Lennox 11U61 Setup And Installation Manual

Page 1
201 Lennox Industries Inc.
Dallas, Texas, USA
THIS MANUAL MUST BE LEFT WITH THE HOMEOWNER
FOR FUTURE REFERENCE
NOTICE
Read this manual before programming this thermostat.
Use this thermostat only as described in this manual.
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life.
Installation and service must be performed by a licensed professional HVAC installer (or equivalent) or service agency.
INSTALLER'S SYSTEM SETUP GUIDE
iComfort Wi-Fi® Flex
Touchscreen Programmable Thermostat (11U61)
CONTROLS
Shipping and Packing List
Thermostat container includes: 1 - Thermostat 4 - Wall anchors 1 - Homeowner's manual 4 - Mounting screws
Equipment Interface container includes: 1 - Equipment Interface Module 1 - Equipment Interface Module Installation Instruction 1 - Warranty card
Page 2
507428-01
2
TABLE OF CONTENTS
Overview - Technical Description and Features 2................
Installation and set up 3.....................................
Adjusting System Settings 4..................................
Connecting to Home Wi-Fi Router 6...........................
Troubleshooting Wi-Fi Connection 9...........................
Account Registration 14......................................
Firmware Update 15.........................................
Adding Conventional Outdoor Unit and Accessories 15............
Outdoor Unit (Air Conditioner or Heat Pump) 15...................
Bypass (24VAC) Humidifier 15..................................
Auxiliary Dehumidifier 16......................................
Adjusting Humidification and Dehumidification Settings with
Conventional Outdoor Units 17................................
Using the Tests / Diagnostics Features 20.......................
Using the Secure Web Portal 22...............................
Skins 22...................................................
Screen-Saver 22............................................
Accessing Installer Screens and Changing
Equipment Parameters 24....................................
Wiring Diagrams 26..........................................
Overview - Technical Description and Features
The iComfort Wi‐Fi® Flex Thermostat is a 24VAC, color display touchscreen and 7-day programmable thermostat. It stores system parameters and settings in non-volatile memory (i.e., it retains data when electrical power fails or is turned off).
The iComfort Wi‐Fi® Flex thermostat can connect to online services via the Internet through the homeowner's Wi-Fi access point. After online registration is completed, the system may then be accessed by the homeowner from anywhere using a remote Internet connection via computer, smartphone or other personal Internet-connected devices.
WARNING
This is a 24VAC Class 2 thermostat. Do not install on voltages higher than 30VAC.
Do not switch system to cool if the outdoor temperature is below 45°F (7°C). This can damage the cooling system.
WARNING
7KLVSURGXFWFRQWDLQVDFKHPLFDONQRZQWRWKH6WDWHRI &DOLIRUQLDWRFDXVHFDQFHUELUWKGHIHFWVRURWKHUUHSURGXFWLYHKDUP
Page 3
7-Day Programmable iComfort Wi‐Fi® Flex Thermostat
3
This thermostat supports:  Wireless bands 802.11b, 802.11g and 802.11n
Three languages (English, French, Spanish)
Air conditioning or heat pump units with up to four
stages of heat / two stages of compressor operation (2 stages of heat pump heating, 2 stages of auxiliary back-up heating and 2 stages of emergency heating)
Variable-capacity / multiple-stage heat / cool and
universal compatibility (gas/electric/heat pump/air conditioner).
Dual-fuel capable with two balance points.
Indoor air quality with time‐based notification of
consumables including media filters, UVC bulbs, humidifier pads and PureAir system catalyst service / replacement,
Humidification measurement and control.
Dew point adjustment control
Equipment maintenance reminders
Autochangeover mode -- Permits control of heating,
cooling, humidification, and dehumidification without user involvement
Installation and Setup
During initial thermostat start-up the following screen will appear (see figure 1). This indicates that the thermostat is active and booting up.
...
Figure 1. Boot-Up Screen
COMMUNICATION ERROR SCREEN
During initial thermostat start-up if the following screen appears (see figure 2), this will indicate that the thermostat has been incorrectly wired or has shorted
Page 4
507428-01
4
wires. Turn power off to the system and verify that all wiring is correct.
Figure 2. Communication Error Screen
Adjusting System Setting
SET TIME AND DATE
Use the arrows to select Time and Date; touch edit to proceed to the “Set current time and date” screen.
When “Time and Date” screen appears, enter the correct date as follows:
Use the left and right arrows to change the month
and year.  Touch a day of the month to select it.  Touch on the hour or minute; up down arrows appear
to allow change.
Touch the am/pm field to toggle it between am and
pm.
When the correct date and time is set, touch save to
save settings and return to previous settings screen.
Touch next to continue to next screen.
CIRCULATE FAN ON TIME SETTING “Circulate” is enabled on the user's home screen or
system settings page. It keeps air circulating from 15%
to 50% percent of time. The following settings approximate how long the fan will run at these typical settings:
15% (9 minutes fan run time per hour) 25% (15 minutes fan run time per hour) 35% (21 minutes fan run time per hour) 45% (27 minutes fan run time per hour).
NOTE - If the circulate fan mode is on, a timer is set to measure all the time that the fan is blowing, regardless if it is running to deliver heating or cooling or just for air circulation.
DEALER NUMBER
Either the dealer number or phone number is required. Once either number is entered, all other fields will automatically be populated once the thermostat has been registered during the Wi-FI set up procedure later on in this instruction (if the dealer has an account with Lennox already).
Page 5
7-Day Programmable iComfort Wi‐Fi® Flex Thermostat
5
NOTE - Dealer number is the dealer's Lennox account number. Dealer phone number is the dealer's main office phone number.
1. Use the arrows to scroll down to the Dealer Number
or Dealer Phone setting. Press the edit button.
2. Enter the Dealer Number or Dealer Phone
Number using the on-screen keyboard. Press save
to continue.
NOTE: If a Dealer Number or Dealer Phone Number is not entered and the next button is selected, a pop-up warning screen will appear.
3. Press yes to continue to the System Devices
screen. Press no to return to the system settings
screen.
WARNING
Are you sure you want to proceed?
Please enter your DEALER PHONE NUMBER or DEALER NUMBER
If you do not enter either, the thermostat will not show up on
DaveNet and you will not be able to remotely monitor the system
status or receive email alerts when there is a problem.
no
yes
WARNING
The dealer number is your Lennox account number) i.e
A12345). Your dealer phone number should be the main office
phone number associated with your dealership. If you have any
questions, please contact your Lennox representative.
Are you sure you want to proceed?
Figure 3. Dealer Number Warning
The following table lists all of the installer configurable system level parameters available from the installer set up screens. After adjusting system settings, select next to continue.
Table 1. System Settings
Parameter
Name
Default
Parameter Value
Setting
Increment
Time and
Date
(Time/date
elements screen)
Daylight
Saving Time
Enabled Enabled, Disabled
Circulate Fan
ON Time
35% Range 15 to 45% 1%
Temperature
Unit
Fahrenheit
Fahrenheit or
Celsius
System Name
(keyboard input
screen)
Dealer
Number
****
(keyboard input
screen)
Note: When adding
the dealer number,
all other dealer
fields will auto pop
ulate once thermo
stat registration is
completed.
Dealer Name Lennox
Dealer
Address
Dealer Phone
1-800-9-LEN
NOX
Dealer Email
Dealer
Website
www.lennox.
com
Page 6
507428-01
6
Connecting to a Home Wi-Fi Router
Check the router utility program or contact service provider for help. When determining the location for the
Wi-Fi thermostat, be sure it is in an area near enough to the home Wi-Fi router to ensure good communications signal strength between the thermostat and the Wi-Fi router. (Hint: Use a smart phone with Wi-Fi and Wi-Fi finder application to locate and determine optimal location based on router Wi-Fi signal strength.)
NOTE - Thermostat will not be able to reliably connect to a router if the received signal strength indicator (RSSI) is
-70 or greater.
NOTE - Correct the cause of any alerts prior to continuing set up. Secure Connection Recommended! Verify the home Wi-Fi router supports at least one of the supports wireless bands (802.11b, g or n). Check router utility program or contact service provider for assistance.
ENABLING WI-FI
To enable the Wi-Fi feature to communicate with a wireless router
1. Press and release Wi-Fi in the lower left corner of
the HOME screen
indoor temperature
indoor humidity is 41%
fan is
OFF
9:39 am Aug 15, 2012
fan is AUTO
cool-to
set temp
75
Heat-to
72
heat
or
cool
fan is AUTO
enter away
outdoor
temperature
80
system is cooling
Wi-Fi
?
1
Wi-Fi
Figure 4. Press Wi-FI
2. Press the Wi-Fi disable button to enable Wi-Fi.
WI-FIL SETTINGS
Press to enable /
disable Wi-FI
disabled
Thermostat is not connected to the Wi-FI network
WI-FI
X
Figure 5. Enable Wi-FI
Page 7
7-Day Programmable iComfort Wi‐Fi® Flex Thermostat
7
3. The User Agreement screens will appear next.
Press next as many times as necessary; then press
accept after reading the User Agreement. ESTABLISHING A WI-FI CONNECTION
There are two methods to set up your Wi-Fi connection. Select either NETWORK SETTINGS or connection status.
Method 1 — Network Settings Method
1. Press NETWORK SETTINGS; this screen shows a
graphical view of buttons representing OPEN and
SECURE Wi-Fi networks and a button for adding a
network.
WI-FI SETTINGS
press to enable /
disable Wi-FI
enabled
Thermostat is not connected to the Wi-FI network
WI-FI
X
NETWORK SETTINGS
press to change network settings
Must setup a network connection before registering thermostat
connection
status
Press to see
connection status
Figure 6. Enable Wi-FI
Open connection which which requires no
password.
Secure connection which requires Wi-Fi
password (security key).
Add a network is required when Wi-Fi
identification (SSID) is being hidden (not broadcasting). You will need to know the Wi-Fi network name (SSID), security encryption type (if enabled), and security password (if security encryption is enabled).
2. When selecting a:  unsecured connection a screen will appear with
two options, connect and router info. Press connect to continue.
secured connection a screen will appear
requesting the Wi-Fi network password (security key). There are two options to select from which are connect and router info. Using the on-screen keyboard, enter the password (security key) and then press connect to continue.
HOME
DS9A
Open connection (no password required)
Secure connection (password required)
(lock icon is present)
Figure 7. Typical Connection Type and Signal
Strength
Page 8
507428-01
8
NOTE - The router info button provides information concerning the home Wi-fi connection (i.e, RSSI, IP address, MAC address and wait state) all of which may be helpful in troubleshooting network connection issues).
3. If connection is successful the screen will return to the available networks screens. Press AP3 as exampled in figure 8 to return to the previous screen. If the connection was successful it will be listed connected as exampled below.
WI-FI SETTINGS
press to enable //
disable Wi-FI
9:39 am Aug 15, 2012
enabled
WI-FI
?
X
AP3
connected
press to change
wireless network
Must setup a network connection before registering thermostat
Wi-Fi
connection
status
Press to see
connection status
thermostat
not
registered
press to change
thermostat
registration
Figure 8. Network Connected
ESTABLISHING A WI-FI CONNECTION TO A HIDDEN NETWORK
1. When connecting to a hidden network, press the
add new network icon to continue. Enter the network name (SSID). If security encryption is
enabled, then press the security is none icon. Select either WEP, WPA or WPA2.
2. Using the on-screen keyboard, enter the password (security key). If the network name or security key combination is incorrect or incorrectly type, and access to the specified network failed, a message will alert you to retry.
3. If connection is successful the screen will return to the available networks screens. The network successfully connected will be listed and shown as connected as exampled in figure 8.
Method 2 — Connection Status Method
1. Press connection status; this screen shows a graphical view of the current connection status.
2. Select the router icon to choose the desire W-Fi network. When selecting a:
unsecured connection a screen will appear with
two options, connect and Router Info. Press connect to continue.
secured connection a screen will appear
requesting the Wi-Fi network password (security key). There are two options to select from which are connect and router info. Using the on-screen keyboard, enter the password
Page 9
7-Day Programmable iComfort Wi‐Fi® Flex Thermostat
9
(security key) and then press connect to continue.
3. If connection is successful the screen will return to the available networks screens. Press X to return to the previous screen. If the connection was successful it will be listed connected as exampled below.
WI-FI SETTINGS
press to enable //
disable Wi-FI
9:39 am Aug 15, 2012
enabled
WI-FI
?
X
xxxx
connected
press to change
wireless network
Must setup a network connection before registering thermostat
Wi-Fi
connection
status
Press to see
connection status
thermostat
not
registered
press to change
thermostat
registration
Figure 9. Network Connected
4. Select X to return to the WI-FI SETTINGS screen. Select connection status again to verify that connection to the router and Internet is active. Both the router and internet icons will have green backgrounds if connections are successful.
5. Skip the next section if connection to the home Wi-Fi router, Internet and server were successful.
Troubleshooting Wi-Fi Connection
ROUTER / MODEM CHECK IF CONNECTION FAILS
1. Make sure the router and modem are turned on.
2. Check for connections to other wireless devices and internet connection.
3. Make sure the thermostat's Wi-Fi is enabled and connected to the home network (Router).
4. If having difficulty connecting to the router, online research the router model number and/or internet provider to discover and verify that the router band is set to B, G or N bands. You will need to access the routers utility program to make any changes. If not accessible please contact your service provider for help. The thermostat will connect to B, G or N band routers at this time. NOTE: When set to B or G bands, video streaming will likely be slower that N band. If homeowner has implemented a dedicated N band router for the purpose of video streaming, a separate router for the thermostat may be required.
5. Reboot your router A Unplug your power cord, wait 30 seconds, then
reconnect. If you have multiple routers, try rebooting all of them when problems occur.
B If their are multiple routers you must have
different name and password for each one.
Page 10
507428-01
10
C On your computer, turning Wi-Fi off and then
back on will force the system to rescan for available networks. Do you see the network your thermostat is trying to connect to?
6. Power cycle the thermostat.
7. Keep cordless phones, microwaves and other electrical equipment at least 3.5 feet (1m) away from access point.
A Try moving your router closer to the device if
possible. If connection is improved, then there is probably some interference. Must have signal stronger than -70db (also, see Router Signal Strength on page 3); anything less will have signal losses or not connect at all.
B Adjust the direction of the router toward the
thermostat. Adjust the routers antenna. A signal repeater may be needed.
8. Try changing channels on the access point and test it out with one of your internet devices (i.e. laptop, desktop). The IP address to the server from the stat will be close to the same IP address from the computer to the server (www.mycomfortsync.com).
COMPUTER CONNECTIONS:
A On Access Point, Login to configuration (usually
web based interface) > go to Wireless Settings and select a different channel > Save settings.
B Devices cannot change Wi-Fi channel. It is set
only at the router.
C On the thermostat, disable, then re-enable the
Wi-Fi connection.
9. Antenna in thermostat is fixed and cannot be moved. Location of your access point with respect to the thermostat is very important.
10. Baby monitors, garage door openers and wireless video cameras may create signal interference.
11. Check your encryption key (Password).
12. Double check and re-enter your WEP/WPA encryption keys / pass-phrases (usually found on the router). If set to WEP security, change to WPA if allowed.
13. In your thermostat's wireless settings, verify that your encryption key (password) is correct. There can not be spaces at the end of the SSID or Password.
14. It is important to note that number of walls that the signal must pass thru to reach the thermostat can be an issue. (e.g. 4 indoor walls, or 1 outdoor wall + 2 indoor walls could mean a weak signal at the thermostat).
15. The addition of a signal repeater or extender maybe an option. (Desktop or wall outlet plug-in devices are available online or at your local electronics stores in price range $70 - $150).
16. If multiple routers are in the home make sure each router has a different name.
Page 11
7-Day Programmable iComfort Wi‐Fi® Flex Thermostat
11
17. If you don't get the pop up box that says the registration request has been forwarded, then the email was not sent to the server and the return registration link will not be sent to your email address. Try all the router troubleshooting procedures and if you still can't get it to send the email, cycle the power to the thermostat. This will cause the thermostat to ask for the Lennox server mac address again and try to resend the email.
18. If all is correct, refer user to their Router manufacturer and Network provider. Router may have incoming fire wall check with service provider.
ROUTER SIGNAL STRENGTH
After connecting to your router, you can check your signal strength by pushing the Wi-Fi icon on the home screen, then the networks button, then your network button, then the router info button (see figure 10).
A strong wireless signal (RSSI) is indicated by a NEGATIVE decibel number in the range from -46 to
-58db; anything greater than -70db will not connect. If you are connected but have a signal above -70db then
you may consider adding a signal repeater/extender or making some of the other router adjustment mentioned in the Router / Modem Check section
router Info
connect
Push router info button
Figure 10. Access connection data
AT+NSTAT=? MAC=00:ID:C9:A0:40:95 WSTATE=CONNECTED MODE=AP
BSSID=98:FC:11:47:B9:00 SSID= LINKSYS” CHANNEL=6 SECURITY=NONE
RSSI=-78 IP ADDR=192.168.8.117 SUBNET=255.255.255.0 GATEWAY=192.168.8.1 DNSI=192.168.1.1 DNS2=0.0.0.0 RXCOUNT=14 TXCOUNT=345 OK
Figure 11. Connection Data
Page 12
507428-01
12
Registering the Thermostat
REGISTRATION FOR ONLINE ACCESS
1. From the WI-FI SETTINGS screen, press either the
thermostat not registered icon or the connection status icon and select the server icon.
WI-FI SETTINGS
connection
status
thermostat
not
registered
AP3
connected
press to change network settings
press to enable /
disable Wi-Fi
press to change
thermostat
registration
press to toggle
off / auto
Wi-Fi
enabled
2. Enter homeowner email address and system description and press the register button.
register
enter your email
Register with iComfort Wi-Fi thermostat to enable remote access and
online weather information
System Desc
3. A pop-up screen will appear asking if the email address below is correct? Verify the email address is correct and press yes.
4. Another pop-up screen will appear notifying the user to check their email.
An email has been sent to
xxxxxxxxxx@lennoxind.com with instructions on how to register your thermostat. If you haven't received the email, please check your spam folder and make sure
that your email address is correct.
NOTE - If the email address originally entered is incorrect, return to the thermostat registered screen and reenter the correct information and press register.
5. After the iComfort Wi‐Fi® server sends the email with the network link, registration and account creation must be completed from the homeowner's personal computer.
Page 13
7-Day Programmable iComfort Wi‐Fi® Flex Thermostat
13
NOTE - Time from pushing the registration button on the thermostat and receiving the consumer portal register link from your email on your computer is normally from 5 to 15 minutes depending on Internet speed and traffic.
6. After registration has been completed, press the connection status icon to verify the connection was successful. If the connection is successful the server icon background will be green.
7. After successful connection to the server is completed, the firmware update button will appear. The default setting is set to auto. If any firmware updates are available they will immediately start downloading and update the thermostat. The thermostat will reboot itself after the update is completed. Updates are done in the background and will not impair normal thermostat operations.
This auto update feature can be disabled by pressing the firmware update button to toggle to OFF but is not recommended.
NOTE - Firmware updates will not affect installer or user thermostat settings. Both will be retained after the update.
WI-FI SETTINGS
connected
Wi-Fi
enabled
thermostat
registered
Connection to server has not bee established or it has been lost.
Please wait until a connection is established.
firmware
update
auto
press to enable /
disable Wi-Fi
press to change wireless network
press to change
thermostat
registration
press to search for new update
NOTE ­If any downloads are available for the thermostat they will start down loading right away. When new firmware is being downloaded or when Gelaskins are being installed, the thermostat screen will temporarily go blank and running units may cease operation while the system is being reset to accommodate the new changes. This is normal and can last a couple minutes.
AP3
connection
status
press to see
connection status
Figure 12. Registration for Online Access
Page 14
507428-01
14
User Account Registration for Lennox Server Access
Figure 13. Registration Screen
NOTE - This following information is customer set up instructions and is shown here to allow the installer to help walk the customer through the set up process.
After registering through your iComfort Wi‐Fi® Flex thermostat interface, go to the homeowner's computer and locate the email sent from the server.
NOTE - if the customer has already set up an account, click the “Click Here” button to access that account.
Click on the Register link; the screen (to the left) will appear. Fill in the User Name and Password fields and check the agree to terms and conditions box. Click Create User button.
A series of pages and prompts follows to provide guidance through profile set up and user preference definitions.
USER NAME REQUIREMENT
The following are the minimum user name requirements:  User name must begin with a letter.
User name has a minimum of four and a maximum
of 37 characters.
User name is not case sensitive.
User name cannot be a email address  User name must be unique. If user name used is
already in use, a message indicating so will appear.
PASSWORD REQUIREMENT
The following are the password requirements:  Upper and lower case combinations are allowed.
At least one number must be used.
Minimum of six characters.
Page 15
7-Day Programmable iComfort Wi‐Fi® Flex Thermostat
15
Firmware Update
FIRMWARE UPDATE BUTTON
1. Firmware Update (Off) – No automatic firmware updates (highly recommend leaving ON)
2. If the status is changed from Off to Auto, it will trigger an immediate check and update for the firmware update. This can take up to 1 hour to complete depending on the user's internet speed, signal strength, internet traffic, etc.
3. Changing from Auto to Off during a download will NOT stop the current download if it is already in process.
4. Firmware Update (Auto) – (Default state). If enabled, the thermostat checks for firmware update a few minutes after commissioning and then every 24 hours in early morning hours.
5. Once a download is completed, the thermostat stops all activity for up to 3 seconds, restarts for 5 seconds, then continues with normal operation. All prior system and user settings are retained (Equipment, programs, Wi-Fi settings, etc.). Note a variation in indoor temperature may be observed after restart. This is normal operation of the thermostat while the temperature sensor algorithms adjust after a restart of the system.
Adding Outdoor Unit and Accessories
OUTDOOR UNIT (AIR CONDITIONER OR HEAT PUMP)
To add (or remove) an outdoor unit, you must be at the “Add or Remove Non-communicating equipment?” screen.
1. Touch the yes button next to Add or Remove Non-communicating equipment?.
2. In the “non-communicating device list” screen, use the arrows to highlight Outdoor Unit Type and touch edit.
3. Touch one of the radio buttons to select a 1-or 2-stage air conditioner unit or a 1-or 2-stage heat pump unit; touch save.
4. Use arrows to highlight any red colored text in the device list (e.g. select Outdoor Unit Capacity; text turns white). Touch edit.
5. Use either the up or down arrows to display the correct size outdoor unit. Touch save to continue.
NOTE - If the defaults are correct, you do not have to make any changes, but you must touch save. When all red text is gone, the back button will appear; touch it to return to the “Add or Remove Non-communicating equipment?” screen.
HUMIDIFIER
Before adding a humidifier, be sure that the:
Page 16
507428-01
16
Humidifier is wired to the equipment interface
module and furnace or air handler control,
Entire system is wired, powered up and you are at
the “Add or Remove Non-communicating equipment?” screen.
To add a humidifier:
1. Touch the yes button on this screen.
2. In the “non-communicating device list” screen, use the arrows to highlight Humidifier (note the current value, Not Installed) and touch edit.
3. Touch one of the radio buttons to select the type of humidifier (or select Not Installed, if removing humidifier); touch save.
4. The previous screen returns, but the current value now shows your selection. Touch the back button.
5. The “Add or Remove...” screen reappears with your addition shown in the system devices list. At this point, you may add more equipment (touch yes) or if finished, touch the next button to advance to the “Adjust a setting...” screen (see page 17).
NOTE - Adding humidity regulating non-communicating devices may be a 2-step procedure:
First the device must be installed and wired. After
the humidifier is installed, the setting under the
"System" mode "Humidification Control Mode" defaults to "Basic".
Second, if you want another mode, i.e. Precision,
Basic Dew Point, or Precision Dew Point, the device requires further configuration (see page 17).
AUXILIARY DEHUMIDIFIER
Before adding a dehumidifier, be sure that:  the dehumidifier is wired to the equipment interface
model and furnace or air handler control.
the entire system is wired, powered up and you are
at the “Add or Remove Non-communicating equipment?” screen.
To add (or remove) a dehumidifier, you must be at the “Add or Remove Non-communicating equipment?” screen.
1. Touch the yes button on this screen.
2. In the “non-communicating device list” screen, use the arrows to highlight Dehumidifier and touch edit. Note the current value (e.g. Not Installed).
3. Touch one of the radio buttons to select the type of dehumidifier (or select Not Installed, if removing dehumidifier); touch save.
4. When you scroll to the Dehumidifier device, (Note the current value, e.g. auxiliary dehumidifier.) Click back to return to the “Add or Remove...” screen.
Page 17
7-Day Programmable iComfort Wi‐Fi® Flex Thermostat
17
5. The “Add or Remove...” screen reappears with your addition shown in the system devices list. At this point, you may add more equipment (touch yes) or if finished, touch the next button to advance to the “Adjust a setting...” screen.
NOTE - The device must be installed and wired. After the dehumidifier is installed, the setting under the "System" mode "Dehumidification Control Mode" defaults to "Basic".
Adjusting Humidification and Dehumidification Settings with Outdoor Units
HUMIDIFICATION SETTINGS — SYSTEM DEVICES SCREEN
Pre-adjustment REQUIREMENTS:
First the device has been installed.
Second, you pressed next at the “Add or
Remove...” screen.
Configure the device as follows:
1. In the “system devices” list, use the arrows to highlight System. Touch edit.
2. In the “System” list, use the arrows to highlight Humidification Control Mode. Touch edit.
3. Touch one of the radio buttons to select the mode of humidification control; touch save. (After saving,
check that the current value now shows the new selection).
4. Touch the back button to return to “Adjust a setting...” screen.
NOTE - If the defaults for the settings are shown in red, you are not required to make any changes, but you must go into the edit tool, and touch save. When all red text is gone, the back button will appear; touch it to return to the “Adjust a setting...” screen.
How Humidification Mode Works
DISPLAY, BASIC AND PRECISION—These modes
allow user control of relative humidity between 15 and 45%. These conditions must be met for either mode to operate:  humidification mode has been enabled, and
the unit is in HEAT mode, and  humidification demand exists (24V present at H),
and
DISPLAY mode indicates humidification is OFF. BASIC mode mode also requires presence of
heating demand [Y for HP heat, or W for gas heat (W may be energized with G de-energized)].
PRECISION—(Available only if Wi-Fi is operational
or outdoor sensor is attached)
Page 18
507428-01
18
Basic Dew Point Control adjustment mode will change the humidification setpoint based on the outdoor temperature and a user-defined dew point adjustment setting.
Precision Dew Point Control adjustment mode will operate when these conditions are met:
humidification mode has been enabled, and
the unit is in HEAT mode, and
humidification demand exists (24V present at H).
HUMIDIFICATION SETTINGS — FEATURE SCREEN
SYSTEM SETTINGS
current indoor humidity is 50%
humidifier
is ON
de-
humidifier
MEDIUM
40
%
set to
50
%
set to
ALL CHANGES MADE ON THIS SCREEN ARE IN STANTLY SAVED.
9:39 am Aug 15, 2012
?
Wi-Fi
OFF
MEDIUM
HIGH
humidifier
display
is ON
humidification
settings
dehumidification
settings
Figure 14. Humidification Controls
1. From the Main Screen, touch the right arrow icon to go the the Features screen.
2. From the Features screen, select system settings.
3. Touch the button of the humidification settings you want to adjust; if it says humidifier OFF, one touch will display a selection for ON.
4. When you touch the set-to button, the arrows appear, allowing you to change to the desired humidity percentage setting.
DEHUMIDIFICATION SETTINGS — SYSTEM DEVICES SCREEN
Pre-adjustment REQUIREMENTS  First the device has been installed
Second, from the “Add or Remove
Non-communicating equipment?”, touch next.
Third, in the “Adjust a setting...” screen, configure
the device as follows:
1. In the “system devices” list, use the arrows to highlight System. Touch edit.
2. Use arrows to highlight Min Dehumidification Setpoint; touch edit. Note the current value (e.g.
45).
3. Use arrows to make changes; touch (After saving,
check that the current value now shows the new selection).
4. Touch the back button to return to “Adjust a setting...” screen.
DEHUMIDIFICATION SETTINGS — FEATURE SCREEN
1. From the Main Screen, touch the right arrow icon to go the the Features screen.
Page 19
7-Day Programmable iComfort Wi‐Fi® Flex Thermostat
19
2. From the Features screen, select system settings.
3. Touch the button of the dehumidification settings you want to adjust; if it says de-humidifier OFF, one touch will display a selection for OFF, MEDIUM or HIGH.
4. Selecting MEDIUM or HIGH will bring on the set-to button.
5. When you touch the set-to button, the arrows appear, allowing you to change to the desired de-humidifier percentage setting.
SYSTEM SETTINGS
current indoor humidity is 50%
humidifier
is ON
de-
humidifier
MEDIUM
40
%
set to
50
%
set to
ALL CHANGES MADE ON THIS SCREEN ARE IN STANTLY SAVED.
9:39 am Aug 15, 2012
?
Wi-Fi
OFF
MEDIUM
HIGH
humidifier
display
is ON
(default is ON)
humidification
settings
dehumidification
settings
Figure 15. Humidifier Controls (Outdoor Unit)
HOW DEHUMIDIFICATION MODE WORK — NO EXTERNAL DEHUMIDIFICATION DEVICE
NOTE - OFF, MEDIUM and HIGH dehumidification modes are also a function of the HVAC system with NO external dehumidification devices installed.
In OFF mode, dehumidification if off.
In MEDIUM mode, dehumidification occurs if these conditions are met and signals are present at specific terminals:
dehumidification has been enabled on installer
settings, and  the unit is in COOL mode, and  dehumidification demand exists (RH above setpoint),
and  cooling demand exists (Y1 energized).
In HIGH mode, dehumidification occurs if all BASIC conditions are true, except cooling demand may or may not be present. Also note that:
Maximum over cool from cooling setpoint is 2ºF. Deadband temperature is limited to a minimum of
5ºF (instead of 3ºF in DRY or MODERATE modes)
because of 2ºF overcooling.
AUXILIARY DEHUMIDIFIER — OUTDOOR UNITS
Control State Conditions
Auxiliary dehumidification is controlled by thermostat.
System must be in cooling mode and have
a call for dehumidification from the thermostat. This will start the auxiliary dehumidifier.
A separate wire from auxiliary dehumidifier
will need to be run to G terminal on indoor unit control to start the blower.
Auxiliary dehumidification is controlled by dehumidi fication control.
Needs a dehumidification demand from the stand-alone dehumidification thermostat and a separate wire run to G terminal on indoor unit to start the blower.
Page 20
507428-01
20
Using the Tests / Diagnostics Features
Blower
HP Heat - 1st Stage
HP Heat - 2nd Stage
Defrost Now
Cooling - 1st Stage
Cooling - 2nd Stage
Gas Heat - 1st Stage
Gas Heat - 2nd Stage
select all
select test to run
deselect all
skip tests
start
Only appears
if test item is
selected
Ö
1
2
3
4
5
Figure 16. Selecting Tests
TO SELECT TESTS TO RUN
Use the following procedure to run tests for various heating and cooling stage operations.
1. Select a specific test (1) to run or use the select all (2) button to run all configurations. Use the deselect all (3) button to un-check desired test.
2. Touch the start button (4) to run all selected tests or touch skip tests (5) to end the test procedure.
3. After the tests are completed or you have selected skip test select the exit button to end.
NOTE - Test mode lasts for 30 minutes (with the temperature updating every 30 seconds) except for the defrost test, which lasts 30 seconds. Tests feature provides the technician time to manually verify the equipment operation.
The tests feature is available after set up has been completed once. After you touch next in the final set up screen, the “select tests to run” screen (figure 16) will appear. (If you want you may skip tests; touch skip tests.)
To run all of the tests, touch select all. All boxes in the list of tests will be checked. Or, touch box(es) next to test(s) to run certain tests.
After the tests have been started, the screen will describe which test is running and show a diagnostic summary of each test (see figure 17). After reviewing the results and concluding that no further tests are needed, touch next to proceed to next test. The technician must verify that the test procedure is producing the desired result at the equipment.
After pressing next after the final test, the Testing finished screen will appear (figure 18). At this point, use the EXIT button (if you have completed the required set up), or use diagnostics button (to analyze the system), or use equipment button (if you wish to make any changes to device details).
Page 21
7-Day Programmable iComfort Wi‐Fi® Flex Thermostat
21
9:39 am Aug 15, 2012
Heating Rate Blower CFM Demand Blower Off Delay Blower On Delay Indoor Blower RPM Indoor Blower Power Flame Current Flame Sense Outdoor Temperature
current test: Blower
Check Blower Operation
% 1400CFM Off Off 0
0.0000%
0.000mA No Flame 63ºF
nextcancel
setup
tests equipment alerts diagnostics
Figure 17. Typical Tests Results Screens
9:39 am Aug 15, 2012
nextcancel
setup
tests equipment
alerts
diagnostics
press 'EXIT' button to start normal operation
The Testing Process is finished
press 'tests' button to run more tests
Figure 18. Testing Finished Screen
Touch confirm to continue system configuration; the screen will change to the system discovery screen. At this point, the program goes through the same set up as the initial set up process which begins on page 3.
NOTE - “Compatible device found” screen (shown below) appears only when a device has been removed and replaced with a compatible device.
Missing Device Equipment Type No. Model No. (control model no.) Serial No. (control serial no.)
Found Compatible Device Equipment Type No. Model No. (control model no.) Serial No. (control serial no.)
Settings were not copied
iComfort® Equipment Interface Module
The iComfort® Equipment Interface Module (EIM) can be configured in the following set ups:
Thermostat, Equipment Interface Module with a (conventional) indoor and outdoor units.
1. Wiring—See Communicating System and Optional Accessories Wiring diagrams.
D 4-conductor thermostat wire from the iComfort
Wi‐Fi® Flex thermostat to the equipment
interface module (R, i+, i-, C)
D Up to 8-conductor thermostat wire from the
conventional furnace and outdoor unit terminal strips to the equipment interface module (R, C, O, Y1, Y2, G, W1, W2 and W3).
D Wiring as required for accessories
2. DO NOT cut any option link on furnace control.
Page 22
507428-01
22
3. After the entire system is wired, power up the system; the iComfort Wi‐Fi® thermostat will check the system for equipment interface module.
4. On the thermostat, go past the Add or remove
non-communicating devices to the To adjust a setting screen. Select System from the device list
using the up/down arrows and press the edit button
5. Select Balance Point Control and press edit. Use the down arrow to select Enabled and press save. High and Low Balance Points will appear in red.
6. Complete Balance Point Control by editing the High and Low Balance Points. It is not necessary to change the defaults, but you must save each setting. The red settings will go away after pressing save. Press the back button to return to the adjust screen.
7. Use the arrows to select Furnace from system devices list; press edit. From this Furnace screen you will have access to the various airflow settings. Set the system air volumes according the needs of the home. When you change certain settings, the system will prompt you to please view and save all red settings. Use the arrows to select the red settings and press edit. Either make changes or not, but press save either way. The red settings will go away after pressing save. When all CFM settings are complete, press the back button. Press next step to advance to the tests button.
8. Test the system operation and confirm the heat pump unit is electrically energized and operational. Press done.
9. Exit the installer set up mode by selecting the EXIT button.
TIPS
High and Low Balance points are enabled and
adjusted under the installer section of the thermostat. In the equipment button select “System” and press edit. Scroll down to Balance Point Control and press edit and select Enabled and then save.
An outdoor temperature sensor is required
(field-provided) and connected to the outdoor air sensor terminal on the Equipment Interface Module.
To display the outdoor temperature on the home
screen of the thermostat, you must turn on the Outdoor Temp Display.
Using the Secure Web Portal
Access all the great Wi-Fi enabled features on your iComfort® thermostat from our secure web portal.
www.myicomfort.com
After signing in, you’ll be able to view your iComfort system settings, adjust the temperature and view reminders and alerts – just as you would on your iComfort thermostat at home. With a familiar look and settings this simple, you should feel right at home. Don’t forget to check out the available Apps and skins.
Page 23
7-Day Programmable iComfort Wi‐Fi® Flex Thermostat
23
1. From the Home screen, press the Features button.
2. Select Display Settings
3. Select outdoor temp display. Options are off, internet and sensor.
indoor temperature
indoor humidity is 41%
cool-to
set temp
75
heat to
70
heat
or
cool
outdoor
temperature
80
touch to go to Features
use arrows
to change
temperature
Outdoor
temperature
system is cooling
9:39 am Aug 15, 2012Wi-Fi
?
enter
away
fan is
OFF
fan is AUTO
forecast
Hi 85 Lo 60
From the web portal welcome page, you may also click on links to launch an interactive demo or learn more about iComfort.
Skins
By adding a skin and matching skin image screen-saver to your iComfort Wi-Fi, you can coordinate it with the decor in any room. Skins are available in many colors, patterns and designs.
Skins can be ordered from nuvango.com
Go to Shop > All Products and scroll down to
EVERYTHING ELSE and select LENNOX
ICOMFORT
After ordering the skin, the company will email the image file (.jpg) to you. The frame skin will be mailed to you as well. The skin image can be uploaded to the iComfort Wi-Fi thermostat from the consumer portal site (www.myicomfort.com) under the tab ”skins”.
Screen-Saver
You can also customize the screen-saver by uploading your own photo on· www.myicomfort.com under the tab ”skins”. Image must be 800x480 DPI in JPG format.
HOW DO I TURN ON SCREEN-SAVER
1. From the thermostat Home screen, press .
2. Press the display setting button.
3. Press the screen saver button.
4. From the pop-up menu, select either on for the default screen-saver or skins for your custom uploaded image. The skin picture will appear after 30 seconds of inactivity.
When set to off, the screen stays on.  When set to on, after 30 seconds of inactivity
the screen will go blank
When set to skins and no skin or custom image
has been uploaded, the screen will display
Page 24
507428-01
24
LENNOX after 30 seconds of inactivity. If a skin or custom image has been uploaded, after 30 seconds of inactivity, the image will be displayed.
Accessing Installer Screens and Changing Equipment Parameters
To access the installer screens after the unit has been placed in operation and the user home screen is displayed, touch the “Lennox” logo and hold for 5 seconds. The system will access the installer screens.
A message screen stating “Qualified Lennox equipment installer warning” screen appears.
1. When pressing yes, the thermostat will search for equipment interface module.
2. When pressing no, the thermostat returns to the main screen.
3. When pressing reset, the thermostat resets all parameters to factory default, searches for communicating equipment and erases all information concerning conventional equipment previously stored in the thermostat.
After initial installation, if an alert is present when you are making changes to settings, no action on the alert is mandatory.
Press equipment if you need to set up equipment parameters and edit details of devices in the system.
Press diagnostics if you need to analyze the system (see page 20).
If any component of the HVAC system has been changed, e.g. replacing an outdoor sensor, reconfiguring the system will be required. To begin reconfiguring a system (after you have accessed the program from the Lennox logo [previous page]), touch the setup button. The “Start system configuration” screen will appear. Press start to proceed. The “Re-configure confirmation” screen will appear. This reminder notes that system configuration may affect some existing device settings and prompts to confirm or cancel the configuration process.
Press confirm to continue system configuration; the screen will change to the system discovery screen. At this point, the program goes through the same set up as the initial set up process which begins on page 3.
NOTE - “Compatible device found” screen (shown below) appears only when a device has been removed and replaced with a compatible device.
Missing Device Equipment Type No. Model No. (control model no.) Serial No. (control serial no.)
Found Compatible Device Equipment Type No. Model No. (control model no.) Serial No. (control serial no.)
Settings were not copied
Page 25
7-Day Programmable iComfort Wi‐Fi® Flex Thermostat
25
ADJUSTING EQUIPMENT PARAMETERS AFTER INITIAL INSTALLER SET UP
1. From the Home Screen, touch and hold Lennox until the warning screen appears. Press yes to continue.
2. Press equipment to change equipment parameters and edit details of devices in the system without having to re-run the set up program.
3. Select the equipment button to continue. The
system devices screen will open. Use the arrows to select a device and touch edit.
4. Use the arrows to highlight a setting and then touch edit.
5. When finished, touch back; equipment parameters screen then touch next. “Select tests to run screen appears"; either run tests as before or touch skip tests.
Page 26
507428-01
26
Wiring Diagrams
Figure 19. Thermostat and Conventional Indoor Unit and Air Conditioner
Page 27
7-Day Programmable iComfort Wi‐Fi® Flex Thermostat
27
Figure 20. Thermostat and Conventional Indoor Unit and Heat Pump
Page 28
507428-01
28
iComfort Wi‐Fi
®
Outdoor Unit
iComfort Wi‐Fi
®
Flex Thermostat
Single wire to
terminal C
Single wire to terminal C
Unused wires
RSBus
Minimum wire size is 18 gauge
Maximum total length of all connections on the RSBus is limit ed to 1500 ft. (450 m). Max. length between components is 300 ft. (90 m).
Note: iComfort Wi‐Fi® Flex thermostat does not require shielded cable wiring.
BEST PRACTICES! Keep all communication wiring as far away from house electric al wiring and large electrical appliances as possible (15' [5m] recommended).
iComfort Wi‐Fi
®
Equipment Interface
Module
Unused wires
Figure 21. Thermostat Wire Termination in Communicating System (Electrical Noise)
Page 29
7-Day Programmable iComfort Wi‐Fi® Flex Thermostat
29
Table 2. Alert Codes and Troubleshooting
Critical alerts are displayed on Home (user) screen, in the Homeowner alert button, and in the Installer alert button. Minor and Moderate alerts are found only in the Installer alert button.
Alert
Code
Priority Alert Text Steps to clear
10 Critical
(Thermostat) The thermostat has found an unknown device on the sys tem.
The room thermostat has found an unknown device on the system. An unknown device is seen by the room thermostat in or outside of configura
tion mode. Clear by reconfiguring the system
11 Critical
(Thermostat) The thermostat cannot find a previously installed unit.
Check all connections and cycle system power. If problem persists, clear by reconfiguring the system. Press the setup tab, touch start, and touch confirm.
12 Critical
(Thermostat) The thermostat cannot find an iComfort®enabled equipment interface module.
Thermostat did not find an Indoor Unit. Make sure there is an iComfort® equip ment interface module is on the system. Check R, i+, i and C connections, ohm wires and cycle power. Replace equipment interface module control if there is no response.
14 Critical
(Thermostat) The thermostat found more than one thermostat, more than one indoor unit, or more than one out door unit on the system.
Check wiring and remove duplicate equipment. Reconfigure system.
18 Minor
(Thermostat) The outside temperature is below the level where the heat pump is programmed to heat the home. The system will not use the heat pump to warm your home.
Notification only  Outdoor Temp is below the Low Balance Point. Heat Pump will not be used to service a heating demand.
19 Minor
(Thermostat) The outside temperature is higher than the level where the fur nace or electric heat is programmed to work. The system will only use the heat pump to warm your home.
Notification only  Outdoor Temp is above the High Balance Point. Indoor Unit (furnace or airhandler) will not be used to service a heating demand.
Page 30
507428-01
30
Table 2. Alert Codes and Troubleshooting
Critical alerts are displayed on Home (user) screen, in the Homeowner alert button, and in the Installer alert button. Minor and Moderate alerts are found only in the Installer alert button.
Alert
Code
Steps to clearAlert TextPriority
29 Critical
(Thermostat) The thermostat is read ing an indoor temperature that is high er than 99ºF. The thermostat will not allow any heating operation to begin until it senses a temperature lower than 99ºF.
Indoor temperature rose above 99ºF during a heating or cooling demand. Heating operation is not allowed. Check to ensure that Heating Equipment is not stuck ON (reversing valve, etc.). Check the accuracy of the thermostat temperature sensor. Select cooling system mode to cool the indoor space.
30 Moderate
(Thermostat) The thermostat is read ing an indoor temperature that is lower than 40ºF. The thermostat will not al low any cooling operation to begin un til it senses a temperature higher than 40ºF.
Indoor Temp fell below 40ºF. Cooling operation is not allowed. Check to ensure that cooling equipment is not stuck ON. Check accuracy of the thermostat temperature sensor. Select heating system mode to heat the indoor space to above 40ºF.
31 Critical
(Thermostat) The thermostat has lost communication with the (furnace, airhandler or outdoor unit) for more than 3 minutes.
[Indicated unit] has not communicated with thermostat for more than 3 minutes. Check connections. Ohm wires. If fault persists, then cycle power. Fault clears after communication is restored.
32 Moderate
(Thermostat) The (furnace, airhandler or outdoor unit) is resetting itself.
[Indicated unit] is resetting itself. This event may occur during a power outage or power fluctuation in the system. If persistent or if it coincides with the sys tem operation then proceed with the following steps. Check the power connec tions, check the amp draw at the transformer (the transformer maybe over loaded) and check 24VAC voltage at the DEVICE. The alarm is only cleared by pressing the clear button on the Installer Alerts Tab. If the fault persists after checking the connections, replace the unit's control board.
34 Critical
(Thermostat) The thermostat does not know the capacity (tonnage) of the (furnace, airhandler or outdoor unit). Please program the correct capacity of the (furnace, airhandler or outdoor
unit).
[Indicated unit] is missing the programmed unit capacity. Go to [Indicated unit] and program the unit capacity manually. See the unit IOM for programming instructions. Remove power to thermostat before programming the unit control board. Once programming is complete, reconnect thermostat wires and recon figure system.
Page 31
7-Day Programmable iComfort Wi‐Fi® Flex Thermostat
31
Table 2. Alert Codes and Troubleshooting
Critical alerts are displayed on Home (user) screen, in the Homeowner alert button, and in the Installer alert button. Minor and Moderate alerts are found only in the Installer alert button.
Alert
Code
Steps to clearAlert TextPriority
36 Critical
(Thermostat) The system has been heating for at least 15 minutes, without a demand for heating.
Run the system in diagnostic mode and verify that it matches actual equipment operation. Check for other alarms/codes that may be preventing the system from operating as expected.
Step 1: Check all heating equipment to determine cause of heating demand. Step 2: Recycle power.
System will clear code when it detects condition has cleared.
37 Critical
(Thermostat) The system has been cooling for at least 15 minutes, without a demand for cooling.
Run the system in diagnostic mode and verify that it matches actual equipment operation. Check for other alarms/codes that may be preventing the system from operating as expected.
Step 1: Check all cooling equipment to determine cause of cooling demand. Step 2: Recycle power.
System will clear code when it detects condition has cleared.
38 Critical
(Thermostat) The system has not been able to turn on the heating for more than 45 minutes. The system will go offline for 60 minutes and try again.
Run the system in diagnostic mode and verify that it matches actual equipment operation. Check for other alarms/codes that may be preventing the system from operating as expected.
Step 1: Check all heating equipment to determine cause. Step 2: Recycle power.
System will clear code when it detects condition has cleared.
39 Critical
(Thermostat) The system has not been able to turn on the cooling for more than 45 minutes. The system will go offline for 60 minutes and try again.
Run the system in diagnostic mode and verify that it matches actual equipment operation. Check for other alarms/codes that may be preventing the system from operating as expected.
Step 1: Check all cooling equipment to determine cause. Step 2: Recycle power.
System will clear code when it detects condition has cleared.
120 Moderate
(Thermostat / Furnace / Air Handler / Outdoor Unit / Equipment Interface Module) There is a delay in the (Ther
mostat, furnace, airhandler or out door unit) responding to the system.
Typically, this alarm/code does not cause any issues and will clear on its own. The alarm/code is usually caused by a delay in the outdoor unit responding to the thermostat. Check all wiring connections. Cleared after unresponsive device responds to any inquiry.
Page 32
507428-01
32
Table 2. Alert Codes and Troubleshooting
Critical alerts are displayed on Home (user) screen, in the Homeowner alert button, and in the Installer alert button. Minor and Moderate alerts are found only in the Installer alert button.
Alert
Code
Steps to clearAlert TextPriority
124 Critical
(Thermostat / Furnace / Air Handler / Outdoor Unit / Equipment Interface Module / Damper Control Module)) The thermostat has lost communica tion with the (furnace, airhandler or outdoor unit) for more than 3 minutes.
Equipment lost communication with the thermostat. Check the wiring connec tions, ohm wires and cycle power. The alarm stops all associated HVAC oper ations and waits for a heartbeat message from the unit that's not communicat ing. The alarm/fault clears after communication is reestablished.
131 Critical
(Thermostat / Furnace / Air Handler / Outdoor Unit / Equipment Interface Module / Damper Control Module)) The (Thermostat, furnace, airhandler or outdoor unit) control parameters are corrupted.
Reconfigure the system. Replace the control if heating or cooling is not avail able.
132 Critical
(Air Handler / Damper Control Mod ule) The device's control software is corrupted.
Recycle power. If failure reoccurs, replace the control. System reset is re quired to recover.
180 Critical
(Furnace / Air Handler / Outdoor Unit/ Equipment Interface Module) The thermostat has found a problem with the (furnace, airhandler or outdoor unit) outdoor sensor.
In normal operation after control recognizes sensors, the alarm will be sent if valid temperature reading is lost. Compare outdoor sensor resistance to tem perature/resistance charts in unit installation instructions. Replace sensor pack if necessary. At the beginning of (any) configuration, furnace or airhandler control will detect the presence of the sensor(s). If detected (reading in range), appropriate feature will be set as 'installed' and shown in the 'About' screen. The alarm/fault will clear upon configuration, or sensing normal values.
290 Critical
(Furnace) There is a problem with the furnace ignition circuit.
The system will go into Watchguard mode. Measure resistance of hot surface igniter. Replace the hot surface ignitor it is not within specifications. The alarm/ fault will clear on next successful ignition.
345 Critical
(Air Handler / Equipment Interface Module / Heat Pump) The “O” relay on the airhandler has failed. Either the pilot relay contacts did not close or the relay coil did not energize.
O relay / Stage 1 failed. Pilot relay contacts did not close or the relay coil did not energize. Replace control. Cleared after the fault recovered following reset.
Page 33
7-Day Programmable iComfort Wi‐Fi® Flex Thermostat
33
Table 2. Alert Codes and Troubleshooting
Critical alerts are displayed on Home (user) screen, in the Homeowner alert button, and in the Installer alert button. Minor and Moderate alerts are found only in the Installer alert button.
Alert
Code
Steps to clearAlert TextPriority
347 Critical
(Furnace / Air Handler / Equipment Interface Module) The “Y1” relay on the (furnace or airhandler) has failed. Either the pilot relay contacts did not close or the relay coil did not ener gize.
Operation stopped. Y1 relay / Stage 1 failed. (Pilot relay contacts did not close or the relay coil did not energize; no input back to IFC chip). Critical Alert. Cleared after reset and Y1 input sensed.
348 Critical
(Furnace / Air Handler) The “Y2” relay on the (furnace or airhandler) has failed. Either the pilot relay contacts did not close or the relay coil did not energize.
Y2 relay / Stage 2 failed. (Pilot relay contacts did not close or the relay coil did not energize; no input back to IFC chip). Critical Alert. Cleared after reset and Y1 input sensed.
380
Moderate
/ Critical
(Equipment Interface Module) Inter lock relay failure (IFC or AHC mode only)
Interlock relay is energized, but input is not sensed after 3 seconds. There will be no heating or cooling due to this error. Deenergize interlock relay and ener gize after 5 minutes if demand is still present.
381
Moderate
/ Critical
(Equipment Interface Module) Inter lock relay stuck (IFC or AHC modes only)
Interlock relay continuously sensed (with relay off). No heating and cooling operations. Alarm clears 30 seconds after fault clears.
382 Moderate
(Equipment Interface Module) Relay W1 failure (IFC and AHC modes only)
W1 relay energized, but input is not sensed after three seconds.
420 Critical
(Outdoor Unit) The “W” output termin al on the outdoor unit is not wired cor rectly
Defrost cycle lasts longer than 20 minutes. Check heat pump operation. Cleared when W1 signal is removed. Applicable only in communicating mode with noncommunicating heat pump.
594
Moderate
/ Critical
(Equipment Interface Module) Precoil discharge air temperature sensor problem (DFM mode only). Advances from moderate to critical after ten (10) minutes.
Interlock relay energized, but input not sensed after 3 seconds. No heating and cooling operations. Deenergize interlock relay and reenergized 5 minutes later if demand is still present. Alarm clears 5 minutes after fault clears.
Page 34
507428-01
34
Table 2. Alert Codes and Troubleshooting
Critical alerts are displayed on Home (user) screen, in the Homeowner alert button, and in the Installer alert button. Minor and Moderate alerts are found only in the Installer alert button.
Alert
Code
Steps to clearAlert TextPriority
600 Critical
Compressor has been cycled OFF on utility load shedding.
Load shedding function: Provides a method for a local utility company to limit the maximum power level usage of the outdoor unit. The feature is activated by applying 24 volts AC power to the L and C terminals on the outdoor control.
601 Critical
Outdoor unit has been cycled OFF on low temperature protection.
Low temperature Protection: Outdoor unit will not operate when the outdoor temperature is at or below 4°F (20°C). If the unit is operating and the outdoor temperature drops below 4°F (20°C), the unit will continue to operate until the room thermostat is satisfied or the outdoor temperature drops to 15°F (26°C). (Outdoor unit ambient sensor provides temperature readings).
700 Moderate
(Thermostat) The temperature sensor in the thermostat is not working prop erly.
Recalibrate thermostat to clear. Replace thermostat if needed.
701 Moderate
(Thermostat) The thermostat is read ing indoor temperatures above the preprogrammed limit.
Recalibrate thermostat to clear; cool thermostat; adjust setpoint. Replace ther mostat, if needed.
702 Moderate
(Thermostat) The thermostat is read ing indoor temperatures below the preprogrammed limit.
Recalibrate thermostat to clear; warm thermostat; adjust setpoint. Replace thermostat, if needed.
703 Moderate
(Thermostat) The humidity sensor in the thermostat is not working properly.
Recalibrate thermostat to clear; adjust setpoint. Replace thermostat, if needed.
704 Moderate
(Thermostat) The thermostat is read ing indoor humidity levels above the preprogrammed limit.
Recalibrate thermostat to clear. Replace thermostat, if needed.
705 Moderate
(Thermostat) The thermostat is read ing indoor humidity levels below the preprogrammed limit.
Recalibrate thermostat to clear. Replace thermostat, if needed.
Ohm
Check
The ohm reading in the system is either too high or too low.
Ohm reading between i+ and i anywhere on the RSBus with supply power off should be between 70 and 90 ohms. If above 90 ohms, check and repair wir ing, splices or other wiring defects that may be causing the excessive resist ance. If less than 70 ohms, check for shorted wires.
Page 35
7-Day Programmable iComfort Wi‐Fi® Flex Thermostat
35
HOMEOWNER SERVICE ALERT CODES
Number Value Number Value Number Value Number Value Number Val ue
3000 Filter 1 3002 Humidifier
Pad
3004 Maintenance 4000 User Wi-Fi state
change, disable
4002 Image file down
load failed
3001 Filter 2 3003 UV Light 3005 PureAir Main
tenance
4001 Firmware download
failed
Loading...