revised 06−2008
The 14HPX is a residential split-system heat pump. The series is designed for use with expansion valves (TXV) and HFC−410A refrigerant. All 14HPX units utilize scroll compres­sors.
14HPX series units are available in 1−1/2, 2, 2 -1/2, 3, 3
-1/2, 4 and 5 ton capacities. All major components (indoor blower and coil) must be matched according to Lennox rec­ommendations for the compressor to be covered under warranty. Refer to the Engineering Handbook for approved system matchups.
This manual is divided into sections which discuss the major components, refrigerant system, charging proce­dure, maintenance and operation sequence.
Information contained in this manual is intended for use by qualified service technicians only. All specifications are subject to change.
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
CAUTION
Electrostatic discharge can affect electronic components. Take precautions during unit instal­lation and service to protect the unit’s electronic controls. Precautions will help to avoid control exposure to electrostatic discharge by putting the unit, the control and the technician at the same electrostatic potential. Neutralize electro­static charge by touching hand and all tools on an unpainted unit surface before performing any service procedure.
WARNING
Refrigerant can be harmful if it is inhaled. Refrigerant must be used and recovered responsibly.
Failure to follow this warning may result in person­al injury or death.
CAUTION
In order to avoid injury, take proper precaution when lifting heavy objects.
Table of Contents
Specifications / Electrical Data Page 2. . . . . . . . .
I Unit Components Page 4. . . . . . . . . . . . . . . . . . .
II Refrigerant System Page 14. . . . . . . . . . . . . . . . .
III Charging Page 17. . . . . . . . . . . . . . . . . . . . . . . . .
IV Maintenance Page 22. . . . . . . . . . . . . . . . . . . . . .
V Diagrams Page 23. . . . . . . . . . . . . . . . . . . . . . . . .
Page 2
SPECIFICATIONS General
Model No. 14HPX−018 14HPX−024 14HPX−030
6
14HPX−036
Data
Nominal Tonnage 1.5
2 2.5 3
1
Sound Rating Number 76 76 76 79
Connections
Liquid line o.d. − in. 3/8 3/8 3/8 3/8
(sweat)
Vapor line o.d. − in. 3/4
3/4 3/4 7/8
2
Refrigerant HFC−410A charge furnished 8 lbs. 4 oz. 8 lbs. 0 oz. 7 lbs. 2 oz. 9 lbs. 12 oz.
Outdoor
Net face area
Outer coil 13.30 13.30 15.21 19.39
Coil sq. ft.
Inner coil 12.60
12.60 14.50 18.77
Tube diameter − in. 5/16 5/16 5/16 5/16
No. of rows 2 2 2 2
Fins per inch 22 22 22 22
Outdoor
Diameter − in. 18 18 18 26
Fan
No. of Blades 3
3 3 4
Motor hp 1/10 1/10 1/10 1/3
Cfm 2165 2165 2232 4090
Rpm 1015 1015 1035 844
Watts 171 171 165 299
Shipping Data − lbs. 1 package 156 156 166 212 ELECTRICAL DATA
Line voltage data − 60 hz − 1ph 208/230V
208/230V 208/230V 208/230V
3
Maximum overcurrent protection (amps) 20 30 30 30
4
Minimum circuit ampacity 11.9 17.5 17.0 19.4
Compressor Rated Load Amps 8.97 13.46 13.1 14.1
p
Locked Rotor Amps 48 58 64 77
Power Factor 0.96 0.97 0.98 0.98
Outdoor
Full Load Amps 0.70 0.70 0.70 1.8
Fan Motor
Locked Rotor Amps 1.4
1.4 1.4 2.9
OPTIONAL ACCESSORIES − must be ordered extra Compressor Crankcase Heater 93M04 S
S S
p
Factory S Compressor Hard Start Kit 10J42 S S S S Compressor Low Ambient Cut−Off 45F08 S S S S Compressor Sound Cover 69J03 S S S S Freezestat 3/8 in. tubing 93G35 S S S S
5/8 in. tubing 50A93 S S S S
Hail Guards 92M89 S S
92M88 S
27W34 S
Indoor Blower Off Delay Relay 58M81 S S S S Loss of Charge Kit 84M23 S S S S
5
Low Ambient Kit 54M89 S S S S Mild Weather Kit 33M07 S S S S Monitor Kit − Service Light 76F53 S S S S Mounting Base 69J06 S S S
g
69J07 S
Outdoor
Thermostat 56A87 S S S S
Thermostat Kit
Mounting Box 31461 S
S S S
Refrigerant Line Sets
L15−41−20 L15−41−30
L15−41−40 L15−41−50
S S S
e Sets
L15−65−30 L15−65−40
L15−65−50
S
Unit Stand−Off Kit 94J45 S S S S
NOTE − Extremes of operating range are plus 10% and minus 5% of line voltage.
1
Sound Rating Number rated in accordance with test conditions included in ARI Standard 270.
2
Refrigerant charge sufficient for 15 ft. length of refrigerant lines.
3
HACR type circuit breaker or fuse.
4
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
5
Crankcase Heater and Freezestat are recommended with Low Ambient Kit.
6
14HPX−036 not available in Canada.
Page 3
SPECIFICATIONS General
Model No. 14HPX−042 14HPX−048 14HPX−060
Data
Nominal Tonnage 3.5
4 5
1
Sound Rating Number 79 80 80
Connections
Liquid line o.d. − in. 3/8 3/8 3/8
(sweat)
Vapor line o.d. − in. 7/8
7/8 1-1/8
2
Refrigerant HFC−410A charge furnished 12 lbs. 7 oz. 12 lbs. 10 oz. 16 lbs. 0 oz.
Outdoor
Net face area
Outer coil 24.93 24.93 29.09
Coil sq. ft.
Inner coil 24.13
24.13 28.16
Tube diameter − in. 5/16 5/16 5/16
No. of rows 2 2 2
Fins per inch 22 22 22
Outdoor
Diameter − in. 26 26 26
Fan
No. of Blades 4
4 4
Motor hp 1/3 1/3 1/3
Cfm 4347 4347 4550
Rpm 843 843 830
Watts 299 299 307
Shipping Data − lbs. 1 package 257 262 307
ELECTRICAL DATA
Line voltage data − 60 hz − 1ph 208/230V
208/230V 208/230V
3
Maximum overcurrent protection (amps) 40 50 60
4
Minimum circuit ampacity 24.2 29 34.8
Compressor
Rated Load Amps
17.94 21.79 26.41
p
Locked Rotor Amps
112
117 134
Power Factor
0.94 0.95 0.98
Outdoor
Full Load Amps
1.8 1.8 1.8
Fan Motor
Locked Rotor Amps
2.9
2.9 2.9
OPTIONAL ACCESSORIES − must be ordered extra Compressor Crankcase Heater Factory S
S S
Compressor Hard Start Kit
10J42 S S
p
81J69 S Compressor Low Ambient Cut−Off 45F08 S S S Compressor Sound Cover 69J03 S S S Freezestat
3/8 in. tubing 93G35 S S S 5/8 in. tubing 50A93 S S S
Hail Guards
27W36 S S
94M94 S Indoor Blower Off Delay Relay 58M81 S S S
Loss of Charge Kit 84M23 S S S
5
Low Ambient Kit 54M89 S S S Mild Weather Kit 33M07 S S S Monitor Kit − Service Light 76F53 S S S Mounting Base 69J07 S S S Outdoor
Thermostat 56A87 S S S
Thermostat Kit
Mounting Box 31461 S
S S
Refrigerant Line Sets
L15−65−30 L15−65−40
L15−65−50
S S
e Sets
Field Fabricate S
Unit Stand−Off Kit 94J45 S S S
NOTE − Extremes of operating range are plus 10% and minus 5% of line voltage.
1
Sound Rating Number rated in accordance with test conditions included in ARI Standard 270.
2
Refrigerant charge sufficient for 15 ft. length of refrigerant lines.
3
HACR type circuit breaker or fuse.
4
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
5
Crankcase Heater and Freezestat are recommended with Low Ambient Kit.
Page 4
I − UNIT COMPONENTS
Unit components are illustrated in figure 1.
14HPX UNIT COMPONENTS
FIGURE 1
service valves
compressor
reversing valve
condenser fan
drier
muffler
high pressure switch (on liquid line, hidden)
txv valve
FIGURE 2
DUAL CAPACITOR
(C12)
COMPRESSOR
CONTACTOR
(K1)
14HPX UNIT CONTROL BOX
GROUNDING
LUG
DEFROST
CONTROL
(CMC1)
A − Control Box (Figure 2)
14HPX units are not equipped with a 24V transformer. All 24 VAC controls are powered by the indoor unit. Refer to wiring diagram.
Electrical openings are provided under the control box cov­er. Field thermostat wiring is made to a 24V terminal strip located on the defrost control board located in the control box. See figure 3.
24V THERMOSTAT TERMINAL STRIP
FIGURE 3
W1 C L R O Y1*Y2
*not used
1 − Compressor Contactor (K1)
The compressor is energized by a contactor located in the control box. See figure 2. Single−pole contactors are used in 14HPX series units. See wiring diagrams for specific unit. K1 is energized through the CMC1 board by the in­door thermostat terminal Y1 (24V) when thermostat de­mand is present.
DANGER
Electric Shock Hazard. May cause injury or death.
Disconnect all remote electrical power supplies before opening unit panel. Unit may have multiple power supplies.
Some units are equipped with single− pole contactors. When unit is equipped with a single−pole contactor, line voltage is present at all components (even when unit is not in operation).
2 − Dual Capacitor (C12)
The compressor and fan in 14HPX series units use permanent split capacitor motors. The capacitor is located inside the unit control box (see figure 2). A single dual" capacitor (C12) is used for both the fan motor and the compressor (see unit wir­ing diagram). The fan side and the compressor side of the ca­pacitor have different MFD ratings.
Page 5
3 − Defrost System (CMC1)
The demand defrost control measures differential tem­peratures to detect when the system is performing poorly because of ice build−up on the outdoor coil. The controller self−calibrates" when the defrost system starts and after each system defrost cycle. The defrost control board com­ponents are shown in figure 4.
The control monitors ambient temperature, outdoor coil temperature, and total run time to determine when a de­frost cycle is required. The coil temperature probe is de­signed with a spring clip to allow mounting to the outside coil tubing. The location of the coil sensor is important for proper defrost operation.
NOTE − The demand defrost board accurately measures the performance of the system as frost accumulates on the outdoor coil. This typically will translate into longer running time between defrost cycles as more frost accumulates on the outdoor coil before the board initiates defrost cycles.
Diagnostic LEDs
The state (Off, On, Flashing) of two LEDs on the defrost board (DS1 [Red] and DS2 [Green]) indicate diagnostics conditions that are described in table 2.
24V TERMINAL STRIP CONNECTIONS
DIAGNOSTIC LEDS
PRESSURE
SWITCH CIRCUIT
CONNECTIONS
TEST PINS
NOTE − Component Locations Vary by Board Manufacturer.
Y2 not used on 14HPX
SENSOR
PLUG IN
(COIL & AM-
BIENT
SENSORS)
REVERSING
VALV E
DELAY
PINS
LOW AMBIENT THERMOSTAT PINS
DEFROST TERMINATION PIN SETTINGS
FIGURE 4
Defrost Control Pressure Switch Connections
The unit’s automatic reset pressure switches (LO PS − S87 and HI PS − S4) are factory−wired into the defrost board on the LO−PS and HI−PS terminals, respectively.
(OPTIONAL) Low Pressure Switch (LO−PS)When the low pressure switch trips, the defrost board will cycle off the compressor, and the strike counter in the board will count one strike. The low pressure switch is ignored under the fol­lowing conditions:
S during the defrost cycle and 90 seconds after the ter-
mination of defrost
S when the average ambient sensor temperature is be-
low 15° F (−9°C)
S for 90 seconds following the start up of the compressor S during "test" mode
High Pressure Switch (HI−PS)When the high pressure switch trips, the defrost control will cycle off the compres­sor, and the strike counter in the control will count one strike.
Defrost Control Pressure Switch Settings
High Pressure (auto reset) − trip at 590 psig; reset at 418.
Low Pressure (auto reset) − trip at 25 psig; reset at 40 psig.
5−Strike Lockout Feature
The internal control logic of the control counts the pressure switch trips only while the Y1 (Input) line is active. If a pres­sure switch opens and closes four times during a Y1 (In­put), the control logic will reset the pressure switch trip counter to zero at the end of the Y1 (Input). If the pressure switch opens for a fifth time during the current Y1 (Input), the control will enter a lockout condition.
The 5−strike pressure switch lockout condition can be reset by cycling OFF the 24−volt power to the control board or by shorting the TEST pins between 1 and 2 seconds. All timer functions (run times) will also be reset.
If a pressure switch opens while the Y1 Out line is engaged, a 5−minute short cycle will occur after the switch closes.
Defrost System Sensors
Sensors connect to the defrost control through a field-re­placeable harness assembly that plugs into the board. Through the sensors, the control detects outdoor ambient and coil temperature fault conditions. As the detected tem­perature changes, the resistance across the sensor changes. Figure 5 shows how the resistance varies as the temperature changes for both type of sensors. Sensor re­sistance values can be checked by ohming across pins shown in table 1.
TABLE 1
Sensor
Temperature Range °F (°C)
Resistance values range (ohms)
Pins/Wire Color
Outdoor (Ambient)
−35 (−37) to 120 (48)
280,000 to 3750 3 & 4
(Black)
Coil −35 (−37) to 120
(48)
280,000 to 3750 5 & 6
(Brown)
Discharge (if applicable)
24 (−4) to 350 (176)
41,000 to 103 1 & 2
(Yellow)
Note: Sensor resistance decreases as sensed temperature increases (see figure5).
NOTE − When checking the ohms across a sensor, be aware that a sensor showing a resistance value that is not within the range shown in table 1, may be performing as de­signed. However, if a shorted or open circuit is detected, then the sensor may be faulty and the sensor harness will needs to be replaced.
Coil SensorThe coil temperature sensor (shown in fig­ure 6) considers outdoor temperatures below −35°F (−37°C) or above 120°F (48°C) as a fault. If the coil temper­ature sensor is detected as being open, shorted or out of the temperature range of the sensor, the board will not per­form demand or time/temperature defrost operation and will display the appropriate fault code. Heating and cooling operation will be allowed in this fault condition.
Page 6
Ambient and Coil Sensor
RESISTANCE (OHMS)
TEMPERATURE (ºF)
5750
7450
9275
11775
15425
19975
26200
34375
46275
62700
100
90
80
70
60
50
40
30
20
10
0
10000 30000 50000 70000 90000
85300
FIGURE 5
COIL SENSOR
− Clip coil temperature sensor from the de­frost board on the bend shown − 6th bend up. Apply grease between bend and sen­sor.
AMBIENT SENSOR
FIGURE 6
Ambient SensorThe ambient sensor (shown in figure 6)
considers outdoor temperatures below −35°F (−37°C) or above 120°F (48°C) as a fault. If the ambient sensor is de­tected as being open, shorted or out of the temperature range of the sensor, the control will not perform demand defrost operation. The control will revert to time/tempera­ture defrost operation and will display the appropriate fault code. Heating and cooling operation will be allowed in this fault condition.
NOTE − Within a single room thermostat demand, if 5−strikes occur, the board will lockout the unit. Defrost board 24 volt power R" must be cycled OFF" or the TEST" pins on board must be shorted between 1 to 2 sec­onds to reset the board.
Defrost Temperature Termination Shunt (Jumper) PinsThe defrost control selections are: 50, 70, 90, and
100°F (10, 21, 32 and 38°C). The shunt termination pin is factory set at 50°F (10°C). If the temperature shunt is not installed, the default termination temperature is 90°F (32°C).
Delay Mode
The defrost control has a field−selectable function to re­duce occasional sounds that may occur while the unit is cycling in and out of the defrost mode. When a jumper is installed on the DELAY pins, the compressor will be cycled off for 30 seconds going in and out of the defrost mode. Units are shipped with jumper installed on DELAY pins.
Page 7
NOTE − The 30 second off cycle is NOT functional when jumpering the TEST pins.
Operational Description
The defrost control has three basic operational modes: normal, calibration, and defrost.
Normal ModeThe demand defrost control monitors the O line, to determine the system operating mode (heat/ cool), outdoor ambient temperature, coil temperature (out­door coil) and compressor run time to determine when a defrost cycle is required.
Calibration ModeThe control is considered uncali­brated when power is applied to the control, after cool mode operation, or if the coil temperature exceeds the ter­mination temperature when it is in heat mode.
Calibration of the control occurs after a defrost cycle to en­sure that there is no ice on the coil. During calibration, the temperature of both the coil and the ambient sensor are measured to establish the temperature differential which is required to allow a defrost cycle. See figure 8 for calibration mode sequence.
Defrost ModeThe following paragraphs provide a de­tailed description of the defrost system operation.
Detailed Defrost System Operation
Defrost CyclesThe demand defrost control initiates a
defrost cycle based on either frost detection or time.
S Frost DetectionIf the compressor runs longer than
34 minutes and the actual difference between the clear coil and frosted coil temperatures exceeds the maxi­mum difference allowed by the control, a defrost cycle will be initiated.
IMPORTANT − The demand defrost control will allow a greater accumulation of frost and will initiate fewer de­frost cycles than a time/temperature defrost system.
S TimeIf 6 hours of heating mode compressor run time
has elapsed since the last defrost cycle while the coil temperature remains below 35°F (2°C), the demand defrost control will initiate a defrost cycle.
ActuationWhen the reversing valve is de−energized, the Y1 circuit is energized, and the coil temperature is below 35°F (2°C), the board logs the compressor run time. If the board is not calibrated, a defrost cycle will be initiated after 34 minutes of heating mode compressor run time. The con­trol will attempt to self−calibrate after this (and all other) de­frost cycle(s).
Calibration success depends on stable system tempera­tures during the 20−minute calibration period. If the control fails to calibrate, another defrost cycle will be initiated after 45 minutes (90 minutes −1 to −4 boards) of heating mode compressor run time. Once the defrost board is calibrated, it initiates a demand defrost cycle when the difference be­tween the clear coil and frosted coil temperatures exceeds the maximum difference allowed by the control OR after 6 hours of heating mode compressor run time has been logged since the last defrost cycle.
NOTE − If ambient or coil fault is detected, the control will not execute the TEST" mode.
TerminationThe defrost cycle ends when the coil tem­perature exceeds the termination temperature or after 14 minutes of defrost operation. If the defrost is terminated by the 14−minute timer, another defrost cycle will be initiated after 34 minutes of run time.
Test ModeWhen Y1 is energized and 24V power is be­ing applied to the control, a test cycle can be initiated by placing the termination temperature jumper across the Test" pins for 2 to 5 seconds. If the jumper remains across the Test" pins longer than 5 seconds, the control will ignore the test pins and revert to normal operation. The jumper will initiate one cycle per test.
Enter the TEST" mode by placing a shunt (jumper) across the TEST" pins on the control after power−up. (The TEST" pins are ignored and the test function is locked out if the shunt is applied on the TEST" pins before power−up). Control timings are reduced, the low−pressure switch is ig­nored and the control will clear any active lockout condi­tion.
Each test pin shorting will result in one test event. For each TEST" the shunt (jumper) must be removed for at least 1 second and reapplied. Refer to flow chart (figure 7) for TEST" operation.
Note: The Y1 input must be active (ON) and the O" room thermostat terminal into board must be inactive.
Defrost Control Diagnostics
See table 2 to determine defrost control operational condi­tions and to diagnose cause and solution to problems.
Page 8
If in COOLING Mode If in HEATING Mode If in DEFROST Mode
Short test pins for longer
than 1 second but less than
2 seconds
Short test pins for more than 2 seconds
Y1 Active (0" line inactive)
Test pin short REMAINS in place for more than 5 seconds Test pins short REMOVED before a
maximum of 5 seconds
Clear any short cycle lockout
and 5 strike fault lockout
function, if applicable. No
other functions will be
executed and unit will
continue in the mode it was
operating.
No further test mode
operation will be
executed until the test
short is removed and
reapplied.
The control will check for ambient
and coil faults (open or shorted).
If a fault exists
, the unit will
remain in Heat Mode and no
further test mode operation will
be executed until the test short is
removed and re applied. If no fault exists
and ambient
temperature is below 35ºF, the
unit will go into Defrost mode.
The unit will terminate
defrost and enter Heat
Mode uncalibrated with
defrost timer set for 34 minute test. No further
test mode operation will
be executed until the test
short is removed and
reapplied.
Clear any short cycle lockout and 5 strike
fault lockout function, if applicable.
The unit will return to Heat mode uncalibrated with defrost
timer set for 34 minutes. No further test mode operation will
be executed until the test short is removed and re applied.
The unit will remain in Defrost mode
until termination on time or temperature
FIGURE 7
Loading...
+ 16 hidden pages