Lennox 13ACX−018, 13ACX−024, 13ACX−030, 13ACX−036, 13ACX−042 Unit Information

...
Page 1
Corp. 0612−L2
Service Literature
Revised 06−2007
13ACX SERIES UNITS
The 13ACX is a high efficiency residential split−system con­densing unit, which features a scroll compressor and de­signed for R−410A refrigerant. 13ACX units are available in sizes ranging from 1−1/2 through 5 tons. The series is de­signed for use with an expansion valve in the indoor unit. This manual is divided into sections which discuss the major components, refrigerant system, charging procedure, main­tenance and operation sequence. Information contained in this manual is intended for use by qualified service technicians only. All specifications are sub­ject to change.
IMPORTANT
Operating pressures of this R−410A unit are higher than pressures in R−22 units. Always use service equipment rated for R−410A.
13ACX
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, person­al injury or loss of life. Installation and service must be performed by a qualified installer or service agency.
WARNING
Warranty will be voided if covered equipment is re­moved from original installation site. Warranty will not cover damage or defect resulting from: Flood, wind, lightning, or installation and operation in a corrosive atmosphere (chlorine, fluorine, salt, re­cycled waste water, urine, fertilizers, or other damag­ing chemicals).
TABLE OF CONTENTS
General Page 1. . . . . . . . . . . . . . . . . . . . . . . . . . .
Specifications / Electrical Data Page 2. . . . . . . .
I Application Page 3. . . . . . . . . . . . . . . . . . . . . . . .
II Unit Components Page 3. . . . . . . . . . . . . . . . . .
III Refrigeration System Page 6. . . . . . . . . . . . . .
IV Charging Page 7. . . . . . . . . . . . . . . . . . . . . . . .
VI Maintenance Page 13. . . . . . . . . . . . . . . . . . . . .
VII Wiring and Sequence of Operation Page 14.
Page 1
©2006 Lennox Industries Inc.
Page 2
SPECIFICATIONS
p p
p
g
General
Model No. 13ACX−018
Data
Nominal Tonnage (kW) 1.5 (5.3) 2 (7.0) 2.5 (8.8) 3 (10.6) 3.5 (12.3) 4 (14.1) 5 (17.6)
Connections (sweat)
1
Refrigerant (R-410A) furnished 4 lbs. 7 oz.
Liquid line o.d. − in. (mm) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5)
Suction line o.d. − in. (mm) 3/4 (19.1)
(2.01 kg)
Outdoor Coil - sq. ft. (m2)
Net face area
Outer coil 13.22 (1.23) 15.11 (1.40) 13.22 (1.23) 13.22 (1.23) 15.11 (1.40) 16.33 (1.52) 21.0 (1.95)
Inner coil − − − − − − 12.60 (1.17) 12.60 (1.17) 14.40 (1.34) 15.71 (1.46) 20.25 (1.88)
Tube diameter − in. (mm) 5/16 (8) 5/16 (8) 5/16 (8) 5/16 (8) 5/16 (8) 5/16 (8) 5/16 (8)
Number of rows 1 1 2 2 2 2 2
Fins per inch (m) 22 (866) 22 (866) 22 (866) 22 (866) 22 (866) 22 (866) 22 (866)
Outdoor Fan
Diameter − in. (mm) 18 (457) 18 (457) 18 (457) 18 (457) 18 (457) 22 (559) 22 (559)
Number of blades 3 3 4 4 4 4 4
Motor hp (W) 1/5 (149) 1/5 (149) 1/5 (149) 1/5 (149) 1/3 (249) 1/4 (186) 1/4 (186)
Cfm (L/s) 2500 (1180) 2500 (1180) 2450 (1155) 2450 (1155) 2930 (1385) 3830 (1805) 3830 (1805)
Rpm 1100 1100 1100 1100 1100 825 825
Watts 200 200 200 200 310 330 330
Shipping Data − lbs. (kg) 1 package 122 (55) 129 (59) 150 (68) 150 (68) 177 (80) 201 (91) 222 (100)
13ACX−024 13ACX−030 13ACX−036 13ACX−042 13ACX−048 13ACX−060
−2 units
3/4 (19.1) 3/4 (19.1) 7/8 (22.2) 7/8 (22.2) 7/8 (22.2) 1-1/8 (28.6)
4 lbs. 14 oz.
(2.21 kg)
6 lbs. 3 oz.
(2.81 kg)
6 lbs. 7 oz.
(2.92 kg)
8 lbs. 14 oz.
(4.03 kg)
8 lbs. 4 oz.
(3.74 kg)
**10 lbs. 0
oz. (4.54 kg)
ELECTRICAL DATA
Line voltage data − 60 hz − 1ph 208/230V 208/230V 208/230V 208/230V 208/230V 208/230V 208/230V
2
Maximum overcurrent protection (amps) 20 30 30 35 40 50 60
3
Minimum circuit ampacity 12.3 17.9 18.7 21.9 24.1 28.9 34.5
Compressor
Rated load amps 9.0 13.4 14.1 16.6 17.9 21.8 26.2
Power factor .96 .97 .98 .98 .94 .95 .98
Locked rotor amps 48 58 73 79 11 2 117 134
Condenser Fan Motor
Full load amps 1.0 1.0 1.0 1.0 1.9 1.7 1.7
Locked rotor amps 1.9 1.9 1.9 1.9 4.1 3.1 3.1
OPTIONAL ACcESSORIES − must be ordered extra
Compressor Crankcase Heater
Compressor Hard Start Kit
Compressor Low Ambient Cut−Off 45F08 Compressor Sound Cover 69J03 Compressor Time−Off Control 47J27 Freezestat
3/8 in. tubing 93G35 1/2 in. tubing 39H29 5/8 in. tubing 50A93
Hail Guards
Loss of Charge Kit 84M23 Low Ambient Kit 34M72 Mounting Base
Refrigerant Line Sets
L15−41−20, L15−41−30,
L15−41−40, L15−41−50
L15−65−30, L15−65−40,
Field Fabricate
Time Delay Relay Kit 58M81 Unit Stand−Off Kit 94J45
** Charge for −1 units 11 lbs 2 oz NOTE  Extremes of operating range are plus 10% and minus 5% of line voltage.
2
HACR type circuit breaker or fuse.
3
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
93M05
31J20
Factory
10J42
88M91
92M88 92M89 45M56 92M94
69J06 69J07
L15−65−50
1
Refrigerant charge sufficient for 15 ft. (4.6 m) length of refrigerant lines.
Page 2
Page 3
I − APPLICATION
13ACX condensing units are available in 1−1/2, 2, 2 -1/2, 3, 3 -1/2, 4 and 5 ton capacities. All major components (indoor blower and coil) must be matched according to Lennox rec­ommendations for the compressor to be covered under war­ranty. Refer to the Engineering Handbook for approved sys­tem matchups.
II − UNIT COMPONENTS
Unit components are illustrated in figure 1.
13ACX PARTS ARRANGEMENT
COMPRESSOR
CONTACTOR
(K1)
GROUNDING
LUG
CONTROL BOX
DUAL CAPACITOR
(C12)
TIMED OFF
CONTROL.
(OPTION)
OUTDOOR FAN
COMPRESSOR
CAPACITOR
TIMED
OFF
CONTROL
(OPTION)
CONTACTOR
FIGURE 1
A − Control Box (Figure 2)
13ACX units are not equipped with a 24V transformer. All 24 VAC controls are powered by the indoor unit. Refer to wiring diagram.
Electrical openings are provided under the control box cov­er. Field thermostat wiring is made to color-coded pigtail connections.
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
CAUTION
Electrostatic discharge can affect electronic com­ponents. Take precautions during unit installation and service to protect the unit’s electronic controls. Precautions will help to avoid control exposure to electrostatic discharge by putting the unit, the con­trol and the technician at the same electrostatic po­tential. Neutralize electrostatic charge by touching hand and all tools on an unpainted unit surface be­fore performing any service procedure.
FIGURE 2
1 − Compressor Contactor K1
DANGER
Shock Hazard Remove all power at disconnect
before removing access panel. Single phase 13ACX units use single-pole contactors. Potential exists for electrical shock resulting in injury or death. Line voltage exists at all compo­nents (even when unit is not in op­eration).
The compressor is energized by a single−pole contactor lo­cated in the control box. See figure 2. K1 is energized by the indoor thermostat terminal Y1 (24V) when thermostat de­mand is present.
2 − Dual Capacitor C12
The compressor and fan in 13ACX series units use per­manent split capacitor motors. The capacitor is located inside the unit control box (see figure 2). A single dual" capacitor (C12) is used for both the fan motor and the compressor (see unit wiring diagram). The fan side and the compressor side of the capacitor have different MFD ratings. See side of capacitor for ratings.
3 − Timed Off Control TOC (option)
The time delay is electrically connected between thermostat terminal Y and the compressor contactor. Between cycles, the compressor contactor is delayed for 5 minutes ± 2 min- utes but may last as long as 8 minutes. At the end of the delay, the compressor is allowed to energize. When thermo­stat demand is satisfied, the time delay opens the circuit to the compressor contactor coil and the compressor is de−en­ergized.
Page 3
Page 4
B − Compressor
The scroll compressor design is simple, efficient and requires few moving parts. A cutaway diagram of the scroll compressor is shown in figure 3. The scrolls are located in the top of the compressor can and the motor is located just below. The oil lev­el is immediately below the motor.
SCROLL COMPRESSOR
DISCHARGE
SUCTION
FIGURE 3
The scroll is a simple compression concept centered around the unique spiral shape of the scroll and its inherent properties. Figure 4 shows the basic scroll form. Two identical scrolls are mated together forming concentric spiral shapes (figure 5). One scroll remains stationary, while the other is allowed to "orbit" (fig­ure 6). Note that the orbiting scroll does not rotate or turn but merely orbits the stationary scroll.
The counterclockwise orbiting scroll draws gas into the outer crescent shaped gas pocket created by the two scrolls (figure 6
− 1). The centrifugal action of the orbiting scroll seals off the flanks of the scrolls (figure 6 − 2). As the orbiting motion contin­ues, the gas is forced toward the center of the scroll and the gas pocket becomes compressed (figure 6 − 3). When the com­pressed gas reaches the center, it is discharged vertically into a chamber and discharge port in the top of the compressor (figure
5). The discharge pressure forcing down on the top scroll helps seal off the upper and lower edges (tips) of the scrolls (figure 5). During a single orbit, several pockets of gas are compressed simultaneously providing smooth continuous compression.
The scroll compressor is tolerant to the effects of liquid return. If liquid enters the scrolls, the orbiting scroll is allowed to separate from the stationary scroll. The liquid is worked toward the center of the scroll and is discharged. If the compressor is replaced, conventional Lennox cleanup practices must be used.
Due to its efficiency, the scroll compressor is capable of draw­ing a much deeper vacuum than reciprocating compressor s . Deep vacuum operation can cause internal fusite arcing resulting in damaged internal parts and will result in com­pressor failure. Never use a scroll compressor for eva­cuating or pumping−down" the system. This type of dam­age can be detected and will result in denial of warranty claims.
The scroll compressor is quieter than a reciprocating com­pressor, however, the two compressors have much different sound characteristics. The sounds made by a scroll compres­sor do not affect system reliability, performance, or indicate damage.
NOTE − During operation, the head of a scroll compressor may be hot since it is in constant contact with discharge gas.
SCROLL FORM
FIGURE 4
CROSS−SECTION OF SCROLLS
DISCHARGE
DISCHARGE PRESSURE
TIPS SEALED BY DISCHARGE PRESSURE
STATIONARY SCROLL
SUCTION
ORBITING SCROLL
FIGURE 5
Page 4
Page 5
SUCTION
1
SUCTION
POCKET
SUCTION
ORBITING SCROLL
STATIONARY SCROLL
FLANKS SEALED
BY CENTRIFUGAL
MOVEMENT OF ORBIT
SUCTION
FORCE
INTERMEDIATE PRESSURE
GAS
2
CRESCENT
SHAPED
GAS POCKET
SUCTION
3
HIGH PRESSURE GAS
FIGURE 6
C − Condenser Fan Motor
All units use single−phase PSC fan motors which require a run capacitor. In all units, the condenser fan is controlled by the compressor contactor.
ELECTRICAL DATA tables in this manual show specifi­cations for condenser fans used in 13ACX ’s.
Access to the condenser fan motor on all units is gained by removing the four screws securing the fan assembly. Se e figur e 7. The gr ill fan assembly can be re moved fr o m the cabinet as one piece. See figure 8. The condenser fan motor is removed from the fan guard by removing the four nuts found on top of the grill. See figure 8 if condenser fan motor replacement is necessary.
DANGER
Make sure all power is disconnected before beginning electrical service procedures.
Remove
screws
4
ALIGN FAN HUB FLUSH WITH END OF SHAFT
FIGURE 8
DISCHARGE
POCKET
D − Loss of Charge Switch (option)
An auto-reset, single-pole/single-throw low loss of charge switch is located in the suction line. This switch shuts off the compressor when suction pressure drops below the factory setting. The switch is closed during normal operating pres­sure conditions and is permanently adjusted to trip (open) at 25 + 5 psi. The switch automatically resets when suction line pressure rises above 55 + 5 psi.
E − High Pressure Switch
13ACX units are equipped with a high pressure switch that is located in the liquid line. The switch (SPST, manual reset, normally closed) removes power from the compressor con­tactor control circuit when discharge pressure rises above factory setting at 590 + 10 psi.
Remove
screws
FIGURE 7
Page 5
Page 6
III − REFRIGERANT SYSTEM
A − Plumbing
Field refrigerant piping consists of liquid and suction lines from the condensing unit (sweat connections) to the indoor evaporator coil (sweat connections). Use Lennox L15 (sweat) series line sets as shown in table 1.
TABLE 1
Unit
Liquid
Line
Suction
Line
L15 Line Sets
to outdoor coil
service
port cap
Service Valve
(Valve Closed)
stem cap
service
port
insert hex
wrench here
−018
−024
−030
−036
−042
−048
−060
3/8 in.
(10 mm)
3/8 in.
(10 mm)
3/8 in.
(10 mm)
3/4 in.
(19 mm)
7/8 in.
(22 mm)
1−1/8 in.
(29 mm)
L15−41
15 ft. − 50 ft.
(4.6 m − 15 m)
L15−65
15 ft. − 50 ft.
(4.6 m − 15 m)
Field
Fabricated
The liquid line and vapor line service valves (figures 9 and
Each valve is equipped with a service port which has a facto­ry−installed Schrader valve. A service port cap protects the Schrader valve from contamination and serves as the pri­mary leak seal. Service valves are not rebuildable. If a valve
has failed, you must replace it.
To Access Schrader Port:
1 − Remove service port cap with an adjustable wrench. 2 − Connect gauge to the service port. 3 − When testing is complete, replace service port cap. Tight-
en finger tight, then an additional 1/6 turn.
To Open Service Valve:
1 − Remove the stem cap with an adjustable wrench. 2 − Using the adjustable wrench to keep the valve station-
ary, use a service wrench with a hex−head extension to back the stem out counterclockwise as far as it will go.
NOTE − Use a 3/16" hex head extension for 3/8" line sizes or a 5/16" extension for large line sizes.
3 − Replace the stem cap. Tighten finger tight, then tighten
an additional 1/6 turn.
To Close Service Valve:
1 − Remove the stem cap with an adjustable wrench. 2 − Using the adjustable wrench to keep the valve station-
ary, use a service wrench with a hex−head extension to turn the stem clockwise to seat the valve. Tighten the stem firmly.
NOTE − Use a 3/16" hex head extension for 3/8" line sizes or a 5/16" extension for large line sizes.
3 − Replace the stem cap. Tighten finger tight, then tighten an
additional 1/6 turn.
NOTE − Stem cap must be replaced to help prevent valve leakage.
Schrader valve open
to line set when valve is
closed (front seated)
(valve front seated)
to indoor coil
Service Valve
insert hex
wrench here
to outdoor coil
service port
cap
(Valve Open)
service
port
to indoor coil
Schrader
valve
FIGURE 9
stem cap
Vapor Line Ball Valve – 5 Ton Units Only
Vapor line service valves function the same way as the other valves, the difference is in the construction. A ball valve is illustrated in figure 10.
The ball valve is equipped with a service port with a factory− installed Schrader valve. A service port cap protects the Schrader valve from contamination and assures a leak−free seal.
Ball Valve (Valve Open)
Use Adjustable Wrench
To open: rotate Stem Clockwise 90°.
To close: rotate Stem Counter-clockwise 90°.
to outdoor coil
service port
cap
service port
Schrader valve
FIGURE 10
stem cap
stem
ball
(shown open)
to indoor coil
Page 6
Page 7
IV − CHARGING
WARNING
R−410A refrigerant can be harmful if it is inhaled. R−410A refrigerant must be used and recovered re­sponsibly.
Failure to follow this warning may result in personal injury or death.
A − Leak Testing
After the line set has been connected to the indoor and out­door units, check the line set connections and indoor unit for leaks.
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of (CFC’s and HFC’s) as of July 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration my be levied for noncompliance.
WARNING
Fire, Explosion and Personal Safety Hazard. Failure to follow this warning could result in damage, personal injury or death. Never use oxygen to pressurize or purge refrigeration lines. Oxygen, when exposed to a spark or open flame, can cause damage by fire and / or an explosion, that can re­sult in personal injury or death.
WARNING
Danger of explosion! When using a high pressure gas such
as dry nitrogen to pressurize a refriger­ant or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kPa).
Using an Electronic Leak Detector
1 − Connect a cylinder of R−410A to the center port of the
manifold gauge set. Connect manifold gauge to service valve port.
2 − With both manifold valves closed, open the valve on the
R−410A cylinder.
3 − Open the high pressure side of the manifold to allow the
R−410A into the line set and indoor unit. Weigh in a trace amount of R−410A. [A trace amount is a maximum of 2 ounces (57 g) or 3 pounds (31 kPa) pressure.] Close the valve on the R−410A cylinder and the valve on the high pressure side of the manifold gauge set. Disconnect the R−410A cylinder.
4 − Connect a cylinder of nitrogen with a pressure regulat-
ing valve to the center port of the manifold gauge set.
5 − Connect the manifold gauge set high pressure hose to
the vapor valve service port. (Normally, the high pres-
sure hose is connected to the liquid line port; however, connecting it to the vapor port better protects the man­ifold gauge set from high pressure damage.)
6 − Adjust the nitrogen pressure to 150 psig (1034 kPa).
Open the valve on the high side of the manifold gauge set which will pressurize line set and indoor unit.
7 − After a few minutes, open a refrigerant port to ensure
the refrigerant you added is adequate to be detected. (Amounts of refrigerant will vary with line lengths.) Check all joints for leaks. Purge nitrogen and R−410A mixture. Correct any leaks and recheck.
B − Evacuating
Evacuating the system of noncondensables is critical for proper operation of the unit. Noncondensables are defined as any gas that will not condense under temperatures and pressures present during operation of an air conditioning system. Noncondensables and water vapor combine with refrigerant to produce substances that corrode copper pip­ing and compressor parts.
NOTE − This evacuation process is adequate for a new installation with clean and dry lines. If excessive mois­ture is present, the evacuation process may be required more than once.
IMPORTANT
Use a thermocouple or thermistor electronic vacuum gauge that is calibrated in microns. Use an instrument that reads from 50 microns to at least 20,000 microns.
1 − Connect manifold gauge set to the service valve ports :
low pressure gauge to vapor line service valve high pressure gauge to liquid line service valve
2 − Connect micron gauge. 3 − Connect the vacuum pump (with vacuum gauge) to the
center port of the manifold gauge set.
4 − Open both manifold valves and start the vacuum
pump.
Page 7
Page 8
5 − Evacuate the line set and indoor unit to an absolute
pressure of 23,000 microns (29.01 inches of mercury). During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once to deter­mine if there is a rapid rise in absolute pressure. A rap- id rise in pressure indicates a relatively large leak. If this occurs, repeat the leak testing procedure.
NOTE − The term absolute pressure means the total actual pressure within a given volume or system, above the absolute zero of pressure. Absolute pressure in a vacuum is equal to atmospheric pressure minus vacu­um pressure.
(29.01 inches of mercury), close the manifold gauge valves, turn off the vacuum pump and disconnect the manifold gauge center port hose from vacuum pump. Attach the manifold center port hose to a nitrogen cylin­der with pressure regulator set to 150 psig (1034 kPa) and purge the air from the hose with nitrogen. Open the manifold gauge valves to break the vacuum in the line set and indoor unit. Close the manifold gauge valves.
CAUTION
Danger of Equipment Damage. Avoid deep vacuum operation. Do not use compres­sors to evacuate a system. Extremely low vacuums can cause internal arcing and compressor failure. Damage caused by deep vacuum operation will void warranty.
7 − Shut off the nitrogen cylinder and remove the manifold
gauge hose from the cylinder. Open the manifold gauge valves to release the nitrogen from the line set and in­door unit.
8 − Reconnect the manifold gauge to the vacuum pump,
turn the pump on, and continue to evacuate the line set and indoor unit until the absolute pressure does not rise above 500 microns (29.9 inches of mercury) within a 20−minute period after shutting off the vacuum pump and closing the manifold gauge valves.
9 − When the absolute pressure requirement above has
been met, disconnect the manifold hose from the vacu­um pump and connect it to an upright cylinder of R−410A refrigerant. Open the manifold gauge valves to break the vacuum from 1 to 2 psig positive pressure in the line set and indoor unit. Close manifold gauge valves and shut off the R−410A cylinder and remove the manifold gauge set.
C − Charging
This system is charged with R−410A refrigerant which oper­ates at much higher pressures than HCFC−22. The recom­mended check expansion valve is approved for use with R−410A. Do not replace it with a valve that is designed to be used with HCFC−22. This unit is NOT approved for use with coils that include metering orifices or capillary tubes.
Check Indoor Airflow before Charging
NOTE − Be sure that filters and indoor and outdoor coils are clean before testing.
Check indoor airflow using the step procedures as illustrated in figure 11.
Temp. of air entering indoor coil ºF
A
Wet−bulb ºF
53º
BULB
80 24 24 24 23 23 22 22 22 20 19 18 17 16 15 78 23 23 23 22 22 21 21 20 19 18 17 16 15 14 76 22 22 22 21 21 20 19 19 18 17 16 15 14 13 74 21 21 21 20 19 19 18 17 16 16 15 14 13 12
Dry−bulb
72 20 20 19 18 17 17 16 15 15 14 13 12 11 10
70 19 19 18 18 17 17 16 15 15 14 13 12 11 10
57 58 59 60 61 62 63 64 65 66 67 68 69 70
T
C
Drop
19º
All temperatures are expressed in ºF
DT
air flowair flow
INDOOR COIL
Step 1. Determine the desired DTMeasure entering air tempera- ture using dry bulb (A) and wet bulb (B). DT is the intersecting value of A and B in the table (see triangle).
Step 2. Find temperature drop across coilMeasure the coil’s dry bulb entering and leaving air temperatures (A and C). Temperature Drop Formula: (T
Step 3. Determine if fan needs adjustmentIf the difference be-
B
A
72º
B
64º
WET
BULB
DRY BULBDRY
tween the measured T +3º, no adjustment is needed. See examples: Assume DT = 15 and A temp. = 72º, these C temperatures would necessitate stated ac­tions:
Cº T
Drop
53º 19 15 = 4 Increase the airflow 58º 14 15 = −1 (within +3º range) no change 62º 10 15 = −5 Decrease the airflow
Step 4. Adjust the fan speedSee indoor unit instructions to in-
crease/decrease fan speed.
Changing air flow affects all temperatures; recheck temperatures to confirm that the temperature drop and DT are within +3º.
Drop
DT = ºF ACTION
FIGURE 11
) = A minus C.
and the desired DT (T
Drop
DT) is within
Drop
Page 8
Page 9
Pre−Charge Maintenance Checks1.
TABLE 2
Normal Operating Pressures (TXV)
Use this table to perform maintenance checks; it is not a procedure for charging
IMPORTANT
13ACX
5F (5C)*
Expansion Valve (TXV)
65 (18) 244 / 135 249 / 137 241 / 134 253 / 134 250 / 135 240 / 130 247 / 129 242 / 130 70 (21) 262 / 136 268 / 138 259 / 135 274 / 135 268 / 137 257 / 131 265 / 130 266 / 131 75 (24) 281 / 137 288 / 138 279 / 136 293 / 136 288 / 138 278 / 132 286 / 131 286 / 132 80 (27) 302 / 138 309 / 140 300 / 137 315 / 137 310 / 139 299 / 133 310 / 132 309 / 133 85 (29) 323 / 139 331 / 140 322 / 138 338 / 139 332 / 140 323 / 134 330 / 132 332 / 134 90 (32) 346 / 141 355 / 142 345 / 140 361 / 139 356 / 140 344 / 135 353 / 133 357 / 135
95 (35) 369 / 142 379 / 143 369 / 141 385 / 141 381 / 141 369 / 136 375 / 134 381 / 136 100 (38) 394 / 143 402 / 144 393 / 142 410 / 142 406 / 143 394 / 137 400 / 136 407 / 137 105 (41) 417 / 145 430 / 145 418 / 143 436 / 143 432 / 143 418 / 139 426 / 137 433 / 138 110 (43) 445 / 146 457 / 146 445 / 144 463 / 145 459 / 145 446 / 140 451 / 139 459 / 140 115 (45) 476 / 148 485 / 147 474 / 145 491 / 146 490 / 145 477 / 141 482 / 141 488 / 141
Fixed Orifice (RFC)
65 (18) 244 / 135 244 / 125 243 / 116 252 / 129 250 / 135 248 / 127 248 / 123 255 / 126
70 (21) 262 / 136 263 / 128 262 / 120 271 / 131 268 / 137 266 / 130 269 / 127 274 / 128
75 (24) 281 / 137 282 / 131 283 / 124 290 / 133 288 / 138 284 / 132 295 / 131 294 / 131
80 (27) 302 / 138 303 / 134 305 / 128 312 / 136 310 / 139 305 / 134 315 / 133 317 / 134
85 (29) 323 / 139 326 / 137 328 / 132 334 / 139 332 / 140 325 / 137 334 / 135 339 / 136
90 (32) 346 / 141 347 / 138 351 / 135 356 / 141 356 / 140 347 / 139 359 / 138 362 / 138
95 (35) 369 / 142 372 / 141 376 / 139 380 / 143 381 / 141 371 / 141 384 / 140 386 / 140 100 (38) 394 / 143 396 / 143 401 / 142 405 / 145 406 / 143 394 / 143 409 / 142 413 / 142 105 (41) 417 / 145 421 / 145 427 / 145 429 / 147 432 / 143 418 / 144 434 / 144 435 / 144 110 (43) 445 / 146 449 / 147 454 / 147 456 / 148 459 / 145 445 / 146 462 / 145 462 / 146 115 (46) 476 / 148 479 / 149 482 / 149 483 / 151 490 / 145 472 / 147 489 / 146 490 / 148
*Values shown are typical pressures; indoor unit match up, indoor air quality equipment, and indoor load will cause the pressures to vary. **Temperature of the air entering the outside coil.
−018 −024 −030 −036 −042 −048
Liquid / Vapor Liquid / Vapor Liquid / Vapor Liquid / Vapor Liquid / Vapor Liquid / Vapor
the system. Minor variations in these pressures may be due to differences in installations. Significant deviations could mean that the system is not properly charged or that a problem exists with some component in the system.
−060−1
Liquid / Vapor
−060−2
Liquid / Vapor
Page 9
Page 10
Determining Charge Method1.
START: Determine how refrigerant is metered
WHEN TO CHARGE?
Warm weather best Can charge in colder weather
CHARGE METHOD? Determine by:
Metering device type Outdoor ambient temperature
REQUIREMENTS:
Sufficient heat load in structure Indoor temperature between 70-80ºF
(21−26ºC)
Manifold gauge set connected to unit Thermometers:
− to measure outdoor ambient temperature
− to measure liquid line temperature
− to measure vapor line temperature
(18.3ºC) and
APPROACH OR
SUBCOOLING
TXV
65ºF
Above
64ºF
(17.7ºC) and
Below
WEIGH-IN
FIGURE 12
Which
metering
device?
40ºF
(4.4ºC) and
Above
RFC
39ºF
(3.8ºC) and
Below
WEIGH-INSUPERHEAT
Weigh in Charge
1.Recover the refrigerant from the unit.
2.Conduct leak check; evacuate as previously outlined.
3.Weigh in the unit nameplate charge plus any charge re­quired for linesets differences from 15 feet. (If weighing facilities are not available, use the subcooling method.)
TABLE 3
Refrigerant Charge per Line Set Lengths
Liquid Line Set
Diameter
3/8 in. (9.5 mm) 3 ounce per 5 ft. (85 g per 1.5 m)
NOTE − *If line length is greater than 15 ft. (4.6 m), add this amount. If line length is less than 15 ft. (4.6 m), subtract this amount.
Ounces per 5 feet (g per 1.5 m) adjust
from 15 feet (4.6 m) line set*
Page 10
Page 11
Superheat RFC Charge
START: Measure outdoor ambient temperature
USE WEIGH-IN METHOD
Weigh-in or remove refriger­ant based upon line length
If refrigerant added or
removed, retest to confirm that unit is
properly charged
If value is greater than shown, add refrigerant; if less than shown, remove refrigerant.
NOTE − Do not at­tempt to charge sys­tem where a dash ap­pears, system could be overcharged. Su­perheat is taken at va­por line service port. Vapor line superheat must never be less than 5ºF at the vapor line service port.
ºF* 50 52 54 56 58 60 62 64 66 68 70 72 74 76 40 15 18 20 23 26 29 32 34 38 41 43 46 48 51 45 13 16 18 21 24 27 30 33 36 39 41 44 46 49 50 11 14 16 19 22 25 28 31 34 37 39 42 44 47 55 9 12141720232730333638404244 60 7 10121518212427303335384043 65 - 6 10 13 16 19 21 24 27 30 33 36 38 41 70 - - 7 1013161921242730333639 75 - - - 6 9 121518212428313437 80 - - - - 5 8 12 15 18 21 25 28 31 35 85 ------811151922263033 90 - - - - - - 5 9 13 16 20 24 27 31 95 -------6101418222529 100 - - - - - - - - 8 12 16 21 24 28 105 --------5913172226 110 ---------611152025 115 ----------8141824
* Dry−bulb temperature (ºF) of entering outdoor ambient air.
BELOW
SHº (Superheat) Values (+/−5ºF)
Wet Bulb (air entering indoor coil)
Ambient 40ºF
Outdoor
(4ºC)?
ABOVE
1.. Confirm proper airflow across coil using figure
11.
2.. Check liquid and vapor line pressures and compare unit pressures with Normal Operating Pressures listed in table 2.
(Note: Table 2 is a general guide. Expect minor pressures variations. Significant differences may mean improper charge or other system problem.)
3.. Use SUPERHEAT to correctly charge unit or to verify the charge is correct.
SUPERHEAT METHOD
4.. Set thermostat to call for heat (must have a cooling load between 70-80ºF (21−26ºC)
5.. Connect gauge set
6.. When heat demand is satisfied, set thermostat to call for cooling
7.. Allow temperatures and pressures to stabilize
8.. Measure the vapor line pressure and use the use value to determine saturation temperature (table 4 on page 11) SATº =_________
9.. Record vapor line temperature VAPº =_________
10.. Subtract to determine superheat (SHº):
11.. VAPº − _____ SATº ______ = SHº______
12.. Record the wet bulb temperature (air entering indoor coil) WB =__________
13.. Record outdoor ambient temperature
14.. Compare results with table to the left
Table 4
HFC−410A Temperature (°F) − Pressure (Psig)
°F Psig °F Psig °F Psig °F Psig °F Psig °F Psig °F Psig °F Psig
32 100.8 48 137.1 63 178.5 79 231.6 94 290.8 11 0 365.0
125 445.9
33 102.9 49 139.6 64 181.6 80 235.3 95 295.1 111 370.0 126 451.8 142 552.3
34 105.0 50 142.2 65 184.3 81 239.0 96 299.4 11 2 375.1 127 457.6 143 559.1
35 107.1 51 144.8 66 187.7 82 242.7 97 303.8 11 3 380.2 128 463.5 144 565.9
36 109.2 52 147.4 67 190.9 83 246.5 98 308.2 11 4 385.4 129 469.5 145 572.8
37 111.4 53 150.1 68 194.1 84 250.3 99 312.7 115 390.7 130 475.6 146 579.8
38 113.6 54 152.8 69 197.3 85 254.1 100 317.2 11 6 396.0 131 481.6 147 586.8
39 115.8 55 155.5 70 200.6 86 258.0 101 321.8 11 7 401.3 132 487.8 148 593.8
40 118.0 56 158.2 71 203.9 87 262.0 102 326.4 11 8 406.7 133 494.0 149 601.0
41 120.3 57 161.0 72 207.2 88 266.0 103 331.0 11 9 412.2 134 500.2 150 608.1
42 122.6 58 163.9 73 210.6 89 270.0 104 335.7 120 417.7 135 506.5 151 615.4
43 125.0 59 166.7 74 214.0 90 274.1 105 340.5 121 423.2 136 512.9 152 622.7
44 127.3 60 169.6 75 217.4 91 278.2 106 345.3 122 428.8 137 519.3 153 630.1
45 129.7 61 172.6 76 220.9 92 282.3 107 350.1 123 434.5 138 525.8 154 637.5
46 132.2 62 175.4 77 224.4 93 286.5 108 355.0 124 440.2 139 532.4 155 645.0
47 134.6 78 228.0 109 360.0 140 539.0
141 545.6
Page 11
Page 12
Approach TXV Charge
START: Measure outdoor ambient temperature
DO NOT CHARGE UNIT
USE WEIGH-IN METHOD
(Results of charging at low
Weigh-in or remove refriger-
temperatures not reliable)
ant based upon line length
If value is greater than shown (high approach), add refrigerant; if less than shown (liquid temp too close to ambient temp, low approach), remove refrigerant.
APPº (Approach) Values(F:+/−1.0°; [C: +/−0.6°])
ºF (ºC)* −018 −024 −030 −036 −042 −048 −060 Any 8 (4.4) 8 (4.5) 9 (5.0) 15 (8.3) 10 (5.6) 6 (3.3) 9 (5.0) *Temperature of air entering outdoor coil
BELOW
Outdoor Am-
bient 65ºF
(18ºC)?
If refrigerant added or
removed, retest to confirm that unit is
properly charged
ABOVE
1.. Confirm proper airflow across coil using figure
11.
2.. Check liquid and vapor line pressures and compare unit pressures with Normal Operat­ing Pressures listed in table 2 on page 9.
(Table 2 is a general guide. Expect minor pressures variations. Significant differences may mean improper charge or other system problem.)
3.. Use APPROACH to correctly charge unit or to verify the charge is correct.
APPROACH METHOD
4.. Set thermostat to call for heat (must have a cooling load between 70-80ºF (21−26ºC)
5.. Connect gauge set
6.. When heat demand is satisfied, set thermo­stat to call for cooling
7.. Allow temperatures and pressures to stabilize
8.. Record outdoor ambient temperature AMBº =_________
9.. Record line temp. LIQº = __________
10.. Subtract to determine approach (APPº):
11.. LIQº_____ − AMBº _____ = APPº_____
12.. Compare results with table to the left
Subcooling TXV Charge
START: Measure outdoor ambient temperature
DO NOT CHARGE UNIT
USE WEIGH-IN METHOD
(Results of charging at low
Weigh-in or remove refriger-
temperatures not reliable)
ant based upon line length
If refrigerant added or
removed, verify
charge using the
approach method
If value is greater than
shown, remove refrigerant; if less than shown, add refrigerant
SCº (Subcooling) Values (F:+/−1.0°; [C: +/−0.6°])
ºF (ºC)* −018 −024 −030 −036 −042 −048 −060 Any 8 (4.4) 8 (4.4) 7 (3.8) 4 (2.2) 8 (4.4) 10 (5.6) 7 (3.9) *Temperature of air entering outdoor coil
BELOW
BLOCK OUTDOOR COIL [sometimes necessary with lower temperatures] Use cardboard or plastic sheet to restrict the airflow through the outdoor coil to achieve pres­sures from 325−375 psig (2240−2585 kPa). Higher pressures are needed to check charge. Block equal sections of air intake panels and move coverings sideways until the liquid pres­sure is in the above noted ranges.
Outdoor Am-
bient 65ºF
(18ºC)?
ABOVE
1.. Confirm proper airflow across coil using figure
11.
2.. Check liquid and vapor line pressures and compare unit pressures with Normal Operat­ing Pressures listed in table 2.
(Table 2 is a general guide. Expect minor pres­sures variations. Significant differences may mean improper charge or other system prob­lem.)
3.. Use SUBCOOLING to correctly charge unit or to verify the charge is correct.
SUBCOOLING METHOD
4.. Set thermostat to call for heat (must have a
cooling load between 70-80ºF (21−26ºC)
5.. Connect gauge set
6.. Measure outdoor ambient temperature
7.. When heat demand is satisfied, set thermo-
stat to call for cooling
8.. Allow temperatures and pressures to stabilize
[NOTE − IF NECESSARY, block outdoor coil to maintain 325 − 375 psig]
9.. Record line temp. LIQº = ______
10.. Measure liquid line pressure and use the val­ue to determine saturation temperature (table 4 on page 11) SATº = ______
11.. Subtract to determine subcooling (SCº):
12.. SATº_____ − LIQº _____ = SCº _____
13.. Compare results with table to the left.
+
Page 12
Page 13
V − MAINTENANCE
WARNING
Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at discon­nect switch(es). Unit may have multiple power supplies.
Maintenance and service must be performed by a qualified installer or service agency. At the beginning of each cooling season, the system should be checked as follows:
1.Make sure power is off before cleaning. Clean and inspect outdoor coil. The coil may be flushed with a water hose.
The outdoor coil is protected by an inner mesh screen and a wire cage (see figure 13). If debris has collected between the mesh screen and the coil and cannot be dislodged by spraying unpressurized water from inside coil surface to the outside, the mesh may be removed by first removing the top of the unit which will allow for re­moval of the wire cage.
Then, using pliers to grip the head of the push pins, pull straight out to extract the push pins along one side of the coil. If necessary, remove the push pins along the back of the unit; it is usually unnecessary to fully remove the inner mesh screen.
Drape the mesh screen back and wash the coil. When all the debris has been removed from the coil, reinstall the mesh screen by positioning it in its original position and reinserting the push pin. No tool is required to push the pin back into the same slot in the fins.
If the push pin is loose and tends not to stay in place, brush the fins with a fin brush (22 fins/in). Line up the push pin a couple fins to the right or left of the original hole and re−insert the pin.
2.Outdoor fan motor is prelubricated and sealed. No further lubrication is needed.
3.Visually inspect connecting lines and coils for evidence of oil leaks.
4.Check wiring for loose connections.
5.Check for correct voltage at unit (unit operating).
6.Check amp−draw outdoor fan motor.
Unit nameplate _________ Actual ____________ .
NOTE − If owner reports insufficient cooling, the unit should be gauged and refrigerant charge checked. See refrigerant charging section.
9 pins used on
−048 and −060; 6 pins all others
PUSH PIN
MESH SCREEN
Figure 13
Indoor Coil
1.Clean coil, if necessary.
2.Check connecting lines and coils for signs of oil leaks.
3.Check the condensate pan line and clean if necessary.
Indoor Unit
1.Clean or change filters.
2.Adjust blower speed for cooling. The pressure drop over the coil should be measured to determine the correct blower CFM. Refer to the unit information service manual for pressure drop tables and procedure.
3.Check all wiring for loose connections
4.Check for correct voltage at unit (blower operating).
5.Check amp−draw on blower motor. Unit nameplate_________ Actual ____________.
Page 13
Page 14
VI − WIRING DIAGRAMS AND SEQUENCE OF OPERATION
13ACX
NOTE− The thermostat used may be electromechanical or electronic. NOTE− Transformer in indoor unit supplies power (24 VAC) to the thermostat and outdoor unit controls.
COOLING:
1− Cooling demand initiates at Y1 in the thermostat. 2− 24VAC from indoor unit (Y1) energizes the TOC timed off control (if used) which energizes contactor K1. 3− K1-1 N.O. closes, energizing compressor (B1) and outdoor fan motor (B4). 4− Compressor (B1) and outdoor fan motor (B4) begin immediate operation..
END OF COOLING DEMAND:
5− Cooling demand is satisfied. Terminal Y1 is de-energized and the TOC( if used) begins its off cycle timing. 6− Compressor contactor K1 is de-energized. 7− K1-1 opens and compressor (B1) and outdoor fan motor (B4) are de-energized and stop immediately.
Page 14
Loading...