Lennox Merit 10HPB, 10HPB18, 10HPB24, 10HPB30, 10HPB36 Installation Instructions Manual

...
Page 1
Page 1
504,828M
*P504828M*
06/04
*2P0604*
2003 Lennox Industries Inc.
Dallas, Texas, USA
10HPB Outdoor Units
Lennox Merit® Series 10HPB outdoor units are approved and warranted only for installation with specially matched indoor coils, line sets, and refrigerant control systems as designated by Lennox. Refer to Lennox Engineering Handbook for expansion valve kits which must be ordered separately.
Shipping and Packing List
1 − Assembled 10HPB outdoor unit
1 − Coupling (18, 24 and 30)
Check unit for shipping damage. Consult last carrier imme­diately if damage is found.
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, person­al injury or loss of life. Installation and service must be performed by a qualified installer or service agency.
IMPORTANT
The Clean Air Act of 1990 bans the intentional vent­ing of refrigerant (CFC’s and HCFC’s) as of July 1,
1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarcera­tion may be levied for noncompliance.
INSTALLATION INSTRUCTIONS
10HPB Series Units
HEAT PUMP UNITS
1−1/2 through 5 tons 504,828M 06/04
Supersedes 02/04
Table of Contents
10HPB Outdoor Units 1. . . . . . . . . . . . . . . . . . . . . . . . . . .
Shipping & Packing List 1. . . . . . . . . . . . . . . . . . . . . . . . .
General Information 1. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit Dimensions 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setting the Unit 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Refrigerant Piping 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Refrigerant Metering Device 10. . . . . . . . . . . . . . . . . . . .
Manifold Gauge Set 10. . . . . . . . . . . . . . . . . . . . . . . . . . .
Service Valves 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Leak Testing 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Evacuation 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Start−Up 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Charging 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Operation 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Defrost System 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maintenance 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Optional Accessories 18. . . . . . . . . . . . . . . . . . . . . . . . . .
Start−Up and Performance Check List 18. . . . . . . . . . . .
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
General Information
These instructions are intended as a general guide and do not supersede national or local codes in any way. Authori­ties having jurisdiction should be consulted before instal­lation.
WARNING
This product and/or the indoor unit it is matched with may contain fiberglass wool.
Disturbing the insulation during installation, mainte­nance, or repair will expose you to fiberglass wool dust. Breathing this may cause lung cancer. (Fiber­glass wool is known to the State of California to cause cancer.)
Fiberglass wool may also cause respiratory, skin, and eye irritation.
To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor.
Lennox Industries Inc.
P.O. Box 799900 Dallas, TX 75379−9900
Litho U.S.A.
Page 2
Page 2
10HPB Unit Dimensions − inches (mm)
Side View
vapor &
liquid line
connection
discharge air
Side View
Top View
A
outdoor
coil fan
compressor
inlet
air
B
24-1/4
(616)
2-3/4 (70)
24-1/4
(616)
electrical
inlets
optional unit stand-off kit (4) (field−installed)
4-3/8 (111 )
6-3/8 (162)
6-3/8 (162)
Top View Base Section
3/4
(19)
4-3/8
(111 )
4-3/8
(111)
4-3/8 (111 )
4-3/8 (111 )
4-3/8 (111 )
coil drain outlets
(around perimeter of base)
optional unit stand-off kit (4) (field−installed)
liquid line
connection
vapor line
connection
2 (51)
COMPRESSOR
inlet
air
inlet
air
inlet
air
Model No.
A B
10HPB18
in. 25 24-1/4
10HPB18
10HPB24
mm 635 616
in. 29 28-1/4
10HPB30
mm 737 718
10HPB36 10HPB42
in. 33 32-1/4
10HPB42
10HPB48 10HPB60
mm 838 819
Page 3
Page 3
Setting the Unit
CAUTION
In order to avoid injury, take proper precaution when lifting heavy objects.
CAUTION
Sharp sheet metal edges can cause injury. When installing the unit, avoid accidental contact with sharp edges.
These units operate under a wide range of weather condi­tions; therefore, several factors must be considered when positioning the outdoor unit. The unit must be positioned to give adequate clearances for sufficient airflow and servic­ing. A minimum clearance of 24 inches (610 mm) between multiple units must be maintained. Refer to figure 1 for installation clearances.
see
note
Installation Clearances
see
note
NOTE − A service clearance of 30" (762 mm) must be main­tained on one of the sides adjacent to the control box. Clear­ance to one of the other three sides must be 36" (914 mm). Clearance to one of the remaining two sides may be 12" (304 mm) and the final side may be 6" (152 mm).
see
note
NOTE − A clearance of 24" (610 mm) must be maintained between two units. NOTE − 48" (1219 mm) clearance required on top of unit. Maximum soffit overhang is 36" (914 mm).
see
note
Figure 1
1 − Place a sound-absorbing material, such as Isomode,
under the unit if it will be installed in a location or posi­tion that will transmit sound or vibration to the living area or adjacent buildings.
2 − Install the unit high enough above the ground or roof to
allow adequate drainage of defrost water and prevent ice buildup.
3 − In heavy snow areas, do not locate the unit where drift-
ing will occur. The unit base should be elevated above the depth of average snows.
NOTE − Elevation of the unit may be accomplished by constructing a frame using suitable materials. If a sup­port frame is constructed, it must not block drain holes in unit base.
4 − When installed in areas where low ambient tempera-
tures exist, locate unit so winter prevailing winds do not blow directly into outdoor coil.
5 − Locate unit away from overhanging roof lines which
would allow water or ice to drop on, or in front of, coil or into unit.
Slab Mounting − Figure 2
When installing a unit at grade level, the top of the slab should be high enough above the grade so that water from higher ground will not collect around the unit. See figure 2. Slab should have a slope tolerance away from the building of 2 degrees or 2 inches per 5 feet (51 mm per 1524 mm). This will prevent ice from building up under the unit during a defrost cycle. Refer to roof mounting section for barrier construction if unit must face prevailing winter winds.
Figure 2
Slab Mounting At Ground Leve
l
discharge air
Mounting slab must slope away from building.
ground level
structure
Roof Mounting − Figure 3
Install the unit a minimum of 6 inches (152 mm) above the roof surface to avoid ice build−up around the unit. Locate the unit above a load bearing wall or area of the roof that can adequately support the unit. Consult local codes for rooftop applications.
Page 4
Page 4
If unit coil cannot be mounted away from prevailing winter winds, a wind barrier should be constructed. Size barrier at least the same height and width as outdoor unit. Install bar­rier 24 inches (610 mm) from the sides of the unit in the di­rection of prevailing winds.
wind barrier
inlet air
inlet air
inlet air
inlet air
prevailing winter winds
Rooftop Application
Wind Barrier Construction
Figure 3
Electrical
WARNING
Unit must be grounded in accordance with national and local codes. Electric Shock Hazard. Can cause injury or death.
1 − Install line voltage power supply to unit from a properly
sized disconnect switch.
2 − Ground unit at unit disconnect switch or to an earth
ground.
NOTE − To facilitate conduit, a hole is in the bottom of the control box. Connect conduit to the control box us ing a proper conduit fitting.
NOTE − Units are approved for use only with copper conductors.
24V, Class II circuit connections are made in the low voltage junction box. Refer to figure 4 for field wiring diagram.
NOTE − A complete unit wiring diagram is located in side the unit control box cover.
3 − Install room thermostat (ordered separately) on an in-
side wall approximately in the center of the conditioned area and 5 feet (1.5 m) from the floor. It should not be installed on an outside wall or where it can be effected by sunlight, drafts or vibrations.
4 − Install voltage wiring from outdoor to indoor unit and
from thermostat to indoor unit. See figures 5 and 6.
Page 5
Page 5
Typical Wiring Field Wiring Diagram
Figure 4
*
*
*May be optional
R
C
W1
Y1
O
G
R
C
W1
W2
W3
G
reversing valve
10HPB and Blower Unit
Thermostat Designations
(Some connections may not apply.
Refer to specific thermostat and indoor unit.)
Thermostat
Indoor
Unit
R
C
W1
Y1
O
Outdoor
Unit
Figure 5
power
power
common common
1st. stage aux. heat
1st. stage aux. heat
indoor blower
compressor
R
C
W1
Y1
O
G
R
C
W1
W2
W3
G
10HPB and Blower Unit
Thermostat Designations
(with auxiliary heat)
(Some connections may not apply.
Refer to specific thermostat and indoor unit.)
Thermostat
Indoor
Unit
Outdoor
Unit
E
R
C
W1
Y1
O
reversing valve
indoor blower
compressor
power
power
common common
1st. stage aux. heat
1st. stage aux. heat
emergency heat
Figure 6
Page 6
Page 6
Refrigerant Piping
Field refrigerant piping consists of liquid and vapor lines from the outdoor unit (sweat connections) to the indoor coil (flare or sweat connections). Use Lennox L15 (sweat, non­flare) series line sets as shown in table 1 or use field-fabri­cated refrigerant lines. Refer to Refrigerant Piping Guide (Corp. 9351−L9) for proper size, type, and application of field−fabricated lines. Valve sizes are also listed in table 1.
Table 1
Refrigerant Line Sets
Valve Field Size
Connections
Recommended Line Set
Model
Liquid
Line
Vapor
Line
Liquid
Line
Vapor
Line
L15
Line Sets
−18
3/8 in.
(10 mm)
5/8"
(15.9 mm)
5/16"*
(7.9 mm)
5/8"
(15.9
mm)
L15−21
15 ft. − 50 ft.
(4.6 m − 15
m)
−24
−30
3/8 in.
(10 mm)
3/4"
(19 mm)
5/16"*
(7.9 mm)
3/4"
(19 mm)
L15−31
15 ft. − 50 ft.
(4.6 m − 15 m)
−36
3/8 in.
(10 mm)
3/4"
(19 mm)
3/8"
(9.5 mm)
3/4"
(19 mm)
L15−41
15 ft. − 50 ft.
(4.6 m − 15 m)
−42
−48
3/8 in.
(10 mm)
7/8"
(22.2 mm)
3/8"
(9.5 mm)
7/8"
(22.2
mm)
L15−65
15 ft. − 50 ft.
(4.6 m − 15 m)
−60
3/8 in.
(10 mm)
1−1/8"
(28.5 mm)
3/8"
(9.5 mm)
1−1/8"
(28.5
mm)
Field
Fabricated
*Use reducer supplied in bag assembly
NOTE − Units are designed for line sets of up to fifty feet (15 m). For applications longer than fifty feet, consult the Len-
nox Refrigerant Piping Guide (Corp. 9351−L9). Select line set diameters from table 1 to ensure that oil returns to the compressor.
Installing Refrigerant Line
During the installation of any heat pump or a/c system, it is important to properly isolate the refrigerant lines to prevent unnecessary vibration. Line set contact with the structure (wall, ceiling or floor) causes some objectionable noise when vibration is translated into sound. As a result, more energy or vibration can be expected. Closer attention to line set isolation must be observed.
Following are some points to consider when placing and installing a high−efficiency outdoor unit:
1- Placement − Be aware some localities are adopting
sound ordinances based on how noisy the unit is from the adjacent property not at the original installation. Install the unit as far as possible from the property line. When possible, do not install the unit directly outside a window. Glass has a very high level of sound transmis­sion.
2- Line Set Isolation − The following illustrations demon-
strate procedures which ensure proper refrigerant line set isolation. Figure 7 shows how to install line sets on vertical runs. Figure 8 shows how to install line sets on horizontal runs. Figure 9 shows how to make a transition from horizontal to vertical. Finally, figure 10 shows how to place the outdoor unit and line set.
Page 7
Page 7
Installing Vertical Runs of Refrigerant Piping
(new construction shown)
PVC Pipe
Fiberglass
Insulation
Caulk
Outside Wall
Vapor Line
(wrapped with Armaflex)
Liquid Line
IMPORTANT - Refrigerant
lines must not contact
structure.
Outside Wall
Inside Wall
Liquid LineVapor Line
IMPORTANT - Refrigerant
lines must not contact wall.
Wood Block
Between Studs
Strap
Sleeve
Wood Block
Strap
Sleeve
Wire Tie
Wire Tie
Wire Tie
NOTE - Similar installation practices should be used if line set is to be installed on exterior of outside wall.
Figure 7
Page 8
Page 8
Installing Horizontal Runs of Refrigerant Piping
8 feet
8 feet
Metal Sleeve
Strapping Material (around vapor line only)
Tape or Wire Tie
Wire Tie
(around vapor line only)
Floor Joist or
Roof Rafter
Tape or Wire Tie
Strap the vapor line to the joist or rafter at 8 ft. intervals then strap the liquid line to the vapor line.
To hang line set from joist or rafter, use either metal strapping material or anchored heavy nylon wire ties.
Floor Joist or Roof Rafter
Figure 8
Page 9
Page 9
Transitioning from Vertical to Horizontal
Runs of Refrigerant Piping
Liquid Line
Vapor Line
Wrapped in
Armaflex
Strap Liquid Line
To Vapor Line
Metal
Sleeve
Anchored Heavy
Nylon Wire Tie
Automotive
Muffler-Type
Hanger
Wall Stud
Wall Stud
Liquid Line
Vapor Line
Wrapped in
Armaflex
Strap Liquid Line
To Vapor Line
Metal
Sleeve
Figure 9
Outside Unit Placement and Installation
Figure 10
Install unit away from windows .
Two 90° elbows installed in line set will reduce line set vibration.
Page 10
Page 10
Brazing Connection Procedure
1 − Cut ends of the refrigerant lines square (free from nicks
or dents). Debur the ends. The pipe must remain round, do not pinch end of the line.
2 − Before making line set connections, use dry nitrogen to
purge the refrigerant piping. This will help to prevent oxidation and the introduction of moisture into the sys­tem.
3 − Use silver alloy brazing rods (5 or 6 percent minimum
silver alloy for copper−to−copper brazing or 45 percent silver alloy for copper−to−brass or copper−to−steel braz­ing) which are rated for use with HCFC22 refrigerant. Wrap a wet cloth around the valve body and the copper tube stub. Braze the line set to the service valve.
4 − Wrap a wet cloth around the valve body and copper
tube stub to protect it from heat damage during braz­ing. Wrap another wet cloth underneath the valve body to protect the base paint.
NOTE − The tube end must stay bottomed in the fitting during final assembly to ensure proper seating, sealing and rigidity.
5 − Install a field−provided thermal expansion valve (ap-
proved for use with HCFC22 refrigerant) in the liquid line at the indoor coil.
Refrigerant Metering Device
10HPB units are used in check expansion valve systems only. See the Lennox Engineering Handbook for approved TXV match-ups and application information.
Check expansion valves equipped with either Chatleff or flare−type fittings are available from Lennox. Refer to the Engineering Handbook for applicable expansion valves for use with specific match-ups. See table 2 for applicable check expansion valve kits.
If you install a check expansion valve with an indoor coil that includes a fixed orifice, remove the orifice be­fore the check expansion valve is installed.
IMPORTANT
Failure to remove RFC orifice when installing an ex­pansion valve on the indoor coil will result in improp­er operation and damage to the system.
Table 2
Indoor Check And Expansion Valve Kits
Model Kit Number
10HPB18 10HPB24 10HPB30 10HPB36
LB−85759F
10HPB42 10HPB48 10HPB60
LB−85759G
See figure 11 for installation of the check expansion valve.
Metering Device Installation
expansion
valve
o−ring
o−ring
strainer
liquid line
stub
distributor
Figure 11
Manifold Gauge Set
When checking the unit charge, use a manifold gauge set that is equipped with low loss" hoses. Do not use a man­ifold gauge set with anything other than a low loss" hose. See figure 12 for manifold gauge connections.
Page 11
Page 11
Figure 12
10HPB Manifold Gauge Connections (Cooling Cycle)
outdoor
coil
defrost thermostat
expansion/
check valve
biflow
filter / drier
to
HCFC−22
drum
low
pressure
high
pressure
compressor
reversing valve
vapor
line
valve
muffler
Note − Arrows indicate the direction of refrigerant flow.
vapor
service
port
expansion/check
valve
Indoor Unit
Outdoor Unit
liquid line
service
port
gauge manifold
distributor
indoor
coil
Service Valves
The liquid line and vapor line service valves (figures 13 and
14) and gauge ports are used for leak testing, evacuating, charging and checking charge. See table 3 for torque re­quirements.
Each valve is equipped with a service port which has a fac­tory−installed Schrader valve. A service port cap protects the Schrader valve from contamination and serves as the primary leak seal.
Table 3
Torque Requirements
Part Recommended Torque
Service valve cap 8 ft.− lb. 11 NM
Sheet metal screws 16 in.− lb. 2 NM
Machine screws #10 28 in.− lb. 3 NM
Compressor bolts 90 in.− lb. 10 NM
Gauge port seal cap 8 ft.− lb. 11 NM
IMPORTANT
Service valves are closed to the outdoor unit and open to line set connections. Do not open the valves until refrigerant lines have been leak tested and evacuated. All precautions should be exercised to keep the system free from dirt, moisture and air.
To Access Schrader Port:
1 − Remove service port cap with an adjustable wrench.
2 − Connect gauge to the service port.
3 − When testing is completed, replace service port cap.
Tighten finger tight, then an additional 1/6 turn.
To Open Liquid or Vapor Line Service Valve:
1 − Remove stem cap with an adjustable wrench.
2 − Use a service wrench with a hex head extension to back
the stem out counterclockwise as far as it will go.
NOTE − Use a 3/16" hex head extension for liquid line sizes or a 5/16" extension for vapor line sizes.
3 − Replace stem cap. Tighten finger tight, then tighten an
additional 1/6 turn.
To Close Liquid Line Service Valve:
1 − Remove stem cap with an adjustable wrench.
2 − Use a service wrench with a hex head extension to turn
the stem clockwise to seat the valve. Tighten firmly.
NOTE − Use a 3/16" hex head extension for liquid line sizes or a 5/16" extension for vapor line sizes.
3 − Replace the stem cap. Tighten finger tight, then tighten
an additional 1/6 turn.
Ball−Type Vapor Line Service Valve
Vapor line service valves function the same way as the oth­er valves, the difference is in the construction. These valves are not rebuildable. If a valve has failed, you must replace it. A ball valve valve is illustrated in figure 14.
Page 12
Page 12
The ball valve is equipped with a service port with a factory− installed Schrader valve. A service port cap protects the Schrader valve from contamination and assures a leak− free seal.
Service Valve
(Valve Closed)
Schrader valve open
to line set when valve is
closed (front seated)
service
port
service
port cap
stem cap
insert hex
wrench here
(valve front seated)
to outdoor coil
to indoor coil
Service Valve
(Valve Open)
Schrader
valve
service
port
service port
cap
insert hex
wrench here
to indoor coil
to outdoor coil
stem cap
Figure 13
Vapor Line (Ball Type) Service Valve
(Valve Open)
Schrader
valve
stem cap
To open: rotate stem counter-clockwise 90.
To close: use adjustable wrench and
rotate stem clockwise 90.
ball
(shown open)
service port
cap
service
port
field side
unit side
stem
Figure 14
Leak Testing
After the line set has been connected to the indoor and outdoor units, check the line set connections and indoor unit for leaks.
WARNING
Danger of fire. Bleeding the refrigerant charge from only the high side may re­sult in the low side shell and suction tubing being pressurized. Appplication of a brazing torch while pressurized may result in ignition of the refrigerant and oil mixture − check the high and low pressures before unbrazing.
WARNING
Refrigerant can be harmful if it is inhaled. Refrigerant must be used and recovered responsibly.
Failure to follow this warning may result in personal injury or death.
WARNING
Danger of explosion: Can cause equip­ment damage, injury or death. Never use oxygen to pressurize a refrigera­tion or air conditioning system. Oxygen will explode on contact with oil and could cause personal injury.
WARNING
Danger of explosion: Can cause equipment damage, injury or death. When using a high pressure gas such as dry nitrogen to pressurize a refrigeration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kPa).
Using an Electronic Leak Detector or Halide
1 − Connect a cylinder of HCFC-22 to the center port of the
manifold gauge set.
2 − With both manifold valves closed, open the valve on
the HCFC-22 cylinder (vapor only).
3 − Open the high pressure side of the manifold to allow
the HCFC-22 into the line set and indoor unit. Weigh in a trace amount of HCFC-22. [A trace amount is a maxi- mum of 2 ounces (57 g) or 3 pounds (31 kPa) pres­sure.] Close the valve on the HCFC-22 cylinder and the valve on the high pressure side of the manifold gauge set. Disconnect the HCFC-22 cylinder.
4 − Connect a cylinder of nitrogen with a pressure regulat-
ing valve to the center port of the manifold gauge set.
Page 13
Page 13
5 − Connect the manifold gauge set high pressure hose to
the vapor valve service port. (Normally, the high pres-
sure hose is connected to the liquid line port; however, connecting it to the vapor port better protects the man­ifold gauge set from high pressure damage.)
6 − Adjust the nitrogen pressure to 150 psig (1034 kPa).
Open the valve on the high side of the manifold gauge set which will pressurize line set and indoor unit.
7 − After a few minutes, open a refrigerant port to ensure
the refrigerant you added is adequate to be detected. (Amounts of refrigerant will vary with line lengths.) Check all joints for leaks. Purge nitrogen and HCFC-22 mixture. Correct any leaks and recheck.
Evacuation
Evacuating the system of noncondensables is critical for proper operation of the unit. Noncondensables are defined as any gas that will not condense under temperatures and pressures present during operation of an air conditioning system. Noncondensables and water vapor combine with refrigerant to produce substances that corrode copper pip­ing and compressor parts.
IMPORTANT
Use a thermocouple or thermistor electronic vacuum gauge that is calibrated in microns. Use an instrument that reads from 50 microns to at least 10,000 microns.
1 − Connect the manifold gauge set to the service valve
ports as follows:
low pressure gauge to vapor line service valvehigh pressure gauge to liquid line service valve
2 − Connect micron gauge.
3 − Connect the vacuum pump (with vacuum gauge) to the
center port of the manifold gauge set.
4 − Open both manifold valves and start the vacuum
pump.
5 − Evacuate the line set and indoor unit to an absolute
pressure of 23,000 microns (29.01 inches of mercu­ry). During the early stages of evacuation, it is desir­able to close the manifold gauge valve at least once to determine if there is a rapid rise in absolute pressure. A rapid rise in pressure indicates a relatively large leak. If this occurs, repeat the leak testing procedure.
NOTE − The term absolute pressure means the total actual pressure within a given volume or system, above the absolute zero of pressure. Absolute pres­sure in a vacuum is equal to atmospheric pressure mi­nus vacuum pressure.
6 − When the absolute pressure reaches 23,000 microns
(29.01 inches of mercury), close the manifold gauge valves, turn off the vacuum pump and disconnect the manifold gauge center port hose from vacuum pump. Attach the manifold center port hose to a nitrogen cylin-
der with pressure regulator set to 150 psig (1034 kPa) and purge the hose. Open the manifold gauge valves to break the vacuum in the line set and indoor unit. Close the manifold gauge valves.
CAUTION
Danger of Equipment Damage. Avoid deep vacuum operation. Do not use compres­sors to evacuate a system. Extremely low vacuums can cause internal arcing and compressor failure. Damage caused by deep vacuum operation will void warranty.
7 − Shut off the nitrogen cylinder and remove the manifold
gauge hose from the cylinder. Open the manifold gauge valves to release the nitrogen from the line set and indoor unit.
8 − Reconnect the manifold gauge to the vacuum pump,
turn the pump on, and continue to evacuate the line set and indoor unit until the absolute pressure does not rise above 500 microns (29.9 inches of mercury) within a 20−minute period after shutting off the vacuum pump and closing the manifold gauge valves.
9 − When the absolute pressure requirement above has
been met, disconnect the manifold hose from the vacu­um pump and connect it to an upright cylinder of HCFC-22 refrigerant. Open the manifold gauge valves to break the vacuum from 1 to 2 psig positive pressure in the line set and indoor unit. Close manifold gauge valves and shut off the HCFC-22 cylinder and remove the manifold gauge set.
Start−Up
IMPORTANT
If unit is equipped with crankcase heater, it should be energized 24 hours before unit start−up to prevent compressor damage as a result of slugging.
1 − Rotate fan to check for frozen bearings or binding.
2 − Inspect all factory and field-installed wiring for loose
connections.
3 − After evacuation is complete, open the liquid line and
vapor line service valves (counterclockwise) to release refrigerant charge (contained in outdoor unit) into the system.
4 − Replace stem caps and secure finger tight, then tight-
en an additional (1/6) one-sixth of a turn.
5 − Check voltage supply at the disconnect switch. The
voltage must be within the range listed on the unit nameplate. If not, do not start the equipment until the power company has been consulted and the voltage condition has been corrected.
Page 14
Page 14
6 − Set the thermostat for a cooling demand, turn on power
to indoor blower unit and close the outdoor unit discon­nect to start the unit.
7 − Recheck voltage while the unit is running. Power must
be within range shown on the nameplate.
Charging
The unit is factory charged with the amount of HCFC-22 re­frigerant indicated on the unit rating plate. This charge is based on a matching indoor coil and outdoor coil with a 15 foot (4.6 m) line set. For varying lengths of line set, refer to table 4 for refrigerant charge adjustment. A blank space is provided on the nameplate to list the actual field charge.
Table 4
Liquid Line
Set Diameter
Oz. per 5 ft. (g per 1.5 m) adjust
from 15 ft. (4.6 m) line set*
5/16 in. (8 mm) 2 ounce per 5 ft. (57g per 1.5 m)
3/8 in. (9.5 mm) 3 ounce per 5 ft. (85g per 1.5 m)
*If line length is greater than 15 ft. (4.6 m), add this amount. If line length is less than 15 ft. (4.6 m), subtract this amount.
The outdoor unit should be charged during warm weather. However, applications arise in which charging must occur in the colder months. The method of charging is deter-
mined by the unit’s refrigerant metering device and the out­door ambient temperature.
Measure the liquid line temperature and the outdoor ambi­ent temperature as outlined below:
1 − Close manifold gauge set valves. Connect the man-
ifold gauge set to the service valves:
low pressure gauge to vapor valve service porthigh pressure gauge to liquid valve service port
Connect the center manifold hose to an upright cylin­der of HCFC-22.
2 − Set the room thermostat to call for heat. This will create
the necessary load for properly charging the system in the cooling cycle.
3 − Use a digital thermometer to record the outdoor ambi-
ent temperature.
4 − When the heating demand has been satisfied, switch
the thermostat to cooling mode with a set point of 68F (20C). When pressures have stabilized, use a digital thermometer to record the liquid line temperature.
5 − The outdoor temperature will determine which charg-
ing method to use. Proceed with the appropriate charg­ing procedure.
Weighing in the Charge TXV Systems –
Outdoor Temp < 65F (18C)
If the system is void of refrigerant, or if the outdoor ambient temperature is cool, the refrigerant charge should be weighed into the unit. Do this after any leaks have been re­paired.
1 − Recover the refrigerant from the unit.
2 − Conduct a leak check, then evacuate as previously
outlined.
3 − Weigh in the unit nameplate charge.
If weighing facilities are not available or if you are charging the unit during warm weather, follow one of the other proce­dures outlined below.
Subcooling Method
Outdoor Temp. < 65°F (18°C)
When the outdoor ambient temperature is below 65°F (18°C), use the subcooling method to charge the unit. It may be necessary to restrict the air flow through the out­door coil to achieve pressures in the 200−250 psig (1379−1724 kPa) range. These higher pressures are nec­essary for checking the charge. Block equal sections of air intake panels and move obstructions sideways until the liq­uid pressure is in the 200−250 psig (1379−1724 kPa) range. See figure 15.
Blocking Outdoor Coil
cardboard or
plastic sheet
Outdoor coil should be
blocked one side
at a time with cardboard
or plastic sheet until proper
testing pressures
are reached.
Figure 15
1 − With the manifold gauge hose still on the liquid service
port and the unit operating stably, use a digital ther-
mometer to record the liquid line temperature. 2 − At the same time, record the liquid line pressure reading. 3 − Use a temperature/pressure chart for HCFC-22 to de-
termine the saturation temperature for the liquid line
pressure reading.
4 − Subtract the liquid line temperature from the saturation
temperature (according to the chart) to determine sub-
cooling. (Saturation temperature − Liquid line tem-
perature = Subcooling)
Page 15
Page 15
5 − Compare the subcooling value with those in table 5. If
subcooling is greater than shown, recover some refrig­erant. If subcooling is less than shown, add some re­frigerant.
Table 5
Subcooling Values
Model
Subcooling Temp. _F (_C)
10HPB18 5 (2.8) 10HPB24 7 (3.9) 10HPB30 9 (5) 10HPB36 11 (6.1) 10HPB42 7 (3.9) 10HPB48 8 (4.4) 10HPB60 10 (5.6)
Charging Using Normal Operating Pressures
and the Approach Method
Outdoor Temp. >
65_F (18_C)
The following procedure is intended as a general guide and
is for use on expansion valve systems only. For best results, indoor temperature should be 70°F (21°C) to 80°F (26°C). Monitor system pressures while charging.
1 − Record outdoor ambient temperature using a digital
thermometer. 2 − Attach high pressure gauge set and operate unit for
several minutes to allow system pressures to stabilize. 3 − Compare stabilized pressures with those provided in
table 6, Normal Operating Pressures." Minor varia-
tions in these pressures may be expected due to differ-
ences in installations. Significant differences could
mean that the system is not properly charged or that a
problem exists with some component in the system.
Pressures higher than those listed indicate that the
system is overcharged. Pressures lower than those
listed indicate that the system is undercharged. Verify
adjusted charge using the approach method.
Table 6
Normal Operating Pressures
Outdoor
10HPB18 10HPB24 10HPB30 10HPB36 10HPB42 10HPB48 10HPB60
Mode
C
oil Air
Entering
Temp. F (C)
liq.
+
10
psig
vap.
+
5
psig
liq.
+
10
psig
vap.
+
5
psig
liq.
+
10
psig
vap.
+
5
psig
liq.
+
10
psig
vap.
+
5
psig
liq.
+
10
psig
vap.
+
5
psig
liq.
+
10
psig
vap.
+
5
psig
liq.
+
10
psig
vap.
+
5
psig
65 (18) 148 71 156 70 165 73 171 68 173 69 163 74 166 71 75 (24) 171 74 182 72 204 70 192 70 205 72 196 74 195 73
Cooli
ng
TXV
85 (29) 200 76 210 74 236 71 222 71 252 73 229 75 227 74
TXV
Only
95 (35) 230 78 241 75 268 73 258 73 278 74 261 77 261 76
y
105 (41) 263 81 275 78 302 74 295 74 315 78 295 78 302 78
20 (−7) 166 33 170 28 178 24 194 26 182 28 178 26 190 27 30 (−1) 177 42 184 36 190 32 208 35 190 36 188 34 204 35
Heating
40 (4) 188 51 194 42 202 39 221 42 202 44 196 42 217 43
50 (10) 200 61 212 56 214 47 236 54 212 54 206 50 234 53
Page 16
Page 16
Approach Method
4 − Use the same digital thermometer used to check out-
door ambient temperature to check liquid line tempera­ture. Verify the unit charge using the approach method. The difference between the ambient and liquid temper­atures should match values given in table 7. Add refrig­erant to lower the approach temperature and remove it to increase the approach temperature. Loss of charge results in low capacity and efficiency.
5 − If the values don’t agree with the those in table 7, add
refrigerant to lower the approach temperature or re­cover refrigerant from the system to increase the ap­proach temperature.
Table 7
Approach Values
Model
Liquid Temp. Minus Ambient Temp.
_F (_C)
10HPB18 12 (6.7) 10HPB24 13 (7.2) 10HPB30 14 (7.8) 10HPB36 10 (5.6) 10HPB42 13 (7.2) 10HPB48 14 (7.8) 10HPB60 13 (7.2)
NOTE − For best results, the same thermometer should be used to check both outdoor ambient and liquid temperatures.
IMPORTANT
Use table 6 as a general guide when performing maintenance checks. This is not a procedure for charging the unit (Refer to Charging/Checking Charge section). Minor variations in these pressures may be expected due to differences in installations. Significant differences could mean that the system is not properly charged or that a problem exists with some component in the system.
System Operation
The outdoor unit and indoor blower cycle on demand from the room thermostat. When the thermostat blower switch is in the ON position, the indoor blower operates continuously.
Filter Drier
The unit is equipped with a biflow filter drier. See figure 12. If replacement is necessary, order another of like design.
Crankcase Heater
IMPORTANT
If unit is equipped with crankcase heater, it should be energized 24 hours before unit start−up to prevent compressor damage as a result of slugging.
Emergency Heat Function
An emergency heat function is designed into some room ther­mostats. This feature is applicable when isolation of the out­door unit is required, or when auxiliary electric heat is staged by outdoor thermostats. When the room thermostat is placed in the emergency heat position, the outdoor unit control circuit is isolated from power and field-provided relays bypass the outdoor thermostats. An amber indicating light simultaneously comes on to remind the homeowner that he is operating in the emergency heat mode.
Emergency heat is usually used during an outdoor unit shut down, but it should also be used following a power outage if power has been off for over an hour and the outdoor tem­perature is below 50°F (10°C). System should be left in the emergency heat mode at least six hours to allow the crank­case heater sufficient time to prevent compressor slug­ging.
Defrost System
The 10HPB defrost system includes two components: a defrost thermostat and a defrost control.
Defrost Thermostat
The defrost thermostat is located on the liquid line between the check/expansion valve and the distributor. When de­frost thermostat senses 42°F (5.5°C) or cooler, the thermo­stat contacts close and send a signal to the defrost control board to start the defrost timing. It also terminates defrost when the liquid line warms up to 70°F (21°C).
Defrost Control
The defrost control board includes the combined func­tions of a time/temperature defrost control, defrost relay, diagnostic LEDs and terminal strip for field wiring connec­tions. See figure 16.
The control provides automatic switching from normal heating operation to defrost mode and back. During com­pressor cycle (call for defrost), the control accumulates compressor run times at 30−, 60−, or 90−minute field−adjust­able intervals. If the defrost thermostat is closed when the selected compressor run time interval ends, the defrost relay is energized and defrost begins.
Defrost Control Timing Pins
Each timing pin selection provides a different accumu­lated compressor run time period during one thermostat run cycle. This time period must occur before a defrost cycle is initiated. The defrost interval can be adjusted to 30 (T1), 60 (T2), or 90 (T3) minutes. See figure 16. The defrost timing jumper is factory−installed to provide a 60−minute defrost interval. If the timing selector jumper is not in place, the control defaults to a 90−minute defrost interval. The maximum defrost period is 14 minutes and cannot be adjusted.
A TEST option is provided for troubleshooting. The TEST
mode may be started any time the unit is in the heating
Page 17
Page 17
mode and the defrost thermostat is closed or jump­ered. If the jumper is in the TEST position at power-up, the
control will ignore the test pins. When the jumper is placed across the TEST pins for two seconds, the control will enter the defrost mode. If the jumper is removed before an addi­tional 5−second period has elapsed (7 seconds total), the unit will remain in defrost mode until the defrost thermostat opens or 14 minutes have passed. If the jumper is not re­moved until after the additional 5−second period has elapsed, the defrost will terminate and the test option will not function again until the jumper is removed and re−ap­plied.
Pressure Switch Circuit
The defrost control incorporates a pressure switch circuit that allows the application of an optional high pressure switch. See figure 16. During a demand cycle, the defrost
control will lock out the unit if the optional high pressure switch opens. The diagnostic LEDs will display a pattern for an open high pressure switch. See table 8. The unit will re­main locked out until the switch resets or is reset.
Remove the factory-installed jumper before connecting the optional high pressure switch to the control board.
NOTE − If not using a pressure switch, the factory-installed jumper wire must be connected.
Diagnostic LEDs
The defrost board uses two LEDs for diagnostics. The LEDs flash a specific sequence according to the condition.
Table 8
Defrost Control Board Diagnostic LED
Mode LED 1 LED 2
Normal operation / power to board
Synchronized Flash with LED 2
Synchronized Flash with LED 1
Board failure or no power Off Off Board failure On On Pressure switch open Flash On
10HPB Defrost Control Board
Figure 16
24V
terminal strip
high pressure switch
connections
S4
connection for
optional
high pressure switch
defrost interval
timing pins
high
pressure
switch
diagnostic
LEDs
NOTE − Remove factory−installed
jumper to add pressure switch.
Page 18
Page 18
Maintenance
WARNING
Electric shock hazard. Can cause inju­ry or death. Before attempting to per­form any service or maintenance, turn the electrical power to unit OFF at dis­connect switch(es). Unit may have multiple power supplies.
Maintenance and service must be performed by a qualified installer or service agency. At the beginning of each cooling season, the system should be checked as follows:
Outdoor Unit
1 − Clean and inspect outdoor coil (may be flushed with a
water hose). Make sure power is off before cleaning.
2 − Outdoor unit fan motor is pre-lubricated and sealed. No
further lubrication is needed.
3 − Visually inspect all connecting lines, joints and coils for
evidence of oil leaks. 4 − Check all wiring for loose connections. 5 − Check for correct voltage at unit (unit operating). 6 − Check amp draw on outdoor fan motor.
Unit nameplate__________Actual__________. 7 - Inspect drain holes in coil compartment base and clean
if necessary.
NOTE − If owner complains of insufficient cooling, the unit
should be gauged and refrigerant charge checked. Refer
to section on refrigerant charging in this instruction.
Indoor Coil
1 − Clean coil if necessary.
2 − Check connecting lines, joints and coil for evidence of
oil leaks.
3 − Check condensate line and clean if necessary.
Indoor Unit
1 − Clean or change filters. 2 − Adjust blower speed for cooling. Measure the pressure
drop over the coil to determine the correct blower CFM. Refer to the unit information service manual for pressure drop tables and procedure.
3 − Belt Drive Blowers − Check belt for wear and proper
tension.
4 − Check all wiring for loose connections. 5 − Check for correct voltage at unit. (blower operating) 6 − Check amp draw on blower motor.
Motor nameplate__________Actual__________.
Optional Accessories
Refer to the Engineering Handbook for optional accesso­ries that may apply to this unit. The following may or may not apply:
Loss of Charge Kit
High Pressure Switch Kit Compressor Monitor Compressor Crankcase Heater
Hail GuardsMounting Bases
Stand−off Kit
Sound Cover
Low Ambient Kit Monitor Kit Mild Weather Kit
Start−Up and Performance Check List
Start−Up and Performance Check List
Job Name
Job Location Installer
Unit Model No. Nameplate Voltage
Rated Load Ampacity Maximum Fuse or Circuit Breaker
Refrigerant Lines:
Service Valves Fully Opened?
Outdoor Fan Checked?
Job No.
City
City
Serial No.
Date
State
State
Service Technician
Compressor
Outdoor Fan
Indoor Filter Clean?
Electrical Connections Tight?
Supply Voltage (Unit Off)
Vapor Pressure
Thermostat
Refrigerant Charge Checked?
Calibrated? Properly Set?
Level?
Properly Insulated?
Voltage With Compressor Operating
Leak Checked?
Service Valve Caps Tight?
Indoor Blower RPM
Outdoor Coil Entering Air Temp.
Discharge Pressure
S.P. Drop Over Indoor (Dry)
Loading...