Lennox 10ACB12, 10ACB24, 10ACB18, 10ACB36, 10ACB30 Installation Instructions Manual

...
Page 1
3DJH
£
PRODUCT LITERATURE
¤
1998 Lennox Industries Inc.
Dallas, Texas
VALUE 10TMCONDENSING UNIT
V alue 10 condensing units are designed for expansion valve (TXV) and RFC systems. Refer to Lennox engi- neering handbook for expansion valve kits which must be ordered separately.
SHIPPING AND PACKING LIST
1-- Assembled 10ACB condensing unit 1-- 45Ecopper street elbow 1-- RFCIV refrigerant metering device (bullet) 1-- Coupling -- 5/16 x 3/8 (18, 24, 30)
Check unit for shipping damage. Consult last carrier immediately if damage is found.
GENERAL INFORMATION
These instructions are intended as a generalguide and do not supersede national or local codes in any way. Authorities having jurisdiction should beconsulted be- fore installation.
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFCs and HCFCs)as ofJuly 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or in- carceration may be levied for non--compliance.
INSTALLATION INSTRUCTIONS
9DOXH706HULHV
$&% &RQGHQVLQJ 8QLWV
&21'(16,1* 81,76
1--1/2 through 5 ton 503,800M 2/98
Supersedes 503,755M
TABLE OF CONTENTS
VALUE 10 CONDENSING UNIT 1.....................
SHIPPING AND PACKING LIST 1......................
GENERAL INFORMATION 1..........................
10ACB UNIT DIMENSIONS 2.........................
SETTING THE UNIT 3................................
ELECTRICAL 3......................................
PLUMBING 4.......................................
REFRIGERANT METERING DEVICE 4..................
MANIFOLD GAUGE SET 5...........................
LIQUID & SUCTION LINE SERVICE VALVES 5..........
LEAK TESTING 6....................................
EVACUATION 7.....................................
START-UP 8........................................
CHARGING CONSIDERATIONS 8.....................
CHARGING FOR RFC SYSTEMS 9....................
CHARGING FOR TXV SYSTEMS 10...................
SYSTEM OPERATION 10.............................
MAINTENANCE 11..................................
10ACB CHECK POINTS 12............................
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
WARNING
Product contains fiberglass wool. Disturbing the insulation in this product during
installation, maintenance, or repair will expose you to fiberglass wool. Breathing this may cause lung cancer. (Fiberglass wool is known to the State of California to cause cancer.)
Fiberglass wool may also cause respiratory, skin, and eye irritation.
To reduce exposure to this substance or forfurther information, consult material safety data sheets available from address shown below, or contact your supervisor.
Lennox Industries Inc. P.O. Box 799900 Dallas, TX 75379--9900
/LWKR 86$
All manuals and user guides at all-guides.com
all-guides.com
Page 2
3DJH
10ACB UNIT DIMENSIONS--INCHES (MM)
SIDE VIEW
SUCTION &
LIQUID LINE
CONNECTION
INLET
AIR
INLET
AIR
DISCHARGE AIR
SIDE VIEW
TOP VIEW
A
OUTDOOR
COIL FAN
COMPRESSOR
INLET AIR
INLET AIR
SUCTION LINE
CONNECTION
B
24-1/4
(616)
3/4 (19)
2-3/4 (70)
24-1/4
(616)
ELECTRICAL
INLETS
LIQUID LINE
CONNECTION
Model No. A B
10ACB12 10ACB18
in. 25 24-1/4
10ACB18
10ACB24 10ACB30
mm 635 616
10ACB36 10ACB42
in. 33 32-1/4
10ACB48 10ACB60 10ACB62
mm 838 819
All manuals and user guides at all-guides.com
Page 3
3DJH
SETTING THE UNIT
Refer to unitdimensions on page 2 for sizing mounting slab, platforms or supports. Refer to figure 1 for instal- lation clearances.
INSTALLATION CLEARANCES
FIGURE 1
36
(914 mm)
*36
(914 mm)
36
(914 mm)
NOTE48 inch clearance required on top of unit.
*NOTEOne side must be 36 inches. Two side may be 12.
*36
(914 mm)
Slab Mounting
When installing unit at grade level, install on a level slab high enough above gradeto allow adequatedrain- age of water.
Top of slab should be located so run--off
water from higher ground will not collect around unit.
Roof Mounting
Install unit at a minimum of 4 inches above the surface of the roof. Care must be taken to ensure weight ofunit is properly distributed over roof joists and rafters. Ei- ther redwood or steel supports are recommended.
ELECTRICAL
In the U.S.A., wiring must conform with current local codes and the current National Electric Code (NEC). In Canada, wiring must conform with current local codes and the current Canadian Electrical Code (CEC). Refer to the furnace or blower coil installation instructions for additional wiring application diagrams and refer to unit rating plate for minimum circuit ampacity and maximum overcurrent protection size.
WARNING
Unit must begrounded inaccordance with nation- al and local codes. Electric Shock Hazard. Can cause injury or death.
Line Voltage
To facilitate conduit, a hole is providedin bottom of the control box. Connect conduit to hole in control box with proper conduit fitting.
127( 8QLWV DUH DSSURYH GIRU XVHZLWKFRSSHUFRQGXF WRUV RQO\
24V, Class II Circuit
24V, Class II Circuit connections are made upin thelow voltage junction box. Refer to figure 2 for field wiring diagram.
NOTE -- A complete unit wiring diagram is located in- side the unit control box cover.
TO
COOLING
SPEED
TO
HEATING
SPEED
Y1
RC
WG
RH
CONDENSING UNIT
TYPICAL INDOOR UNIT
ROOM THERMOSTAT
POWER
GROUND
PER NATIONAL
AND LOCAL
CODES
24v
TRANSFORMER
24V
CLASS II
JUNCTION
BOX
TO
HEATING
CONTROLS
TO 24V CLASS II POWER SOURCE
-- 20 VA MINIMUM
K3 INDOOR BLOWER RELAY
NOTE--IF INDOOR UNIT IS NOT EQUIPPED WITH
BLOWER RELAY, IT MUST BE FIELD PROVIDED
AND INSTALLED (P--8--3251 OR EQUIVALENT)
NOTE--SEE UNIT WIRING DIAGRAM
FOR POWER SUPPLY CONNECTIONS.
24V CLASS II INSTALLED AT FACTORY 24V CLASS II FIELD INSTALLED
FIGURE 2
Y1
C
C
T1
R
W1
G
C
W2
10ACB TYPICAL FIELD WIRING DIAGRAM
All manuals and user guides at all-guides.com
Page 4
3DJH
PLUMBING
Field refrigerant piping consists of liquid and suction lines from the condensing unit (sweat connections) to the indoor evaporator coil (flare or sweatconnections). Use Lennox L10 (flare) or L15 (sweat, non-flare) series line sets as shown in table 1 or use field-fabricated re- frigerant lines. Referto unit information manual piping section for proper size, type and application of field-- fabricated lines.
Sweat Connection Procedure
1-- Ends of refrigerant lines must be cut square, free
from nicks or dents, deburred. Pipe must remain round, do not pinch end of line.
2-- Wrap a wet cloth around the liquid line valve body
and copper tube stub to protect from heat damage during brazing. Wrap another wet cloth underneath the liquid valve to protect the base paint.
3-- Quench the jointswith a wetcloth to preventpossible
heat damage to the valve core and opening port.
4-- A field provided filter drier should be installed as
close as possible to the expansion device.
REFRIGERANT METERING DEVICE
10ACBunits are applicableto either RFCIV oran expan- sion valve system. See indoor coil installation instruc- tions and the Lennox engineering handbook for ap- proved RFC and TXV match-ups and application information. Table1 lists 10ACBunit liquid and suction line sizes and corresponding line sets.
TABLE 1
REFRIGERANT LINE KITS
UNIT
LIQUID
LINE
SUCTION
LINE
L10
LINE SETS
10ACB24
10ACB30
10ACB42
3/8
in
(10 mm)
3/4 in.
(19 mm)
L10--41 20 ft. -- 50 ft. (6m--15m)
10ACB18
5/16 in*
(8 mm)
3/8 in
(10 mm)
L10--65
30 ft. -- 50 ft.
(9m--15m)
L10--21
20 ft. -- 50 ft.
(6m--15m)
5/8 in
(16 mm)
7/8 in.
(22 mm)
10ACB48
3/8 in
(10 mm)
1--1/8 in. (29 mm)
FIELD
FABRICATED
10ACB60
*Use reducer supplied in bag assembly.
L15
LINE SETS
L15--41 20 ft. -- 50 ft. (6m--15m)
L15--65
30 ft. -- 50 ft. (9m--15m)
L15--21 20 ft. -- 50 ft.
(6m--15m)
FIELD
FABRICATED
10ACB36
10ACB62
NOTE -- Line length should be no greater than 50 feet (15.2 m). Select line set diameters from table 1 to en- sure oil return to compressor.
RFC Systems
10ACB units are shipped with an RFCIV metering de- vice. Replace existing RFCIV in indoor unit with RFCIV supplied with the outdoor unit. Place the supplied RFCIV sticker on indoor cabinet after installation. See table 2 for size of RFCIV bullet shipped in each 10ACB unit. In cases of non-traditional applications, RFCIV bullet shipped may not be appropriate. Refer to the in- door coil installation instructions and the engineering handbook for specific orifice information.
7$%/(
5)&,9 '5,// 6,=(6
10ACB UNIT RFCIV PART # RFCIV DRILL SIZE
10ACB12 42J35 0.047 10ACB18 42J39 0.055 10ACB24 66J87 0.062 10ACB30 42J45 0.067 10ACB36 42J48 0.073 10ACB42 42J52 0.080 10ACB48 42J54 0.084 10ACB60 42J58 0.092
RFCIV bullet is installed as shown in figure 3. Take care not to twist cap tubes when loosening seal nut from orifice body.
RF
CIV INSTALLATION
DISTRIBUTOR
BULLET
ORIFICE
ORIFICE
BODY
SEAL
NUT
FIGURE 3
SWEAT
CONNECTION
All manuals and user guides at all-guides.com
Page 5
3DJH
Expansion Valve Systems
Expansion valves equipped with either Chatleff or flare type fittings are available from Lennox. Refer to the indoor coil installation instructions ortheengineer- ing handbook for applicable expansion valves for use with specific match--ups.
If an expansion valve application is desired with indoor coil product shipped with an RFCIV orifice, the RFCIV re- strictor must be removed before installing the expan- sion valve.
IMPORTANT
Failure to remove RFCIV wheninstalling an expan- sion valveto the indoor coil will result in improper operation and damage to the system.
0$1,)2/' *$8*( 6(7
A manifold gauge set equipped with low loss hoses should be used when checking unit charge. A manifold gauge set with anything other than low loss hose should not be used.
/,48,' 68&7,21 /,1( 6(59,&( 9$/9(6
The liquid lineand suction line service valves (figures 4 and 5) and gauge ports are accessible from outside the unit. The service ports are used for leak testing, eva- cuating, charging and checking charge.
The valve is equipped with a service port. A schrader valve is factory installed. A service port cap is supplied to protect the schrader valve from contamination and serve as the primary leak seal.
To Access Schrader Port:
1-- Remove service port cap with an adjustable wrench. 2-- Connect gauge to the service port. 3-- When testing is completed, replace service port cap.
T ighten finger tight, then an additional 1/6 turn.
To Open Liquid or Suction Line Service V alve:
1-- Remove stem cap with an adjustable wrench. 2-- Using service wrench and 5/16 hex head extension
back the stem out counterclockwise until the valve stem just touches the retaining ring.
Do not attempt to backseat this valve. Attempts to backseat this valve will cause snap ring to explode from valve body under pressure of refrigerant. Personal injury and unit damage will result.
'$1*(5
3-- Replace stem cap tighten firmly. Tighten finger tight,
then tighten an additional 1/6 turn.
FIGURE 4
LIQUID LINE SERVICE VALVE (VALVE OPEN)
SCHRADER
VALVE
SERVICE
PORT
SERVICE
PORT
CAP
INSERT HEX
WRENCH HERE
TO INDOOR
COIL
TO OUTDOOR
COIL
STEM CAP
SCHRADER VALVE OPEN
TO LINE SET WHEN VALVE
IS CLOSED (FRONT SEATED)
SERVICE
PORT
SERVICE
PORT CAP
RETAINING RING
STEM CAP
INSERT HEX
WRENCH HERE
LIQUID LINE SERVICE VALVE (VALVE CLOSED)
(VALVE FRONT SEATED)
TO OUTDOOR
COIL
TO INDOOR
COIL
To Close Liquid or Suction Line Service V alve:
1-- Remove stem cap with an adjustable wrench. 2-- Using service wrench and 5/16 hex head exten-
sion, turn stem clockwise to seatthe valve. Tighten firmly.
All manuals and user guides at all-guides.com
Page 6
3DJH
3-- Replace stem cap. T ighten finger tight, then tighten
an additional 1/6 turn.
FIGURE 5
SUCTION LINE SERVICE VALVE (VALVE OPEN)
SCHRADER
VALVE
SERVICE PORT
SERVICE PORT
CAP
INSERT HEX
WRENCH HERE
TO INDOOR
COIL
TO OUTDOOR
COIL
STEM CAP
SCHRADER VALVE OPEN
TO LINE SET WHEN VALVE IS
CLOSED (FRONT SEATED)
SERVICE
PORT
SERVICE PORT
CAP
RETAINING RING
STEM CAP
INSERT HEX
WRENCH HERE
SUCTION LINE SERVICE VALVE (VALVE CLOSED)
(VALVE FRONT
SEATED)
TO INDOOR
COIL
TO OUTDOOR
COIL
5
--Ton Suction Line (Ball Type) Service Valve
A ball-ty pe full service valve only is used on five ton units (10ACB60/62 ). These suction line service valves function the same way ,differences are in construction. Valves are not rebui ldabl e. If a valve has failed i t must be re- placed. A ball valv e valve is illustra ted in fi gure 6.
The ball valve is equipped with a s ervic e port. A schrader valveis fac tory installed. A service po rt cap is suppli ed to prot ect the schrader val ve from c on- tamination and assure a leak free seal.
SUCTION LINE (BALL TYPE) SERVICE VALVE
(VALVE OPEN)
FIGURE 6
SCHRADER VALVE
SERVICE PORT
SERVICE PORT
CAP
STEM CAP
STEM
USE ADJUSTABLE WRENCH
ROTATE STEM CLOCKWISE 90ETO CLOSE
ROTATE STEM COUNTER-CLOCKWISE 90ETO OPEN
BALL
(SHOWN OPEN)
TO OUTDOOR COIL
TO INDOOR COIL
/($. 7(67,1*
After the line set has been connected to the indoor and outdoor units, the line set connections and indoor unit must be checked for leaks.
WARNING
Never use oxygen to pressurize refrigeration or air conditioning system. Oxygen will explode on con- tact with oil and could cause personal injury. When using high pressure gas such as nitrogen or CO
2
for this purpose, be sure to use a regulator that can control the pressure down to 1 or 2 psig.
Using an Electronic Leak Detector or Halide
1-- Connect cylinder of HCFC-22to center port of man-
ifold gauge set.
2-- With both manifold valves closed, open the valve
on the HCFC-22 bottle (vapor only).
3-- Open the high pressure side of the manifold to al-
low HCFC-22 into the line set and indoor unit. Weigh in a trace amount of HCFC-22.
(A trace
amount is a maximum of 2 ounces or 3 poun
ds
pressure.)
Close the valve on the HCFC-22 bottle and the valveon the high pressure side of theman- ifold gauge set. Disconnect HCFC-22 bottle.
4-- Connect a cylinder of nitrogen with a pressure reg-
ulating valve to the center port of the manifold gauge set.
All manuals and user guides at all-guides.com
all-guides.com
Page 7
3DJH
5 -- Connect the high pressure hose of the manifold
gauge set to the service port of the suction valve.
(Normally, the high pressure hose is connected to the liquid line port, however, connecting it to the suction port better protects the manifold gauge set from high pressure damage.)
6-- Adjust nitrogen pressure to 150 psig. Open the
valve on the high side of the manifold gauge set which will pressurize line set and indoor unit.
7-- After a short period of time, open a refrigerant port
to make sure the refrigerantadded is adequate to be detected. (Amounts of refrigerant will vary with line lengths.) Check all joints for leaks. Purge nitrogen and HCFC-22 mixture. Correct any leaks and re- check.
(9$&8$7,1*
Evacuating the system of non--condensables is critical for proper operation of the unit. Non--condensables are defined as anygas that will not condense under temper- atures and pressures present during operation of an air conditioning system. Non--condensables and water va- por combine with refrigerant to produce substances that corrode copper piping and compressor parts.
1-- Connect manifold gauge set to the service valve
ports as follows: low pressure gauge to suction line service valve; high pressure gauge to liquid line service valve.
2-- Connect the vacuum pump (with vacuum gauge)
to the center port of the manifold gauge set.
3-- Open both manifold val ves and start vacuum
pump.
4-- Evacuate the lineset and indoorunit to an
absolute
pressure
of 23mm of mercury or approximately 1 inch of mercury. During the early stages ofevacua- tion, it is desirable to close the manifold gauge valve at least once to determine if there is a rapid rise in
absolute pressure
. A rapid rise in pressure indicates a relatively large leak. If this occurs, the leak testing procedure must be repeated.
NOTE -- The term
absolute pressure
means the to-
tal actual pressure within a given volume or sys- tem, above theabsolute zero of pressure. Absolute pressure in a vacuum is equal to atmospheric pres- sure minus vacuum pressure.
5-- When the absolute pressure reaches 23mm ofmer-
cury, close the manifold gauge valves, turn off the vacuum pump and disconnect the manifold gauge center port hose from vacuum pump. Attach the manifold center port hose to a nitrogen cylinder with pressure regulator set to 150 psig and purge the hose. Open the manifold gauge valves to break the vacuum in the line set and indoor unit. Close the manifold gauge valves.
&$87,21
Danger of Equipment Damage. Avoid deep vacuum operation. Do not use com- pressors to evacuate a system. Extremely low vacuums can cause internal arcing and compressor failure. Damage caused by deep vacuum operation will void warranty.
6-- Shut off the nitrogen cylinderand remove the man-
ifold gauge hose from the cylinder. Open the man- ifold gauge valves to release the nitrogen from the line set and indoor unit.
7-- Reconnect the manifold gauge to the vacuum
pump, turn the pump on and continue to evacuate the line set and indoor unit until the absolute pres- sure does not rise above .5mm of mercury within a 20 minute period after shutting off the vacuum pump and closing the manifold gauge valves.
8-- Depending on the equipment used to determine
the vacuum level, the following units are equiva- lent to absolute pressure of .5mm of mercury or 500 microns.
9-- When theabsolute pressure requirement abovehas
been met, disconnect the manifold hose from the vacuum pump and connect it to an upright bottle of HCFC-22 refrigerant. Open the manifold gauge valves to break the vacuum in the line set and in- door unit. Close manifold gauge valves and shut off HCFC-22 bottle and remove manifold gauge set.
All manuals and user guides at all-guides.com
Page 8
3DJH
67$5783
IMPORTANT
Crankcase heater (used on 3--1/2, 4 and 5 ton units) should be energized 24 hours before unit start--up to prevent compressor damage as a re- sult of slugging.
1-- Rotate fan to check for frozen bearings or binding. 2-- Inspect all factory and field-installed wiring for
loose connections.
3-- After evacuation is complete, open liquid line and
suction line service valves to release refrigerant charge (contained in condensing unit) into thesys- tem.
4-- Replace stem caps and secure finger tight, then
tighten an additional (1
/6) one-sixth of a turn.
5-- Check voltagesupply at the disconnect switch. The
voltage must be within the range listed on unit nameplate. If not, do not start the equipment until the power company has been consulted and the voltage condition corrected.
6-- Set the thermostat for cooling demand, turn on
power to evaporator blower and close condensing unit disconnect switch to start unit.
7-- Recheck voltage with unit running. Power must be
within range shown on nameplate. Check amper- age draw of unit. Refer to unit nameplate for cor- rect running amps.
&+$5*,1* &216,'(5$7,216
Units are factory charged with the amount of HCFC-22 refrigerant indicated on the unit rating plate. This charge is based on a matching indoor coil and outdoor coil with 20 ft. (6.1m) line set. For varying lengths of line set, refer to table 3 for refrigerant charge adjustment. A blank space is provided on the rating plate to list the ac- tual field charge.
Liquid Line
Set Diameter
Ozs. per 5 ft. (ml per mm) adjust
from 20 ft. (6.1m) line set*
3/8 in.
(10mm)
5/16 in.
(8mm)
2 ounce per 5 ft.
(57ml per 1.5m)
3 ounce per 5 ft.
(85ml per 1.5m)
*If line length is greater than 20 ft. (6.1m), add this amount. If line length is less than 20 ft. (6.1m), subtract this amount.
TABLE 3
If the system is void of refrigerant, the recommended and most accurate method of charging is to weigh the refrigerant into the unit according to the total amount shown on the unit nameplate. This may be done after any leaks have been repaired. If weighing facilities are not available or if unit is just low on charge, use one of the procedures outlined.
Charging a condensing unit is recommended during warm weather. However, applications arise in which charging must occur in the colder months.
The way the
unit is charged depends on the units
refrigerant me-
tering
device
and the
outdoor ambient temperature
.
For RFC systems,
weighing in the charge
and
subcooling
are two acceptable means of charging under certain conditions. For installations of an RFC system where the outdoor ambient is less than 65EF(18EC), weighing in the charge is the best method. However , in installations where the outdoor ambient is 65EF(18EC) or above, sub- cooling is the best method.
Weighing in the charge
and the
approach
method are the two recommended procedures for charging the 10ACBusing an expansionvalve system forrefrigerant metering. The difference between the two involves the outdoor ambient temperature. For expansion valve systems where the outdoor ambient temperature is 60EF(16EC) or above, the approach method may be used. For expansion valve systems where the outdoor ambient temperature is below 60EF(16EC),weighing in the charge is recommended.
All manuals and user guides at all-guides.com
Page 9
3DJH
TABLE 4
NORMAL OPERATI NG PRESSURES IN PSIG (LIQUID AND SUCTION +/-- 10 PSIG)*
OUT. COIL
ENTERING
10ACB12 10ACB18 10ACB24 10ACB30 10ACB36 10ACB42 10ACB48 10ACB60 10ACB62
MODE
ENTERING
AIR TEMP.
qF(q
C)
LIQ. SUC. LIQ. SUC. LIQ. SUC. LIQ. SUC. LIQ. SUC. LIQ. SUC. LIQ. SUC. LIQ. SUC. LIQ. SUC.
65 (18.3) 145
71 155 65 160 65 168 63 176 62 162 68 157 69 153 66 159 64
75 (23.9) 167 77 181 70 188 70 197 68 203 66 185 72 182 72 180 71 188 68
RFCIV
85 (29.4) 192 81 208 75 216 74 227 73 233 70 210 73 204 73 210 74 219 72
95 (35.0) 221 84 238 80 247 78 258 77 266 74 252 76 244 76 245 77 253 75
105 (40.6) 253 87 270 84 280 82 292 80 299 77 287 79 278 79 279 79 287 76
65 (18.3) 140 79 159 73 164 71 173 71 179 68 157 71 158 70 142 73 151 69
75 (23.9) 161 80 183 75 189 73 199 73 205 70 187 73 182 72 168 75 179 71
TXV
85 (29.4) 189 81 209 77 217 75 228 75 235 72 217 74 205 73 202 76 211 73
95 (35.0) 220 83 238 80 247 78 258 77 266 74 255 76 246 76 245 77 249 74
105 (40.6) 254 84 269 82 279 80 292 79 299 77 289 77 280 79 280 78 286 75
*These are typical pressures only. Indoor evaporator match up, indoor air quality and evaporator load will cause the pressures to vary.
IMPORTANT
Use table 4 as a general guidefor performing main- tenance checks. Table 4 is not a procedure for charging the system. Minor variations in these pressures may be expected due to differences in installations. Significant deviations could mean that the system is not properly charged or that a problem exists with some component in the sys- tem. Used prudently, table 4 could serve as a useful service guide.
Before charging the unit, follow the procedure below to determine: the liquid line temperature and the out- door ambient temperature.
1 -- Connect manifold gauge set to service valves: low
pressure gauge to suction valve service port; high pressure gauge to liquid valve service port. Con- nect the center manifold hose to an upright bottle of HCFC-22. Close manifold gauge set valves.
2 -- Set the room thermostat to call for heat. This will
create the necessary load forproperly charging the system in the cooling cycle.
3 -- Record the outdoor ambient temperature. For
greater accuracy, use the same electronic ther- mometer to measure liquid temperature.
4 -- When thermostat demand has been satisfied,
switch to cooling mode with a set point of 68EF (20EC). When pressures have stabilized, record the liquid line temperature.
5 -- The outdoor temperature will determine which
charging method to use. Proceed with the ap- propriate charging procedure below.
&+$5*,1* )25 5)& 6<67(06
Weighing in the Charge Method
RFC Systems, < 65EF
(18EC)
Outdoor Temp
1-- Recover the refrigerant from the unit. 2-- Conduct a leak check, then evacuate as previously
outlined.
3-- Weigh in the factory charge as shown on the out-
door units rating plate.
The Subcooling Method
RFC Systems, >
65EF
(18EC)
Outdoor Temp
1-- With the manifold gauge hosestill on the liquidser-
vice port and the unit operating stably, record the liquid line temperature.
2-- At the same time, record the liquid line pressure
reading.
3-- Using a temperature/pressure chart for HCFC-22,
determinethe saturation temperature forthe liquid line pressure reading.
All manuals and user guides at all-guides.com
Page 10
3DJH 
4-- Subtract the liquid line temperature from the satu-
ration temperature (according to the chart) to de- termine subcooling.
(Saturation temperature --
Liquid line temperature = Subcooling)
5-- Compare the subcooling value with those in table
5. If subcooling is greater than shown, some refrig- erant must be recovered. If subcooling is less than shown, some refrigerant must be added.
TABLE 5
SUBCOOLING FOR RFC SYSTEMS
OUTDOOR
LIQUID SUBCOOLING [+ 1EF (.6EC)]
TEMP.
EF(E
C)
012 018 024 030 036 042 048 060
60
(16)
14
(7.8)17(9.5)18(10)18(10)14(8)14(8)12(6.7)14(8)
65
(18)
13
(7.2)16(8.9)16(8.9)17(9.5)13(7.8)13(7.8)11(6.1)14(8)
70
(21)
12
(6.7)15(8.3)14(7.8)16(8.9)12(6.7)13(7.8)10(5.6)13(7.8)
75
(24)
10
(5.6)14(7.8)12(6.7)15(8.3)10(5.6)12(6.7)9(5)13(7.8)
80
(27)
9
(5)13(7.2)11(6.1)14(8)9(5)11(6.1)9(5)12(6.7)
85
(29)
8
(4.5)12(6.7)10(5.6)13(7.8)8(4.4)10(5.6)9(5)12(6.7)
90
(32)
7
(3.9)11(6.1)9(5)12(6.7)7(3.9)10(5.6)8(4.5)12(6.7)
95
(35)
6
(3.3)9(5)8(4.5)11(6.1)6(3.3)9(5)8(4.5)12(6.7)
100 (38)
4
(2.2)8(4.5)7(3.9)10(5.6)5(2.8)9(5)8(4.5)11(6.1)
105 (41)
2
(1.1)7(3.9)6(3.3)9(5)4(2.2)9(5)7(3.9)10(5.6)
110 (43)
2
(1.1)6(3.3)6(3.3)7(3.9)3(1.7)8(4.5)7(3.9)9(5)
115 (45)
1
(0.6)5(2.8)5(2.8)5(2.8)2(1.1)7(3.9)6(3.3)8(4.5)
Note -- For best results, the same electronic thermometer should be used to check both outdoor ambient and liquid temperatures.
&+$5*,1* )25 7;9 6<67(06
Weighing in the Charge
TXV Systems, < 60EF
(16EC)
Outdoor Temp
1-- Recover the refrigerant from the unit. 2-- Conduct a leak check, then evacuate as previously
outlined.
3-- Weigh in the factory charge as shown on the out-
door units rating plate.
The Approach Method
TXV Systems, >
60EF
(16EC)
Outdoor Temp
Having taken the outdoor ambient and liquid line tem- perature readings, subtract the outdoor ambient tem- perature from the liquid line temperature to determine the Approach temperature.
(Liquid LineEF(EC) -- Out-
door AmbientEF(EC) = Approach Temperature.)
The
resulting difference (Approach temperature) should
agree with the values given in table 6. If not, add refrig- erant to lower the approach temperature or recover re- frigerant from the system to increase the approach temperature.
TABLE 6
APPROACH METHOD
MODEL
NO.
APPROACH TEMPERATURE
LIQUID LINE -- OUTDOOR AMBIENT
EF(E
C)
10ACB12 7 (3.9) 10ACB18 5 (2.8) 10ACB24 9 (5) 10ACB30 10 (5.6) 10ACB36 12 (6.7) 10ACB42 14 (8) 10ACB48 13 (7.2) 10ACB60 12 (6.7) 10ACB62 12 (6.7)
Note -- For best results, the same electronic thermometer should be used to check both outdoor ambient and liquid temperatures.
6<67(0 23(5$7,21
Condensing unit and indoor blower cycle on demand from room thermostat. When thermostat blower switch is switched toONposition, indoor blower oper- ates continuously.
Crankcase Heater
Three and one-half, four and five ton units areequipped with internal self-regulating crankcase heaters.
Compressor Start Kit
Three and one-half, four and five ton single-phase units have internal start components and do not require field installation of a compressor start kit.
Timed-Off Control (Option Units ONLY)
Option units are factory-equipped with a timed-off control which helps equalize system pressures that al- lows the compressor to start in an unloaded condition as well as preventing compressor short-cycling. The timed-off control delays compressor start-up for five minutes on thermostat demand. Mounted in the con- trol box, the control is wired between thermostat ter- minal Y and the compressor contactor.
High and Low Pressure Switches (International and Option Units ONLY)
10ACB international and option units are factory- equipped with both high and low pressure switches. The pressure switches are located on thevalve cores in the liquid line to allow easy access. The manually reset high pressure switch protects the system from high pressure conditions as a result of a fan failure or a
All manuals and user guides at all-guides.com
Page 11
3DJH 
blocked or dirty coil. The low pressure switch (SPST, NO) protects thesystemcompressor fromdamage due to loss of charge. The switch will trip at 15 +/-- 5 psig (103 +/-- 34kPa) and automatically resets at 25 +/--3 psig (172 +/-- 21 kPa).
Refrigerant Sight Glass (Option Units ONLY)
A refrigerant sight glass is provided in the bag assem- bly for field installation. The sight glass can beinstalled in the liquid line to help monitor system charge.
0$,17(1$1&(
:$51,1*
(OHFWULF VKRFN KD
]DUG &DQ FDXVH LQMX U\ RU GHDWK %HIRUH DWWHPSWLQJ WR SHU IRUP DQ\ VHUYLFH RU PDLQWHQDQFH WXUQ WKH HOHFWULFDO SRZHU WR XQLW 2)) DW GLV FRQQHFW VZLWFKHV 8QLW PD\ KDYH PXOWLSOH SRZHU VXSSOLHV
At the beginning of each cooling season, the system should be checked as follows:
1-- Clean and inspect condenser coil. Coil may be
flushed with a water hose. Make sure power is off before cleaning.
2-- Visually inspect connecting lines and coils for evi-
dence of oil leaks.
3-- Check wiring for loose connections. 4-- Check for correct voltage at unit (unit operating). 5-- Check condenser fan motor amp--draw.
Unit nameplate _________ Actual ____________ .
127(,IRZQHU FRPSODLQV RI LQVXIILFLHQW FRROLQJ WKH XQLW VKRXOG EH JDXJHG DQG UHIULJHUDQW FKDUJH FKHFNHG 5HIHU WR VHFWLRQ RQ UHIULJHUDQW FKDUJLQJ LQ WKLV LQVWUXFWLRQ
Evaporator Coil
1-- Clean coil, if necessary. 2-- Check connecting lines and coils for evidence of oil
leaks.
3-- Check condensate line and clean, if necessary.
Indoor Unit
1-- Clean or change filters. 2-- Adjust blower speed for cooling. The pressure drop
over the coil should be measured to determine the correct blower CFM. Refer to the unit information service manual for pressure drop tables and proce- dure.
3--
Belt Drive Blowers --
Check belt forwear andproper
tension. 4-- Check all wiring for loose connections 5-- Check for correct voltage at unit (blower operat-
ing). 6-- Check amp-draw on blower motor
Unit nameplate_________ Actual ____________.
All manuals and user guides at all-guides.com
all-guides.com
Page 12
3DJH 
67$57
83 $1' 3(5)250$1&( &+(&. /,67
-RE 1DPH
-RE /RFDWLRQ
,QVWDOOHU
8QLW 0RGHO 1R
1DPHSODWH 9ROWDJH
0LQLPXP &LUFXLW $PSDFLW\
0D[LPXP 2YHUFXUUHQW 3URWHFWLRQ 6L]H
5HIULJHUDQW /LQHV
6HUYLFH 9DOYHV )XOO\ 2SHQ"
&RQGHQVHU )DQ &KHFNHG"
-RE 1R
&LW\
&LW\
6HULDO 1R
'DWH
6WDWH
6WDWH
6HUYLFH WHFKQLFLDQ
$PSV
6XSSO\ &RQGHQVHU )DQ
&RPSUHVVRU
,QGRRU )LOWHU &OHDQ"
,QGRRU %ORZHU &)0
6XSSO\ 9ROWDJH 8QLW 2II 63 'URS 2YHU (YDSRUDWRU 'U\
&RQGHQVHU (QWHULQJ $LU 7HPSHUDWXUH
'LVFKDUJH 3UHVVXUH 6XFWLRQ 3UHVVXUH
&22/,1* 6(&7,21
7+(50267$ 7
5HIULJHUDQW &KDUJH &KHFNHG"
3URSHUO\ 6HW" /HYHO"
3URSHUO\ ,QVXODWHG"
6HUYLFH 9DOYH &DSV 7LJKW"
/HDN &KHFNHG"
9ROWDJH :LWK &RPSUHVVRU 2SHUDWLQJ
(OHFWULFDO &RQQHFWLRQV 7LJKW"
All manuals and user guides at all-guides.com
Loading...