Lennox 13ACD-018-230, 13ACD-024-230, 13ACD-030-230, 13ACD-036-230, 13ACD-042-230 Installation Instructions Manual

...
Page 1
INSTALLATION INSTRUCTIONS
13ACD Split System Air Conditioner
with Dry Nitrogen Holding Charge
This manual must be left with the homeowner for future reference.
Table of Contents
General ........................................................................2
Unit Dimensions - inches (mm) ...................................2
Parts Arrangement.......................................................2
Shipping and Packing List ...........................................3
Torque Requirements ..................................................3
Operating Gauge Set and Service Valves ................... 3
Recovering Refrigerant from Existing System .............4
New Outdoor Unit Placement ......................................5
Replacement Line Set .................................................6
Brazing Connections ...................................................7
Removing Existing Metering Device and Flushing Line
Set and Indoor Coil ....................................................10
Installing New Indoor Metering Device ...................... 11
Leak Test Line Set and Indoor Coil ............................12
Evacuating Line Set, Indoor Coil and Outdoor Unit ...13
Electrical ....................................................................14
Servicing Outdoor Unit Delivered Void of Nitrogen
Charge .......................................................................15
Maintenance ..............................................................15
CAUTION
Improper selection of a matching indoor unit and a matching metering device, improper installation, adjustment, alteration, service or maintenance may void
the warranty. The qualied installer or agency must use
factory-authorized kits or accessories when modifying this products. Refer to the individual instructions packaged with the kits or accessories when installing.
WARNING
Installation or repairs made by unqualied persons can
result in hazards to you and others. Installation MUST conform with local building codes or, in the absence of local codes, with the National Electrical Code NFPA 70/ANSI C1-1993 or current edition and Canadian Electrical Code Part 1 CSA C22.1.
215 Metropolitan Drive
West Columbia, SC 29170
NOTE
This unit is factory-charged with dry nitrogen. The unit is intended for installation in existing HCFC-22 systems. Carefully follow all installation procedures. Open both service valves to evacuate system. This
unit is constructed without a factory installed lter drier. Field-provided liquid line lter drier should be installed
per Figure 6A.
NOTE
These instructions are intended as a general guide and do not supersede national, state or local codes in any way.
WARNING
This product contains a chemical known to the State of California to cause cancer, birth defects or other reproductive harm.
506694-01 Issue 1720 Page 1 of 16
Save these instructions for future reference
Page 2
General
SIDE VIEW
A
A
The 13ACD air conditioner, which will also be referred to in this instruction as the outdoor unit, uses HCFC-22 refrigerant. This outdoor unit is intended as a replacement outdoor component for use in residential systems which include an existing indoor coil which is functioning properly. It is NOT intended for new installations.
This outdoor unit is:
shipped from the factory with nitrogen holding charge that must be purged from the unit;
Unit Dimensions - inches (mm)
designed for use with HCFC-22 refrigerant only;
designed for use in systems that use either a RFC
device (orice) included with outdoor unit or thermal
expansion valve (TXV). See the 13ACD product
specication sheet for approved xed orice sizes and
expansion valve kit match ups.
Important — The air conditioning unit must have properly matched system components including indoor unit and refrigerant metering device. Mismatched equipment may have an impact on the operation, performance, reliability, and warranty of the air conditioning unit.
OUTDOOR COIL FAN
COMPRESSOR
Discharge Air
B
SIDE VIEW
SUCTION AND LIQUID LINE
OPTIONAL UNIT STANDOFF KIT
CONNECTIONS
(4) (FIELD-INSTALLED)
Model A B
13ACD-018-230 24-1/4 (616) 25-1/4 (641)
13ACD-024-230 24-1/4 (616) 25-1/4 (641)
13ACD-030-230 24-1/4 (616) 33-1/4 (845)
13ACD-036-230 24-1/4 (616) 33-1/4 (845)
13ACD-042-230 28-1/4 (718) 29-1/4 (743)
13ACD-048-230 28-1/4 (718) 37-1/4 (946)
13ACD-060-230 28-1/4 (718) 33-1/4 (845)
Parts Arrangement
CONTROL BOX
GROUND LUG
SINGLE -POLE
CONTACTOR (K1)
Figure 1. Typical Unit Parts Arrangement
NOTE: PLUMBING LAYOUT
TWEEN MODEL SIZES.
DUAL RUN CAPACITO R (C12)
LIQUID LINE
SERVICE VALVE
SUCTION LINE SERVICE VALVE
506694-01Issue 1720Page 2 of 16
Page 3
Shipping and Packing List
Operating Gauge Set and Service Valves
Check the unit for shipping damage. If damaged, or if parts are missing, immediately contact the last shipping carrier.
1 — Assembled 13ACD unit
1 — Refrigerant ow control (RFC) kit (orice) (see Table 3
for a complete list of available xed orice kits)
Torque Requirements
When servicing or repairing HVAC components, ensure the fasteners and caps are appropriately tightened. Table 1 lists torque values for fasteners.
Parts Recommended Torque
Service valve cap 8 ft. lb. 11 NM
Sheet metal screws 16 in. lb. 2 NM
Machine screws #10 28 in. lb. 2 NM
Compressor bolts 90 in. lb. 10 NM
Gauge port seal cap 8 ft. lb. 11 NM
Table 1. Torque Requirements
Using Manifold Gauge Set
When checking the system charge, only use a manifold
gauge set that features low-loss anti-blow back ttings.
Operating Service Valves
The liquid and vapor line service valves are used for
removing refrigerant, ushing, leak testing, evacuating,
checking charge and charging.
Each valve is equipped with a service port which has a factory-installed valve core. Figure 2 provides information on accessing and operating both angle and ball-type service valves.
IMPORTANT
To prevent stripping of the various caps used, the
appropriately sized wrench should be used and tted
snugly over the cap before tightening.
Operating Angle-Type Service Valve:
1. Remove stem cap with an appropriately sized wrench.
2. Use a service wrench with a hex-head extension (3/16” for liquid line valve sizes and 5/16” for vapor line valve sizes) to back the stem out counterclockwise as far as it will go.
TO INDOOR
TO OUTDOOR
SERVICE PORT
UNIT
UNIT
CAP
ANGLE-TYPE SERVICE VALVE
When service valve stem is OPEN, the service port is open to line set, indoor and outdoor unit.
Operating Ball-Type Service Valve:
1. Remove stem cap with an appropriately sized wrench.
2. Use an appropriately sized wrenched to open. To open valve, rotate stem counterclockwise 90°. To close rotate stem clockwise 90°.
TO OPEN ROTATE STEM COUNTERCLOCKWISE 90°.
TO CLOSE ROTATE STEM CLOCKWISE 90°.
SERVICE PORT
SERVICE PORT
SERVICE PORT
CORE
CAP
TO OUTDOOR
UNIT
TO INDOOR UNIT
BALL (SHOWN
CLOSED)
VALV E STEM
STEM CAP
(BACK-SEATED OPENED)
SERVICE PORT CORE
(VALVE STEM SHOWN OPEN) INSERT HEX WRENCH HERE
STEM
CAP
ANGLE-TYPE SERVICE VALV E
(FRONT-SEATED CLOSED)
(VALVE STEM SHOWN CLOSED) INSERT HEX WRENCH HERE
When service valve stem is
CLOSED, the service port is
open to the line set and indoor
To Access Service Port:
A service port cap protects the service port core from contamination and serves as the primary leak seal.
1. Remove service port cap with an appropriately sized wrench.
2. Connect gauge set to service port.
3. When testing is completed, replace service port cap and tighten as follows:
With torque wrench: Finger tighten and torque cap per table 1.
Without torque wrench: Finger tighten and use an appropriately sized wrench to turn an additional 1/6 turn clockwise.
Reinstall Stem Cap:
Stem cap protects the valve stem from damage and serves as the primary seal. Replace the stem cap and tighten as follows:
With Torque Wrench: Finger tighten and then torque cap per table 1.
Without Torque Wrench: Finger tighten and use an appropriately sized wrench to turn an additional 1/12 turn clockwise.
unit.
10
9
10
9
1/6 TURN
12
1
11
8
7
11
8
7
6
1/12 TURN
12
6
2
3
4
5
1
2
3
4
5
Figure 2. Operating Angle and Ball-Type Service Valves
506694-01 Issue 1720 Page 3 of 16
Page 4
Recovering Refrigerant from Existing System
RECOVERING
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFCs, HCFCs and HFCs) as of July 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for noncompliance.
REFRIGERANT FROM SYSTEM
DISCONNECT POWER
Disconnect all power to the existing outdoor unit at the service
1
disconnect switch or main fuse box/breaker panel.
SERVICE
DISCONNECT
SWITCH
CONNECT MANIFOLD GAUGE SET
Connect a gauge set, clean recovery cylinder and a recovery
2
machine to the service ports of the existing unit. Use the instructions provided with the recovery machine to make the connections.
MANIFOLD GAUGES
RECOVERY MACHINE
LOW
HIGH
RECOVERING REFRIGERANT
Remove existing refrigerant using one of the following procedures:
3
IMPORTANT — Some system configurations may contain higher than normal refrigerant charge due to either large internal coil volumes,
and/or long line sets.
METHOD 1:
Use this method if the existing outdoor unit is not equipped with shut-off valves, or if the unit is not operational and you plan to use the existing refrigerant to flush the system.
Remove all refrigerant from the existing system. Check gauges after shutdown to confirm that the entire system is completely void of refrigerant.
METHOD 2:
Use this method if the existing outdoor unit is equipped with manual shut-off valves, and you plan to use new refrigerant to flush the system.
The following devices could prevent full system charge recovery into the outdoor unit
Outdoor unit's high or low-pressure switches (if applicable) when tripped can cycle the compressor OFF.
Compressor can stop pumping due to tripped internal pressure relief valve.
Compressor has internal vacuum protection that is designed to unload the scrolls (compressor stops pumping) when the pressure ratio meets a certain value or when the suction pressure is as high as 20 psig. (Compressor suction pressures should never be allowed Prolonged operation at low suction pressures will result in overheating of the scrolls and permanent damage to the scroll tips, drive bearings and internal seals.)
Once the compressor cannot pump down to a lower pressure due to one of the above system conditions, shut off the vapor valve. Turn OFF the main power to unit and use a recovery machine to recover any refrigerant left in the indoor coil and line set.
Perform the following task:
A Start the existing system in the cooling mode and close the liquid line valve. B Use the compressor to pump as much of the existing HCFC-22 refrigerant into the outdoor unit until the outdoor system is full. Turn the outdoor unit
main power OFF and use a recovery machine to remove the remaining refrigerant from the system.
NOTE — It may be necessary to bypass the low pressure switches (if equipped) to ensure complete refrigerant evacuation.
C When the low side system pressures reach 0 psig, close the vapor line valve.
D Check gauges after shutdown to confirm that the valves are not allowing refrigerant to flow back into the low side of the system.
:
CLEAN RECOVERY CYLINDER
OUTDOOR UNIT
to go into a vacuum.
Figure 3. Refrigerant Recovery
506694-01Issue 1720Page 4 of 16
Page 5
New Outdoor Unit Placement
DETAIL A
DETAIL B
Remove existing outdoor unit prior to placement of new outdoor unit. See Unit Dimensions on Page 2 for sizing mounting slab, platforms or supports. Refer to Figure 4 for mandatory installation clearance requirements.
CLEARANCE ON ALL SIDES — INCHES (MILLIMETERS)
6 (152)
ACCESS PANEL
NOTES:
Clearance to one of the other three
12 (305)
36 (914)
30 (762)
LINE SET CONNECTIONS
sides must be 36 inches (914mm).
Clearance to one of the remaining two sides may be 12 inches (305mm) and the final side may be 6 inches (152mm).
MINIMUM CLEARANCE BETWEEN
TWO UNITS
24 (610)
MINIMUM CLEARANCE
ABOVE UNIT
48 (1219)
Install unit away from windows .
Figure 4. Installation Clearances
Install unit level or, if on a slope, maintain slope tolerance of 2 degrees (or 2 inches per 5 feet [50 mm per 1.5 m]) away from building structure.
Two 90° elbows installed in line set will reduce line set vibration.
MOUNTING SLAB MUST SLOPE AWAY FROM BUILDING.
Figure 5. Placement and Slab Mounting
STRUCTURE
DISCHARGE AIR
GROUND LEVEL
506694-01 Issue 1720 Page 5 of 16
Page 6
Positioning Considerations
NOTE
CAUTION
In order to avoid injury, take proper precaution when lifting heavy objects.
CAUTION
Physical contact with metal edges and corners while applying excessive force or rapid motion can result in personal injury. Be aware of, and use caution when working near these areas during installation or while servicing this equipment.
Consider the following when positioning the unit:
Some localities are adopting sound ordinances based on the unit’s sound level registered from the adjacent property, not from the installation property. Install the unit as far as possible from the property line.
When possible, do not install the unit directly outside a window. Glass has a very high level of sound transmission. For proper placement of unit in relation to a window, see the provided illustration in Figure 5.
Placing Outdoor Unit on Slab
When installing a unit at grade level, the top of the slab should be high enough above the grade so that water from higher ground would not collect around the unit as illustrated in Figure 5.
Slab may be level or have a slope tolerance away from the building of not more than two degrees, or 2 inches per 5 feet (51 mm per 1524 mm) as illustrated in Figure 5.
Installing Outdoor Unit on Roof
Install the unit at a minimum of 4 inches (102 mm) above the surface of the roof. Ensure the weight of the unit is properly distributed over roof joists and rafters. Redwood or steel supports are recommended.
Roof Damage!
This system contains both refrigerant and oil. Some
rubber roong material may absorb oil and cause the
rubber to swell when it comes into contact with oil. The rubber will then bubble and could cause leaks. Protect the roof surface to avoid exposure to refrigerant and oil during service and installation. Failure to follow this notice could result in damage to roof surface.
Replacement Line Set
This section provides information on replacement of existing line set. If replacement line set is not required, then proceed to Brazing Connections on Page 7.
Refrigerant Line Set
Field refrigerant piping consists of liquid and suction lines from the outdoor unit (braze connections) to the indoor unit
coil (are or braze connections). If replacing line set, use brazed, non-are line set, or eld-fabricated refrigerant
lines as listed in Table 2.
Existing line set should meet size requirements listed in Table 2.
NOTE: When installing refrigerant lines longer than 50 feet, contact technical support for assistance. To obtain the correct information from manufacturer, be sure to communicate the following points:
Model (13ACD) and size of unit (e.g. -060).
Line set diameters for the unit being installed as listed in Table 2 and total length of installation.
Number of elbows and if there is a rise or drop of the piping.
Model
13ACD-018-230
13ACD-024-230
13ACD-030-230
13ACD-036-230
13ACD-048-230
13ACD-060-230 3/8 in. (10 mm) 1-1/8 in. (29 mm) 3/8 in. (10 mm) 1-1/8 in. (29 mm)
3/8 in. (10 mm) 3/4 in. (19 mm) 3/8 in. (10 mm) 3/4 in. (19 mm)
3/8 in. (10 mm) 7/8 in. (22 mm) 3/8 in. (10 mm) 7/8 in. (22 mm)13ACD-042-230
Field Connections Recommended Line Set
Liquid Line Suction Line Liquid Line Suction Line Line Sets
Table 2. Refrigerant Line Set - inches (mm)
Field-fabricated
brazed, non are
506694-01Issue 1720Page 6 of 16
Page 7
Brazing Connections
Use the procedures outline in Figure 6A and Figure 6B for brazing line set connections to service valves.
WARNING
When using a high pressure gas such as dry nitrogen to pressurize a refrigeration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kPa).
WARNING
Danger of re. Bleeding the refrigerant
charge from only the high side may result in pressurization of the low side shell and suction tubing. Application of a brazing torch to a pressurized system may result in ignition of the refrigerant and oil mixture
- Check the high and low pressures before applying heat.
IMPORTANT
Use silver alloy brazing rods with 5% minimum silver alloy for copper-to-copper brazing. Use 45% minimum alloy for copper-to-brass and copper-to-steel brazing.
CAUTION
Brazing alloys and ux contain materials which are
hazardous to your health.
Avoid breathing vapors or fumes from brazing operations. Perform operations only in well-ventilated areas.
Wear gloves and protective goggles or face shield to protect against burns.
Wash hands with soap and water after handling brazing
alloys and ux.
IMPORTANT
Allow braze joint to cool before removing the wet rag from the service valve. Temperatures above 250ºF can damage valve seals.
506694-01 Issue 1720 Page 7 of 16
Page 8
CUT AND DEBUR
Cut ends of the refrigerant lines square (free from nicks or dents)
1
and debur the ends. The pipe must remain round. Do not crimp end of the line.
CUT AND DEBUR
LINE SET SIZE MATCHES
SERVICE VA LVE CONNECTION
SERVICE VA LVE
COPPER TUBE
REDUCER
CONNECTION
STUB
LINE SET SIZE IS SMALLER
THAN CONNECTION
REFRIGERANT LINE
DO NOT CRIMP SERVICE VALV E
CONNECTOR WHEN PIPE IS
SMALLER THAN CONNECTION
CAP AND CORE REMOVAL
Remove service cap and core from both the
2
vapor and liquid line service ports.
SERVICE PORT
CAP
SERVICE
PORT CORE
LIQUID LINE SERVICE
VALV E
SUCTION / VAPOR LINE
SERVICE VA LVE
ATTACH THE MANIFOLD GAUGE SET FOR BRAZING LINE SETS TO LIQUID AND SUCTION / VAPOR LINE SERVICE VA LVES
3
Flow regulated nitrogen (at 1 to 2 psig) through the low-side refrigeration gauge set into the liquid line service port valve, and out of the suction / vapor line service port valve.
A Connect gauge set low pressure side to
liquid line service valve (service port).
B Connect gauge set center port to bottle of
nitrogen with regulator.
C Remove Schrader valve in suction / vapor
line service port to allow nitrogen to escape.
ATTACH
GAUGES
HIGHLOW
USE REGULATOR TO FLOW
NITROGEN AT 1 TO 2 PSIG.
SERVICE
PORT CORE
SERVICE PORT CAP
SUCTION / VAPOR SERVICE PORT MUST BE
OPEN TO ALLOW EXIT POINT FOR NITROGEN
VAPOR LINE
INDOOR
UNIT
LIQUID LINE
LIQUID LINE FILTER DRIER
(FIELD-PROVIDED)
C
LIQUID LINE SERVICE
SUCTION /
VAPOR LINE
SERVICE
VALV E
VALV E
A
SERVICE VA LVES, POINT FLAME
Figure 6A. Brazing Procedure
B
OUTDOOR
UNIT
WHEN BRAZING LINE SET TO
AWAY FROM SERVICE VALVE.
NITROGEN
506694-01Issue 1720Page 8 of 16
Page 9
WRAP SERVICE VALVES
To help protect service valve seals during brazing, wrap a saturated cloth around service valve bodies and copper tube stub. Use another
4
saturated cloth underneath the valve body to protect the base paint.
FLOW NITROGEN
Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration gauge set into the valve stem port connection on the liquid service valve and
5
out of the suction / vapor valve stem port. See steps 3A, 3B and 3C on manifold gauge set connections.
BRAZE LINE SET
Wrap both service valves with a saturated cloth as illustrated here before brazing to line set.
6
LIQUID LINE SERVICE VALVE
WHEN BRAZING LINE SET TO
SERVICE VALVES, POINT FLAME
AWAY FROM SERVICE VALVE.
IMPORTANT —
additional saturated cloths to help cool brazed joint.
Do not remove wet rag until piping has cooled. Temperatures above 250ºF will damage valve seals.
1. FIRE, PERSONAL INJURY, OR PROPERTY DAMAGE will result if you do not wrap a wet cloth
around both liquid and suction line service valve bodies and copper tube stub while brazing in the line set! The braze, when complete, must be quenched with water to absorb any residual heat.
2. Do not open service valves until refrigerant lines and indoor coil have been leak-tested and evacuated.
Refer to procedures provided in this supplement.
Allow braze joint to cool. Apply
WARNING
SUCTION / VAPOR LINE
SATURATED CLOTH
LIQUID LINE
SUCTION / VAPOR LINE
SERVICE VA LVE
SATURATED CLOTH
WHEN BRAZING LINE SET TO
SERVICE VA LVES, POINT FLAME
AWAY FROM SERVICE VALVE.
PREPARATION FOR NEXT STEP
7
After all connections have been brazed, disconnect manifold gauge set from service ports. Apply saturated rags to both service valves to cool piping. Once piping is cool, remove all wet cloths.
506694-01 Issue 1720 Page 9 of 16
Figure 6B. Brazing Procedure (cont.)
Page 10
Removing Existing Metering Device and Flushing Line Set and Indoor Coil
1A
1B
Flushing is only recommended if existing indoor coil and line set are to be used. Otherwise, proceed to Installing Indoor Metering Device on Page 11.
TYPICAL EXISTING FIXED ORIFICE REMOVAL PROCEDURE (UNCASED COIL SHOWN)
DISTRIBUTOR TUBES
LIQUID LINE ORIFICE HOUSING
DISTRIBUTOR
ASSEMBLY
A On fully cased coils, remove the coil access and plumbing panels. B Remove any shipping clamps holding the liquid line and distributor
assembly.
C Using two wrenches, disconnect liquid line from liquid line orifice
housing. Take care not to twist or damage distributor tubes during this process.
D Remove and discard fixed orifice, valve stem assembly if present
and Teflon
E Use a field-provided fitting to temporarily reconnect the liquid line to
the indoor unit's liquid line orifice housing.
LIQUID LINE ASSEMBLY
(INCLUDES STRAINER)
®
washer as illustrated above.
TEFLON® RING
FIXED ORIFICE
BRASS NUT
CONNECT GAUGES AND EQUIPMENT FOR FLUSHING PROCEDURE
2
INVERTED CYLINDER CONTAINS CLEAN LIQUID HCFC-22* TO BE USED FOR FLUSHING.
A
1
VAPOR LINE
SERVICE VALVE
EXISTING
INDOOR
UNIT
LIQUID LINE SERVICE
VALV E
VAPOR
LIQUID
D
RECOVERY
CYLINDER
A Inverted HCFC-22 cylinder with clean refrigerant* to the vapor service
valve.
B HCFC-22 gauge set (low side) to the liquid line valve. C HCFC-22 gauge set center port to inlet on the recovery machine with an
empty recovery tank to the gauge set.
D Connect recovery tank to recovery machine per machine instructions.
OUTDOOR
B
NEW
UNIT
OPENED
C
RECOVERY MACHINE
MANIFOLD
LOW
TANK RETURN
INLET
DISCHARGE
GAUGE
OR
TWO PIECE PATCH PLATE
(UNCASED COIL ONLY)
A On fully cased coils, remove the coil access and plumbing panels. B Remove any shipping clamps holding the liquid line and distributor
C Disconnect the equalizer line from the expansion valve equalizer line
D Remove the vapor line sensing bulb. E Disconnect the liquid line from the expansion valve at the liquid line
F Disconnect the expansion valve from the liquid line orifice housing.
HIGH
G Remove and discard expansion valve and the two Teflon H Use a field-provided fitting to temporary reconnect the liquid line to the
CLOSED
3
TYPICAL EXISTING EXPANSION VALVE REMOVAL PROCEDURE (UNCASED COIL SHOWN)
LIQUID LINE
DISTRIBUTOR
TUBES
DISTRIBUTOR
ASSEMBLY
MALE EQUALIZER
LINE FITTING
SENSING BULB
assembly.
fitting on the vapor line.
assembly.
Ta ke care not to twist or damage distributor tubes during this process.
indoor unit's liquid line orifice housing.
ORIFICE
HOUSING
EQUALIZER LINE
STUB END
TEFLON RING
VAPOR
EXPANSION
VALV E
®
LIQUID LINE
ASSEMBLY WITH
BRASS NUT
LINE
TEFLON
RING
®
SENSING
LINE
LIQUID
®
rings.
FLUSHING LINE SET
The line set and indoor unit coil must be flushed with at least the same amount of clean refrigerant* that previously charged the system. Check the charge in the flushing cylinder before proceeding.
A Set the recovery machine for liquid recovery and start the
recovery machine. Open the gauge set valves to allow the recovery machine to pull a vacuum on the existing system line set and indoor unit coil.
B Invert the cylinder of clean refrigerant* and open its valve to allow
B
liquid refrigerant to flow into the system through the vapor line valve. Allow the refrigerant to pass from the cylinder and through the line set and the indoor unit coil before it enters the recovery machine.
C After all of the liquid refrigerant has been recovered, switch the
recovery machine to vapor recovery so that all of the HCFC-22 vapor is recovered. Allow the recovery machine to pull the system down to zero.
D Close the valve on the inverted HCFC-22 drum and the gauge
set valves. Pump the remaining refrigerant out of the recovery machine and turn the machine off.
LINE
*IMPORTANT - Clean refrigerant is any refrigerant in a system that has not had compressor burn out. If the system has experienced burn out, it is recommended that the existing line set and indoor coil be replaced.
Figure 7. Removing Metering Device and Flushing
506694-01Issue 1720Page 10 of 16
Page 11
Installing New Indoor Metering Device
1A
This outdoor unit is designed for use in existing HCFC-22
systems that use either a xed orice (RFC) or expansion
valve metering device (purchased separately) at the indoor coil.
INDOOR EXPANSION VALV E INSTALLATION
(Uncased Coil Shown)
LIQUID LINE
ORIFICE
HOUSING
STUB
END
TEFLON RING
EQUALIZER LINE
VAPOR
EXPANSION
VALV E
®
ASSEMBLY WITH
LINE
TEFLON
LIQUID LINE
BRASS NUT
TWO PIECE
PATCH PLAT E
(UNCASED
COIL ONLY)
DISTRIBUTOR
TUBES
DISTRIBUTOR
ASSEMBLY
MALE EQUALIZER LINE
FITTING (SEE
EQUALIZER LINE INSTALLATION FOR FURTHER DETAILS)
Sensing bulb insulation is required if mounted external to the coil casing. sensing bulb installation for bulb positioning.
®
RING
SENSING
LINE
LIQUID LINE
See the 13ACD product specication sheet for approved xed orice sizes and expansion valve kit match ups. The
expansion valve unit can be installed internal or external to the indoor coil.
A Remove the field-provided fitting that temporarily
reconnected the liquid line to the indoor unit's distributor assembly.
B Install one of the provided Teflon
stubbed end of the expansion valve and lightly lubricate the connector threads and expose surface of the Te flon
C Attach the stubbed end of the expansion valve to the
liquid line orifice housing. Finger tighten and use an appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in the figure above, or 20 ft-lb.
D Place the remaining Teflon
valve. Lightly lubricate connector threads and expose surface of the Teflon
E Attach the liquid line assembly to the expansion valve. Finger tighten and
use an appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in the figure above or 20 ft-lb.
®
ring with refrigerant oil.
®
ring with refrigerant oil.
®
rings around the
®
washer around the other end of the expansion
SENSING BULB INSTALLATION
A Attach the vapor line sensing bulb in the proper
orientation as illustrated to the right using the clamp and screws provided.
NOTE — Confirm proper thermal contact between vapor line and expansion bulb before insulating the sensing bulb once installed.
B Connect the equalizer line from the expansion valve to the equalizer
vapor port on the vapor line. Finger tighten the flare nut plus 1/8 turn (7 ft-lbs) as illustrated below.
VAPOR LINE
ON LINES SMALLER THAN 7/8”, MOUNT SENSING BULB AT EITHER THE 3 OR 9 O'CLOCK POSITION.
1/2 Turn
11
10
9
8
1/8 Turn
11
10
9
8
7
12
1
2
3
4
5
7
6
12
1
2
3
4
5
6
EQUALIZER LINE INSTALLATION
Remove and discard either the flare seal cap or flare nut with copper flare seal bonnet from the equalizer line port on the vapor line as illustrated in the figure below.
FLARE SEAL CAP
OR
FLARE NUT
COPPER FLARE SEAL BONNET
MALE BRASS EQUALIZER LINE FITTING
VAPOR LINE
DISTRIBUTOR TUBES
LIQUID LINE ORIFICE HOUSING
BULB
VAPOR LINE
BULB
1B
REMOVE AND DISCARD WHITE
®
TEFLON
SEAL (IF PRESENT)
12
12
TEFLON® RING
FIXED ORIFICE
BULB
NOTE — NEVER
MOUNT ON BOTTOM
OF LINE.
ON 7/8” AND LARGER LINES, MOUNT SENSING BULB AT EITHER THE 4 OR 8 O'CLOCK POSITION. NEVER MOUNT ON BOTTOM OF LINE.
BULB
FIXED ORIFICE (RFC) DEVICE INSTALLATION
SEE TABLE 3 FOR INDOOR FIXED ORIFICE KITS CATALOG NUMBERS.
BRASS NUT
506694-01 Issue 1720 Page 11 of 16
Figure 8. Installing Indoor Metering Device
Page 12
Capacity
1
018 10W95 100484-07 0.055
024 98M12 100484-12 0.062
030 11W00 100484-16 0.067
036 98M78 100484-24 0.076
042 10W86 100484-28 0.080
048 98M14 100484-36 0.089
060 98M15 100484-45 0.099
Catalog Number
Part
Number
Drill Size
Table 3. Indoor Fixed Orice Kits
Leak Test Line Set and Indoor Coil
After completing the leak testing of the line set and indoor coil as outlined in Figure 9, proceed to Evacuating Line Set and Indoor Coil on Page 13.
CONNECT GAUGE SET
A Connect an HCFC-22 manifold gauge set high pressure hose
to the vapor valve service port.
NOTE — Normally, the high pressure hose is connected to the liquid line port. However, connecting it to the vapor port better protects the manifold gauge set from high pressure damage.
B With both manifold valves closed, connect the cylinder of
HCFC-22 refrigerant to the center port of the manifold gauge set.
NOTE — Later in the procedure, the HCFC-22 container will be replaced by the nitrogen container.
IMPORTANT Leak detector
must be capable of sensing HCFC-22 refrigerant.
IMPORTANT
The Environmental Protection Agency (EPA) prohibits the intentional venting of HCFC refrigerants during maintenance, service, repair and disposal of appliance. Approved methods of recovery, recycling or reclaiming must be followed.
WARNING
Refrigerant can be harmful if it is inhaled. Refrigerant must be used and recovered responsibly.
Failure to follow this warning may result in personal injury or death.
HIGHLOW
MANIFOLD GAUGE SET
OUTDOOR UNIT
B
TO VAPOR
SERVICE VA LVE
A
HCFC-22
NITROGEN
TEST FOR LEAKS
After the line set has been connected to the indoor and outdoor units, check the line set connections and indoor unit for leaks. Use
2
the following procedure to test for leaks:
A With both manifold valves closed, connect the cylinder of HCFC-22 refrigerant to the center port of the manifold gauge set. Open the
valve on the HCFC-22 cylinder (vapor only).
B Open the high pressure side of the manifold to weigh in a trace amount of HCFC-22 into the line set and indoor unit. A trace amount is a
maximum of two ounces (57 g) refrigerant or three pounds (31 kPa) pressure. Close the valve on the HCFC-22 cylinder and the valve on the high pressure side of the manifold gauge set. Disconnect the HCFC-22 cylinder.
C Connect a cylinder of dry nitrogen with a pressure regulating valve to the center port of the manifold gauge set.
D Adjust dry nitrogen pressure to 150 psig (1034 kPa). Open the valve on the high side of the manifold gauge set in order to pr essurize the line
set and the indoor unit.
E After a few minutes, open one of the service valve ports and verify that the refrigerant added to the system earlier is measurable with a
leak detector.
F After leak testing, disconnect gauges from service ports.
DIGITAL SCALE
Figure 9. Leak Test
IMPORTANT
Leak detector must be capable of sensing HCFC-22 refrigerant.
506694-01Issue 1720Page 12 of 16
Page 13
Evacuating Line Set, Indoor Coil and Outdoor Unit
CONNECT GAUGE SET
NOTE — Remove cores from service valves (if not already done).
1
Connect low side of manifold gauge set with 1/4 SAE in-line tee to vapor line service valve
Connect high side of manifold gauge set to liquid line service valve
Connect micron gauge available connector on the 1/4 SAE in-line tee.
Connect the vacuum pump (with vacuum gauge) to the center port of the manifold gauge set. The center port line will be used later for both the HCFC-22 and nitrogen containers.
NITROGEN
HCFC-22
VACUUM PUMP
OUTDOOR
UNIT
A
B
A34000 1/4 SAE TEE WITH SWIVEL COUPLER
500
C
MICRON
GAUGE
MANIFOLD
GAUGE SET
TO VAPOR
SERVICE VA LVE
TO LIQUID LINE SERVICE VA LVE
D
EVACUATE THE SYSTEM
A Open the liquid and vapor line service valves (counterclockwise) to release the factory nitrogen charge (contained in outdoor unit) into the
2
system.
B Open both manifold valves and start the vacuum pump. C Evacuate the line set, indoor unit and outdoor unit to an absolute pressure of 23,000 microns (29.01 inches of mercury).
NOTE — During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once. A rapid rise in pressure indicates a relatively large leak. If this occurs, repeat the leak testing procedure.
NOTE — The term absolute pressure means the total actual pressure within a given volume or system, above the absolute zero of pressure. Absolute pressure in a vacuum is equal to atmospheric pressure minus vacuum pressure.
D When the absolute pressure reaches 23,000 microns (29.01 inches of mercury), perform the following:
Close manifold gauge valves
Close valve on vacuum pump
Turn off vacuum pump
Disconnect manifold gauge center port hose from vacuum pump
Attach manifold center port hose to a dry nitrogen cylinder with pressure regulator set to 150 psig (1034 kPa) and purge the hose.
Open manifold gauge valves to break the vacuum in the line set and indoor unit.
Close manifold gauge valves.
E Shut off the dry nitrogen cylinder and remove the manifold gauge hose from the cylinder. Open the manifold gauge valves to release the
dry nitrogen from the line set and indoor unit.
F Reconnect the manifold gauge to the vacuum pump, turn the pump on, and continue to evacuate the line set and indoor unit until the
absolute pressure does not rise above 500 microns (29.9 inches of mercury) within a 20-minute period after shutting off the vacuum pump and closing the manifold gauge valves.
G When the absolute pressure requirement above has been met, disconnect the manifold hose from the vacuum pump and connect it to an
upright cylinder of HCFC-22 refrigerant. Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and indoor unit.
H Perform the following:
Close manifold gauge valves.
Shut off HCFC-22 cylinder.
Reinstall service valve cores by removing manifold hose from service valve. Quickly install cores with core tool while maintaining a positive system pressure.
Replace stem caps and secure finger tight, then tighten an additional one-sixth (1/6) of a turn as illustrated.
RECOMMEND MINIMUM 3/8” HOSE
10
9
8
1/6 TURN
12
11
7
6
HIGHLOW
1
2
3
4
5
506694-01 Issue 1720 Page 13 of 16
Figure 10. Evacuating System
Page 14
Electrical
In the U.S.A., wiring must conform with current local codes and the current National Electric Code (NEC). In Canada, wiring must conform with current local codes and the current Canadian Electrical Code (CEC).
Refer to the furnace or air handler installation instructions for additional wiring application diagrams and refer to unit
SIZE CIRCUIT AND INSTALL DISCONNECT SWITCH
Refer to the unit nameplate for minimum circuit ampacity, and maximum fuse or circuit breaker (HACR per NEC). Install power wiring and properly sized disconnect switch.
SERVICE
DISCONNECT
SWITCH
MAIN FUSE BOX/ BREAKER PANEL
nameplate for minimum circuit ampacity and maximum overcurrent protection size.
24VAC Transformer
Use the transformer provided with the furnace or air handler for low-voltage control power (24VAC - 40 VA minimum).
CHECK EXISTING ROOM THERMOSTAT
Ensure that existing room thermostat is installed on an inside wall approximately in the center of the conditioned area and 5 feet (1.5m) from the floor. It should not be installed on an outside wall or where it can be affected by sunlight or drafts.
THERMOSTAT
5 FEET
(1.5M)
NOTE — Units are approved for use only with copper conductors. Ground unit at disconnect switch or to an earth ground.
NOTE — 24VAC, Class II circuit connections are made in the control panel.
HIGH VOLTAGE / GROUND WIRES
Any excess high voltage field wiring should be trimmed and secured away from any low voltage field wiring. To facilitate a conduit, a cutout is located in the bottom of the control panel. Connect conduit to the control panel using a proper conduit fitting.
CONTROL WIRING
Use existing or replace low voltage wiring from outdoor to indoor unit and from thermostat to indoor unit as illustrated.
A Run 24VAC control wires through hole with grommet and secure with provided wire tie.
B Make 24VAC thermostat wire connections. Locate the two wires from the contactor and make connection using field provided wire nuts:
Black to Y1
Black to C (common)
NOTE — For proper voltages, select thermostat wire (control wires) gauge per table below.
NOTE — Do not bundle any excess 24VAC control wires inside
TYPICAL LOW VOLTAGE CONTROL
control panel.
WIRING
THERMOSTAT INDOOR UNIT
SINGLE PHASE
B
CONTROL
WIRING
A
GROMMET AND WIRE TIE
W1
R
Y
G
C
POWER
HEAT
COOLING
INDOOR
BLOWER
COMMON
R
W
Y
BLACK
G
C
BLACK
OUTDOOR
UNIT
Y1
C
HIGH VOLTAGE
CONNECTIONS
(CONTACTOR)
GROUND
HIGH VOLTAGE FIELD WIRING
LOW VOLTAGE FIELD WIRING
FACTORY WIRING
WIRE RUN LENGTH AWG# INSULATION TYPE
LESS THAN 100' (30 METERS) 18 TEMPERATURE RATING
MORE THAN 100' (30 METERS) 16 35ºC MINIMUM.
HIGH VOLTAGE
FLEXIBLE CONDUIT
NOTE — Wire tie provides low voltage control wire strain relief and to maintain separation of field installed low and high voltage circuits.
506694-01Issue 1720Page 14 of 16
Page 15
WARNING
Electric Shock Hazard. Can cause injury or death. Unit must be grounded in accordance with national and
local codes.
Line voltage is present at all components when unit is not in operation on units with single-pole contactors. Disconnect all remote electric power supplies before opening access panel. Unit may have multiple power supplies.
Figure 11. Typical Unit Wiring Diagram
IMPORTANT
If unit is equipped with a crankcase heater, it should be energized 24 hours before unit start-up to prevent compressor damage as a result of slugging.
Servicing Outdoor Unit Delivered Void of Nitrogen Charge
If the outdoor unit is void of factory nitrogen charge, clean the system using the procedure described below.
1. Use nitrogen to repressurize system and check for leaks.
2. Evacuate the system using evacuating procedure provided in this instruction.
3. Use nitrogen to break the vacuum and install a new
lter drier in the system.
4. Evacuate the system again using evacuating procedure provided in this instruction.
5. Monitor the system to determine the amount of moisture remaining in the oil. It may be necessary
to replace the lter drier several times to achieve
the required dryness level. If system dryness is not
veried, the compressor will fail in the future.
Maintenance
Maintenance and service must be performed by a qualied
installer or service agency. At the beginning of each cooling season, the system should be checked as follows:
Outdoor Unit
1. Outdoor unit fan motor is pre-lubricated and sealed. No further lubrication is needed.
2. Visually inspect all connecting lines, joints and coils for evidence of oil leaks.
3. Check all wiring for loose connections.
4. Check for correct voltage at unit (unit operating).
5. Check amp draw on outdoor fan motor.
Motor Nameplate:_________ Actual:__________.
506694-01 Issue 1720 Page 15 of 16
Page 16
6. Inspect drain holes in coil compartment base and clean if necessary.
NOTE: If insufcient cooling occurs, the unit should be
gauged and refrigerant charge should be checked.
Outdoor Coil
Clean and inspect outdoor coil (may be ushed with a
water hose). Ensure power is off before cleaning.
NOTE: It may be necessary to ush the outdoor coil
more frequently if it is exposed to substances which are
corrosive or which block airow across the coil (e.g., pet urine, cottonwood seeds, fertilizers, uids that may contain
high levels of corrosive chemicals such as salts)
Sea Coast — Moist air in ocean locations can carry salt, which is corrosive to most metal. Units that are located near the ocean require frequent inspections and maintenance. These inspections will determine the necessary need to wash the unit including the outdoor coil. Consult your installing contractor for proper intervals/procedures for your geographic area or service contract.
Indoor Unit
1. Clean or change lters.
2. Some blower motors are pre-lubricated and permanently sealed. No more lubrication is needed.
3. Adjust blower speed for cooling. Measure the pressure drop over the coil to determine the correct blower CFM. Refer to the unit information service manual for pressure drop tables and procedure.
4. Belt Drive Blowers - Check belt for wear and proper tension.
5. Check all wiring for loose connections.
6. Check for correct voltage at unit. (blower operating)
7. Check amp draw on blower motor.
Motor Nameplate:_________ Actual:__________.
Indoor Coil
1. Clean coil if necessary.
2. Check connecting lines, joints and coil for evidence of oil leaks.
3. Check condensate line and clean if necessary.
Start-Up and Performance Checklist
Job Name: ______________________________________________ Job No. _________________ Date: ________________
Job Location: ____________________________________________ City: ____________________ State: ________________
Installer: ________________________________________________ City: ____________________ State: ________________
Unit Model No. ___________________________________________ Serial No. _______________________________________
Service Technician: _______________________________________ Nameplate Voltage: _______________________________
Rated Load Ampacity: _______________ Compressor Amperage: _________________ Outdoor Fan: _____________________
Maximum Fuse or Circuit Breaker: ____________________________
Electrical Connections Tight?
Indoor Blower RPM: ______________________________________ S.P. Drop Over Indoor (Dry): ________________________
Outdoor Coil Entering Air Temperature: _______________________
Indoor Filter Clean? Supply Voltage (Unit Off): __________________________
Voltage with Compressor Operating: ___________________
Outdoor Fan Checked?
Refrigerant Lines: Leak Checked? Properly Insulated?
Service Valves: Fully Opened? Caps Tight?
Thermostat Calibrated? Properly Set? Level?
506694-01Issue 1720Page 16 of 16
Loading...