Lennox 1003C User Manual

EPA CERTIFIED
CATALYTIC WOOD
BURNING STOVE
RETAIN THESE
INSTRUCTIONS
FOR FUTURE
REFERENCE
INSTALLATION AND OPERATION
MANUAL
MODEL 1003C
THIS APPLIANCE MUST BE INSTALLED BY A QUALIFIED INSTALLER.
READ ENTIRE MANUAL THOROUGHLY BEFORE INSTALLATION.
P/N 775003M, Rev. P, 11/03
IMPORTANT WARNINGS
CAUTION: PLEASE READ THIS ENTIRE MANUAL BEFORE YOU INSTALL AND USE YOUR NEW ROOM HEATER. FOR YOUR SAFETY, FOLLOW THE INSTALLATION, OPERATION AND MAINTENANCE INSTRUC­TIONS EXACTLY, WITHOUT DEVIATION. FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN PROPERTY DAMAGE, BODILY INJURY, OR EVEN DEATH. IF THIS APPLIANCE IS NOT PROPERLY INSTALLED, A HOUSE FIRE MAY RESULT. CONTACT YOUR LOCAL BUILDING OR FIRE OFFICIALS ABOUT RESTRICTIONS AND INSTALLATION INSPECTION REQUIREMENTS IN YOUR AREA.
1. If utilizing an older chimney, it must be in­spected for adequate serviceability. Refer to the heading Chimney Inspection on page 10 of this manual.
2. The minimum clearances must be maintained for all combustible surfaces and materials in­cluding; furniture, carpet, drapes, clothing, wood, papers, etc. Do not store firewood within this clearance space. Failure to maintain clear­ances to all combustibles may result in a house fire.
3. This appliance requires non-combustible floor protection as outlined in this manual (see Floor Protection on page 5 for additional information).
4. Minimum ceiling height must be 7 feet (213 cm) (measured from base of appliance to ceiling).
5. DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE CONNECTED TO ANOTHER APPLIANCE.
6. Do not connect this appliance to air ducts or any air distribution system.
7. PREVENT CREOSOTE FIRE: Inspect and clean chimney frequently. Under certain conditions of use, creosote buildup may occur rapidly. In­spect chimney connector and chimney twice monthly and clean if necessary. Using green or inadequately seasoned wood can greatly in­crease creosote buildup. Use dry wood to mini­mize creosote buildup.
8. USE SOLID WOOD FUEL ONLY: This appliance is approved for burning dry seasoned natural wood only. CAUTION: BURN UNTREATED WOOD ONLY. OTHER MATERIALS SUCH AS WOOD PRESERVATIVES, METAL FOILS, COAL, PLASTIC, GARBAGE, SULFUR OR OIL MAY DAMAGE THE CATALYST. DO NOT BURN GARBAGE OR FLAMMABLE FLUIDS SUCH AS GASOLINE, NAPHTHA OR ENGINE OIL.
9. Never use gasoline, gasoline-type lantern fuel, kerosene, charcoal lighter fluid, or similar liq­uids to start or "freshen up" a fire in this heater. Keep all such liquids well away from the heater while it is in use.
10. DO NOT OVERFIRE: If heater or chimney con­nector glows, you are overfiring. Overfiring this appliance could cause a house fire. Overfiring is
a condition where the appliance is operated at temperatures above its design capabilities (see Overfiring, on page 23). Overfiring can be caused by improper installation, improper op­eration, lack of maintenance or improper fuel usage. Damage caused from overfiring is NOT covered under the manufacturers limited war­ranty. (see Care and Operation, pages 14 to 17).
11. NEVER LEAVE AN UNATTENDED STOVE BURNING ON HIGH. Operation of the stove with the primary air control at its highest burn rate setting for extended periods can cause danger­ous overfiring conditions. The primary air con­trol should only be positioned at the highest setting during start-up procedures and for short durations. When leaving the stove unattended ensure that the primary air control is set to the low or medium low range.
12. Use a metal container with a tight fitting lid to dispose of ashes.
13. IN THE EVENT OF A COMPONENT FAILURE, USE ONLY COMPONENTS PROVIDED BY THE MANUFACTURER AS REPLACEMENT PARTS.
14. Burning any kind of fuel uses oxygen from the dwelling. Be sure that you allow an adequate source of fresh air into the room where the stove is operating (see Ventilation, page 11 and Outside Air, page 8).
15. CAUTION: HOT WHILE IN OPERATION. An ap­pliance hot enough to warm your home can se­verely burn anyone touching it. Keep children, clothing and furniture away. Contact may cause skin burns. Do not let children touch the appli­ance. Train them to stay a safe distance from the unit.
16. Build fires directly upon the brick hearth inside the stove. Do not use grates, irons or any other method to elevate the fire.
17. SAVE THESE INSTRUCTIONS.
18. See the listing label located on the back of stove (or see Safety/Listing Label on page 29).
PAGE 2
TABLE OF CONTENTS
Important Warnings ................................................ 2
Testing/Listing, EPA, Using this Manual.................. 3
Planning Your Installation ..................................... 4-7
Manufactured (Mobile) Home Requirements ...........8
Installation .......................................................... 8-13
Care and Operation .......................................... 14-17
Recommended Fuel ......................................... 17-18
Maintenance ..................................................... 18-20
Troubleshooting ................................................ 21-23
Specifications..........................................................24
Replacement Parts List..................................... 25-27
Optional Accessories ..............................................28
Safety/Listing Label.................................................29
EPA Label ...............................................................30
Ownership Records ...............................................31
TESTING/LISTING
Model 1003C has been tested to UL Standard 1482 and ULC-S627 by OMNI-Test Laboratories Inc.; Bea­verton, Oregon; Report number #030-S-02-2.
EPA CERTIFICATION
This stove has been tested to rigorous emissions stan­dard, and has been certified by the Environmental Pro­tection Agency.
USING THIS MANUAL
Please read and carefully follow all of the instructions found in this manual. Please pay special attention to the safety instructions provided in this manual. The Home­owner’s Care and Operation Instructions included here will assure you have many years of dependable and enjoyable service from your appliance.
CONGRATULATIONS ON THE PURCHASE OF YOUR NEW WOODSTOVE MANUFACTURED BY LENNOX HEARTH PRODUCTS.
When you purchased your new woodstove, you joined the ranks of thousands of concerned indi­viduals whose answer to their home heating needs reflects their concern for aesthetics, efficiency and our environment. We extend our continued support to help you achieve the maximum benefit and en­joyment available from your new wood stove.
It is our goal at Lennox Hearth Products to provide you, our valued customer, with an appliance that will ensure you years of trouble free warmth and pleasure.
Thank you for selecting a Lennox Hearth Products stove as the answer to your home heating needs.
Sincerely, All of us at Lennox Hearth Products
PACKAGING LIST
This appliance is packaged with an accessory package, which contains the following:
One - Installation and operation instructions manual. One - Warranty. One - Catalytic combustor temperature probe and
sleeve.
One - Damper Hook
PAGE 3
PLANNING YOUR INSTALLATION
QUESTIONS TO ASK LOCAL BUILDING OFFICIAL
A correct installation is critical and imperative for reduc­ing fire hazards and perilous conditions that can arise when wood burning appliances are improperly installed. The installer must follow all of the manufacturers’ in­structions.
The installation of a wood burning appliance must con­form to local codes and applicable state and federal requirements. Familiarity with these requirements be­fore installation is essential. Important considerations to discuss with local building officials include:
1. Applicable codes (i.e. Uniform Mechanical Code, State or Regional Codes.)?
Electrical codes: Optional Blower Assemblies have a
flexible electrical cord that must be electrically grounded per local codes or per electrical codes:
In USA, NEC, ANSI/NFPA 70-2002. In Canada, CSA C22.1
WARNING: ELECTRICAL GROUNDING INSTRUC­TIONS: THIS APPLIANCE IS EQUIPPED WITH A THREE-PRONG (GROUNDING) PLUG FOR YOUR PROTECTION AGAINST SHOCK HAZARD AND SHOULD BE PLUGGED DIRECTLY INTO A PROP­ERLY GROUNDED THREE-PRONG RECEPTACLE. DO NOT CUT OR REMOVE THE GROUNDING PRONG FROM THIS PLUG. DO NOT ROUTE POWER CORD UNDER OR IN FRONT OF APPLI­ANCE.
2. Local amendments?
3. Is a permit required - cost?
(You may wish to contact your insurance company
to ask if they require this).
4. Is outside combustion air required?
5. Rooms where the installation is not allowed?
SMOKE DETECTORS Since there are always several potential sources of fire in any home, we recommend installing smoke detec­tors. If possible, install the smoke detector in a hallway adjacent to the room (to reduce the possibility of occa­sional false activation from the heat produced by the stove). If your local code requires a smoke detector be installed within the same room, you must follow the re­quirements of your local code. Check with your local building department for requirements in your area.
SELECTING A LOCATION The design of your home and where you place your stove will determine its value as a source of heat. A wood stove depends primarily on air circulation (con­vection) to disperse its heat, and therefore, a central location is often best. There are other practical consid­erations, which must be considered before a final selec­tion of locations is made:
Existing Chimneys Wood Storage Aesthetic Considerations Roof Design (Rafter Locations & Roof Pitch) Room Traffic Proximity to Combustibles Electrical Wiring
The installation of this stove will require some research. Once your options are determined, consult with your local building department who will be able to give you the necessary installation requirements for your area (Is a building permit required, rooms where installation may not be allowed etc.).
WARNING: CHECK ALL LOCAL BUILDING AND SAFETY CODES BEFORE INSTALLATION. THE IN­STALLATION INSTRUCTIONS AND APPROPRIATE CODE REQUIREMENTS MUST BE FOLLOWED EX­ACTLY AND WITHOUT COMPROMISE. ALTERA­TIONS TO THE STOVE ARE NOT ALLOWED. DO NOT CONNECT THE STOVE TO A CHIMNEY SYS­TEM SERVING ANOTHER STOVE, APPLIANCE, OR ANY AIR DISTRIBUTION DUCT. FAILURE TO FOL­LOW THESE INSTRUCTIONS WILL VOID THE MANUFACTURERS WARRANTY.
If you plan to vent your stove into an existing masonry chimney, have the chimney inspected by a local fire marshal or qualified installer. Remember that a stove's performance is heavily influenced by the chimney and its location on the roof. An oversized flue may not pro­vide effective draw, and a flue liner may be required (see Draft Requirements, page 11). Consult your dealer or qualified installer before final selection is made.
This stove requires pre-installation work to be com­pleted before installation can take place. This may in­clude modification for flue and chimney.
NOTE – This appliance IS into a Manufactured (Mobile) Home in Canada and the USA.
approved for installation
PAGE 4
PLANNING YOUR INSTALLATION
FLOOR PROTECTION
This appliance requires non-combustible floor protec­tion for ember protection. If the floor protection is to be stone, tile, brick, etc., it must be mortared or grouted to form a continuous non-combustible surface. If a chim­ney connector extends horizontally over the floor, pro­tection must cover the floor under the connector and at least 2" (51 mm) to either side.
The floor protection must extend completely beneath the stove and to the front, sides, and rear as indicated:
USA REQUIREMENTS
16” (406 mm) min. to the front of the fuel door glass 8” (203 mm) min. beyond the sides of the fuel door
opening
0” (0 mm) min. to the back of the stove body
CANADA REQUIREMENTS 18” (457 mm) min. to the front of the fuel door glass 8” (203 mm) min. beyond the sides of the stove body 8” (203 mm) min. to the back of the stove body
STANDARD PARALLEL HEARTH PAD SHOWN
0” - USA
8” – Can.
STOVE TOP
8” (203 mm)
Canada
8” (203 mm)
USA
DOOR
18” (457 mm)
ada
Can-
8” (203 mm)
8” (203 mm)
USA
Canada
PAGE 5
PLANNING YOUR INSTALLATION
COMBUSTIBLE WALL CLEARANCES
WARNING: IT IS VERY IMPORTANT THAT YOU OB­SERVE THE MINIMUM CLEARANCES.
There are listed clearances for your stove which were deter­mined in a Laboratory test using various "classes" of stove pipe or chimney. Minimums are first established for the stove itself and increased based on how much heat is transferred by each class of pipe.
NOTE: Manufactured (mobile) home installations require the use of a Type L-Vent Chimney connector only. Use of a single wall flue pipe connection is not permitted.
Manufactured (Mobile) Home Standard and Residential Reduced - Using 6” (152 mm) diameter Type L-Vent connector
pipe (to the top of the stove) with listed factory-built 103HT chimney suitable for use with solid fuels or a code approved masonry chimney. Approved brands of factory built chimney are Dura-Vent, Security, Jake Evans and Metal Bestos.
MANUFACTURED (MOBILE) HOME INSTALLATIONS MUST BE EQUIPPED WITH A RAIN CAP AND SPARK ARRESTOR.
Clearances (inches / millimeters)
A. 14 / 356 C. 17 / 432 E. 16 / 406 B. 25 / 635 D. 9 / 229 F. 8 / 203
Residential Standard (not approved for manufactured [mobile] homes) Using 6” (152 mm) diameter, single wall
connector pipe with listed factory-built to the top of the stove.
Clearances (inches / millimeters)
A. 22 / 559 C. 25 / 635 E. 16 / 406 B. 25.5 / 648 D. 16 / 406 F. 15 / 381
Residential Note: Approved for 6” (152 mm) diameter, single wall, minimum 24 MSG black or blued steel con­nector pipe with listed factory-built 103HT chimney suitable for use with solid fuels or a code approved masonry chimney.
Manufactured (Mobile) Home Reduced and Residen­tial Reduced Using 6” (152 mm) diameter Type L-Vent
connector pipe (to the top of the stove) with listed fac­tory-built 103HT chimney suitable for use with solid fuels or a code approved masonry chimney. Approved brands of factory built chimney are Dura-Vent, Security, Jake Evans and Metal Bestos. MANUFACTURED (MOBILE) HOME INSTALLATIONS MUST BE EQUIPPED WITH A RAIN CAP AND SPARK ARRESTOR. Alcove size: 84” (213 cm) minimum height, 56” (143 cm) minimum width, and 24” (610 mm) maximum depth.
Clearances (inches / millimeters)
A. 11 / 280 C. 14.5 / 369 E. 16 / 406 B. 25.5 / 648 D. 5.5 / 140 F. 5.5 / 140
Vent Height (all installations) - The pipe should extend 12 feet above the stove top, as a minimum, to achieve a stable draft.
Corner Installation
F
B
E
C
Parallel Installation
A
45°
D
PAGE 6
PLANNING YOUR INSTALLATION
ALCOVE CLEARANCES NOTE:" = inches, mm = millimeter, cm = centimeter
Alcoves must have minimum dimensions of 84" (214 cm) height, 56" (142 cm) width and 24" (610 mm) maximum depth.
Require pipe: Type L Vent pipe to the top of the stove. Manufactured (mobile) home installations must be equipped with a rain cap and spark arrestor and must use a pipe shield extending a minimum of 24" (610 mm) above the stove (resting on stove) is mandatory for the installation of this appliance into a combustible alcove.
Alcove Dimension Requirements
24” (610 mm)
Depth
Maximum
84”
(214 cm)
Min.
Alcove Top View / Stove Clearances
ALCOVE CLEARANCES:
Back wall to pipe O.D. 11" / 280 mm Side wall to pipe O.D. 25.5" / 648 mm Back wall to stove 5.5" / 140 mm Side wall to stove 16" / 407 mm
56” (143 cm) Minimum
Alcove - Top View
5.5” (140 mm) 11” (280 mm)
16”
(407 mm)
* NOTE: Alcove dimensions cannot
25.5”
(648 mm)
be reduced by the use of non-combustible materials such as brick, stone, etc. Alcove dimensions listed are minimum dimensions and are not measurements for building an Alcove. You will need to consider these clearances, as well as other dimensional requirements before you build the alcove and install this appliance.
REDUCED MASONRY STRUCTURE CLEARANCE (ALCOVE)
Your stove can be installed in a masonry structure with reduced clearances if the structure was built to National Building Code for fireplaces and chimneys (UBC 37).
The firebox of the masonry structure must be of ade­quate size to allow a minimum of 6” (152.4 mm) clear­ance to the sides and top of the stove and 2” (50.8 mm) clearance to the rear. All stove models must be installed on their original listed legs or base unless otherwise specified by OMNI Testing Laboratory.
The minimum venting requirement is a listed chimney liner that extends from the flue collar of the stove to the first tile liner of the chimney where it is sealed. All joints and connections must be made airtight to prevent leak­ing and
downdrafts.
PROTECTED WALL CLEARANCE Some local codes will allow reduced clearances when the stove is installed adjacent to a protected wall system. Your local building official must approve the variance. Normally, the protected wall system is defined as a non­combustible material with a minimum of 1” (25.4 mm) air space behind. Check your local building codes or with a qualified installer (Ref. NFPA 211).
PAGE 7
INSTALLATION
AIR INTAKE COVER
The pedestal is equipped with an air intake cover (lo­cated at the top front of the pedestal). The air intake cover should be adjusted to the open position if outside combustion air is NOT provided. If outside combustion air is provided, adjust to the closed position (see illustra­tion to the right).
Air Intake
Cover
Open
Pedestal
Front
Closed
OUTSIDE AIR
In all manufactured (mobile) homes and in many site built residences (subject to local code), a stove may be required to use outside air for combustion. A 5 ¼” (133 mm) square outside air floor duct is available through your dealer.
Stove
Outside Air Floor Duct
This stove can take in outside air directly through the base. This type installation requires a hole through the floor protector and the use of outside air floor duct (cata­log # 14M67) to penetrate into the air space below the home. When outside air is hooked up, the Air Intake Cover must be adjusted to the closed position (see Air Intake Cover section on this page).
NOTE: Because the base sits 1” (25.4 mm) off the floor, the outside air floor duct can be positioned along the front to rear center line under the pedestal, but as close to the opening in the base as location permits. The air duct opening must be protected from any possible ob­struction including loose floor insulation.
MANUFACTURED (MOBILE) HOME REQUIREMENTS
This stove is certified as a Room Heater, Solid Fuel Type and may be used in Manufactured Housing providing the following requirements are followed:
An outside air inlet must be provided for combustion and be unrestricted while unit is in use.
WARNING: DO NOT INSTALL IN SLEEPING ROOM.
Regulations require that the appliance must be se­cured to the floor and grounded to the chassis. See Securing the Stove to the Floor (and) Grounding Stove.
Required venting is 6” (152 mm) diameter Type L­Vent connector pipe with listed factory-built 103HT chimney suitable for use with solid fuels or a code approved masonry chimney. Approved brands of fac­tory built chimney are listed in this manual. A rain cap and spark arrestor is required (see Clearances, pages 6 & 7).
CAUTION: THE STRUCTURAL INTEGRITY OF THE MOBILE HOME FLOOR, WALL, AND CEIL-
Floor Protector
ING/ROOF MUST BE MAINTAINED.
The chimney must provide for a section joint so that any parts extending above 13’ 6” (411 cm) from ground level can be removed for transportation of the mobile dwelling.
PAGE 8
INSTALLATION
SECURING THE STOVE TO THE FLOOR Manufactured (Mobile) Homes Only
Once the outside air floor duct is in position, replace the floor protector. Make sure that the floor protector's hole is aligned with the outside air opening. Next position and align the stove on the hearth pad. Manufactured (mobile) home installations require that the stove be secured to the floor. This ensures that the stove will not shift when the manufactured (mobile) home is moved. To do this, mark where the holes are to be drilled using a marking instrument long enough and small enough to fit through the (4) four holes in the stove base. Mark holes, then remove the stove. Drill the (4) four holes, with a ¼” (7 mm) drill bit. Drill down through the floor protector and the manufactured (mobile) home floor. Use ¼” (7 mm) lag bolts and secure to the manufactured (mobile) home floor.
NOTE: If the composition of the manufactured (mobile) home floor is of light particleboard construction, you will be required to secure the stove with regular hex head bolts and nuts. This will ensure that the bolts will not rip out of the floor when the manufactured (mobile) home is being moved.
GROUNDING STOVE Manufactured (Mobile) Homes Only
Regulations require that all stoves installed in manufac­tured (mobile) homes must be grounded. To do this sim­ply attach a piece of No. 8 copper wire, at least 18” (457 mm) in length from the stove to the chassis of the manu­factured (mobile) home.
INSTALLING CATALYTIC TEMPERATURE PROBE
Locate the temperature probe with sleeve in the literature packet. Insert sleeve, then temperature probe into the ¼” (7 mm) diameter hole on the stove top.
REMOVE ASH DRAWER CLIP The ash drawer is secured for shipping with a small re­taining screw at the top of drawer. Remove and discard this screw.
TYPES OF CHIMNEYS The chimney is a vital part of your stove installation. A properly built masonry chimney or a properly installed factory built chimney will assure a consistent draft under a variety of weather conditions (a smoking stove is usu­ally caused by a chimney problem). The stove flue size is 6” (152 mm) diameter, which is approximately 28 square inches (712 square millimeters) minimum. The maximum flue size should be no more than (3)-three times the cross sectional area of the size of the stove flue collar. In this case, that would be no larger than a 10“ (254 mm) diameter stack, or approximately 85 square inches (216 square centimeters) maximum.
All chimneys must be installed as specified by local building codes and according to the chimney manufac­turer instructions (in the case of a factory built chimney). See the chimney manufacturer instructions for exact specifications. Factory built chimneys must comply with UL 103HT or ULC S629.
Factory Built Chimney
Tile-lined Masonry Chimney
ACCEPTABLE CONNECTOR PIPE FOR INSTALLA­TIONS For Standard Residential Clearances:
Six 6 inch (152 mm) minimum, single wall, 25 gage minimum thickness, stove pipe is acceptable. Three (3) pre-drilled holes are provided in the flue collar for fastening the pipe securely to the stove. Use sheet metal screws to do this. Addi­tional sections of single wall pipe should be fastened to­gether with at least three (3) sheet metal screws each section. When connecting to the factory built ceiling sup­port package, use the manufacturer's transition piece, usually called a dripless connector, to join single wall pipe to their factory built chimney section.
Minimum Flue Size
: The required minimum diameter
and area required for the flue size is (respectively) 6 inches / 152 mm diameter, which is approximately 28 square inches / 711 square mm. The maximum flue size should be no more than (3) three times the cross sec­tional area of the size of the 6 inches / 152 mm diameter flue collar. In this case, that would be no larger than a 10 inch (254 mm) diameter (area = approx. 85 sq. inches [216 sq. cm]).
Connection To A Factory Built Chimney
: This space
heater is to be connected to a factory-built chimney con­forming to CAN / ULC – S629, Standard for 650°C Fac­tory-Built Chimneys.
For Reduced Residential Clearances
: Type L and
listed double wall connector pipe is acceptable. Install any factory built brand of pipe according to the manufac­turer's instructions.
PAGE 9
INSTALLATION
CHIMNEY INSPECTION
Existing chimneys must be inspected before installing your stove. Consult your local building department for chimney code requirements. A masonry chimney must have a code approved liner. This liner must not have bro­ken or missing pieces. Some non-code masonry chim­neys may be brought up to code by being relined. (Con­sult your dealer or qualified chimney sweep). Factory built chimneys should also be inspected, first for creo­sote deposits (which should be removed), and then for integrity of the stainless steel liner. Look for obvious bulges in the lining, which may indicate the need to re­place that section (use a bright flashlight).
Also, inspect the attic to see that the chimney has proper clearance to combustible framing members. For interior masonry chimneys and most factory-built chimneys, this must be a 2“ (51 mm) air space clearance, which must not be filled with insulation or any other material. An ex­terior masonry chimney must have a 1“ (25.4 mm) air space clearance.
Vapor Barrier At Chimney Penetration
Install all venting components per the Vent Manufactur­ers installation instructions. Ensure that there is an effec­tive vapor barrier at the location where the chimney penetrates to the exterior of the structure. This can be accomplished by applying a non-hardening waterproof sealant to the following components:
Around the chimney at the point where the storm collar will meet the chimney just above the Flashing.
Along the vertical seam of the chimney pipe, where it is exposed to the weather.
On each nail head on the flashing.
Around the chimney at the point where the storm
collar will meet the chimney just above the flashing.
Notes:
On a flat or tarred and graveled roof, nail and seal the flat roof flashing to the roof on all sides with roof­ing compound.
Do not put screws through the flashing into the chim­ney pipe.
CHIMNEY HEIGHT REQUIREMENTS The chimney must extend 3 feet (914 mm) above the level of roof penetration and a minimum of 2 feet (610 mm) higher than any roof surface within 10 feet (305 cm) (see below). Check with your local building officials for any addi­tional requirements for your area.
Due to prevailing winds, local terrain, adjacent tall trees, a hill, or ravine near the home, or adjacent structures, addi­tional chimney height or a special chimney cap may be re­quired to ensure optimum performance.
The 2’ by 10’ Rule for Vent Termination
The top of the flue must be 2’ (610 mm) higher than any part of the roof within 10’ (305 cm) horizontal and a mini­mum of 3’ (915 mm) higher than the highest point of roof penetration.
Requires A Listed Termination Cap
2’ (610mm)
10’ (305 cm)
3’ (915mm)
For Manufactured (Mobile) Homes Only
: Portions of
the chimney and termination that exceed an elevation of 13½ feet above ground level may be designed to be re­moved for transporting the manufactured (mobile) home.
PAGE 10
INSTALLATION
DRAFT REQUIREMENTS
The appliance is merely one component of a larger sys­tem. The other equally important component is the vent­ing system which is necessary for achieving the required flow of combustion air to the fire chamber and for safely removing unwanted combustion byproducts from the ap­pliance. If the venting system's design does not promote these ends, the system may not function properly. Poorly functioning venting systems may create performance problems (i.e. smoking stove, poor heat output, fire goes out, window blackens, increased creosote buildup, etc.) as well as be a safety hazard. Some factors that may lead to performance problems are as follows:
Oversized or undersized chimney.
Excessive offsets in venting.
Insufficient vertical height of chimney.
Insufficient chimney termination height in relationship
to roof.
Insufficient ventilation.
Lack of maintenance.
Improper operation.
Burning improper fuel (unit is approved for use with
natural dry well-seasoned wood only).
Down drafts in the chimney (may need a special wind cap).
To ensure that the venting system is functioning properly a draft test should be performed (see Draft Test Proce-
dure on this page).
American National Standards Institute ANSI/NFPA 211­92: A chimney or vent shall be so designed and con­structed to develop a flow sufficient to completely re­move all flue and vent gases to the outside atmosphere. The venting system shall satisfy the draft requirements of the connected appliance in accordance with the manu­facturer instructions.
DRAFT TEST PROCEDURE
After this appliance is installed a draft test should be per­formed to ensure proper draft. A qualified technician should perform the draft test procedure as follows:
1) Close all windows and doors in the dwelling.
2) Turn on or operate all appliances which remove air from the home (such as a furnace, heat pump, air conditioner, clothes dryer, exhaust fans, fireplaces, and other fuel burning appliances).
3) Drill a hole in the vent pipe per the draft gauge manufacturers instructions (to create a draft test port). Note: Hole location should be a minimum of 1 foot above flue outlet collar.
4) Start a fire (See How To Start And Maintain A Fire on page 16).
5) After the fire is well established (20-25 minutes) and burning at a low setting, perform the draft test per the gauge manufacturer instructions. The draft gauge should read between .05 and .07” W.C. (inches water column). Excessive draft (above .07 W.C.I.) can result in too much combustion air to be pulled into the firebox, this will produce hotter burns and could result in overfiring. Too little draft (below .05” W.C.) will not allow enough combustion air delivery to maintain a fire well or cause performance problems such as smoking (this may result in improper operation of appliance, i.e. will not maintain fire well unless ash drawer or fuel door is left open).
6) Install a screw to seal the draft test port in the vent pipe. If the draft test reading was not within the required range, correct the installation and repeat this procedure.
VENTILATION REQUIREMENTS / PROVIDE ADE­QUATE AIR FOR COMBUSTION
THE FRESH AIR REQUIREMENTS OF THIS APPLI­ANCE MUST BE MET WITHIN THE SPACE WHERE IT WILL BE INSTALLED. VENTILATION IS ESSENTIAL WHEN USING A SOLID FUEL BURNING HEATER.
In well insulated and weather tight homes, it may be diffi­cult to establish a good draft up the chimney (caused by a shortage of air in the home). The lack of air is caused by many common household appliances which exhaust air from the home (such as a furnace, heat pump, air conditioner, clothes dryer, exhaust fans, fireplaces, and other fuel burning appliances). Also, the combustion pro­cess of this heater uses oxygen from inside the dwelling. If the available fresh air delivery in the dwelling is insuffi­cient to support the demands of these appliances, prob­lems can result (i.e. excessive negative pressure can develop in the dwelling which will affect the rate at which this appliance can draft thus resulting in performance problems; See Draft Requirements on this page). To cor­rect this problem it may help to open a window (prefera­bly on the windward side of the house) or install a vent to provide make-up air into the dwelling.
PAGE 11
INSTALLATION
See Pipe Manufacturers Instructions For Installation Requirements Of Venting Components And Vent Clearances.
RESIDENTIAL STANDARD
Using 6” (152 mm) Diameter Single Wall
Connector Pipe. Not Approved For
Manufactured (Mobile) Homes.
Chimney Termination Cap
Storm Collar
MANUFACTURED (MOBILE) HOME STANDARD
Using 6” (152 mm) Diameter Type L-Vent Connector Pipe
Spark Arrestor Cap
3 ft. (915 mm) Minimum
Storm Collar
Flashing
Roof Flashing
Ceiling Support Assembly
Slip Adapter
Chimney Connector
Minimum 12­15 ft. (366­458 cm) of Flue to Achieve a Stable Draft
7 ft. (214 cm)
Minimum
Floor Protection
14.5” (369 mm)
Support Box
DVL Close Clearance Connector
6” x 24” 24-Gage Single Wall Pipe
Square, Outside Air Floor Duct
5 ¼” (134 mm)
IMPORTANT NOTES:
Minimize the use of elbows (30°, 45° or 90°)
- Offsets in the venting system are very restrictive and will inhibit the draft (i.e. You will lose approximately 5 feet of effective draft for every 90 degrees of direction change). This appliance re­quires 12 to 15 feet of effective draft for optimum perform­ance (see Draft Requirements on page 11).
First section of pipe must be vertical - Use as much straight
vertical pipe directly above the appliance as possible be­fore using an elbow (a 2’ to 3’ initial vertical rise is sug­gested).
PAGE 12
INSTALLATION - Combustible Wall Chimney Connector Pass-Throughs
r
d
pp
pp
y
y
A
Min. 12 in. (304.8mm)
Min. Chimney Clearance from Masonry to Sheet Steel
B
Supports & Combustibles – 2 in. (50.8mm)
Factory Built Chimney Length
Air Space – 9 in. (228.6mm) Min.
Min. Chimney Clearance from Masonry to Sheet Steel
C
Supports & Combustibles – 2 in. (50.8mm)
2 Ventilated Air Channels, Each 1 in. (25.4 mm) Construction of Sheet Steel
D
Sheet Steel Supports
Chimney Section
Air Space – 2 in. (50.8mm) Min.
Min. Chimney Clearance to Brick & Combustibles – 2 in. (50.8mm)
Chimney Flue
Nonsoluble Refractory Cement
Chimney Length Flush with In­side of Flue
Chimney
Flue
Masonry Chimney
Sheet Steel Su
Chimney Flue
Masonr Chimney
Min. Chimney Clearance from Masonry to Sheet Steel Supports & Com­bustibles – 2 in.
Chimney Connector
Masonr Chimney
Sheet Steel Su
Sheet Steel Supports
Min. Clearance 12 in. (304.8mm) of Brick
Chimney Connector
Fire Clay Liner
Min. Clearance 9 in. (228.6mm)
Soli Listed Factory­Built Chimney Length
orts
2 Air Channels, Each 1 in. (25.4 mm)
Chimney Connector
Min. 6 in. (152.4mm) glass Fiber Insulation
Chimney Connector
Use Chimney Mfrs. Parts to Attach Connec­tor Securely
-Insulated
orts
Min. Clearance
1 in. (25.4 mm) Air Space to Chimney Length
Chimney Connector
Chimney Length
Method A. 12” (304.8 mm) Clearance to Combustible Wall Mem-
ber: Using a minimum thickness 3.5” (89 mm) brick and a 5/8” (15.9 mm) minimum wall thickness clay liner, construct a wall pass-through. The clay liner must conform to ASTM C315 (Stan­dard Specification for Clay Fire Linings) or its equivalent. Keep a minimum of 12” (304.8 mm) of brick masonry between the clay liner and wall combustibles. The clay liner shall run from the brick masonry outer surface to the inner surface of the chimney flue liner but not past the inner surface. Firmly grout or cement the clay liner in place to the chimney flue liner.
Method B. 9” (228.6 mm) Clearance to Combustible Wall Member: Using a 6” (152.4 mm) inside diameter, listed, factory-built Solid­Pak chimney section with insulation of 1” (25.4 mm) or more, build a wall pass-through with a minimum 9” (228.6 mm) air space be­tween the outer wall of the chimney length and wall combustibles. Use sheet metal supports fastened securely to wall surfaces on all sides, to maintain the 9” (228.6 mm) air space. When fastening supports to chimney length, do not penetrate the chimney liner (the inside wall of the Solid-Pak chimney). The inner end of the Solid-Pak chimney section shall be flush with the inside of the ma­sonry chimney flue, and sealed with a non-water soluble refractory cement. Use this cement to also seal to the brick masonry pene­tration.
Method C. 6” (152.4 mm) Clearance to Combustible Wall Mem­ber: Starting with a minimum 24 gage (.024” [.61 mm]) 6” (152.4 mm) metal chimney connector, and a minimum 24 gage ventilated wall thimble which has two air channels of 1” (25.4 mm) each, construct a wall pass-through. There shall be a minimum 6” (152.4) mm separation area containing fiberglass insulation, from the outer surface of the wall thimble to wall combustibles. Support the wall thimble, and cover its opening with a 24-gage minimum sheet metal support. Maintain the 6” (152.4 mm) space. There should also be a support sized to fit and hold the metal chimney connector. See that the supports are fastened securely to wall surfaces on all sides. Make sure fasteners used to secure the metal chimney connector do not penetrate chimney flue liner.
Method D. 2” (50.8 mm) Clearance to Combustible Wall Member: Start with a solid-pak listed factory built chimney section at least 12” (304 mm) long, with insulation of 1” (25.4 mm) or more, and an inside diameter of 8” (2 inches [51 mm] larger than the 6” [152.4 mm] chimney connector). Use this as a pass-through for a mini­mum 24-gage single wall steel chimney connector. Keep solid-pak section concentric with and spaced 1” (25.4 mm) off the chimney connector by way of sheet metal support plates at both ends of chimney section. Cover opening with and support chimney sec­tion on both sides with 24 gage minimum sheet metal supports. See that the supports are fastened securely to wall surfaces on all sides. Make sure fasteners used to secure chimney section do not penetrate chimney flue liner.
NOTES:
1. Connectors to a masonry chimney, excepting method B, shall extend in one continuous section through the wall pass-through system and the chimney wall, to but not past the inner flue liner face.
2. A chimney connector shall not pass through an attic a floor, or ceiling.
3. Where passage through a wall, or partition of combustible construction is desired, the installation shall conform to CAN/CSA-B365.
or roof space, closet or similar concealed space, o
PAGE 13
CARE AND OPERATI0N
ASH DRAWER
The large ash drawer located on the left side of the ped­estal is designed to make cleaning easier by containing the ashes in a removable drawer.
Ash
Drawer
Secondary Air Tube
Bypass Damper Control
Tunnel Baffle
Positioning Stops
Damper Door
Catalytic Combustor
WARNING: DO NOT OPERATE THIS STOVE WITHOUT THE ASH DRAWER PROPERLY INSTALLED AND SE­CURED (SEALED), AS THIS WILL PRODUCE EX­TREME TEMPERATURES, RESULTING IN OVERFIR­ING. THE ASH DRAWER GASKET PROVIDES AN IM­PORTANT SEAL, AND MUST BE MAINTAINED (SEE MAINTENANCE REQUIREMENTS ON PAGE 19). OVERFIRING CAN RESULT IN DAMAGE TO THE AP­PLIANCE OR A HOUSE FIRE. OPERATION WITH THE ASH DRAWER OPEN OR AJAR, NULLIFIES THE SAFETY LISTING AND VOIDS THE WARRANTY.
CATALYTIC COMBUSTOR How it works: From 5 to 30 percent of the chemical en-
ergy contained in every log escapes up the chimney when wood is burned in a conventional stove. The cata­lytic combustor is designed to make use of this energy, converting it into useful heat as it lessens chimney creo­sote build-up and air pollution. The catalytic combustor consists of a durable temperature resistant ceramic com­position, which is extruded into a cellular, or honeycomb, configuration. After extrusion, this ceramic monolith is fired and then covered with a noble-metal catalyst. When wood smoke contacts this catalyst, chemical changes occur that causes the smoke to ignite at temperatures around 600° F. Normally, smoke will ignite and burn only at temperatures around 1000° F.
CATALYTIC BYPASS DAMPER CONTROL The operating handle of your Bypass Damper Control is located on the front of the Stove Flue Collar. By moving the Bypass Damper Control the operator can route the exhaust either through the Catalytic Combustor (pushed in) or directly up the flue (pulled out). When starting a fire or refueling, the bypass damper control handle should be pulled out. Once the fire is established it should be pushed in.
Catalyic Combustor Retainer Clip
PRIMARY AIR CONTROL
The primary combustion air delivery is controlled by the Primary Air Control Assembly. The control handle is lo­cated on the lower right side (front) of the stove - see illustration below. The heat output can be controlled by sliding the handle to a higher or lower heat output set­ting. The fuel, the amount of heat and burn times de­sired, the type of installation are all variables that will affect the control setting. The same control settings in a variety of installations will produce different results. You will need to try different settings so you can learn how much heat to expect and how long the fire will burn.
Primary Air Control Handle
Slide the control to the left for a lower burn
rate, to the right for a higher burn rate.
LOW HIGH
You will generally want to set the primary air control on low or medium. The stove is safe burning on any setting as long as combustibles are kept at the specified safe distances.
PAGE 14
CARE AND OPERATION
FUEL DOOR
The gold or black door option is purchased separately, but is required. Install the door per instructions provided in kit (see page 28 for ordering information).
WARNING: DO NOT OPERATE THIS STOVE WITHOUT THE DOOR PROPERLY INSTALLED AND SECURED AS THIS WILL PRODUCE EXTREME TEMPERATURES (OVERFIRING). THE DOOR AND GLASS GASKETS PROVIDE IMPORTANT SEALS, AND MUST BE MAIN­TAINED (SEE MAINTENANCE REQUIREMENTS ON PAGE 19). OVERFIRING CAN RESULT IN DAMAGE TO THE APPLIANCE OR A HOUSE FIRE. OPERATION WITH THE DOOR OFF OR OPEN NULLIFIES THE SAFETY LISTING AND VOIDS THE WARRANTY.
Door Operation: The door handle assembly opens and
securely latches the fuel door closed. To open the door, rotate the coil handle to the 9:00 position until door re­leases. To close and latch, hold the coil handle in the 9:00 position, close the door, then rotate the handle to the 6:00 position. See illustration below.
Fuel Door
To Open, Rotate Handle 90 Degrees Clockwise
CAUTION: WHEN OPENING THE DOOR, DO NOT EX­TEND IT BEYOND ITS NORMAL TRAVEL. OVEREX­TENDING THE DOOR TO A FURTHER OPEN POSITION CAN PUT EXCESSIVE STRESS ON HINGE AREA OF DOOR AND HINGE PINS AND MAY RESULT IN BREAK­AGE.
Gold Doors: Gold doors are plated with 24-karat indus-
trial grade gold and will require curing to harden the gold. Once it is cured it will never tarnish. Prior to burning this appliance the doorframe should be cleaned thoroughly with a good window cleaning solution and a soft cloth. Do not use any metal polishes or abrasives to clean the gold surface. Any oils or fingerprints left on the gold could become permanent blemishes if the stove is burned prior to their removal. After the first few fires, the
gold will cure. The ¾” (19 mm) door rope gasket is made of highly durable high temperature resistant mate­rial. It must be kept in good condition. Do not leave the stove burning with the door ajar or open. Leaving the door ajar or open while the stove is burning will cause excessive heat build up in the stove (overfiring) and could ignite surrounding combustibles as well as damage the stove (such damage is not covered by the manufac­turers warranty).
GLASS The Glass is a super heat resistant ceramic that with­stands continuous temperatures up to 1390° F. This tem­perature is well beyond the temperatures in which you operate your stove. If the glass ever becomes damaged in any way, replace it, using only
5 mm ceramic glass
(part # G2000-7).
This appliance is designed to provide a flow of air over the inside of the glass, which along with high heat helps keep it clean. When operating the stove on low for ex­tended periods of time, the glass may get dirty. A short, hot fire (15 - 20 minutes) will help clean off much of the normal buildup (see Troubleshooting, pages 21-23). A commercial glass cleaner designed for stoves is recom­mended for cleaning.
The glass should be cleaned thoroughly with glass cleaner and a soft cloth BEFORE the stove is burned.
USE CONTROL SETTINGS THAT WORK FOR YOU The fuel, the amount of heat you want, the type of instal­lation you have and how long you wish the fire to burn are all variables that will affect the control settings. The same control settings in a variety of installations will pro­duce different results.
Familiarize yourself with your stove by trying different settings so you can learn how much heat to expect and how long the fire will burn. It may take a week or two to learn, but your patience will be rewarded by the warmth and pleasant satisfaction that only a wood fire can pro­vide.
PAGE 15
CARE AND OPERATION
BREAK-IN PERIOD
Your stove finish is a high temperature paint that re­quires time and temperature to completely cure. We rec­ommend that you ventilate the house during the initial burns. The paint emits non-toxic odors during this proc­ess.
KEEP YOUR HOUSE WELL VENTILATED DURING THE CURING PROCESS TO PREVENT ACTIVATION OF YOUR HOME SMOKE DETECTOR.
The paint manufacturer recommends three burn cycles to cure the paint. The first two burns should be low heat, approximately 250° F., for 20 minutes each, using paper and light kindling.
After each 20-minute burn, allow the appliance to cool completely. The third burn should be at least medium high or about 450° F. for 45 - 60 minutes. The paint will become soft and emit non-toxic haze during these burns. Keep the area well ventilated.
As the paint cures it will become slightly lighter in color. Eventually the entire surface will become an even color. Once the paint has been softened and cooled two or three times, it will harden. Do not turn on a blower during the curing process. Do not place anything on the stove surface until the paint is completely cured. Do not at­tempt to repaint the stove until the paint is completely cured. If the surface later becomes stained or marred, it may be lightly sanded and touched up with spray paint from the same paint manufacturer (See Small Area Paint Touch-Up, page 18). Paint is available at your local au­thorized Lennox Hearth Products dealer. Never attempt to paint a hot stove.
CATALYTIC COMBUSTOR
During the start-up of a cold stove, a medium to high fir­ing rate must be maintained for about 20 minutes. The high firing rate will ensure that the stove, the flue, the catalyst, and the fuel are all stabilized at proper operat­ing temperatures. Even though it's possible to have tem­peratures in the stove reach 600° F. within two or three minutes after the fire is started, do not set the primary air control lever to the "LOW" position until approximately twenty minutes have passed. Setting the primary air control on "LOW" too early could result in either the fire or the catalytic combustor going out.
At the end of a burn cycle, it's possible that the hot em­bers remaining might not provide sufficient fuel value for the catalyst to retain its minimum operating temperature of 600° F. During the refueling, we recommend that the stove be refired for about 10 minutes with the bypass open to ensure a good draw is established and that the
catalyst reaches 600° F. The refiring will ensure sufficient temperatures and proper amounts of volatiles for the catalyst to operate properly.
When refueling a hot stove with the catalyst still operat­ing, no refiring step is necessary. Just open the bypass, set the primary air control to high, open the door ap­proximately ½” (1 cm), and wait for about thirty seconds. Load the fuel, close the door, close the bypass and set the primary air control to normal operation. Tempera­tures within the firebox should be hot enough to maintain the catalytic operation.
HOW TO START AND MAINTAIN A FIRE
1. Check to be sure the grate is in place and the ash drawer is closed.
2. Open the bypass damper control by pulling it toward you. In the "OPEN" position the draft air will bypass the catalytic combustor and make starting the fire easier.
3. Set the primary air control lever on "HIGH". The "HIGH" setting will maximize your primary combus­tion air.
4. Build a fire directly on the firebrick covering the bot­tom of the stove.
a. Place five or six loosely crumpled sheets of
newspaper in the stove.
b. Add a small amount of dry kindling randomly on
the top of the newspaper.
c. Place a few more loosely crumpled newspapers
on top of the kindling and light the bottom paper first, then light the top paper. Once the kindling is ignited and burning on its own, close the fuel door. The upper fire should help preheat the chimney and create an effective draft while the lower fire ignites the kindling.
5. When the kindling is burning well, add increasingly
larger pieces of wood until the fire is actively burn­ing.
6. When the fire is well established, use the damper
hook and close the bypass by pushing the control rod in (catalytic temperature probe should read 600°F, takes approximately 20 - 25 minutes to reach this temperature).
7. When the fire is well-established slide the air control
lever for the desired heat output.
PAGE 16
CARE AND OPERATION FUEL
REFUELING
To refuel the stove, open the bypass damper and move the primary air control to "HIGH." Let the fire "LIVEN UP" for about one minute. Open the fuel door about ½” (1 cm) and hold in this position about 30 seconds or until the stove is drafting well. Open the door and add wood. After refueling, reset the primary draft control to the desired po­sition, and close the bypass when the catalytic tempera­ture probe reaches operating temperatures of 600° F indi­cated on the temperature probe.
BYPASS DAMPER CONTROL
The operating handle of your bypass damper control is located on the front of the stove flue collar. By moving the bypass damper control, the operator can route the fire either through the catalytic combustor (pushed in) or directly up the flue (pulled out). When starting a fire or refueling, the bypass damper control must be pulled out. Once the fire is established, it must be pushed in.
Secondary Air Tube
Bypass Damper Control
Tunnel Baffle
Positioning Stops
Damper Door
Catalytic Combustor
Catalyic Combustor Retainer Clip
CATALYTIC TEMPERATURE PROBE
The catalytic temperature probe monitors the tempera­ture of your catalytic combustor. Once you have estab­lished a fire and the catalytic temperature probe indi­cates the temperature of your catalytic combustor. When it reaches a temperature of 600 degrees (approximately 20 - 25 minutes), close the bypass damper control. De­pending on the type and size of the fuel load as well as the length of time the stove has been burning, your cata­lytic combustor should operate –between 1000 to 1800 degrees.
When the optional blower is operating it will affect the temperature probe reading. Turn the blower off for an accurate reading.
BURN RECOMMENDED FUEL This appliance is approved for use with untreated natural dry wood only (see Important Warnings, page 2, #8). Burning materials other than natural wood will shorten the life of the catalytic combustor. Do not burn particle­board or pressed logs using bonding agents as they can produce conditions, which will deteriorate metal or dam­age the catalyst. Green or uncured wood does not work well as fuel, and can cause increased creosote buildups and plugging of the catalytic combustor. The value of green wood as a source of heat is limited. Do not over­load or use kindling wood or mill ends for primary fuel as this may cause overfiring. Overfiring is a condition where excessive temperatures are reached, beyond the design capabilities of the stove. The damage that occurs from overfiring is not covered under the stove warranty.
WARNING: BURNING IMPROPER FUEL (I.E. CHAR­COAL) CAN RESULT IN CARBON MONOXIDE POISON­ING WHICH MAY LEAD TO DEATH!
CARBON MONOXIDE POISONING – EARLY SIGNS OF CARBON MONOXIDE POISONING RESEMBLE THE FLU WITH HEADACHES, DIZZINESS, OR NAU­SEA. IF YOU HAVE THESE SIGNS, GET FRESH AIR AT ONCE! HAVE THE HEATER INSPECTED BY A QUALIFIED SERVICE TECHNICIAN. SOME PEOPLE ARE MORE AFFECTED BY CARBON MONOXIDE THAN OTHERS. THESE INCLUDE PREGNANT WOMEN, PEOPLE WITH HEART OR LUNG DISEASE OR ANEMIA, THOSE UNDER THE INFLUENCE OF
ALCOHOL, AND THOSE AT HIGH ALTITUDES.
WHY SEASONED WOOD?
The key to the success of a good fire that produces heat from a woodstove is the wood. It needs to be well­seasoned natural wood.
What does “Well-Seasoned” mean? When a tree is cut down, the wood is green, full of sap and moisture. This moisture content can exceed 80%, which must be re­duced to less than 20%. Wood properly seasoned is then capable of generating the heat the stove was designed to provide.
Green wood does not burn easily. Attempting to burn green wood often results in a lot of smoke and very little fire. Time is the most important factor in seasoning wood. Ideally the moisture content should be reduced to 11-20%, although very few of us will be able to check that figure. There are several steps that should be taken to ensure that that you come close to these figures.
PAGE 17
FUEL MAINTENANCE
SEASONING GUIDE
Softwoods – 6 months to 18 months Hardwoods – 12 months to 24 months
Logs that are 5” (127 mm) diameter across or larger should be split in half, three pieces if over 8” (203 mm), and four pieces when over a foot (305 mm) across. If the tree was fell 2 to 4 years ago, it still needs to be cut, split, and seasoned for 6 to 24 months depending on the wood.
WOOD STORAGE
Wood to be seasoned should be stacked in an area open enough to ensure good air circulation on both sides – leaving adequate space between woodpiles to walk comfortable. Do not stack wood against a wall or building. It helps to elevate the woodpiles off the ground (two 2 x 4’s running lengthwise beneath the woodpile works well). This allows air to flow under the bottom logs. Wood that is kept outdoors, either covered with a tarp, or not covered at all, will not burn well until it has been in an enclose space for one to two months.
MAINTENANCE
FIREBRICK
The firebrick should be inspected periodically and re­placed if damaged (crumbling or excessively cracked).
SMALL AREA PAINT TOUCH-UP
The stove body is painted with a quality high­temperature stove paint. Use only model TSPK-B Stove Paint, Catalog # 70K99. Do not touch-up your stove with any other paint.
Using one small piece of 320 grit sand paper and lightly sand the blemish so that the edges are “feathered” or smooth to the touch between the painted and bare sur­faces. Do not let the sand paper gum up with paint, as this will cause scratches on the metal surface. If there are any scratches, use 600 grit sandpaper instead. Mask off surfaces you do not want painted. Paint lightly over the bare surface first as this will act as an under­coat. Then paint over a larger area in smooth even strokes to blend.
See Break-In Period on page 16 for information on curing the paint.
CLEANING BLOWER INTAKE
If an optional blower kit (catalog #14M22) is installed, the blower air intake requires cleaning at least once a year to remove lint, dust, etc. If there are pets in the dwelling, the intake should be cleaned at least twice a year.
ASH REMOVAL AND DISPOSAL
CAUTION: MAKE SURE THAT THE FIRE IS OUT AND THE STOVE IS COLD BEFORE REMOVING ASHES! NEVER BURN YOUR STOVE WITH THE ASH DRAWER OPEN OR UNSECURED!
Ash
Drawer
Ashes can hold live embers for several days, and must be disposed of with care.
Scrape ashes from the firebox through the grate into the ash drawer. After emptying, clean and replace the ash drawer and tighten the securing knobs.
NEVER place ashes in a cardboard box or any other combustible receptacle.
Proper Disposal of Ashes:
Ashes should be placed in a metal container with a tight fitting lid. The closed container of ashes should be placed on a noncombustible floor or on the ground, well away from all combustible materials, pending final dis­posal. If the ashes are disposed of by burial in soil or other wise locally dispersed, they should be retained in the closed container until all cinders have thoroughly cooled.
PAGE 18
MAINTENANCE
DOOR / GLASS GASKET AND ASH DRAWER GAS­KET
A 3/4" (19 mm) spun fiberglass gasket provides the seal around the fuel door and a 1/8” (3.2 mm) x 1” (25.4 mm) flat woven gasket glass provides the seal around the glass. A ½” (13 mm) flat fiberglass gasket provides the seal around the ash drawer. Should these gaskets be­come frayed or damaged, they should be replaced with the same size and type as the original gasket. Contact your dealer for ordering. Use high temperature silicone sealer as an adhesive for the fuel door gasket. The glass and ash drawer gaskets have self-adhesive back­ing.
WARNING: THE GASKETS MUST BE KEPT IN GOOD CONDITION. DO NOT LEAVE THE STOVE BURNING WITH THE DOOR OR ASH DRAWER OPEN OR AJAR. THIS WILL CAUSE EXCESSIVE HEAT BUILD UP IN THE UNIT AND COULD IGNITE SURROUNDING COMBUSTI­BLES AS WELL AS DAMAGE THE STOVE BY OVERFIR­ING IT. OVERFIRING IS A CONDITION WHERE EXCES­SIVE TEMPERATURES ARE REACHED, BEYOND THE DESIGN CAPABILITIES OF THE STOVE (SUCH DAMAGE IS NOT COVERED BY THE MANUFACTURER'S WAR­RANTY).
SERVICING GLASS
CAUTION: BE CAREFUL NOT TO ABUSE THE DOOR ASSEMBLY BY STRIKING OR SLAMMING IT. IF THE DOOR ASSEMBLY OR GLASS IS BROKEN OR DAM­AGED, THEY MUST BE REPLACED BEFORE HEATER CAN BE SAFELY OPERATED. USE ONLY COMPO­NENTS PROVIDED BY THE MANUFACTURER AS REPLACEMENT PARTS.
Cleaning Glass: Ensure stove is cold prior to cleaning glass.
A commercial glass cleaner designed for stoves is recom­mended. Do not use abrasive cleaners.
Replacing Glass:
1. Remove door from stove by lifting door up and off hinge pins: Place the door on a flat protected (towel) clean flat surface with the inside of the door facing up. Remove the glass clips (by removing screws holding clips), then carefully remove broken glass one piece at a time (protective gloves are recommended).
2. Clean area where the glass with gasket will be in­stalled.
3. Install new glass with gasket (use only factory 5 mm glass with glass channel gasket. Do not substitute). Carefully reinstall glass clips. Be very careful not to overtighten screws.
4. Reinstall door.
CREOSOTE FORMATION AND NEED FOR REMOVAL What is Creosote - When wood is burned slowly, it pro-
duces tar and other organic vapors, which combine with expelled moisture to form creosote. The creosote vapors condense in the relatively cool chimney flue of a slow­burning fire. As a result, creosote residue accumulates on the flue lining. When ignited this creosote makes an ex­tremely hot fire. Also, creosote deposits tend to form in long runs of venting where gases become too cool prior to exhausting. Note: Single wall pipe cools rapidly, there­fore installations using this type of flue are more suscepti­ble to creosote deposits.
To inhibit the build up of creosote, adjust the primary air control to a medium-high or high setting for a 10-minute period each day. Do not attempt to burn out heavy creo­sote accumulations in this manner. This must be re­moved from the chimney by scraping or brushing to re­duce the risk of a chimney fire.
Burn Approved Fuel Only - This stove is approved for burning dry seasoned natural wood only. Using green or inadequately seasoned wood may increase creosote buildup.
Inspection Frequency - The chimney connector and chimney should be inspected at least twice monthly during the heating season to determine if a creosote buildup has occurred. If creosote has accumulated it should be removed to reduce the risk of a chimney fire.
Cleaning - Remove the catalytic combustor and open the bypass damper prior to having your chimney cleaned (should be done by a qualified chimney sweep). See Maintenance Section, Catalytic Combus- tor, page 20 for instructions on removing catalytic com­bustor.
IMPORTANT: Make sure the bypass damper is in the open position prior to chimney cleaning.
In the event of a chimney fire - Make sure the fuel door
is securely closed. Adjust the primary air control to the lowest (most closed) setting. Call the fire department im­mediately. After a chimney fire, the complete chimney system should be checked by a qualified technician be­fore further use.
Consult your dealer for suggestions on proper chimney care. Contact your local municipal or provincial fire author­ity for information on how to handle a chimney fire. Have a clearly understood plan for handling a chimney fire.
PAGE 19
MAINTENANCE
CATALYST REPLACEMENT
The normal expected life of a catalyst (catalytic com­bustor) is 10,000 to 12,000 hours if the appliance is op­erated correctly and proper fuels are used. If the cata­lyst has been deactivated, it should be replaced. Symp­toms of deactivation include – noticeably darker smoke exiting chimney and less heat output. If these symp­toms remain after normal maintenance or a major cleaning (see Catalytic Combustor on this page for cleaning instructions), the catalyst, p/n 14000 will re­quire replacement. Also, if the catalyst is broken and / or missing large pieces, it should be replaced.
Note: The catalyst does not need to be glowing to be working. It will glow at times, but it can work very effec­tively at temperatures well below the 1000° F level (at which it will begin to glow).
Stove Operation if Catalyst Is Deactivated
to operate the appliance temporarily with a deactivated catalyst (although it will be out of compliance with EPA certification requirements). To operate, follow normal lighting and refueling procedures as outlined in this manual with one of the following exceptions.
During start-up, disregard catalytic temperature
probe reading to determine when to close bypass damper control. Instead allow 20-25 minutes, then close the bypass damper control.
During refueling, disregard catalytic temperature
probe reading to determine when to close bypass damper control. Instead allow 3-5 minutes after re­fueling, then close the bypass damper control.
CATALYTIC COMBUSTOR This appliance has been designed with a catalytic com­bustor, which will improve its overall performance. Re­moving the combustor assembly for cleaning and rein­stallation is simple and convenient. Cleaning the com­bustor helps reduce buildup of ash and retarding chemi­cals. To clean the combustor, a soft brush, vacuum cleaner, or pipe cleaner may be used.
Cleaning the combustor once a year, preferably when your flue system is serviced, is sufficient for most users. Reinstall the combustor according to the following in­structions.
The catalytic activity and effectiveness of a two to three year old combustor can be improved by following this Major Cleaning Procedure - Soak the combustor in a hot cleaning solution of a 50/50 mixture of white vinegar and distilled water for 30 minutes. Then rinse by soak­ing in hot distilled water. After 15 minutes, remove the combustor from the rinse water and gently shake out excess water. It is unlikely that you will notice a visible difference in the combustor after this cleaning proce-
– It is safe
dure. The combustor unit is fragile in comparison to the rest of the stove, so handle with care.
1. Place the combustor on the tunnel baffle as shown in illustration (ceramic honeycomb to the back and louvered slots to the front). Push it back into the tun­nel baffle until it hits the positioning stops. Make sure it is sitting flat against the bottom and the sides so that it does not tilt forward and jump the positioning stops.
2. Position combustor clip over the middle of the sec­ondary air tube as illustrated. Make sure that one of the holes in the secondary air tube is centered in the ½” (13 mm) hole on the clip. You can feel with your fingertip.
3. Tighten screw snugly, but do not over-tighten or you may spread the clip apart.
Side Cut-Away View of Firebox
Positioning Stops
Tunnel Baffle
Catalytic Combustor
Damper Door
Use 7/16” Socket. Tighten Snug (Do Not Overtighten)
Retainer Clip
Secondary Air Tube
Catalytic Combustor Retainer Clip
Secondary Air Tube
Setscrew
PAGE 20
TROUBLESHOOTING
SMOKES OUT FUEL DOOR WHEN OPEN (see ✸)
1. The primary air control is closed.
2. The chimney is too cool. Set the primary air control on "HIGH" with the bypass damper control "OPEN" for a few minutes before opening the fuel door.
3. Excess creosote will not only restrict your draft but it will create a risk of a creosote fire. Strictly adhere to maintenance requirements as outlined in this man­ual. If excess creosote has built up on the inside of the firebox sides and door, burn a small hot fire at in­tervals that are more frequent with air control on HIGH for a few minutes.
4. Deposits may have built up in the chimney and are restricting the draft, or the spark arrester on top of the chimney may be plugged.
5. Chimney diameter too large or too small to provide adequate draft.
6. The house is too airtight (usually takes 20 to 30 min­utes for problem to appear as stove lowers air pres­sure in house). Crack a window open or provide an outside source of air near stove.
7. Insufficient vertical height to chimney to achieve adequate draft.
8. The combustor is plugged from engaging too soon (remove combustor and clean, see Maintenance section, page 20).
DOES NOT PRODUCE ENOUGH HEAT (✸)
1. Using green or insufficiently cured wood.
2. Excessive draft.
3. High ceilings (heat rises quickly, but can be recircu­lated by a well-placed ceiling fan with a win­ter/summer switch).
4. The area to heat, is too large (square foot heating estimates are based on "average" climates and home design).
5. There's an obstruction in the chimney.
6. The chimney or chimney cap is restricted by creo­sote preventing enough draw to sustain a "HIGH" heat rate.
7. Combustor light off has not occurred.
DOES NOT MAINTAIN A FIRE ()
1. Soft wood does not burn as long or as well as sea­soned hardwood resulting in a short burn time.
2. Wood size too small. Burns at too rapid a rate.
3. The gasket seal on the fuel door, ash drawer or glass is leaking air. Repair or replace it if necessary.
4. There is an obstruction in the chimney.
5. The stove was not up to normal operating tempera­ture before the bypass damper control was pushed closed.
6. Excessive draft.
BACKPUFFING (✸)
1. Downdraft in the chimney (may need a special
wind cap).
2. The catalytic combustor is too hot (avoid burn-
ing soft, pitchy woods, or large amounts of small­diameter wood).
3 The house is too air tight (ventilation is needed).
4. Insufficient vertical height to chimney to achieve
adequate draft.
ODORS
1. Creosote accumulation in firebox (brush out on
next cleaning).
2. Chimney downdraft when stove is not operating
(close primary air control).
3. Catalytic combustor not functioning.
4. Paint curing on first several burns.
DIRTY GLASS (✸)
1. Poor draft conditions.
2. Long burn periods at low draft settings.
3. Burning wet, pitchy or spongy wood.
4. Poorly arranged logs (too close to glass).
() DRAFT PROBLEMS: IF INSTALLING INTO A
LARGER FLUE, IT MAY BE NECESSARY TO USE A FULL LENGTH LINER TO ACHIEVE ADE­QUATE DRAFT FOR THE APPLIANCE. A DRAFT GAUGE SHOULD READ A MINIMUM OF .05" W.C. (INCHES WATER COLUMN) NOT TO EX­CEED .07" W.C. FOR OPTIMUM PERFORMANCE (See Draft Requirements, page 11).
PAGE 21
TROUBLESHOOTING
CATALYST PLUGGING
1. Burning materials that produce a lot of char and fly ash. Do not burn materials such as garbage, gift wrap, cardboard, etc.
2. Burning wet pitchy woods or burning large loads of small diameter wood with the combustor in the op­eration position (without light-off taking place). Burn proper fuel only. Do not close bypass until tempera­tures are high enough to initiate light off.
CATALYST DEACTIVATION
1. Burning large quantities of trash, pressure-treated lumber or painted woods, etc. will deactivate the catalyst. Burn proper fuels only. See Catalyst Re- placement, page 20.
CATALYST SUBSTRATE CRACKING
1. Normal operation, as long as combustor remains intact. If cracking causes large pieces to fall out, re­place combustor.
2. Mishandling or abuse. Handle with care.
3. Excessive draft. Correct installation. See Draft Re-
quirements, page 11.
CATALYST SUBSTRATE
1. Extreme thermal shock. Combustor is being worked too hard.
2. Excessive draft. Correct installation. See Draft Re-
quirements, page 11.
CATALYST PEELING
Extreme Temperatures (over-firing) at combustor sur­face can cause the catalyst to peel. Some minor peeling does not affect function. Severe peeling would close cell openings and cause a plugging problem. If peeling is severe, replace combustor. Do not overfire appliance. See Overfiring, on page 23.
TAR AND LIQUID CREOSOTE LEAKING FROM METAL FLUE JOINTS
1. No chimney cap on chimney. Install cap.
2. Metal flue assembled improperly. Top flue sections should be inserted into lower flue sections.
DENSE SMOKE LEAVING CHIMNEY
1. Water vapor (on cold still days water vapor may be mistaken for smoke). Water vapor is normal and should be of little concern.
2. Wet, pitchy woods being burned. Burn dry sea­soned wood only.
3. Bypass in open position. Close bypass.
4. Combustor not functioning. See Catalyst Replace- ment, page 20.
NOISY HEAT SHIELD (OIL CANNING)
Rear or side heat shields make a noise (bong) during heat up or cool down.
Large pieces of metal such as a side or rear heat shield on a stove will normally expand and retract as it heats and cools. If a noise develops in these shields (i.e. as component heats and expands, it may flex, resulting in a “bong” sound) it can be corrected. See following pro­cedures:
There is an adjustable tension bolt rear heat shield. To eliminate the expansion noise during stove use, adjust the bolt and nut to increase tension on the shield.
Tension Bolt
in the center of the
PAGE 22
TROUBLESHOOTING
OVERFIRING DAMAGE
If the heater or chimney connector glows, the appli­ance is overfiring. Other symptoms may include: Cracking, warping or burning out of components, cata­lytic combustor may deteriorate, gold doors may turn color, stove glass may develop a haze which will not come off with cleaning, firebox baffle plate (tunnel baf­fle) may warp, etc. Overfiring of a stove is a condition where excessive temperatures are reached, beyond the design capabilities of the appliance. The damage that occurs from overfiring is not covered under the manufacturers limited warranty. The following are a few conditions that should be evaluated and (cor­rected if necessary) if an overfiring condition is sus­pected:
Overfiring Caused From Improper Installation
The venting system must satisfy the draft Require­ments of the appliance. The appliance is merely one component of a larger system. The other equally im­portant component is the venting system, which is necessary for achieving the required flow of combus­tion air to the fire chamber and for safely removing unwanted combustion byproducts from the appliance. If the venting system’s design does not promote these ends, the system may not function properly, which may create performance problems as well as may be a safety hazard. To ensure that all installation re­quirements have been met as outlined in the installa­tion manual. The chimney should be clean and in good repair. A draft test should be performed to de­termine if the draft requirements of the appliance are being met. A draft gauge should read between .05 and .07 inches water column (W.C.I.).
Excessive draft (above .07 W.C.I.) will allow too much combustion air to be pulled into the firebox, which re­sults in hotter burns. Too little draft (below .05 W.C.I.) will not allow enough combustion air delivery to main­tain a fire well or cause performance problems such as smoking (this may result in improper operation of appliance, i.e. will not maintain fire well unless cata­lytic bypass is left open, or with fuel door left open (see below - Overfiring Caused From Improper Opera-
tion).
Overfiring Caused From Improper Operation
Never burn the appliance with the fuel door open or ajar, or the ash drawer open. Never burn the stove with the bypass handle in the open position once the fire has been established or the air control in the "high" position for extended periods.
Overfiring Caused From Improper Maintenance
Should the fuel door, glass or ash drawer gaskets be­come worn or damaged, they should be replaced.
Overfiring Caused From Improper Fuel
This appliance is approved for use with natural dry well seasoned wood only (consult your dealer for ap­proved fuels in your area). Do not burn garbage, par­ticleboard scraps, or pressed logs using bonding agents because they can produce conditions that will deteriorate metal. Green or uncured wood does not work well as fuel, and can cause increased creosote buildups. Do not overload or use kindling wood or mill ends as primary fuel.
PAGE 23
SPECIFICATIONS: Model 1003C
Maximum Log Length 18” (458 mm)
Manufactured (Mobile) Home Approved Yes, U.S.A. and Canada
Outside Air Provision Yes
Flue Collar Size 6” (153 mm)
Flue Position Top
Stove Back to Flue Center 9” (229 mm)
Width 25.25” (642 mm)
Depth 27” (686 mm)
Height (to flue) 34.5” (877 mm)
Height 32.5” (826 mm)
Approx. Burn Time 8 - 12 hours
Fuel Capacity 50 – 70 lbs. (23 – 32 kg)
Fire Box Size 3 cubic feet (914 cubic millimeters)
Loading Front
Catalyst Standard
Maximum Burn Rate 51,100 BTU
EPA BTU Range 11,700 - 36,800 BTU
EPA Efficiency 72 %
Emissions Rate (gram/hour) 3.7 gph
Approx. Weight With Brick 360 lbs. (168 kg)
Blower (Optional) 160 CFM, .9 amp, W/ speed control Rheostat (75v - 110v)
Note: Dimensions shown are approximations
only (+/- ¼” - 6.4 mm).
Side View
Front View
Door Sold Seperately
PAGE 24
REPLACEMENT PARTS LIST: Model 1003C
ITEM NO DESCRIPTION
Door Parts
27M65 Clip Kit, Glass
G6000 Door Assembly, Black, H0533 (handle included)
14M72 Door Assembly, Gold, G3000 (handle included)
86-128 Gasket Kit, Door (3/4" rope, includes adhesive)
27M81 Gasket Kit, Glass (10' of 10580. self adhesive backing)
G2000-7 Glass, Small Arched, 9 3/8 x 15 3/4" (gasket not included)
10300 Handle Assembly, Door
11531 Hinge Pin, Retrofit (2 if set is needed)
10362 Torque Plate (latch)
Draft Module Parts
907 Handle, Spring Module (00907)
26M29 Module Assembly, Draft (11658)
Catalytic Combustor Parts
11000 Clip, Combustor (bracket w/ setscrew)
CLIP-2 Clip, Combustor (stair step clip)
14000 Combustor Assembly, 3" - Includes ceramics, gasket & housing
11481H Gasket, Interam Combustor (1/16 x 3 x 36") - 11481
C-200-51 Hook, Damper (coil handle with hook for opening / closing damper bypass)
11485 Housing, Combustor (also requires 1 each P/N 11481H)
H0310 Probe, Combustor Temperature (Z-SC-107)
Room Air Blower Parts (if optional blower is installed)
14M22 Blower Kit (includes Dial-A-Temp) - 820
14440 Rheostat, Dial-A-Temp
14M21 Stove Stat Kit (automates fan) - 18840
Miscellaneous Parts
1100 Ash Drawer Assembly (01100)
14M67 Duct, Floor, 5 1/4" Square, 78-35 (for pedestal based models)
27M80H Gasket Kit, Ash Drawer, 3/8" x 1/8" (16' of 01098)
1135 Knob, Ash Drawer (01135)
70K99 Paint, Metallic Black, 12 oz Spray Can, 76-141MB (#6309)
Firebox Parts
26M27 Damper Kit (includes damper, linkage and rod)
FB14 Firebrick, 6 3/4 x 3 x 2 3/8” Left (requires 1)
FB15 Firebrick, 6 3/4 x 3 x 2 3/8” Right (requires 1)
FB12 Firebrick, 7 3/8 x 4 ½ x 6 ¾” Left (requires 1)
FB13 Firebrick, 7 3/8 x 4 ½ x 6 ¾” Right (requires 1)
FB-1 Firebrick, 9 x 4 ½” Regular (order 5, if set is needed)
FB-2 Firebrick, 9 x 4 ½” w/Notch (order 8, if set is needed)
1115 Grate, Cast Iron (SN>3200 approx.) - 01115
PAGE 25
REPLACEMENT PARTS LIST: Model 1003C
Cat. No. Model Description
/ Part No. Firebrick - All firebrick are 1 ¼” thick (see firebrick diagram below)
FB-1 Firebrick, 9 x 4 ½” Regular (order 5, if set is needed)
FB-2 Firebrick, 9 x 4 ½” W/Notch (order 8, if set is needed)
FB12 Firebrick, 7 3/8 x 4 ½ x 6 ¾” Left (requires 1)
FB13 Firebrick, 7 3/8 x 4 ½ x 6 ¾” Right (requires 1)
FB14 Firebrick, 6 3/4 x 3 x 2 3/8” Left (requires 1)
FB15 Firebrick, 6 3/4 x 3 x 2 3/8” Right (requires 1)
1115 Grate, Cast Iron
Firebrick
Left
Right
For the location of the nearest Dealer for replacement parts, contact: Lennox Hearth Products 1110 West Taft Avenue Orange, CA 92865
Bottom
Back
PAGE 26
COMPONENT DIAGRAMS - Model 1003C
Catalytic Combustor System Components
Secondary Air Tube
Bypass Damper Control
Tunnel Baffle
Positioning Stops
Damper Door
Catalytic Combustor
Catalyic Combustor Retainer Clip
Air Intake Draft Module
Door Assembly
Damper Assembly
Setscrews
Bypass Damper Control Rod
Damper Blade Assembly (Linkage)
Damper Door
Handle Assembly (P/N LB-102214)
Nut
Torque Plate
Handle Rod
Washers
Coil Handle
PAGE 27
OPTIONAL ACCESSORIES - Model 1003C Note: Install and use accessories per instructions provided with the accessory kit.
Catalog # Model Description
14M67 OAFD-S Outside Air Floor Duct
* 14M72 DK100-G Gold Door Kit
* H0533 DK100-B Black Door Kit
14M22 BK-100 Blower Kit
14M21 SSK Stove Stat Kit
70K99 TSPK-B Touch-up Spray Paint Kit, Black (12 oz
spray can)
Stove-Stat Kit (SSK)
To automate the blower system an additional Stove-Stat kit can be purchased. The Stove-Stat is a heat sensor switch that will automatically turn on the blower when the stove is hot and automatically turn it off when the stove is cool.
Stove-Stat Magnetic Head
Outside Air Floor Duct
Outside air can be delivered for combustion air by utilizing this floor penetration duct.
(Duct penetration measures 5 ¼” square)
Blower Kit (BK-100)
A Blower Kit (includes rheostat for variable speed control) is available for increased heat circulation.
Stove Rear Heat Shield
(OAFD-S)
Stove
Floor Protector
Floor Duct
Blower Assembly
Blower Power Cord Plug
Stove-Stat Power Cord Plug
Grounded 110 Volt Wall Receptacle
160 CFM Blower Assembly
2 Screws 10-24 x 1/2
Variable Speed Control, Dial-A-Temp
Plug Dial-A-Temp into Wall Outlet
Plug Power Cord into Bottom of Dial-A-Temp
PAGE 28
SAFETY/LISTING LABEL
PAGE 29
EPA LABEL
PAGE 30
OWNERSHIP RECORDS
Dealer’s Name:
Dealer’s Address:
City: State: Zip Code:
Serial Number: Date of Purchase: Date Installed:
Notes:
SERVICE AND MAINTENANCE LOG
Service Service Service Date Technician Description
Page 31
1110 West Taft Avenue
Orange, CA 92865
Loading...