Lennox 070V36B, 090V60C, 110V60C, 090V36C User Manual

INSTALLATION
2011 Lennox Industries Inc.
Dallas, Texas, USA
AIR FLOW
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, person­al injury or loss of life. Installation and service must be performed by a licensed professional installer (or equivalent), service agency or the gas supplier.
INSTRUCTIONS SLP98DFV
DAVE LENNOX SIGNATURE COLLECTION GAS FURNACE DOWNFLOW AIR DISCHARGE
506611−01 02/2011 Supersedes 10/2010
THIS MANUAL MUST BE LEFT WITH THE
HOMEOWNER FOR FUTURE REFERENCE
This is a safety alert symbol and should never be ignored. When you see this symbol on labels or in manuals, be alert to the potential for personal injury or death.
CAUTION
As with any mechanical equipment, personal injury can result from contact with sharp sheet metal edges. Be careful when you handle this equipment.
A thermostat is not included and must be ordered separately.
The Lennox icomfort Touch thermostat must be
used in communicating applications.
In non−communicating applications, the Lennox
ComfortSense® 7000 thermostat may be used, as well as other non−communicating thermostats.
In all cases, setup is critical to ensure proper sys­tem operation.
Field wiring for both communicating and non−com­municating applications is illustrated in diagrams, which begin on Page 30.
®
Litho U.S.A.
NOTICE
Table of Contents
Unit Dimensions 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parts Arrangement 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SLP98DFV Gas Furnace 4. . . . . . . . . . . . . . . . . . . . . . . . .
Shipping and Packing List 4. . . . . . . . . . . . . . . . . . . . . . . .
Safety Information 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Use of Furnace as a Construction Heater 5. . . . . . . . . . .
General 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setting Equipment 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Filters 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Duct System 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pipe and Fittings Specifications 10. . . . . . . . . . . . . . . . . . .
Joint Cementing Procedure 11. . . . . . . . . . . . . . . . . . . . . .
Venting Practices 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Vent Piping Guidelines 12. . . . . . . . . . . . . . . . . . . . . . . . . .
Gas Piping 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
02/11
*2P0211*
Page 1
Electrical 27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Integrated Control 36. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Blower Motor Performance 40. . . . . . . . . . . . . . . . . . . . . . .
Unit Start Up 45. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Gas Pressure Measurement 46. . . . . . . . . . . . . . . . . . . . .
High Altitude Information 46. . . . . . . . . . . . . . . . . . . . . . . .
Proper Combustions 47. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Other Unit Adjustments 46. . . . . . . . . . . . . . . . . . . . . . . . . .
Heating Sequence of Operation 48. . . . . . . . . . . . . . . . . .
Service 50. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Planned Service 52. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Integrated Control Diagnostic Codes 53. . . . . . . . . . . . . .
Configuring Unit Size Codes 56. . . . . . . . . . . . . . . . . . . . .
Troubleshooting 57. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Repair Parts List 63. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
506611−01
*P506611-01*
Unit Dimensions − inches (mm)
COMBUSTION
AIR INTAKE
EXHAUST AIR
OUTLET
21/16 (52)
5
(127)
21/4
(57)
9/16
(14)
RETURN AIR
OPENING
B
9/16 (14)
TOP VIEW
3/4
(19)
AIR
C
A
B
FLOW
Supply
Air
9/16 (14)
3/4
(19)
33
(838)
11/2 (38)
Front Panel
2 (51)
Either Side
GAS PIPING INLET
(Either Side)
91/8 (232) Right 69/16 (167) Left
273/4 (7705)
197/16
(494)
ELECTRICAL INLET
(Either Side)
CONDENSATE
TRAP CONNECTION
(Either Side)
67/16 (163)
Either Side
191/4
(489)
9 (229) Right
Either Side
Supply
Air
9/16 (14)
3/4
(19)
FRONT VIEW SIDE VIEW
SLP98DF Model No.
070V36B 171/2 446 163/8 416 16 406 75/8 194
090V36C 090V48C 090V60C 110V60C
A B C D
in. mm in. mm in. mm in. mm
21 533 197/8 505 191/2 495 93/8 238
Page 2
Parts Arrangement
CONTROL BOX
(includes variable capacity
integrated control,
transformer, circuit breaker
and door switch)
BLOWER ASSEMBLY
(Variable Speed Blower
Motor Is Hidden)
BLOWER
ACCESS
PANEL
BAG ASSEMBLY
ACCESS PANEL
COMBUSTION AIR INDUCER
GAS VALVE
PRIMARY LIMIT
BURNER BOX ASSEMBLY
FIGURE 1
Page 3
SLP98DFV Gas Furnace
Safety Information
The SLP98DFV category IV gas furnace is equipped with a variable−capacity, variable−speed integrated control. This control ensures compatibility with the Lennox icom­fort Touch thermostat and Harmony III zone control system, as well as a thermostat which provides humidity control.
The furnace is equipped for installation in natural gas ap­plications only. A changeover kit may be ordered for LP applications.
The SLP98DFV must be installed only as a Direct Vent gas central furnace.
NOTE − In Direct Vent installations, combustion air is taken from outdoors and flue gases are discharged outdoors. See figure 2 for applications including roof termination.
DIRECT VENT INSTALLATION
COMBUSTION AIR INTAKE OUTSIDE OF HOUSE
SLP98DFV
EXHAUST OUTLET
FIGURE 2
Shipping and Packing List
Package 1 of 1 contains
1 − Assembled SLP98DFV unit
1 − Bag assembly containing the following:
3 − Wire nuts
1 − Snap bushing
1 − Snap plug
1 − Wire tie
1 − Condensate trap
Check equipment for shipping damage. If you find any damage, immediately contact the last carrier.
The following items may also be ordered separately:
1 − Thermostat
1 − Natural to LP gas conversion kit
1 − High altitude kit
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, person­al injury or loss of life. Installation and service must be performed by a licensed professional installer (or equivalent), service agency or the gas supplier.
CAUTION
As with any mechanical equipment, personal injury can result from contact with sharp sheet metal edges. Be careful when you handle this equipment.
Use only the type of gas approved for use with this furnace. Refer to unit nameplate.
Building Codes
In the USA, installation of gas furnaces must conform with lo­cal building codes. In the absence of local codes, units must be installed according to the current National Fuel Gas Code (ANSI-Z223.1/NFPA 54). The National Fuel Gas Code is available from the following address:
American National Standards Institute, Inc. 11 West 42nd Street New York, NY 10036
Installation Locations and Clearances
In Canada, installation must conform with current National Standard of Canada CSA-B149 Natural Gas and Propane Installation Codes, local plumbing or waste water codes and other applicable local codes.
This furnace is designed for installation clearances to com­bustible material as listed on the unit nameplate and in the table in figure 7. Accessibility and service clearances must take precedence over fire protection clearances.
For installation in a residential garage, the furnace must be installed so that the burner(s) and the ignition source are located no less than 18 inches (457 mm) above the floor. The furnace must be located or protected to avoid physical damage by vehicles. When a furnace is installed in a public garage, hangar, or other building that has a haz­ardous atmosphere, the furnace must be installed accord­ing to recommended good practice requirements and cur­rent National Fuel Gas Code or CSA B149 standard.
NOTE − Furnace must be adjusted to obtain a temperature rise (100% percent capacity) within the range(s) specified on the unit nameplate. Failure to do so may cause erratic limit operation and may also result in premature heat exchanger failure.
This SLP98DFV furnace must be installed so that its elec­trical components are protected from water.
Page 4
Installed in Combination with a Cooling Coil
When this furnace is used with cooling units, it shall be installed in parallel with, or on the upstream side of, cooling units to avoid condensation in the heating compartment. With a parallel flow arrangement, a damper (or other means to control the flow of air) must adequately prevent chilled air from entering the furnace (figure 3). If the damper is manual­ly operated, it must be equipped to prevent operation of ei­ther the heating or the cooling unit, unless it is in the full
HEAT or COOL setting.
SLP98DFV INSTALLED PARALLEL
WITH COOLING COIL
GAS UNIT
Dampers
(open during heating
operation only)
AIR HANDLER
Dampers
(open during cooling
operation only)
FIGURE 3
When installed, this furnace must be electrically grounded according to local codes. In addition, in the United States, installation must conform with the current National Electric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available from the following ad­dress:
National Fire Protection Association 1 Battery March Park Quincy, MA 02269
NOTE − This furnace is designed for a minimum continu­ous return air temperature of 60°F (16°C) or an intermit­tent operation down to 55°F (13°C) dry bulb for cases where a night setback thermostat is used. Return air tem­perature must not exceed 85°F (29°C) dry bulb.
In Canada, all electrical wiring and grounding for the unit must be installed according to the current regulations of the Canadian Electrical Code Part I (CSA Standard C22.1) and/or local codes.
CAUTION
Do not set thermostat below 60°F (16°C) in heating mode. Setting thermostat below 60°F (16°C) reduces the number of heating cycles. Damage to the unit may occur that is not covered by the warranty.
The SLP98DFV furnace may be installed in alcoves, clos­ets, attics, basements, garages, and utility rooms.
This furnace is not designed for installation in mobile homes, recreational vehicles, or outdoors.
Never use an open flame to test for gas leaks. Check all connections using a commercially available soap solution made specifically for leak detection.
Use of Furnace as Construction Heater
Lennox does not recommend the use of SLP98DFV units as a construction heater during any phase of construction. Very low return air temperatures, harmful vapors and op­eration of the unit with clogged or misplaced filters will dam­age the unit.
SLP98DFV units may be used for heating of buildings or structures under construction, if the following conditions are met:
D The vent system must be permanently installed per
these installation instructions.
D A room thermostat must control the furnace. The use of
fixed jumpers that will provide continuous heating is not allowed.
D The return air duct must be provided and sealed to the
furnace.
D Return air temperature range between 60°F (16°C) and
80°F (27°C) must be maintained.
D Air filters must be installed in the system and must be
maintained during construction.
D Air filters must be replaced upon construction comple-
tion.
D The input rate and temperature rise must be set per the
furnace rating plate.
D One hundred percent (100%) outdoor air must be pro-
vided for combustion air requirements during construc­tion. Temporary ducting may supply outdoor air to the furnace. Do not connect duct directly to the furnace.
D The furnace heat exchanger, components, duct system,
air filters and evaporator coils must be thoroughly cleaned following final construction clean−up.
D All furnace operating conditions (including ignition, in-
put rate, temperature rise and venting) must be verified according to these installation instructions.
Page 5
General
When the furnace is installed in an unconditioned space, consider provisions required to prevent freezing of condensate drain system.
WARNING
Product contains fiberglass wool.
Disturbing the insulation in this product during installation, maintenance, or repair will expose you to fiberglass wool. Breathing this may cause lung cancer. (Fiberglass wool is known to the State of Cal­ifornia to cause cancer.)
Fiberglass wool may also cause respiratory, skin, and eye irritation.
To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor.
Lennox Industries Inc. P.O. Box 799900 Dallas, TX 75379−9900
CAUTION
SLP98DFV unit should not be installed in areas nor­mally subject to freezing temperatures.
These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities having jurisdiction before installation.
In addition to the requirements outlined previously, the fol­lowing general recommendations must be considered when installing a SLP98DFV furnace:
Place the furnace as close to the center of the air dis­tribution system as possible. The furnace should also be located close to the chimney or vent termination point.
When the furnace is installed in an attic or other insu­lated space, keep insulation away from the furnace.
Installation − Setting Equipment
WARNING
Do not install the furnace on its front, back or in the horizontal position. See figure 5. Do not connect the return air ducts to the back of the furnace. Doing so will adversely affect the operation of the safety con­trol devices, which could result in personal injury or death.
Select a location that allows for the required clearances that are listed on the unit nameplate. Also consider gas supply connections, electrical supply, vent connection, condensate trap and drain connections, and installation and service clearances [24 inches (610 mm) at unit front]. The unit must be level from side to side. Unit may
be positioned from level to 1/2" toward the front to aid in draining. See figure 4.
SETTING EQUIPMENT
AIR FLOW
FRONT VIEW SIDE VIEW
Unit must be level side−to−side. Unit may be positioned
from level to 1/2" toward the front to aid in draining.
AIR FLOW
SIDE VIEW
FIGURE 4
AIR FLOW
1/2"
max.
Front
Horizontal
Back
NOTE − Do not install the furnace on its front, back or in the horizontal position.
FIGURE 5
Page 6
NOTE − The 1/2 hp blower motor used in some SLP98DFV unit is equipped with three flexible legs and one rigid leg. The rigid leg is equipped with a shipping bolt and a flat white plastic washer (rather than the rubber mounting grommet used with a flexible mounting leg). The bolt and washer
must be removed before the furnace is placed into op­eration. After the bolt and washer have been removed, the
rigid leg will not touch the blower housing.
SLP98DF070V36B and
SL98DF090V036C WITH 1/2 HP
BLOWER MOTOR
RIGID LEG
remove shipping bolt and washer
The unit may be installed three ways in downflow applica­tions: on non−combustible flooring, on combustible flooring using a base, or on a reverse−flow cooling coil cabinet. Do
not drag the unit across the floor in the downflow posi­tion. Floor and flange damage will result. Refer to figure 7 for clearances in downflow applica-
tions.
Downflow Application Installation Clearances
Top
Left Side Right Side
FIGURE 6
Allow for clearances to combustible materials as indicated on the unit nameplate. Minimum clearances for closet or al­cove installations are shown in figure 7.
WARNING
Blower access panel must be securely in place when blower and burners are operating. Gas fumes, which could contain carbon monoxide, can be drawn into living space resulting in personal injury or death.
WARNING
Improper installation of the furnace can result in per­sonal injury or death. Combustion and flue products must never be allowed to enter the return air system or air in the living space. Use sheet metal screws and joint tape to seal return air system to furnace. In platform installations with furnace return, the fur­nace should be sealed airtight to the return air ple­num. A door must never be used as a portion of the return air duct system. The base must provide a stable support and an airtight seal to the furnace. Al­low absolutely no sagging, cracks, gaps, etc. For no reason should return and supply air duct sys­tems ever be connected to or from other heating de­vices such as a fireplace or stove, etc. Fire, explo­sion, carbon monoxide poisoning, personal injury and/or property damage could result.
Bottom
Top 0
*Front 0
Back 0
Sides 0†
Vent 0
Floor NC
*Front clearance in alcove installation must be 24 in. (610 mm). Maintain a minimum of 24 in. (610 mm) for front service access. †Allow proper clearances to accommodate condensate trap and vent pipe installation. The furnace may be installed on a combustible wood floor if an op­tional base is installed between the furnace and the combustible floor.
FIGURE 7
Installation on Non−Combustible Flooring (Figure 8)
1 − Cut floor opening keeping in mind clearances listed on
unit rating plate. Also keep in mind gas supply connec­tions, electrical supply, flue and air intake connections and sufficient installation and servicing clearances. See table 1 for correct floor opening size.
2 − Flange warm air plenum and lower the plenum into the
opening.
3 − Set the unit over the plenum and seal the plenum to
the unit.
4 − Ensure that the seal is adequate.
Page 7
TABLE 1
NON−COMBUSTIBLE FLOOR OPENING SIZE
Cabinet Width
B Cabinet (17.5") 19 − 3/4 502 16 − 5/8 422
C Cabinet (21") 19 − 3/4 502 20−1/8 511
NOTE − Floor opening dimensions listed are 1/4 inch (6 mm) larger than the unit opening. See dimension drawing on page 2.
SLP98DF UNIT
Front to Rear Side to Side
in. mm in. mm
SLP98DF UNIT
PROPERLY
SIZED FLOOR
OPENING
SUPPLY AIR
PLENUM
COMBUSTIBLE FLOORING BASE
PROPERLY
SIZED FLOOR
OPENING
SUPPLY AIR
PLENUM
FIGURE 8
Installation on Combustible Flooring (Figure 9)
1 − When unit is installed on a combustible floor, a down-
flow combustible flooring base must be installed be­tween the furnace and the floor. The base must be or­dered separately. See table 2 for opening size to cut in floor.
CAUTION
The furnace and combustible flooring base shall not be installed directly on carpeting, tile, or other com­bustible material other than wood flooring.
TABLE 2
COMBUSTIBLE FLOORING BASE OPENING SIZE
Cabinet
Width
B Cabinet
(17.5")
C Cabinet
(21")
Catalog Number
11M60
11M61
Front to Rear Side to Side
in. mm in. mm
22 559 18 − 3/4 476
22 559 22 − 3/4 578
FIGURE 9
2 − After opening is cut, set combustible flooring base into
opening.
3 − Check fiberglass strips on combustible flooring base
to make sure they are properly glued and positioned.
4 − Lower supply air plenum into combustible flooring
base until plenum flanges seal against fiberglass strips.
NOTE − Be careful not to damage fiberglass strips. Check for a tight seal.
5 − Set the furnace over the plenum.
6 − Ensure that the seal between the furnace and plenum
is adequate.
Installation on Cooling Coil Cabinet (Figure 10)
NOTE − Downflow combustible flooring base is not used.
1 − Refer to reverse−flow coil installation instructions for
correctly sized opening in floor and installation of cabi­net.
2 − When cooling cabinet is in place, set and secure the
furnace according to the instructions that are provided with the cooling coil. Secure the furnace to the cabinet.
3 − Seal the cabinet and check for air leaks.
Page 8
PROPERLY
SIZED FLOOR
OPENING
FIGURE 10
SLP98DF UNIT
COOLING COIL
PLENUM
PLENUM
(Field Provided)
SECURE FROM
INSIDE CABINET
Side View
SEALING STRIP (Field Provided)
CABINET
SIDE PANEL
FIGURE 12
Filters
This unit is not equipped with a filter or rack. A field−pro­vided filter is required for the unit to operate properly. Table 3 lists recommended filter size. A filter must be in place whenever the unit is operating.
TABLE 3
Furnace
Cabinet Width
Filter Size
Return Air Opening −− Downflow Units
Return air may be brought in only through the top opening of a furnace installed in the downflow position. The follow­ing steps should be taken when installing plenum:
1 − Bottom edge of plenum should be flanged with a
hemmed edge (See figure 11 or 12).
2 − Sealing strips should be used to ensure an airtight seal
between the cabinet and the plenum.
3 − In all cases, plenum should be secured to top of fur-
nace using sheet metal screws.
4 − Make certain that an adequate seal is made.
PLENUM
(Field Provided)
SEALING STRIP (Field Provided)
SECURE FROM
OUTSIDE CABINET
CABINET
SIDE PANEL
Side View
FIGURE 11
B Cabinet (17−1/2")
C Cabinet (21−1/2")
16 X 25 X 1 (1)
Duct System
Use industry-approved standards to size and install the supply and return air duct system. This will result in a quiet and low-static system that has uniform air distribution.
NOTE − Operation of this furnace in heating mode (indoor blower operating at selected heating speed) with an exter­nal static pressure which exceeds 0.8 inches w.c. may re­sult in erratic limit operation.
Return Air Plenum Return air must not be drawn from a room where this
furnace, or any other gas−fueled appliance (i.e., water heater), or carbon monoxide−producing device (i.e., wood fireplace) is installed. When return air is drawn
from a room, a negative pressure is created in the room. If a gas appliance is operating in a room with negative pres­sure, the flue products can be pulled back down the vent pipe and into the room. This reverse flow of the flue gas may result in incomplete combustion and the formation of carbon monoxide gas. This toxic gas might then be dis­tributed throughout the house by the furnace duct sys­tem.
Use fiberglass sealing strips, caulking, or equivalent seal­ing method between the plenum and the furnace cabinet to ensure a tight seal. If a filter is installed, size the return air duct to fit the filter frame.
Page 9
Pipe & Fittings Specifications
All pipe, fittings, primer and solvent cement must conform with American National Standard Institute and the Ameri­can Society for Testing and Materials (ANSI/ASTM) stan­dards. The solvent shall be free−flowing and contain no lumps, undissolved particles or any foreign matter that ad­versely affects the joint strength or chemical resistance of the cement. The cement shall show no gelation, stratifica­tion, or separation that cannot be removed by stirring. Re­fer to table 4 for approved piping and fitting materials.
PIPING AND FITTINGS SPECIFICATIONS
Schedule 40 PVC (Pipe) D1785 Schedule 40 PVC (Cellular Core Pipe) F891
Schedule 40 PVC (Fittings) D2466
Schedule 40 CPVC (Pipe) F441
Schedule 40 CPVC (Fittings) F438
SDR−21 PVC or SDR−26 PVC (Pipe) D2241
SDR−21 CPVC or SDR−26 CPVC (Pipe) F442
Schedule 40 ABS Cellular Core DWV (Pipe) F628
Schedule 40 ABS (Pipe) D1527
Schedule 40 ABS (Fittings) D2468
ABS−DWV (Drain Waste & Vent) (Pipe & Fittings)
PVC−DWV (Drain Waste & Vent) Pipe & Fittings)
PRIMER & SOLVENT CEMENT
PVC & CPVC Primer F656 PVC Solvent Cement D2564
CPVC Solvent Cement F493
ABS Solvent Cement D2235
PVC/CPVC/ABS All Purpose Cement For Fittings & Pipe of the same material
ABS to PVC or CPVC Transition Solvent Cement
CANADIAN PIPE, FITTINGS &
SOLVENT CEMENT
PVC & CPVC Pipe and Fittings PVC & CPVC Solvent Cement
ABS to PVC or CPVC Transition Cement
TABLE 4
D2661
D2665
ASTM
SPECIFICATION
D2564, D2235, F493
D3138
MARKING
ULCS636
CAUTION
Solvent cements for plastic pipe are flammable liq­uids and should be kept away from all sources of ignition. Do not use excessive amounts of solvent cement when making joints. Good ventilation should be maintained to reduce fire hazard and to minimize breathing of solvent vapors. Avoid contact of cement with skin and eyes.
IMPORTANT
SLP98DFV exhaust and intake connections are made of PVC. Use PVC primer and solvent cement when using PVC vent pipe. When using ABS vent pipe, use transitional solvent cement to make con­nections to the PVC fittings in the unit.
Use PVC primer and solvent cement or ABS solvent cement meeting ASTM specifications, refer to Table 4. As an alter­nate, use all purpose cement, to bond ABS, PVC, or CPVC pipe when using fittings and pipe made of the same materi­als. Use transition solvent cement when bonding ABS to ei­ther PVC or CPVC.
Low temperature solvent cement is recommended. Metal or plastic strapping may be used for vent pipe hangers. Uni­formly apply a liberal coat of PVC primer for PVC
Canadian Applications Only − Pipe, fittings, primer and solvent cement used to vent (exhaust) this ap­pliance must be certified to ULC S636 and supplied by a single manufacturer as part of an approved vent (ex­haust) system. In addition, the first three feet of vent pipe from the furnace flue collar must be accessible for inspection.
Table 5 lists the available exhaust termination kits.
Page 10
SLP98DF
UNIT
OUTDOOR TERMINATION KITS USAGE
TABLE 5
STANDARD CONCENTRIC
Outdoor
VENT
PIPE
DIA.
(in.)
2 YES YES YES* YES YES YES
Exhaust
Accelerator
(Dia. X
Length)
1−1/2" X 12" 2" X 12"
Outdoor Exhaust
Accelerator
(Dia. X
Length)
2" Wall Plate
Kit
22G44
or 30G28
3" Wall Plate
Kit
44J40
or 81J20
2" Wall
Ring Kit
15F74 51W11**
Flush­Mount
Kit
Concentric
44W92
1−1/2"
Kit
71M80
or
2"
Concentric
Kit
69M29
or
44W92
3"
Concentric
Kit
60L46
or 44W93
070
090
110
*Requires field−provided and installed 1−1/2" exhaust accelerator. ** Kit 51W11 includes h a 1−1/2" accelerator which must be used for all SLP98DFV−070 and −090 installations.  Termination kits 44W92, 44W93, 30G28 and 81J20 approved for use in Canadian installations.  The 44W92 concentric kit includes a 1−1/2" accelerator which must be installed on the exhaust outlet when this kit is used with the SL98DF070V36B furnaces.
Joint Cementing Procedure
All cementing of joints should be done according to the specifications outlined in ASTM D 2855.
NOTE − A sheet metal screw may be used to secure the intake pipe to the connector, if desired. Use a drill or self tapping screw to make a pilot hole.
2−1/2 YES YES YES* YES YES YES
3 YES YES YES* YES YES YES
2 YES YES YES YES YES YES
2−1/2 YES YES YES YES YES YES
3 YES YES YES YES YES YES
2 YES YES YES YES YES YES
2−1/2 YES YES YES YES YES
3 YES YES YES YES YES
5 − Uniformly apply a liberal coat of PVC primer for PVC or
use a clean dry cloth for ABS to clean inside socket surface of fitting and male end of pipe to depth of fitting socket.
6 − Promptly apply solvent cement to end of pipe and in-
side socket surface of fitting. Cement should be ap­plied lightly but uniformly to inside of socket. Take care to keep excess cement out of socket. Apply sec­ond coat to end of pipe.
DANGER
DANGER OF EXPLOSION!
Fumes from PVC glue may ignite during system check. Allow fumes to dissipate for at least 5 minutes before placing unit into operation.
NOTE − Time is critical at this stage. Do not allow prim­er to dry before applying cement.
7 − Immediately after applying last coat of cement to pipe,
and while both inside socket surface and end of pipe are wet with cement, forcefully insert end of pipe into socket until it bottoms out. Turn PVC pipe 1/4 turn dur­ing assembly (but not after pipe is fully inserted) to dis-
1 − Measure and cut vent pipe to desired length.
2 − Debur and chamfer end of pipe, removing any ridges
or rough edges. If end is not chamfered, edge of pipe may remove cement from fitting socket and result in a leaking joint.
3 − Clean and dry surfaces to be joined.
NOTE − Check the inside of vent pipe thoroughly for any obstruction that may alter furnace operation.
4 − Test fit joint and mark depth of fitting on outside of pipe.
tribute cement evenly. DO NOT turn ABS or cellular core pipe.
NOTE − Assembly should be completed within 20 sec­onds after last application of cement. Hammer blows should not be used when inserting pipe.
8 − After assembly, wipe excess cement from pipe at end
of fitting socket. A properly made joint will show a bead around its entire perimeter. Any gaps may indi­cate a defective assembly due to insufficient solvent.
9 − Handle joints carefully until completely set.
Page 11
Venting Practices
Piping Suspension Guidelines
SCHEDULE 40 PVC −−
Support every 5 feet.
all other pipe* −−
Support every 3 feet.
* See table 4 for allowable pipe.
NOTE − Isolate piping at the point where it exits the outside wall or roof in order to prevent transmission of vibration to the structure.
Wall Thickness Guidelines
24" maximum 3/4" minimum
1 − In areas where piping penetrates joists or interior
walls, hole must be large enough to allow clearance on all sides of pipe through center of hole using a hanger.
2 − When furnace is installed in a residence where unit is
shut down for an extended period of time, such as a vacation home, make provisions for draining conden­sate collection trap and lines.
Exhaust Piping (Figure 16)
Route piping to outside of structure. Continue with installa­tion following instructions given in piping termination sec­tion.
CAUTION
Do not discharge exhaust into an existing stack or stack that also serves another gas appliance. If verti­cal discharge through an existing unused stack is re­quired, insert PVC pipe inside the stack until the end is even with the top or outlet end of the metal stack.
inside outside
Wall
FIGURE 13
REPLACING FURNACE THAT WAS PART OF A
CHIMNEY
OR GAS
VENT
(Check sizing
for water
heater only)
FURNACE
(Replaced
by SLP98)
If an SLP98 furnace replaces a furnace which was com­monly vented with another gas appliance, the size of the existing vent pipe for that gas appliance must be checked. Without the heat of the original furnace flue products, the existing vent pipe is probably oversized for the single water heater or other appliance. The vent should be checked for proper draw with the remaining appliance.
COMMON VENT SYSTEM
WATER
HEATER
OPENINGS
(To Adjacent
Room)
FIGURE 14
CAUTION
The exhaust vent pipe operates under positive pres­sure and must be completely sealed to prevent leak­age of combustion products into the living space.
Vent Piping Guidelines
The SLP98DFV is installed only as a Direct Vent gas central furnace.
NOTE − In Direct Vent installations, combustion air is taken from outdoors and flue gases are discharged outdoors.
Intake and exhaust pipe sizing −− Size pipe according to
tables 6 and 7. Table 6 lists the minimum vent pipe lengths permitted. Table 7 lists the maximum pipe lengths per- mitted.
Regardless of the diameter of pipe used, the standard roof and wall terminations described in section Exhaust Piping Terminations should be used. Exhaust vent termination pipe is sized to optimize the velocity of the exhaust gas as it exits the termination. Refer to table 9.
In some applications which permit the use of several differ­ent sizes of vent pipe, a combination vent pipe may be used. Contact Lennox’ Application Department for assis­tance in sizing vent pipe in these applications.
15 ft.*
TABLE 6
EXAMPLE
5 ft. plus 2 elbows of 2", 2−1/2"
or 3" diameter pipe
MINIMUM VENT PIPE LENGTHS
SLP98DF
MODEL
070, 090, 110
*Any approved termination may be added to the minimum equivalent length listed.
MIN. EQUIV.
VENT LENGTH
NOTE − It is acceptable to use any pipe size which fits within the guidelines allowed in table 7.
Page 12
NOTE − The exhaust collar on all models is sized to ac­commodate 2" Schedule 40 vent pipe. Contact the Ap­plication Department for more information concerning sizing of vent systems which include multiple pipe sizes.
NOTE All horizontal runs of exhaust pipe must slope back toward unit. A minimum of 1/4" (6mm) drop for each 12" (305mm) of horizontal run is mandatory for drainage.
NOTE − Exhaust pipe MUST be glued to furnace exhaust fittings.
NOTE − Exhaust piping should be checked carefully to make sure there are no sags or low spots.
Use the following steps to correctly size vent pipe diameter.
Furnace
1
2
Capacity?
Which termination?
070, 090, 110
btuh
Standard or Concentric? See table 5
IMPORTANT
Do not use screens or perforated metal in exhaust or intake terminations. Doing so will cause freeze−ups and may block the terminations.
3
4
5
6
7
Which needs most elbows?
How many?
Desired pipe size?
What is the altitude?
Use table 7 to find
max intake or
exhaust pipe length.
Intake or exhaust?
2", 2−1/2", 3"
Page 13
FIGURE 15
Maximum Allowable Intake or Exhaust Vent Length in Feet
TABLE 7
*Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake and Exhaust must be same pipe size.
Standard Termination at Elevation 0 − 4500’
Number Of
90° Elbows
Used
1 91 69 14 140 93 43 162 143 11 8
2 86 64 9 135 88 38 157 138 11 3 3 81 59 4 76 54 125 78 28 147 128 103 5 71 49 120 73 23 142 123 98 6 66 44 115 68 18 137 118 93 7 61 39 110 63 13 132 113 88 8 56 34 105 58 9 51 29 100 53 122 103 78
10 46 24 95 48 117 98 73
Number Of
90° Elbows
Used
1 66 69 14 115 93 43 137 143 11 8
2 61 64 9 110 88 38 132 138 11 3 3 56 59 4 51 54 100 78 28 122 128 103 5 46 49 95 73 23 117 123 98 6 41 44 90 68 18 112 118 93 7 36 39 85 63 13 107 113 88 8 31 34 80 58 9 26 29 75 53 97 103 78
10 21 24 70 48 92 98 73
Number Of
90° Elbows
Used
1 41 44 2 36 39 85 63 107 113 88 3 31 34 80 58 102 108 83 4 26 29 75 53 97 103 78 5 21 24 70 48 92 98 73 6 16 19 65 43 87 93 68 7 11 14 60 38 82 88 63
8
9 50 28 72 78 53
10 45 23 67 73 48
070 090 110 070 090 110 070 090 110
070 090 11 0 070 090 110 070 090 110
070 090 11 0 070 090 110 070 090 110
n/a
2" Pipe 2−1/2" Pipe 3" Pipe
Model Model Model
130 83 33 152 133 108
n/a
127 108 83
n/a
Standard Termination Elevation 4501’ − 7500’
2" Pipe 2−1/2" Pipe 3" Pipe
Model Model Model
105 83 33 127 133 108
n/a
102 108 83
n/a
Standard Terminatiuon at Elevation 7501’ − 10,000’’
2" Pipe 2−1/2" Pipe 3" Pipe
Model Model Model
n/a
n/a
90 68
n/a
55 33 77 83 58
112 11 8 93
NOTE − Table 7 continued on next page with concentric terminations.
Page 14
TABLE 7
Maximum Allowable Intake or Exhaust Vent Length in Feet
*Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake and Exhaust must be same pipe size.
Concentric Termination at Elevation 0 − 4500’
Number Of
90° Elbows
Used
1 83 67 12 130 89 39 146 139 11 4
2 78 62 7 125 84 34 141 134 109 3 73 57 4 68 52 115 74 24 131 124 99 5 63 47 110 69 19 126 119 94 6 58 42 105 64 14 121 114 89 7 53 37 100 59 8 48 32 95 54 111 104 79 9 43 27 90 49 106 99 74
10 38 22 85 44 101 94 69
Number Of
90° Elbows
Used
1 58 67 12 105 89 39 121 114 11 4
2 53 62 7 100 84 34 11 6 109 109 3 48 57 4 43 52 90 74 24 106 99 99 5 38 47 85 69 19 101 94 94 6 33 42 80 64 14 96 89 89 7 28 37 75 59 8 23 32 70 54 86 79 79 9 18 27 65 49 81 74 74
10 13 22 60 44 76 69 69
Number Of
90° Elbows
Used
1 33 42 2 28 37 75 59 91 109 84 3 23 32 70 54 86 104 79 4 18 27 65 49 81 99 74 5 13 22 60 44 76 94 69 6 7 12 50 34 66 84 59
8
9 40 24 56 74 49
10 35 19 51 69 44
070 090 11 0 070 090 110 070 090 11 0
070 090 11 0 070 090 110 070 090 11 0
070 090 11 0 070 090 110 070 090 110
n/a
2" Pipe 2−1/2" Pipe 3" Pipe
Model Model Model
120 79 29 136 129 104
n/a
n/a
Concentric Termination Elevation 4501’ − 7500’
2" Pipe 2−1/2" Pipe 3" Pipe
Model Model Model
95 79 29 111 104 104
n/a
n/a
Concentric Terminatioin at Elevation 7501’ − 10,000’’
2" Pipe 2−1/2" Pipe 3" Pipe
Model Model Model
80 64
17 55 39 71 89 64
n/a
n/a
45 29 61 79 54
n/a
116 109 84
91 84 84
96 11 4 89
Page 15
TYPICAL EXHAUST PIPE CONNECTIONS AND CONDENSATE TRAP INSTALLATION
TRAP
2”
2”
2”
DO NOT transition from smaller to larger pipe size in horizontal
3”
TRANSITION
*2“
Use only the factory−supplied
trap. Trap can be installed on
either side of cabinet within 5 ft.
of the furnace.
* When transitioning up in pipe size, use the shortest length of 2” PVC pipe possible.
NOTE Exhaust pipe and intake pipe must be the same diameter.
runs of exhaust pipe.
Air Intake
FIGURE 16
TYPICAL AIR INTAKE PIPE CONNECTIONS
2”
2”
2”
Exhaust
TOP VIEW
TRAP
TRANSITION
*2”
*2”
Use only the factory−supplied
trap. Trap can be installed on
either side of cabinet within 5 ft.
of the furnace.
* When transitioning up in pipe size, use the shortest length of 2” PVC pipe possible.
NOTE Intake pipe and exhaust pipe must be the same diameter.
3”
3”
TRANSITION
*2”
Air Intake
FIGURE 17
Exhaust
TOP VIEW
Page 16
VENT TERMINATION CLEARANCES
FOR DIRECT VENT INSTALLATIONS IN THE USA AND CANADA
INSIDE CORNER
DETAIL
G
D
A
E
B
L
C
Fixed
F
Closed
Operable
B
B
B
VENT TERMINAL
AIR SUPPLY INLET
US Installations
A =
B =
Clearance above grade, veranda,
porch, deck or balcony
Clearance to window or
door that may be opened
12 inches (305mm) or 12 in. 305mm)
above average snow accumulation.
6 inches (152mm) for appliances <10,000
Btuh (3kw), 9 inches (mm) for appliances
> 10,000 Btuh (3kw) and <50,000 Btuh
(15 kw), 12 inches (305mm) for ap-
pliances > 50,000 Btuh (15kw)
C =
Clearance to permanently
closed window
D =
Vertical clearance to ventilated soffit
located above the terminal within a
* Equal to or greater than soffit depth
horizontal distance of 2 feet (mm)
from the center line of the terminal
E =
F =
G =
H =
Clearance to unventilated soffit
Clearance to outside corner
Clearance to inside corner
Clearance to each side of center line ex-
tended above meter / regulator assembly
I =
Clearance to service regulator
vent outlet
J =
Clearance to non−mechanical air
supply inlet to building or the com-
bustion air inlet to any other ap-
pliance
* Equal to or greater than soffit depth * Equal to or greater than soffit depth
* No minimum to outside corner
3 feet (.9m) within a height 15 feet (4.5m)
above the meter / regulator assembly
*
3 feet (.9m)
6 inches (152mm) for appliances <10,000
Btuh (3kw), 9 inches (mm) for appliances
> 10,000 Btuh (3kw) and <50,000 Btuh
(15 kw), 12 inches (305mm) for ap-
pliances > 50,000 Btuh (15kw)
K =
L =
M =
1
2
 A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.
 Permitted only if veranda, porch, deck or balcony is fully open on a minimum of two sides beneath the floor. Lennox recommends avoiding this location if possible.
Clearance to mechanical air sup-
ply inlet
Clearance above paved sidewalk or
paved driveway located on public property
Clearance under veranda, porch,
deck or balcony
In accordance with the current ANSI Z223.1/NFPA 54 Natural Fuel Gas Code
In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code
3 feet (.9m) above if within 10 feet
(3m) horizontally
* 7 feet (2.1m)
*12 inches (305mm)
FIGURE 18
H
Operable
A
Fixed
Closed
J
B
I
M
AREA WHERE TERMINAL IS NOT PERMITTED
1
Canadian Installations
12 inches (305mm) or 12 in. 305mm)
above average snow accumulation.
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
* 12"
* 12"
* Equal to or greater than soffit depth* Equal to or greater than soffit depth
* No minimum to outside corner
*
*
3 feet (.9m) within a height 15 feet (4.5m)
above the meter / regulator assembly
3 feet (.9m)
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
6 feet (1.8m)
7 feet (2.1m)
12 inches (305mm)
*For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B149.1, clearance will be in accordance with local installation codes and the requirements of the gas supplier and these installation instructions."
K
2
Page 17
Details of Intake and Exhaust Piping Terminations for Direct Vent Installations
NOTE − In Direct Vent installations, combustion air is tak­en from outdoors and flue gases are discharged to out­doors.
NOTE − Flue gas may be slightly acidic and may adversely affect some building materials. If any vent termination is used and the flue gasses may impinge on the building ma­terial, a corrosion−resistant shield (minimum 24 inches square) should be used to protect the wall surface. If the optional tee is used, the protective shield is recommended. The shield should be constructed using wood, plastic, sheet metal or other suitable material. All seams, joints, cracks, etc. in the affected area should be sealed using an appropriate sealant. See figure 21.
Intake and exhaust pipes may be routed either horizontally through an outside wall or vertically through the roof. In attic or closet installations, vertical termination through the roof is preferred. Figures 19 through 28 show typical termina­tions.
1 − Exhaust and intake exits must be in same pressure
zone. Do not exit one through the roof and one on the side. Also, do not exit the intake on one side and the exhaust on another side of the house or structure.
2 − Intake and exhaust pipes should be placed as close
together as possible at termination end (refer to il­lustrations). Maximum separation is 3" (76mm) on roof terminations and 6" (152mm) on side wall termina­tions.
3 − On roof terminations, the intake piping should termi-
nate straight down using two 90° elbows (See figure
19).
4 − Exhaust piping must terminate straight out or up as
shown. A reducer may be required on the exhaust pip­ing at the point where it exits the structure to improve the velocity of exhaust away from the intake piping. See table 9.
NOTE − Care must be taken to avoid recirculation of exhaust back into intake pipe.
Inches(mm)
8" (203mm) MIN
12" (305mm) ABOVE
AVERAGE SNOW
ACCUMULATION
3" (76mm) OR
2" (51mm) PVC
PROVIDE SUPPORT
FOR INTAKE AND
EXHAUST LINES
DIRECT VENT ROOF TERMINATION KIT
3"(76mm) MAX.
(15F75 or 44J41)
SIZE TERMINATION PIPE PER TABLE 9.
UNCONDITIONED
ATTIC SPACE
1/2" (13mm) FOAM
INSULATION IN
UNCONDITIONED
SPACE
FIGURE 19
FIELD−SUPPLIED WALL TERMINATION OR
(15F74) WALL RING TERMINATION KIT
NOTE − FIELD−PROVIDED
REDUCER MAY BE
REQUIRED TO ADAPT
LARGER VENT PIPE SIZE
TO TERMINATION.
1/2" (13mm) ARMAFLEX
INSULATION IN
UNCONDITIONED SPACE
SIZE TERMINATION
PER TABLE 9
D
B
C
A
1/2" (13mm) ARMAFLEX INSULATION
IN UNCONDITIONED SPACE
STRAIGHT
APPPLICATION
D
* WALL
SUPPORT
E
B
A
C
EXTENDED
APPLICATION
See venting table 7 for maximum venting lengths with this arrangement.
* Use wall support every 24" (610 mm). Use two wall supports if extension is greater than 24" (610 mm) but less than 48" (1219 mm). NOTE − One wall support must be 6" (152 mm) from top of each pipe (intake and exhaust).
A−Minimum clearance
above grade or average
snow accumulation
B−Maximum horizontal
separation between
intake and exhaust
C−Minimum from
end of exhaust to
inlet of intake
D−Maximum exhaust
pipe length
E−Maximum wall support
distance from top of each
pipe (intake/exhaust)
2" (51mm)
Vent Pipe
12" (508MM) 12" (508MM)
6" (152MM) 6" (152MM)
8" (203MM) 8" (203MM)
12" (305MM) 20" (508MM)
6" (152MM) 6" (152MM)
3" (76mm)
Vent Pipe
FIGURE 20
Page 18
B
D
B
D
Intake
C
1
C
A
Exhaust
2
A
3
Front View of
Intake and Exhaust
Intake
Exhaust
TABLE 8
D
E
1
B
12"
C
2
A
A− Clearance above
grade or average snow
accumulation
B−Horizontal
separation between
intake and exhaust
C−Minimum from
end of exhaust to
inlet of intake
D−Exhaust pipe length
E−Wall support distance
from top of each pipe
(intake/exhaust)
2" (51mm)
Vent Pipe
12" (508MM) Min.
6" (152MM) Min.
24" (610 MM) Max
9" (227MM) Min.
12" (305MM) Min. 16" (405 MM) Max.
6" (152MM) Max.
3" (76mm)
Vent Pipe
12" (508MM) Min.
6" (152MM) Min.
24" (610 MM) Max
9" (227MM) Min.
12" (305MM) Min. 20" (508MM) Max.
6" (152MM) Max.
1
not use an accelerator in applications that include an exhaust termination tee. The accelerator is not required.
2
termination is used and flue gases will impinge on the building materials, a corrosion−resistant shield (24 inches square) should be used to protect the wall surface. If optional tee is used, the protective shield is recommende­d. The shield should be constructed using wood, sheet metal or other suitable material. All seams, joints, cracks, etc. in affected area, should be sealed using an appropriate sealant.
3
Exhaust pipe 45° elbow can be rotated to the side away from the combustion air inlet to direct exhaust away
from adjacent property. The exhaust must never be directed toward the combustion air inlet.
NOTE − See unit installation instructions for proper exhaust pipe termination size reduction.
The exhaust termination tee should be connected to the 2" or 3" PVC flue pipe as shown in the illustration. Do
As required. Flue gas may be acidic and may adversely affect some building materials. If a side wall vent
FIGURE 21
Page 19
FIELD−SUPPLIED WALL TERMINATION OR
(15F74) WALL RING TERMINATION KIT
With INTAKE ELBOW
NOTE − FIELD−PROVIDED
REDUCER MAY BE
REQUIRED TO ADAPT
LARGER VENT PIPE SIZE
TO TERMINATION.
1/2" (13mm) ARMAFLEX
INSULATION IN UN-
CONDITIONED SPACE
SIZE TERMINATION
PER TABLE 9
D
* WALL
SUPPORT
B
C
A
1/2" (13mm) ARMAFLEX INSULATION
IN UNCONDITIONED SPACE
E
STRAIGHT
APPPLICATION
D
B
A
C
See venting table 7 for maximum venting lengths with this arrangement.
* Use wall support every 24" (610 mm). Use two wall supports if extension is greater than 24" (610 mm) but less than 48" (1219 mm). NOTE − One wall support must be 6" (152 mm) from top of each pipe (intake and exhaust).
EXTENDED
APPLICATION
EXHAUST PIPE TERMINATION SIZE REDUCTION
SLP98DFV
MODEL
*070 2", 2−1/2" or 3" 1−1/2" *090 2", 2−1/2" or 3" 2"
110 2", 2−1/2" or 3" 2"
Exhaust Pipe Size Termination Pipe Size
*SLP98DF −070 and −090 units with the flush−mount ter­mination must use the 1−1/2" accelerator supplied with the kit.
5 − On field−supplied terminations for side wall exit, ex-
haust piping may extend a maximum of 12 inches (305mm) for 2" PVC and 20 inches (508mm) for 3" (76mm) PVC beyond the outside wall. Intake piping should be as short as possible. See figures 20 and 22.
6 − On field−supplied terminations, a minimum distance
between the end of the exhaust pipe and the end of the intake pipe without a termination elbow is 8" and a minimum distance of 6" with a termination elbow. See figures 20 and 22.
7 − If intake and exhaust piping must be run up a side wall
to position above snow accumulation or other ob­structions, piping must be supported every 24" (610mm) as shown in figures 20 and 22. In addition, close−coupled wall termination kits must be extended for use in this application. See figures 30 and 31. When exhaust and intake piping must be run up an outside wall, the exhaust piping must be terminated with pipe sized per table 9.The intake piping may be equipped with a 90° turndown elbow. Using a turn­down elbow will add 5 feet (1.5m) to the equivalent length of the pipe.
8 − Based on the recommendation of the manufacturer, a
multiple−furnace installation may use a group of up to four terminations assembled together horizontally, as shown in figure 25.
TABLE 9
A−Minimum clearance
above grade or average
snow accumulation
B−Maximum horizontal
separation between
intake and exhaust
C−Minimum from
end of exhaust to
inlet of intake
D−Maximum exhaust
pipe length
E−Maximum wall support
distance from top of each
pipe (intake/exhaust)
2" (51mm)
Vent Pipe
12" (508MM) 12" (508MM)
6" (152MM) 6" (152MM)
6" (152MM)
12" (305MM) 20" (508MM)
6" (152MM) 6" (152MM)
3" (76mm)
Vent Pipe
6" (152MM)
FIGURE 22
Page 20
1−1/2" (38mm) accelerator
provided on 71M80 &
44W92 kits for
SLP98DFV−36B−070
12” (305mm)
Minimum
Above Average
Snow
Accumulation
CLAMP
DIRECT VENT CONCENTRIC ROOFTOP TERMINATION
71M80, 69M29 or 60L46 (US)
41W92 or 41W93 (Canada)
INTAKE
SHEET METAL STRAP
(Clamp and sheet metal strap must be field installed to support the weight of the termination kit.)
REDUCER MAY BE REQUIRED
PIPE SIZE TO TERMINATION
FLASHING
(Not Furnished)
FIELD−PROVIDED
TO ADAPT LARGER VENT
FIGURE 23
Loading...
+ 44 hidden pages