Lennox 10ACE Installation Instructions Manual

INSTALLATION
2006 Lennox Industries Inc.
Dallas, Texas, USA
WARNING
Improper installation, adjustment, alteration, ser­vice or maintenance can cause personal injury, loss of life, or damage to property.
Installation and service must be performed by a qualified installer or service agency.
IMPORTANT
INSTRUCTIONS
10ACE Series Units
CONDENSER UNITS
505,128M 03/06 Supersedes 01/06
Table of Contents
10ACE Outdoor Units 1. . . . . . . . . . . . . . . . . . . . . . . . . .
Shipping & Packing List 1. . . . . . . . . . . . . . . . . . . . . . . .
General Information 2. . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit Dimensions 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setting the Unit 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Refrigerant Piping 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Refrigerant Metering Devices 4. . . . . . . . . . . . . . . . . . .
Manifold Gauge Set 5. . . . . . . . . . . . . . . . . . . . . . . . . . .
Service Valves 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Leak Testing 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Evacuation 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Start−Up 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Refrigerant Charging 8. . . . . . . . . . . . . . . . . . . . . . . . . . .
System Operation 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maintenance 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Optional Accessories 11. . . . . . . . . . . . . . . . . . . . . . . . . .
Start−Up & Performance Check List 11. . . . . . . . . . . . . .
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
Litho U.S.A.
The Clean Air Act of 1990 bans the intentional vent­ing of refrigerant (CFC’s and HCFC’s) as of July 1,
1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incar­ceration may be levied for noncompliance.
WARNING
This product and/or the indoor unit it is matched with may contain fiberglass wool.
Disturbing the insulation during installation, main­tenance, or repair will expose you to fiberglass wool dust. Breathing this may cause lung cancer. (Fiber­glass wool is known to the State of California to cause cancer.)
Fiberglass wool may also cause respiratory, skin, and eye irritation.
To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor.
Lennox Industries Inc. P.O. Box 799900 Dallas, TX 75379−9900
CAUTION
Physical contact with metal edges and corners while applying excessive force or rapid motion can result in personal injury. Be aware of, and use caution when working near these areas during installation or while servicing this equipment.
10ACE Outdoor Units
Lennox Merit® 10ACE outdoor units are designed for use in either fixed orifice or expansion valve (TXV) systems. The TXV may require a field−installed hard start kit. Refer to the Lennox Engineering Handbook for expansion valve kits which must be ordered separately.
Shipping & Packing List
1 − Assembled outdoor unit 1 − Fixed orifice refrigerant metering device
Check the unit for shipping damage. Consult last carrier immediately if damage is found.
03/06 505,128M
*2P0306* *P505128M*
Page 1
Unit Dimensions − inches (mm)
OPTIONAL UNIT STAND−OFF KIT (4) (Field Installed)
4−3/8
AIR
4−3/8 (111)
OPTIONAL UNIT STAND−OFF KIT (4) (Field Installed)
AIRAIR
AIR
C
COIL DRAIN OUTLETS (Around perimeter of base)
VAPOR LINE CONNECTION
LIQUID LINE CONNECTION
B
A
ELECTRICAL INLETS
6−3/8 (162)
OUTDOOR COIL FAN
COMPRESSOR
VAPOR & LIQUID LINE CONNECTION
(111)
COMPRESSOR
6−3/8 (162)
TOP VIEW BASE SECTION
C
DISCHARGE AIR
4−3/8 (111)
4−3/8 (111)
4−3/8 (111)
4−3/8 (111)
2 (51)
3/4 (19)
10ACE Model A B C
−024 25 (635) 24−1/4 (616) 24−1/4 (565)
−036 33 (635) 32−1/4 (616) 24−1/4 (565)
−048 33 (838) 32−1/4 (819) 24−1/4 (616)
−060 33 (940) 32−1/4 (921) 24−1/4 (718)
General Information
These instructions are intended as a general guide and do not supersede national or local codes in any way. Consult authorities who have jurisdiction before installation.
When servicing or repairing HVAC components, ensure the fasteners are appropriately tightened. Table 1 shows torque values for fasteners.
2−3/4 (70)
SIDE VIEW
Table 1
Torque Requirements
Part Recommended Torque
Service valve cap 8 ft.− lb. 11 NM
Sheet metal screws 16 in.− lb. 2 NM
Machine screws #10 28 in.− lb. 3 NM
Compressor bolts 90 in.− lb. 10 NM
Gauge port seal cap 8 ft.− lb. 11 NM
Setting the Unit
Refer to unit dimensions for sizing mounting slab, plat­forms or supports. Refer to figure 1 for installation clear­ances.
505128M 03/06
Page 2
Slab Mounting
When installing unit at grade level, install on a level slab high enough above grade to allow adequate drainage of water. Top of slab should be located so run−off water from higher ground will not collect around unit.
Installation Clearances
1. Install line voltage power supply to unit from a properly sized disconnect switch.
2. Install line voltage power supply to unit from a properly sized disconnect switch. Any excess high voltage field wiring should be trimmed or secured away from the low voltage field wiring (see figures 2 and 3).
Separating High/Low Voltage Field Wiring
(as noted)
(as noted)
(as noted)
*A service clearance of 30" (762 mm) must be maintained on one of the sides adjacent to the control box. Clearance to one of the other three sides must be 36" (914 mm). Clearance to one of the remaining two sides may be 12" (304 mm) and the final side may be 6" (152 mm).
A clearance of 24" (610 mm) must be maintained between two units. 48" (1219 mm) clearance required on top of unit. Maximum soffit over­hang is 36" (914 mm).
(as noted)
Figure 1
.Roof Mounting
Install the unit at a minimum of 4 inches (102 mm) above the surface of the roof. Ensure the weight of the unit is properly distributed over roof joists and rafters. Redwood or steel supports are recommended.
Electrical
*−048 &
−060 models
WIRE TIES
Figure 2
Typical Field Wiring Diagram
*
*
*
High Voltage Field Wiring
Low Voltage Field Wiring
Factory Wiring
(SEE
NOTE)
208−230/60/1
In Canada, wiring must conform with current local codes and the current Canadian Electrical Code (CEC).
WARNING
Electric Shock Hazard. Can cause in­jury or death.
Line voltage is present at all compo­nents on units with single-pole con­tactors, even when unit is not in op­eration!
Unit may have multiple power sup­plies. Disconnect all remote electric power supplies before opening ac­cess panel.
Unit must be grounded in accordance with national and local codes.
Refer to the furnace or blower coil installation instructions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size.
GROUND
WARNING! − ELECTRIC SHOCK HAZARD. Can cause INJURY or DEATH. Unit must be grounded in accordance with national and local codes.
NOTE − For use with copper conductors only. Refer to unit rating plate for minimum circuit ampacity and maximum over-current protection size.
Figure 3
3. Ground unit at unit disconnect switch or to an earth ground.
NOTE − To facilitate conduit, a hole is located in the bottom of the control box. Connect conduit to the con­trol box using a proper conduit fitting. Units are ap­proved for use only with copper conductors.
24V, Class II circuit connections are made to the low voltage pigtails. Refer to figure 3 for field wiring dia­gram. A complete unit wiring diagram is located inside the unit control box cover.
4. Install room thermostat (ordered separately) on an in­side wall approximately in the center of the conditioned area and 5 feet (1.5 m) from the floor. It should not be installed on an outside wall or where it can be effected by sunlight, drafts or vibrations.
Page 3
10ACE SERIES
NOTE − For proper voltages, select thermostat wire
color coded, temperature
gauge per the following chart:
Wire run length AWG # Insulation type
less than 100’ (30m) 18
more than 100’ (30m) 16
color−coded, temperature rating 35ºC minimum
5. Install low voltage wiring from outdoor to indoor unit and from thermostat to indoor unit. See figure 4.
Typical Field Low Voltage Wiring Diagram
Thermostat Indoor Unit
Sweat Connection Procedure
1. Cut ends of the refrigerant lines square (free from nicks or dents). Debur the ends. The pipe must remain round, do not pinch end of the line.
2. Wrap a wet cloth around the valve body and copper tube stub to protect it from heat damage during braz­ing. Wrap another wet cloth underneath the valve body to protect the base paint.
3. Quench the joints with a wet cloth to prevent possible heat damage to the valve core and opening port.
4. Install a field−provided filter dryer as close as possible to the expansion device.
R
W1
Y
G
C
power
heat
cooling
indoor blower
common
R
Outdoor Unit
W
Y
G
C
Y1
C
NOTE − see unit wiring diagram for power supply connec­tions. If indoor unit is not equipped with blower relay. It must be field−provided and installed (P−8−3251 or equivalent).
Figure 4
Refrigerant Piping
Field refrigerant piping consists of liquid and vapor lines from the outdoor unit (sweat connections) to the indoor coil (flare or sweat connections). Use Lennox L15 (sweat, non­flare) series line sets as shown in table 2 or use field-fabri­cated refrigerant lines. Refer to Refrigerant Piping Guide (Corp. 9351−L9) for proper size, type, and application of field−fabricated lines. Valve sizes are also listed in table 2.
Table 2
Refrigerant Line Kits
Valve Field Size Connections
Liquid
Model
NOTE − Units are designed for line sets of up to 50 feet (15 m). For applications longer than 50 feet, consult the Lennox Refrigerant Piping Guide (Corp. 9351−L9). Select line set diameters from table 2 to en­sure that oil returns to the compressor.
Line
−024
−036
−048 3/8 in
−060 3/8 in
3/8 in
(10mm)
(10 mm)
(10 mm)
Vapor Line
3/4 in.
(19mm)
7/8 in.
(22 mm)
1−1/8 in.
(29 mm)
Recommended Line Set
Liquid Line
3/8 in
(10mm)
3/8 in
(10 mm)
3/8 in
(10 mm)
Vapor Line
3/4 in.
(19mm)
7/8 in.
(22 mm)
1−1/8 in. (29 mm)
L15 Line Sets
L15−41
15 ft.− 50 ft.
(4.6 m − 15m)
L15−65
15 ft.− 50 ft.
(4.6 m − 15m)
Fabricated
Field
Refrigerant Metering Device
Use 10ACE units in either TXV systems or fixed orifice sys- tems. See the Lennox Engineering Handbook for ap­proved TXV and fixed orifice match-ups and application in­formation. Table 2 lists the unit liquid and vapor line sizes and corresponding line sets.
Fixed Orifice Systems
10ACE units are shipped with a fixed orifice refrigerant me­tering device. Replace the existing indoor unit fixed orifice with the orifice supplied with the outdoor unit. Place the supplied fixed orifice sticker on the indoor cabinet after installation. See table 3 for the fixed orifice size for each unit. In nonstandard applications, the provided fixed orifice may not be appropriately sized. Refer to the Engineering Handbook for specific orifice information.
Table 3
Fixed Orifice Drill Sizes
Unit
Catalog #
10ACE−024 100484−12 .062
10ACE−036 100484−22 .073
10ACE−048 100484−33 .086
10ACE−060 100484−44 .098
Install the fixed orifice as shown in figure 5. Do not twist the cap tubes when loosening the seal nut from the orifice housing.
Metering Device Installation
Fixed Orifice
O−RING
DISTRIBUTOR
NOTE − If installing expansion valve with an indoor coil that includes a fixed orifice, remove orifice before installing valve.
FIXED ORIFICE
EXPANSION VALVE & O−RING (See NOTE)
STRAINER
Figure 5
Expansion Valve Systems
Expansion valves equipped with Chatleff fittings are avail­able from Lennox. Refer to the Engineering Handbook for expansion valves for use with specific match−ups.
Fixed Orifice
Drill Size
or
LIQUID LINE STUB
505128M 03/06
Page 4
If you install a expansion valve with an indoor coil that includes a fixed orifice, remove the orifice before the expansion valve is installed.
IMPORTANT
Failure to remove the fixed orifice when installing an expansion valve on the indoor coil will result in im­proper operation and damage to the system.
Manifold Gauge Set
When checking the unit charge, use a manifold gauge set that is equipped with low loss" hoses. Do not use a man­ifold gauge set with anything other than a low loss" hose.
Service Valves
The service valves (liquid line − figure 6, vapor line − figures 7 and 8) and gauge ports are used for leak testing, eva­cuating, charging and checking charge. Each valve is equipped with a service port which has a factory−installed Schrader valve. A service port cap protects the Schrader valve from contamination and serves as the primary leak seal.
To Access Schrader Port:
1. Remove service port cap with an adjustable wrench.
2. Connect gauge to the service port.
3. When testing is complete, replace service port cap. Tighten finger tight, then torque per table 1 (Page 2) .
To Open Front-Seated Service Valves:
1. Remove stem cap with an adjustable wrench.
2. Use a service wrench with a hex−head extension (3/16" for liquid-line valve sizes; 5/16" for vapor-line valve sizes) to back the stem out counterclockwise as far as it will go.
3. Replace the stem cap. Tighten finger tight, then torque per table 1 (Page 2) .
To Close Front-Seated Service Valves:
1. Remove the stem cap with an adjustable wrench.
2. Use a service wrench with a hex−head extension (3/16" for liquid-line valve sizes; 5/16" for vapor-line valve sizes) to turn the stem clockwise to seat the valve. Tighten it firmly.
3. Replace the stem cap. Tighten finger tight, then torque per table 1 (Page 2) .
Vapor Line Ball Valve
Ball-type service valve (10ACE−060 only, figure 8) func­tions the same way as the other valves but cannot be re­built; if one fails, replace with a new valve. The ball valve is equipped with a service port with a factory−installed Schrader valve. A service port cap protects the Schrader valve from contamination and assures a leak−free seal.
Front-Seated Liquid Line Service Valve
STEM SCHRADER VALVE [OPEN TO LINE SET WHEN VALVE IS CLOSED (FRONT SEATED)]
TO OUT­DOOR COIL
SERVICE PORT CAP
CAP
(VALVE FRONT-SEATED)
Valve in closed position Valve in open position
INSERT HEX WRENCH HERE
TO INDOOR COIL
Figure 6
Front-Seated Vapor Line Service Valve
STEM CAP
SCHRADER VALVE
INSERT HEX WRENCH HERE
TO OUTDOOR COIL
(VALVE FRONT-SEATED)
Valve in closed position
[OPEN TO LINE SET WHEN VALVE IS CLOSED (FRONT SEATED)]
SERVICE PORT CAP
SERVICE PORT
TO INDOOR COIL
Valve in open position
Figure 7
Ball−Type Vapor Valve (Valve Closed)
STEM
USE ADJUSTABLE WRENCH
TO OPEN: ROTATE STEM COUNTER-CLOCKWISE 90°. TO CLOSE: ROTATE STEM CLOCKWISE 90°.
TO INDOOR COIL
CAP
STEM
SERVICE PORT
SCHRADER VALVE
TO OUTDOOR COIL
BALL (SHOWN CLOSED)
SERVICE PORT CAP
Figure 8
Page 5
10ACE SERIES
Leak Testing
After the line set has been connected to the indoor and out­door units, check the line set connections and indoor unit for leaks.
WARNING
Danger of fire!
Bleeding the refrigerant charge from only the high side may result in the low side shell and suction tubing be­ing pressurized. Application of a braz­ing torch while pressurized may re­sult in ignition of the refrigerant and oil mixture − check the high and low pressures before unbrazing.
WARNING
Refrigerant can be harmful if it is inhaled. Refriger­ant must be used and recovered responsibly.
Failure to follow this warning may result in personal injury or death.
4. Connect a cylinder of nitrogen with a pressure regulat­ing valve to the center port of the manifold gauge set.
5. Connect the manifold gauge set high pressure hose to the vapor valve service port. (Normally, the high pres-
sure hose is connected to the liquid line port; however, connecting it to the vapor port better protects the man­ifold gauge set from high pressure damage.)
6. Adjust the nitrogen pressure to 150 psig (1034 kPa). Open the valve on the high side of the manifold gauge set which will pressurize line set and indoor unit.
7. After a few minutes, open a refrigerant port to ensure the refrigerant you added is adequate to be detected. (Amounts of refrigerant will vary with line lengths.) Check all joints for leaks. Purge nitrogen and HCFC-22 mixture. Correct any leaks and recheck.
Evacuation
Evacuating the system of noncondensables is critical for proper operation of the unit. Noncondensables are defined as any gas that will not condense under temperatures and pressures present during operation of an air conditioning system. Noncondensables and water vapor combine with refrigerant to produce substances that corrode copper pip­ing and compressor parts.
IMPORTANT
WARNING
Danger of explosion!
Can cause equipment damage, injury or death. Never use oxygen to pres­surize a refrigeration or air condition­ing system. Oxygen will explode on contact with oil and could cause per­sonal injury.
WARNING
Danger of explosion!
When using a high pressure gas such as dry nitrogen to pressurize a refrig­eration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to
13.8 kPa).
Using an Electronic Leak Detector or Halide
1. Connect a cylinder of HCFC-22 to the center port of the manifold gauge set.
2. With both manifold valves closed, open the valve on the HCFC-22 cylinder (vapor only).
3. Open the high pressure side of the manifold to allow the HCFC-22 into the line set and indoor unit. Weigh in a trace amount of HCFC-22. [A trace amount is a maximum of 2 ounces (57 g) or 3 pounds (31 kPa) pressure.] Close the valve on the HCFC-22 cylinder and the valve on the high pressure side of the manifold gauge set. Disconnect the HCFC-22 cylinder.
Use a thermocouple or thermistor electronic vacuum gauge that is calibrated in microns. Use an instrument that reads from 50 microns to at least 23,000 microns.
1. Connect manifold gauge set to the service valve ports as follows:
low pressure gauge to vapor line service valvehigh pressure gauge to liquid line service valve
2. Connect micron gauge.
3. Connect the vacuum pump (with vacuum gauge) to the center port of the manifold gauge set.
4. Open both manifold valves and start the vacuum pump.
5. Evacuate the line set and indoor unit to an absolute pressure of 23,000 microns (29.01 inches of mercu­ry). During the early stages of evacuation, it is desir­able to close the manifold gauge valve at least once to determine if there is a rapid rise in absolute pressure. A rapid rise in pressure indicates a relatively large leak. If this occurs, repeat the leak testing procedure.
NOTE − The term absolute pressure is defined as the total actual pressure within a given volume or system, above the absolute zero of pressure. Absolute pres­sure in a vacuum is equal to atmospheric pressure mi­nus vacuum pressure.
6. When the absolute pressure reaches 23,000 microns (29.01 inches of mercury), close the manifold gauge valves, turn off the vacuum pump and disconnect the manifold gauge center port hose from vacuum pump. Attach the manifold center port hose to a nitrogen cyl­inder with pressure regulator set to 150 psig (1034 kPa) and purge the hose. Open the manifold gauge valves to break the vacuum in the line set and indoor unit. Close the manifold gauge valves.
505128M 03/06
Page 6
CAUTION
Danger of Equipment Damage.
Avoid deep vacuum operation. Do not use compres­sors to evacuate a system. Extremely low vacuums can cause internal arcing and compressor failure.
Damage caused by deep vacuum operation will void warranty.
7. Shut off the nitrogen cylinder and remove the manifold gauge hose from the cylinder. Open the manifold gauge valves to release the nitrogen from the line set and indoor unit.
8. Reconnect the manifold gauge to the vacuum pump, turn the pump on, and continue to evacuate the line set and indoor unit until the absolute pressure does not rise above 500 microns (29.9 inches of mercury) within a 20−minute period after shutting off the vacuum pump and closing the manifold gauge valves.
9. When the absolute pressure requirement above has been met, disconnect the manifold hose from the vac­uum pump and connect it to an upright cylinder of HCFC-22 refrigerant. Open the manifold gauge valves to break the vacuum from 1 to 2 psig positive pressure in the line set and indoor unit. Close manifold gauge valves and shut off the HCFC-22 cylinder and remove the manifold gauge set.
Start Up
IMPORTANT
If unit is equipped with crankcase heater, it should be energized 24 hours before unit start−up to pre­vent compressor damage as a result of slugging.
1. Rotate the fan to check for frozen bearings or binding.
2. Inspect all factory− and field-installed wiring for loose connections.
3. After evacuation is complete, open the liquid line and vapor line service valves to release refrigerant charge (contained in outdoor unit) into the system.
4. Replace the stem caps and secure finger tight, then tighten an additional one-sixth (1/6) of a turn.
5. Check voltage supply at the disconnect switch. The voltage must be within the range listed on the unit’s nameplate. If not, do not start the equipment until you have consulted the power company and the voltage condition has been corrected.
6. Set the thermostat for a cooling demand. Turn on pow­er to the indoor blower and close the outdoor unit dis­connect switch to start the unit.
7. Recheck voltage while the unit is running. Power must be within range shown on the nameplate.
Page 7
10ACE SERIES
Refrigerant Charging
T
Units are factory charged with the amount of HCFC-22 re­frigerant indicated on the unit nameplate. This charge is based on a matching indoor coil and outdoor coil with a 15 ft. (4.6 m) line set. For varying lengths of line set, refer to table 4 for refrigerant charge adjustment check.
Table 4
Refrigerant Charge per Line Set Lengths
Liquid Line
Set Diameter
5/16 in. (8 mm) 2 ounce per 5 ft. (57 g per 1.5 m)
3/8 in. (9.5 mm) 3 ounce per 5 ft. (85 g per 1.5 m)
NOTE − *If line length is greater than 15 ft. (4.6 m), add this amount. If line length is less than 15 ft. (4.6 m), subtract this amount.
The outdoor unit should be charged during warm weather. However, applications arise in which charging must occur in the colder months. The method of charging is deter-
mined by the unit’s refrigerant metering device and the outdoor ambient temperature.
Measure the liquid line temperature and the outdoor ambi­ent temperature as outlined below:
1. Connect the manifold gauge set to the service valves:
low pressure gauge to vapor valve service porthigh pressure gauge to liquid valve service port
2. Connect the center manifold hose to an upright cylin­der of HCFC-22. Close manifold gauge set valves.
3. Set the room thermostat to call for heat. This will create the necessary load for properly charging the system in the cooling cycle.
4. Use a digital thermometer to record the outdoor ambi­ent temperature.
5. When the heating demand has been satisfied, switch the thermostat to cooling mode with a set point of 68F (20C). When pressures have stabilized, use a digital thermometer to record the liquid line temperature.
6. The outdoor temperature will determine which charg­ing method to use. Proceed with the appropriate charging procedure.
Charge Using Weigh−in Method (Fixed Orifice/ TXV Systems) − Outdoor Temp. <65°F (18°C)
If the system is void of refrigerant, or if the outdoor ambient temperature is cool, use the weigh−in method to charge the unit. Do this after any leaks have been repaired.
1. Recover the refrigerant from the unit.
Oz. per 5 ft. (g per 1.5 m) adjust
from 15 ft. (4.6 m) line set*
2. Conduct a leak check, then evacuate as previously outlined.
3. Weigh in the charge according to the total amount shown on the unit nameplate.
If weighing facilities are not available or if you are charging the unit during warm weather, follow one of the other pro­cedures outlined below.
Charge Using Subcooling Method (Fixed Orifice Systems) − Outdoor Temp. >
If you charge a fixed orifice system when the outdoor ambi­ent is 65F (18C) or above, use the subcooling method to charge the unit.
1. With the manifold gauge hose still on the liquid service port and the unit operating stably, use a digital thermometer to record the liquid line temperature.
2. At the same time, record the liquid line pressure reading.
3. Use a temperature/pressure chart for R−22 to determine the saturation temperature for the liquid line pressure reading.
4. Subtract the liquid line temperature from the saturation temperature (according to the chart) to determine subcooling.
Saturation Temperature F (C) Liquid Line Temperature F (C) = Subcooling ValueF (C)
5. Compare the subcooling value with those in table 5. If subcooling is greater than shown, recover some refrigerant. If subcooling is less than shown, add some refrigerant.
65°F (18°C)
Table 5
Subcooling Values for Fixed Orifice Systems
Outdoor
emp.
F (C)
65 (18) 10 (5.6) 17 (9.5) 15 (8.3) 14 (8)
70 (21) 9 (5) 17 (9.5) 14 (8) 15 (8.3)
75 (24) 8 (4.5) 16 (9) 13 (7) 15 (8.3)
80 (27) 7 (3.9) 15 (8.3) 13 (7) 14 (8)
85 (29) 6 (3.3) 14 (8) 12 (6.7) 14 (8)
90 (32) 5 (2.8) 14 (8) 12 (6.7) 13 (7)
95 (35) 4 (2.2) 12 (6.7) 12 (6.7) 13 (7)
100 (38) 4 (2.2) 11 (6) 11 (6) 12 (6.7)
105 (41) 3 (1.7) 10 (5.6) 10 (5.6) 12 (6.7)
110 (43) 3 (1.7) 9 (5) 9 (5) 11 (6)
115 (45) 2 (1.1) 8 (4.5) 8 (4.5) 10 (5.6)
10ACE−24 10ACE−36 10ACE−48 10ACE−60
Liquid Subcooling [+ 1_F (.6_C)]
505128M 03/06
Page 8
Charge Using Approach Method (TXV Systems)
Temp5F
− Outdoor Temperature >
The following procedure is intended as a general guide and is for use on expansion valve (TXV) systems only. For best results, indoor temperature should be 70°F (21°C) to 80°F (26°C). Monitor system pressures while charging.
1. Record outdoor ambient temperature using a digital thermometer.
2. Attach high pressure gauge set and operate unit for several minutes to allow system pressures to stabilize.
3. Compare stabilized pressures with those provided in table 7, Normal Operating Pressures."
65°F (18°C)
IMPORTANT
Use table 7 to help perform maintenance checks. Table 7 is not a procedure for charging the system.
Minor variations in these pressures may be due to differences in installations. Significant deviations could mean that the system is not properly charged or that a problem exists with some component in the system.
Pressures higher than those listed indicate that the system is overcharged. Pressures lower than those listed indicate that the system is undercharged. Verify adjusted charge using the approach method.
NOTE − For best results, use the same digital ther­mometer to check both outdoor ambient and liquid temperatures.
4. Check the liquid line temperature. The difference be­tween the ambient and liquid temperatures should match values given in table 6. Loss of charge results in low capacity and efficiency.
5. If the values do not agree with the those in table 6, add refrigerant to lower the approach temperature, or re­cover refrigerant from the system to increase the ap­proach temperature.
Table 6
Approach Values
10ACE Model −024 −036 −048 −060
Temp. °F (°C) 18 (10) 11 (6) 8 (4.5) 13 (7)
Approach Value is the Liquid Line Temperature minus Outdoor Ambi­ent Temperature [ºF (ºC) + 1ºF (0.5ºC)]
Table 7
Normal Operating Pressures*
10ACE−024 10ACE−036 10ACE−048 10ACE−060
5
(5C)**
Expansion Valve
65 (18) 163 70 162 70 159 71 170 74
75 (24) 193 71 187 74 188 72 201 76
85 (29) 225 72 219 75 220 73 234 77
95 (35) 260 73 253 77 251 76 270 79
105 (41) 298 74 291 79 290 77 309 79
110 (43) 318 75 310 80 309 78 331 80
115 (45) 338 75 329 81 328 79 351 81
Fixed Orifice
65 (18) 165 63 168 67 163 68 189 72
75 (24) 194 67 195 71 190 71 203 74
85 (29) 224 70 224 75 220 74 233 77
95 (35) 257 73 255 78 251 77 265 79
105 (41) 293 76 289 82 288 79 301 82
110 (43) 313 78 305 83 307 80 319 83
115 (45) 332 79 324 84 325 82 339 84
* Values shown are typical pressures (in. psig +2psig); indoor unit
match up, indoor air quality equipment, and indoor load will cause the pressures to vary.
** Temperature of the air entering the outside coil.
Liq. Suc. Liq. Suc. Liq. Suc. Liq. Suc.
Page 9
10ACE SERIES
System Operation
The outdoor unit and indoor blower cycle on demand from the room thermostat. When the thermostat blower switch is in the ON position, the indoor blower operates continu- ously.
Maintenance
NOTE − White residue may surface on guards and grilles of outdoor units. This is caused by mild acids present in minute quantities in the plasticizer applied to make the coating flexible. The residue is comprised of non−toxic, common fatty acids found in natural animal and vegetable oils, and can be removed by wiping the parts with a cloth. Once outside, and over time, the rain will wash off any re­maining residue.
Maintenance and service must be performed by a qualified installer or service agency. At the beginning of each cool­ing season, the system should be checked as follows:
WARNING
Electric shock hazard. Can cause inju­ry or death. Before attempting to per­form any service or maintenance, turn the electrical power to unit OFF at dis­connect switch(es). Unit may have multiple power supplies.
1. Clean and inspect the outdoor coil. The coil may be flushed with a water hose. Make sure power is off be­fore cleaning.
The outdoor coil is protected by an inner mesh screen and a wire cage (see figure 9).
6 pins
If debris has collected between the mesh screen and the coil and cannot be dislodged by spraying unpres­surized water from the inside coil surface to the out­side, the mesh may be removed by first removing the top of the unit which will allow for removal of the wire cage.
Then, using pliers to grip the head of the push pins, pull straight out to extract the push pins along one side of the coil. If necessary, remove the push pins along the back of the unit; it is usually unnecessary to fully re­move the inner mesh screen.
Drape the mesh screen back and wash the coil. When all the debris has been removed from the coil, reinstall the mesh screen by positioning it in its original position and reinserting the push pin. No tool is required to push the pin back into the same slot in the fins.
If the push pin is loose and tends not to stay in place, brush the fins with a 22 fpi fin brush (except model
−024, 18 fpi). Line up the push pin a couple fins to the right or left of the original hole and re−insert the pin.
2. Condenser fan motor is prelubricated and sealed. No further lubrication is needed.
3. Visually inspect connecting lines and coils for evi­dence of oil leaks.
4. Check wiring for loose connections.
5. Check for correct voltage at unit (unit operating).
6. Check amp−draw condenser fan motor. Unit nameplate _________ Actual ____________ .
NOTE − If the owner reports insufficient cooling, the unit should be gauged and the refrigerant charge should be checked. Refer to the charging section in this instruction.
PUSH PIN
MESH SCREEN
505128M 03/06
Figure 9
Indoor Coil
1. Clean coil, if necessary.
2. Check connecting lines and coils for evidence of oil leaks.
3. Check the condensate pan line and clean it if neces­sary.
Indoor Unit
1. Clean or change filters.
2. Adjust blower speed for cooling. Measure the pressure drop over the coil to determine the correct blower CFM. Refer to the unit information service manual for pressure drop tables and procedure.
3. Belt Drive Blowers − Check belt for wear and proper tension.
4. Check all wiring for loose connections
5. Check for correct voltage at unit (blower operating).
6. Check amp−draw on blower motor Unit nameplate_________ Actual ____________.
Page 10
Optional Accessories
Refer to the Engineering Handbook for optional accesso­ries that may apply to this unit. The following may or may not apply:
Loss of Charge Kit
High Pressure Switch Kit
Compressor Monitor
Compressor Crankcase Heater (standard on 4 and 5
ton units)
Hail Guards Mounting Bases Timed Off Control Stand−off Kit Sound Cover Low Ambient Kit
Start Up and Performance Checklist
Job Name Job no. Date
Job Location City State
Installer City State
Unit Model No. Serial No. Service Technician
Nameplate Voltage
Rated Load Ampacity Compressor Outdoor Fan
Maximum Fuse or Circuit Breaker
Electrical Connections Tight? Indoor Filter clean? Supply Voltage (Unit Off)
Indoor Blower RPM S.P. Drop Over Indoor (Dry) Outdoor Coil Entering Air Temp.
Discharge Pressure Vapor Pressure Refrigerant Charge Checked?
Refrigerant Lines: Leak Checked? Properly Insulated? Outdoor Fan Checked?
Service Valves: Fully Opened? Caps Tight? Thermostat
Voltage With Compressor Operating Calibrated? Properly Set?  Level? 
Page 11
10ACE SERIES
Loading...