Lennox 14HPX-024-230-01, 14HPX-024-230-10, 14HPX-024-230-11, 14HPX-024-230-12, 14HPX-024-230-13 Installation And Service Procedure

...
INSTALLATION AND SERVICE
PROCEDURE
Service Literature
LOUVERED
Corp. 0719-L5
Revised April, 2017
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause personal injury, loss of life, or damage to property.
Installation and service must be performed by a licensed professional installer (or equivalent) or a service agency.
IMPORTANT
This unit must be matched with an indoor coil as specified in Lennox Product Specification bulletin. Coils previously charged with HCFC-22 must be flushed.
WARNING
Electric Shock Hazard. Can cause injury or death. Unit must be grounded in accordance with national and local codes.
Line voltage is present at all components when unit is not in operation on units with single‐pole contactors. Disconnect all remote electric power supplies before opening access panel. Unit may have multiple power supplies.
14HPX
TABLE OF CONTENTS
Model Number Identification 2......................
Typical Serial Number Identification 2..............
Specifications 2.................................
Electrical Data 4................................
Unit Dimensions 7.................................
Typical Unit Parts Arrangement 8...................
General Information 9.............................
Operating Gauge Set and Service Valves 9...........
Unit Placement 12.................................
Removing and Installing Louvers 13.................
New or Replacement Line Set 15....................
Brazing Connections 17...........................
Flushing Line Set and Indoor Coil 20................
Installing Indoor Metering Device 21................
Leak Test Line Set and Indoor Coil 22...............
Evacuating Line Set and Indoor Coil 23.............
Electrical Connections 24..........................
System Operation (14HPX-XXX-230-01 through -016)26 Defrost System (14HPX-XXX-230-01 through -016) 26.
System Operation (14HPX-XXX-230-017) 31.........
Defrost System (14HPX-XXX-230-017) 31............
Maintenance 32...................................
Start-Up and Performance Checklist 35..............
Sequence of Operations 36.........................
Servicing Unit Void of Charge 40....................
Start-Up 40.......................................
System Refrigerant 40.............................
®
The Merit HFC-410A refrigerant only. This unit must be installed with an approved indoor air handler or coil. See the Lennox 14HPX Product Specification bulletin (EHB) for approved indoor component matchups.
This outdoor unit is designed for use in systems that use the following refrigerant metering device:
Check thermal expansion valve (CTXV)
The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFCs, HCFCs and HFCs) as of July 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for noncompliance.
14HPX model is designed for use with
IMPORTANT
Page 1
Model Number Identification
HP X14 024
Nominal SEER
Unit Type
HP = Heat Pump
Refrigerant
X = R-410A
Typical Serial Number Identification
Location Code
19 = Saltillo, Mexico
58 = Marshalltown, IA
Year Code
08 = 2008 09 = 2009 10 = 2010
19 09 C
230
Cooling Capacity - Tons 018 = 1.5
024 = 2 030 = 2.5 036 = 3 042 = 3.5 048 = 4 060 = 5
05716
Month Code
A = January B = February C = March
11
Minor Revision Number
Voltage
230 = 208/230V-1phase-60hz
5 (or 6) Digit Unique Number
Specifications
Unit Outdoor Fan
Model Number
14HPX-018-230-01, 10, -11, 12, -13, -14,
-15
14HPX-018-230-17, -18 76
1
Tested according to AHRI Standard 270-2008 test conditions.
2
Refrigerant charge sufficient for 15 feet of line set.
3
Later models employed a smaller filter drier resulting in less refrigerant charge required. Verify factory charge from unit nameplate.
Model Number
14HPX-024-230-01, -10, -11, -12, -13, -14,
-15
14HPX-024-230-17 76 6 lbs. 4 oz. 3 22
14HPX-024-230-18 76 6 lbs. 4 oz. or 5 lbs. 14 oz.
1
Tested according to AHRI Standard 270-2008 test conditions.
2
Refrigerant charge sufficient for 15 feet of line set.
3
Later models employed a smaller filter drier resulting in less refrigerant charge required. Verify factory charge from unit nameplate.
Model Number
14HPX-030-230-01, -10, -11, -13, -14 76 7 lbs. 2 oz. 3 18
14HPX-030-230-17 76 6 lbs. 0 oz. 3 22
14HPX-030-230-18 76 6 lbs. 0 oz. or 5 lbs. 10 oz.
1
Tested according to AHRI Standard 270-2008 test conditions.
2
Refrigerant charge sufficient for 15 feet of line set.
3
Later models employed a smaller filter drier resulting in less refrigerant charge required. Verify factory charge from unit nameplate.
Sound Rating Number
Sound Rating Number
Sound Rating Number
1
(dB)
76 8 lbs. 4 oz. 3 18
1
(dB)
76 8 lbs. 0 oz. 3 18
1
(dB)
Factory Refrigerant
6 lbs. 11 oz. or 5 lbs.
Unit Outdoor Fan
Factory Refrigerant
Unit Outdoor Fan
Factory Refrigerant
Charge
11 oz.
Charge
Charge
2
3
2
2
Number of Blades Diameter - inches.
3 22
Number of Blades Diameter - inches.
3
3
3 22
Number of Blades Diameter - inches.
3 22
Page 2
Unit Outdoor Fan
Model Number
Sound Rating Number
(dB)
1
Factory Refrigerant
Charge
2
Number of Blades Diameter - inches.
14HPX-036-230-01, -10, -11, -12 76 9 lbs. 12 oz. 4 26
14HPX-036-230-17 76 9 lbs. 12 oz. 3 22
14HPX-036-230-18 76 9 lbs. 12 oz. or 9 lbs. 6 oz.
1
Tested according to AHRI Standard 270-2008 test conditions.
2
Refrigerant charge sufficient for 15 feet of line set.
3
Later models employed a smaller filter drier resulting in less refrigerant charge required. Verify factory charge from unit nameplate.
3
3 22
Unit Outdoor Fan
Model Number
Sound Rating
Number (dB)
Factory Refrigerant Charge
1
2
Number of Blades Diameter - inches.
14HPX-042-230-01, -10, -11, -12 76 12 lbs. 7 oz. 4 26
14HPX-042-230-17 76 11 lbs. 14 oz. 4 26
14HPX-042-230-18 76 11 lbs. 14 oz. 4 26
1
Tested according to AHRI Standard 270-2008 test conditions.
2
Refrigerant charge sufficient for 15 feet of line set.
3
Later models employed a smaller filter drier resulting in less refrigerant charge required. Verify factory charge from unit nameplate.
Unit Outdoor Fan
Model Number
Sound Rating
Number (dB)
Factory Refrigerant Charge
1
2
Number of Blades Diameter - inches.
14HPX-048-230-01, -10, -11, -12 76 12 lbs. 10 oz. 4 26
14HPX-048-230-17 76 10 lbs. 07 oz. 4 26
14HPX-048-230-18 76 10 lbs. 07 oz. 4 26
1
Tested according to AHRI Standard 270-2008 test conditions.
2
Refrigerant charge sufficient for 15 feet of line set.
3
Later models employed a smaller filter drier resulting in less refrigerant charge required. Verify factory charge from unit nameplate.
Unit Outdoor Fan
Model Number
Sound Rating Number
(dB)
1
Factory Refrigerant Charge
2
Number of Blades Diameter - inches.
14HPX-060-230-01, -10, -11, -12 76 16 lbs. 0 oz. 4 26
14HPX-060-230-17 76 12 lbs. 11 oz. 4 26
14HPX-060-230-18 76 12 lbs. 11 oz. 4 26
1
Tested according to AHRI Standard 270-2008 test conditions.
2
Refrigerant charge sufficient for 15 feet of line set.
3
Later models employed a smaller filter drier resulting in less refrigerant charge required. Verify factory charge from unit nameplate.
Page 3
14HPX SERIES
Electrical Data
208/230V-60 Hz-1 Ph
Unit Compressor Condenser Fan
Model Number Label Rev.
Over-
current
Protection
(amps)
1
Minimum
Circuity
Ampacity
Maximum
1.0 20 12.3 8.97 48.0 1/5 1075 1.1 1.4
14HPX-018-230-01
2.0. 3,0 &
4.0
20 11.9 8.97 48.0 1/10 1075 .70 1.4
14HPX-018-230-10 1.0 20 11.9 8.97 48.0 1/10 1075 .70 1.4
14HPX-018-230-11 1.0 20 11.9 8.97 48.0 1/10 1075 .70 1.4
14HPX-018-230-12 1.0 20 11.9 10.18 48.0 1/10 1075 .70 1.4
14HPX-018-230-13 1.0 20 11.9 10.18 48.0 1/10 1075 .70 1.4
14HPX-018-230-14 1.0 20 11.9 10.18 48.0 1/10 1075 .70 1.4
14HPX-018-230-15 1.0 20 11.9 10.18 48.0 1/10 1075 .70 1.4
14HPX-018-230-17
14HPX-018-230-18
1
HACR type circuit breaker or fuse.
2
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
1.0, 2.0 &
3.0
20 12.3 8.96 48.0 1/6 825 1.1 1.87
1.0 20 12.3 8.96 48.0 1/6 825 1.1 1.87
2.0 20 12.2 9.0 48.0 1/6 825 1.0 1.87
Rated
Load
Amps
2
(RLA)
Locked
Rotor Amps
(LRA)
Motor HP
Nominal
RPM
Full Load
Amps (FLA)
Locked
Rotor Amps
(LRA)
208/230V-60 Hz-1 Ph
Unit Compressor Condenser Fan
Model Number Label Rev.
14HPX-024-230-01
1.0 30 17.9 13.46 58.0 1/5 1075 1.1 1.4
2.0 & 3.0 30 17.5 13.46 58.0 1/10 1075 .70 1.4
Maximum
Over-
current
Protection
(amps)
1
Minimum
Circuity
Ampacity
Rated
Load
Amps
2
(RLA)
Locked
Rotor Amps (LRA)
Motor HP
Nominal
RPM
Full Load
Amps (FLA)
Locked
Rotor Amps (LRA)
14HPX-024-230-10 1.0 30 17.5 13.46 58.0 1/10 1075 .70 1.4
14HPX-024-230-11 1.0 30 17.5 13.46 58.0 1/10 1075 .70 1.4
14HPX-024-230-12 1.0 30 17.5 13.46 58.0 1/10 1075 .70 1.4
14HPX-024-230-13 1.0 30 17.5 13.46 58.0 1/10 1075 .70 1.4
14HPX-024-230-14 1.0 30 17.5 13.46 58.0 1/10 1075 .70 1.4
14HPX-024-230-15 1.0 30 17.5 13.46 58.0 1/10 1075 .70 1.4
14HPX-024-230-17
14HPX-024-230-18
1
HACR type circuit breaker or fuse.
2
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
1.0, 2.0,
3.0 & 4.0
30 17.9 13.44 58.0 1/6 825 1.1 1.87
1.0 30 17.9 13.44 58.0 1/6 825 1.1 1.87
2.0 30 17.9 17.9 58.0 1/6 825 1.1 1.87
Page 4
208/230V-60 Hz-1 Ph
Unit Compressor Condenser Fan
Model Number Label Rev.
Maximum
Over-
current
Protection
(amps)
1
Minimum
Circuity
Ampacity
Rated
Load
Amps
2
(RLA)
Locked
Rotor Amps (LRA)
Motor HP
Nominal
RPM
Full Load
Amps (FLA)
Locked
Rotor Amps (LRA)
1.0 30 17.2 12.9 64.0 1/5 825 1.1 1.4
14HPX-030-230-01
2.0, 3.0,
4.0 & 5.0
30 17.0 13.1 64.0 1/10 1075 .70 1.3
14HPX-030-230-10 1.0 30 17.0 13.1 64.0 1/10 1075 .70 1.3
14HPX-030-230-11 1.0 30 17.0 13.1 64.0 1/10 1075 .70 1.3
14HPX-030-230-13 1.0 30 17.0 13.1 64.0 1/10 1075 .70 1.3
14HPX-030-230-14 1.0 30 17.0 13.1 64.0 1/10 1075 .70 1.3
14HPX-030-230-17 1.0 25 17.1 12.8 64.0 1/6 825 1.1 1.9
14HPX-030-230-18 1.0 25 17.1 12.8 64.0 1/6 825 1.1 1.9
1
HACR type circuit breaker or fuse.
2
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
208/230V-60 Hz-1 Ph
Unit Compressor Condenser Fan
Model Number Label Rev.
1.0, 2.0,
14HPX-036-230-01
3.0, 4.0 &
5.0
Maximum
Over-
current
Protection
(amps)
1
Minimum
Circuity
Ampacity
30 19.4 14.1 77.0 1/3 825 1.8 2.9
Rated
Load
Amps
2
(RLA)
Locked
Rotor Amps (LRA)
Motor HP
Nominal
RPM
Full Load
Amps (FLA)
Locked
Rotor Amps (LRA)
14HPX-036-230-10 1.0 30 19.4 14.1 77.0 1/3 825 1.8 2.9
14HPX-036-230-11 1.0 30 19.4 14.1 77.0 1/3 825 1.8 2.9
14HPX-036-230-12 1.0 30 19.4 14.1 77.0 1/3 825 1.8 2.9
14HPX-036-230-17 1.0 & 2.0 30 18.7 14.08 77.0 1/6 825 1.1 1.87
14HPX-036-230-18
1
HACR type circuit breaker or fuse.
2
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
1.0 30 18.7 14.08 77.0 1/6 825 1.1 1.87
2.0 30 18.7 14.1 77.0 1/6 825 1.1 1.87
208/230V-60 Hz-1 Ph
Unit Compressor Condenser Fan
Model Number Label Rev.
14HPX-042-230-01
1.0 40 23.9 17.69 07.0 1/3 825 1.8 2.9
2.0 & 3.0 40 24.2 17.94 112.0 1/3 825 1.8 2.9
Maximum
Over-
current
Protection
(amps)
1
Minimum
Circuity
Ampacity
Rated
Load
Amps
2
(RLA)
Locked
Rotor Amps (LRA)
Motor HP
Nominal
RPM
Full Load
Amps (FLA)
Locked
Rotor Amps (LRA)
14HPX-042-230-10 1.0 40 24.2 17.94 112.0 1/3 825 1.8 2.9
14HPX-042-230-11 1.0 40 24.2 17.94 112.0 1/3 825 1.8 2.9
14HPX-042-230-12 1.0 40 24.2 17.94 112.0 1/3 825 1.8 2.9
14HPX-042-230-17
14HPX-042-230-18
1
HACR type circuit breaker or fuse.
2
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
1.0, 2.0,
3.0 & 4.0
40 24.2 17.92 112.0 1/3 825 1.8 2.9
1.0 40 24.2 17.92 112.0 1/3 825 1.8 2.9
2.0 40 24.2 18.0 112.0 1/3 825 1.8 2.9
Page 5
14HPX SERIES
208/230V-60 Hz-1 Ph
Unit Compressor Condenser Fan
Model Number Label Rev.
14HPX-048-230-01
1.0, 2.0,
3.0 & 4.0
Maximum
Over-
current
Protection
(amps)
1
Minimum
Circuity
Ampacity
50 29.0 21.79 117.0 1/3 825 1.8 2.9
Rated
Load
Amps
2
(RLA)
Locked
Rotor Amps (LRA)
Motor HP
Nominal
RPM
Full Load
Amps (FLA)
Locked
Rotor Amps (LRA)
14HPX-048-230-10 1.0 50 29.0 21.79 117.0 1/3 825 1.8 2.9
14HPX-048-230-11 1.0 50 29.0 21.79 117.0 1/3 825 1.8 2.9
14HPX-048-230-12 1.0 50 29.0 21.79 117.0 1/3 825 1.8 2.9
14HPX-048-230-17
14HPX-048-230-18
1
HACR type circuit breaker or fuse.
2
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
1.0, 2.0 &
3.0
50 29.0 21.76 117.0 1/3 825 1.8 2.9
1.0 50 29.0 21.76 117.0 1/3 825 1.8 2.9
2.0 50 29.0 21.8 117.0 1/3 825 1.8 2.9
208/230V-60 Hz-1 Ph
Unit Compressor Condenser Fan
Model Number Label Rev.
14HPX-060-230-01
1.0, 2.0 &
3.0
Maximum
Over-
current
Protection
(amps)
1
Minimum
Circuity
Ampacity
60 34.8 26.41 134.0 1/3 825 1.8 2.9
Rated
Load
Amps
2
(RLA)
Locked
Rotor Amps (LRA)
Motor HP
Nominal
RPM
Full Load
Amps (FLA)
Locked
Rotor Amps (LRA)
14HPX-060-230-10 1.0 60 34.8 26.41 134.0 1/3 825 1.8 2.9
14HPX-060-230-11 1.0 60 34.8 26.41 134.0 1/3 825 1.8 2.9
14HPX-060-230-12 1.0 60 34.8 26.41 134.0 1/3 825 1.8 2.9
14HPX-060-230-17
1.0, 2.0,
3.0 & 4.0
50 29.4 22.10 125.0 1/3 825 1.8 2.9
14HPX-060-230-18 1.0 50 29.4 22.10 125.0 1/3 825 1.8 2.9
1
HACR type circuit breaker or fuse.
2
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
Page 6
Unit Dimensions - inches (mm)
A
OUTDOOR
COIL FAN
A
DISCHARGE AIR
C
COMPRESSOR
B
SUCTION AND LIQUID
LINE CONNECTION
OPTIONAL UNIT
STANDOFF KIT (4)
SIDE VIEW
(FIELD INSTALLED)
Table 1. Unit Dimensions (14HPX-XXX-230-01 through -012)
Model Number A B C
14HPX-018-230 24-1/4 (616) 29-1/4 (743) 28-1/2 (724)
14HPX-024-230 24-1/4 (616) 29-1/4 (743) 28-1/2 (724)
14HPX-030-230 24-1/4 (616) 33-1/4 (845) 32-1/2 (826)
14HPX-036-230 32-1/4 (819) 29-1/4 (743) 28-1/2 (724)
14HPX-042-230 32-1/4 (819) 37-1/4 (946) 36-1/2 (927)
14HPX-048-230 32‐1/4 (819) 37-1/4 (946) 36-1/2 (927)
14HPX-060-230 32‐1/4 (819) 43-1/4 (1099) 42-1/4 (1073)
Table 2. Unit Dimensions (14HPX-XXX-230-017)
SIDE VIEW
Model Number A B C
14HPX-018-230 28-1/4 (718) 37-1/4 (946) 36-1/2 (927)
14HPX-024-230 28-1/4 (718) 37-1/4 (946) 36-1/2 (927)
14HPX-030-230 28-1/4 (718) 37-1/4 (946) 36-1/2 (927)
14HPX-036-230 28-1/4 (718) 33-1/4 (845) 32-1/2 (826)
14HPX-042-230 32-1/4 (819) 37-1/4 (946) 36-1/2 (927)
14HPX-048-230 32‐1/4 (819) 37-1/4 (946) 36-1/2 (927)
14HPX-060-230 32‐1/4 (819) 43-1/4 (1099) 42-1/4 (1073)
Page 7
14HPX SERIES
Typical Unit Parts Arrangement
CAPACITOR
GROUND
LUG
CUTOUT FOR HIGH VOLTAGE CONDUIT
CONTROL
CONTACTOR
DEFROST CONTROL BOARD
CONTROL WIRE LOOP
CHECK EXPANSION
NOTE — PLUMBING LAYOUT AND COMPRESSOR TYPE MAY VARY SLIGHTLY BETWEEN MODEL SIZES.
COMPRESSOR
HARNESS
DEFROST
THERMOSTAT
VALV E
EQUALIZER LINE
BI-FLOW FILTER
LIQUID LINE SERVICE
DRIER
TRUE SUCTION
PORT
HIGH PRESSURE
SWITCH (S4)
VALV E
COMPRESS0R
DISCHARGE LINE
MUFFLER
LOW PRESSURE SWITCH
REVERSING VALVE SO LENOID
VAPOR LINE SERVICE VALVE
REVERSING VALV E
Figure 1. Typical Unit Parts Arrangement (14HPX-XXX-230-01 through -012)
Page 8
DUAL RUN
CAPACITOR
(C12)
CONTACTOR
(K-1)
GROUND
LUG
DEFROST
CONTROL
(CMC1)
CUTOUT FOR
HIGH VOLTAGE
CONDUIT
CONTROL
PROTECTION SWITCH
EXTERNAL SWITCH)
CONTROL WIRE LOOP
THERMAL
(S173) (ONLY ON
UNITS USING
SWITCH
COVER
COMPRESSOR HARNESS
DEFROST THERMOSTAT
EXPANSION VALVE
EQUALIZER LINE
BI-FLOW FILTER
(S6)
CHECK /
DRIER
TRUE SUCTION
PORT
COMPRESS0R
DISCHARGE LINE
MUFFLER
LOW PRESSURE SWITCH (S87)
REVERSING VALVE (L1)
CRANKCASE CASE HEATER (HR1) (-036,
-042, -048, -060 UNITS ONLY)
CRANKCASE HEATER THERMOSTAT
(S40) (-036, -042, -048, -060 UNITS ONLY)
HIGH PRESSURE SWITCH (S4)
NOTE — PLUMBING LAYOUT AND COMPRESSOR TYPE MAY VARY SLIGHTLY BETWEEN MODEL SIZES.
Figure 2. Typical Unit Parts Arrangement (14HPX-XXX-230-017)
General Information
These instructions are intended as a general guide and do not supersede national or local codes in any way. Consult authorities having jurisdiction before installation.
WARNING
This product contains a chemical known to the State of California to cause cancer, birth defects, or other repro ductive harm.
REVERSING VALVE SOLENOID
VAPOR LINE
LIQUID LINE SERVICE
VALV E
VAPOR LINE SERVICE VALVE (BALL-TYPE -060 ONLY)
SERVICE VALVE (ANGLE-TYPE - ALL OTHER SIZES)
Operating Gauge Set and Service Valves
CAUTION
As with any mechanical equipment, contact with sharp sheet metal edges can result in personal injury. Take care while handling this equipment and wear gloves and pro tective clothing.
Page 9
14HPX SERIES
TORQUE REQUIREMENTS
When servicing or repairing heating, ventilating, and air conditioning components, ensure the fasteners are appropriately tightened. Table 3 lists torque values for fasteners.
IMPORTANT
Only use Allen wrenches of sufficient hardness (50Rc ­Rockwell Harness Scale minimum). Fully insert the wrench into the valve stem recess.
Service valve stems are factory-torqued (from 9 ft-lbs for small valves, to 25 ft-lbs for large valves) to prevent refrigerant loss during shipping and handling. Using an Allen wrench rated at less than 50Rc risks rounding or breaking off the wrench, or stripping the valve stem recess.
See the Lennox Service and Application Notes #C-08-1 for further details and information.
Table 3. Torque Requirements
Parts Recommended Torque
Service valve cap 8 ft.- lb. 11 NM
Sheet metal screws 16 in.- lb. 2 NM
Machine screws #10 28 in.- lb. 3 NM
Compressor bolts 90 in.- lb. 10 NM
Gauge port seal cap 8 ft.- lb. 11 NM
USING MANIFOLD GAUGE SET
When checking the system charge, only use a manifold gauge set that features low loss anti-blow back fittings.
Manifold gauge set used with HFC-410A refrigerant systems must be capable of handling the higher system operating pressures. The gauges should be rated for use with pressures of 0 - 800 psig on the high side and a low side of 30” vacuum to 250 psig with dampened speed to 500 psi. Gauge hoses must be rated for use at up to 800 psig of pressure with a 4000 psig burst rating.
IMPORTANT
To prevent stripping of the various caps used, the appropriately sized wrench should be used and fitted snugly over the cap before tightening.
When servicing or repairing HVAC components, ensure the fasteners are appropriately tightened. Table 3 provides torque values for fasteners.
OPERATING SERVICE VALVES
The liquid and vapor line service valves are used for removing refrigerant, flushing, leak testing, evacuating, checking charge and charging.
Each valve is equipped with a service port which has a factory-installed valve stem. Figure 3 provides information on how to access and operating both angle and ball service valves.
Page 10
SERVICE VALVES
ANGLE AND BALL
Operating Angle Type Service Valve:
1. Remove stem cap with an appropriately sized wrench.
2. Use a service wrench with a hex-head extension (3/16” for liquid line valve sizes and 5/16” for vapor line valve sizes) to back the stem out counterclockwise as far as it will go.
SERVICE PORT CAP
SERVICE PORT CORE
(VALVE STEM SHOWN
TO INDOOR
UNIT
(VALVE STEM SHOWN OPEN) INSERT HEX WRENCH HERE
CLOSED) INSERT HEX WRENCH HERE
SERVICE PORT
CORE
TO OUTDOOR UNIT
ANGLE-TYPE SERVICE VALVE
(BACK-SEATED OPENED)
When service valve is OPEN, the service port is open to linE set, indoor and outdoor unit.
Operating Ball Type Service Valve:
1. Remove stem cap with an appropriately sized wrench.
2. Use an appropriately sized wrenched to open. To open valve, roate stem counterclockwise 90°. To close rotate stem clockwise 90°.
TO INDOOR UNIT
TO OPEN ROTATE STEM COUNTERCLOCKWISE 90°.
TO CLOSE ROTATE STEM CLOCKWISE 90°.
SERVICE PORT
SERVICE PORT
SERVICE PORT
CORE
CAP
TO OUTDOOR
UNIT
BALL (SHOWN CLOSED)
VALV E STEM
STEM CAP
STEM CAP
ANGLE-TYPE SERVICE VALVE
(FRONT-SEATED CLOSED)
WHEN SERVICE VALVE IS CLOSED, THE SERVICE PORT IS OPEN TO
THE LINE SET AND INDOOR UNIT.
To Access Service Port:
A service port cap protects the service port core from contamination and serves as the primary leak seal.
1. Remove service port cap with an appropriately sized wrench.
2. Connect gauge set to service port.
3. When testing is completed, replace service port cap and tighten as follows:
With torque wrench: Finger tighten and
torque cap per table 3.
Without torque wrench: Finger tighten and
use an appropriately sized wrench to turn an additional 1/6 turn clockwise.
Reinstall Stem Cap:
Stem cap protects the valve stem from damage and serves as the primary seal. Replace the stem cap and tighten as follows:
9
10
8
11
12
7
6
With Torque Wrench: Finger tighten and
then torque cap per table 3.
Without Torque Wrench: Finger tight
en and use an appropriately sized wrench to turn an additional 1/12 turn clockwise.
9
10
8
11
12
7
6
1/6 TURN
1
2
3
4
5
1/12 TURN
1
2
3
4
5
NOTE — A label with specific torque requirements may be affixed to the stem cap. If the label is present, use the specified torque.
Figure 3. Angle and Ball Service Valves
Page 11
14HPX SERIES
See
NOTES
See NOTES
See NOTES
See
NOTES
CONTROL
BOX
NOTES:
Service clearance of 30 in. (762 mm) must be maintained on one of the sides adjacent to the control box.
Clearance to one of the other three sides must be 36 in. (914 mm)
Clearance to one of the remaining two sides may be 12 in. (305 mm) and the final side may be 6 in. (152 mm).
A clearance of 24 in. must be maintained between two units.
48 in. (1219 mm) clearance required on top of unit.
NOTICE: Specific applications may require adjustment of the listed installation clearances to provide protection for the unit from physical damage or to avoid conditions which limit operating efficiency. (Example: Clearances may have to be increased to prevent snow or ice from falling on the top of the unit. Additional clearances may also be required to prevent air recirculation when the unit is installed under a deck or in another tight space.)
Figure 4. Installation Clearances
DETAIL A
INSTALL UNIT AWAY
FROM WINDOWS
TWO 90 ELBOWS INSTALLED IN LINE SET
WILL REDUCE LINE SET VIBRATION
Figure 5. Placement, and Slab Mounting
Unit Placement
See Unit Dimensions on page 4 for sizing mounting slab, platforms or supports. Refer to figure 4 for mandatory installation clearance requirements.
CAUTION
In order to avoid injury, take proper precaution when lifting heavy objects.
DETAIL B
INSTALL UNIT LEVEL OR, IF ON A SLOPE, MAINTAIN SLOPE TOLERANCE OF 2 DEGREES (OR 2 INCHES PER 5 FEET [50 MM PER 1.5 M]) AWAY FROM BUILDING STRUCTURE.
BUILDING
STRUCTURE
POSITIONING CONSIDERATIONS
Consider the following when positioning the unit:
Some localities are adopting sound ordinances based
on the unit's sound level registered from the adjacent property, not from the installation property. Install the unit as far as possible from the property line.
When possible, do not install the unit directly outside a
window. Glass has a very high level of sound transmission. For proper placement of unit in relation to a window see the provided illustration in figure 5, detail A.
DISCHARGE AIR
MOUNTING SLAB
GROUND LEVEL
Page 12
PLACING UNIT ON SLAB
When installing unit at grade level, the top of the slab should be high enough above grade so that water from higher
least the same height and width as outdoor unit. Mount barrier 24 inches (610 mm) from the sides of the unit in the direction of prevailing winds.
ground will not collect around the unit. The slab should have a slope tolerance as described in figure 5, detail B.
ROOF MOUNTING
Install the unit a minimum of 6 inches (152 mm) above the roof surface to avoid ice build-up around the unit. Locate the unit above a load bearing wall or area of the roof that can adequately support the unit. Consult local codes for rooftop applications.
If unit coil cannot be mounted away from prevailing winter winds, a wind barrier should be constructed. Size barrier at
Roof Damage! This system contains both refrigerant and oil. Some
rubber roofing material may absorb oil and cause the rubber to swell when it comes into contact with oil. The rubber will then bubble and could cause leaks. Protect the roof surface to avoid exposure to refrigerant and oil during service and installation. Failure to follow this notice could result in damage to roof surface.
Removing and Installing Louvered Panels – Initial Builds
WARNING
To prevent personal injury, or damage to panels, unit or structure, be sure to observe the following:
While installing or servicing this unit, carefully stow all removed panels out of the way, so that the panels will not cause injury to personnel, nor cause damage to objects or structures nearby, nor will the panels be subjected to damage (e.g., being bent or scratched).
While handling or stowing the panels, consider any weather conditions, especially windy conditions, that may cause panels to be blown around and battered.
NOTICE
When removing the unit panels. Remove panel A first, then B, C and final ly D. When reinstalling panels, reverse that order starting with panel D, C,
B and finally A.
REMOVAL
STEP 1
TO REMOVE PANEL, REMOVE MOUNTING SCREWS SECURING PANEL TO THE UNIT.
STEP 1
STARTING WITH PANEL D,
PANEL A
STEP 2
SLIGHTLY LIFT PANEL A IN ORDER TO CLEAR SIDE LIPS OF PANEL FROM BASE OF UNIT.
STEP 3
TILT PANEL OUT SLIGHTLY AND PULL DOWNWARD TO REMOVE.
REPEAT STEPS 1, 2 AND 3 TO REMOVE PANELS B, C AND FINALLY D.
PANEL A
INSERT PANEL UNDER UNIT TOP CAP LIP AND LIFT SLIGHTLY TO CLEAR SIDE LIP OF PANEL FROM BASE.
STEP 2
MOVE PANEL IN TOWARDS UNIT. ALIGN LEFT/RIGHT SIDE LIPS OF PANEL WITH GROOVE INSERTS ALONG LEFT/RIGHT SIDE OF UNIT.
PANEL B
WARNING
PANEL A
INSTALLATION
STEP 3
SECURE PANEL, WITH MOUNTING SCREWS.
REPEAT STEPS 1 AND 2 TO INSTALL PANELS C, B AND FINALLY A.
PANEL C
PANEL D
TOP CAP
SIDE
GROOVE
BASE
PANEL D
Figure 6. Louvered Panels
Page 13
14HPX SERIES
Removing and Installing Louvered Panels – Later Builds
WARNING
To prevent personal injury, or damage to panels, unit or structure, be sure to observe the following:
While installing or servicing this unit, carefully stow all removed panels out of the way, so that the panels will not cause injury to personnel, nor cause damage to objects or structures nearby, nor will the panels be subjected to damage (e.g., being bent or scratched).
While handling or stowing the panels, consider any weather conditions, especially windy conditions, that may cause panels to be blown around and battered.
STEP 1
TO REMOVE PANEL, REMOVE MOUNTING SCREWS SECURING PANEL TO THE UNIT.
STEP 2
SLIGHTLY LIFT PANEL IN ORDER TO CLEAR SIDE LIPS OF PANEL FROM BASE OF UNIT.
STEP 3
TILT PANEL OUT SLIGHTLY AND PULL DOWNWARD TO REMOVE.
REMOVAL
PANEL CENTER
CORNER
POST
PANEL LEFT
STEP 1
INSERT PANEL UNDER UNIT TOP CAP LIP AND LIFT SLIGHTLY TO CLEAR SIDE LIP OF PANEL FROM BASE.
STEP 2
MOVE PANEL IN TOWARDS UNIT. ALIGN LEFT/RIGHT SIDE LIPS OF PANEL WITH GROOVE INSERTS ALONG LEFT/RIGHT SIDE OF UNIT.
STEP 3
SECURE PANEL, WITH MOUNTING SCREWS.
CORNER POST
PANEL CENTER
CORNER
POST
PANEL RIGHT
TOP CAP
GROOVE
PANEL INSTALLATION
Figure 7. Louvered Panels
Page 14
SIDE
BASE
New or Replacement Line Set
This section provides information on new installation or replacement of existing line set. If a new or replacement line set is not required, then proceed to Brazing Connections on page .
If refrigerant lines are routed through a wall, seal and isolate the opening so vibration is not transmitted to the building. Pay close attention to line set isolation during installation of any HVAC system. When properly isolated from building structures (walls, ceilings. floors), the refrigerant lines will not create unnecessary vibration and subsequent sounds.
Also, consider the following when placing and installing a high-efficiency air conditioner:
REFRIGERANT LINE SET
Field refrigerant piping consists of liquid and suction lines from the outdoor unit (braze connections) to the indoor unit coil (flare or braze connections). Use Lennox L15 (braze, non-flare) series line set, or use field-fabricated refrigerant lines as listed in table 4.
The compressor is charged with sufficient Polyol ester oil for line set lengths up to 50 feet. Recommend adding oil to system based on the amount of refrigerant charge in the system. No need to add oil in system with 20 pounds of refrigerant or less. For systems over 20 pounds - add one ounce for every five pounds of refrigerant.
Recommended topping-off POE oils are Mobil EAL ARCTIC 22 CC or ICI EMKARATE RL32CF.
MATCHING WITH NEW OR EXISTING INDOOR COIL AND LINE SET
The RFC1-metering line consisted of a small bore copper line that ran from condenser to evaporator coil. Refrigerant was metered into the evaporator by utilizing temperature/pressure evaporation effects on refrigerant in the small RFC line. The length and bore of the RFC line corresponded to the size of cooling unit.
If the 14HPX is being used with either a new or existing indoor coil which is equipped with a liquid line which served as a metering device (RFCI), the liquid line must be replaced prior to the installation of the 14HPX unit. Typically a liquid line used to meter flow is 1/4” in diameter and copper.
LINE SET ISOLATION
Table 4. Refrigerant Line Set (MM)
Field
Model
-018
-024
-030
-036
-042
-048
-060
NOTE — Some applications may require a field provided 7/8” to 1-1/8” adapter
Connections
Liquid Line
3/8 in. (10 mm)
3/8 in. (10 mm)
3/8 in. (10 mm)
Vapor Line
3/4 in (19 mm)
7/8 in (22 mm)
7/8 in. (22 mm)
Recommended Line Set
Liquid Line
3/8 in. (10 mm)
3/8 in. (10 mm)
3/8 in. (10 mm)
Vapor Line
3/4 in (19 mm)
7/8 in (22 mm)
7/8 in. (22 mm)
L15 Line Sets
L15-41 15 ft. - 50 ft. (4.6 m - 15 m)
L15-65 15 ft. - 50 ft. (4.6 m - 15 m)
Field Fabricated
NOTE — When installing refrigerant lines longer than 50 feet, contact Lennox Technical Support Product Applications for assistance or Lennox piping manual. To obtain the correct information from Lennox, be sure to communicate the following points:
Model (14HPX) and size of unit (e.g. -060).
Line set diameters for the unit being installed as listed
in table 4 and total length of installation.
Number of elbows and if there is a rise or drop of the
piping.
IMPORTANT
Mineral oils are not compatible with HFC-410A. If oil must
be added, it must be a Polyol ester oil.
CAUTION
Brazing alloys and flux contain materials which are hazardous to your health.
Avoid breathing vapors or fumes from brazing operations. Perform operations only in well ventilated areas.
Wear gloves and protective goggles or face shield to protect against burns.
Wash hands with soap and water after handling brazing alloys and flux.
IMPORTANT
The Environmental Protection Agency (EPA) prohibits the intentional venting of HFC refrigerants during maintenance, service, repair and disposal of appliance. Approved methods of recovery, recycling or reclaiming must be followed.
IMPORTANT
If this unit is being matched with an approved line set or indoor unit coil which was previously charged with mineral oil, or if it is being matched with a coil which was manufactured before January of 1999, the coil and line set must be flushed prior to installation. Take care to empty all existing traps. Polyol ester (POE) oils are used in Lennox units charged with HFC-410A refrigerant. Residual mineral oil can act as an insulator, preventing proper heat transfer. It can also clog the expansion device, and reduce the system performance and capacity. Failure to properly flush the system per the instructions below will void the warranty.
Page 15
14HPX SERIES
LINE SET
INSTALLATION
Line Set Isolation — The following illustrations are
examples of proper refrigerant line set isolation:
REFRIGERANT LINE SET — TRANSITION
FROM VERTICAL TO HORIZONTAL
ANCHORED HEAVY NYLON
WIRE TIE OR AUTOMOTIVE
MUFFLER‐TYPE HANGER
AUTOMOTIVE
MUFFLER‐TYPE HANGER
IMPORTANT — Refrigerant lines must not contact structure.
REFRIGERANT LINE SET — INSTALLING
VERTICAL RUNS (NEW CONSTRUCTION SHOWN)
NOTE — Insulate liquid line when it is routed through areas where the surrounding ambient temperature could become higher than the temperature of the liquid line or when pressure drop is equal to or greater than 20 psig.
IMPORTANT — Refrigerant lines must not contact wall
OUTSIDE WALL
VAPOR LINE
LIQUID LINE
WALL STUD
STRAP LIQUID LINE TO VAPOR LINE
LIQUID LINE
NON-CORROSIVE
METAL SLEEVE
VAPOR LINE - WRAPPED IN ARMAFLEX
REFRIGERANT LINE SET — INSTALLING
HORIZONTAL RUNS
To hang line set from joist or rafter, use either metal strapping material or anchored heavy nylon wire ties.
WIRE TIE (AROUND VAPOR LINE ONLY)
8 FEET (2.43 METERS)
STRAPPING
MATERIAL (AROUND
VAPOR LINE ONLY)
TAPE OR WIRE TIE
FLOOR JOIST OR
ROOF RAFTER
8 FEET (2.43 METERS)
NON-CORROSIVE METAL SLEEVE
STRAP THE VAPOR LINE TO THE JOIST OR RAFTER AT 8 FEET (2.43 METERS) INTERVALS THEN STRAP THE LIQUID LINE TO THE VAPOR LINE.
TAPE OR WIRE TIE
WIRE TIE
INSIDE WALL
CAULK
LIQUID LINE
STRAP
NON-CORROSIVE METAL SLEEVE
WIRE TIE
WOOD BLOCK
WIRE TIE
STRAP
WOOD BLOCK
BETWEEN STUDS
SLEEVE
VAPOR LINE WRAPPED
WITH ARMAFLEX
OUTSIDE
WALL
PVC
PIPE
FIBERGLASS
INSULATION
NOTE — Similar installation practices should be used if line set is to be installed on exterior of outside wall.
FLOOR JOIST OR
ROOF RAFTER
WARNING — Polyol ester (POE) oils used with HFC-410A refrigerant absorb moisture very quickly. It is very important that the
refrigerant system be kept closed as much as possible. DO NOT remove line set caps or service valve stub caps until you are ready to make connections.
Figure 8. Line Set Installation
Page 16
Loading...
+ 36 hidden pages