LEM LEM HAS 50-S Datasheet

Page 1
I
Current Transducer HAS 50 ... 600-S
For the electronic measurement of currents: DC, AC, pulsed...,
= 50 ... 600 A
P N
with galvanic separation between the primary circuit and the secondary circuit.
Electrical data
Type Primary nominal Primary current, RMS current measuring range 1)
I
HAS 50-S 50 ±150 HAS 100-S 100 ±300 HAS 200-S 200 ±600 HAS 300-S 300 ±900 HAS 400-S 400 ±900 HAS 500-S 500 ±900 HAS 600-S 600 ±900
UC Supply voltage (±5 %) 1) ±15 V I R U R
Current consumption ±15 mA
C
Insulation resistance @ 500 V DC > 1000 MΩ
INS
Output voltage (Analog) @ ±I
out
Output internal resistance approx 100
out
RL Load resistance 2) > 1 kΩ
Accuracy - Dynamic performance data
ε
Total error @ I
tot
, TA = 25 °C (excluding o󰀨set) < ±1 % of I
P N
εL Linearity error 3) (0 ... ±I U
Electrical o󰀨set voltage, TA = 25 °C < ±20 mV
O E
U
Hysteresis o󰀨set voltage @ IP = 0,
O M
after an excursion of 1 × I
TCU
Temperature coe󰀩cient of U
O E
HAS 100 ... 600-S < ±1 mV/K
TCU t
Temperature coe󰀩cient of U
out
Delay time to 90 % of I
D 90
P N
BW Frequency bandwidth (−3 dB) 5) DC ... 50 kHz
General data
TA Ambient operating temperature −10 ... +80 °C TS Ambient storage temperature −25 ... +80 °C m Mass approx 60 g
Standards UL UL 508:2010 EMC IEC 61000-6-2:2016 IEC 61800-3:2017 Safety IEC 61010-1:2010 Environmental IEC 61477-1:2012 IEC 61800-2:2012
1)
Notes:
limited as the nominal. To measure the full dened measuring range, the load resistor should be at minimum 10 kΩ
variation of the o󰀨set between 390 MHz and 400 MHz with a eld intensity of 10 [V/m].
15April2020/version 15
Operating at ±12 V ≤ UC < ±15 V will reduce the measuring range
2)
If the customer uses 1 kΩ of the load resistor, the primary current has to be
3)
Linearity data exclude the electrical o󰀨set
4)
For a di/dt = 50 A/µs
5)
Under small signals condition
6)
Regarding compliance towards IEC 61000-4-3 (IEC 61800-3:2017):
(A) I
P N
, RL = 10 kΩ, TA = 25 °C ±4 V
P N
) < ±1 % of I
P N
HAS 50-S < ±2 mV/K
O E
(% of reading) < ±0.1 %/K
out
(A)
P M
< ±20 mV
P N
4) < 3 µs
LEM reserves the right to carry out modications on its transducers, in order to improve them, without prior notice
P N
P N
Features
● Hall e󰀨ect measuring principle
● Insulating plastic case made of
polycarbonate PBT recognized according to UL 94-V0.
Advantages
● Easy mounting
● Low power consumption
● Small size and space saving
● Only one design for wide current
ratings range
● High immunity to external interference.
Applications
● AC variable speed drives
● Static converters for DC motor
drives
● Battery supplied applications
● Uninterruptible Power Supplies
(UPS)
● Switched Mode Power Supplies (SMPS)
● Power supplies for welding applications.
Application domain
6)
● Industrial.
LEM International SA Chemin des Aulx 8 1228 PLAN-LES-OUATES Switzerland www.lem.com
Page 1/3
Page 2
Current Transducer HAS 50 ... 600-S
d
Basic insulation
Reinforced insulation
Insulation coordination
Ud RMS voltage for AC insulation test, 50 Hz, 1 min 3.6 kV UNi Impulse withstand voltage 1.2/50 µs > 6.6 kV
Min
dCp Creepage distance 7.08 mm dCI Clearance 6.23 mm CTI Comparative tracking index (group IIIa) 275
Applications examples
According to IEC 61010-1 standard and following conditions:
● Over voltage category OV 3
● Pollution degree PD2
● Non-uniform eld
IEC 61010-1
, dCI, U
Cp
Ni
Nominal voltage
600 V
300 V
Safety
This transducer must be used in limited-energy secondary circuits according to IEC 61010-1.
This transducer must be used in electric/electronic equipment with respect to applicable standards and safety requirements in accordance with the manufacturer’s operating instructions.
Caution, risk of electrical shock
When operating the transducer, certain parts of the module can carry hazardous voltage (eg. primary busbar, power supply). Ignoring this warning can lead to injury and/or cause serious damage. This transducer is a build-in device, whose conducting parts must be inaccessible after installation. A protective housing or additional shield could be used. Main supply must be able to be disconnected.
15April2020/version 15
LEM reserves the right to carry out modications on its transducers, in order to improve them, without prior notice
Page 2/3
LEM International SA Chemin des Aulx 8 1228 PLAN-LES-OUATES Switzerland www.lem.com
Page 3
Dimensions HAS 50 ... 600-S (in mm)
Note
Mechanical characteristics
● General tolerance ±0.5 mm
● Transducer fastening 1 hole 4.5 mm
1 M4 steel screw Recommended fastening torque 0.75 N·m (±10 %)
● Connection of secondary Molex type 2501P04V00A
: 1) Recommanded mating connector : Molex
511910400 (housing) and 508029101 (contact).
d
Cl
d
Cp
Connection
I
P
U
C
R
L
U
C
Remarks
U
is positive when IP ows in the direction of the arrow.
out
● Temperature of the primary conductor should not exceed 100 °C.
● Installation of the transducer must be done unless
1)
otherwise specied on the datasheet, according to LEM
Transducer Generic Mounting Rules. Please refer to
LEM document N°ANE120504 available on our Web site:
https://www.lem.com/en/le/3137/download/.
● Dynamic performances (di/dt and delay time) are best with a single bar completely lling the primary hole.
● This is a standard model. For di󰀨erent versions (supply voltages, turns ratios, unidirectional measurements...), please contact us.
15April2020/version 15
LEM reserves the right to carry out modications on its transducers, in order to improve them, without prior notice
Page 3/3
LEM International SA Chemin des Aulx 8 1228 PLAN-LES-OUATES Switzerland www.lem.com