LEGRAND Trimod 10 kVA, Trimod 20 kVA, Trimod 15 kVA, Trimod 40 kVA, Trimod 30TM kVA Operating And Maintenance Manual

...
Trimod®
Operating and Maintenance Manual
®
Part. LE05768AA-07/12-01 GF
2
EN
ENGLISH 3
Trimo
Trimod®
3
Operating and Maintenance Manual
1 Foreword 6
1.1 Overview 6
1.2 Purpose of the manual 6
1.3 Where nad how to keep the manual 7
1.4 Manual update 7
1.5 Collaboration with the user 7
1.6 Manufacturer 7
1.7 Responsabilities of the manufacturer and guarantee 7
1.8 Copyright 8
2 Technological description 9
2.1 Technology Trimod® 9
2.2 Features 9
2.3 Models 12
2.4 Communications device 20
2.4.1 RS232 serial ports 20
2.4.2 Relay interface 20
2.4.3 Logic Level Interface 21
2.4.4 Communications slot 21
2.4.5 Power module block diagram 22
2.4.6 Interconnection block diagram 22
3 Safety provisions 23
3.1 General notes 23
3.2 Symbols 23
3.3 Definitions of “operator” and “specialized technician” 23
3.3.1 Qualification required to the operator 23
3.3.2 Qualification required to the specialized technician 24
3.4 Individual protective gear 24
3.4.1 Gear to wear 24
3.5 Indications of danger in the work place 25
3.5.1 Indications on board the equipment 25
3.6 Residual risks 25
3.7 General warnings 26
3.8 Emergency interventions 27
3.8.1 First aid intereventions 27
3.8.2 Fire prevention measures 27
Index of contents
4
4 Unpacking 28
4.1
Visual inspection
28
4.1.1 Checking the equipment and accessories supplied 28
4.2 Unpacking 28
4.3 Checking the contents of the pack 28
4.4 Storing 29
4.4.1 UPS 29
4.4.2 Batteries 29
4.5 Handling 30
4.6 Positioning 30
4.7 Last operations 31
5 Installation 32
5.1 Safety rules and regulations 32
5.1.1 Mains connections for TN systems 33
5.1.2 Mains connections for TT systems 34
5.2 Electrical connections 35
5.2.1 Safety reccomandations 35
5.2.2 Preliminary operations 35
5.2.3 Connectiong the loads 35
5.2.4 Emergency Power Off (Remote E.P.O.) 36
5.2.5 Installing the Trimod® BATTERY 36
5.2.6 Protections 39
5.2.7 Earthing 39
5.2.8 Connectiong the power supply 39
5.2.9 Wiring 40
5.3 Wiring diagrams 40
5.3.1 THREE-PHASE input, THREE-PHASE output 41
5.3.2 THREE-PHASE input, SINGLE-PHASE output output connections 45
5.3.3 SINGLE-PHASE input, SINGLE-PHASE output connections 45
5.3.4 SINGLE-PHASE input, THREE-PHASE output connections 48
5.3.5 SINGLE-PHASE input connections no. 3 separate outputs 49
5.3.6 UPS Trimod® 30TM connections 52
Index of contents
Trimod®
Operating and Maintenance Manual
5
6 Configuration and Start-up 53
6.1 Input configuration 53
6.2 Output configuration 53
6.3 Checks prior to switching ON 53
6.4 Starting procedure 53
7 Control panel 56
7.1 “Service Mode” function 57
7.2 Main menu and submenus 57
7.2.1 UPS status 61
7.2.2 UPS settings 64
7.2.3 Power Modules 67
7.2.4 Events 69
7.2.5 Tools 69
7.2.6 Logout 70
7.2.7 Turning the single output phases ON and OFF 70
7.2.8 Shutting down the UPS Trimod® 70
8. Diagnostics 71
8.1 Luminous and acoustic signals 71
8.2 Messagges 73
9. Maintenance 80
9.1 Introduction 80
9.2 Preventive maintenance 80
9.3 Periodical checks 80
9.3.1 Preparing the UPS for maintenance. Forced bypass mode 80
9.4 Adding or replacing a power module or battery drawers 81
9.4.1 Power Module 81
9.4.2 Exit from the maintenance manual bypass 81
9.4.3 Battery drawers 82
10. Dismantling 83
10.1 Disposing of the batteries 83
10.2 Dismantling the UPS 83
10.3 Disposing of the electronic components 83
11. Tables 84
Index of contents
6
1.1 Overview
Congratulations for having bought a LEGRAND® UPS Trimod® product.
Thanks to UPS Trimod® unit your critical equipment will be protected by a constant and reliable supply of power for years to come.
LEGRAND® is based in Italy and specializes in designing and producing UPS units. The UPS Trimod® system is unique, modular and the last generation of three-phase medium power UPS units. Highly reliable, low running costs and excellent electrical performance are but a few of the great features of this innovative UPS. Moreover, the criteria and methods that LEGRAND® uses for its design and production comply with the strictest quality standards. The product is, in fact, produced at an ISO14001 certied factory in full compliance with the eco-design laws.
The UPS Trimod® system is made in compliance with the existing European Community directives and with the technical standards that include their requirements as certied by the Declaration of Conformity issued by the Manufacturer and enclosed with this manual.
This publication, simply dened ‘manual’ herein, contains all the information for the installation, use and maintenance of the equipment specied in the Declaration of Conformity.
This equipment will be referred to simply as ‘equipment’ or even ‘machine’ in this manual and is manufactured by LEGRAND®.
The contents of this manual are intended for an operator who has already been instructed on the precautions to be taken in relation to the presence of electricity.
The persons to whom this publication is addressed, normally dened ‘users’, are all those people who, for their eld of expertise, have the need and/or obligation to provide instructions or work directly on the equipment.
These people can be the following:
- managers;
- heads of operating areas;
- department heads;
- operators directly concerned with transporting, storing, installing, using and servicing machines from the moment they are put on the market up to the day they are scrapped;
- direct private users.
The original text of this publication, written in the Italian language, is the only reference for solving any disputes concerning the interpretation of translations into Community languages.
This publication is to be considered an integral part of the equipment supplied and, as such, must be kept for future reference up until the equipment is denitively dismantled and scrapped.
1.2 Purpose of the manual
The purpose of this manual is to provide indications for using the equipment safely and to carry out routine maintenance procedures.
Adjustments and extraordinary maintenance jobs are not dealt with in this manual as they are reserved exclusively to the assistance technician who must observe to the technical and design characteristics for which the equipment was made when working on it.
It is essential that this manual is read through but it is not a substitute for the expertise of the technical personnel who must have had adequate preliminary training.
The intended use and congurations envisaged for the equipment are the only ones allowed by the Manufacturer; do not attempt to use the equipment in disagreement with the indications given.
1. Foreword
Trimod®
Operating and Maintenance Manual
7
Any other use or conguration must be agreed on beforehand with the Manufacturer in writing and, in such a case, will be an enclosure to the manual.
For its use the user must also comply with the specic laws on work that exist in the country where the equipment is installed.
Reference is also made in this manual to laws, directives, etc., that the user must know and consult in order to full the purposes established by the manual.
1.3 Where and how to keep the manual
This manual (and its enclosures) must be kept in a safe, dry place and always be available for consultation. We suggest making a copy and ling it. If information is exchanged with the Manufacturer or assistance personnel authorised by the former, please refer to the equipment’s rating plate data and serial number.
The manual must be kept for the equipment’s useful life cycle and, if necessary (e.g. damage which prevents it being consulted even partially) the user must ask the Manufacture for a new copy, quoting the publishing code on the cover.
1.4 Manual update
The manual reects the state of the art at the moment the equipment was put on the market, of which it is an integral part. The publication complies with the directives in force at such a date. The manual cannot be considered inadequate if updates of standards or changes are made to the equipment.
Any integration to the manual which the Manufacturer deems tting to send to the users, must be kept with the manual, becoming an integral part of it.
1.5 Collaboration with the user
The Manufacturer is available to its clientele to provide additional information and will take into consideration any suggestions made to improve this manual to bring it even closer to the requirements for which it was drawn up.
If the equipment is sold, which always includes handing over this operating manual, the primary user must notify the Manufacturer, giving him the address of the new user so the latter can be reached if there are any communications and/ or updates deemed indispensable.
LEGRAND® reserves the property rights of this publication and forbids the total or partial reproduction of it without prior written consent.
1.6 Manufacturer
The equipment’s identication data are given on the ID plate.
1.7 Responsibilities of the manufacturer and guarantee
In order to use the guarantee supplied by the Manufacturer the user must scrupulously comply with the precautions indicated in the manual and in particular:
- to always work within the equipment’s limits of use;
- to always carry out constant and accurate maintenance;
- to have persons use the equipment with proven capabilities and skill and adequately trained for the purpose;
The Manufacturer declines all liabilities, direct and indirect, resulting from:
- disregard for the instructions and if the equipment is used dierently to what is foreseen in the operating manual.
- use by personnel who have not read and understood properly the contents of the manual;
- a use failing to conform to the specic laws existing in the country of installation;
8
- changes made to the equipment, software, operating logic that were not authorised by the Manufacturer in writing;
- unauthorised repairs;
- exceptional events.
When the equipment is sold to a third party this manual has to go with it; if the manual is not given to the new user then all purchaser rights are automatically invalidated, including guarantee terms where applicable.
If the equipment is sold to a thirty party in a country of a dierent language it is the responsibility of the original user to provide a true translation of this manual in the language of the country where the equipment is going to be used.
1.8 Copyright
The information in this manual must not be disclosed to third parties. Any duplication, total or partial, not authorised in writing by the Manufacturer, obtained by photostatting, duplicating or any other method, even electronically, violates the copyright conditions and can be persecuted by law.
1. Foreword
Trimod®
Operating and Maintenance Manual
9
2.1 Trimod® Technology
Congratulations on your purchase of a UPS Trimod® product from LEGRAND®.
Thanks to the UPS Trimod® your critical equipment will be protected by a constant and reliable supply of power for years to come.
LEGRAND® has developed a project that is both innovative and unique, creating Trimod®, the UPS with a power range of 10, 15, 20, 30, 40 and 60 kVA capable of adapting itself at any time to the changing requirements of protected loads: greater power, longer autonomy, redundancy. The basic concepts of the Trimod® project are, in fact, modularity, expandability and redundancy which, besides oering maximum reliability, are also the guarantee of a considerable economic saving.
Trimod® is a modular uninterrupted power supply unit with individually programmable basic modules so you can have the input/output conguration you want. In this way it is possible to control three- and single-phase voltage in input and output to have, as preferred the classical three/three, three/single, single/three and single/single lines but it is not limited to just this: you can also have single- and three-phase lines in output simultaneously or two or more single-phase lines also of dierent powers (on request).
And then, for each conguration it is possible to obtain redundancy, both complete and partial by which we mean that, for example, a normal (or redundant) threephase line plus a redundant (or normal) single-phase line can coexist in output. A microcontroller mounted in each basic module is capable of monitoring the main functions of each single power unit, monitoring its correct operation and signalling any malfunctions. The modularity philosophy has also been used for the batteries which are supplied in single pull-out boxes. THDi = 3% ­Power Factor > 0.99 – High Yield – High Reliability – Easy to install and service.
2.2 Features
Redundant modular architecture
Redundant modular architecture is the best way to protect a company’s critical points. Advantages:
- There is just one control of the devices powered
- Modular Expandability
- Module redundancy
- Easy to service
- Low running cost
- Compact size
Yield
The UPS units of the Trimod® line place particular attention on the energy taken from the mains and that supplied to the user points. High Yield (>94%), PFC in Input >0.99, THDi 3%. Advantages:
- Increasing the yield means reducing the part of power absorbed by the UPS but not supplied at the load and transmitted to the environment in the form of heat.
- Les s heat dispersed in the environment means reducing the use of aeratin g or conditioning systems on the installation premises.
- PFC in input means no rephasing costs and consequently no increased rates.
- No need to oversize a generator (if used) upstream from the UPS
Expandability
The majority of UPS units on the market is neither modular nor expandable and therefore initial oversizing of the system is necessary to ensure future expansions (which might not even happen). Advantages:
- The modular and expandable Trimod® systems allow optimisation of the investments made in UPS units, adapting them to actual requirements without preventing future expansions and avoiding an unnecessary waste of energy.
- System yield is increased thanks to correct sizing
Reliability
To have a redundancy level with traditional UPS units it is necessary to put at least 2 in parallel, thus doubling the power bought, the space taken up and the electricity consumed. Instead Trimod®’s modular architecture allows redundant congurations inside just one single cabinet.
2. Technological description
10
Advantages:
- A UPS with a modular redundant architecture can be congured as an N+X system redundant in power; even in the case of a failing module the equipment carries on working and there is no stop in work.
- Clear indications and a large display speed up troubleshooting.
- The modular architecture makes short work of repairing a failure by simply replacing the module in question without interrupting service.
- A high resolution percentage of failures at the rst assistance intervention.
Power module
The basic module, available in three power sizes, 3,400 VA, 5,000 VA and 6,700 VA, is basically made up of the following functional blocks: command and control logic (microprocessor controlled), rectier/PFCr, inverter, booster, battery charger, automatic bypass. The power unit is the Plug & Play type to facilitate power expansion and all maintenance works. Each module is paralleled with other identical ones until the UPS power is reached. The power modules are separate from each other and can work even if one malfunctions. A LED on the front of the module, with a trac-light code, quickly shows the operating state of the electronic unit.
Prescription forms for PM4, PM6 and PM7 only on the related cabinets: UPS Trimod® electrical distribution equipment is sized for its nominal power and must be used only with power modules originally installed. Each cabinet must use only the provided power modules, described in table "Mechanical properties" on page 18 of this manual. It is not possible to use power modules other than those indicated, nor mix with other models and/or replace the type of modules.
• The model, the power rating and the type of power module to be installed in the UPS cabinet UPS Trimod® are indicated on the user manual and on the label inside the door of the UPS.
• The type and power rating of the power module are indicated on the label axed to the bottom of the power module for proper identication.
It is recommended to use only provided UPS Trimod® Power Modules.
Battery drawers
The battery modules are designed for easy insertion in the cabinet with no work needed to connect them; they are easy to handle thanks to their light weight, likewise any maintenance or replacing. A box holds 5 12V, 7.2 Ah or 9 Ah batteries connected in series and, thanks to the Plug & Play connection can be easily pulled out and put inside the cabinet. In order to guarantee maximum safety, especially during maintenance, the voltage of each box is adequately disconnected into two 24 and 36V branches and restored only when the box is placed right inside its housing. This conforms to the CEI-EN 60950 standard on electrical safety which establishes that adequate safeguards must be used and particular attention where there are dangerous voltages higher than 50 Vdc with the possibility of direct contact. Autonomy can be increased further still by adding other battery ‘boxes’ in multiples of four, exploiting the space inside the UPS and the space in the additional ‘modular cabinets
Digital display and displaying alarms
Trimod® is controlled by a microprocessor and has a backlit alphanumerical liquid crystal display (LCD) with 20 characters on 4 lines built into the front of the UPS where there is also a highly luminous operating status indicator which, by means of a trac-light code, indicates the operating status and any alarm conditions. Four simple push buttons near the display allow the user to: see operating data, set operating parameters, analyse the state of each single power module, select the language in which to see the messages and execute a set of functional tests.
BCM (Battery Charger Module)
It works together with internal PM chargers, with the same intelligent management of the charging cycle. For each BCM installed the maximum batteries recharging current is increased of 15Adc: 1 BCM has a charging current equivalent to that of 6 (internal to the charger) PMs. This guarantees to reduce charging time in installations that require long backup time UPS and increases the availability of the UPS system after a power failure (blackout). During operation, the module draws current from the phase input (slot) in which it is installed. If at least n°1 PM is present, it is possible to install any number of BCM.
2. Technological description
Trimod®
Operating and Maintenance Manual
11
All informations about BCM are indicated by LED on the front of the module and described on the display menu. The module is controlled by a microprocessor to optimize performance and reliability, we recommend the use in combination with higher than 60Ah capacity batteries.
Input voltage 230V +15% -20%, rated output power 4kW, maximum rated current 15Adc, maintenance voltage 13.75Vdc/ battery. Operating status through the UPS front panel LEDs and multi-colored, adjustable fan speed versus power output, overtemperature protection. Intelligent charging cycle with four stages to maximize battery life (constant current, nal charge, maintenance and stand-by).
O-Line Mode
The UPS Trimod® ® provides a mode of operation o-line that allows to save power while still providing the protection of the continuity of power supply to the connected load. During the operation O-Line, the load is powered directly by the mains through the automatic internal bypass circuit in power modules. This means that the voltage and the output frequency are the same as the network input, and the UPS Trimod can not control these variables. The benet that you get in the O-Line mode is greater electrical eciency since UPS doesn’t work. If the output voltage goes out of tolerance range (± 15% of the set voltage output) or is lacking, the UPS activates its stage inverter powering the load with the energy stored in the batteries. The runtime during battery operation depends on the conguration of the UPS (full load, battery capacity) and the percentage of applied load. When AC input is within the parameters of tolerance, the UPS automatically returns to the O-Line mode. And it is possible to change the operating mode between On-Line and O-Line (and vice versa) when the UPS is ON or OFF (entering Service Mode).
• To activate the O-Line, enter the Main Menu -> Settings UPS -> Bypass -> O-Line Mode and select Enabled, conrm the selection with the Enter button.
• To activate the On-Line, enter the Main Menu -> Settings UPS -> Bypass -> O-Line Mode and select Disabled, conrm the selection with the Enter button.
WARNING!
If the load needs to be fed without any interruption or with a regulated voltage amplitude and/or frequence it is
recommended to use the UPS Trimod® mode On-Line double conversion.
12
UPS Trim od® 10 UPS Trim od® 10/15/20
2.3 Models
2. Technological description
Trimod®
Operating and Maintenance Manual
13
UPS Trim od® 10/15/20 UPS Trim od® 30 TT
14
UPS Trim od® 30 TM UPS Trim od® 40
2. Technological description
Trimod®
Operating and Maintenance Manual
15
UPS Trim od® 60
16
2. Technological description
UPS Trim od® BATTERY UPS Trim od® BATTERY/2
Trimod®
Operating and Maintenance Manual
17
3 104 36
10 kVA
3 104 37
15 kVA
3 104 37
20 kVA
3 104 39
30 kVA TM
3 104 38
30 kVA TT
3 104 40
40 kVA
3 104 41
60 kVA
Rated Power 10 kVA 15 kVA 20 kVA 30 kVA 30 kVA 40 kVA 60 kVA
Active Power 9 kW 13.5 kW 18 kW 27 kW 27 kW 36 kW 54 kW
Technology
On Line, double conversion
IEC 62040-3 VF I – S S - 111
IN/OUT configuration
Single / Single – Single / Tri – Tri /
Single – Tri /Tri (can be configured by user)
Tri / Tri
UPS architecture
Modular with 3400 VA - 5000VA - 6700VA power modules housed in a single cabinet
Expendable, Redundant N+X (except for Trimod® 30 kVA TM and Trimod® 60 kVA).
General charateristics
3 104 36
10 kVA
3 104 37
15 kVA
3 104 37
20 kVA
3 104 39
30 kVA TM
3 104 38
30 kVA TT
3 104 40
40 kVA
3 104 41
60 kVA
Maximum current (Three-phase - Three-phase) 18.5 A 27.8 A 37 A 55.5 A 55.5 A 74 A 111 A
Maximum current (Three-phase - Single-phase) 18.5 A 27.8 A 37 A 55.5 A - - -
Maximum current (Single-phase - Three-phase) 55.5 A 83.3 A 111 A 166.5 A - - -
Maximum current (Single-phase - Single-phase) 55.5 A 83.3 A 111 A 166.5 A - - -
Input voltage
230 V + 15% - 20% (Single-phase)
400 V + 15% - 20% (Three-phase)
(Neutral line is essential)
400 V + 15% - 20%
(Three-phase)
(Neutral line is essential)
Input frequency 50 / 60 Hz
Power factor on the input > 0.99
THD input current < 3%
Input
3 104 36
10 kVA
3 104 37
15 kVA
3 104 37
20 kVA
3 104 39
30 kVA TM
3 104 38
30 kVA TT
3 104 40
40 kVA
3 104 41
60 kVA
Maximum current (Three-phase - Three-phase) 14.50 A 21.7 A 29 A 43.5 A 43.5 A 58 A 87 A
Maximum current (Three-phase - Single-phase) 43.5 A 65.2 A 87 A 130.5 A - - -
Maximum current (Single-phase - Three-phase) 14.50 A 21.7 A 29 A 43.5 A - - -
Maximum current (Single-phase - Single-phase) 43.5 A 65.2 A 87 A 130.5 A - - -
Output voltage
230 V ± 1% (Single-phase)
400 V ± 1% (Three-phase)
400 V ± 1% (Three-phase)
Static tolerance of output voltage 1%
Output frequency 50 / 60 Hz synchronized
Wave shape Sinusoidal
Mains efficiency (AC/AC on line) 94% max
Mains efficiency (AC/AC eco mode) 99% max
Tolerated overload 125% per 10 min – 150% per 60 s
Output
18
3 104 36
10 kVA
3 104 37
15 kVA
3 104 37
20 kVA
3 104 39
30 kVA TM
3 104 38
30 kVA TT
3 104 40
40 kVA
3 104 41
60 kVA
Type of batteries 12V 7.2Ah or 12V 9Ah maintenance-free sealed lead batteries
Tolerated overload 125% per 2 min – 150% per 30 s
Batteries
3 104 36
10 kVA
3 104 37
15 kVA
3 104 37
20 kVA
3 104 39
30 kVA TM
3 104 38
30 kVA TT
3 104 40
40 kVA
3 104 41
60 kVA
Bypass
Automatic (static and electromechanical)
Manual (for maintenance)
Signals and alarms
Large alphanumerical display with 4 lines,
multicolored status indicator, buzzer
Communication ports Two RS 232 ports, 1 relay interface, 1 contact port
Software Can be downloaded free of charge from the web site www.ups.legrand.com
Protections
Electronic against overloads, short-circuits and excessive battery discharging.
Functions blocks if autonomy ends.
Powering surge limiter.
E.P.O. contact (total shutdown in an emergency) BackFeed Protection.
3 104 36
10 kVA
3 104 37
15 kVA
3 104 37
20 kVA
3 104 39
30 kVA TM
3 104 38
30 kVA TT
3 104 40
40 kVA
3 104 41
60 kVA
Net weight UPS (without batteries) 110 Kg 130 Kg 154 Kg
Dimensions UPS (L x H x D) (mm) 414 x 1367 x 628
3400VA Power modules installed 3
5000VA Power modules installed 3 6 6
6700VA Power modules installed 3 6 9
Power modules - Net weight 8 Kg
Battery drawing - Net Weight 14 Kg
3 104 36
10 kVA
3 104 37
15 kVA
3 104 37
20 kVA
3 104 39
30 kVA TM
3 104 38
30 kVA TT
3 104 40
40 kVA
3 104 41
60 kVA
Operating temperature 0°C ÷ 40°C
Relative humidity 20% ÷ 80% non-condensing
Noise level at 1m 58 ÷ 62 dBA
Grade of protection IP 21
Accessories
Mechanical characteristics
Environmental conditions
2. Technological description
Trimod®
Operating and Maintenance Manual
19
INPUT
Rated voltage and tolerance 230 Vac +15% -20%
Rated current 19.3 Arms
Power Factor PF > 0.99
Input current THD THDi < 3%
ENVIRONMENTAL CONDITIONS
Operating temperature 0°C ÷ 40°C
Relative humidity 20% ÷ 80% non-condensing
Noise level at 1m 42 ÷ 46 dBA
Grade of protection IP 20 (IEC 529)
OUTPUT
Maintenance voltage 13.75 Vdc/battery
Rated current (max) 15 Adc
AC/DC Efficiency >93% at max rated current
INDICATIONS
Operating mode (multi-color LED on the module and display menu information on the UPS)
Yellow LED, Fast intermittent: f1 recharge fase. Green LED, Slow intermittent: f2 recharge fase and maintenance. Green LED, fi xed: stand-by Red LED: Fault mode
STANDARD
EN 62040-1, EN 62040-2, EN 62040-3
Bcm technical specifications
20
2.4 Communication devices
The uninterrupted power supplies of the UPS Trimod® family have 2 RS 232 serial ports, 1 relay interface and 1 output on a 9-pole male tray-shaped connector, logic level SELV. insulated.
AT T EN T ION
To en su re o pe ra to r sa fe ty it i s ma nd at or y fo r th e in te r fa ce s to b e co nn ec te d so t ha t:
- the maximum voltage between any two conductors connected to the interface and between either of these two
conductors and earth is less than a peak 42V or less than 60Vdc;
- the insulation voltage between any conductor connected to the interface and earth is at least 1500Vac
2.4.1 RS232 serial ports
The rst of the two RS232 serial ports used on the uninterrupted power supply unit and called “maintenance interface” is located at the top behind the front door. It is dedicated exclusively to diagnostic functions and updating machine rmware. The second, called “user interface”, is at the top at the back of the UPS. Thanks to this port that, with either a computer or specic network card, it is possible to access UPS operating data and to control the unattended turning o of the operating system.
2.4.2 Relay interface/E.P.O.
The default setting of the relay interface contacts is Normally Open (NO) but can be congured as Normally Closed (NC) via the UPS display. Inoltre è presente l’ingresso per la funzione E.P.O. The indications available with this interface are:
• running on battery
• autonomy reserve
• generic alarm
• overload
• UPS running on bypass
Electrical specications/contact interface
The technical specications of the relay interface contacts are the following:
• V
MAX
= 250VAC - 30VDC, I
MAX
= 5A
E.P.O. input
Voltage with open contacts 12VDC, current with closed contacts 5mA.
The indications available with this interface are the following:
2. Technological description
PIN FUNCTION
1 -2 Running on battery
3 - 4 Autonomy Reserve
5 - 6 Generic alarm
7 - 8 Overload
PIN FUNCTION
1 -2 Running on Bypass
3 - 4 E.P.O.
5 - 6 -
Trimod®
Operating and Maintenance Manual
21
2.4.3 Logic level interface
Logic level interface is available on connector DB15 (F) and it allows the UPS to be connected to a remote system for monitoring its operating status, making available the following indications and controls:
• Mains/battery operated;
• Autonomy reserve
• UPS fault
• Overload
• UPS on bypass
• ON/OFF input
The functions of the interface pins are:
• Pin 1: GND;
• Pin 2: Mains/Battery (output, active high);
• Pin 3: Autonomy Reserve (output, active high);
• Pin 4: RS232 power supply;
• Pin 6: do not connect
• Pin 7: Overload (open collector, active low);
• Pin 12: UPS on Battery (open collector, active low);
• Pin 13: UPS on Bypass (open collector, active low);
• Pin 14: Autonomy Reserve (open collector, active low);
• Pin 15: Alarm (open collector, active low)..
Electrical specifications
Logic output: 12V
DC
max., output impedance 2.2kΩ in series. RS232 power supply: 12VDC 700mA max., not adjusted. Open collector outputs (all): 30VDC, 100mA max
2.4.4 Communication slot
In the rear part of UPS Trimod® an SNMP Slot is available for SNMP Adapter (Optional).
ATTENTION
The maximum current taken from pin4 of connector DB15 “RS232 power supply” and from the SNMP slot for the
network board to work must be, in total, less than 700mA.


22
2.4.5 Power module block diagram
2.4.6 Trimod® 30KVA TM Interconnection block diagram
All UPS Trimod® models have a similar block diagram.
2. Technological description
Trimod®
Operating and Maintenance Manual
23
3.1 General notes
WARNING
Before doing any operation on the equipment, it is necessary to read through the whole manual carefully, paying
attention to this chapter in particular.
The equipment has been built for the application specified in the declaration of conformity enclosed with this manual. For no reason whatsoever it is allowed to use it for purposes other than those for which it has been designed, nor in ways different to those explained in the manual. The various interventions must be carried out following the criteria and chronology described in this manual.
3.2 Symbols
In this manual some operations are highlighted by graphical symbols that call the attention of the reader to the dangerousness of the operations. The graphics are as follows:
WARNING
This means the possibility of an event happening that could lead to serious injury or great damage to the equipment
if adequate precautions are not taken.
ATTENTION
This means the possibility of an event happening that could lead to slight injury or material damage if adequate
precautions are not taken.
INDICATION
This means important information that must be read paying maximum attention.
3.3 Definitions of ‘Operator’ and ‘Specialized Technician’
The professional figure that is going to access the equipment for normal use is defined by the term “operator”. With this definition we mean personnel who know how to use and service the equipment and have the following requirements:
1. Specific training that authorises them to work according to the safety standards in relation to the dangers that the
presence of electricity can bring about.
2. Training on how to use the Individual Protective Devices and on the basic first aid interventions.
When the company person in charge of safety chooses the operator who is to use the equipment – who must be suitable for work in accordance with the existing laws – he must consider the physical aspect (no impairment), the psychological aspect (mental equilibrium, sense of responsibility) and personal education, training, experience and knowledge of the standards, prescriptions and provisions for the prevention of accidents.
Based on the skill and capacity found, he shall also see to the operator’s training in order to give him full knowledge of the equipment and of the parts it is made of.
To conclude, the operator must be made aware of the contents of this manual.
3.3.1 Qualification required to the operator
The operator must follow the instructions given to ensure maximum safety for himself and for the others. In particular he must comply with all the requirements contained in this manual throughout all the operating phases.
Typical activities envisaged:
- using the equipment when it is working normally and resetting subsequent to a stop;
- taking the necessary measures to maintain performance quality;
- cleaning the equipment
- collaborating with personnel who are to see to extraordinary maintenance work (“specialized technician”).
3. Safety Provisions
24
3.3.2 Qualification required to the specialized technician
The professional person who has to look after installation, starting and extraordinary maintenance is defined by the term “specialized technician”.
With such a definition we mean people with knowledge of the procedures for installing, assembling, repairing and servicing the equipment and who have specific technical qualification. Besides the requirements listed for a generic operator, the specialized technician must have had technical training or specific training for the procedures needed to use and service the equipment in complete safety.
Broadly speaking, the specialized technician will be a person selected among the professional people in the department and who has proven experience and capacities and specific technical expertise in relation to the type of work to be done.
WARNING
The person in charge of safety is responsible for the protection against and prevention of company risks in
accordance with the European Directive 89/391 EEC (safety at the work place), in ITALY it is part of the Law Decree dated 12/11/1994.
The person in charge of safety must ensure that all people working on the machine have received all the relevant
instructions of this manual, included start-up and commissioning, and with particular reference to the contents of this chapter.
3.4 Individual protective gear
WARNING
There is a high risk of electrical shock with the equipment as well as a considerable short circuit current. When
using and servicing the equipment it is absolutely forbidden to work without the protective gear mentioned in this paragraph.
The personnel who are going to work and/or transit near the equipment must not wear clothes with baggy sleeves or laces, belts, bracelets or other metal items that could be a hazard source.
3.4.1 Gear to wear
The following indications summarise the protective gear to wear.
Accident and spark proof footwear with rubber sole and reinforced toe Use: always
Waterproof rubber gloves Use: always
Protective gear Use: always
Protective glasses Use: always
3. Safety Provisions
Trimod®
Operating and Maintenance Manual
25
3.5 Indications of danger in the work place
The following signs must be placed in all points of access to the premises where the equipment is installed.
Electric current It indicates the presence of live parts.
Emergency interventions Do not use water to extinguish a fire but only the extinguishers designed specifically for putting fires out on electronic equipment.
No smoking This indication explains that it is forbidden to smoke in the area where the sign is affixed.
3.5.1 Indications on board the equipment
The explanatory plates on the equipment can vary according to the country of destination and to the relative applicable construction laws. Strictly comply with what is required. It is strictly forbidden to remove these plates or to work in a way different from what is indicated on them. All the data on the plates must always be readable and cleaned periodically. If a plate is ruined and/or is no longer legible, even only in part, ask for a new one from the Manufacturer who is bound to supply a substitute.
WARNING
The plates must be neither removed nor covered; it is forbidden to affix others on the equipment without the prior
written authorisation from the Manufacturer.
3.6 Residual risks
‘Residual’ risks are risks that were impossible to eliminate at the design phase and, as such, are potentially present on the equipment.
These risks are found with a specific analysis as prescribed by the standards of the sector. The documentation relative to the analysis is included in the Technical File of the machine filed by the Manufacturer.
In the case of the UPS Trimod® there are no residual risks provided that all the indications and provisions in this manual are scrupulously complied with.
WARNING
The risk can be drastically reduced by wearing the Individual Protective Gear listed in this chapter, considered
indispensable. Always work with due caution when near the dangerous areas indicated by the signs on board the equipment.
26
3.7 General warnings
ATTENTION
The equipment generates, uses and can radiate energy and radio frequencies. If not installed and used in agreement
with the indications given in this manual, it can interfere with radio communications.
- The equipment must be kept and used in accordance with the instructions given herein and as suggested from time to
time.
- The department manager must instruct the operating and maintenance personnel on how to use and service the
equipment in complete safety.
- Only specialized and specifically instructed personnel must be allowed to access the equipment for maintenance work.
All the time such maintenance work is being done, ‘Work underway’ signs must be affixed in the department that can be seen from all access points.
- Connection of the equipment (and of any accessory devices) must include standard earthing to discharge short circuit
current and electrostatic voltages. Mains voltage must correspond to the value on the ID plate. Use of current adapters is not allowed. When connecting pay attention to polarities.
- Any work on the equipment must be done only after it has been disconnected from the supply mains via the switch
which must be padlocked.
- When the equipment is received, or prior to switching on each time, DO NOT switch the UPS on if the batteries are
leaking.
- Tools used for maintenance (pliers, screwdrivers, etc.) must be the electrically insulated type.
- It is strictly forbidden to deposit combustible materials near the equipment. It must always be kept locked and access
allowed only to specifically trained personnel.
- Do not deactivate the safety devices or delude the indications, alarms and warnings, whether they are communicated
automatically or by means of plates on the installation.
- Do not turn the machine on without the fixed protections in place (panels, etc.).
- In the case of breakages, deformation or malfunctions of the equipment or parts of it, repair or replace immediately,
avoiding “emergency” repairs.
- It is not allowed, for any reason, to modify, manipulate or in any way alter the structure of the equipment, the devices
mounted on it, operating sequence, etc., without having first consulted the Manufacturer.
- If the fuses have to be changed, always and only use ones of the same type.
- Changing the batteries is a job for a specialized technician. Bear in mind that the electrolyte can cause irreparable
injury to skin, mucous membranes, and eyes and is toxic if inhaled or swallowed. Always work with the most suitable Individual Protective Gear. Do not forget that the batteries must be disposed of according to the laws existing in the country where the equipment is installed as they are toxic waste. Under no circumstances can a battery be burnt as it would cause an explosion!
- All maintenance work, routine and extraordinary, must be recorded in a register, noting the date, time, type of job,
name of the operator and all useful information. If necessary use the pages added at the end of the “Maintenance “chapter.
- Do not use oils or chemicals to clean with as they can corrode or damage parts of the equipment.
- Both the equipment and the work place must be kept perfectly clean.
- When maintenance is finished check carefully that no tools and/or materials have been left near the equipment before
turning the electricity back on.
3. Safety Provisions
Trimod®
Operating and Maintenance Manual
27
3.8 Emergency interventions
The following information is of a general nature. For specific interventions please consult the laws existing in the country where the equipment is installed.
3.8.1 First aid interventions
If any first aid intervention is required, comply with company rules and traditional procedures.
3.8.2 Fire-prevention measures
- Do not use water to extinguish fire but only the extinguishers designed specifically for putting fires out on electronic
equipment.
Loading...
+ 61 hidden pages