Lennox 10ACB12, 10ACB24, 10ACB18, 10ACB36, 10ACB30 Installation Instructions Manual

...
3DJH
£
PRODUCT LITERATURE
¤
1998 Lennox Industries Inc.
Dallas, Texas
VALUE 10TMCONDENSING UNIT
V alue 10 condensing units are designed for expansion valve (TXV) and RFC systems. Refer to Lennox engi- neering handbook for expansion valve kits which must be ordered separately.
SHIPPING AND PACKING LIST
1-- Assembled 10ACB condensing unit 1-- 45Ecopper street elbow 1-- RFCIV refrigerant metering device (bullet) 1-- Coupling -- 5/16 x 3/8 (18, 24, 30)
Check unit for shipping damage. Consult last carrier immediately if damage is found.
GENERAL INFORMATION
These instructions are intended as a generalguide and do not supersede national or local codes in any way. Authorities having jurisdiction should beconsulted be- fore installation.
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFCs and HCFCs)as ofJuly 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or in- carceration may be levied for non--compliance.
INSTALLATION INSTRUCTIONS
9DOXH706HULHV
$&% &RQGHQVLQJ 8QLWV
&21'(16,1* 81,76
1--1/2 through 5 ton 503,800M 2/98
Supersedes 503,755M
TABLE OF CONTENTS
VALUE 10 CONDENSING UNIT 1.....................
SHIPPING AND PACKING LIST 1......................
GENERAL INFORMATION 1..........................
10ACB UNIT DIMENSIONS 2.........................
SETTING THE UNIT 3................................
ELECTRICAL 3......................................
PLUMBING 4.......................................
REFRIGERANT METERING DEVICE 4..................
MANIFOLD GAUGE SET 5...........................
LIQUID & SUCTION LINE SERVICE VALVES 5..........
LEAK TESTING 6....................................
EVACUATION 7.....................................
START-UP 8........................................
CHARGING CONSIDERATIONS 8.....................
CHARGING FOR RFC SYSTEMS 9....................
CHARGING FOR TXV SYSTEMS 10...................
SYSTEM OPERATION 10.............................
MAINTENANCE 11..................................
10ACB CHECK POINTS 12............................
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
WARNING
Product contains fiberglass wool. Disturbing the insulation in this product during
installation, maintenance, or repair will expose you to fiberglass wool. Breathing this may cause lung cancer. (Fiberglass wool is known to the State of California to cause cancer.)
Fiberglass wool may also cause respiratory, skin, and eye irritation.
To reduce exposure to this substance or forfurther information, consult material safety data sheets available from address shown below, or contact your supervisor.
Lennox Industries Inc. P.O. Box 799900 Dallas, TX 75379--9900
/LWKR 86$
All manuals and user guides at all-guides.com
all-guides.com
3DJH
10ACB UNIT DIMENSIONS--INCHES (MM)
SIDE VIEW
SUCTION &
LIQUID LINE
CONNECTION
INLET
AIR
INLET
AIR
DISCHARGE AIR
SIDE VIEW
TOP VIEW
A
OUTDOOR
COIL FAN
COMPRESSOR
INLET AIR
INLET AIR
SUCTION LINE
CONNECTION
B
24-1/4
(616)
3/4 (19)
2-3/4 (70)
24-1/4
(616)
ELECTRICAL
INLETS
LIQUID LINE
CONNECTION
Model No. A B
10ACB12 10ACB18
in. 25 24-1/4
10ACB18
10ACB24 10ACB30
mm 635 616
10ACB36 10ACB42
in. 33 32-1/4
10ACB48 10ACB60 10ACB62
mm 838 819
All manuals and user guides at all-guides.com
3DJH
SETTING THE UNIT
Refer to unitdimensions on page 2 for sizing mounting slab, platforms or supports. Refer to figure 1 for instal- lation clearances.
INSTALLATION CLEARANCES
FIGURE 1
36
(914 mm)
*36
(914 mm)
36
(914 mm)
NOTE48 inch clearance required on top of unit.
*NOTEOne side must be 36 inches. Two side may be 12.
*36
(914 mm)
Slab Mounting
When installing unit at grade level, install on a level slab high enough above gradeto allow adequatedrain- age of water.
Top of slab should be located so run--off
water from higher ground will not collect around unit.
Roof Mounting
Install unit at a minimum of 4 inches above the surface of the roof. Care must be taken to ensure weight ofunit is properly distributed over roof joists and rafters. Ei- ther redwood or steel supports are recommended.
ELECTRICAL
In the U.S.A., wiring must conform with current local codes and the current National Electric Code (NEC). In Canada, wiring must conform with current local codes and the current Canadian Electrical Code (CEC). Refer to the furnace or blower coil installation instructions for additional wiring application diagrams and refer to unit rating plate for minimum circuit ampacity and maximum overcurrent protection size.
WARNING
Unit must begrounded inaccordance with nation- al and local codes. Electric Shock Hazard. Can cause injury or death.
Line Voltage
To facilitate conduit, a hole is providedin bottom of the control box. Connect conduit to hole in control box with proper conduit fitting.
127( 8QLWV DUH DSSURYH GIRU XVHZLWKFRSSHUFRQGXF WRUV RQO\
24V, Class II Circuit
24V, Class II Circuit connections are made upin thelow voltage junction box. Refer to figure 2 for field wiring diagram.
NOTE -- A complete unit wiring diagram is located in- side the unit control box cover.
TO
COOLING
SPEED
TO
HEATING
SPEED
Y1
RC
WG
RH
CONDENSING UNIT
TYPICAL INDOOR UNIT
ROOM THERMOSTAT
POWER
GROUND
PER NATIONAL
AND LOCAL
CODES
24v
TRANSFORMER
24V
CLASS II
JUNCTION
BOX
TO
HEATING
CONTROLS
TO 24V CLASS II POWER SOURCE
-- 20 VA MINIMUM
K3 INDOOR BLOWER RELAY
NOTE--IF INDOOR UNIT IS NOT EQUIPPED WITH
BLOWER RELAY, IT MUST BE FIELD PROVIDED
AND INSTALLED (P--8--3251 OR EQUIVALENT)
NOTE--SEE UNIT WIRING DIAGRAM
FOR POWER SUPPLY CONNECTIONS.
24V CLASS II INSTALLED AT FACTORY 24V CLASS II FIELD INSTALLED
FIGURE 2
Y1
C
C
T1
R
W1
G
C
W2
10ACB TYPICAL FIELD WIRING DIAGRAM
All manuals and user guides at all-guides.com
3DJH
PLUMBING
Field refrigerant piping consists of liquid and suction lines from the condensing unit (sweat connections) to the indoor evaporator coil (flare or sweatconnections). Use Lennox L10 (flare) or L15 (sweat, non-flare) series line sets as shown in table 1 or use field-fabricated re- frigerant lines. Referto unit information manual piping section for proper size, type and application of field-- fabricated lines.
Sweat Connection Procedure
1-- Ends of refrigerant lines must be cut square, free
from nicks or dents, deburred. Pipe must remain round, do not pinch end of line.
2-- Wrap a wet cloth around the liquid line valve body
and copper tube stub to protect from heat damage during brazing. Wrap another wet cloth underneath the liquid valve to protect the base paint.
3-- Quench the jointswith a wetcloth to preventpossible
heat damage to the valve core and opening port.
4-- A field provided filter drier should be installed as
close as possible to the expansion device.
REFRIGERANT METERING DEVICE
10ACBunits are applicableto either RFCIV oran expan- sion valve system. See indoor coil installation instruc- tions and the Lennox engineering handbook for ap- proved RFC and TXV match-ups and application information. Table1 lists 10ACBunit liquid and suction line sizes and corresponding line sets.
TABLE 1
REFRIGERANT LINE KITS
UNIT
LIQUID
LINE
SUCTION
LINE
L10
LINE SETS
10ACB24
10ACB30
10ACB42
3/8
in
(10 mm)
3/4 in.
(19 mm)
L10--41 20 ft. -- 50 ft. (6m--15m)
10ACB18
5/16 in*
(8 mm)
3/8 in
(10 mm)
L10--65
30 ft. -- 50 ft.
(9m--15m)
L10--21
20 ft. -- 50 ft.
(6m--15m)
5/8 in
(16 mm)
7/8 in.
(22 mm)
10ACB48
3/8 in
(10 mm)
1--1/8 in. (29 mm)
FIELD
FABRICATED
10ACB60
*Use reducer supplied in bag assembly.
L15
LINE SETS
L15--41 20 ft. -- 50 ft. (6m--15m)
L15--65
30 ft. -- 50 ft. (9m--15m)
L15--21 20 ft. -- 50 ft.
(6m--15m)
FIELD
FABRICATED
10ACB36
10ACB62
NOTE -- Line length should be no greater than 50 feet (15.2 m). Select line set diameters from table 1 to en- sure oil return to compressor.
RFC Systems
10ACB units are shipped with an RFCIV metering de- vice. Replace existing RFCIV in indoor unit with RFCIV supplied with the outdoor unit. Place the supplied RFCIV sticker on indoor cabinet after installation. See table 2 for size of RFCIV bullet shipped in each 10ACB unit. In cases of non-traditional applications, RFCIV bullet shipped may not be appropriate. Refer to the in- door coil installation instructions and the engineering handbook for specific orifice information.
7$%/(
5)&,9 '5,// 6,=(6
10ACB UNIT RFCIV PART # RFCIV DRILL SIZE
10ACB12 42J35 0.047 10ACB18 42J39 0.055 10ACB24 66J87 0.062 10ACB30 42J45 0.067 10ACB36 42J48 0.073 10ACB42 42J52 0.080 10ACB48 42J54 0.084 10ACB60 42J58 0.092
RFCIV bullet is installed as shown in figure 3. Take care not to twist cap tubes when loosening seal nut from orifice body.
RF
CIV INSTALLATION
DISTRIBUTOR
BULLET
ORIFICE
ORIFICE
BODY
SEAL
NUT
FIGURE 3
SWEAT
CONNECTION
All manuals and user guides at all-guides.com
Loading...
+ 8 hidden pages