Lennox 13ACX, 13ACX-018, 13ACX-024, 13ACX-030, 13ACX-036 Installation Instructions Manual

...
Page 1
INSTALLATION
2010 Lennox Industries Inc.
Dallas, Texas, USA
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
Improper installation, adjustment, alteration, service or maintenance can cause personal injury, loss of life, or damage to property.
Installation and service must be performed by a licensed professional installer (or equivalent) or a service agency.
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFCs, HCFCs and HFCs) as of July 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for noncompliance.
INSTRUCTIONS
Merit® Series 13ACX Units
AIR CONDITIONER
506374−01 03/10 Supersedes 11/09
TABLE OF CONTENTS
Shipping and Packing List 1. . . . . . . . . . . . . . . . . . . . . . . .
General 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit Dimensions 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Typical Unit Parts Arrangement 2. . . . . . . . . . . . . . . . . . .
Model Number Identification 3. . . . . . . . . . . . . . . . . . . . . .
General Information 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operating Gauge Set and Service Valves 3. . . . . . . . . . .
Recovering Refrigerant from Existing System 5. . . . . . .
New Outdoor Unit Placement 6. . . . . . . . . . . . . . . . . . . . .
New or Replacement Line Set 6. . . . . . . . . . . . . . . . . . . . .
Metering Devices and Flushing the System 10. . . . . . . .
Testing for Leaks 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Evacuating the System 13. . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Connections 14. . . . . . . . . . . . . . . . . . . . . . . . . .
Servicing Unit Delivered Void of Charge 16. . . . . . . . . . .
Unit Start−Up 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Refrigerant 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Removing and Installing Louvers 22. . . . . . . . . . . . . . . . .
System Operation 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maintenance 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Start−Up and Performance Checklist 24. . . . . . . . . . . . . .
Shipping and Packing List
Litho U.S.A.
IMPORTANT
This unit must be matched with an indoor coil as specified in Lennox Engineering Handbook. Coils previously charged with HCFC−22 must be flushed.
Electric Shock Hazard. Can cause injury or death. Unit must be grounded in accordance with national and local codes.
Line voltage is present at all components when unit is not in operation on units with single-pole contactors. Disconnect all remote electric power supplies before opening access panel. Unit may have multiple power supplies.
03/10 506374−01
Check the unit for shipping damage and listed times below are intact. If damaged, or if parts are missing, immediately contact the last shipping carrier.
1  Assembled outdoor unit 1  Refrigerant flow control kit (Fixed Orifice) 1  Liquid line filter drier
General
13ACX, which will also be referred to in this instruction as the outdoor unit, uses HFC−410A refrigerant. This outdoor unit must be installed with a matching indoor unit and line set as outlined in the Lennox 13ACX Engineering Handbook.
This outdoor unit is designed for use in systems that use one of the following refrigerant metering devices:
Thermal expansion valve (TXV) Fixed orifice
Page 1
*2P0310* *P506374-01*
Page 2
Unit Dimensions − Inches (mm)
A
OUTDOOR
COIL FAN
COMPRESSOR
B
SUCTION AND LIQUID
LINE CONNECTION
OPTIONAL UNIT
STANDOFF KIT (4)
SIDE VIEW
Model Numbers A B
−018 24−1/4 (616) 25−1/4 (641)
−024 24−1/4 (616) 25−1/4 (641)
−030 24−1/4 (616) 29−1/4 (743)
−036 24−1/4 (616) 29−1/4 (743)
−042 28−1/4 (724) 29−1/4 (743)
−048 28−1/4 (724) 37−1/4 (925)
−060 28−1/4 (724) 33−1/4 (845)
(FIELD INSTALLED)
DISCHARGE AIR
SIDE VIEW
A
Typical Unit Parts Arrangement
CONTROL
CAPACITOR
GROUND LUG
CONTACTOR
CUTOUT FOR HIGH VOLTAGE CONDUIT
NOTE  PLUMBING LAYOUT AND COMPRESSOR TYPE MAY VARY SLIGHTLY BETWEEN MODEL SIZES.
COMPRESS0R
DISCHARGE LINE
COMPRESSOR
HARNESS
OUTDOOR COIL
HIGH PRESSURE
SWITCH (S4)
CONTROL WIRE LOOP
506374−01 03/10
LIQUID LINE SERVICE VALVE
Page 2
SUCTION LINE SERVICE VALVE
Page 3
Model Number Identification
AC X13 024
Nominal SEER
Unit Type
AC = Air Conditioner
Refrigerant
X = R−410A
This product and/or the indoor unit it is matched with may contain fiberglass wool.
Disturbing the insulation during installation, maintenance, or repair will expose you to fiberglass wool dust. Breathing this may cause lung cancer. (Fiberglass wool is known to the State of California to cause cancer.)
Fiberglass wool may also cause respiratory, skin, and eye irritation.
To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor.
Lennox Industries Inc. P.O. Box 799900 Dallas, TX 75379−9900
CAUTION
Physical contact with metal edges and corners while applying excessive force or rapid motion can result in personal injury. Be aware of, and use caution when working near these areas during installation or while servicing this equipment.
General Information
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities who have jurisdiction before installation.
230
2
Minor Revision Number
Voltage
230 = 208/230V−1phase−60hz
Cooling Capacity − Tons 018 = 1.5
024 = 2 030 = 2.5 036 = 3 042 = 3.5 048 = 4 060 = 5
IMPORTANT
Only use Allen wrenches of sufficient hardness (50Rc − Rockwell Harness Scale minimum). Fully insert the wrench into the valve stem recess.
Service valve stems are factory−torqued (from 9 ft−lbs for small valves, to 25 ft−lbs for large valves) to prevent refrigerant loss during shipping and handling. Using an Allen wrench rated at less than 50Rc risks rounding or breaking off the wrench, or stripping the valve stem recess.
See the Lennox Service and Application Notes #C−08−1 for further details and information.
IMPORTANT
To prevent stripping of the various caps used, the appropriately sized wrench should be used and fitted snugly over the cap before tightening.
When servicing or repairing HVAC components, ensure the fasteners are appropriately tightened. Table 1 provides torque values for fasteners.
Table 1. Torque Requirements
Parts Recommended Torque
Service valve cap 8 ft.− lb. 11 NM
Sheet metal screws 16 in.− lb. 2 NM
Machine screws #10 28 in.− lb. 3 NM
Compressor bolts 90 in.− lb. 10 NM
Gauge port seal cap 8 ft.− lb. 11 NM
Operating Gauge Set and Service Valves
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities who have jurisdiction before installation.
TORQUE REQUIREMENTS
When servicing or repairing heating, ventilating, and air conditioning components, ensure the fasteners are appropriately tightened. Table 1 lists torque values for fasteners.
USING MANIFOLD GAUGE SET
When checking the system charge, only use a manifold gauge set that features low loss anti−blow back fittings.
Manifold gauge set used with HFC−410A refrigerant systems must be capable of handling the higher system operating pressures. The gauges should be rated for use with pressures of 0 − 800 psig on the high side and a low side of 30" vacuum to 250 psig with dampened speed to 500 psi. Gauge hoses must be rated for use at up to 800 psig of pressure with a 4000 psig burst rating.
Page 3
13ACX SERIES
Page 4
OPERATING SERVICE VALVES
The liquid and vapor line service valves are used for removing refrigerant, flushing, leak testing, evacuating, checking charge and charging.
SERVICE VALVES
VARIOUS TYPES
OPEN TO BOTH INDOOR AND
OUTDOOR UNITS
SERVICE PORT CAP
SERVICE PORT
TO INDOOR
CORE
UNIT
SERVICE PORT
(VALVE STEM SHOWN OPEN) INSERT HEX WRENCH HERE
Each valve is equipped with a service port which has a factory−installed valve stem. Figure 1 provides information on how to access and operating both angle and ball service valves.
SERVICE PORT CAP
SERVICE PORT
(VALVE STEM SHOWN CLOSED) INSERT HEX WRENCH HERE
CLOSED TO BOTH
INDOOR AND OUTDOOR
UNITS
TO INDOOR UNIT
FRONT-SEATED
STEM CAP
SERVICE PORT
CORE
VALVE STEM
TO INDOOR
UNIT
TO OUTDOOR
UNIT
(FRONT−SEATED
STEM CAP
ANGLE−TYPE
SERVICE VALVE
CLOSED)
TO OUTDOOR UNIT
WHEN SERVICE VALVE IS CLOSED, THE SERVICE PORT IS OPEN TO THE LINE SET AND INDOOR UNIT.
WHEN SERVICE VALVE IS OPEN, THE SERVICE PORT IS OPEN TO LINE SET, INDOOR AND OUTDOOR UNIT.
To Access Service Port:
A service port cap protects the service port core from contamination and serves as the primary leak seal.
1. Remove service port cap with an appropriately sized wrench.
2. Connect gauge set to service port.
3. When testing is completed, replace service port cap and tighten as fol­lows:
With Torque Wrench: Finger tighten and torque cap per Table 1. Without Torque Wrench: Finger tighten and use an appropriately
sized wrench to turn an additional 1/6 turn clockwise.
Operating Angle Type Service Valve:
1. Remove stem cap with an appropriately sized wrench.
2. Use a service wrench with a hex−head extension (3/16" for liquid line valve sizes and 5/16" for vapor line valve sizes) to back the stem out counterclockwise as far as it will go.
ANGLE−TYPE SERVICE VALVE
(BACK−SEATED OPENED)
TO OPEN ROTATE STEM COUNTERCLOCKWISE 90°.
TO CLOSE ROTATE STEM CLOCKWISE 90°.
SERVICE PORT
SERVICE PORT CORE
SERVICE PORT CAP
TO OUTDOOR UNIT
1/6 TURN
12
11
10
9
8
1
2
3
4
5
7
6
BALL (SHOWN CLOSED)
BALL−TYPE SERVICE
VAL VE
STEM CAP
Operating Ball Type Service Valve:
1. Remove stem cap with an appropriately sized wrench.
2. Use an appropriately sized wrenched to open. To open valve, rotate stem counterclockwise 90°. To close rotate stem clockwise 90°.
VALVE STEM
Reinstall Stem Cap:
Stem cap protects the valve stem from damage and serves as the primary seal. Replace the stem cap and tighten as follows:
With Torque Wrench: Finger tighten and then torque cap per Table 1. Without Torque Wrench: Finger tighten and use an appropriately sized wrench to turn
an additional 1/12 turn clockwise.
NOTE  A label with specific torque requirements may be affixed to the stem cap. If the label is present, use the specified torque.
Figure 1. Angle and Ball Service Valves
506374−01 03/10
Page 4
9
10
8
11
1/6 TURN
12
1
2
3
4
5
7
6
Page 5
Recovering Refrigerant from Existing System
RECOVERING
REFRIGERANT FROM SYSTEM
DISCONNECT POWER
Disconnect all power to the existing outdoor unit at the service
1
disconnect switch or main fuse box/breaker panel.
MAIN FUSE BOX/
BREAKER PANEL
SERVICE
DISCONNECT
SWITCH
RECOVERING REFRIGERANT
Remove existing HCFC−22 refrigerant using one of the following procedures:
3
IMPORTANT  Some system configurations may contain higher than normal refrigerant charge due to either large internal coil volumes,
and/or long line sets.
CONNECT MANIFOLD GAUGE SET
Connect a gauge set, clean recovery cylinder and a recovery
2
machine to the service ports of the existing unit. Use the instructions provided with the recovery machine to make the connections.
MANIFOLD GAUGES
RECOVERY MACHINE
LOW
CLEAN RECOVERY CYLINDER
OUTDOOR UNIT
HIGH
METHOD 1:
Us this method if the existing outdoor unit is not equipped with shut−off valves, or if the unit is not operational and you plan to use the existing HCFC−22 to flush the system.
Remove all HCFC−22 refrigerant from the existing system. Check gauges after shutdown to confirm that the entire system is completely void of refrigerant.
METHOD 2:
Use this method if the existing outdoor unit is equipped with manual shut−off valves, and you plan to use new HCFC−22 refrigerant to flush the system.
The following devices could prevent full system charge recovery into the outdoor unit:
Outdoor unit’s high or low−pressure switches (if applicable) when tripped can cycle the compressor OFF. Compressor can stop pumping due to tripped internal pressure relief valve. Compressor has internal vacuum protection that is designed to unload the scrolls (compressor stops pumping) when the pressure ratio meets
a certain value or when the suction pressure is as high as 20 psig. (Compressor suction pressures should never be allowed to go into a vacuum. Prolonged operation at low suction pressures will result in overheating of the scrolls and permanent damage to the scroll tips, drive bearings and internal seals.)
Once the compressor can not pump down to a lower pressure due to one of the above system conditions, shut off the vapor valve. Turn OFF the main power to unit and use a recovery machine to recover any refrigerant left in the indoor coil and line set.
Perform the following task:
A. Start the existing HCFC−22 system in the cooling mode and close the liquid line valve. B. Use the compressor to pump as much of the existing HCFC−22 refrigerant into the outdoor unit until the outdoor system is full. Turn the outdoor unit
main power OFF and use a recovery machine to remove the remaining refrigerant from the system.
NOTE  It may be necessary to bypass the low pressure switches (if equipped) to ensure complete refrigerant evacuation.
C. When the low side system pressures reach 0 psig, close the vapor line valve.
D. Check gauges after shutdown to confirm that the valves are not allowing refrigerant to flow back into the low side of the system.
Page 5
13ACX SERIES
Page 6
New Outdoor Unit Placement
See Unit Dimensions on Page 2 for sizing mounting slab, platforms or supports. Refer to Figure 2 for mandatory installation clearance requirements.
*
INSTALL UNIT AWAY
FROM WINDOWS
NOTES:
*
*
*
Service panel access clearance of 30 in. (762 mm) must be
maintained.
Clearance to one of the other three sides must be 36 in. (914
Clearance on one of the remaining two sides may be 12 in. (305
.
mm)
mm) and the final side may be 6 in. (152 mm)
.
Clearance required on top of unit is 48 in. (1219 mm).
A clearance of 24 in. (610 mm) must be maintained between two
units.
Figure 2. Installation Clearances
POSITIONING CONSIDERATIONS
CAUTION
TWO 90 ELBOWS INSTALLED IN LINE SET
WILL REDUCE LINE SET VIBRATION
Figure 3. Outside Unit Placement
PLACING OUTDOOR UNIT ON SLAB
When installing a unit at grade level, the top of the slab should be high enough above the grade so that water from higher ground would not collect around the unit as illustrated in Figure 4.
DISCHARGE AIR
BUILDING
STRUCTURE
MOUNTING SLAB
GROUND LEVEL
In order to avoid injury, take proper precaution when lift­ing heavy objects.
Consider the following when positioning the unit:
Some localities are adopting sound ordinances based
on the unit’s sound level registered from the adjacent property, not from the installation property. Install the unit as far as possible from the property line.
When possible, do not install the unit directly outside
a window. Glass has a very high level of sound transmission. For proper placement of unit in relation to a window see the provided illustration in Figure 3.
506374−01 03/10
Figure 4. Typical Slab Mounting at Ground Level
Slab may be level or have a slope tolerance away from the building of not more than two degrees, or 2 inches per 5 feet (51 mm per 1524 mm) as illustrated in Figure 4.
INSTALLING OUTDOOR UNIT ON ROOF
Install the unit at a minimum of 4 inches (102 mm) above the surface of the roof. Ensure the weight of the unit is properly distributed over roof joists and rafters. Redwood or steel supports are recommended.
New or Replacement Line Set
This section provides information on installation or replacement of existing line set. If line set is not being installed or replace then proceed to Brazing Connections on Page 9.
Page 6
Page 7
If refrigerant lines are routed through a wall, seal and isolate the opening so vibration is not transmitted to the building. Pay close attention to line set isolation during installation of any HVAC system. When properly isolated from building structures (walls, ceilings. floors), the refrigerant lines will not create unnecessary vibration and subsequent sounds.
Also, consider the following when placing and installing a high−efficiency air conditioner:
REFRIGERANT LINE SET
Field refrigerant line set consists of liquid and suction lines from the outdoor unit to the indoor unit coil. Use Lennox L15 (braze, non−flare) series line set, or field−fabricated refrigerant lines that meet the specifications listed below.
Table 2. Refrigerant Line Set
Valve Field
−018
−024
−030
−036
−042
−048
−060
Connections
Liquid Line
3/8 in.
(10 mm)
3/8 in.
(10 mm)
3/8 in.
(10 mm)
Suction Line
(19 mm)
(22 mm)
1−1/8 in. (29 mm)
3/4 in.
7/8 in.
Model
NOTE  Some applications may required a field provided 7/8" to 1−1/8" adapter
Recommended Line Set
Liquid Line
3/8 in
(10 mm)
3/8 in.
(10 mm)
3/8 in.
(10 mm)
Suction Line
3/4 in.
(19 mm)
7/8in.
(22 mm)
1−1/8 in. (29 mm)
L15 Line Set
15 ft. − 50 ft.
(4.6 m −
15 ft. − 50 ft.
(4.6 m −
Fabricated
L15−41
15 m)
L15−65
15 m)
Field
NOTE − When installing refrigerant lines longer than 50 feet, contact Lennox Technical Support Product Applications for assistance or Lennox piping manual. To obtain the correct information from Lennox, be sure to communicate the following points:
Model (13ACX) and size of unit (e.g. −060). Line set diameters for the unit being installed as listed
in Table 2 and total length of installation.
Number of elbows and if there is a rise or drop of the
piping.
MATCHING WITH NEW OR EXISTING INDOOR COIL AND LINE SET
The RFC1−metering line consisted of a small bore copper line that ran from condenser to evaporator coil. Refrigerant was metered into the evaporator by utilizing temperature/pressure evaporation effects on refrigerant in the small RFC line. The length and bore of the RFC line corresponded to the size of cooling unit.
If the 13ACX is being used with either a new or existing indoor coil which is equipped with a liquid line which served as a metering device (RFCI), the liquid line must be replaced prior to the installation of the 13ACX unit. Typically a liquid line used to meter flow is 1/4" in diameter and copper.
LIQUID LINE FILTER DRIER INSTALLATION
The filter drier (one is shipped with each 13ACX unit) must be field installed in the liquid line between the outdoor unit’s liquid line service valve and the indoor coil’s metering device (fixed orifice or TXV) as illustrated in Figure 5. This
filter drier must be installed to ensure a clean, moisture−free system. Failure to install the filter drier will void the warranty. A replacement filter drier is available from Lennox. See Brazing Connections on Page 9 for special procedures on brazing filter drier connections to the liquid line.
BRAZE CONNECTION
POINTS
LIQUID
LINE
OUTDOOR
UNIT
LIQUID LINE
SERVICE VALVE
LINE
LIQUID LINE
FILTER DRIER
Figure 5. Typical Liquid Line Filter Drier Installation
CAUTION
Brazing alloys and flux contain materials which are hazardous to your health.
Avoid breathing vapors or fumes from brazing operations. Perform operations only in well ventilated areas.
Wear gloves and protective goggles or face shield to protect against burns.
Wash hands with soap and water after handling brazing alloys and flux.
IMPORTANT
The Environmental Protection Agency (EPA) prohibits the intentional venting of HFC refrigerants during maintenance, service, repair and disposal of appliance. Approved methods of recovery, recycling or reclaiming must be followed.
IMPORTANT
If this unit is being matched with an approved line set or indoor unit coil which was previously charged with mineral oil, or if it is being matched with a coil which was manufactured before January of 1999, the coil and line set must be flushed prior to installation. Take care to empty all existing traps. Polyol ester (POE) oils are used in Lennox units charged with HFC−410A refrigerant. Residual mineral oil can act as an insulator, preventing proper heat transfer. It can also clog the expansion device, and reduce the system performance and capacity. Failure to properly flush the system per the instructions below will void the warranty.
Page 7
13ACX SERIES
Page 8
LINE SET
INSTALLATION
Line Set Isolation  The following illustrations are
examples of proper refrigerant line set isolation:
REFRIGERANT LINE SET  TRANSITION
FROM VERTICAL TO HORIZONTAL
ANCHORED HEAVY NYLON WIRE TIE OR AUTOMOTIVE
MUFFLER-TYPE HANGER
AUTOMOTIVE
MUFFLER-TYPE HANGER
IMPORTANT  Refrigerant lines must not contact structure.
REFRIGERANT LINE SET  INSTALLING
VERTICAL RUNS (NEW CONSTRUCTION SHOWN)
NOTE  Insulate liquid line when it is routed through areas where the surrounding ambient temperature could become higher than the temperature of the liquid line or when pressure drop is equal to or greater than 20 psig.
IMPORTANT  Refrigerant lines must not contact wall
OUTSIDE WALL
VAPOR LINE
LIQUID LINE
WALL STUD
STRAP LIQUID LINE TO VAPOR LINE
LIQUID LINE
NON−CORROSIVE
METAL SLEEVE
VAPOR LINE − WRAPPED IN ARMAFLEX
REFRIGERANT LINE SET  INSTALLING
HORIZONTAL RUNS
To hang line set from joist or rafter, use either metal strapping material or anchored heavy nylon wire ties.
WIRE TIE (AROUND VAPOR LINE ONLY)
8 FEET (2.43 METERS)
STRAPPING
MATERIAL (AROUND
VAPOR LINE ONLY)
TAPE OR WIRE TIE
FLOOR JOIST OR
ROOF RAFTER
8 FEET (2.43 METERS)
NON−CORROSIVE METAL SLEEVE
STRAP THE VAPOR LINE TO THE JOIST OR RAFTER AT 8 FEET (2.43 METERS) INTERVALS THEN STRAP THE LIQUID LINE TO THE VAPOR LINE.
TAPE OR WIRE TIE
WIRE TIE
INSIDE WALL
WOOD BLOCK
BETWEEN STUDS
SLEEVE
VAPOR LINE WRAPPED
WITH ARMAFLEX
OUTSIDE
WALL
PVC
PIPE
FIBERGLASS
INSULATION
CAULK
STRAP
NON−CORROSIVE METAL SLEEVE
WIRE TIE
WOOD BLOCK
WIRE TIE
STRAP
LIQUID LINE
NOTE  Similar installation practices should be used if line set is to be installed on exterior of outside wall.
FLOOR JOIST OR
ROOF RAFTER
506374−01 03/10
WARNING  Polyol ester (POE) oils used with HFC−410A refrigerant absorb moisture very quickly. It is very important that the
refrigerant system be kept closed as much as possible. DO NOT remove line set caps or service valve stub caps until you are ready to make connections.
Figure 6. Line Set Installation
Page 8
Page 9
BRAZING
CONNECTIONS
CUT AND DEBUR
Cut ends of the refrigerant lines square
1
(free from nicks or dents) and debur the ends. The pipe must remain round and do not pinch end of the line.
ATTACHED GAUGES
A. Connect gauge set low pressure side to liquid line service
3
valve.
B. Connect gauge set center port to bottle of nitrogen with
regulator.
SERVICE PORT MUST BE OPEN TO ALLOW EXIT
INDOOR
UNIT
NOTE − Use silver alloy brazing rods with five or six percent minimum silver alloy for copper−to−copper brazing, 45 percent alloy for copper−to−brass and copper−to−steel brazing.
CAP AND CORE REMOVAL
Remove service cap and core
2
from both the vapor and liquid line service ports.
HIGHLOW
B
ATTACH
POINT FOR NITROGEN
VAPOR LINE
GAUGES
VAPOR LINE
SERVICE
VALV E
OUTDOOR
UNIT
USE REGULATOR TO FLOW
NITROGEN AT 1 TO 2 PSIG.
WRAP SERVICE VALVE
To protect components during
4
brazing, wrap a wet cloth around the liquid line service valve body and copper tube stub and use another wet cloth underneath the valve body to protect the base paint.
BRAZE LINE SET
Braze the liquid line to the liquid line
6
service valve. Turn off nitrogen flow.
POINT FLAME AWAY FROM
SERVICE VALVE
LIQUID LINE
LIQUID LINE SERVICE
5
NOTE  The fixed orifice or check expansion valve metering device at the indoor unit will allow low pressure nitrogen to flow through the system.
VALV E
FLOW NITROGEN
Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration gauge set into the valve stem port connection on the liquid line service valve and out of the valve stem port connection on the vapor service valve.
INSTALL SERVICE PORT CAPS ONLY
After all connections have been brazed, disconnect manifold gauge
7
set from service ports, cool down piping with wet rag and remove all wrappings. Do not reinstall cores until after evacuation procedure. Reinstall service port caps if desired to close off refrigerant ports.
A
LOW
NITROGEN
HIGH
USE REGULATOR TO
FLOW NITROGEN AT 1
TO 2 PSIG.
NITROGEN
WARNING  Allow braze joint to cool before removing the wet rag from the service valve. (TEMPERATURES ABOVE 250ºF CAN DAMAGE VALVE SEALS
IMPORTANT  Connect gauge set low pressure side to vapor line service valve and repeat procedure starting at paragraph 4 for brazing the liquid line to service port valve.
SERVICE PORT
Figure 7. Brazing Connections
Page 9
SERVICE PORT CORE
SERVICE PORT CAP
13ACX SERIES
Page 10
Metering Devices and Flushing the System
FLUSHING
LINE SET AND INDOOR COIL (1 OF 2)
TYPICAL FIXED ORIFICE REMOVAL AND REPLACEMENT PROCEDURE
(Uncased Coil Shown)
1
DISTRIBUTOR TUBES
LIQUID LINE ORIFICE HOUSING
TEFLON RING
FIXED ORIFICE
TWO PIECE PATCH PLATE
(UNCASED COIL ONLY)
DISTRIBUTOR
TUBES
TYPICAL CHECK EXPANSION VALVE
REMOVAL PROCEDURE
(Uncased Coil Shown)
ORIFICE
HOUSING
STUB END
TEFLON RING
CHECK
EXPANSION
VALV E
TEFLON
RING
LIQUID LINE
SENSING
LINE
BRASS NUT
DISTRIBUTOR
ASSEMBLY
A. On fully cased coils, remove the coil access and plumbing panels. B. Remove any shipping clamps holding the liquid line and distributor
assembly.
C. Using two wrenches, disconnect liquid line from liquid line orifice
housing. Take care not to twist or damage distributor tubes during this process.
D. Remove and discard fixed orifice, valve stem assembly if present
and Teflon washer as illustrated above.
E. Use a field−provided fitting to temporary reconnect the liquid line to
the indoor unit’s liquid line orifice housing.
F. Reverse above order to install.
REMOVE AND DISCARD
WHITE TEFLON SEAL (IF
PRESENT)
LIQUID LINE ASSEMBLY
(INCLUDES STRAINER)
CONNECT GAUGES AND EQUIPMENT FOR FLUSHING PROCEDURE
2
VAPOR LINE
SERVICE VALVE
EXISTING
INDOOR
UNIT
LIQUID LINE SERVICE
RECOVERY
CYLINDER
A. Inverted HCFC−22 cylinder with clean refrigerant to the vapor service
B. HCFC−22 gauge set (low side) to the liquid line valve. C. HCFC−22 gauge set center port to inlet on the recovery machine with
D. Connect recovery tank to recovery machines per machine
VALV E
LIQUID
D
valve.
an empty recovery tank to the gauge set.
instructions.
INVERTED HCFC−22 CYLINDER CONTAINS CLEAN HCFC−22 TO BE USED FOR FLUSHING.
A
1
VAPOR
OUTDOOR
B
NEW
UNIT
C
GAUGE
MANIFOLD
LOW
OPENED
TANK RETURN
INLET
DISCHARGE
RECOVERY MACHINE
CLOSED
HIGH
OR
A. On fully cased coils, remove the coil access and plumbing panels. B. Remove any shipping clamps holding the liquid line and distributor as-
C. Disconnect the equalizer line from the check expansion valve equaliz-
D. Remove the vapor line sensing bulb. E. Disconnect the liquid line from the check expansion valve at the liquid
F. Disconnect the check expansion valve from the liquid line orifice hous-
G. Remove and discard check expansion valve and the two Teflon rings. H. Use a field−provided fitting to temporary reconnect the liquid line to the
DISTRIBUTOR
ASSEMBLY
MALE EQUALIZER
LINE FITTING
SENSING BULB
sembly.
er line fitting on the vapor line.
line assembly.
ing. Take care not to twist or damage distributor tubes during this pro­cess.
indoor unit’s liquid line orifice housing.
CAUTION This procedure should not be performed on sys­tems which contain contaminants (Example compressor burn out.
EQUALIZER LINE
ASSEMBLY WITH
VAPOR
LINE
LIQUID LINE
BRASS NUT
LIQUID
FLUSHING LINE SET
The line set and indoor unit coil must be flushed with at least the
3
same amount of clean refrigerant that previously charged the sys­tem. Check the charge in the flushing cylinder before proceeding.
B
A. Set the recovery machine for liquid recovery and start the recov-
ery machine. Open the gauge set valves to allow the recovery machine to pull a vacuum on the existing system line set and in­door unit coil.
B. Invert the cylinder of clean HCFC−22 and open its valve to allow
liquid refrigerant to flow into the system through the vapor line valve. Allow the refrigerant to pass from the cylinder and through the line set and the indoor unit coil before it enters the recovery machine.
C. After all of the liquid refrigerant has been recovered, switch the
recovery machine to vapor recovery so that all of the HCFC−22 vapor is recovered. Allow the recovery machine to pull down to 0 the system.
D. Close the valve on the inverted HCFC−22 drum and the gauge
set valves. Pump the remaining refrigerant out of the recovery machine and turn the machine off.
LINE
506374−01 03/10
Page 10
Page 11
FLUSHING LINE SET AND INDOOR COIL (2 OF 2)
TYPICAL CHECK EXPANSION VALVE INSTALLATION PROCEDURE
This outdoor unit is designed for use in systems that use check expansion valve metering device. See the Lennox 13ACX Engineering Handbook
4
for approved check expansion valve kit match−ups and application information.
The check expansion valve unit can be installed internal or
TWO PIECE
PATCH PLATE
(UNCASED
COIL ONLY)
DISTRIBUTOR
TUBES
DISTRIBUTOR
ASSEMBLY
MALE EQUALIZER LINE
FITTING (SEE
EQUALIZER LINE
INSTALLATION FOR
FURTHER DETAILS)
SENSING BULB INSULATION IS REQUIRED IF MOUNTED EXTERNAL TO THE COIL CASING. SENSING BULB INSTALLATION FOR BULB POSITIONING.
(Uncased Coil Shown)
LIQUID LINE
ORIFICE
HOUSING
STUB
END
TEFLON RING
EQUALIZER LINE
CHECK
EXPANSION
VALV E
LIQUID LINE
ASSEMBLY WITH
BRASS NUT
VAPOR
LINE
external to the indoor coil. In applications where an uncased coil is being installed in a field−provided plenum, install the check expansion valve in a manner that will provide access for field servicing of the check expansion valve. Refer to below illustration for reference during installation of check expansion valve unit.
TEFLON
RING
A. Remove the field−provided fitting that temporary reconnected the liquid
line to the indoor unit’s distributor assembly.
SENSING
LINE
LIQUID LINE
B. Install one of the provided Teflon rings around the stubbed end of the
check expansion valve and lightly lubricate the connector threads and expose surface of the Teflon ring with refrigerant oil.
C. Attach the stubbed end of the check expansion valve to the liquid line
orifice housing. Finger tighten and use an appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in the figure above, or 20 ft−lb.
D. Place the remaining Teflon washer around the other end of the check
expansion valve. Lightly lubricate connector threads and expose sur­face of the Teflon ring with refrigerant oil.
E. Attach the liquid line assembly to the check expansion valve. Finger
tighten and use an appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in the figure above or 20 ft−lb.
VAPOR LINE
BULB
12
9
ON LINES SMALLER THAN 7/8", MOUNT SENSING BULB AT EITHER THE 3 OR 9 O’CLOCK POSITION.
BULB
10
8
11
12
7
6
1/2 TURN
1
2
3
4
5
SENSING BULB INSTALLATION
A. Attach the vapor line sensing bulb in the proper orientation
as illustrated to the right using the clamp and screws pro­vided.
NOTE  Confirm proper thermal contact between vapor line and check expansion bulb before insulating the sensing bulb once installed.
B. Connect the equalizer line from the
check expansion valve to the equalizer vapor port on the vapor line. Finger tighten the flare nut plus 1/8 turn (7 ft−lbs) as illus­trated below.
10
9
11
12
1
8
7
EQUALIZER LINE INSTALLATION
A. Remove and discard either the flare seal cap or flare nut
with copper flare seal bonnet from the equalizer line port on the vapor line as illustrated in the figure to the right.
B. Remove and discard either the flare seal cap or flare nut
with copper flare seal bonnet from the equalizer line port on the vapor line as illustrated in the figure to the right.
5
6
1/8 TURN
2
3
4
VAPOR LINE
FLARE SEAL CAP
ON 7/8" AND LARGER LINES, MOUNT SENSING BULB AT EITHER THE 4 OR 8 O’CLOCK
12
BULB
NOTE  NEVER MOUNT ON BOTTOM OF LINE.
OR
POSITION. NEVER MOUNT ON BOTTOM OF LINE.
BULB
FLARE NUT
COPPER FLARE SEAL BONNET
MALE BRASS EQUALIZER LINE FITTING
VAPOR LINE
Page 11
13ACX SERIES
Page 12
Leak Testing the System
LEAK TEST
LINE SET AND INDOOR COIL
CONNECT GAUGE SET
A. Connect an HFC−410A manifold gauge set high
1
pressure hose to the vapor valve service port.
B. With both manifold valves closed, connect the
cylinder of HFC−410A refrigerant to the center port of the manifold gauge set.
NOTE  Later in the procedure, the HFC−410A container will be replaced by the nitrogen container.
NOTE  Normally, the high pressure hose is connected to the liquid line port. How­ever, connecting it to the vapor port better protects the manifold gauge set from high pressure damage.
HIGHLOW
MANIFOLD GAUGE SET
OUTDOOR UNIT
USE REGULATOR TO FLOW
NITROGEN AT 1 TO 2 PSIG.
NITROGEN
TEST FOR LEAKS
After the line set has been connected to the indoor unit and air conditioner, check the line set connections and
2
indoor unit for leaks. Use the following procedure to test for leaks: A. With both manifold valves closed, connect the cylinder of HFC−410A refrigerant to the center port of the manifold gauge set. Open
the valve on the HFC−410A cylinder (vapor only).
B. Open the high pressure side of the manifold to allow HFC−410A into the line set and indoor unit. Weigh in a trace amount of
HFC−410A. [A trace amount is a maximum of two ounces (57 g) refrigerant or three pounds (31 kPa) pressure]. Close the valve on the HFC−410A cylinder and the valve on the high pressure side of the manifold gauge set. Disconnect the HFC−410A cylinder.
C. Connect a cylinder of dry nitrogen with a pressure regulating valve to the center port of the manifold gauge set.
D. Adjust dry nitrogen pressure to 150 psig (1034 kPa). Open the valve on the high side of the manifold gauge set in order to pressurize the
line set and the indoor unit.
E. After a few minutes, open one of the service valve ports and verify that the refrigerant added to the system earlier is measurable
with a leak detector.
F. After leak testing disconnect gauges from service ports.
HFC−410A
When using a high pressure gas such as dry nitrogen to pressurize a refrigeration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kPa).
Refrigerant can be harmful if it is inhaled. Refrigerant must be used and recovered responsibly.
Failure to follow this warning may result in personal injury or death.
B
TO VAPOR
SERVICE VALVE
Fire, Explosion and Personal Safety Hazard.
Failure to follow this warning could result in damage, personal injury or death.
Never use oxygen to pressurize or purge refrigeration lines. Oxygen, when exposed to a spark or open flame, can cause damage by fire and/or an explosion, that could result in personal injury or death.
IMPORTANT
A
506374−01 03/10
Leak detector must be capable of sensing HFC refrigerant.
Page 12
Page 13
Evacuating the System
EVACUATING
LINE SET AND INDOOR COIL
CONNECT GAUGE SET
NOTE  Remove cores from service valves (if not al­ready done).
1
A. Connect low side of manifold gauge
set with 1/4 SAE in−line tee to vapor line service valve
B. Connect high side of manifold gauge
set to liquid line service valve
C. Connect micron gauge available
connector on the 1/4 SAE in−line tee.
D. Connect the vacuum pump (with
vacuum gauge) to the center port of the manifold gauge set. The center port line will be used later for both the HFC−410A and nitrogen containers.
USE REGULATOR TO FLOW
NITROGEN AT 1 TO 2 PSIG.
HFC−410A
VACUUM PUMP
OUTDOOR
UNIT
A
B
A34000 1/4 SAE TEE WITH SWIVEL COUPLER
500
C
D
MICRON
GAUGE
TO VAPOR
SERVICE VALVE
TO LIQUID LINE SERVICE VALVE
LOW
MANIFOLD
GAUGE SET
HIGH
NITROGEN
EVACUATE THE SYSTEM
A. Open both manifold valves and start the vacuum pump.
2
B. Evacuate the line set and indoor unit to an absolute pressure of 23,000 microns (29.01 inches of mercury).
NOTE  During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once. A rapid rise in pressure indicates a relatively large leak. If this occurs, repeat the leak testing procedure.
NOTE  The term absolute pressure means the total actual pressure within a given volume or system, above the absolute zero of pressure. Absolute pressure in a vacuum is equal to atmospheric pressure minus vacuum pressure.
C. When the absolute pressure reaches 23,000 microns (29.01 inches of mercury), close the manifold gauge valves, turn off the vacuum
pump and disconnect the manifold gauge center port hose from vacuum pump. Attach the manifold center port hose to a dry nitrogen cylinder with pressure regulator set to 150 psig (1034 kPa) and purge the hose. Open the manifold gauge valves to break the vacuum in the line set and indoor unit. Close the manifold gauge valves.
D. Shut off the dry nitrogen cylinder and remove the manifold gauge hose from the cylinder. Open the manifold gauge valves to release the
dry nitrogen from the line set and indoor unit.
E. Reconnect the manifold gauge to the vacuum pump, turn the pump on, and continue to evacuate the line set and indoor unit until the
absolute pressure does not rise above 500 microns (29.9 inches of mercury) within a 20−minute period after shutting off the vacuum pump and closing the manifold gauge valves.
F. When the absolute pressure requirement above has been met, disconnect the manifold hose from the vacuum pump and connect it to
an upright cylinder of HFC−410A refrigerant. Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and indoor unit.
G. Perform the following:
RECOMMEND
MINIMUM 3/8" HOSE
Close manifold gauge valves. Shut off HFC−410A cylinder. Reinstall service valve cores by removing manifold hose from service valve. Quickly install cores with
core tool while maintaining a positive system pressure.
Replace the stem caps and secure finger tight, then tighten an additional one−sixth (1/6) of a turn as
illustrated.
11
10
9
8
7
12
6
1/6 TURN
1
2
3
4
5
Page 13
13ACX SERIES
Page 14
IMPORTANT
Use a thermocouple or thermistor electronic vacuum gauge that is calibrated in microns. Use an instrument capable of accurately measuring down to 50 microns.
Danger of Equipment Damage. Avoid deep vacuum operation. Do not use compressors to evacuate a system. Extremely low vacuums can cause internal arcing and compressor failure. Damage caused by deep vacuum operation will void warranty.
Evacuating the system of non−condensables is critical for proper operation of the unit. Non−condensables are
defined as any gas that will not condense under temperatures and pressures present during operation of an air conditioning system. Non−condensables and water suction combine with refrigerant to produce substances that corrode copper piping and compressor parts.
Electrical
In the U.S.A., wiring must conform with current local codes and the current National Electric Code (NEC). In Canada, wiring must conform with current local codes and the current Canadian Electrical Code (CEC).
Refer to the furnace or air handler installation instructions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size.
24VAC TRANSFORMER
Use the transformer provided with the furnace or air handler for low-voltage control power (24VAC − 40 VA minimum)
SIZE CIRCUIT AND INSTALL SERVICE DISCONNECT SWITCH
Refer to the unit nameplate for minimum circuit ampacity, and maximum fuse or circuit breaker (HACR per NEC). Install power wiring and properly sized disconnect switch.
MAIN FUSE BOX/
BREAKER PANEL
SERVICE
DISCONNECT
SWITCH
NOTE  Units are approved for use only with copper conductors. Ground unit at disconnect switch or to an earth ground.
Electric Shock Hazard. Can cause injury or death. Unit must be grounded in accordance with national and local codes.
Line voltage is present at all components when unit is not in operation on units with single-pole contactors. Disconnect all remote electric power supplies before opening access panel. Unit may have multiple power supplies.
INSTALL THERMOSTAT
Install room thermostat (ordered separately) on an inside wall approximately in the center of the conditioned area and 5 feet (1.5m) from the floor. It should not be installed on an outside wall or where it can be affected by sunlight or drafts.
THERMOSTAT
5 FEET
(1.5M)
NOTE  24VAC, Class II circuit connections are made in the control panel.
506374−01 03/10
Page 14
Page 15
ROUTING HIGH VOLTAGE/ GROUND AND CONTROL WIRING
HIGH VOLTAGE / GROUND WIRES
Any excess high voltage field wiring should be trimmed and secured away from any low voltage field wiring. To facilitate a conduit, a cutout is located in the bottom of the control panel. Connect conduit to the control panel using a proper conduit fitting.
HIGH VOLTAGE
CONNECTIONS
(CONTACTOR)
CONTROL WIRING
NOTE  Wire tie provides low voltage control wire strain relief and to maintain separation of field installed low and high voltage circuits.
NOTE  For proper voltages, select thermostat wire (control wires) gauge per Table above.
NOTE  Do not bundle any excess 24VAC control wires inside control panel.
HIGH VOLTAGE FIELD WIRING
LOW VOLTAGE FIELD WIRING
FACTORY WIRING
Install low voltage wiring from outdoor to indoor unit and from thermostat to indoor unit as illustrated.
A. Run 24VAC control wires through hole with grommet and secure with
provided wire tie.
B. Make 24VAC thermostat wire connections. Locate the two wires from the
contactor and make connection using field provided wire nuts:
Yellow to Y1 Black to C (common)
WIRE RUN LENGTH AWG# INSULATION TYPE
LESS THAN 100’ (30 METERS) 18 TEMPERATURE RATING
MORE THAN 100’ (30 METERS) 16 35ºC MINIMUM.
SINGLE PHASE
GROUND
THERMOSTAT INDOOR UNIT
W1
G
C
R
Y
POWER
HEAT
COOLING
INDOOR
BLOWER
COMMON
R
W
Y
G
C
B
CONTROL
WIRING
HIGH VOLTAGE FLEXIBLE CONDUIT
AND WIRE TIE
OUTDOOR
UNIT
Y1
C
A
GROMMET
Figure 8. Typical 13ACX Unit Wiring Diagram
Page 15
13ACX SERIES
Page 16
GAUGE SET
CONNECTIONS FOR TESTING AND CHARGING
SUCTION LINE
B
SERVICE PORT CONNECTION
REFRIGERANT TANK
MANIFOLD GAUGE SET
LOW
HIGH
OUTDOOR UNIT
CHARGE IN
LIQUID PHASE
DIGITAL SCALE
A
D
TEMPERATURE
SENSOR
LINE SERVICE
A. Close manifold gauge set valves and connect the center hose to a cylinder of HFC−410A. Set for liquid phase charging.
B. Connect the manifold gauge set’s low pressure side to the suction line service port.
C. Connect the manifold gauge set’s high pressure side to the liquid line service port.
D. Position temperature sensor on liquid line near liquid line service port.
TO LIQUID
VALV E
C
Figure 9. Gauge Set Setup and Connections
Servicing Units Delivered Void of Charge
If the outdoor unit is void of refrigerant, clean the system using the procedure described below.
1. Leak check system using procedure outlined on Page
12.
2. Evacuate the system using procedure outlined on Page 13.
3. Use nitrogen to break the vacuum and install a new filter drier in the system.
4. Evacuate the system again using procedure outlined on Page 13.
5. Weigh in refrigerant using procedure outlined under
Start−Up and Charging Procedures.
6. Monitor the system to determine the amount of moisture remaining in the oil. It may be necessary to replace the filter drier several times to achieve the required dryness level. If system dryness is not
verified, the compressor will fail in the future.
Unit Start−Up
2. Inspect all factory− and field−installed wiring for loose connections.
3. After evacuation is complete, open the liquid line and suction line service valves to release the refrigerant charge (contained in air conditioner) into the system.
4. Replace the stem caps and tighten to the value listed in Table 1.
5. Check voltage supply at the disconnect switch. The voltage must be within the range listed on the unit’s nameplate. If not, do not start the equipment until you have consulted with the power company and the voltage condition has been corrected.
6. Set the thermostat for a cooling demand. Turn on power to the indoor handler and close the air conditioner disconnect switch to start the unit.
7. Recheck voltage while the unit is running. Power must be within range shown on the nameplate.
8. Check system for sufficient refrigerate using the procedures that follow.
TEMPERATURE SENSOR
(LIQUID LINE)
IMPORTANT
If unit is equipped with a crankcase heater, it should be energized 24 hours before unit start−up to prevent compressor damage as a result of slugging.
1. Rotate fan to check for binding.
506374−01 03/10
System Refrigerant
This section outlines procedures for:
1. Connecting gauge set for testing and charging;
2. Checking and adjusting indoor airflow;
3. Adding or removing refrigerant.
Page 16
Page 17
ADDING OR REMOVING REFRIGERANT
This system uses HFC−410A refrigerant which operates at much higher pressures than HCFC−22. The pre−installed liquid line filter drier is approved for use with HFC−410A only. Do not replace it with components designed for use with HCFC−22. This unit is NOT approved for use with coils which use capillary tubes or fixed orifices as a refrigerant metering device.
Check airflow using the Delta−T (
DT) process using the illustration in Figure 10.
AIRFLOW
INDOOR COIL
Temperature of air entering indoor coil ºF
A
Wet−bulb ºF
80 24 24 24 23 23 22 22 22 20 19 18 17 16 15 78 23 23 23 22 22 21 21 20 19 18 17 16 15 14 76 22 22 22 21 21 20 19 19 18 17 16 15 14 13
Dry−bulb
74 21 21 21 20 19 19 18 17 16 16 15 14 13 12 72 20 20 19 18 17 17 16 15 15 14 13 12 11 10 70 19 19 18 18 17 17 16 15 15 14 13 12 11 10
57 58 59 60 61 62 63 64 65 66 67 68 69 70
DT
DRY
BULB
C
53º
T
19º
Drop
air flow
air flow
B
B
64º
All temperatures are expressed in ºF
INDOOR COIL
WET BULB
Use the following procedure to adjust for optimal air flow across the indoor coil:
1. Determine the desired DT  Measure entering air temperature using dry bulb (A) and wet bulb (B). DT is the intersecting value of A and B in the Table (see triangle).
2. Find temperature drop across coil  Measure the coil’s dry bulb entering and leaving air temperatures (A and C). Temperature Drop Formula: (T
3. Determine if fan needs adjustment  If the difference between the measured T
DT (T
DT) is within +3º, no adjustment is needed. See example below:
Drop
) = A minus C.
Drop
and the desired
Drop
Assume DT = 15 and A temp. = 72º, these C temperatures would necessitate stated actions:
A
72º
DRY BULB
T
53º 19 – 15 = 4 Increase the airflow 58º 14 15 = −1 (within +3º range) no change 62º 10 15 = −5 Decrease the airflow
DT = ºF ACTION
Drop
4. Adjust the fan speed  See indoor unit instructions to increase/decrease fan speed.
Figure 10. Checking Indoor Airflow over Evaporator Coil using Delta−T (DT) Chart
Changing air flow affects all temperatures; recheck temperatures to confirm that the temperature drop and DT are within +3º.
Page 17
13ACX SERIES
Page 18
START: Determine how refrigerant is metered
WHEN TO CHARGE?
Warm weather best Can charge in colder weather
CHARGE METHOD? Determine by:
Metering device type Outdoor ambient temperature
REQUIREMENTS:
Sufficient heat load in structure Indoor temperature between 70-80ºF
(21−26ºC)
(18.3ºC) and
Above
Manifold gauge set connected to unit Thermometers:
− to measure outdoor ambient temperature
− to measure liquid line temperature
− to measure suction line temperature
APPROACH OR
SUBCOOLING
Figure 11. Determining Charge Method
65ºF
TXV
64ºF
(17.7ºC) and
Below
WEIGH-IN
Which
metering
device?
40ºF
(4.4ºC) and
Above
RFC
39ºF
(3.8ºC) and
Below
WEIGH-INSUPERHEAT
START: Measure outdoor ambient temperature
USE EITHER APPROACH
OR SUBCOOLING
METHOD
65ºF
(18.3ºC) and
Above
WEIGH IN TXV
Refrigerant Charge per Line Set Length
Liquid Line
Set Diameter
3/8" (9.5 mm)
NOTE − *If line length is greater than 15 ft. (4.6 m), add this amount. If line length is less than 15 ft. (4.6 m), subtract this amount.
Ounces per 5 feet (g per 1.5 m)
adjust from 15 feet (4.6 m) line set*
3 ounce per 5’ (85 g per 1.5 m)
Figure 12. HFC−410A Weigh In TXV Method
(17.7ºC) and
ABOVE or
BELOW
64ºF
Below
1. Check Liquid and suction line pressures
2. Compare unit pressures with Table 3, Normal Operating Pressures.
3. Conduct leak check; evacuate as previously outlined.
4. Weigh in the unit nameplate charge plus any charge required for line set differences over feet.
This nameplate is for illustration purposes only. Go to actual nameplate on outdoor unit for charge information.
506374−01 03/10
Page 18
Page 19
START: Measure outdoor ambient temperature
DO NOT CHARGE UNIT
USE WEIGH-IN METHOD
(Results of charging at low
Weigh-in or remove refriger-
temperatures not reliable)
ant based upon line length
If refrigerant is added or removed, retest to confirm that unit is properly charged.
64ºF
(17.7ºC) and
Below
(18.3ºC) and
ABOVE or
BELOW
65ºF
Above
1. Confirm proper airflow across coil using Figure
10.
2. Compare unit pressures with Table 3, Normal Operating Pressures.
3. Set thermostat to call for heat (must have a cooling load between 70-80ºF (21−26ºC).
4. Connect gauge set.
5. When heat demand is satisfied, set thermostat to call for cooling.
6. Allow temperatures and pressures to stabilize.
7. Record outdoor ambient temperature:
AMBº =_________
8. Record liquid line temperature:
LIQº = __________
9. Subtract to determine approach (APPº):
LIQº_____ − AMBº _____ = APPº_____
10. Compare results with table below.
If value is greater than shown (high approach), add refrigerant; if less than shown (liquid temperature too close to ambient temperature, low approach), remove refrigerant.
Figure 13. HFC−410A Approach TXV Charge
START: Measure outdoor ambient temperature
USE WEIGH-IN METHOD
DO NOT CHARGE UNIT
Weigh-in or remove refrigerant
(Results of charging at low
based upon line length
temperatures not reliable)
CARDBOARD OR PLASTIC SHEET
If refrigerant is added or removed, verify charge using the Approach Method.
64ºF
(17.7ºC) and
Below
BLOCK OUTDOOR COIL: [sometimes necessary with lower temperatures] Use cardboard or plastic sheet to restrict the airflow through the outdoor coil to achieve pressures from 325−375 psig (2240−2585 kPa). Higher pressures are needed to check charge. Block equal sections of air intake panels and move coverings sideways until the liquid pressure is in the above noted ranges.
If value is MORE than shown, remove refrigerant.
APPº (Approach) Values(F:+/−1.0° [C: +/−0.6°])
ºF (ºC)* −018 −024 −030 −036 −042 −048 −060 Any 4 (2.2) 8 (4.4) 8 (4.4) 11 (6.1) 9 (5.0) 8 (4.4) 9 (5.0) *Temperature of air entering outdoor coil
65ºF
(18.3ºC) and
Above
ABOVE or
BELOW
1. Confirm proper airflow across coil using Figure
10.
2. Compare unit pressures with Table 3, Normal Operating Pressures.
3. Set thermostat to call for heat (must have a
cooling load between 70-80ºF (21−26ºC)
4. Connect gauge set
5. Measure outdoor ambient temperature
6. When heat demand is satisfied, set thermostat to
call for cooling
7. Allow temperatures and pressures to stabilize.
NOTE − If necessary, block outdoor coil to maintain 325 − 375 psig.
8. Record liquid line temperature:
LIQº = ______
9. Measure liquid line pressure and use the value to
determine saturation temperature (see Table 4):
SATº = ______
10. Subtract to determine subcooling (SCº):
SATº_____ − LIQº _____ = SCº _____
11. Compare results with table below.
If value is LESS than shown, add refrigerant.
Figure 14. HFC−410A Subcooling TXV Charge
MORE or
LESS
SCº (Subcooling) Values (F:+/−1.0° [C: +/−0.6°])
ºF (ºC)* −018 −024 −030 −036 −042 −048 −060 Any 10 (5.6) 10 (5.6) 9 (5.0) 12 (6.7) 9 (5.0) 9 (5.0) 7 (3.9) *Temperature of air entering outdoor coil
Page 19
13ACX SERIES
Page 20
START: Measure outdoor ambient temperature
USE SUPERHEAT
40ºF
(4.4ºC) and
Above
WEIGH IN RFC
Refrigerant Charge per Line Set Length
(3.8ºC) and
ABOVE or
BELOW
39ºF
Below
1. Check Liquid and suction line pressures
2. Compare unit pressures with Table 3,
Normal Operating Pressures.
3. Conduct leak check; evacuate as
previously outlined.
4. Weigh in the unit nameplate charge plus
any charge required for line set differences over feet.
Liquid Line
Set Diameter
3/8" (9.5 mm)
NOTE − *If line length is greater than 15 ft. (4.6 m), add this amount. If line length is less than 15 ft. (4.6 m), subtract this amount.
Ounces per 5 feet (g per 1.5 m)
adjust from 15 feet (4.6 m) line set*
3 ounce per 5’ (85 g per 1.5 m)
Figure 15. HFC−410A Weigh In RFC Method
START: Measure outdoor ambient temperature
USE WEIGH-IN METHOD
Weigh-in or remove refrigerant based upon line length
Wet Bulb (air entering indoor coil) ºF* 50 52 54 56 58 60 62 64 66 68 70 72 74 76 40 15 18 20 23 26 29 32 34 38 41 43 46 48 51 45 13 16 18 21 24 27 30 33 36 39 41 44 46 49 50 11 14 16 19 22 25 28 31 34 37 39 42 44 47 55 9 12141720232730333638404244 60 7 10121518212427303335384043 65 - 6 10 13 16 19 21 24 27 30 33 36 38 41 70 - - 7 1013161921242730333639 75 - - - 6 9 121518212428313437 80 - - - - 5 8 12 15 18 21 25 28 31 35 85 - - - - - - 8 11 15 19 22 26 30 33 90 - - - - - - 5 9 131620242731 95 - - - - - - - 6 101418222529 100 --------81216212428
If refrigerant is REMOVED, retest to confirm that unit is properly charged.
105 --------5913172226 110 ---------611152025 115 ----------8141824
* Dry−bulb temperature (ºF) of entering outdoor ambient air.
(3.8ºC) and
Below
SHº (Superheat) Values (+/−5ºF)
ABOVE or
BELOW39ºF
40ºF
(4.4ºC) and
Above
This nameplate is for illustration purposes only. Go to actual nameplate on outdoor unit for charge information.
1. Confirm proper airflow across coil using Figure
10.
2. Compare unit pressures with Table 3, Normal Operating Pressures.
3. Use SUPERHEAT to correctly charge unit or to verify the charge is correct.
4. Set thermostat to call for heat (must have a cooling load between 70-80ºF (21−26ºC)
5. Connect gauge set.
6. When heat demand is satisfied, set thermostat to call for cooling.
7. Allow temperatures and pressures to stabilize.
8. Measure the suction line pressure and use the use value to determine saturation temperature (Table
4):
SATº =_________
9. Record suction line temperature:
VAPº =_________
10. Subtract to determine superheat (SHº):
VAPº − _____ SATº ______ = SHº______
11. Record the wet bulb temperature (air entering indoor coil):
WB =_______
12. Record outdoor ambient temperature.
13. Compare results with table to the left.
NOTE − Do not attempt to charge system where a dash appears, system could be overcharged. Superheat is taken at suction line service port. Suction line superheat must never be less than 5ºF at the suction line service port.
If value is LESS than shown, then REMOVE refrigerant.
Figure 16. HFC−410A Superheat RFC Method
506374−01 03/10
MORE or
LESS
If value is MORE than shown, then ADD refrigerant.
Page 20
If refrigerant is ADDED, retest to confirm that unit is properly charged.
Page 21
Table 3. HFC−410A Normal Operating Pressures (Liquid +10 and Suction +5 psig)
Use this table to perform maintenance checks; it is not a procedure for charging the system. Minor variations in these pressures may be due to differences in installations.
IMPORTANT
Significant deviations could mean that the system is not properly charged or that a problem exists with some component in the system.
13ACX
5F (5C)* Liquid / Suction Liquid / Suction Liquid / Suction Liquid / Suction Liquid / Suction Liquid / Suction Liquid / Suction
Expansion Valve (TXV)
65 (18) 233 / 132 244 / 137 248 / 127 263 / 135 238 /132 235 / 132 241 / 130
70 (21) 251 / 133 263 / 138 263 / 131 281 / 138 262 / 133 254 / 132 260 / 130
75 (24) 265 / 133 285 / 139 284 / 132 302 / 140 280 / 134 276 / 134 280 / 132
80 (27) 292 / 135 307 / 140 307 / 134 325 / 142 301 / 136 298 / 134 299 / 134
85 (29) 314 / 136 329 / 141 330 / 135 349 / 142 327 / 137 323 / 135 321 / 135
90 (32) 338 / 137 354 / 142 355 / 136 375 / 143 353 / 138 350 / 137 344 / 134
95 (35) 362 / 138 379 / 143 380 / 137 404 / 144 377 / 140 377 / 138 371 / 135
100 (38) 388 / 140 404 / 144 407 / 138 433 / 145 404 / 141 406 / 140 400 / 137
105 (41) 415 / 141 438 / 145 434 / 139 462 / 147 435 / 142 430 / 141 428 / 139
110 (43) 444 / 142 464 / 147 465 / 141 494 / 149 465 / 143 464 / 142 458 / 141
115 (45) 475 / 143 495 / 148 497 / 142 527 / 150 499 / 144 495 / 143 484 / 142
Fixed Orifice (RFC)
65 (18) 233 / 121 246 / 126 245 / 123 261 / 134 246 / 126 247 / 125 248 / 124
70 (21) 250 / 124 265 / 129 265 / 126 281 / 136 263 / 128 266 / 128 266 / 126
75 (24) 270 / 128 286 / 132 286 / 129 301 / 138 284 / 131 286 / 131 288 / 130
80 (27) 291 / 131 307 /135 308 / 132 324 / 140 305 / 133 307 / 133 309 / 133
85 (29) 313 / 134 330 / 137 331 / 135 346 / 142 327 / 135 329 / 135 330 / 135
90 (32) 335 / 136 353 / 140 355 / 138 371 / 144 350 / 138 353 / 138 354 / 138
95 (35) 359 / 138 378 / 142 380 / 140 396 / 146 374 / 140 377 / 140 377 / 140
100 (38) 383 / 140 402 / 143 405 / 142 422 / 148 399 / 142 403 / 142 406 / 142
105 (41) 409 / 142 428 / 145 431 / 144 448 / 150 424 / 144 428 / 144 431 / 144
110 (43) 436 / 145 456 / 147 458 / 146 477 / 151 452 / 146 455 / 146 457 / 146
115 (46) 464 / 147 486 / 149 487 / 148 506 / 153 481 / 148 483 / 147 484 / 148
*Values shown are typical pressures; indoor unit match up, indoor air quality equipment, and indoor load will cause the pressures to vary. **Temperature of the air entering the outside coil.
−018 −024 −030 −036 −042 −048 −060
Table 4. HFC−410A Temperature  Pressure (Psig)
°F °C Psig °F °C Psig
−40 −40.0 11.6 60 15.6 170
−35 −37.2 14.9 65 18.3 185
−30 −34.4 18.5 70 21.1 201
−25 −31.7 22.5 75 23.9 217
−20 −28.9 26.9 80 26.7 235
−15 −26.1 31.7 85 29.4 254
−10 −23.3 36.8 90 32.2 274
−5 −20.6 42.5 95 35.0 295 0 −17.8 48.6 100 37.8 317 5 −15.0 55.2 105 40.6 340
10 −12.2 62.3 110 43.3 365 15 −9.4 70.0 115 46.1 391 20 −6.7 78.3 120 48.9 418 25 −3.9 87.3 30 −1.1 96.8 130 54.4 476 35 1.7 107 135 57.2 507 40 4.4 11 8 140 60.0 539 45 7.2 130 50 10.0 142 55 12.8 155
125 51.7 446
145 62.8 573 150 65.6 608
Page 21
13ACX SERIES
Page 22
Removing and Installing Louvers
WARNING
To prevent personal injury, or damage to panels, unit or structure, be sure to observe the following:
While installing or servicing this unit, carefully stow all removed panels out of the way, so that the panels will not cause injury to personnel, nor cause damage to objects or structures nearby, nor will the panels be subjected to damage (e.g., being bent or scratched).
While handling or stowing the panels, consider any weather conditions, especially windy conditions, that may cause panels to be blown around and battered.
ORDER OF REMOVAL AND REINSTALLATION
When removing the unit panels. Remove panel A first, then B, C and finally D. When reinstalling pan­els, reverse that order starting with panel D, C, B and finally A.
REMOVAL
STEP 1
TO REMOVE PANEL, REMOVE MOUNTING SCREWS SECURING PANEL TO THE UNIT.
PANEL A
PANEL B
PANEL A
PANEL C
WARNING
PANEL D
INSTALLATION
TOP CAP
STEP 1
STARTING WITH PANEL D, INSERT PANEL UNDER UNIT TOP CAP LIP AND LIFT SLIGHTLY TO CLEAR SIDE LIP OF PANEL FROM BASE.
SIDE
GROOVE
STEP 2
SLIGHTLY LIFT PANEL A IN ORDER TO CLEAR SIDE LIPS OF PANEL FROM BASE OF UNIT.
STEP 3
TILT PANEL OUT SLIGHTLY AND PULL DOWNWARD TO REMOVE.
REPEAT STEPS 1, 2 AND 3 TO REMOVE PANELS B, C AND FINALLY D.
PANEL A
506374−01 03/10
STEP 2
MOVE PANEL IN TOWARDS UNIT. ALIGN LEFT/RIGHT SIDE LIPS OF PANEL WITH GROOVE INSERTS ALONG LEFT/RIGHT SIDE OF UNIT.
STEP 3
SECURE PANEL, WITH MOUNTING SCREWS.
REPEAT STEPS 1 AND 2 TO INSTALL PANELS C, B AND FINALLY A.
BASE
Page 22
PANEL D
Page 23
System Operation
The outdoor unit and indoor blower will cycle on and off as dictated by demands from the room thermostat. When the thermostat’s blower switch is in the ON position, the indoor blower will operate continuously.
HIGH PRESSURE SWITCH
13ACX units are equipped with a high-pressure switch that is located in the liquid line of the compressor as illustrated in figure on Page 2.
The switch is a Single Pole, Single Throw (SPST), manual−reset switch which is normally closed and removes power from the compressor when discharge pressure rises above factory setting at 590 + 10 psi. The manual−reset switch can be identified by a red cap that is press to preform the reset function.
Maintenance
DEALER
Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch(es). Unit may have multiple power supplies.
Improper installation, adjustment, alteration, service or maintenance can cause personal injury, loss of life, or damage to property.
Installation and service must be performed by a licensed professional installer (or equivalent) or a service agency.
Maintenance and service must be performed by a qualified installer or service agency. At the beginning of each cooling season, the system should be checked as follows:
Outdoor Unit
1. Outdoor unit fan motor is pre−lubricated and sealed. No further lubrication is needed.
2. Visually inspect all connecting lines, joints and coils for evidence of oil leaks.
3. Check all wiring for loose connections.
4. Check for correct voltage at unit (unit operating).
5. Check amp draw on outdoor fan motor.
Motor Nameplate:_________ Actual:__________.
6. Inspect drain holes in coil compartment base and clean if necessary.
NOTE - If insufficient cooling occurs, the unit should be gauged and refrigerant charge should be checked.
NOTE  It may be necessary to flush the outdoor coil more frequently if it is exposed to substances which are corrosive or which block airflow across the coil (e.g., pet urine, cottonwood seeds, fertilizers, fluids that may contain high levels of corrosive chemicals such as salts)
Sea Coast  Moist air in ocean locations can carry salt, which is corrosive to most metal. Units that are located near the ocean require frequent inspections and maintenance. These inspections will determine the necessary need to wash the unit including the outdoor coil. Consult your installing contractor for proper intervals/procedures for your geographic area or service contract.
Indoor Unit
1. Clean or change filters.
2. Lennox blower motors are prelubricated and permanently sealed. No more lubrication is needed.
3. Adjust blower speed for cooling. Measure the pressure drop over the coil to determine the correct blower CFM. Refer to the unit information service manual for pressure drop tables and procedure.
4. Belt Drive Blowers − Check belt for wear and proper tension.
5. Check all wiring for loose connections.
6. Check for correct voltage at unit. (blower operating)
7. Check amp draw on blower motor.
Motor Nameplate:_________ Actual:__________.
Indoor Coil
1. Clean coil if necessary.
2. Check connecting lines, joints and coil for evidence of oil leaks.
3. Check condensate line and clean if necessary.
HOMEOWNER
Cleaning of the outdoor unit’s coil should be performed by a trained service technician. Contact your dealer and set up a schedule (preferably twice a year, but at least once a year) to inspect and service your outdoor unit. The following maintenance may be performed by the homeowner.
CAUTION
Physical contact with metal edges and corners while applying excessive force or rapid motion can result in personal injury. Be aware of, and use caution when working near these areas during installation or while servicing this equipment.
IMPORTANT
Sprinklers and soaker hoses should not be installed where they could cause prolonged exposure to the outdoor unit by treated water. Prolonged exposure of the unit to treated water (i.e., sprinkler systems, soakers, waste water, etc.) will corrode the surface of steel and aluminum parts and diminish performance and longevity of the unit.
Outdoor Coil
Clean and inspect outdoor coil (may be flushed with a water hose). Ensure power is off before cleaning.
Outdoor Coil
The outdoor unit must be properly maintained to ensure its proper operation.
Page 23
13ACX SERIES
Page 24
Please contact your dealer to schedule proper
inspection and maintenance for your equipment.
Make sure no obstructions restrict airflow to the
outdoor unit.
Grass clippings, leaves, or shrubs crowding the unit
can cause the unit to work harder and use more energy.
Keep shrubbery trimmed away from the unit and
periodically check for debris which collects around the unit.
Routine Maintenance
In order to ensure peak performance, your system must be properly maintained. Clogged filters and blocked airflow prevent your unit from operating at its most efficient level.
1. Air Filter  Ask your Lennox dealer to show you
where your indoor unit’s filter is located. It will be either at the indoor unit (installed internal or external to the cabinet) or behind a return air grille in the wall or ceiling. Check the filter monthly and clean or replace it as needed.
2. Disposable Filter  Disposable filters should be
replaced with a filter of the same type and size.
NOTE If you are unsure about the filter required for your system, call your Lennox dealer for assistance.
3. Reusable Filter  Many indoor units are equipped
with reusable foam filters. Clean foam filters with a mild soap and water solution; rinse thoroughly; allow filter to dry completely before returning it to the unit or grille.
NOTE The filter and all access panels must be in place any time the unit is in operation.
4. Electronic Air Cleaner  Some systems are
equipped with an electronic air cleaner, designed to remove airborne particles from the air passing through the cleaner. If your system is so equipped, ask your dealer for maintenance instructions.
5. Indoor Unit  The indoor unit’s evaporator coil is
equipped with a drain pan to collect condensate formed as your system removes humidity from the inside air. Have your dealer show you the location of the drain line and how to check for obstructions. (This would also apply to an auxiliary drain, if installed.)
Thermostat Operation
See the ComfortSense® 7000 thermostat homeowner manual for instructions on how to operate your thermostat.
Preservice Check
If your system fails to operate, check the following before calling for service:
Verify room thermostat settings are correct. Verify that all electrical disconnect switches are ON. Check for any blown fuses or tripped circuit breakers. Verify unit access panels are in place. Verify air filter is clean. If service is needed, locate and write down the unit
model number and have it handy before calling.
Accessories
For update−to−date information, see any of the following publications:
Lennox 13ACX Engineering Handbook Lennox Product Catalog Lennox Price Book
Start−Up and Performance Checklist
Job Name Job no. Date
Job Location City State
Installer City State
Unit Model No. Serial No. Service Technician
Nameplate Voltage
Rated Load Ampacity Compressor Outdoor Fan
Maximum Fuse or Circuit Breaker
Electrical Connections Tight? Indoor Filter clean? Supply Voltage (Unit Off)
Indoor Blower RPM S.P. Drop Over Indoor (Dry) Outdoor Coil Entering Air Temp.
Discharge Pressure Suction Pressure Refrigerant Charge Checked?
Refrigerant Lines: Leak Checked? Properly Insulated? Outdoor Fan Checked?
Service Valves: Fully Opened? Caps Tight? Thermostat
Voltage With Compressor Operating Calibrated? Properly Set?  Level? 
506374−01 03/10
Page 24
Loading...